Appendix_8.5_Eglin_FA_MNS.pdf
PDF 194 KB Posted
- Attached to
- CTG Modular Facilities Federal contract opportunity
- Solicitation number
- FA282318R4014
About this file
FA MNS
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Appendix_8.4_Eglin_Architectural_Compatibility_Plan_2012_1.pdf | ||
| FTFA13-1096_-_SOW_-_Addenda_1_10.4.18.pdf | ||
| Site_Visit_Questions_10.02.18_RJC.pdf | ||
| Appendix_8.7_Eglin_Design_Manual.pdf | ||
| Appendix_8.6_Eglin_Cable_Guide.pdf | ||
| Site_Visit_Sign-In_Sheet.pdf | ||
| Tab_04_FTFA131096_SOW_Appendix_3.pdf | ||
| Solicitation_Questions_-_Answered_RJC_9.25.18.docx | DOCX document | |
| FTFA_13-1096_SSP_1_Financial_Responsibility_Questionnaire.pdf | ||
| Wage_Determination.pdf | ||
| 50_Divisions_Cost_Estimate_w_Instructions.xls | XLS spreadsheet | |
| EAFB_Form_90_(2016).pdf | ||
| FTFA13-1096_-_SOW_-_8.17.18.pdf | ||
| FTFA_13-1096_Past_Performance_Information.pdf | ||
| Attach_D_-_Eglin_Specific_Contract_Language.pdf | ||
| FTFA_13-1096_Past_Performance_Questionnaire.pdf | ||
| FA282318R4014_CTG_Temp_Facility.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
March 2016
REQUIREMENTS FOR FIRE ALARM SYSTEMS AT EGLIN AFB:
FIRE ALARM TRANSCEIVERS
All Fire Alarm transceivers shall be standalone units and completely compatible with the existing Monaco Enterprises Model D-21-M central station system.
Transceivers shall have the appropriate number of zones to interface with the Fire Alarm Control
Panel and other required equipment. The authority having jurisdiction shall approve the fire alarm zones. Transceivers shall operate on a frequency of 141.3625 MHZ. Transceivers shall not be mounted higher than 60 inches from floor level.
**Notes:
Monaco Audio Board and Relay Board are not required and shall not be installed.
External activation of in-building MNS will be the function of 96 CS.
Lightning arrestors shall be mounted IAW installation manuals from the manufacturer and in a location easily accessible for maintenance with reasonable effort and without removal of additional facility finishes (sheet rock, ceiling grid, etc).
The installer is responsible to determine the proper location and type of antenna to be utilized.
When it is determined that the use of a directional (YAGI) antenna is required, the following shall apply. YAGI antennas installed on buildings shall be mounted on 1 inch heavy wall galvanized rigid conduit, utilizing positive means to prevent the antenna and/or mast from twisting by wind.
In cases where it is determined that an “Omni” antenna will be sufficient, the antenna may be mounted on ¾ inch rigid electrical conduit or a mast of proved equal strength.
Coaxial cable shall be enclosed in metal conduit from the transceiver to the antenna. In cases where overhead outdoor routing is deemed necessary the cable shall be installed in accordance with all codes and directives. Coaxial cables running overhead shall be approved for the purpose and installed accordingly. Coaxial length will be used to determine if low loss coaxial cable is necessary. Measures shall be taken to avoid sharp bends or “kinking” of coaxial cables.
The installer shall demonstrate the forward and the reflected power of installed antenna systems prior to acceptance in accordance with manufacturer’s specifications
AC power sources for the transceiver shall be protected by surge/lightning suppressors.
Suppressors shall not be installed within the enclosure of the transceiver.
FIRE ALARM SYSTEMS
Control panels must be located in office/administrative space or other rooms with similar temperature/humidity controls — control panels shall not be located in the aircraft servicing areas or mechanical/utility spaces without both temperature and humidity controls. Simple heating (i.e., for freeze protection) and/or ventilation is not sufficient for these electronic systems.
The following is an excerpt from one manufacturer's literature for their most current control system and clearly demonstrates this sensitivity. While the literature indicates compliance with
NFPA 72 requirements, it clearly recommends much narrower environmental limits for locating the control panel.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0-49°C/32–120°F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that–this system and its peripherals be installed in an environment with a normal room temperature of
15-27°C/60–80°F.
The following laptop requirements shall apply for intelligent fire alarm systems when determined by the Government and negotiated on an individual task order the contractor shall provide: one laptop to be turned over to fire alarm shop with the latest version of operating system required for the programming software, the software required to program the FACP, and any associated program as required by the programming software. All original manufacturers’ software for each laptop when addressable fire alarm systems are installed shall be provided to the Eglin AFB alarm shop. The following requirements shall apply: all software, hardware, passwords, cables, adapters, etc required for the maintenance, testing, and reprogramming of the fire alarm system shall be unconditionally turned over to the Gov't, and the above noted software, hardware, passwords, etc will become the unconditional property of the government. Software turned over to Gov't shall be the original manufacturer's licensed software on cd (or DVD) with jeweled case;
copies of software shall not be acceptable. Software and cd, or DVD, shall be brand new and unused.
When determined by the Government and negotiated on an individual task order the contractor shall provide the manufacturer’s recommended/required level of training on all the installed equipment and software, regarding installation, operation, maintenance, testing, future expansion, and programming of the fire alarm system for two (2) personnel. This training shall meet or exceed NFPA 72 National F/A and Signaling Code 10.4.2.2 for System Installers,
10.4.3.1 (1) for Inspection, Testing and Maintenance Personnel as well as the manufacturer’s required level of training and shall guarantee the unconditional operation and future purchase of additional and/or replacement equipment. The training shall take place at one of the locations normally used by the manufacturer and/or distributor to conduct factory training for their in-house employees. The government employees shall be trained alongside technicians employed by the installed equipment manufacture and/or distributer. Upon successful completion of all curriculum requirements the government personnel shall be awarded a certification and provided full access to all available technical support resources, to include at a minimum, on-line and telephone support provided to manufacture and/or distributer personnel.
Provide as-built drawings of the fire alarm system, as follows: floor plan/s showing all fire alarm system components and their addresses. Fire alarm riser diagram shall show all fire alarm components. Two copies of the programming and of any drawings will be provided to the Eglin
Alarm Maintenance section on CD or DVD. Drawings need to accessible and viewable with the laptop. All requirements shall be accomplished prior to final acceptance.
PROVIDE AS-BUILT DRAWINGS OF FIRE ALARM SYSTEM, AS FOLLOWS
1. FLOOR PLAN/S SHOWING ALL FIRE ALARM SYSTEM COMPONENTS and their addresses
2. FIRE ALARM RISER DIAGRAM SHOWING ALL FIRE ALARM COMPONENTS
3. FIRE ALARM LEGEND
4. FIRE ALARM NOTES
5. ABOVE NOTED ITEMS "1" THRU "4", SHALL BE PROVIDED ELECTRONICALLY
ON A CD.
SECTION 1.0
1.1 DESCRIPTION:
A. The fire alarm system shall comply with requirements of NFPA Standard No. 72 for
Auxiliary Protected Premises Signaling Systems except as modified and supplemented by this specification. The system field wiring shall be supervised either electrically or by software-directed polling of field devices.
B. The fire alarm system shall comply with requirements of NFPA Standard No. 72 for
Remote Station Protected Premises Signaling Systems except as modified and supplemented by this specification. The system field wiring shall be supervised either electrically or by software-directed polling of field devices.
C. The fire alarm system shall be manufactured by an ISO 9001 certified company and meet the requirements of BS EN9001: ANSI/ASQC Q9001-1994.
D. The installing company shall employ NICET (minimum Level III Fire Alarm
Technology) technicians on site to guide the final check-out and to ensure the systems integrity.
1.2 SCOPE:
Basic Performance:
1. Alarm, trouble and supervisory signals from all intelligent reporting devices shall be encoded on NFPA Style 6 (Class A) or NFPA Style 7 (Class A) Signaling Line Circuits
(SLC).
2. Initiation Device Circuits (IDC) shall be wired Class A (NFPA Style D) as part of an addressable device connected by the SLC Circuit.
3. Notification Appliance Circuits (NAC) shall be wired Class A (NFPA Style Z) as part of an addressable device connected by the SLC Circuit.
4. All circuits shall be power-limited, UL864 9th edition requirements.
5. A single ground fault or open circuit on the system Signaling Line Circuit shall not cause system malfunction, loss of operating power or the ability to report an alarm when wired NFPA Style 6/7.
6. All AC power to the fire systems shall be protected by the use of surge/lightning protectors. All circuits of the fire systems that enter or exit the protected facility shall have surge/lightning protectors installed.
1.3 SUBMITTALS
A. General:
1. Two copies of all submittals shall be submitted to the CE SABER PM/CE Engineer for review.
2. All references to manufacturer's model numbers and other pertinent information herein is intended to establish minimum standards of performance, function and quality.
Equivalent compatible UL-listed equipment from other manufacturers may be substituted for the specified equipment as long as the minimum standards are met.
3. For equipment other than that specified, the contractor shall supply proof that such substitute equipment equals or exceeds the features, functions, performance, and quality of the specified equipment.
B. Shop Drawings:
1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications.
2. Include manufacturer's name(s), model numbers, ratings, power requirements, equipment layout, device arrangement, complete wiring point-to-point diagrams, and conduit layouts.
3. Show annunciator layout, configurations, and terminations.
C. Manuals:
1. Submit simultaneously with the shop drawings, complete operating and maintenance manuals listing the manufacturer's name(s), including technical data sheets.
2. Wiring diagrams shall indicate internal wiring for each device and the interconnections between the items of equipment.
3. Provide a clear and concise description of operation that gives, in detail, the information required to properly operate the equipment and system.
4. Provide three complete, including programmers, manuals to Civil Engineering Alarm maintenance at acceptance.
D. Software Modifications:
Provide all hardware, software, programming tools and documentation necessary to modify the fire alarm system on site. Modification includes addition and deletion of devices, circuits, zones and changes to system operation and custom label changes for devices or zones. The system structure and software shall place no limit on the type or extent of software modifications on-site. Modification of software shall not require power-down of the system or loss of system fire protection while modifications are being made.
1.4 GUARANTY:
All work performed and all material and equipment furnished under this contract shall be free from defects and shall remain so for a period of at least one (1) year from the date of acceptance. The full cost of maintenance, labor and materials required to correct any defect during this one year period shall be included in the submittal bid.
1.5 APPLICABLE STANDARDS AND SPECIFICATIONS:
The specifications and standards listed below form a part of this specification. The system shall fully comply with the latest issue of these standards, if applicable.
A. National Fire Protection Association (NFPA) - USA:
No. 13 Sprinkler Systems
No. 70 National Electric Code (NEC)
No. 72 National Fire Alarm Code
No. 101 Life Safety Code
B. Applicable Unified Facilities Criteria (UFC)
C. The system and its components shall be Underwriters Laboratories, Inc. listed under the appropriate UL testing standard as listed herein for fire alarm applications and the installation shall be in compliance with the UL listing.
D. Local and State Building Codes
E. All requirements of the Authority Having Jurisdiction (AHJ)
1.8 APPROVALS:
A. The system shall have proper listing and/or approval from the following nationally recognized agencies:
UL Underwriters Laboratories Inc
ULC Underwriters Laboratories Canada
FM Factory Mutual
MEA Material Equipment Acceptance (NYC)
CSFM California State Fire Marshal
SECTION 2.0 - PRODUCTS
2.1 EQUIPMENT AND MATERIAL, GENERAL:
A. All equipment and components shall be new, and the manufacturer's current model and version. The materials, appliances, equipment and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a fire protective signaling system, meeting the National Fire Alarm Code.
B. All equipment and components shall be installed in strict compliance with manufacturers' recommendations. Consult the manufacturer's installation manuals for all wiring diagrams, schematics, physical equipment sizes, etc., before beginning system installation.
C. All equipment shall be attached to walls and ceiling/floor assemblies and shall be held firmly in place (e.g., detectors shall not be supported solely by suspended ceilings).
Fasteners and supports shall be adequate to support the required load.
2.2 CONDUIT AND WIRE:
A. Conduit:
1. Conduit shall be in accordance with The National Electrical Code (NEC), local and state requirements.
2. All wiring shall be installed in conduit or raceway. Conduit fill shall not exceed 40 percent of interior cross sectional area where three or more cables are contained within a single conduit.
3. Wiring installation — practices in ANSI/NECA 305-2001 shall be followed. Cable must be separated from any open conductors of power, or Class 1 circuits, and shall not be placed in any conduit, junction box or raceway containing these conductors, per NEC
Article 760-55. Power wiring and limited power wiring shall not be co-located in the same conduit, raceway, or enclosure. Such wiring may only be located together within the listed control panel and shall be installed in accordance with the manufacturer's guidance. There should be no stray detectable voltages, no ground faults, open circuits, or short circuits when tested IAW NEC 305.
4. Wiring for 24-volt DC control, alarm notification, emergency communication and similar power-limited auxiliary functions may be run in the same conduit as initiating and signaling line circuits. All circuits shall be provided with transient suppression devices and the system shall be designed to permit simultaneous operation of all circuits without interference or loss of signals.
5. Conduit shall not enter the fire alarm control panel or any other remotely mounted control panel equipment or back boxes, except where conduit entry is specified by the
FACP manufacturer.
6. Conduit shall be 3/4-inch (19.1 mm) minimum, red in color.
B. Wire:
1. All fire alarm system wiring shall be new.
2. Wiring shall be in accordance with local, state and national codes (e.g., NEC Article
760) and as recommended by the manufacturer of the fire alarm system. Number and size of conductors shall be as recommended by the fire alarm system manufacturer.
3. All wire and cable shall be listed and/or approved by a recognized testing agency for use with a protective signaling system.
4. Wire and cable not installed in conduit shall have a fire resistance rating suitable for the installation as indicated in NEC 760 (e.g., FPLR).
5. All field wiring shall be electrically supervised for open circuit and ground fault.
C. Terminal Boxes, Junction Boxes and Cabinets: All boxes and cabinets shall be UL listed for their use and purpose.
D. The fire alarm control panel shall be connected to a separate dedicated branch circuit, maximum 20 amperes. This circuit shall be labeled at the main power distribution panel as
FIRE ALARM. Fire alarm control panel primary power wiring shall be 12 AWG. The control panel cabinet shall be grounded securely to facility ground. The control panel enclosure shall feature a quick removal chassis to facilitate rapid replacement of the FACP electronics.
1. The FACP shall be capable of coding Notification Appliance Circuits in March Time
Code (120 PPM), Temporal (NFPA 72 A-2-2.2.2), and California Code. Main panel notification circuits (NACs 1 & 2) shall also automatically synchronize any of the following manufacturer's notification appliances connected to them: System Sensor, Wheelock, or Gentex with no need for additional synchronization modules.
2.3 SYSTEM COMPONENTS:
A. Programmable Electronic Sounders:
1. Electronic sounders shall operate on 24 VDC nominal.
2. Electronic sounders shall be field programmable without the use of special tools, at a sound level of at least 90 dBA measured at 10 feet from the device.
3. Shall be flush or surface mounted as shown on plans.
B. Speakers:
1. All speakers shall operate on 25 or 70 VRMS or with field selectable output taps from 0.5 to 2.0 Watts.
2. Speakers in corridors and public spaces shall produce a nominal sound output of 84 dBA at 10 feet (3m).
3. Frequency response shall be a minimum of 400 HZ to 4000 HZ.
4. The back of each speaker shall be sealed to protect the speaker cone from damage and dust.
C. Strobe lights shall meet the requirements of the ADA, UL Standard 1971, be fully synchronized, and shall meet the following criteria:
1. The maximum pulse duration shall be 2/10 of one second.
2. Strobe intensity shall meet the requirements of UL 1971.
3. The flash rate shall meet the requirements of UL 1971.
D. Manual Fire Alarm Stations
1. Manual fire alarm stations shall be non-breakglass type, equipped with key lock so that they may be tested without operating the handle.
2. Stations must be designed such that after an actual activation, they cannot be restored to normal except by key reset.
3. An operated station shall automatically condition itself so as to be visually detected.
4. Manual stations shall be constructed of high impact Lexan, with operating instructions provided on the cover. The word FIRE shall appear on the manual station in letters one half inch (12.7 mm) in size or larger.
E. Duct Smoke Detectors: Duct smoke detectors shall be installed upon the composite supply/return air ducts(s), with properly sized air sampling tubes. Duct detectors shall be resettable at the FACP.
F. Automatic Conventional Heat Detectors
1. Automatic heat detectors shall be fixed temperature rated at 135 degrees Fahrenheit
(57.2 Celsius) for areas where ambient temperatures do not exceed 100 degrees (37.7
Celsius), and 200 degrees (93.33 Celsius) for areas where the temperature does not exceed 150 degrees (65.5 Celsius).
2. Automatic heat detectors shall be a low profile, ceiling mount type with positive indication of activation.
3. Heat detectors shall be addressable.
G. Alphanumeric LCD Type Annunciator:
1. The alphanumeric display annunciator shall be a supervised, remotely located back-lit LCD display containing a minimum of eighty (80) characters for alarm annunciation in clear English text.
2. The LCD annunciator shall display all alarm and trouble conditions in the system.
3. An audible indication of alarm shall be integral to the alphanumeric display.
4. The display shall be UL listed for fire alarm application.
5. It shall be possible to connect up to 32 LCD displays and be capable of wiring distances up to 6,000 feet from the control panel.
6. The annunciator shall connect to a separate, dedicated "terminal mode" EIA-485 interface. This is a two-wire loop connection and shall be capable of distances to 6,000 feet. Each terminal mode LCD display shall mimic the main control panel.
7. The system shall allow a minimum of 32 terminal mode LCD annunciators. Up to 10
LCD annunciators shall be capable of the following system functions: Acknowledge, Signal Silence and Reset, which shall be protected from unauthorized use by a key switch or password.
8. The LED annunciator shall offer an interface to a graphic style annunciator and provide each of the features listed above.
H. All interfaces and associated equipment are to be protected so that they will not be affected by voltage surges or line transients consistent with UL standard 864.
I. Addressable Manual Fire Alarm Box (manual station) and/or Manual Discharge Stations.
1. Addressable manual fire alarm boxes shall, on command from the control panel, send data to the panel representing the state of the manual switch and the addressable communication module status. They shall use a key operated test-reset lock, and shall be designed so that after actual emergency operation, they cannot be restored to normal use except by the use of a key.
2. All operated stations shall have a positive, visual indication of operation and utilize a key type reset.
3. Manual fire alarm boxes shall be constructed of Lexan with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches (44 mm) or larger.
4. Manual discharge stations shall not be located within 5 feet of a manual fire alarm pull station. When a manual foam discharge station and a manual fire alarm station are both located at a doorway the stations shall be located on opposite sides of the doorway.
Manual discharge stations shall be housed under a clear plastic tamper cover. Manual discharge stations shall comply with the signage and color coding in ETL 02-15.
J. Intelligent Photoelectric Smoke Detector
The detectors shall use the photoelectric (light-scattering) principal to measure smoke density and shall, on command from the control panel, send data to the panel representing the analog level of smoke density.
K. Intelligent Laser Photo Smoke Detector
1. The intelligent laser photo smoke detector shall be a spot type detector that incorporates an extremely bright laser diode and an integral lens that focuses the light beam to a very small volume near a receiving photo sensor. The scattering of smoke particles shall activate the photo sensor.
2. The laser detector shall have conductive plastic so that dust accumulation is reduced significantly.
3. The intelligent laser photo detector shall have nine sensitivity levels and be sensitive to a minimum obscuration of 0.03 percent per foot.
4. The laser detector shall not require expensive conduit, special fittings or PVC pipe.
5. The intelligent laser photo detector shall support standard, relay, isolator and sounder detector bases.
6. The laser photo detector shall not require other cleaning requirements than those listed in NFPA 72. Replacement, refurbishment or specialized cleaning of the detector head shall not be required.
7. The laser photo detector shall include two bicolor LEDs that flash green in normal operation and turn on steady red in alarm.
L. Intelligent Multi Criteria Acclimating Detector
1. The intelligent multi criteria Acclimate detector shall be an addressable device that is designed to monitor a minimum of photoelectric and thermal technologies in a single sensing device. The design shall include the ability to adapt to its environment by utilizing a built-in microprocessor to determine its environment and choose the appropriate sensing settings. The detector design shall allow a wide sensitivity window, no less than 1 to 4% per foot obscuration. This detector shall utilize advanced electronics that react to slow smoldering fires and thermal properties all within a single sensing device.
2. The microprocessor design shall be capable of selecting the appropriate sensitivity levels based on the environment type it is in (office, manufacturing, kitchen etc.) and then have the ability to automatically change the setting as the environment changes (as walls are moved or as the occupancy changes).
3. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena.
M. Intelligent Thermal Detectors
Thermal detectors shall be intelligent addressable fixed temperature devices with a temperature rated according to the area(s) installed.
N. Intelligent Duct Smoke Detector
1. The smoke detector housing shall accommodate either an intelligent ionization detector or an intelligent photoelectric detector, of that provides continuous analog monitoring and alarm verification from the panel. Duct Smoke Detectors shall be resettable from the FACP.
2. When sufficient smoke is sensed, an alarm signal is initiated at the FACP, and appropriate action taken to change over air handling systems to help prevent the rapid distribution of toxic smoke and fire gases throughout the areas served by the duct system.
O. Addressable Dry Contact Monitor Module
1. Addressable monitor modules shall be provided to connect one supervised IDC zone of conventional alarm initiating devices (any N.O. dry contact device) to one of the fire alarm control panel SLCs.
2. The IDC zone shall be suitable for Style D or Style B operation. An LED shall be provided that shall flash under normal conditions, indicating that the monitor module is operational and in regular communication with the control panel.
3. For difficult to reach areas, the monitor module shall be available in a miniature package and shall be no larger than 2-3/4 inch (70 mm) x 1-1/4 inch (31.7 mm) x 1/2 inch (12.7 mm). This version need not include Style D or an LED.
4. Modules shall be capable of addresses 1 thru 159
P. Two Wire Detector Monitor Module
1. Addressable monitor modules shall be provided to connect one supervised IDC zone of conventional 2-wire smoke detectors or alarm initiating devices (any N.O. dry contact device).
2. The IDC zone may be wired for Class A or B (Style D or Style B) operation. An LED shall be provided that shall flash under normal conditions, indicating that the monitor module is operational and in regular communication with the control panel.
3. Modules shall be capable of addresses 1 thru 159
Q. Addressable Control Module
1. Addressable control modules shall be provided to supervise and control the operation of one conventional NACs of compatible, 24 VDC powered polarized audio/visual notification appliances.
2. The control module NAC may be wired for Style Z or Style Y (Class A/B) with up to
1 amp of inductive A/V signal, or 2 amps of resistive A/V signal operation.
3. Audio/visual power shall be provided by a separate supervised power circuit from the main fire alarm control panel or from a supervised UL listed remote power supply.
4. The control module shall be suitable for pilot duty applications and rated for a minimum of 0.6 amps at 30 VDC.
5. Modules shall be capable of addresses 1 thru 159
R. Addressable Relay Module
Addressable Relay Modules shall be available for HVAC control and other building functions. The relay shall be form C and rated for a minimum of 2.0 Amps resistive or
1.0 Amps inductive. The relay coil shall be magnetically latched to reduce wiring connection requirements, and to insure that 100% of all auxiliary relay or NACs may be energized at the same time on the same pair of wires.
S. Isolator Module
1. Isolator modules shall be provided to automatically isolate wire-to-wire short circuits on an SLC Class A or Class B branch. The isolator module shall limit the number of modules or detectors that may be rendered inoperative by a short circuit fault on the
SLC loop segment or branch. At least one isolator module shall be provided for each floor or protected zone of the building.
2. If a wire-to-wire short occurs, the isolator module shall automatically open-circuit
(disconnect) the SLC. When the short circuit condition is corrected, the isolator module shall automatically reconnect the isolated section.
3. The isolator module shall not require address-setting, and its operations shall be totally automatic. It shall not be necessary to replace or reset an isolator module after its normal operation.
4. The isolator module shall provide a single LED that shall flash to indicate that the isolator is operational and shall illuminate steadily to indicate that a short circuit condition has been detected and isolated.
2.4 BATTERIES:
A. The battery shall have sufficient capacity to power the fire alarm system for not less than forty eight hours plus 15 minutes of alarm upon a normal AC power failure.
B. The batteries are to be completely maintenance free. Fluid level checks for refilling, spills, and leakage shall not be required.
C. If necessary to meet standby requirements, external battery and charger systems may be used.
SECTION 3.0 - EXECUTION
3.1 INSTALLATIONS:
A. Installation shall be in accordance with the NEC, NFPA 72, local and state codes, as shown on the drawings, and as recommended by the major equipment manufacturer.
B. All Fire Alarm Control Panels and BT-X FM transceivers shall be mounted in conditioned air space.
C. All fire detection and alarm system devices, control panels and remote annunciators shall be flush mounted when located in finished areas and may be surface mounted when located in unfinished areas.
D. Manual fire alarm boxes shall be suitable for surface mounting or semi-flush mounting as shown on the plans, and shall be installed not less than 42 inches (1067 mm), nor more than 48 inches (122 mm) above the finished floor.
3.2 TESTING:
The service of a competent, factory-trained engineer or technician authorized by the manufacturer of the fire alarm equipment shall be provided to technically supervise and participate during all of the adjustments and tests for the system. All testing shall be in accordance with NFPA 72.
A. Each of the alarm conditions that the system is required to detect should be introduced on the system. Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points.
B. When the system is equipped with optional features, the manufacturer's manual shall be consulted to determine the proper testing procedures. This is intended to address such items as verifying controls performed by individually addressed or grouped devices, sensitivity monitoring, verification functionality and similar.
3.3 FINAL INSPECTIONS:
At the final inspection, a factory-trained representative of the manufacturer of the major equipment shall demonstrate that the system functions properly in every respect.
3.4 INSTRUCTIONS:
A. Instruction shall be provided as required for operating the system. Hands-on demonstrations of the operation of all system components and the entire system including program changes and functions shall be provided.
B. The contractor and/or the systems manufacturer's representatives shall provide a typewritten "Sequence of Operation.
File details come from the government source that posted it.