SOW_Attachment_1_-_Drawings_(adobe_version).pdf

PDF 222 KB Posted

Attached to
REMOVE/REPLACE CHILLER, BLDG 1270 Federal contract opportunity
Solicitation number
FA2517-17-Q-5016
Issued by
Department of the Air Force Space Command

View the file

Other files for this federal contract opportunity

Other files attached to REMOVE/REPLACE CHILLER, BLDG 1270, newest first.
File Type Posted
QA__4__Replace_Bldg_1270_Chiller.docx DOCX document
Q&A__3_-_Remove_Replace_Chiller_Bldg_1270.pdf PDF
TDKA141108-SOW_FINAL.docx DOCX document
Q&A_2.docx DOCX document
Question_&_Answers_B1270.docx DOCX document
Amendment_01.docx DOCX document
SOW_Attachment_1_-_Drawing.dwg DWG drawing
Combined_Synopsis-Remove-Replace_Chiller,_Bldg_1270.pdf PDF
SOW_Attachment_2_-_Generic_Chiller_Layout.pdf PDF
Attachment_2_Price_Template_Remove-Replace_Chiller_Bldg_1270.xlsx XLSX spreadsheet
Attachment_1_-_Remove-Replace_Chiller,_Bldg_1270_SOW_FINAL.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHILLED WATER PIPING SCHEMATIC

NO SCALE

SUCTION DIFFUSER

STRAINER WITH

BLOWDOWN VALVE

GAUGE AND GAUGE COCK (TYP)

PUMP SKID/BASE

VIBRATION ISOLATION

CONCRETE PAD

FLEX CONNECTOR (TYP)

CHECK VALVE (TYP)

ISOLATION VALVE (TYP)

ISOLATION

VALVE (TYP)

PIPE STAND

SUPPORT

FLOOR

PS PS

AUTOMATIC

AIR VENT

(TYP)

TO SYSTEM

TS

TS

CWR/HWR

CWS/HWS

CWS/HWS

4"

4"

4"

3"

4"

CWS

CWR

NORMALLY OPEN WINTER,

CLOSED SUMMER

3" 4"

3" 4"

3"

CIRCULATING PUMP

1"

B-2

BDD

BDD

4"

NORMALLY CLOSED WINTER,

OPEN SUMMER

DEMOLISH DUAL WATER PUMPS (P1, P2, AND

P3). CONTRACTOR SHALL DEMOLISH PUMPS

ONE AT A TIME TO FACILITATE REMOVAL

WITHOUT UNDUE DOWNTIME TO FACILITY.

PROVIDE ALL ACCESSORIES AS REQUIRED AND

SHOWN.

P1

P2

P3

PIPING TO

CHILLER, CH-1

PIPING UNDER

GRADE

GENERAL NOTES:

1. THE FOLLOWING NOTES APPLY TO ALL

MECHANICAL DRAWINGS TO THE EXTENT

APPLICABLE.

2. NOT ALL DUCTWORK, OFFSETS, PIPING, EQUIPMENT

AND ACCESSORIES ARE NECESSARILY SHOWN ON

THESE DRAWINGS. REFER TO ALL OTHER PLANS,

SECTIONS, DETAILS, SCHEDULES, CONTROL

DRAWINGS AND SPECIFICATIONS FOR COMPLETE

SYSTEM REQUIREMENTS.

3. COORDINATE EXACT LOCATIONS OF ROOF, WALL,

AND FLOOR PENETRATIONS WITH GENERAL

CONTRACTOR.

4. MANY AREAS OF CONSTRUCTION WILL BE VERY

CONGESTED. INSTALLATION OF MATERIALS AND

EQUIPMENT SHALL BE COORDINATED WITH ALL

OTHER TRADES AND EXISTING CONDITIONS TO

ENSURE THAT THERE IS ADEQUATE ROOM FOR

ALL OTHER MATERIALS AND EQUIPMENT TO BE

INSTALLED UNDER THIS CONTRACT. INSTALLATION

OF MATERIALS AND EQUIPMENT WHICH DOES NOT

ALLOW FOR INSTALLATION OF REMAINING

MATERIALS AND EQUIPMENT WILL BE REMOVED

AND RELOCATED AT NO COST TO THE

GOVERNMENT.

5. COORDINATE FINAL LOCATION OF DUCTWORK,

PIPING, DIFFUSERS, EQUIPMENT, ETC. WITH ALL

OTHER TRADES AND EXISTING CONDITIONS BEFORE

FABRICATION OR INSTALLATION.

6. CONTRACTOR SHALL PROVIDE ALL REQUIRED

OFFSETS, TRANSITIONS, AND FITTINGS FOR

DUCTWORK AND PIPING TO COMPLETE THE

SYSTEMS.

7. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS PRIOR TO ORDERING OR FABRICATION

OF MATERIAL OR PERFORMING ANY NEW WORK.

DEVIATIONS FROM CONDITIONS SHOWN IN THESE

PLANS SHALL BE REPORTED TO THE CO/COR

IMMEDIATELY AND NO WORK SHALL BE

PERFORMED IN THIS AREA UNTIL A RESOLUTION

HAS BEEN ESTABLISHED. SITE CONDITIONS

DIFFERING FROM THOSE SHOWN ON THESE PLANS

WILL NOT GENERALLY BE CONSIDERED A BASIS

FOR CONTRACT MODIFICATIONS AS THE

CONTRACTOR SHALL TAKE INTO ACCOUNT WORST

CASE SITE CONDITIONS WHEREVER POSSIBLE.

8. DUCTWORK MAINS ARE GENERALLY INTENDED TO

RUN BELOW THE STRUCTURE WITH INDIVIDUAL

BRANCHES ROUTED UP THROUGH AND IN

BETWEEN ROOF STRUCTURE MEMBERS. DUCTWORK

MAINS ARE LAID OUT AND INTENDED TO RUN

BETWEEN LIGHT FIXTURE SPACING, NOT ABOVE

LIGHTS UNLESS NO OTHER ROUTING IS POSSIBLE.

ALL PIPING IS LAID OUT AND INTENDED TO RUN

UP THROUGH AND BETWEEN STRUCTURAL

MEMBERS AND TO STAY ABOVE DUCT ROUTING.

COORDINATE WITH EXISTING CONDITIONS.

9. ALL PENETRATIONS THROUGH FIRE/SMOKE RATED

CONSTRUCTION SHALL BE SEALED WITH A FIRE

RATED CAULK EQUAL TO OR EXCEEDING THE

CONSTRUCTION FIRE RATING.

10. COORDINATE ROUTING OF DUCTWORK AND PIPING

WITH ELECTRICAL EQUIPMENT. DO NOT ROUTE

DUCTWORK AND PIPING DIRECTLY OVER THE TOP

OF ELECTRICAL PANELBOARDS AND SWITCHBOARDS.

11. ALL PRODUCTS LISTED ON THE SCHEDULE SHEETS

ARE TO BE CONSIDERED BASIS OF DESIGN TO

ESTABLISH MINIMUM & MAXIMUM PERFORMANCE

CHARACTERISTICS. OTHER MATERIALS WILL BE

ALLOWED AS SUBSTITUTIONS PROVIDED THEY MEET

OR EXCEED ALL PERFORMANCE CHARACTERISTICS

LISTED THEREIN AND MEET OR EXCEED ALL

SPECIFICATION REQUIREMENTS.

12. ALL SCHEDULED VALUES ARE FOR 6172 FT.

ELEVATION UNLESS INDICATED OTHERWISE.

13. ALL DEVICES AND EQUIPMENT TO BE SALVAGED

OR RE-USED MUST BE CLEANED AND ALL

DAMAGED PARTS REPAIRED OR REPLACED.

14. PROVIDE PRODUCT DATA SUBMITTALS FOR ALL

EQUIPMENT ALONG WITH OPERATION AND

MAINTENANCE MANUALS. INCLUDE MANUFACTURER'S

MODEL NUMBER, SERIAL NUMBER, ELECTRICAL

CHARACTERISTICS, WEIGHT, CAPACITIES, ETC.

15. CONTRACTOR SHALL PROVIDE WORK IN PHASES

AS REQUIRED BY GOVERNMENT WHILE MINIMIZING

POTENTIAL WORK DELAYS.

16. CONTROL DEVICES SHALL COMMUNICATE OVER

BACNET COMMUNICATION PROTOCOL.

17. CONSTRUCTION DOCUMENTS CONSIST OF THESE

DRAWINGS, A SEPARATE BOOK OF SPECIFICATIONS,

AND THE STATEMENT OF WORK (SOW). THE

DRAWINGS, SPECIFICATIONS, AND STATEMENT OF

WORK (SOW) ARE COMPLEMENTARY, NONE ARE

MEANT TO STAND ALONE FOR ANY PORTION OF

THE WORK DESCRIBED HEREIN. IF ANY

DISCREPANCY EXISTS, CONTACT THE CO/COR FOR

CLARIFICATION BEFORE PROCEEDING WITH

CONSTRUCTION.

GENERAL NOTES:

1. THE FOLLOWING NOTES APPLY TO ALL

MECHANICAL DRAWINGS TO THE EXTENT

APPLICABLE.

2. NOT ALL DUCTWORK, OFFSETS, PIPING, EQUIPMENT

AND ACCESSORIES ARE NECESSARILY SHOWN ON

THESE DRAWINGS. REFER TO ALL OTHER PLANS,

SECTIONS, DETAILS, SCHEDULES, CONTROL

DRAWINGS AND SPECIFICATIONS FOR COMPLETE

SYSTEM REQUIREMENTS.

3. COORDINATE EXACT LOCATIONS OF ROOF, WALL,

AND FLOOR PENETRATIONS WITH GENERAL

CONTRACTOR.

4. MANY AREAS OF CONSTRUCTION WILL BE VERY

CONGESTED. INSTALLATION OF MATERIALS AND

EQUIPMENT SHALL BE COORDINATED WITH ALL

OTHER TRADES AND EXISTING CONDITIONS TO

ENSURE THAT THERE IS ADEQUATE ROOM FOR

ALL OTHER MATERIALS AND EQUIPMENT TO BE

INSTALLED UNDER THIS CONTRACT. INSTALLATION

OF MATERIALS AND EQUIPMENT WHICH DOES NOT

ALLOW FOR INSTALLATION OF REMAINING

MATERIALS AND EQUIPMENT WILL BE REMOVED

AND RELOCATED AT NO COST TO THE

GOVERNMENT.

5. COORDINATE FINAL LOCATION OF DUCTWORK,

PIPING, DIFFUSERS, EQUIPMENT, ETC. WITH ALL

OTHER TRADES AND EXISTING CONDITIONS BEFORE

FABRICATION OR INSTALLATION.

6. CONTRACTOR SHALL PROVIDE ALL REQUIRED

OFFSETS, TRANSITIONS, AND FITTINGS FOR

DUCTWORK AND PIPING TO COMPLETE THE

SYSTEMS.

7. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS PRIOR TO ORDERING OR FABRICATION

OF MATERIAL OR PERFORMING ANY NEW WORK.

DEVIATIONS FROM CONDITIONS SHOWN IN THESE

PLANS SHALL BE REPORTED TO THE CO/COR

IMMEDIATELY AND NO WORK SHALL BE

PERFORMED IN THIS AREA UNTIL A RESOLUTION

HAS BEEN ESTABLISHED. SITE CONDITIONS

DIFFERING FROM THOSE SHOWN ON THESE PLANS

WILL NOT GENERALLY BE CONSIDERED A BASIS

FOR CONTRACT MODIFICATIONS AS THE

CONTRACTOR SHALL TAKE INTO ACCOUNT WORST

CASE SITE CONDITIONS WHEREVER POSSIBLE.

8. DUCTWORK MAINS ARE GENERALLY INTENDED TO

RUN BELOW THE STRUCTURE WITH INDIVIDUAL

BRANCHES ROUTED UP THROUGH AND IN

BETWEEN ROOF STRUCTURE MEMBERS. DUCTWORK

MAINS ARE LAID OUT AND INTENDED TO RUN

BETWEEN LIGHT FIXTURE SPACING, NOT ABOVE

LIGHTS UNLESS NO OTHER ROUTING IS POSSIBLE.

ALL PIPING IS LAID OUT AND INTENDED TO RUN

UP THROUGH AND BETWEEN STRUCTURAL

MEMBERS AND TO STAY ABOVE DUCT ROUTING.

COORDINATE WITH EXISTING CONDITIONS.

9. ALL PENETRATIONS THROUGH FIRE/SMOKE RATED

CONSTRUCTION SHALL BE SEALED WITH A FIRE

RATED CAULK EQUAL TO OR EXCEEDING THE

CONSTRUCTION FIRE RATING.

10. COORDINATE ROUTING OF DUCTWORK AND PIPING

WITH ELECTRICAL EQUIPMENT. DO NOT ROUTE

DUCTWORK AND PIPING DIRECTLY OVER THE TOP

OF ELECTRICAL PANELBOARDS AND SWITCHBOARDS.

11. ALL PRODUCTS LISTED ON THE SCHEDULE SHEETS

ARE TO BE CONSIDERED BASIS OF DESIGN TO

ESTABLISH MINIMUM & MAXIMUM PERFORMANCE

CHARACTERISTICS. OTHER MATERIALS WILL BE

ALLOWED AS SUBSTITUTIONS PROVIDED THEY MEET

OR EXCEED ALL PERFORMANCE CHARACTERISTICS

LISTED THEREIN AND MEET OR EXCEED ALL

SPECIFICATION REQUIREMENTS.

12. ALL SCHEDULED VALUES ARE FOR 6172 FT.

ELEVATION UNLESS INDICATED OTHERWISE.

13. ALL DEVICES AND EQUIPMENT TO BE SALVAGED

OR RE-USED MUST BE CLEANED AND ALL

DAMAGED PARTS REPAIRED OR REPLACED.

14. PROVIDE PRODUCT DATA SUBMITTALS FOR ALL

EQUIPMENT ALONG WITH OPERATION AND

MAINTENANCE MANUALS. INCLUDE MANUFACTURER'S

MODEL NUMBER, SERIAL NUMBER, ELECTRICAL

CHARACTERISTICS, WEIGHT, CAPACITIES, ETC.

15. CONTRACTOR SHALL PROVIDE WORK IN PHASES

AS REQUIRED BY GOVERNMENT WHILE MINIMIZING

POTENTIAL WORK DELAYS.

16. CONTROL DEVICES SHALL COMMUNICATE OVER

BACNET COMMUNICATION PROTOCOL.

17. CONSTRUCTION DOCUMENTS CONSIST OF THESE

DRAWINGS, A SEPARATE BOOK OF SPECIFICATIONS,

AND THE STATEMENT OF WORK (SOW). THE

DRAWINGS, SPECIFICATIONS, AND STATEMENT OF

WORK (SOW) ARE COMPLEMENTARY, NONE ARE

MEANT TO STAND ALONE FOR ANY PORTION OF

THE WORK DESCRIBED HEREIN. IF ANY

DISCREPANCY EXISTS, CONTACT THE CO/COR FOR

CLARIFICATION BEFORE PROCEEDING WITH

CONSTRUCTION.

TONS

CAPACITY FAN

QTY HP FLA

6.61.56

LRA

RLA

50.2418.8

MAX.

FT.

WPDGPM

LWT

°F

MOTOR DATA

COMPRESSOR

QTY

1-755.9TRANE CGAM060A2**3AXB2A1CH-1

MARK EWT

54.5

°F

AIR COOLED LIQUID CHILLER SCHEDULE

REMARKS

1. CAPACITY BASED ON 6172 FT. ELEVATION, 35% PROPYLENE GLYCOL, AND 95°F AMBIENT.

2. AHRI RATED WITH CAPACITY OF MINIMUM 57.8 TONS.

3. ELECTRICAL DATA FOR EACH FAN OR COMPRESSOR.

4. UNIT SHALL HAVE TWO CIRCUITS, WITH 4 CAPACITY STEPS. CIRCUITS SHALL BE EQUALLY

SIZED.

5. 208 VOLT 3 PHASE 60 HERTZ UNIT.

6. 10.40EER FULL LOAD AND15.34EER IPLV AT AHRI CONDITIONS.

7. R-410a REFRIGERANT.

AND MODEL #

MANUFACTURER

MARK

PUMP SCHEDULE

ELEC. CHAR.REMARKS

208V/3Ø/60

MIN.

EFF.HPFT.

HD.GPM

74 125 7.5 61

SERVICE

P1,P2,P3

MFR.

WATER

CHILL/HOTBASE

MOUNTED

TYPEMODEL NO.

1,2PACO -

1. 35% PROPYLENE GLYCOL.

2. PROVIDE WITH SUCTION DIFFUSER. REFER TO PROJECT SPECIFICATIONS.

RPM

°F

TEMP

PSIG

PRESSURE

44/180

CWR/HWR

CWS/HWS

CWS/HWS

4"

4"

4"

3"

4"

CWS

CWR

NORMALLY OPEN WINTER,

CLOSED SUMMER

3" 4"

3" 4"

3"

CIRCULATING PUMP

1"

B-2

BDD

BDD

4"

NORMALLY CLOSED WINTER,

OPEN SUMMER

PIPING TO

CHILLER, CH-1

PIPING UNDER

GRADE

P1

P2

P3

L L

CH-1

4" CHILLED WATER PIPING

(HEAT TRACE AND

INSULATED WITH METAL

JACKET)

PROVIDE NEW PIPING AND ACCESSORIES

TO INCLUDE, BUT NOT BE LIMITED TO,

STRAINER, VIBRATION ISOLATORS,

MECHANICAL GAUGES, BALANCING VALVE,

BYPASS VALVE, P-T PORTS, ETC

4" CHILLED WATER PIPING

(HEAT TRACE AND

INSULATED WITH METAL

JACKET)

MAINTAIN MANUFACTURERS CLEARANCES AS A

MINIMUM

SUCTION DIFFUSER

STRAINER WITH

BLOWDOWN VALVE

GAUGE AND GAUGE COCK (TYP)

PUMP SKID/BASE

VIBRATION ISOLATION

CONCRETE PAD

FLEX CONNECTOR (TYP)

CHECK VALVE (TYP)

ISOLATION VALVE (TYP)

ISOLATION

VALVE (TYP)

PIPE STAND

SUPPORT

FLOOR

PS PS

AUTOMATIC

AIR VENT

(TYP)

TO SYSTEM

TS

TS

GENERAL NOTES:

1. THE FOLLOWING NOTES APPLY TO ALL

MECHANICAL DRAWINGS TO THE EXTENT

APPLICABLE.

2. NOT ALL DUCTWORK, OFFSETS, PIPING, EQUIPMENT

AND ACCESSORIES ARE NECESSARILY SHOWN ON

THESE DRAWINGS. REFER TO ALL OTHER PLANS,

SECTIONS, DETAILS, SCHEDULES, CONTROL

DRAWINGS AND SPECIFICATIONS FOR COMPLETE

SYSTEM REQUIREMENTS.

3. COORDINATE EXACT LOCATIONS OF ROOF, WALL,

AND FLOOR PENETRATIONS WITH GENERAL

CONTRACTOR.

4. MANY AREAS OF CONSTRUCTION WILL BE VERY

CONGESTED. INSTALLATION OF MATERIALS AND

EQUIPMENT SHALL BE COORDINATED WITH ALL

OTHER TRADES AND EXISTING CONDITIONS TO

ENSURE THAT THERE IS ADEQUATE ROOM FOR

ALL OTHER MATERIALS AND EQUIPMENT TO BE

INSTALLED UNDER THIS CONTRACT. INSTALLATION

OF MATERIALS AND EQUIPMENT WHICH DOES NOT

ALLOW FOR INSTALLATION OF REMAINING

MATERIALS AND EQUIPMENT WILL BE REMOVED

AND RELOCATED AT NO COST TO THE

GOVERNMENT.

5. COORDINATE FINAL LOCATION OF DUCTWORK,

PIPING, DIFFUSERS, EQUIPMENT, ETC. WITH ALL

OTHER TRADES AND EXISTING CONDITIONS BEFORE

FABRICATION OR INSTALLATION.

6. CONTRACTOR SHALL PROVIDE ALL REQUIRED

OFFSETS, TRANSITIONS, AND FITTINGS FOR

DUCTWORK AND PIPING TO COMPLETE THE

SYSTEMS.

7. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS PRIOR TO ORDERING OR FABRICATION

OF MATERIAL OR PERFORMING ANY NEW WORK.

DEVIATIONS FROM CONDITIONS SHOWN IN THESE

PLANS SHALL BE REPORTED TO THE CO/COR

IMMEDIATELY AND NO WORK SHALL BE

PERFORMED IN THIS AREA UNTIL A RESOLUTION

HAS BEEN ESTABLISHED. SITE CONDITIONS

DIFFERING FROM THOSE SHOWN ON THESE PLANS

WILL NOT GENERALLY BE CONSIDERED A BASIS

FOR CONTRACT MODIFICATIONS AS THE

CONTRACTOR SHALL TAKE INTO ACCOUNT WORST

CASE SITE CONDITIONS WHEREVER POSSIBLE.

8. DUCTWORK MAINS ARE GENERALLY INTENDED TO

RUN BELOW THE STRUCTURE WITH INDIVIDUAL

BRANCHES ROUTED UP THROUGH AND IN

BETWEEN ROOF STRUCTURE MEMBERS. DUCTWORK

MAINS ARE LAID OUT AND INTENDED TO RUN

BETWEEN LIGHT FIXTURE SPACING, NOT ABOVE

LIGHTS UNLESS NO OTHER ROUTING IS POSSIBLE.

ALL PIPING IS LAID OUT AND INTENDED TO RUN

UP THROUGH AND BETWEEN STRUCTURAL

MEMBERS AND TO STAY ABOVE DUCT ROUTING.

COORDINATE WITH EXISTING CONDITIONS.

9. ALL PENETRATIONS THROUGH FIRE/SMOKE RATED

CONSTRUCTION SHALL BE SEALED WITH A FIRE

RATED CAULK EQUAL TO OR EXCEEDING THE

CONSTRUCTION FIRE RATING.

10. COORDINATE ROUTING OF DUCTWORK AND PIPING

WITH ELECTRICAL EQUIPMENT. DO NOT ROUTE

DUCTWORK AND PIPING DIRECTLY OVER THE TOP

OF ELECTRICAL PANELBOARDS AND SWITCHBOARDS.

11. ALL PRODUCTS LISTED ON THE SCHEDULE SHEETS

ARE TO BE CONSIDERED BASIS OF DESIGN TO

ESTABLISH MINIMUM & MAXIMUM PERFORMANCE

CHARACTERISTICS. OTHER MATERIALS WILL BE

ALLOWED AS SUBSTITUTIONS PROVIDED THEY MEET

OR EXCEED ALL PERFORMANCE CHARACTERISTICS

LISTED THEREIN AND MEET OR EXCEED ALL

SPECIFICATION REQUIREMENTS.

12. ALL SCHEDULED VALUES ARE FOR 6172 FT.

ELEVATION UNLESS INDICATED OTHERWISE.

13. ALL DEVICES AND EQUIPMENT TO BE SALVAGED

OR RE-USED MUST BE CLEANED AND ALL

DAMAGED PARTS REPAIRED OR REPLACED.

14. PROVIDE PRODUCT DATA SUBMITTALS FOR ALL

EQUIPMENT ALONG WITH OPERATION AND

MAINTENANCE MANUALS. INCLUDE MANUFACTURER'S

MODEL NUMBER, SERIAL NUMBER, ELECTRICAL

CHARACTERISTICS, WEIGHT, CAPACITIES, ETC.

15. CONTRACTOR SHALL PROVIDE WORK IN PHASES

AS REQUIRED BY GOVERNMENT WHILE MINIMIZING

POTENTIAL WORK DELAYS.

16. CONTROL DEVICES SHALL COMMUNICATE OVER

BACNET COMMUNICATION PROTOCOL.

17. CONSTRUCTION DOCUMENTS CONSIST OF THESE

DRAWINGS, A SEPARATE BOOK OF SPECIFICATIONS,

AND THE STATEMENT OF WORK (SOW). THE

DRAWINGS, SPECIFICATIONS, AND STATEMENT OF

WORK (SOW) ARE COMPLEMENTARY, NONE ARE

MEANT TO STAND ALONE FOR ANY PORTION OF

THE WORK DESCRIBED HEREIN. IF ANY

DISCREPANCY EXISTS, CONTACT THE CO/COR FOR

CLARIFICATION BEFORE PROCEEDING WITH

CONSTRUCTION.

D

ES

C R

IP

TI

O N

M A R K

D A

TE

SI

ZE

D A

TE

A N

SI

D

M

A R

R

EP

A

IR

C

H

IL

LE

R B

W O R K P

LA

N

M101

TD

K A st S pa ce W in g

P et er so n

A ir F or ce B as e

C ol or ad o Sp ri ng s, C

O

C

ES

C

EN

M

PROFESSIONAL SEAL

EN

SS

RE

D

AP

PDAN ER

G

EN

S R

T

HT

DEMOLITION MECHANICAL ROOM

SCALE: N.T.S.M101

1 NEW WORK MECHANICAL ROOM

SCALE: N.T.S.M101

DEMOLITION MECHANICAL YARD

SCALE: N.T.S.M101

2 NEW WORK MECHANICAL YARD

SCALE: N.T.S.M101

TYPICAL PUMP DETAIL

SCALE: N.T.S.M101

Model
Layout1