Questions and Answers Triangle Cooling Towers
1) Is there a breaker that feeds the disconnects at the existing cooling towers or are they fed from a motor control center?
A) Each cooling tower fan is supplied power via individual breaker/switch from the motor control center panels.
2) Is there one feeder circuit feeding each cooling tower fan or are there 2 separate circuits one feeding each fan?
A) Each tower has two fans with each fan having a separate power circuit from the mcc.
3) Are there separate basin heater circuit for each cooling tower?
A) There are no basin heaters or heater power circuits on the cooling towers