Building 104 As Builts REV_3 50.pdf
PDF 134 KB Posted
- Solicitation number
- FA282322R0014
About this file
This solicitation is for upgrade work to the emergency power system at Building 104 on Eglin Air Force Base in Florida. The project includes replacing electrical panels and transformers, installing a new automatic transfer switch and emergency generator, replacing the diesel fuel storage and piping, and upgrading distribution panels to consolidate all mission critical loads. The work must comply with DOD, Air Force, and base design standards. The acquisition is a small business set-aside with an anticipated value between $1 million and $5 million. The North American Industry Classification code is 236220 and the solicitation process will use best value with award based on best value to the government. The statement of work specifies the required upgrades and removals in detail.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ST
ST
ST
ST
ST
ST
ST
STST
VAV 1.1
120 V., 1 Ø
VAV 1.2
120 V., 1 Ø
VAV 1.3
120 V., 1 Ø
VAV 1.4
120 V., 1 Ø
VAV 1.9
120 V., 1 Ø
VAV 1.8
120 V., 1 Ø
VAV 1.5
120 V., 1 Ø
VAV 1.7
120 V., 1 Ø
VAV 1.6
120 V., 1 Ø
FD FD
SCALE: 1/8" = 1'-0"
FIRST FLOOR ELECTRICAL PLAN - NEW WORK
WORK NOTES:
SEE "PARTIAL ELECTRICAL PLAN - NEW WORK", THIS SHEET, FOR ADDITIONAL
ELECTRICAL REQUIREMENTS THIS AREA,
EXISTING PANEL "MDP" (WESTINGHOUSE CDP), 480/277 V., 3 Ø, 4 W., 800 A. MAIN
BREAKER. REUSE EXISTING 200/3 SPARE CIRCUIT BREAKER FOR FEEDER TO NEW
PANEL "AC-2". SEE "SINGLE LINE DIAGRAM", SHEET E-601.
EXISTING PANEL "TECH" (FPE CDP), 208/120 V., 3 Ø, 4 W., 400 A. MAIN BREAKER. ADD
TWO NEW 20/1 CIRCUIT BREAKERS IN EXISTING SPACE FOR NEW CIRCUITS TO VAV
BOXES.
TECH-7
TECH-7
SCALE: 1/8" = 1'-0"
PARTIAL ELECTRICAL PLAN - NEW WORK
FD FD
M
AC-2:8/10/12 (20/3)
3 # 12, 1 # 12
GND., 1/2" LFMC
HWP-1
3 HP, 480 V., 3Ø
COMBINATION STARTER /
DISCONNECT SWITCH - 30 A., 3
P. W/ NEMA SIZE 0 STARTER -
PROVIDE NAMEPLATE
ENGRAVED "SERVED FROM
PANEL 'AC-2' ON SECOND
FLOOR."
E-111
FIRST FLOOR ELECTRICAL PLAN - NEW WORK
FIVGAS, J.
WYNN, E.W.
5013AK FTFA 13-1087 13AK 55
AS NOTED
15 NOV. 2013
REPLACE HVAC
BUILDING 104
FTFA 13-1087
PETERSON ENGINEERING, INC.
75 SOUTH "F" STREET
PENSACOLA, FLORIDA 32502
(850) 434-0513
GRAPHIC SCALES
1/8" = 1'-0" 8' 0' 8' 24'16' 32'
1 7JUL14 ADD POWER TO HWP-1. REVISE WORK NOTE 2. EWW
2 FIRE DAMPERS ARE MANUAL CAJ
Revised Record
SPECIAL NOTE:
FIRE DAMPERS ARE SPRING LOADED WITH FUSIBLE LINK.
D P R O J E C T
B u i l d i n g
A s B u i l t s S u b m i t t a l s
A S
B U I L T
R E V I S E D E R d w g
P M
D W G
T o
P D F p c