Exhibit F - Test and Balance Report.pdf
PDF 1 MB Posted
- Attached to
- Design-Build Miscellaneous Repairs Federal contract opportunity
- Solicitation number
- 12505B21R0002
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign In Sheets.pdf | ||
| SF-30 Amendment 01.pdf | ||
| Wage Determination.pdf | ||
| ARS-372.pdf | ||
| ARS Facilities Design Standards.pdf | ||
| Exhibit A - Drawings for Recent Work.pdf | ||
| Exhibit B - Specifications for Recent Work.pdf | ||
| Exhibit E - Electrical O-M Manual.pdf | ||
| ARS-371.pdf | ||
| SF-1442 with Clauses and Provisions.pdf | ||
| Statement of Work.pdf | ||
| Exhibit C - Make Up Air Unit O-M Manual Part 1.pdf | ||
| Exhibit D - Make Up Air Unit O-M Manual Part 2.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Corporate Office: SLD Division - St. Louis Area:
249 Cass Avenue 7 Eagle Center, Suite A
Mt. Clemens, MI 48043 O'Fallon, IL 62269
Email: bopenlander@RB-Construction.com
TO:
WE ARE SENDING: x Attached Under separate cover via
Letter Prints Drawings
Report Specifications Analytical Results
Sketch Change Order
COPIES DATE DESCRIPTION
and in accordance with the Jim Phelps Landscape, Inc. proposal dated 06/10/13.
COPY TO: SIGNED:
Action Submittal 36 Section 23 05 93 SD-06 Test Reports-HVAC Test & Balance Report-11JUL19
The information enclosed has been reviewed by RB Construction and found to be in accordance with the Contract Documents or comments/corrections noted.
Project Manager
LETTER OF TRANSMITTAL
Date: 07/11/19 Project No.: 18741
Contract: 1232SC18C0068
Livestock Behavior Research Unit (LBRU)
Animal Holding Area
Project:
Telephone: (586)264-9478
NO.
United States Department of Agriculture Agricultural Research Service
Mindy Leach, Engineering Project Manager
Eastern Business Service Center
1815 N. University St.
Peoria, IL 61604
Phone: 309-681-6577
11-Jul-19 01 mailto:bopenlander@RB-Construction.com
North Mechanical Contracting, Inc.
This Submittal Has Been Reviewed For General Compliance With The Contract Documents Produced
Signature:_____________________________________________
NORTH MECHANICAL Group No. 230593
CONTRACTING, INC. Submittal No. 230593-01
2627 N. EMERSON AVE. Thursday, July 11, 2019
INDIANAPOLIS, IN 46218 Page 1 of 1
(317) 610-2627
Submittal Item Group Desc.: Testing, Adjusting and Balancing for HVAC Start Date: 2019-07-11
Group Completion: Req Comp Date: 2019-07-18
Job Number: L261 Received:
Job Name: USDA LBRU Animal Holding Area Forwarded:
Reference: Sent 2019-07-11
Description: Product Data Returned:
Drawing Date:
Status: Sent Vendor: North Mechanical Contracting
Revision: 0 1 -1
Drawing #:
Phase/CC/CT/Acct:///
Notes: 3.3 DALT Procedures
Reviewer
Comments: North Mechanical
Contracting, Inc. Has
Reviewed This Submittal For
General Conformance With
The Design Concept And
Contract Documents.
colleen.taylor Brad
CERTIFIED TEST, ADJUST, and BALANCE REPORT
Date: 6-20-19
PROJECT:
Co. Road 750 North
West Lafayette, Indiana
Engineer: USDA
HVAC
Contractor: North Mechanical
3313 Imperial Parkway
Lafayette, Indiana 47909
NEBB TAB FIRM: BLEDSOE ENVIRONMENTAL LLC
ADDRESS: 1400 Sunday Drive, Indianapolis, IN. 46217
PHONE: ( 317 ) 821 - 4750
Certification NO. 2956
LBRU Animal Holding Area
Project:
Scope:
Pages Report Title 1 Table of Contents 2 Report Certification's 3-5 Instrument Calibration 6 Balance Procedures 7-8 Summary 9
MAU 10-13
Exhaust 14-15
@ Atmosphere PLEAT Pleated Filter BSW Bird Screen Wire PF Power Factor BHP Brake Horse Power R/A Return Air DD Direct Drive RM Room EFF Efficiency Factor RVA Rotating Vane Anemometer EF Exhaust Fan SETPT Set point HZ Hertz TCC Temperature Control Contractor NA Not Applicable TA Throwaway Filters NS Not Specified VFD Variable Frequency Drive
OSA Outside Air
Table of Contents
LBRU Animal Holding Area
Air Test & Balance
MECHANICAL LEGEND
Bledsoe Environmental 1400 Sunday Drive
Indianapolis, IN. 46217 P: (317) 821-4750
INSTRUMENT CALIBRATION REPORT
PROJECT:
Instrument Model Serial # APPLICATION DATES OF USE CAL. DATE
Shortridge ADM 870C M91954 Direct Reading CFM 1/16/2019
Fluke 373 38300334 Volts/Amps 1/8/2019
Shimpo DT-205L C066B0039 Rotations 1/11/2019
Dwyer SAH 01PXJN Air Flow Hood 12/20/2018
Alnor HM680 70534165 Hydronic Pressure 1/31/2019
Dwyer 490W-6HKIT 18PWPO4142 Hydronic Pressure 0-200PSIG 1/7/2019
Dwyer 490W-6HKIT 18PWPW4156 Hydronic Pressure 0-200PSIG 1/7/2019
Dwyer 490W-6HKIT 18PWP04117 Hydronic Pressure 0-50PSIG 1/7/2019
Dwyer 490W-6HKIT 18PWP04135 Hydronic Pressure 0-50PSIG 1/7/2019
REMARKS:
NEBB TAB FIRM: Bledsoe Environmental LLC
TAB SUPERVISOR: John Zeilinga REG. NO.: 2956
NA
NA
NA
NA
NA
HYDRONIC
NA
LBRU Animal Holding Area
AIR
6/20/2019
6/20/2019
Constant Volume Balance Procedures
1. Verify the construction team has completed responsibilities for system installation and startup.
2. Check unit is free of debris and final connections are complete.
3. Confirm that the correct air filters have been installed.
4. Check all mains and branch ducts to ensure the system complete.
5. Verify that all manual branch and outlet volume dampers are locked 100% open.
6. Check damper operation; fully open, fully closed, start unit with dampers in the fully open position.
7. Check power to unit, compare to information listed on motor.
8. Check for correct fan rotation.
9. Measure fan RPM and compare to design RPM.
10. Set the unit to max speed; record motor data ,volts, amps, and fan RPM.
11. Check for unusual noises indicating mechanical malfunction.
12. Verify that the temperature control contractor's sequence of operation is controlling unit.
13. Set unit to deliver 110% of design airflow and record fan speed.
14. Set OSA to design airflow, record damper position and control set point.
15. Record the outlet airflow of each zone.
16. Proportionally balance the highest zone to the system average.
17. Proportionally balance all zones to ±10% of design and record test data.
18. At the conclusion of all inlet and outlet balancing, re-adjust the AHU minimum outside air ventilation rate.
19. Simulate loaded filters, measure the pressure drop across the air filters and adjust the temporary blockage to meet specified requirements.
20. Set unit to design airflow and record final measurements; OSA, fan speed, volts, amps, and static profile.
21. After the supply, return, and exhaust systems are properly balanced, adjust OSA to 100%, traverse supply air fan, compare to design airflow of unit.
22. In each condition, verify that the system is operating in compliance with specified requirements.
23. Measure building static pressure and compare to specified requirements.
LBRU Animal Holding Area
System:
Project:
MAU-1
BALANCE PROCEDURES
Exhaust System Balance Procedures
1. Check unit is free of debris, and final connections are complete.
2. Check all mains and branch ducts to ensure system is complete.
3. Verify that all manual branch and outlet volume dampers are locked 100% open.
4. Check damper operation, verify dampers are in the full open position .
5. Check power to unit, compare to information listed on motor.
6. Check for correct fan rotation.
7. Measure fan RPM and compare to design RPM.
8. Set unit to max speed; record motor data ,volts, amps, and fan RPM.
9. Check for unusual noises indicating mechanical malfunction.
10. Set unit to deliver 110% of design airflow and record fan speed.
11. Record outlet airflow of each zone.
12. Proportionally balance the highest zone to the system average.
13. Proportionally balance all zones to ±10% of design and record test data.
14. Record all test data; motor data, volts, amps, fan RPM, and the unit static profile.
BALANCE PROCEDURES
Project: LBRU Animal Holding Area
System: Exhaust Fans
1400 Sunday Drive
Indianapolis, IN. 46217
(317) 821-4750 bledsoebalance@comcast.net
Project:
Date:
Tech: John Zeilinga
Summary
LBRU Animal Holding Area
System(s) Description: This project consist of one new make up air unit located outside on grade, serving the research room. This unit is 100% outside air, with a gas fired heater. Three new exhaust fans located in the corridor serving the research room and feed room.
Testing Results: See the report pages for settings and measurements taken.
Remedial Conclusion:
mailto:bledsoebalance@comcast.net
AIR APPARATUS REPORT
Project: Systems/Unit: MAU-1
Location: Serving:
Make Make/Frame NS
Model No. Design H.P./RPM 1765
Type/Size FC Actual HP Serial Number Volts/Phase/Hertz 230 1 60
Arr./Class DWDI F.L. Amps/S.F. 1.15 Discharge Make Sheave
Make Sheave Sheave Diam/Bore 2VP42 x 1 1/8" Sheave Diam/Bore 2BK90H x Sheave ℄ Distance
No. Belts/make/size Sheave Oper Diam.
No. Filters/type/size
TEST DATA DESIGN TEST DATA DESIGN
Total CFM (l/s) 4000 Discharge S.P.
Total Outlet CFM 4000 Suction S.P.
Fan RPM 1100 Reheat Coil ΔS.P.
Total S.P. Cooling Coil ΔS.P.
External S.P. 1.5" Preheat Coil ΔS.P.
Motor Volts 230 236 Filter ΔS.P.
Motor Amps 8.6 1.4
Outside Air CFM 4000 O/S Air Damp. Position
Return Air CFM NA Ret. Air Damp. Position
VFD
REMARKS: * At the limit of the belt/motor adjustment.
TEST DATE: 6-20-19
READINGS BY: John
LBRU Animal Holding Area
PRP
TH 90 CCW
3516953
3T-IBT-600-300-300-G18
21"
Middle *2 Bando BX59
6 WA 16x20x2
8.6
Research
PRP
UNIT DATA MOTOR DATA
18X18
On Grade
WestinghouseThermtek
ACTUAL
NA
.41"
.22"
ACTUAL
.22"
.19"
BLEDSOE ENVIRONMENTAL LLC
1400 Sunday Drive, Indianapolis, IN. 46217
H 1 3/16"
.08"
100% open
NA
53 Hz
PROJECT: SYSTEM / UNIT:
⁄ F ilt er
Total S.P. .41" Open External S.P. .22" Open
Heating ∆P NA Filter ∆P .08"
REMARKS:
TEST DATE:
READINGS BY:
BLEDSOE ENVIRONMENTAL LLC.
1400 Sunday Drive, Indianapolis, IN. 46217
6/20/2019 John
NA
100%OSA Damper Position
Return Damper Position
Static Pressure Profile
LBRU Animal Holding Area MAU-1
.22
H ea tin g
Se ct io n
NA Fa n
.19 Sc re en
.08
Fi lte r
RECTANGULAR DUCT
TRAVERSE REPORT
PROJECT: SYSTEM / UNIT:
LOCATION / ZONE: SERVICE:
ALTITUDE: DENSITY: CORR. FACTOR:
DUCT REQUIRED
S.P. Air Temp. SCFM SCFM
Size: 24 X 24 Area FPM CFM 4000 FPM CFM
1361 1258 1192 1175
1266 1323 1349 1192
1101 1412 1373 1175
1057 1091 1397 1309
Instrument: RPM: Sub Total: Number Points: 16
REMARKS:
TEST DATE:
READINGS BY:
BLEDSOE ENVIRONMENTAL LLC
1400 Sunday Drive, Indianapolis, IN. 46217
SUB - TOTALS
Datameter 811 20031
* Taken to calculate AK for grilles. Final RPM is 648 equals 4001 CFM.
0 0 0 0 0 0 0
DUCT EDGE
VELOCITY 4785 5084 5311 4851 0 0 0
DISTANCE FROM 3.00 9.00 15.00 21.00
15.00 3
21.00 4
3.00 1
9.00 2
7 10 11 12 13DISTANCE FROM POSITION 1 2 3
BOTTOM
.33"
4.00 ft² 1000 1252 5008
6/20/2019 John
LBRU Animal Holding Area MAU-1 Main Supply Duct Research Room
ACTUAL
8 94 5 6
AIR OUTLET TEST REPORT
PROJECT: SYSTEM:
OUTLET MANUFACTURER: TEST APPARATUS:
Area
Served NO. Type Size AK VEL CFM VEL CFM VEL CFM VEL CFM
Research 1 SG-1 12x6 .31 645 200 385 119 615 191 96% Research 2 SG-1 12x6 .31 645 200 243 75 610 189 95% Research 3 SG-1 12x6 .31 645 200 549 170 621 193 97% Research 4 SG-1 12x6 .31 645 200 440 136 622 193 97% Research 5 SG-1 12x6 .31 645 200 759 235 625 194 97% Research 6 SG-1 12x6 .31 645 200 750 233 656 203 102% Research 7 SG-1 12x6 .31 645 200 1033 320 675 209 105% Research 8 SG-1 12x6 .31 645 200 843 261 623 193 97% Research 9 SG-1 12x6 .31 645 200 0 0 634 197 99% Research 10 SG-1 12x6 .31 645 200 758 235 650 202 101% Research 11 SG-1 12x6 .31 645 200 0 0 635 197 99% Research 12 SG-1 12x6 .31 645 200 685 212 670 208 104% Research 13 SG-1 12x6 .31 645 200 937 290 655 203 102% Research 14 SG-1 12x6 .31 645 200 780 242 650 202 101% Research 15 SG-1 12x6 .31 645 200 815 253 645 200 100% Research 16 SG-1 12x6 .31 645 200 880 273 642 199 100% Research 17 SG-1 12x6 .31 645 200 1025 318 670 208 104% Research 18 SG-1 12x6 .31 645 200 1007 312 670 208 104% Research 19 SG-1 12x6 .31 645 200 995 308 675 209 105% Research 20 SG-1 12x6 .31 645 200 0 0 670 208 104%
4000 3992 4006 100%
REMARKS: * Opposed Blade Dampers have been set.
TEST DATE: 6-20-19
READINGS BY: John
BLEDSOE ENVIRONMENTAL LLC.
1400 Sunday Drive, Indianapolis, IN. 46217
MAU-1
Titus RVA
PreliminaryOutlet Design Final
LBRU Animal Holding Area
Notes% of Design
FAN TEST REPORT
PROJECT:
FAN DATA FAN NO. EF-1A FAN NO. EF-1B FAN NO. EF-2
Location Service Manufacturer Model Number Serial Number Type/Class Inline 1 Inline 1 Inline 1
Motor Make/Style Genteq NS Genteq NS Genteq NS
Motor H.P./RPM/Frame Volts/Phase/Hertz F.L. Amps/S.F. 7.5 TP 7.5 TP 7.5 TP
Motor Sheave Make/Model Motor Sheave Diam./Bore Fan Sheave Make Fan Sheave Diam./Bore No. Belts/Make/Size Sheave ℄ Distance/Pos
TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL
CFM (l/s) 2000 2010 2000 1988 1200 1153
Fan RPM 3 Speed High 3 Speed High 3 Speed Med
S.P. In/Out .46" .28" .42" .36" 1.33" .13"
Total S.P. .74" .78" 1.46"
Voltage 115 121 115 121 115 121
Amperage 7.5 6.7 7.5 6.7 7.5 6.5
REMARKS:
TEST DATE: 6/20/2019
READINGS BY: John
1400 Sunday Drive, Indianapolis, IN. 46217
Direct Drive
Direct Drive
Direct Drive Direct Drive
Direct Drive
Direct Drive Direct Drive
Direct Drive Direct Drive
Direct Drive
Direct DriveDirect Drive
BLEDSOE ENVIRONMENTAL LLC.
Direct Drive
E19LZ29789
3/4 1750 NS
115 1 60115 1 60
Direct Drive Direct Drive
E19LZ29788
3/4 1750 NS3/4 1750 NS
115 1 60
Direct Drive Direct Drive Direct Drive
E19LZ29790
SX115Q2C
Pennbarry
LBRU Animal Holding Area
Corridor
Research Room
Pennbarry
SX115Q2C
CorridorCorridor
Research Room
Pennbarry
Feed Room
SX115Q2C
AIR OUTLET TEST REPORT
PROJECT: SYSTEM:
OUTLET MANUFACTURER: TEST APPARATUS:
Area
Served NO. Type Size AK VEL CFM VEL CFM VEL CFM VEL CFM
EF-1A 2000 2010 2010 101% *
Research 1 CRG-1 22x22 1 1000 960 960 96% * Research 2 CRG-1 22x22 1000 1050 1050 105%
EF-1B 2000 1988 1988 99% *
Research 1 CRG-1 22x22 1 1000 1023 1023 102% * Research 2 CRG-1 22x22 1000 965 965 97%
EF-2
Feed Rm 1 CRG-1 22x22 1 1200 500 1153 96% *
REMARKS: * Volume dampers positions have been marked.
TEST DATE: 6-20-19
READINGS BY: John
BLEDSOE ENVIRONMENTAL LLC.
1400 Sunday Drive, Indianapolis, IN. 46217
LBRU Animal Holding Area Exhaust
Titus Balometer
Outlet Design Preliminary Final % of Design Notes