Attch_1_-_SXHT_16-1047_Drawings.pdf
PDF 3 MB Posted
- Solicitation number
- FA252117B0009
About this file
Attachment 1_Drawings
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FA252117B00090001_Update_DBA_and_SV.pdf | ||
| Attach_3_4Aug2017_Wage_Determination.pdf | ||
| Attach_9_Site_Visit_Notes_SXHT_16-1047_Construct_Install_Utilities_Bldg_992.pdf | ||
| Attch_6-__Q&A_Template.docx | DOCX document | |
| FA252117B0009_IFB.pdf | ||
| Attch_8-__Site_Visit_EAL.docx | DOCX document | |
| Attch_4_-_GPP_and_RPR_Certification_Form.pdf | ||
| Attch_7_-_Site_Visit_ROE.doc | DOC document | |
| Attch_2-_SXHT_16-1047_Specifications.pdf | ||
| Attch_3_-_DBWD_FL170001_14_Jul_2017.pdf | ||
| Attch_5_-_Haz_Waste_Form.doc | DOC document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCALE:
STATE OF FLORIDA
NONE
AIR FORCE BASE
MIAMI
TAMPA
ORLANDO
PATRICK
TALLAHASSEE
JACKSONVILLE
T
A
X
I
W
A
Y
B
X
T
A
X
I
W
M
T
A
X
I
W
J
A
X I W
A
X
I W
R
U
N
U
P
D
T
A
X
I
W
D
H
E
A
D
I
N
G
T
A
X
I
W
T
A
X
I
W
Z
A
X
I
W
G
A
X
I
W
L
U
N
W
T A
X I W
I
N
S
T
R
U
M
E
N
N
W
T
R
I
M
U
T
R
I
M
U
T
A
X
I
W
X
F
E
V
T
A
X
I
W
A
X
I W
A
X
I W
C
A
X
I W
R
M
D
E
A
C
C
E
S
O
A
D
A
C
C
E
A
D
PINEDA EXPRESSWAY
SOUTH GATE (PERSONNEL ONLY)
B
A
N
A
V
E
R
B A
N
A N
A
R
I V
E R
A
T
L A
N
T
E
A
N
TRUCK
DELIVERY ONLY
BUILDING 423-CONTRACTING OFFICER
BUILDING 535-45TH CES
MAIN GATE (PERSONNEL ONLY)
S.R. A1A
B
A
N
A
V
E
R
A
T
L A
N
T
E
A
N
GOLF COURSE
PATRICK AIR FORCE BASE
SXHT 16-1047
FLORIDA
SCALE:
LOCATION MAP
NONE
TRUE
NORTH
CONST/INSTALL UTILITY CONNECTIONS
FOR SHOP EQUIP. B992 - DESIGN
PROJECT AREA
G-001
J
M
A Y
H E
W
L
C
O L
E M
A N
L O
C A
T I O
N
M
A P
P
R O
J E
E
A
A
N D
D R
A W
I N
G
I N
D E
X
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
Q U
I P
B
D
E S
I G
N
S X
P A
F B
F
L
N
DRAWING INDEX
Sheet Number Sheet Title
GENERAL
G-001
LOCATION MAP, PROJECT AREA AND DRAWING INDEX
CIVIL
C-101
UTILITY SITE PLAN, TRENCH PLACEMENT AND CONNECTION DETAILS
ELECTRICAL
E-001
ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS
E-002 CONSTRUCTION REQUIREMENTS AND EROSION CONTROLS
E-003 CONSTRUCTION DETAILS
ES-101 ELECTRICAL SITE PLAN
ED-101 POWER AND COMMUNICATIONS PLAN - EXISTING AND DEMO
ED-102 LIGHTING PLAN - EXISTING AND DEMOLITION
E-101 POWER AND COMMUNICATIONS PLAN - EXISTING AND NEW
E-102 LIGHTING PLAN - EXISTING AND NEW
E-501 ELECTRICAL SWITCH AND GROUNDING DETAILS
E-601 SINGLE LINE DIAGRAM - EXISTING AND DEMOLITION
E-602 SINGLE LINE DIAGRAM - EXISTING AND NEW
E-701 ELECTRICAL SCHEDULES
E-702 ELECTRICAL SCHEDULES
E-703 ELECTRICAL SCHEDULES
PROJECT LOCATION
CE OPERATIONS:
COMMUNICATIONS:
PROJECT MANAGER:
CHIEF, ENGINEERING FLIGHT:
USER:
SAFETY:
SECURITY FORCES:
ATO:
OTHER:
ENVIRONMENTAL:
FIRE:
A
P
P
R
O
V
E
D
PERMIT(S)/ENVIRONMENTAL ACTIONS
REQUIRED PRIOR TO CONSTRUCTION
ERP/STORMWATER
ERP/WETLANDS/DREDGE & FILL
FDEP/DRINKING WATER
FDEP/DOM. WASTE WATER ARCHEO./HISTORICAL
SURVEY/WILDLIFE
OTHER
NONE
FDEP/IND. WASTE WATER
IRP
FDEP/FUEL TANK
NOI/SWPPP
ASBESTOS
NOTE: IF IT IS SUSPECTED THAT ANY HAZARDOUS MATERIAL NOT
IDENTIFIED ON THESE DRAWINGS IS REQUIRED TO BE DISTURBED IN
ORDER TO PERFORM THE CONTRACT WORK, LEAVE MATERIAL
UNDISTURBED AND IMMEDIATELY INFORM THE CONTRACTING OFFICER.
HEAVY METALS
YES NO
LEAD
PCB
NOT
VERIFIED
HAZARDOUS MATERIALS
U S
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D n g i n e e r i n g I n c
L L
E N
E A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
An O ne id a N at io n Co m pa ny
A
M b a r v i r x
S D x
C x
C x
C x
C x
C x
S
S
S
S
W x
W x
W x
W x
W x
E
E
E
E
S
S
S
S
S
S
S
S
S
S
S
S
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
2'' W 2'' W
2'' W 2'' W
NORTH
SCALE:
UTILITY SITE PLAN
1" = 20'
N
SCALE:
TRENCH CONNECTION DETAIL
NONE
B
C-101
SCALE:
TRENCH PLACEMENT DETAIL
1" = 3'
C-101
FLAG NOTES:
1. PROVIDE UNDERGROUND ELECTRICAL WIRING IN NEW CONDUIT FROM NEW TRANSFORMER TO NEW PANEL P1 IN FACILITY 992. EXISTING CONDUIT
TO BE ABANDONED IN PLACE. SEE ELECTRICAL SHEETS.
2. PROVIDE 2" PVC WATER LINE CONNECTION FROM EXISTING 2" WATER SUPPLY LINE TO NEW HOSE BIB. ATTACH WATER LINE TO EXISTING INTERIOR
WALL BRACING WITH UNISTRUT AND CLIPS.
3. PROVIDE PREFABRICATED SLOPED 4" FLOOR DRAINAGE TRENCH SYSTEM. JRS 9930 ENVIRO-FLO II OR APPROVED EQUAL. INSTALL 4" PVC PIPE
CONNECTION FOR TRENCH DRAIN SYSTEM TO EXISTING FACILITY 992 SANITARY SEWER SERVICE LINE. SAW CUT AND REMOVE EXISTING
CONCRETE FLOOR SLAB AND INSTALL NEW TRENCH DRAIN SYSTEM PER MANUFACTURER'S INSTALLATION REQUIREMENTS AND SPECIFICATIONS.
4. PROVIDE EROSION AND SEDIMENT CONTROLS PER DRAWINGS E-002 AND E-003.
GENERAL NOTES:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REQUEST THAT ALL UTILITIES BE FIELD LOCATED BEFORE BEGINNING CONSTRUCTION.
LOCATIONS OF ALL EXISTING UTILITIES SHOWN ON THE DRAWINGS ARE FOR INFORMATIONAL PURPOSES ONLY.
2. THE GOVERNMENT IS NOT RESPONSIBLE FOR DAMAGES TO EXISTING UTILITIES CAUSED BY THE CONTRACTOR'S NEGLIGENCE. EXTREME CAUTION
SHALL BE USED TO MAINTAIN INTEGRITY OF EXISTING UTILITIES.
3. THE CONTRACTOR SHALL USE CAUTION WHEN WORKING AROUND EXISTING UTILITIES AND PROTECT THEM IN PLACE.
4. CONTRACTOR SHALL MEET THE PROJECT SPECIFICATIONS AND VERIFY QUANTITIES PRIOR TO CONSTRUCTION.
5. THE TERM "PROVIDE" USED IN THE PROJECT DRAWINGS SHALL MEAN TO PROVIDE MATERIALS, EQUIPMENT, AND MANPOWER TO INSTALL, CONNECT, AND PLACE INTO SERVICE WITHIN THE SPECIFIED OR APPROVED MANNER SYSTEMS MATERIAL AND SPECIFIC FUNCTIONAL TASK DESCRIBED.
6. CONTRACTOR SHALL REPAIR OR RESTORE ALL DISTURBED AREAS TO ORIGINAL CONDITION OR BETTER.
60'40'20'0'20'
GRAPHIC SCALE 1" = 20'
FACILITY 992
F.F.E - 7.00
C-101
EXISTING CONCRETE
FLOOR SLAB
F.F.E. 7.00
PROPOSED PREFABRICATED
FLOOR TRENCH DRAIN
EXISTING 4" SANITARY
SERVICE
PROPOSED 4" PVC
DRAIN PIPE
E
V
R
I F
Y
4' FIELD VERIFY
COMPACTED SUBGRADE PER
TRENCH DRAIN MANUFACTURE'S
REQUIREMENTS AND
SPECIFICATIONS
EXISTING CONCRETE
FLOOR SLAB
EXISTING BUILDING
SIDING
BUILDING WALL
B
C-101
E
X
I S
T
I
G
S
A
N
I T
A
W
E
R
EXISTING WATER
SERVICE/BACK FLOW
PREVENTER
WATER JET MACHINE
OMAX
PUMP
NEW 2" WATERLINE
UNISTRUT / CLIPS
CLEAN OUT
C-101
M
S
P I V
E Y
M
S
P I V
E Y
U T
I L I T
Y
S
I T
E
P
L A
N
T
R E
N C
H
P
L A
C E
M E
N T
A N
D
C
O N
N E
C T
I O
N
D
E T
A I L S
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
EXISTING SANITARY
SERVICE
SOLIDS REMOVAL
SYSTEM
PUMP
EXISTING CURB
6'
EXISTING CURB
EXISTING ASPHALT
EXISTING CURB
EXISTING WATER LINE
EXISTING STORM
DRAIN
M
I
N
I
M
O
CHILLER
CLOSED
LOOP
SYSTEM
WATER
TANK
DROP SAW
STORAGE
PART
WASHER
EXISTING
CLEANOUT
NEW
HOSE BIB
NEW
CLEANOUT
RESTROOM
24'-6"
32'-0"
23'-0"
6' 9'0'
3'
3'
GRAPHIC SCALE 1" = 3'
CONC. FOOTER
(TYP.)
NORTH
N
A
M b a r v
E-001
ELECTRICAL LEGEND
(APPLIES TO ALL ELECTRICAL SHEETS)
BRANCH CIRCUIT CONDUIT RUN. ARROW INDICATES HOME
RUN, MINIMUM CONDUIT SIZE SHALL BE 3/4". HOMERUNS
LONGER THAN 100' SHALL USE MINIMUM #10 CONDUCTOR.
EXISTING - TO REMAIN
NEW - TO BE INSTALLED
GROUNDING CONDUCTOR, BELOW GRADE
208/120V PANELBOARD, 3 PHASE, 4 WIRE WITH GROUND
G
GROUND ROD - SHOWN WITH BONDED CONNECTION POINT
480/277V PANELBOARD, 3 PHASE, 4 WIRE WITH GROUND
A - AMPERES, AMPS
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLING UNIT
AIC - AMPS INTERRUPTING CAPACITY
BKR - BREAKER
C - CONDUIT
CB - CIRCUIT BREAKER
CHWP - CHILLED WATER PUMP
CKT - CIRCUIT
CLG - CEILING
CU - COPPER
CWP - WATER PUMP CONDENSER
DC - DROP CORD
DH - DEHUMIDIFIER
DIA (Ø) - DIAMETER
DIM - DIMENSION
DISC - DISCONNECT SWITCH
DWG - DRAWING
EF - EXHAUST FAN
ELEC - ELECTRIC
EMT - ELECTRICAL METALLIC TUBING
ETR - EXISTING TO REMAIN
EXTR - EXTERIOR
EXST - EXISTING
FLA - FULL LOAD AMPS
GEN - GENERATOR/GENSET
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
GND - GROUND
HP - HORSEPOWER
KCMIL - THOUSAND CIRCULAR MILS
KW - KILOWATT
LAVs - LAVATORIES/RESTROOMS
LTG - LIGHTING
LV - LOW VOLTAGE
MECH - MECHANICAL
MCP - MOTOR CIRCUIT PROTECTION
MTD - MOUNTED
N/A - NOT APPLICABLE
NC - NORMALLY CLOSED
NIC - NOT IN CONTRACT
NO - NORMALLY OPEN
NTS - NOT TO SCALE
Ø - PHASE
PNL - PANEL, PANELBOARD
PVC - POLYVINYL CHLORIDE
PWR - POWER
RECP - RECEPTACLE
RGS - RIGID GALVANIZED STEEL
RM - ROOM
SFS - SECURITY FORCES SQUADRON
SS - STAINLESS STEEL
ST - SHUNT TRIP
STRP - STRIP
SW - SWITCH
SYS - SYSTEM
TYP - TYPICAL
UG - UNDERGROUND
UON - UNLESS OTHERWISE NOTED
V - VOLTS
W - WATTAGE
WP - WEATHERPROOF
XFER - TRANSFER
XFMR - TRANSFORMER
ABBREVIATIONS:
(APPLIES TO ALL ELECTRICAL SHEETS)
ELECTRICAL NOTES:
1. IT IS THE INTENT OF THESE CONTRACT DRAWINGS TO PROVIDE A COMPLETE
AND WORKABLE FACILITY.
2. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS,
BENDS, ELBOWS, OR OTHER SPECIFIC ELEMENTS THAT MAY BE REQUIRED
FOR PROPER INSTALLATION OF THE WORK. SUCH WORK SHALL BE VERIFIED
AT THE SITE. ADDITIONAL BENDS, OFFSETS, AND CONDUIT AS REQUIRED BY
VERTICAL AND HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB
CONDITIONS, SHALL BE PROVIDED TO COMPLETE THE WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
3. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF
EQUIPMENT SHOWN ON PLANS ARE APPROXIMATE. SUCH ITEMS SHALL BE
PLACED TO ELIMINATE INTERFERENCE WITH OTHER EQUIPMENT. THE EXACT
LOCATIONS SHALL BE DETERMINED IN THE FIELD.
4. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2017 EDITION OF THE
NATIONAL ELECTRICAL CODE (NFPA 70).
5. MATERIALS SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC.
OR ANOTHER APPROVED/CERTIFIED TESTING LABORATORY. SHOULD PLANS
AND CODES CONFLICT, CONTACT THE CONTRACTING OFFICER. MAKE NO
CHANGES, EVEN IN CASE OF CONFLICT, WITHOUT FIRST OBTAINING THE
APPROVAL OF THE CONTRACTING OFFICER.
6. A GREEN, COPPER GROUND WIRE SHALL BE INSTALLED IN ALL CONDUIT
SYSTEMS AND SHALL BE BONDED TO ALL ENCLOSURES, BOXES, AND
EQUIPMENT. RECEPTACLES WITH GREEN WIRE SHALL BE BONDED TO BOX
THEN TO RECEPTACLE SUCH THAT REMOVAL OF RECEPTACLE DEVICE SHALL
NOT INTERRUPT GREEN WIRE BOND TO METALLIC BOX OR ENCLOSURE.
7. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO ENCLOSURES,
BOXES, AND EQUIPMENT WHERE CONCENTRIC OR ECCENTRIC KNOCKOUTS
ARE USED.
8. EQUIPMENT SIZES INDICATED ARE MINIMUM, BEFORE INSTALLING ANY WIRE
OR CONDUIT, THE CONTRACTOR SHALL OBTAIN THE EXACT EQUIPMENT
REQUIREMENTS AND SHALL INSTALL WIRE, CONDUIT, CIRCUIT BREAKERS AND
OTHER ITEMS OF THE CORRECT SIZE FOR THE EQUIPMENT ACTUALLY
INSTALLED. HOWEVER, WIRE AND CONDUIT SIZES FOR THE EQUIPMENT
SHALL BE TAKEN AS A MINIMUM AND SHALL NOT BE REDUCED WITHOUT
WRITTEN APPROVAL.
9. THE INSTALLATION OF THE ELECTRICAL WORK SHALL BE COORDINATED WITH
THE WORK OF THE OTHER TRADES.
10. THE INSTALLATION SHALL BE ACCOMPLISHED BY WORKERS SKILLED IN THIS
TYPE OF WORK. THE INSTALLATION SHALL BE MADE SO THAT THERE IS NO
DEGRADATION OF THE DESIGNED FIRE RATINGS.
11. THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND AT
SUCH A TIME AS WILL REQUIRE A MINIMUM OF CUTTING AND PATCHING OF
THE BUILDING STRUCTURE.
12. 'PROVIDE', AS USED HERE ON THE DRAWINGS, IS AN ALL-INCLUSIVE TERM
REQUIRING CONTRACTOR TO FURNISH, INSTALL, WIRE, AND CONNECT ALL
SPECIFIED EQUIPMENT AS WELL AS COMPONENTS, ACCESSORIES, WIRING,
AND MOUNTING HARDWARE TO INSURE THAT SPECIFIED EQUIPMENT
FUNCTIONS TO MEET SYSTEM(S) REQUIREMENTS.
13. WHERE NEW-TO-EXISTING CONNECTIONS ARE INDICATED, THE CONTRACTOR
SHALL PROVIDE ALL MATERIALS (JUNCTION BOXES, CONDUIT, WIRE, AND
CONNECTIONS) AND LABOR REQUIRED TO MAKE THE CONNECTIONS.
14. UNLESS OTHERWISE NOTED, ALL POWER CIRCUIT CONDUCTORS SHALL BE
COPPER AND MINIMUM #12AWG. CONDUITS SHALL BE 3/4" MINIMUM.
15. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT
EXISTING UTILITIES FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL
EXPENSE FOR REPAIR OR REPLACEMENT OF THE UTILITIES OR OTHER
PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE
COMPLETION OF THIS WORK.
16. ALL BOLTS, NUTS, WASHERS, ETC. USED FOR GROUNDING AND BONDING
CONNECTIONS SHALL BE COPPER. CONTRACTOR SHALL UTILIZE
CONNECTORS TO PREVENT GALVANIC ACTION.
17. FINAL ACCEPTANCE WILL DEPEND UPON SATISFACTORY PERFORMANCE OF
EQUIPMENT. NO CONDUCTOR SHALL BE ENERGIZED UNTIL THE INSTALLATION
HAS BEEN APPROVED.
18. CONDUITS SHALL BE SUPPORTED BY SUITABLE CLAMPS, HANGERS OR
STRAPS TO PROVIDE A RIGID INSTALLATION. CONDUIT SUPPORTS SHALL NOT
BE FASTENED OR ATTACHED TO OTHER PIPES. PERFORATED STRAP
HANGERS WILL NOT BE ALLOWED. EMPTY CONDUIT SHALL BE THOROUGHLY
SWABBED OUT WITH DRY SWAB TO REMOVE MOISTURE AND DEBRIS BEFORE
WIRE IS DRAWN IN. END OF CONDUIT SHALL BE TIGHTLY PLUGGED UNTIL
WIRE IS PULLED. NO CONDUIT SHALL BE LOCATED TO IMPAIR THE STRENGTH
OF STRUCTURAL MEMBERS. MAKE CHANGES IN DIRECTION OF RUNS WITH
SYMMETRICAL BENDS. MAKE FIELD MADE BENDS AND OFFSETS WITH HICKEY
OR CONDUIT BENDING MACHINE. DO NOT INSTALL CRUSHED OR DEFORMED
CONDUITS. AVOID TRAPPED CONDUITS. PREVENT PLASTER, DIRT, OR TRASH
FROM LODGING IN CONDUIT, BOXES, FITTINGS. FREE CLOGGED CONDUITS OF
OBSTRUCTIONS.
19. IN ACCORDANCE WITH NFPA 70, GROUND EXPOSED, NON-CURRENT
CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC
RACEWAY SYSTEMS, GROUNDING CONDUCTOR IN METALLIC RACEWAYS.
20. FASTEN CONDUITS TO SHEET METAL BOXES AND CABINETS WITH TWO
LOCKNUTS WHERE REQUIRED BY NFPA 70, WHERE INSULATED BUSHINGS ARE
USED, AND WHERE BUSHINGS CANNOT BE BROUGHT INTO FIRM CONTACT
WITH THE BOX; OTHERWISE, USE MINIMUM SINGLE LOCKNUT AND BUSHING.
LOCKNUTS SHALL HAVE SHARP EDGES FOR DIGGING INTO WALLS OF METAL
ENCLOSURE. INSTALL BUSHINGS ON ENDS OF CONDUITS, AND PROVIDE
INSULATING TYPE WHERE REQUIRED BY NFPA 70.
21. PROVIDE AND INSTALL AT WALL OR FLOOR PENETRATIONS A PERMANENT
FIRE STOP SYSTEM. THE SYSTEM SHALL CONSIST OF A WATER BASED FIRE
STOP COMPOUND AS THE FILL, VOID, OR CAVITY MATERIAL ALONG WITH
APPROPRIATE DAMMING MATERIAL (AS PER MANUFACTURER'S
INSTRUCTIONS). THE FIRE STOP COMPOUND SHALL NOT CONTAIN ANY
SOLVENTS, INORGANIC FIBERS, OR SILICONE COMPOUNDS AND SHALL NOT
REQUIRE HEAT TO ACTIVATE THE SEAL. THE FIRE STOP COMPOUND SHALL BE
ONE-PART MATERIALS, REQUIRING NO CRITICAL MIXING. THE PENETRATION
SEAL MATERIAL MUST BE UNAFFECTED BY MOISTURE AND MUST MAINTAIN
THE INTEGRITY OF THE FLOOR OR WALL ASSEMBLY FOR ITS RATED TIME
PERIOD WHEN TESTED IN ACCORDANCE WITH ASTM E84. THE SYSTEM SHALL
BE UL CLASSIFIED AND INSTALLED TO PROVIDE A 2 HOUR FIRE RATING. THE
PENETRATION FIRE STOP MATERIAL SHALL BE FLAME-SAFE FS1900 SERIES
COMPOUND AS MANUFACTURED BY GRACE CONSTRUCTION PRODUCTS OR
EQUAL.
22. DEVICE PLATES FOR SWITCHES AND RECEPTACLES SHALL BE SUITABLY
MARKED, SHOWING THE PANEL AND CIRCUIT NUMBER OF THE SOURCE.
REQUIRED MARKING SHALL CONSIST OF A SELF-ADHESIVE LABEL HAVING 1/4
INCH EMBOSSED LETTERS.
23. DISPOSAL OF FLUORESCENT LAMPS AND MERCURY SWITCHES SHALL
COMPLY WITH SPECIFICATION SECTION 01 57 19.
24. DAMAGE DONE TO ZINC COATING OF GALVANIZED CONDUIT, BOXES, AND
FITTINGS, INCLUDING EXPOSED CONDUIT THREADS AND ZINC FINISHES
SCRATCHING, SHALL BE REPAIRED BY CLEANING, PREPPING, AND COATING
DAMAGED SURFACE WITH INORGANIC ZINC COMPOUND.
25. PROVIDE ELECTRICAL CONDUIT AS FOLLOWS:
- RIGID GALVANIZED STEEL - ABOVE GRADE OUTSIDE
- EMT - ABOVE GRADE INSIDE WHERE NOT SUBJECT TO PHYSICAL DAMAGE
- PVC SCHEDULE 40 - BELOW GRADE
- PVC SCHEDULE 80 - WHERE SUBJECT TO PHYSICAL DAMAGE
EXCEPT: ALL EXPOSED ELECTRICAL CONDUIT VULNERABLE TO
MECHANICAL DAMAGE SHALL BE RIGID GALVANIZED STEEL, UNLESS NOTED
OTHERWISE.
4' INDUSTRIAL FLUORESCENT LIGHT FIXTURE
NON-FUSED DISCONNECT SWITCH
NEW SPEAKER, PUBLIC ADDRESS, CEILING MOUNTED
4' FLUORESCENT LIGHT FIXTURE
2/0 BARE COPPER LIGHTNING PROTECTION CONDUCTORLP
DC DROP CORD POWER RECEPTACLE
WAP
WIRELESS ACCESS POINT - CEILING MOUNTED
COMBINATION MOTOR STARTER
E
NEW - UNDERGROUND ELECTRIC
SPD
SURGE PROTECTIVE DEVICE
ELECTRIC MOTOR
EXISTING - UNDERGROUND ELECTRIC
EXISTING - WATER LINE
E
W x
GND
GROUND BAR
NEUTRAL BAR
NEUT
4' WALL MOUNTED FLUORESCENT LIGHT FIXTURE
NEW HEAT DETECTOR
MOTION SENSOR
J JUNCTION BOX
SP
SPEAKER, PUBLIC ADDRESS, WALL MOUNTED
SCREEN PROJECTOR
P
SECURITY DEVICE / SENSOR
WHM
WATT HOUR METER
F
FUSED DISCONNECT SWITCH
VFD
VARIABLE FREQUENCY DRIVE
FUSED/MAGNETIC MOTOR STARTER
M
TO BE REMOVED
S
TO BE REMOVED SPEAKER, PUBLIC ADDRESS, CEILING MOUNTED
S
TO BE REMOVED HEAT DETECTOR
J
M
A Y
H E
W
L
C
O L
E M
A N
E L E
C T
R I C
A L
N
O T
E S
L E
G E
D
A B
B R
E V
I A
T I O
N S
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
PAD-MOUNTED TRANSFORMER (MV)
TRANSFORMER (LV)
T
FEEDER NUMBER (SEE FEEDER SCHEDULE ON SHEET E-701)
X
480V PANELBOARD, 3 PHASE, 3 WIRE WITH GROUND
RECEPTACLE, 120V, QUAD
EXISTING - 4" SANITARY SERVICE
4'' SS
EXISTING - UNDERGROUND COMM SERVICE
C x
EXISTING - STORM DRAIN
SD
x
FIRE ALARM CONTROL PANEL
F
A
M b a r v
SITE DESCRIPTION
OWNER AND ADDRESS: UNITED STATES AIR FORCE
1224 JUPITER STREET, BUILDING 534
PATRICK A.F.B., FLORIDA 32925
LOCATION: PATRICK AIR FORCE BASE
LATITUDE: 28° 14' 06" N LONGITUDE: 80° 36' 38" W
SECTION / TOWNSHIP / RANGE: 2,3,10,11,15 / 26 S / 37 E
PROJECT NAME: CONST/INSTALL UTILITY CONNECTIONS FOR
SHOP EQUIP. B992-DESIGN
PROJECT DESCRIPTION: THIS PROJECT CONSISTS OF EXCAVATION WORK FOR
THE INSTALLATION OF NEW UNDERGROUND UTILITIES.
SITE MAPS: CONSULT ASSOCIATED PLANS FOR EROSION AND SEDIMENT
CONTROLS, STORMWATER DISCHARGE POINTS LOCATION OF SURFACE WATER
AND CONSTRUCTION IMPACT.
SITE AREA:
1. TOTAL AREA OF SITE = 1 AC
2. TOTAL AREA DISTURBANCE = 1 AC
3. WETLAND AREA = NONE
4. RECEIVING WATER = BANANA RIVER
CERTIFICATION OF COMPLIANCE WITH FEDERAL,
STATE AND LOCAL REGULATIONS
IN AN EFFORT TO ENSURE COMPLIANCE WITH FEDERAL, STATE AND LOCAL LAWS
REGARDING EROSION AND TURBIDITY CONTROLS, THE FOLLOWING PERMITS
HAVE BEEN OBTAINED AND ARE AVAILABLE ON-SITE:
D.E.P. PERMIT: NONE
C.O.E. PERMIT: NONE
S.J.R.W.M.D. E.R.PERMIT: NONE
D.E.P. N.O.I.: TO BE SUBMITTED BY CONTRACTOR
SEQUENCE OF MAJOR ACTIVITIES
THE ORDER OF ACTIVITIES WILL BE AS FOLLOWS:
1. SUBMIT NOTICE OF INTENT (N.O.I.)
2. FLAG THE WORK LIMITS & MARK TREE OR PROTECTED AREA BUFFER, IF
APPLICABLE.
3. COORDINATE PRE-CONSTRUCTION MEETING WITH DESIGNATED SITE
SUPERINTENDENT AND INSPECTOR(S) IN CHARGE OF SWPPP REQUIREMENTS
4. INSTALL REQUIRED PERIMETER CONTROLS
5. PERFORM DEMOLITION OPERATIONS, IF APPLICABLE.
6. INSTALL STRUCTURES
7. STABILIZE DENUDED AREAS AND STOCKPILES AS SOON AS PRACTICABLE
8. INSTALL PERMANENT SEEDING/SODDING AND PLANTING AND WATER AS
REQUIRED UNTIL PERMANENTLY ESTABLISHED
9. WHEN ALL CONSTRUCTION ACTIVITY IS COMPLETE AND THE SITE IS
STABILIZED, COORDINATE INSPECTION OF ALL WORK AREAS.
10.REMOVE ANY EROSION CONTROL DEVICES AND RESEED/SOD AS REQUIRED.
11.SUBMIT NOTICE OF TERMINATION (N.O.T.)
CONSTRUCTION CONTRACTOR REQUIREMENTS
IN ADDITION TO THE RESPONSIBILITIES OUTLINED IN THE ABOVE SECTIONS, IT IS
ALSO THE CONSTRUCTION CONTRACTOR'S RESPONSIBILITY TO ENSURE THE
FOLLOWING IS CONDUCTED:
* N.O.I. FORM IS COMPLETED AND SUBMITTED WITH APPROPRIATE FEE AT LEAST
48 HOURS PRIOR TO INITIATING ANY LAND CLEARING ACTIVITY
* CONSTRUCTION CONTRACTOR AND ALL CONSTRUCTION SUB-CONTRACTORS
COMPLETE CERTIFICATION SIGNIFYING THAT THEY ARE AWARE OF TERMS AND
CONDITIONS OF THE GENERIC PERMIT
* CHANGES TO SWPPP ARE COMPLETED, AS NEEDED, TO ENSURE COMPLIANCE
WITH FEDERAL, STATE AND LOCAL REQUIREMENTS AND THE REPORT FORM FOR
CHANGES TO SWPPP IS COMPLETED, WHEN NECESSARY.
* SITE INSPECTIONS ARE PERFORMED AND THE INSPECTION REPORT FORM
COMPLETED AS INDICATED BY PLAN BY CONSTRUCTION CONTRACTOR'S
QUALIFIED INSPECTOR.
* MAINTENANCE ON BMPs AND MAINTENANCE RECORD COMPLETED AS INDICATED
BY PLAN.
* N.O.T. FORM IS COMPLETED AND SUBMITTED AS INDICATED BY PLAN.
IT IS THE CONSTRUCTION CONTRACTOR'S RESPONSIBILITY TO IMPLEMENT THE
BEST MANAGEMENT PRACTICES (BMPs) AS SHOWN ON THE SITE PLAN AND AS
CONTAINED IN THIS SWPPP. IT IS ALSO THE CONSTRUCTION CONTRACTOR'S
RESPONSIBILITY TO ENSURE THESE BMPs ARE PROPERLY INSTALLED, MAINTAINED AND FUNCTIONING PROPERLY TO PREVENT TURBID OR POLLUTED
WATER FROM LEAVING THE PROJECT SITE. THE CONSTRUCTION CONTRACTOR
SHALL ADJUST THE EROSION AND TURBIDITY CONTROLS SHOWN ON THE SITE
PLAN AND ADD ADDITIONAL CONTROL MEASURES, AS REQUIRED TO ENSURE THE
SITE MEETS ALL FEDERAL, STATE AND LOCAL EROSION AND TURBIDITY CONTROL
REQUIREMENTS. BEST MANAGEMENT PRACTICES SHALL BE IMPLEMENTED BY
THE CONSTRUCTION CONTRACTOR AS REQUIRED TO MEET THE SEDIMENT AND
TURBIDITY REQUIREMENTS IMPOSED ON THE PROJECT SITE BY THE REGULATORY
AGENCIES.
THE CONSTRUCTION CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFICATION,
MITIGATION, & REPAIR COSTS ASSOCIATED WITH NON-COMPLIANCE. IT IS THE
CONSTRUCTION CONTRACTOR'S RESPONSIBILITY TO INSTALL ADDITIONAL
MEASURES TO ATTAIN IMMEDIATE COMPLIANCE, SHOULD VIOLATIONS BE
IDENTIFIED.
EROSION AND SEDIMENT CONTROLS
PERIMETER CONTROLS:
1. SILT FENCE: FILTER FABRIC BARRIERS CAN BE USED BELOW DISTURBED
AREAS SUBJECT TO SHEET AND RILL EROSION WITH THE FOLLOWING
LIMITATIONS:
A. WHERE THE MAXIMUM DRAINAGE AREA IS 1/4 ACRE PER 100 FEET OF LENGTH.
B. USE 4"x4" TRENCH & 8" FABRIC EXTENDED INTO GROUND BEFORE BACKFILL &
COMPACTION.
C. MAXIMUM USEFUL LIFE 6 MONTHS.
SWALE / LIVE STREAM SILT / SEDIMENT CONTAINMENT:
1. SEE FDOT INDEX 102, CHART 1, SHEET 1 FOR SPACING REQUIREMENTS FOR
TYPE I AND II SYNTHETIC BALE BARRIERS & SILT FENCES.
2. TURBIDITY CURTAINS SHALL BE LOCATED PARALLEL TO FLOW OF A MOVING
BODY OF WATER & SHALL NOT BE PLACED ACROSS THE MAIN FLOW OF A
SIGNIFICANT BODY OF MOVING WATER.
3. SOIL PARTICLES SHALL BE ALLOWED TO SETTLE A MINIMUM OF 6-12 HOURS
BEFORE REMOVAL OF TURBIDITY CURTAIN.
4. LAND DISTURBING ACTIVITY SHALL NOT CREATE VIOLATIONS OF WATER
QUALITY STANDARDS. MONITORING OF TURBIDITY LEVELS SHALL OCCUR IN
ACCORDANCE WITH PERMIT CONDITIONS.
STOCKPILING MATERIAL:
1. NO EXCAVATED MATERIAL SHALL BE STOCKPILED IN SUCH A MANNER AS TO
DIRECT RUNOFF DIRECTLY OFF THE PROJECT SITE INTO ANY ADJACENT
WATER BODY OR STORM WATER COLLECTION FACILITY.
VEGETATION:
1. TEMPORARY STABILIZATION SHALL BE APPLIED TO AREAS OPENED BY
CONSTRUCTION OPERATIONS AND THAT ARE NOT ANTICIPATED TO BE
RE-DISTURBED AND RECEIVE FINAL STABILIZING TREATMENT WITHIN 14 DAYS.
IF, AFTER 14 DAYS FROM TIME OF STABILIZATION, THE TEMPORARY GRASSED
AREAS HAVE NOT ATTAINED A MINIMUM OF 70% GOOD GRASS COVER, THE
AREA WILL BE REWORKED AND ADDITIONAL MEASURES APPLIED SUFFICIENT
TO ESTABLISH THE DESIRED VEGETATIVE COVER.
2. PERMANENT STABILIZATION SHALL BE PERFORMED IN ALL AREAS THAT HAVE
BEEN DISTURBED BY CONSTRUCTION ACTIVITY UNLESS OTHERWISE DIRECTED
BY THE CONTRACTING OFFICER TO PRESERVE THE FUNCTION OF CRITICAL
SCRUB HABITAT. FINAL STABILIZATION MUST BE INITIATED NO MORE THAN 7
DAYS AFTER LAND DISTURBING ACTIVITIES HAVE CEASED IN THAT AREA.
UNDER NO CIRCUMSTANCES WILL THE CONTRACTOR BE PERMITTED TO CAUSE
A DEGRADATION OF OFFSITE WATER QUALITY. IF SEED IS USED THE SEEDING
MIX MUST PROVIDE BOTH LONG-TERM VEGETATION AND RAPID GROWTH
SEASONAL VEGETATION. SLOPES STEEPER THAN 4:1 SHALL BE SODDED.
3. DISTURBED SIDE SLOPES OF DRAINAGE CONVEYANCE SWALES OR SURFACE
WATERS SHALL BE IMMEDIATELY SODDED. SOD SHALL BE PEGGED OR
STAPLED TO RESIST WASHOUT.
4. CONSTRUCTION CONTRACTOR SHALL STABILIZE COMPLETED PORTIONS OF
THE PROJECT AS WORK PROGRESSES TO PROTECT AGAINST EROSION
UNLESS OTHERWISE DIRECTED BY THE CONTRACTING OFFICER TO PRESERVE
THE FUNCTION OF CRITICAL SCRUB HABITAT. CONSTRUCTION CONTRACTOR
SHALL IMMEDIATELY REPAIR, FILL AND SOD ERODED AREAS OF THE PROJECT
THAT RESULT FROM THE CONSTRUCTION LAND ALTERATIONS.
5. ALL AREAS THAT ARE SEEDED/SODDED SHALL BE INSTALLED AND WATERED
UNTIL THE GROUND COVER IS FULLY ESTABLISHED.
POLLUTANT SOURCE CONTROLS:
WASTE DISPOSAL:
1. WASTE MATERIALS AND RUBBISH SHALL BE COLLECTED AND STORED IN
CONTAINERS OR, IF APPROPRIATE, IN PILES. SEPARATE, SELF-CLOSING,
NONFLAMMABLE, NON-REACTIVE CONTAINERS SHALL BE USED FOR GARBAGE.
OILY FLAMMABLE AND DANGEROUS WASTES, NON-SALVAGE MATERIAL AND
DEBRIS SHALL BE REMOVED FROM WORK AREAS AND DISPOSED OF DAILY.
THE CONSTRUCTION CONTRACTOR SHALL USE A LANDFILL OUTSIDE OF THE
BASE FOR DISPOSAL OF CCAFS AND PAFB C&D IN ACCORDANCE WITH FLORIDA
DEPARTMENT OF ENVIRONMENTAL PROTECTION (FDEP) PERMITS.
2. ASBESTOS WASTE SHALL BE DISPOSED OF OUTSIDE OF THE BASE IN
ACCORDANCE WITH FEDERAL, STATE, AND LOCAL REGULATIONS.
3. ORANGEBURG DUCT HAS BEEN IDENTIFIED AT MANHOLE 2048 (606B) BASED ON
PREVIOUS MANHOLE SURVEYS. PRIOR TO THE START OF CONSTRUCTION,
TEST ALL KNOWN ORANGEBURG DUCT FOR ASBESTOS. IF ASBESTOS IS
FOUND, ABATE ACM IN CONFORMANCE WITH FLORIDA STATUTES
469.001-469.014 AND 29 CFR 1926 1101. IF ADDITIONAL ORANGEBURG DUCT IS
ENCOUNTERED DURING CONSTRUCTION, NOTIFY THE CONTRACTING OFFICER
BEFORE PROCEEDING. ORANGEBURG DUCT SHALL BE CLEANED PRIOR TO
PULLING NEW CABLE AS INDICATED IN SPECIFICATION SECTION 26 05 13.00 98
PARAGRAPH ENTITLED "EXISTING FIBER (ORANGEBURG) DUCT".
4. REFER TO SPECIFICATIONS FOR FURTHER WASTE AND DISPOSAL AND RECORD
KEEPING REQUIREMENTS.
HAZARDOUS / NON HAZARDOUS:
1. ALL HAZARDOUS WASTE SHALL BE MANAGED IN ACCORDANCE WITH STATE
AND FEDERAL REGULATIONS, INCLUDING 45 SW OPLAN 19-14, BY THE
CONSTRUCTION CONTRACTOR AND SHALL BE TURNED OVER TO THE AIR
FORCE FOR DISPOSAL UNDER THE AIR FORCE'S EPA IDENTIFICATION NUMBER.
2. AT THE PRE-CONSTRUCTION CONFERENCE, THE CONSTRUCTION
CONTRACTOR SHALL PROVIDE THE CONTRACTING OFFICER WITH A LIST OF
ALL HAZARDOUS MATERIALS TO BE INCORPORATED INTO THE PROJECT
INCLUDING THE MATERIAL SAFETY DATA SHEET IN ACCORDANCE WITH DFARS
52.223-3, HAZARDOUS WASTE MATERIAL IDENTIFICATION AND MATERIAL
SAFETY DATA AND PROJECT SPECIFICATIONS. THE CONSTRUCTION
CONTRACTOR SHALL SUBMIT COPIES OF SIGNED INTERNAL MANIFESTS TO THE
CONTRACTING OFFICER MONTHLY.
3. THE CONSTRUCTION CONTRACTOR SHALL NOTIFY THE CONTRACTING
OFFICER IMMEDIATELY IF ANY CONTAMINATED SOIL, GROUND WATER OR
SUSPECT DEBRIS IS ENCOUNTERED DURING EXCAVATION, DEMOLITION OR
CONSTRUCTION OF THE PROJECT.
SANITARY WASTE:
1. ALL SANITARY WASTE SHALL BE COLLECTED FROM THE PORTABLE UNITS AS
NEEDED TO PREVENT POSSIBLE SPILLAGE. THE WASTE SHALL BE COLLECTED
AND DISPOSED OF IN ACCORDANCE WITH STATE AND LOCAL WASTE DISPOSAL
REGULATIONS FOR SANITARY SEWER.
OFFSITE VEHICLE TRACKING:
1. A STABILIZED CONSTRUCTION ENTRANCE SHALL BE PROVIDED, WHERE
NECESSARY, TO HELP REDUCE VEHICLE TRACKING OF SEDIMENT. THE PAVED
STREET ADJACENT TO THE SITE ACCESS SHALL BE SWEPT DAILY TO REMOVE
ANY EXCESS MUD, DIRT OR ROCK TRACKED FROM THE SITE. DUMP TRUCKS
HAULING MATERIAL FROM THE CONSTRUCTION SITE SHALL BE COVERED WITH
A TARPAULIN.
FERTILIZERS, PESTICIDES, HERBICIDES:
1. THE SPECIFIED REQUIREMENT FOR FERTILIZERS, PESTICIDES, AND
HERBICIDES SHALL BE IDENTIFIED. THE QUANTITIES AND METHODS OF
APPLICATION SHALL BE CHECKED TO ASCERTAIN THEY ARE APPROPRIATE AND
CONSISTENT WITH LOCAL GUIDELINES.
GOOD HOUSEKEEPING:
THE FOLLOWING GOOD HOUSEKEEPING PRACTICES SHALL BE FOLLOWED ONSITE
DURING THE CONSTRUCTION PROJECT:
1. ALL CONSTRUCTION EQUIPMENT SHALL BE IN PROPER WORKING ORDER AND
INSPECTED REGULARLY. ALL EQUIPMENT SHALL HAVE THE BUILT-IN CAPACITY,
STABILITY, AND NECESSARY SAFETY FEATURES TO FULLY COMPLY WITH THE
PROJECT SPECIFICATIONS AND REQUIREMENTS, WITHOUT SHOWING
EVIDENCE OF UNDUE STRESS OR FAILURE. CONSTRUCTION CONTRACTOR
PERSONNEL SHALL BE IN SUFFICIENT NUMBER OF COMPETENT WORKERS ON
THE JOB AT ALL TIMES TO INSURE WORK IS MADE A TIMELY AND
SATISFACTORY MANNER. A COMPETENT AND EXPERIENCED SUPERVISOR,
REPRESENTING THE CONSTRUCTION CONTRACTOR, SHALL BE IN DIRECT
CHARGE AND CONTROL OF OPERATIONS AT ALL TIMES. EQUIPMENT
BREAKDOWNS OR OTHER UNFORESEEN WORK STOPPAGES SHALL
IMMEDIATELY CONSIDER THE PROTECTION OF SURFACE WATERS FROM
POTENTIAL POLLUTION.
2. DRIP PANS SHALL CONTAIN LEAKS OR SPILLS WHENEVER NECESSARY FOR
MAINTENANCE ACTIVITIES. ALL SPILLS SHALL BE CLEANED UP IMMEDIATELY IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
3. AN EFFORT SHALL BE MADE TO STORE ONLY ENOUGH PRODUCTS REQUIRED
TO DO THE JOB.
4. ALL MATERIALS STORED ONSITE SHALL BE STORED IN NEAT, ORDERLY
MANNER IN THEIR APPROPRIATE CONTAINERS AND, IF POSSIBLE, UNDER A
ROOF OR OTHER ENCLOSURE.
5. PRODUCTS SHALL BE KEPT IN THEIR ORIGINAL CONTAINERS WITH THE
ORIGINAL MANUFACTURER'S LABEL.
6. SUBSTANCES SHALL NOT BE MIXED WITH ONE ANOTHER UNLESS
RECOMMENDED BY THE MANUFACTURER.
7. WHENEVER POSSIBLE, ALL OF A PRODUCT SHALL BE USED UP BEFORE
DISPOSING OF THE CONTAINER.
8. MANUFACTURER'S RECOMMENDATIONS FOR PROPER USE AND DISPOSAL
SHALL BE FOLLOWED.
INSPECTION AND MAINTENANCE PLAN
INSPECTION AND MAINTENANCE REPORTS:
1. THE CONSTRUCTION CONTRACTOR'S QUALIFIED INSPECTOR SHALL INSPECT
ALL POINTS OF DISCHARGE INTO SURFACE WATERS, ALL DISTURBED AREAS
OF CONSTRUCTION THAT HAVE NOT BEEN FINALLY STABILIZED, AREAS OF
STORAGE MATERIALS THAT ARE EXPOSED TO PRECIPITATION, STRUCTURAL
CONTROLS AND LOCATIONS WHERE VEHICLES ENTER OR EXIT THE SITE AT
LEAST ONCE EVERY SEVEN CALENDAR DAYS AND WITHIN 24 HOURS OF THE
END OF A STORM THAT IS 0.50 INCHES OR GREATER. WHEN THE SITE HAS
BEEN FINALLY STABILIZED, THE INSPECTION SHALL OCCUR AT LEAST
MONTHLY. ALL INSPECTIONS SHALL BE DOCUMENTED IN THE SWPPP USING
THE SWPPP INSPECTION REPORT FORM.
2. THE EROSION CONTROL SHALL BE MAINTAINED IN GOOD AND EFFECTIVE
OPERATING CONDITIONS, AND REPAIR TO IMPACTED SYSTEMS SHALL BE
INITIATED AND COMPLETED IMMEDIATELY. WHERE EROSION CONTROL
MEASURES ARE DEEMED INEFFECTUAL BY THE CONSTRUCTION CONTRACTOR,
THE GOVERNMENT ENVIRONMENTAL REPRESENTATIVE OR THE CONTRACTING
OFFICER, THE CONSTRUCTION CONTRACTOR SHALL IMMEDIATELY
COORDINATE CORRECTIVE MEASURES FOR REPAIR AND REPLACEMENT. ALL
REGULAR AND SPECIAL MAINTENANCE SHALL BE RECORDED IN THE SWPPP ON
THE MAINTENANCE REPORT FORM. ALTERNATIVE MEASURES, REPAIRS, AND
REPLACEMENT SHALL BE IMMEDIATELY IMPLEMENTED AND RECORDED WITH
THE FORM FOR CHANGES TO THE SWPPP. IN NO CASE SHALL
IMPLEMENTATION OF THE REPAIR OR REPLACEMENT OCCUR MORE THAN 7
CALENDAR DAYS FOLLOWING THE INSPECTION.
3. THE GOVERNMENT ENVIRONMENTAL REPRESENTATIVE'S QUALIFIED
INSPECTORS SHALL PERIODICALLY REVIEW THE CONSTRUCTION
CONTRACTOR'S INSPECTION REPORTS FOR ADEQUACY AND COMPLETION AND
REPORT IN WRITING, TO THE CONTRACTING OFFICER ANY DEFICIENCIES IN
THE REPORTING. THE CONSTRUCTION CONTRACTOR SHALL ADJUST THE
REPORTING REQUIREMENTS TO THE SATISFACTION OF THE CONTRACTING
OFFICER. THE GOVERNMENT ENVIRONMENTAL REPRESENTATIVE REPORTS
SHALL ALSO BE MADE A RECORD OF THE SWPPP.
4. ALL REPORTS, PLANS, AND AMENDMENTS SHALL BE MADE PART OF THE
SWPPP. SUCH REPORTS SHALL IDENTIFY ANY INCIDENTS OF
NON-COMPLIANCE. WHEN A REPORT DOES NOT IDENTIFY ANY INCIDENCES OF
NONCOMPLIANCE, THE REPORT SHALL CONTAIN A CERTIFICATION THAT THE
FACILITY IS IN COMPLIANCE WITH THE SWPPP AND GENERIC PERMIT. THE
REPORT SHALL BE SIGNED IN ACCORDANCE WITH THE GENERIC PERMIT.
NON-STORM WATER DISCHARGES
DEWATERING DISCHARGES:
1. DEWATERING ACTIVITIES ARE SUBJECT TO REVIEW OF THE JURISDICTIONAL
STATE AGENCIES, THE CONTRACTING OFFICER AND UNITED STATES AIR
FORCE ENVIRONMENTAL AND IRP OFFICES. DISCHARGES SHALL PROVIDE
PROVISIONS SO THAT NO UPSTREAM FLOODING OR IMPOUNDMENT OCCURS
AND NO SILTATION, EROSION, OR TURBID DISCHARGES OCCURS IN VIOLATION
OF STATE WATER QUALITY STANDARDS. ALL TEMPORARY WORKS SHALL BE
COMPLETELY REMOVED AND ALL AREAS RESTORED TO GRADES, ELEVATIONS
AND CONDITIONS THAT OCCURRED BEFORE CONSTRUCTION AS SOON AS
POSSIBLE.
2. IT IS NOTED HERE THAT GROUNDWATER DEWATERING ACTIVITIES AT
CONSTRUCTION SITES CANNOT BE CONDUCTED UNDER THE GENERIC PERMIT
FOR STORMWATER DISCHARGE FROM LARGE AND SMALL CONSTRUCTION
ACTIVITIES. PURSUANT TO SECTION 62-621.300(2, FAC, A SEPARATE PERMIT,
ENTITLED, GENERIC PERMIT FOR THE DISCHARGE OF PRODUCED GROUND
WATER FROM ANY NON-CONTAMINATED SITE ACTIVITY, MUST BE APPLIED FOR
TO CONDUCT GROUND WATER DEWATERING ACTIVITIES, IF NECESSARY.
TERMINATION PLAN
1. WHEN THE SITE HAS BEEN FINALLY STABILIZED AND ALL STORMWATER
DISCHARGES FROM CONSTRUCTION SITES ELIMINATED, THE CONSTRUCTION
CONTRACTOR SHALL SUBMIT A NOTICE OF TERMINATION (N.O.T.) WITHIN 14
DAYS OF FINAL STABILIZATION WITH A SUFFICIENT AMOUNT OF ESTABLISHED
PERMANENT VEGETATION.
2. AFTER FILING N.O.T., THE CONSTRUCTION CONTRACTOR SHALL SUBMIT THE
FINAL SWPPP, INCLUDING ALL REPORTS AND RECORDS, TO THE CONTRACTING
OFFICER. THE OWNER SHALL THEN BE RESPONSIBLE TO RETAIN A COPY OF
THE POLLUTION PREVENTION PLAN FOR A PERIOD OF THREE YEARS FROM THE
DATE THE SITE IS FINALLY STABILIZED.
CERTIFICATION:
"I CERTIFY UNDER PENALTY OF LAW THAT I UNDERSTAND, AND SHALL COMPLY
WITH, THE TERMS AND CONDITIONS OF THE STATE OF FLORIDA GENERIC PERMIT
FOR STORMWATER DISCHARGE FROM LARGE AND SMALL CONSTRUCTION
ACTIVITIES AND THIS STORMWATER POLLUTION PREVENTION PLAN PREPARED
THEREUNDER."
E-002
J
M
A Y
H E
W
L
C
O L
E M
A N
C O
N S
T R
U C
T I O
N
R
E Q
U I R
E M
E N
D
E R
O S
I O
N
C
O N
T R
O L S
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L U
S A
F
T
H
C
I V
G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A
D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D n g i n e e r i n g I n c
L L E
N
E A
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
A
M b a r v
SILT FLOW
M
I N
FILTER FABRIC
ELEVATION
SECTION
EROSION CONTROL NOTES:
1. AFTER EACH STORM EVENT, THE SILT FENCE SHALL BE INSPECTED. SEDIMENT DEPOSITS SHALL BE REMOVED AND
WASHOUTS/STRUCTURAL FAILURES SHALL BE REPAIRED IMMEDIATELY.
2. TWO SILT FENCES SHALL BE ATTACHED BY PLACING THE END POST OF THE SECOND FENCE INSIDE THE END POST
OF THE FIRST FENCE. BOTH POSTS SHALL BE ROTATED AT LEAST 180° IN A CLOCKWISE DIRECTION TO CREATE A
TIGHT SEAL WITH THE FABRIC MATERIAL. DRIVE BOTH POSTS 18" INTO THE GROUND & BURY FLAP.
3. SILT FENCES SHALL BE REMOVED ONLY AFTER DISTURBED AREAS HAVE BEEN STABILIZED.
WOOD POST @ 10' O.C.
MIN 1" X 2" X 3'
TRENCH MIN 4" X 4"
BURY MIN 8" OF FABRIC IN TRENCH
GEOTEXTILE SILT SCREEN
STAPLE TO POST
THIS METHOD OF INLET PROTECTION IS APPLICABLE WHERE THE INLET DRAINS A
RELATIVELY FLAT AREA (SLOPES NO GREATER THAN 5 PERCENT) WHERE SHEET OR
OVERLAND FLOWS (NOT EXCEEDING 0.5 cfs) ARE TYPICAL. THE METHOD SHALL NOT APPLY
TO INLETS RECEIVING CONCENTRATED FLOWS, SUCH AS IN STREET OR HIGHWAY MEDIANS.
FABRIC SEDIMENT FILTER
SPECIFIC APPLICATION
BURLAP FABRIC
STAKES
BURIED BURLAP
FABRIC
RUNOFF WATER
WITH SEDIMENT
FILTERED WATER
CATCH BASIN INLET SEDIMENT TRAP
SILT FENCE
E-003
J
M
A Y
H E
W
L
C
O L
E M
A N
C O
N S
T R
U C
T I O
N
D
E T
A I L S
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L U
S A
F
T
H
C
I V
G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A
D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D n g i n e e r i n g I n c
L L E
N
E A
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
A
M b a r v
E
E
S D
C x
C x
C x
C x
C x
C x
C x
C x
C x
S
S
S
S
W x
W x
W x
W x
W x
W x
W x
W x
W x
E
E
E
E
E
E
E
E
W
T
E
SCALE:
ELECTRICAL SITE PLAN
1" = 20'
60'40'20'0'20'
GRAPHIC SCALE 1" = 20'
GENERAL NOTE:
1. SEE SINGLE LINE DIAGRAM ON SHEET E-602 AND FEEDER SCHEDULE ON E-701 FOR CONDUIT AND
CONDUCTOR SIZES.
FLAG NOTES:
1. REMOVE EXISTING 500 KVA PADMOUNTED TRANSFORMER AND DELIVER TO PAFB ELECTRIC SHOP.
INSTALL NEW 750 KVA PADMOUNTED TRANSFORMER. INSTALL NEW TRANSFORMER ON NEW
CONCRETE PAD. PROVIDE GROUNDING FOR NEW TRANSFORMER PER DETAIL ON SHEET E-501.
2. PROVIDE 2 NEW 5" CONDUITS. CONDUITS SHALL BE DIRECT BURIED, 18" BELOW GRADE. ROUTE
CONDUIT PARALLEL TO EXISTING 4" CONDUIT PER FLAG NOTE 4.
3. EXISTING TRANSFORMER, 480-208/120V, SHALL REMAIN.
4. EXISTING 4" CONDUIT SHALL BE ABANDONED IN PLACE AFTER REMOVAL OF CONDUCTORS. FIELD
VERIFY EXACT ROUTING OF EXISTING CONDUIT. COORDINATE WITH WORK OF FLAG NOTE 2.
5. EXISTING CONCRETE PAD SHALL BE REMOVED. PROVIDE NEW CONCRETE PAD AS REQUIRED TO
MATCH NEW TRANSFORMER DIMENSIONS. SEE TYPICAL PAD DETAIL ON DRAWING E-501 FOR
ADDITIONAL REQUIREMENTS.
6. EXISTING TRANSFORMER T959 SHALL REMAIN.
7. EXISTING 4" CONDUIT WITH (3) #2 15 KV. REMOVE EXISTING CONDUCTORS AND INSTALL NEW
CONDUCTORS (3) #2 15 KV EPR.
ES-101
J
M
A Y
H E
W
L
C
O L
E M
A N
E L E
C T
R I C
A L
S
I T
E
P
L A
N
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L n g i n e e r i n g I n c
L L E
N
E A
U S
T
H
C
I V
G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A
D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
TRUE
NORTH
NORTH
PLAN
A
M b a r v
XFMR-1
PAD
TTC
EXIST F/A
DISCONNECT
1 2 3 4 5
T
P2-12
P2-12
P2-12
P2-12 P2-12
T
ED-101
SCALE:
POWER AND COMMUNICATIONS PLAN - EXISTING AND DEMOLITION
3/16" = 1'-0"
TRUE
NORTH
NORTH
PLAN
GENERAL NOTE:
1. REMOVE ASSOCIATED CONDUIT, WIRE, AND SUPPORTS OF EQUIPMENT BEING REMOVED.
FLAG NOTES:
1. EXISTING ELECTRICAL PANEL SHALL REMAIN.
2. REMOVE EXISTING ELECTRICAL PANEL.
3. EXISTING FIRE ALARM CONTROL PANEL SHALL REMAIN.
4. EXISTING TELEPHONE TERMINAL CABINET SHALL REMAIN.
5. EXISTING RECEPTACLE SHALL BE DISCONNECTED FROM CIRCUIT P2-12 AND BE REMOVED. SPLICE
CONDUCTORS AS REQUIRED TO MAINTAIN POWER TO OTHER RECEPTACLES FED BY P2-12. PROVIDE
BLANK COVER TO CONVERT EXISTING OUTLET BOX TO A JUNCTION BOX. SEE DRAWING E-101 FOR
NEW RECEPTACLE BEING INSTALLED NEAR THIS LOCATION ON A NEW CIRCUIT.
6. EXISTING RECEPTACLE SHALL REMAIN FED FROM CIRCUIT P2-12.
7. EXISTING DISCONNECT SWITCH SHALL REMAIN.
8. REMOVE EXISTING DISCONNECT SWITCH.
J
M
A Y
H E
W
L
C
O L E
M A
N
P O
W E
R
A
M
M U
N I C
A T
I O
A
N
E X
I S
T I N
G
A
M
O
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A
I L
I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L n g i n e e r i n g I n c
L L
E N
E A
U S
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
16'12'8'0'2'4' 4'
GRAPHIC SCALE 3/16" = 1'-0"
PANEL
P-5
PANEL
P-3
PANEL
P-4
FACP
PANEL
P-1
PANEL
P-2
P4-14,16,18
P4-20,22,24
MEZZANINE
A
M b a r v
1 2 3 4 5
LIGHTING PLAN - EXISTING AND DEMOLITION
3/16" = 1'-0"
TRUE
NORTH
NORTH
PLAN
GENERAL NOTE:
1. EXISTING LIGHTING FIXTURES ARE LOCATED APPROXIMATELY 16' TO 20' ABOVE FINISHED FLOOR.
FLAG NOTE:
1. EXISTING FLUORESCENT FIXTURE ATTACHED TO THE CEILING STRUCTURE. DISCONNECT EXISTING
CONDUIT AND WIRE. RETAIN FIXTURES FOR REINSTALLATION AS SHOWN ON DRAWING E-102.
16'12'8'0'2'4' 4'
GRAPHIC SCALE 3/16" = 1'-0"
(TYP)
ED-102
J
M
A Y
H E
W
L
C
O L
E M
A N
L I G
H T
I N
G
P
L A
N
E
X I S
T I N
G
A
M
O L
I T
I O
N
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A
I L
I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L n g i n e e r i n g I n c
L L
E N
E A
U S
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I L
T
D
A T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
MEZZANINE
A
M b a r v
XFMR-1
PAD
1 2 3 4 5
FFF
F F
F F F
F
T
T
P2-12
P5-8
P2-12
P5-8
P2-12
P4-11
P4-9P4-11P4-9
F F F
EXIST F/A
DISCONNECT
J
J
E-101
SCALE:
POWER AND COMMUNICATIONS PLAN - EXISTING AND NEW
3/16" = 1'-0"
TRUE
NORTH
NORTH
PLAN
J
M
A Y
H E
W
L
C
O L E
M A
N
P O
W E
R
A
M
M U
N I C
A T
I O
A
N
E X
I S
T I N
G
A
W
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L
L
U
T I L
I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L n g i n e e r i n g I n c
L L
E N
E A
U S
T
H
C
I V
G
I N
E E
R
S
Q U
A D
R O
N
I L
T
D
A T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A
D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
16'12'8'0'2'4' 4'
GRAPHIC SCALE 3/16" = 1'-0"
TTC
FACP
PANEL
P-3
PANEL
P-4
PANEL P-5
GENERAL NOTES:
1. SEE FEEDER SCHEDULE ON SHEET E-701 FOR CONDUIT AND CONDUCTOR SIZES.
2. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE. FACILITY USER TO POSITION EQUIPMENT PRIOR
TO ELECTRICAL CONNECTIONS BEING MADE.
3. DISCONNECT SWITCH RATINGS SHALL BE EQUAL TO OR GREATER THAN THE CIRCUIT AMPACITY
SHOWN IN THE FEEDER SCHEDULE TABLE ON SHEET E-701.
4. CONDUIT SHALL NOT BE ROUTED ON THE FLOOR. PROVIDE STEEL SUPPORT STANCHIONS
CONSTRUCTED OF UNISTRUT TYPE CHANNEL WITH ASSOCIATED UNISTRUT TYPE HORIZONTAL
CONVEYANCE, WALL BRACKETS AND ADDITIONAL HARDWARE. HORIZONTAL SECTIONS SHALL BE
APPROXIMATELY 10' ABOVE FINISHED FLOOR. COORDINATE SUPPORT LOCATIONS WITH THE
FACILITY USER TO AVOID INTERFERENCE WITH PLANNED USAGE OF SHOP EQUIPMENT.
FLAG NOTES:
1. EXISTING ELECTRICAL PANEL.
2. PROVIDE NEW ELECTRICAL PANEL.
3. EXISTING FIRE ALARM CONTROL PANEL.
4. EXISTING TELEPHONE TERMINAL CABINET.
5. PROVIDE NEW DISCONNECT SWITCH. SEE GENERAL NOTE 3.
6. PROVIDE BLANK COVER TO CONVERT EXISTING OUTLET BOX TO A JUNCTION BOX. SEE DRAWING
ED-101 FOR REMOVAL OF EXISTING RECEPTACLE.
7. PROVIDE NEW QUAD RECEPTACLE AND FEED FROM CIRCUIT P5-8. LOCATE RECEPTACLE ADJACENT
TO THE JUNCTION BOX IDENTIFIED BY FLAG NOTE 6.
8. PROVIDE NEW QUAD RECEPTACLE IN CENTER OF SHOP AREA. SEE GENERAL NOTE 4.
PANEL
P-1
PANEL
P-2
P4-31,33,35
P1-20,22,24
P1-8,10,12
P5-31,33,35
P1-14,16,18
P5-27,29
BEAD BLASTER
P1-13,15,17
P1-2,4,6
P1-19,21
K
ROLLING
TABLE/SHEET
STORAGE
METAL
RECYCLE
W A
T E
R
T A
N K
WATER
JET
MACHINING
CENTER
CLOSED
LOOP
SYSTEM
CHILLER
OMAX
PUMP
DROP SAW
S T
O R
A G
E
HORIZ
STORAGE
S T
O R
A G
E
V E
R T
S H
E E
T
S T
O R
A G
E
PRTR
PART
WASHER
ROLLING
TABLE/SHEET
STORAGE
WELDING
ENCLOSURE
OVEN
F U
R N
A C
E
VAC
VAC
A
M
P
TURNING CENTER
TURNING
CENTER
ROLLING
TABLE/SHEET
STORAGE
TOOL
BOX
DRILL
PRESS
IRON
WORKER
ARBER
PRESS
B
P5-34,36
J
P5-30,32
J
EJ
D
ULTRASONIC
WELDER
E
G
J
MEZZANINE
P4-38,40,42
B
P4-20,22,24
E
P4-9,11
M
P1-31,33,35
E
F
TIG
WELDER
(TYP)
J
(TYP)
A
M b a r v
1 2 3 4 5
LIGHTING PLAN - NEW CONSTRUCTION
3/16" = 1'-0"
TRUE
NORTH
NORTH
PLAN
GENERAL NOTE:
1. CONNECT LIGHTING FIXTURES TO EXISTING CIRCUITS AND SWITCHES.
FLAG NOTE:
1. REINSTALL EXISTING FLUORESCENT FIXTURES SO THAT BOTTOM OF FIXTURE IS 12' ABOVE FINISHED
FLOOR. REPOSITION FIXTURES AS SHOWN ON THIS SHEET TO ALLOW FOR MAINTENANCE ACCESS.
PROVIDE NEW 3/4" CONDUIT AND #12 WIRE FOR RECONNECTION OF EXISTING CIRCUIT TO THE
RELOCATED FIXTURES.
16'12'8'0'2'4' 4'
GRAPHIC SCALE 3/16" = 1'-0"
(TYP)
E-102
J
M
A Y
H E
W
L
C
O L E
M A
N
L I G
H T
I N
G
P
L A
N
E
X I S
T I N
G
A
W
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L
L
U
T I L
I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L n g i n e e r i n g I n c
L L
E N
E A
U S
T
H
C
I V
G
I N
E E
R
S
Q U
A D
R O
N
I L
T
D
A T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A
D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
MEZZANINE
A
M b a r v
SEE DETAIL
TO SWITCH GND BUS.
PROVIDE #4/0 BSD COPPER
WELD (TYP)
EXOTHERMIC
PROVIDE
GROUND RODS
COPPER CLAD STEEL
PROVIDE (2) 3/4" x 10'-0"
24" BELOW GRADE.
GROUNDING CONDUCTOR, MINIMUM
PROVIDE #4/0 BSD COPPER
E-501
CONCRETE 4000 PSI @ 28 DAYS
M I N
"CADWELD" TYPE
EXOTHERMIC WELD
#4/0 BSD CU.
GROUND CABLE
CRUSHED STONE
GROUND RODS
PROVIDE (2)
3/4" X 10'-0"
COPPER CLAD STEEL
GROUND ROD
6"
4" MAX
SIZE PAD AS REQUIRED TO
SUIT EQUIPMENT FURNISHED
#4 BAR @ 12" MAX. EA. WAY
TOP & BOTTOM
FINISHED
GRADE
#4
9"
#4 CENTERED
SCALE:
TYPICAL TRANSFORMER GROUNDING DETAIL
NONE
C
SCALE:
GROUND ROD DETAIL
NONE
C
E-501
SCALE:
15KV PAD MOUNTED EQUIPMENT
NONE
CONCRETE PAD DETAIL FOR
SCALE:
SECTION
NONE
A
E-501
SCALE:
SECTION
NONE
B
E-501
CONDUIT/CABLE ENTRY AREA
#5 BAR @ 12" MAX. TOP & BOTTOM
M
A X
REAR
12"
FRONT
12"
A
E-501
4"
T O
T
T O
M
NOTE: SIZE OF PAD SHALL BE A MINIMUM OF 12" WIDER
AND 12" LONGER THAN TRANSFORMER OR SWITCH
DIMENSIONS.
B
E-501
4"
PLAN VIEW
SCALE:
TYPICAL DETAIL
NONE
E-501
J
M
A Y
H E
W
L
C
O L E
M A
N
E L
E C
T R
I C
W I T
D
G R
O U
N D
I N
G
D
E T
A I L
S
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L
L
U
T I L
I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I L
T
D
A T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D n g i n e e r i n g I n c
L L
E N
E A
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
SCALE:
MEDIUM VOLTAGE CIRCUIT IDENTIFICATION TAG DETAIL - EXAMPLE
NONE
BɸFROM
Bɸ TO
FROM
AT EQUIPMENT
MHTOMHBɸ
SS37V1-1
MH Bɸ
AT MANHOLES OR HANDHOLES
2329 2418
CKT N0IC10
KCMIL KCMIL
KCMILKCMIL
INDICATES PHASE OF
SINGLE CONDUCTOR CABLE
CABLE
1" HIGH POLYETHYLENE TAGS
WITH BLACK ON YELLOW FINISH
STANDARD CHARACTERS
(TYPICAL CABLE NUMBER SHOWN)
NYLON SELF-LOCKING
TIE-STRAPS
CABLE
POLYETHYLENE TAG HOLDER
WITH BLACK FINISH (TYP)
NOTE: AT EQUIPMENT, CABLE TAG
SHALL IDENTIFY EQUIPMENT AT OTHER
END OF THE CABLE.
A
M b a r v
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
E-601
J
M
A Y
H E
W
L
C
O L
E M
A N
S I N
G
N
E
D
I A
G R
X I S
T I N
G
A
N D
D E
M O
L I T
I O
N
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L
SCALE: NONE
SINGLE LINE DIAGRAM - EXISTING AND DEMOLITION
(2) SETS
4" SCH 80 PVC WITH
3#250 KCMIL AND
1#2 GND IN EACH CONDUIT
225 KVA
480-280/120V
SERVICE
ENTRANCE
GROUND
A/C PACKAGED
UNIT
40A
3P
300A
3P
400A
3P
PANEL P1, 400A, 3P, 3W
SQUARE D I-LINE OR EQUAL
20A
3P
SERVICE
ENTRANCE
GROUND
500 KVA
13.2 KVA - 480/277V
PAD MOUNTED
TRANSFORMER
PANEL
P-3
125A
3P
SPD
1,3,5 2 4 6 7,9,11 8 10 12 13 16 201814
M
R E
C E
P T
A C
L E
U P
P E
R
N
W
L I G
H T
S
H I G
H
B
A Y
S O
U T
H
O U
T S
I D
E
D R
Y E
R
F
U T
U R
E
L I G
H T
S
M E
Z Z
A
B O
V E
A N
D
B
E L O
W
T V
S S
PANEL P2, 208Y/120V, 3 PH, 4W
600A
O U
T S
I D
E
L I G
H T
I N
G
L I G
H T
S
H I G
H
B
A Y
N O
R T
H
S P
A R
E
600A3P
SPD
S O
U T
H
R E
C E
P T
A C
L E
S
N O
R T
H
R E
C E
P T
A C
L E
S
15 17
R
O L L U
P
D O
O R
S
R E
C E
P T
A C
L E
U P
P E
R
S
E
R E
C E
P T
A C
L E
R E
C E
P T
A C
L E
R E
C E
P T
A C
L E
S
A D
T C
O M
M
R E
C E
P T
A C
L E
S
F I R
E
A
L A
R M
R E
C E
P T
A C
L E
S
L O
W E
R
L I G
H T
N O
R T
H
R E
C E
P T
A C
L E
S
R E
C E
P T
A C
L E
S
R E
C E
P T
A C
L E
S
R E
C E
P T
A C
L E
S
SUBFEED SUBFEED
P A
N E
L
P
O
F F
I C
E
P A
N E
L
P
FLAG NOTE:
1. REMOVE EXISTING (3) 1C #2.
20A
3P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
200A
3P
20A
1P
20A
1P
30A
1P
30A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
200A
3P
200A
3P
1,2,3
SW #23 (FDR A1)
7,8,94,5,6 10,11,12
T907
225KVA
208Y/120V
T959
112.5KVA
208Y/120V
A
M b a r v
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
E-602
J
M
A Y
H E
W
L
C
O L
E M
A N
S I N
G
N
E
D
I A
G R
X I S
T I N
G
A
W
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L
225 KVA
480-280/120V
SERVICE
ENTRANCE
GROUND
A/C PACKAGED
UNIT
40A
3P
300A
3P
1000A
3P
PANEL P1, 1000A, 3P, 4W
SQUARE D I-LINE OR EQUAL
30A
3P
750 KVA
13.2 KVA - 480/277V
PAD MOUNTED
TRANSFORMER
3-AXIS
MILL
20A
3P
SPD
80A
3P
20A
3P
FURNACE
125A
3P
IRON
WORKER
30A
3P
40A
3P
OMAX CLOSED
LOOP SYSTEM
15A
2P
NEUTRAL
GROUND
GENERAL NOTE:
1. SEE SHEET E-701 FOR FEEDER AND CONDUIT SIZES.
WHM 1
OMAX
PUMP
OMAX
CHILLER
AIR
COMPRESSOR
BC DE F G B
FLAG NOTES:
1. PROVIDE NEW SMART METER MOUNTED WITHIN THE SWITCHBOARD.
METER SHALL BE SCHNEIDER PM5560S METSEPM5560 BASIC METERING
WITH CLASS 0.2S ACCURACY + 4DI/2DO + DATA LOGGING + MULTI TARIFF
+ DUAL ETHERNET AND SERIAL COMMS + 4TH CT INPUT FOR NEUTRAL &
GROUND MEASUREMENT + INTERNAL WEB SERVER. (INCLUDE GATEWAY
+ CYBER SECURITY). INSTALL WITH THE MODBUS TCP/IP ETHERNET
CARD INCLUDED
2. PROVIDE NEW (3) 1C #2, 15KV EPR CABLE.
A
L
J
SCALE: NONE
SINGLE LINE DIAGRAM - EXISTING AND NEW
SERVICE
ENTRANCE
GROUND
1,3,5 2 4 6 7,9,11 8 10 12 13 16 201814
M
R E
C E
P T
A C
L E
U P
P E
R
N
W
L I G
H T
S
H I G
H
B
A Y
S O
U T
H
O U
T S
I D
E
D R
Y E
R
F
U T
U R
E
L I G
H T
S
M E
Z Z
A
B O
V E
A N
D
B
E L O
W
T V
S S
PANEL P2, 208Y/120V, 3 PH, 4W 600A
O U
T S
I D
E
L I G
H T
I N
G
L I G
H T
S
H I G
H
B
A Y
N O
R T
H
S P
A R
E
600A3P
SPD
S O
U T
H
R E
C E
P T
A C
L E
S
N O
R T
H
R E
C E
P T
A C
L E
S
15 17
R
O L L U
P
D O
O R
S
R E
C E
P T
A C
L E
U P
P E
R
S
E
R E
C E
P T
A C
L E
R E
C E
P T
A C
L E
R E
C E
P T
A C
L E
S
A D
T C
O M
M
R E
C E
P T
A C
L E
S
F I R
E
A
L A
R M
R E
C E
P T
A C
L E
S
L O
W E
R
L I G
H T
N O
R T
H
R E
C E
P T
A C
L E
S
R E
C E
P T
A C
L E
S
R E
C E
P T
A C
L E
S
R E
C E
P T
A C
L E
S
SUBFEED SUBFEED
P A
N E
L
P
O
F F
I C
E
P A
N E
L
P
20A
3P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
200A
3P
20A
1P
20A
1P
30A
1P
30A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
20A
1P
200A
3P
200A
3P
1,2,3
SW #23 (FDR A1)
7,8,94,5,6 10,11,12
T907
225KVA
208Y/120V
T959
112.5KVA
208Y/120V
7,9,11
38,40,42
1,3,5 31,33,35
13,15,172,4,6 8,10,12 14,16,18 20,22,24
19,21
PANEL
P-3
125A
3P
37,39,41
A
M b a r v
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
E-701
J
M
A Y
H E
W
L
C
O L
E M
A N
E L E
C T
R I C
A L
S
C H
E D
U L E
S
C
H
A R
T N
E T
T
S X
G
B
E A
R D
C O
N S
T I N
S T
A L L
U
T I L I T
Y
C
O N
N E
C T
I O
R
S H
U
I P
B
D
E S
I G
N
S X
P A
F B
F
L
Panel : PANEL P1 (EXST)
BUILDING 992
Voltage: 480Y/277V, 3-PHASE Amps: 400 kAIC Rating:
SQUARE D TYPE NQ
Main: Breaker
BKR A/P
Description
VA Circuit # A B C Circuit # VA
Description
BKR A/P
30/3
Surge Protection
0 1 0 2 SPACE
0 3 0 4 SPACE
0 5 0 6 SPACE
40/3
AC Packaged Unit
6967 7 6967 8 SPACE
6967 9 6967 10 SPACE
6967 11 6967 12 SPACE
SPACE 13 14 SPACE
SPACE 15 16 SPACE
SPACE 17 18 SPACE
SPACE 19 20 SPACE
SPACE 21 22 SPACE
SPACE 23 24 SPACE
125/3 PANEL P3 27217 25 95381 26 68164 PANEL P2 VIA TRANSFORMER 300/3
27271 27 95435 28 68164
27271 29 95435 30 68164
Row Code Factor Name
Aph(VA) Bph(VA) Cph(VA)
Panel Summary
Total Connected Load
VA: 308060
(None)
34021 34089 34089
Amps:
370.6
2 Motor 9087 9087 9087
3 General 85205 85205 85205
Total Demand Load
VA: 308060
Total 128313 128381 128381
Amps:
370.6
Total CodeFactor Load
VA: 385075
Amps:
463.3
Total Design Load
VA: 385075
Totals
Amps:
463.3
Panel : PANEL P1 (NEW)
BUILDING 992
Voltage: 480Y/277V, 3-PHASE Amps: 1200 kAIC Rating: 30
Main: Breaker
BKR A/P
Description
VA Circuit # A B C Circuit # VA
Description
BKR A/P
30/3
Surge Protection
0 1 2614 2 2614 OMAX CHILLER 20/3
0 3 2614 4 2614
0 5 2614 6 2614
40/3
@@ AC Packaged Unit
6967 7 41607 8 34640 FURNACE 125/3
6967 9 41607 10 34640
6967 11 41607 12 34640
80/3
OMAX Pump
13333 13 17663 14 4330 IRON WORKER 30/3
13333 15 17663 16 4330
13333 17 17663 18 4330
15/2 OMAX CLOSED LOOP SYSTEM 1200 19 9860 20 8660 AIR COMPRESSOR 40/3
1200 21 9860 22 8660
SPACE 23 8660 24 8660
SPACE 25 26 SPACE
SPACE 27 28 SPACE
SPACE 29 30 SPACE
20/3 3-AXIS MILL 2771 31 2771 32 SPACE
2771 33 2771 34 SPACE
2771 35 2771 36 SPACE
125/3
@@ PANEL P3
27217 37 102217 38 75000
@@ PANEL P2 VIA TRANSFORMER
300/3
27271 39 102271 40 75000
27271 41 102271 42 75000
Row Code Factor Name
Aph(VA) Bph(VA) Cph(VA)
Panel Summary
Total Connected Load
VA: 535280
(None)
82285 82353 80853
Amps:
645.4
2 Motor 41565 41565 41565
3 General 93750 93750 93750
Total Demand Load
VA: 535280
Total 217600 217668 216168
Amps:
645.4
Total CodeFactor Load
VA: 651436
Amps:
785.4
Total Design Load
VA: 651436
Totals
Amps:
785.4
PANEL SCHEDULE LEGEND:
EXISTING LOAD BEING DEMOLISHED
NEW LOAD BEING ADDED TO EXISTING PANEL
EXISTING LOAD CONNECTED TO NEW PANEL
FEEDER SCHEDULE
TAG PHASE NEUTRAL GND CONDUIT CIRCUIT AMPACITY REMARKS
A 6 #500 2 #500 5" 1200A THREE PHASE 2 SETS
B 3 #8 1 #10 1" 40A THREE PHASE
C 3 #10 1 #10 1 #10 1" 30A THREE PHASE
D 3 #3 1 #8 1 1/4" 80A THREE PHASE
E 3 #12 1 #12 3/4" 20A THREE PHASE
F 3 #1 1 #6 2" 125A THREE PHASE
G 3 #10 1 #10 3/4" 30A THREE PHASE
H 2 #10 1 #10 3/4" 30A SINGLE PHASE
J 2 #12 1 #12 3/4" 15A/20A SINGLE PHASE
K 3 #4 1 #10 1" 60A THREE PHASE
L 3 #350 1 #4 4" 300A THREE PHASE EXISTING CONDUIT
M 2 #10 1 #10 1 #10 3/4"
(2) 20A
SINGLE PHASE
A
M b a r v
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
E I S
R A
N G
E
A
R C
H I T
E C
T E
N G
I N
E E
R
I N
S P
E C
T I O
N
S
E R
V I C
E S
F A
D
O n e i d a
T o t a l
I n t e g r a t e d
E n t e r p r i s e s
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
This is the start of the file's text. The full file is on GovTribe.