Amendment_2.docx

DOCX document 12 KB Posted

Attached to
Peterson AFB Fire extinguisher maintenance Federal contract opportunity
Solicitation number
fa251717q5005
Issued by
Department of the Air Force Space Command

About this file

Amendment 2; re-post questions/answers

View the file

Other files for this federal contract opportunity

Other files attached to Peterson AFB Fire extinguisher maintenance, newest first.
File Type Posted
Answers_To_questions.docx DOCX document
Attch_2_Price_Template_amended.xlsx XLSX spreadsheet
UPDATED_PETERSON_Nov_SS.XLSX XLSX spreadsheet
Attch_2_Price_Template_amended.xlsx XLSX spreadsheet
Attch_4_Terms_and_Conditions.docx DOCX document
Attch_3_Contractor_Submittal_Form.docx DOCX document
Attch_2_Price_Template.xlsx XLSX spreadsheet
Attch_1_PWS.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Below Fire responses to your questions,

- Section 1.3.4.1.3. It states that the government is going to provide the contractor with Halon 1211 and that we cannot take Halon from our own stock.

Answer-Correct. The AF will provide a Halon tank. We are not allowed to purchase Halon outside DLA channels

- How will PAFB go about supplying / providing us the Halon? Will they deliver the cylinders we need to capture the chemical and also cylinders that contain the new chemical?

Answer-The AF will not deliver the Halon Tank. The tank is located at bldg.. 218 on PAFB. It is the same cylinder that is used for recovery and filling.

- In order to perform the hydrostatic testing/6yr maintenance on the Halon Extinguishers, chemical in tanks must be captured by transferring it to sealed cylinder. Then once the tanks have been hydro testing & dry, we transfer the chemical that was captured back in, plus have to add approximately 20lbs - 30lbs of new Halon 1211. (20 - 30 lbs. on average is typically lost during transfer of high pressure extinguishers).

Answer-Correct

- Section 1.3.4.1.2 - Is PAFB going to provide temporary wheeled Halon extinguishers, so that the existing wheeled extinguishers can be removed for service?

Answer-We have ample spare extinguishers to allow the contractor to service ones needing service. Not all extinguishers can be removed from service at the same time