FA3016-16-R-0032 Atch 3
Appendix B – Trane VFD Specifications
Mechanical Specifications - Adaptive Frequency Drive
TRANE Remote Mounted (free standing) Air Cooled Adaptive Frequency Drive (AFD) The Trane AFD is a remote air-cooled, microprocessor based pulsed width modulation design. The AFD is both voltage and current regulated. Output power devices: IGBT transistors.
The AFD is remote (free standing) and ships completely assembled, wired and tested to the job site. Patented Trane AFD control logic is specifically designed to interface with the centrifugal water chiller controls. AFD control adapts to the operating ranges and specific characteristics of the chiller, and chiller efficiency is optimized by coordinating compressor motor speed and compressor inlet guide vane position. Chilled water control and AFD control work together to maintain the chilled water setpoint, improve efficiency and avoid surge. If a surge is detected, AFD surge avoidance logic will make adjustments to move away from and avoid surge at similar conditions in the future. Use only copper conductors for terminal connections. Failure to do so may cause corrosion or overheating, and starter damage.
Remote (Free Standing) AFD Design Features
* NEMA 1 ventilated enclosure with a hinged doors, is tested to a minimum short circuit rating (SCR) of 65,000 amps.
The AFD includes a padlockable door-mounted overcurrent device with a minimum AIC rating of 65,000 amps. The entire package is UL/CUL listed. Other AFD features include:
* Simple modular construction.
* Design access from the front
* The drive is rated for nominal chiller voltage +/-10%.
* Displacement power factor - minimum of .97 at all loads.
* Minimum efficiency of 97% at rated load and 60 hertz.
* Soft-start; linear acceleration; coast to stop.
* Adjustable frequency from 38 to 60 hertz.
* All control circuit voltages are physically and electrically isolated from power circuit voltage.
* 150% instantaneous torque available for improved surge control.
* Output line-to-line and line-to-ground short circuit protection.
* Harmonic currents are minimized through the use of a standard DC Link reactor. The reactor will limit the total demand distortion to approximately 35%
Chiller Unit Control Features for AFD The chiller unit control panel capabilities provide for the control/configuration interface to, and the retrieval/display of, AFD-related data. AFD standard design features controlled through Adapiview include:
* Current limited to 100%
* Motor overload protection.
* Motor overtemperature protection.
* Phase loss, reversal, imbalance protection.
* Overvoltage/undervoltage protection.
AdaptiView displays the input voltage, output or load current and the frequency command. On the AFD enclosure, there is a display that can be utilized by operators as needed and it includes a full comprehensive list of AFD parameters.
Designed for top entry line power and bottom exit load cables, the load cable connections are "bolted" type. The customer is responsible for the terminal lugs. The AFD should be located within 100 feet of the chiller (cable length not to exceed 100 feet) to insure proper operation. If the AFD is located further than 100 feet from the chiller, a field supplied filter should be installed between the chiller and AFD.
Environmental Ratings:
* 14F to 104 operating ambient temperature
* Altitude to 1000m, amperage derate of 4% per every 1000 meters above 1000 meters up to 3000 meters
* Humidity, 95% non-condensing
Unit Dimensions - Adaptive Frequency Drive
REMOTE MOUNTED ADAPTIVE FREQUENCY DRIVE W/ NEMA 12 ENCLOSURE, PAGE 1 OF 2
17 5/16"
12 7/16"
Adaptive Frequency Drive for Chillers
7 7/8"
7 7/8"
1 7/8"
2 13/16"
3 7/8"
9 1/8" 12 13/16" 2 13/16"
15 5/8"
17 5/16"
23 3/4"
8 1/2"
2 13/16"
18"
69 1/2"
47 3/8"
(126 1/4")
1 7/8"
35 5/16" (L2)
30 5/8"
(L1-L2-L3)
5 13/16"
102 1/2"
(126 1/4") 23 5/8" 23 5/8" 31 1/2"
16 5/16" 16 5/16" 16 5/16" 24 3/16"
23 3/4"
30 13/16" (L1)
39 7/8" (L3)
3 1/4"
3 3/4"
18 11/16"
3 5/8"
3 3/4"
71"
2 9/16"
3 5/8"3 5/8" 3 5/8" 3 5/8"
3 5/8"3 5/8"
26 13/16"
89 7/8"
(23 13/16")
89 3/16"
7 7/8"
18 3/4" 2 1/2"
2 1/2"
18 7/8"
(GND)
16 11/16"
(T1) 29 5/8"
(T2) 37 9/16"
(T3) 45 7/16"
23 3/4"
16 5/16"
18 1/8"
4 1/16"
14 13/16"
3 5/8"
2 7/16"
125 1/16"
Unit Dimensions - Adaptive Frequency Drive
NOTES:
1. FAILURE TO REMOUNT CABINET FLOOR GLAND PLATES
WILL HAVE A NEGATIVE INFLUENCE ON THE UNIT'S
INTERNAL COOLING CAPACITY AND CAN CAUSE TRIP FAULTS.
2. MAXIMUM CABLE LENGTHS BETWEEN DRIVE AND
MOTOR SHOULD BE 100 FEET OR LESS.
3. CUSTOMER PROVIDED LOAD LUGS TO BE CRIMP
ON CONNECTION FOR BOLT ON LUG.
4. CONNECTIONS ARE SPACED HORIZONTALLY WITH
DIMENSION/LOCATION SHOWN IN THE FRONT VIEW.
5. SEE PREVIOUS PAGE FOR STARTER ENCLOSURE DIMENSIONAL
INFORMATION.
6. BREAKER AIC (AMPS INTERRUPTING CAPACITY) = APPLIES
TO THE CIRCUIT BREAKER AS A COMPONENT ONLY AND IS
THE MAXIMUM CURRENT THAT A CIRCUIT BREAKER CAN
INTERRUPT WITHOUT DAMAGE TO ITSELF.
7. STARTER SCR (SHORT CIRCUIT RATING) = THE MAXIMUM
FAULT CURRENT TO WHICH A STARTER MAY BE EXPOSED
AND SAFELY BE CONTAINED WITHIN THE STARTER ENCLOSURE.
HOWEVER, THE COMPONENTS MAY SUSTAIN DAMAGE.
8. CONTACT TRANE CENTRAVAC MARKETING WITH ANY QUESTIONS.
9. THE VALUES LISTED ARE 460/480 AND 575/600 VOLT.
10. TERMINALS ACCEPT COPPER OR ALUMINUM WIRE.
3085.0 lb
REMOTE MOUNTED ADAPTIVE FREQUENCY DRIVE W/ NEMA 12 ENCLOSURE, PAGE 2 OF 2
CBIC = CIRCUIT BREAKER HIGH-INTERRUPT
(4) 300-500 MCM(8) 4/0-500 MCM100,000 A CBIC933 100,000 A
26 9/16"
13 1/16" MIN
A A
31 5/16"
23 7/16"
(126 1/4")
22 1/2" (L1-L2-L3)
2 15/16"
16 7/8"
VIEW A-A
10 1/8"
GROUND
BUSBAR
11 3/4"
14 11/16" (T3)
16 9/16" (T2)
18 7/16" (T1)
23 7/16" MAX
DOOR OPENING
94 MAX
DOOR SWING
MAX
RLA AIC AMPS
BREAKER
RATINGS (RMS SYSMETRICAL AMPS)
SHORT CIRCUIT WITHSTAND INCOMING LINE
PROVISIONS PROVISIONS
OUTPUT LOAD
CONNECTION
PANEL STARTER
WEIGHT
Weight, Clearance & Rigging Diagram - Adaptive Frequency Drive
3085.0 lbF3
Frame Weight
*IMAGE SHOWN ABOVE IS AN EXAMPLE. NOT SPECIFIC TO THE UNIT.
Field Wiring - Adaptive Frequency Drive
(SEEUNITNAMEPLATE)
LINEVOLTAGE
CUSTOMERSUPPLIED
L1GND L3L2
L1G L2 L3
2Q1MAINCIRCUITBREAKEROR
2S1FUSEDDISCONNECTSWITCH
ANDSTART-UPPROCEDURESHAVEBEENCOMPLETED.
DONOTROUTELOWVOLTAGE(30V)WITHCONTROLVOLTAGE(115V)ANDDONOTPOWERUNITUNTILCHECK-OUT
DASHEDLINESINDICATEFIELDWIRINGBYOTHERS.WIRENUMBERSSHOWNARERECOMMENDEDBYTRANE.
2.
1.
NOTES:
DEVICEPREFIXCODE
=MAINUNITCONTROLPANELDEVICE
=REMOTEMOUNTEDDEVICE
=UNITMOUNTEDDEVICE
=CUSTOMERPROVIDEDDEVICE5
96 97
T1
T1
T2
T6 T2
T3
T3T4 T5
4M1MOTOR
TERMINALCONNECTIONS
ANDTAGPROCEDURESBEFORESERVICING.
FAILURETODOSOMAYCAUSE
DAMAGETOTHEEQUIPMENT.
OTHERTYPESOFCONDUCTORS.
UNITTERMINALSARENOTDESIGNEDTOACCEPT
FAILURETODOTHEABOVEBEFORESERVICING
COULDRESULTINDEATHORSERIOUSINJURY.
INSTRUCTIONSFORCAPACITORDISCHARGE.
VARIABLESPEEDDRIVE,REFERTODRIVE
DISCHARGEDSTOREDVOLTAGE.UNITSWITH
INSURETHATALLMOTORCAPACITORSHAVE
USECOPPERCONDUCTORSONLY!
CAUTION
HAZARDOUSVOLTAGE!
REMOTEDISCONNECTSANDFOLLOWLOCKOUT
DISCONNECTALLELECTRICPOWERINCLUDING
WARNING
TRANESUPPLIEDREMOTE
MOUNTEDLOWVOLTAGE
ADAPTIVEFREQUENCY
DRIVEPANEL
1X1-1
WB4SHIELDINGTOBE
GROUNDEDATMAIN
CONTROLPANELONLY
1X1-G
1A1J5-4
1A1J5-3 2A1J3-3COM+
2A1J3-4COM-
SHIELD
WB4
BLK
WHT
1A7J2-2 10A 2X1-8
1A7J2-4
1X1-4
9A
4B
1X1-12
1X1-3 3B
2A
2X1-7
2X1-4
2X1-2
2X1-3
MAINUNITCONTROLPANEL
TERMINALCONNECTIONS
1A
1X1-G
GRN/YEL
DRIVE
2X1-1
PANELGND
4000VAAT115VAC,8AWGMAXWIRESIZE
SEENAMEPLATE;MINIMUMCIRCUITAMPACITY
FIELDWIRINGCIRCUITSELECTIONINFORMATION
CONTACTRATING;2.88AINDUCTIVE,1/3HP,0.25KWAT115VAC.14AWGMAXWIRESIZE.
PUMPMOTOR;1PH3/4HP,11.7FULLLOADAMPSAT115VAC.14AWGMAXWIRESIZE.
(BELDENTYPE8760RECOMMENDED)
CIRCUITPROTECTEDAT20A,115VAC1PH,10AWGMAXWIRESIZE
24VDC,12MARESISTIVELOAD,14AWGMAXWIRESIZE
TWISTED,SHIELDEDPAIR,30VDC,MAXLENGTH1500FT
1A*,2A*ANDGRN/YEL
5S3THRU5S8
9A*AND10A*
ALLREMAININGLLIDTERMINALS
5S1*,5S2*,3B*AND4B*
*TAPPEDCONTROLCONDUCTORS
WB4
SUPPLYANDMOTORLEADS
WIRENOORDEVICE
2A2ADAPTIVEFREQUENCYDRIVE
REMOTE AFD CONNECTION DIAGRAM
FA3016-16-R-0032 Atch 3