Exhibit A - Drawings for Recent Work.pdf

PDF 5 MB Posted

Attached to
Design-Build Miscellaneous Repairs Federal contract opportunity
Solicitation number
12505B21R0002
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area

View the file

Other files for this federal contract opportunity

Other files attached to Design-Build Miscellaneous Repairs, newest first.
File Type Posted
Site Visit Sign In Sheets.pdf PDF
SF-30 Amendment 01.pdf PDF
SF-1442 with Clauses and Provisions.pdf PDF
Statement of Work.pdf PDF
Exhibit C - Make Up Air Unit O-M Manual Part 1.pdf PDF
Exhibit D - Make Up Air Unit O-M Manual Part 2.pdf PDF
ARS Facilities Design Standards.pdf PDF
Exhibit B - Specifications for Recent Work.pdf PDF
Exhibit E - Electrical O-M Manual.pdf PDF
Exhibit F - Test and Balance Report.pdf PDF
ARS-371.pdf PDF
Wage Determination.pdf PDF
ARS-372.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

600 N.

750 N.

500 N.

ANIMAL

BEHAVIOR

LAB

S A

LI

S

B U

R Y

S T.

UNION

ST.

LAFAYETTE

WEST

LAFAYETTE

CO.RD 750 NORTH

U S

SCALE:

SITE LOCATION PLAN

NTS

SCALE:

VICINITY PLAN

NTS

ANIMAL

BEHAVIOR LAB

WABASH RIVER

NORTHWESTERN

AVE

MAIN ST.

LIST OF DRAWINGS

SHEET DWG. TITLE

AD101 ARCHITECTURAL DEMO3

A101 FIRST FLOOR PLAN - NEW CONSTRUCTION4

A401 BUILDING AND WALL SECTIONS

A402 EXISTING BUILDING SECTIONS AND DETAILS

P001

P101

PLUMBING REMOVAL PLAN

P102

PLUMBING NEW WORK FLOOR PLAN - GAS AND WATER

PLUMBING PLANS - SANITARY - DEMOLITION AND NEW WORK

P501 PLUMBING GAS RISER DIAGRAM AND DETAILS

P701 PLUMBING DETAILS

PD101

15 M001 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

M101

MECHANICAL DEMOLITION FLOOR PLAN

17 MECHANICAL NEW WORK FLOOR PLAN

M601 MECHANICAL SCHEDULES

M701 MECHANICAL DETAILS

MD101

E001

22 E101

ELECTRICAL DEMOLITION PLAN

ELECTRICAL LIGHTING PLAN

E501 ELECTRICAL POWER RISER DIAGRAM AND PANEL SCHEDULES

E701 ELECTRICAL DETAILS

ED101

E201 ELECTRICAL POWER PLAN

1 CS COVER SHEET

ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

PLUMBING GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

A001 ARCHITECTURAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

A102 DOOR SCHEDULE, FINISH SCHEDULE

A103 ARCHITECTURAL DETAILS

Xref O:\2017\SAGQ178056.02\90-SAGQ178056.02_XREF\178056.02 _TB-36x24.dwg

COVER SHEET

CS

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:29:58 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_COVER SHEET.dwg Save Date: 04/24/2018 12:23 PM

USDA AGRICULTURAL RESEARCH SERVICE

FY17-MWA-1

LBRU ANIMAL HOLDING AREA

WEST LAFAYETTE, IN

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:01 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A001.dwg Save Date: 04/24/2018 01:28 PM

GENERAL NOTES, SYMBOLS

AND ABBREVIATIONS

A001

1/8" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:08 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_AD101.dwg Save Date: 04/23/2018 04:57 PM

ARCHITECTURAL DEMO

AD101

Plotted By: Plot Date: 4/24/2018 1:30:17 PM Saved By: Save Date:

1-1/2" = 1'-0"

1/8" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:17 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A101.dwg Save Date: 04/24/2018 11:39 AM

FIRST FLOOR PLAN NEW

CONSTRUCTION

A101

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:22 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A102.dwg Save Date: 04/24/2018 11:40 AM

DOOR AND FINISH

SCHEDULE

A102

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:32 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A103.dwg Save Date: 04/24/2018 11:47 AM

ARCHITECTURAL DETAILS

A103

1/4" = 1'-0"

3/4" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:44 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A401.dwg Save Date: 04/23/2018 05:35 PM

BUILDING AND WALL

SECTIONS

A401

1/4" = 1'-0"

3/4" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:58 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A402.dwg Save Date: 04/24/2018 11:30 AM

EXISTING BUILDING

SECTIONS & DETAILS

A402

ABBREVIATIONS

AAV AIR ADMITTANCE VALVE

ABV ABOVE

AD AREA DRAIN

ADA AMERICAN DISABILITY ACT

AFF ABOVE FINISHED FLOOR

AP ACCESS PANEL

ARCH ARCHITECTURAL

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS

ASSE AMERICAN SOCIETY OF SANITARY ENGINEERS

BLDG BUILDING

BLW BELOW

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWV BACK WATER VALVE

CA COMPRESSED AIR

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

CONT CONTINUATION

CW COLD WATER

DD DECK DRAIN

DFU DRAINAGE FIXTURE UNIT

DIA DIAMETER

DMR DISTRIBUTED METER ROOM

DN DOWN

DWG DRAWING

DWH DOMESTIC WATER HEATER

DF DRINKING FOUNTAIN

E EXISTING

EA EACH

EQUIP EQUIPMENT

ERD EMERGENCY ROOF DRAIN

ERD(G) EMERGENCY ROOF DRAIN-GREEN ROOF

EST EMERGENCY STORM

EST(G) EMERGENCY STORM-FROM GREEN ROOF

ET EXPANSION TANK

ETR EXISTING TO REMAIN

F WATER FILTER

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FL FLOOR

FS FLOW SWITCH

FT FEET

FM FORCED MAIN

GAL GALLON

GCO GRADE CLEAN OUT

GD GARBAGE DISPOSAL

GH GARDEN HYDRANT

GPM GALLONS PER MINUTE

HB HOSE BIB

HDPE HIGH DENSITY POLYETHYLENE

HP HORSE POWER

HW HOT WATER SUPPLY

HWR HOT WATER RETURN

HPCW HIGH PRESSURE COLD WATER

HWSH HOT WATER STORAGE/HEATER

IN INCH

INV INVERT

KW KILOWATT

LAV LAVATORY

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MECH MECHANICAL

MFR MANUFACTURER

MGCV MASTER GAS CONTROL VALVE

MIN MINIMUM

MS MOP SINK

MTD MOUNTED

N NEW

NC NORMALLY CLOSED

NFWH NON FREEZE WALL HYDRANT

NG NATURAL GAS

NIC NOT IN CONTRACT

NO. NUMBER

NO NORMALLY OPEN

NT ACID NEUTRALIZATION TANK

ORD OVERFLOW ROOF DRAIN

ORD(G) OVERFLOW ROOF DRAIN-GREE ROOF

OSD OPEN SITE DRAIN

P PUMP

PD PLANTER DRAIN

PDD POOL DECK DRAIN

PDI PLUMBING AND DRAINAGE INSTITUTE

PH PHASE (ELECTRICAL)

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

RCV RISER CONTROL VALVE

REF REFRIGERATOR

RD ROOF DRAIN

RD(G) ROOF DRAIN-GREEN ROOF

RH ROOF HYDRANT

RPM REVOLUTIONS PER MINUTE

RR RAINWATER REUSE

RW RAIN WATER

RWC RAIN WATER CONDUCTOR

SA SHOCK ABSORBER

SAN SANITARY/WASTE PIPE

SF SQUARE FEET

SFU SUPPLY FIXTURE UNIT

SS STAINLESS STEEL

SS SERVICE SINK

ST STORM WATER

ST(G) STORM-FROM GREEN ROOF

STRUC STRUCTURAL

TD TRENCH DRAIN

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER TUBE

TW TEMPERED WATER

TYP TYPICAL

UR URINAL

V VENT PIPE

VTR VENT THRU ROOF

W WATT

WD WASTE DISPOSER

WC WATER CLOSET

WCO WALL CLEANOUT

WH WALL HYDRANT

WM WATER METER

WTR WATER

W/ WITH

W/O WITHOUT

PLUMBING SYMBOLS

NOTE: ALL SYMBOLS MAY NOT APPEAR ON THE DRAWINGS.

REDUCED PRESSURE ZONE BACKFLOW PREVENTER (ASSE1013)

BALL VALVE

CHECK VALVE

DOUBLE CHECK VALVE BACKFLOW PREVENTER (ASSE 1015,1048)

SOLENOID VALVE

GATE VALVE

PRESSURE REDUCING VALVE

THERMOSTATIC MIXING VALVE

PLUG VALVE

BACKFLOW PREVENTER (ASSE 1015 &1024)

PUMP

WATER HAMMER ARRESTOR ('A' = PDI SIZE)

PRESSURE GAUGE

THERMOMETER GAUGE

AQUASTAT VALVE

BALANCING VALVE

PIPE VALVES AND ACCESSORIES

VACUUM RELIEF VALVE

STRAINER

REDUCER/INCREASER

CAPPED CONNECTION

PIPE UNION

ELBOW TURNED UP

TEE UP

TEE DOWN

SHUT-OFF VALVE IN RISER

ELBOW TURNED DOWN

PIPE FITTINGS

COLD WATER PIPING

HOT WATER PIPING

HOT WATER RETURN PIPING

GAS PIPING

SANITARY PIPING ABOVE GROUND

VENT PIPING

STORM WATER PIPING ABOVE GROUND

PIPE REPRESENTATION

STORM WATER PIPING BELOW GROUND

SANITARY PIPING BELOW GROUND

G

STORM WATER PIPING FROM GREEN ROOF ABOVE GROUND

STORM WATER PIPING FROM GREEN ROOF BELOW GROUND

GENERAL PLUMBING NOTES

1. ALL PLUMBING WORK SHALL COMPLY WITH THE 2012 INTERNATIONAL PLUMBING CODE.

2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES AND TAXES.

3. CONTRACTOR SHALL MAKE NO CHANGES WITHOUT THE WRITTEN PERMISSION FROM THE ARCHITECT.

4. CONTRACTOR ASSUMES RESPONSIBILITY FOR PROPER ARRANGEMENT OF PIPE, FIXTURES, ETC TO CONNECT APPROVED EQUIPMENT IN A PROPER AND APPROVED MANNER. CONTRACTOR SHALL FOLLOW EQUIPMENT MANUFACTURER'S DETAILED INSTRUCTIONS AND THE CONTRACT DOCUMENTS. NOTIFY THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH ALL WORK.

NO EQUIPMENT INSTALLATION OR CONNECTIONS SHALL BE MADE IN A MANNER THAT VOIDS THE MANUFACTURER'S

WARRANTY.

5. BEFORE POURING CONCRETE FLOORS INSTALL ALL REQUIRED SLEEVES.

6. DO NOT CUT STRUCTURAL MEMBERS WITHOUT THE APPROVAL OF THE ARCHITECT/ENGINEER, AND PERFORM CUTTING IN A

MANNER AS DIRECTED BY A/E.

7. PROVIDE SLEEVES FOR ALL FLOOR PENETRATIONS WITH TOP OF SLEEVE 2' ABOVE FINISHED FLOOR.

8. PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL PLUMBING FIXTURES COMPLETELY AS SPECIFIED ON DRAWINGS.

9. PROVIDE SHUT-OFF VALVES ON ALL EQUIPMENT AND ANGLE STOPS IN HOT AND COLD WATER PIPING TO ALL PLUMBING

FIXTURES.

10. FLOOR TO BE SLOPED 1/8" TO FLOOR DRAINS. TOP OF DRAIN FLUSH WITH FINISHED FLOOR.

11. MIXING VALVES SHALL BE USED TO TEMPER HOT WATER AT ALL PUBLIC LAVATORIES AND HAND WASHING FACILITIES. SET AT

105 DEGREES F.

12. CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR ALL VALVES AND MECHANICAL EQUIPMENT.

13. MAINTAIN WORK AREA CLEAN AT ALL TIMES DURING CONSTRUCTION. AFTER COMPLETING INSTALLATION OF WORK, CLEAN ALL

FIXTURES OF ALL RUBBISH, PLASTER, DIRT AND OTHER DEBRIS.

14. TEST ALL SYSTEMS. ALL FIXTURES SHALL OPERATE SATISFACTORILY AS DESIGNED AND INTENDED. REPORT ANY DEFICIENCIES

TO THE ARCHITECT/ENGINEER.

15. ALL POTABLE WATER PIPING SHALL BE DISINFECTED AND FLUSHED IN FULL ACCORDANCE WITH THE LOCAL AUTHORITIES

HAVING JURISDICTION.

16. ALL PIPING SYSTEMS SHALL BE TESTED AT DESIGN PRESSURES FOR A PERIOD OF TIME AS PRESCRIBED BY THE LOCAL

AUTHORITIES HAVING JURISDICTION.

17. CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS, EQUIPMENT, LAYOUT DRAWINGS, AND ALL OTHER RELATED DRAWINGS AS REQUIRED FOR DIMENSIONS, DETAILS, ETC. PLUMBING LAYOUT SHOWN ON THIS DRAWING IS FOR GENERAL ARRANGEMENT ONLY. CONTRACTOR SHALL COORDINATE ALL WORK WITH FIELD CONDITIONS AND ALL OTHER TRADES INVOLVED AS REQUIRED. DO NOT SCALE DIMENSIONS FROM THIS DRAWING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN

FIELD AS REQUIRED.

18. CONTRACTOR SHALL REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND CUT SHEETS AS REQUIRED FOR

INSTALLATION OF EQUIPMENT.

19. CONTRACTOR SHALL FURNISH AND INSTALL ALL PIPING, FITTINGS, VALVES, PARTS AND ACCESSORIES REQUIRED FOR PROPER INSTALLATION AND OPERATION OF PLUMBING SYSTEM. (INCLUDING ALL FITTINGS AND DEVICES REQUIRED BY CODE, SUCH AS CHECK VALVES, VACUUM BREAKERS, SAFETY RELIEF VALVES, VACUUM RELIEF, ETC. ALL FLOOR DRAINS, WHERE REQUIRED BY

CODES AND REGULATIONS, SHALL BE PROVIDED WITH TRAP PRIMER VALVE AND FITTINGS.

20. ALL PIPING SHALL BE HUNG, FIRMLY ANCHORED AND SUPPORTED IN ACCORDANCE WITH MSS SP-58 MSS SP-69.

21. CONTRACTOR SHALL FURNISH AND INSTALL WATER SHOCK ARRESTORS DOWN STREAM OF SOLENOID AND QUICK CLOSING VALVES. AIR CHAMBERS SHALL NOT BE CONSIDERED AN EQUAL TO WATER ARRESTORS AS SPECIFIED.

22. PLUMBING CONTRACTOR SHALL PROVIDE ACCESS PANELS WHERE REQUIRED FOR ACCESS TO VALVES IN CEILINGS AND

WALLS.

23. VALVES AND FITTINGS SHALL BE OF THE SAME SIZE AS THE LINE ON WHICH THEY ARE LOCATED, UNLESS OTHERWISE

INDICATED ON DRAWINGS.

24. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY SUPPORTING DEVICES FOR ALL FIXTURES INCLUDED IN

CONTRACT OR HEREIN SPECIFIED OR OTHERWISE.

25. CONTRACTOR SHALL SLEEVE ALL PIPING CROSSING THROUGH OR UNDERNEATH STRUCTURAL MEMBERS. NOTIFY ARCHITECT AND ENGINEERS PRIOR TO PROCEEDINGS WITH WORK TO ASSURE STRUCTURAL SUPPORT WILL NOT BE AFFECTED.

26. DOMESTIC WATER SHALL BE SLOPED TO DRAIN POINTS.

27. ALL SANITARY DRAINAGE PIPING 3" AND LARGER SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/8" FALL PER 1'-0" OF RUN

OTHERWISE NOTED.

28. ALL SANITARY DRAINAGE PIPING 2" AND LESS SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/4" FALL PER 1'-0" OF RUN

OTHERWISE NOTED.

29. ALL STORM DRAINAGE PIPE SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/8" FALL PER 1'-0" OF RUN OTHERWISE NOTED.

30. ALL ILLUSTRATED DRAINAGE PIPING IS BELOW THE FLOOR ON WHICH IT IS DRAWN UNLESS OTHERWISE NOTED. ALL DOMESTIC WATER AND VENT PIPING ILLUSTRATED IS ABOVE OR AT THE CEILING ON WHICH IT IS DRAWN UNLESS OTHERWISE NOTED.

31. PROVIDE PRODUCTS AND FIXTURES AS SPECIFIED OR EQUIVALENT.

32. AT FLOOR DRAIN TRAP SEALS SHALL BE MAINTAINED BY AN APPROVED TRAP PRIMER.

33. MAKE FINAL CONNECTIONS AFTER FIXTURES AND EQUIPMENT ARE SET IN PLACE. ALL REQUIRED TRIM, FAUCETS AND MINOR ITEMS NECESSARY FOR A COMPLETE FUNCTIONING INSTALLATION, SUCH AS STRAINERS, TRAPS, TAILPIECES, ESCUTCHEONS, ETC., SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE WITH EQUIPMENT REQUIREMENTS. ALL

FAUCETS TO BE HEAVILY CHROME-PLATED.

34. CONTRACTOR ASSUMES RESPONSIBILITY FOR PROPER ARRANGEMENT OF PIPE, FIXTURES, ETC TO CONNECT APPROVED EQUIPMENT IN A PROPER AND APPROVED MANNER. CONTRACTOR SHALL FOLLOW EQUIPMENT MANUFACTURER'S DETAILED INSTRUCTIONS AND THE CONTRACT DOCUMENTS. NOTIFY THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH ALL WORK.

NO EQUIPMENT INSTALLATION OR CONNECTIONS SHALL BE MADE IN A MANNER THAT VOIDS THE MANUFACTURER'S

WARRANTY.

35. SUBMIT OPERATING AND MAINTENANCE MANUALS AND WARRANTY CERTIFICATES TO OWNER.

36. WATER HAMMER ARRESTERS SHALL BE INSTALLED IN FRONT OF ALL QUICK CLOSING VALVES SUCH AS MECHANICAL

EQUIPMENT AND AUTOMATIC CLOTHES WASHERS.

37. THE DOMESTIC WATER SYSTEM SHALL BE DISINFECTED AND FLUSHED IN FULL ACCORDANCE WITH THE LOCAL AUTHORITIES

HAVING JURISDICTION.

BACK WATER VALVE

GREASE SANITARY ABOVE GROUND

GREASE SANITARY BELOW GROUND

GR

GR

DESIGN CRITERIA

NOTE: ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.

DETAIL NUMBER

DETAIL NUMBER

WHERE THE DETAIL IS DRAWN

WHERE THE DETAIL IS DRAWN

WHERE THE DETAIL REFERENCED

DETAIL ANNOTATIONS

DOMESTIC WATER RISER DESIGNATION

SANITARY WATER RISER DESIGNATION

STORM RISER DESIGNATION

GAS RISER DESIGNATION

REVISION NUMBER

ANNOTATIONS

POINT OF DEMOLITION

POINT OF CONNECTION

AREA DRAIN

FLOOR DRAIN

GARAGE DRAIN

OVER FLOW ROOF DRAIN

ROOF DRAIN

FLOOR CLEAN OUT

FLOOR SINK DRAIN

DRAINS

HORIZONTAL CLEANOUT

WALL HYDRANT

HOSE BIB

MISCELLANEOUS

GAS METER

WATER METER

WATER FILTER

VACCUM BREAKER

TEMPERATURE AND PRESSURE RELIEF VALVE

TRAP PRIMER

DIRT LEG

TRENCH DRAIN

BREAK PIPE BELOW

X"

X"

PIPE SIZE

PIPE SIZE/NOTE

OPEN SITE DRAIN

FUNNEL FLOOR DRAIN

GREEN STORM RISER DESIGNATION

VENT RISER DESIGNATION

ROOF DRAIN-GREEN ROOF

EMERGENCY ROOF DRAIN

EMERGENCY ROOF DRAIN-GREEN ROOF

EMERGENCY STORM RISER DESIGNATION

EMEREGENCY GREEN STORM RISER DESIGNATION

OVER FLOW ROOF DRAIN-GREEN ROOF

GRADE CLEAN OUT

ROOF HYDRANT

GARDEN HYDRANT

TRAP PRIMER TUBE

INDIRECT DRAINAGE PIPE

EMERGENCY STORM WATER PIPING ABOVE GROUND

EMERGENCY STORM WATER PIPING BELOW GROUND

EMERGENCY STORM WATER PIPING FROM GREEN ROOF ABOVE GROUND

EMERGENCY STORM WATER PIPING FROM GREEN ROOF BELOW GROUND

GAS PIPING

ST

ST

ST(G)

ST(G)

EST

EST

EST(G)

EST(G)

ID

TP

2012 INTERNATIONAL BUILDING CODE

2012 INTERNATIONAL PLUMBING CODE

2012 INTERNATIONAL MECHANICAL CODE

2012 INTERNATIONAL FUEL GAS CODE

EQUIPMENT DESIGNATIONEQPM

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:02 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P001.dwg Save Date: 04/24/2018 12:23 PM

PLUMBING GENERAL NOTES,

SYMBOLS & ABBREVIATIONS

P001

EXISTING LIQUID

SEWAGE STORAGE

BASINS, TO REMAIN

IE 738.97'

(-3.33")

FD ETR

EXISTING 4"

CLEANOUTS

FD ETR

REMOVE EXIST SANITARY

PIPE UNDER SLAB UP TO

EXISTING FLOOR DRAIN

(E)4" SANITARY TO

SEPTIC SYSTEM (NIS)

EXISTING FD

EXISTING FD

EXISTING 4"

CLEANOUT

EXISTING FD

EXISTING 4"

CLEANOUT

EXISTING FD

EXISTING FD

EXISTING UNDERGROUND

CW PIPING TO REMAIN. SEE DETAIL ON P-701 FOR

WORK AT BOOSTER PUMP

CAP PIPE AT

SOURCE

SHEET KEY NOTES

GENERAL NOTES

1. CONTRACTOR IS RESPONSIBLE TO ENSURE THAT THE EXISTING

UNDERGROUND PIPING IS NOT DAMAGED DURING THE REMOVAL

OF EXISTING GUTTER.

1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL

OTHER TRADES.

2. ANY DAMAGE TO THE ITEMS NOT IN SCOPE OF WORK SHALL BE

REPAIRED / REPLACED TO MATCH EXISTING CONDITIONS AT NO

EXTRA COST TO THE OWNER.

SCALE:

PLUMBING NEW WORK PLAN - SANITARY

1/8" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:09 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_PD101.dwg Save Date: 04/23/2018 05:31 PM

4'0 8' 16'

NORTH

1/8" = 1'-0"

PLUMBING - REMOVALS PLAN

PD-101

SHEET KEY NOTES

(E)1" G

(50 CFH)

(E)1-1/4" G

250(CFH)

(E)1" G

(50 CFH)

(E)1" G

(100 CFH)

(E)1-1/4" G

(250 CFH)

(E)1-1/2" G

(500 CFH)

(E)1" G

(250 CFH)

(E)2" G

(250 CFH)

(N)1" G

(100 CFH)

(E)2" G

475(CFH)

(E)1" G

(175 CFH)

1-1/4" G

(130 CFH)

1-1/4" G

(130 CFH)

MAU-1

325 CFH

NATURAL GAS SERVICE

EXISTING TO REMAIN.

1-1/2" G

(325 CFH)

1-1/4" G

(130 CFH)

UH-1A

130 CFH

UH-1A

130 CFH

IRH

50 CFH

IRH

50 CFH

UH

250 CFH

IRH

250 CFH

RTU-175 CFH

(E)1-1/2" G

(425 CFH)

2" G

(585 CFH)

2" G

(585 CFH)

RELOCATED

IRH

50 CFH

GM

IRH

50 CFH

IRH

50 CFH

GFU

100 CFH

(E)1-1/4" G

(250 CFH)

UH

250 CFH

FV

FV

TRENCH DRAIN

FLUSH VALVE

AND CABINET

(TYP)

FV

FV

EXISTING UNDERGROUND

CW PIPING TO REMAIN.

3/4" G

(50 CFH)

3/4" G

(50 CFH)

FD ETR

FD ETR

SEE DETAIL ON P-701 FOR

WORK AT BOOSTER PUMP GENERAL NOTES

1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL

OTHER TRADES.

2. ANY DAMAGE TO THE ITEMS NOT IN SCOPE OF WORK SHALL BE

REPAIRED / REPLACED TO MATCH EXISTING CONDITIONS AT NO

EXTRA COST TO THE OWNER.

1. PROVIDE FLUSH VALVE, WHITEHALL MODEL WH2803-1 OR

EQUIVALENT, COMPLETE WITH ACCESSORIES TO BE

INSTALLED PER MANUFACTURER RECOMMENDATIONS.

2. NEW PRECHARGED BLADDER TANK. SEE DETAIL P-701 FOR

PIPING ARRANGEMENT OF BLADDER TANK.

3. 1-1/4" PRESSURIZED WATER SUPPLY TO THE TRENCH DRAIN

FLUSH VALVE SYSTEM VIA A 1 14" REDUCED PRESSURE ZONE

BACKFLOW PREVENTER (ASSE-1013).

4. FLUSH VALVE WITHIN A RECESSED WALL CABINET.

5. 1/2" HOT + COLD WATER (INSULATED) SUPPLY TO NEW LAB

SINK CONNECT TO HOUSE HOT AND COLD WATER SUPPLY

SYSTEM.

CAP PIPE AT

SOURCE

FF 742.30

FV

FV

FLUSH VALVE (TYP)

FV

1"1"

1-1/4"

1"

1-1/4"

1"

1 1/4"

1"

1"

SCALE:

PLUMBING NEW WORK FLOOR PLAN - GAS AND WATER

1/8" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:14 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P101.dwg Save Date: 04/24/2018 11:50 AM

4'0 8' 16'

NORTH

1/8" = 1'-0"

PLUMBING NEW WORK FLOOR

PLAN - GAS AND WATER

P101

EXISTING LIQUID

SEWAGE STORAGE

BASINS, TO REMAIN

IE 738.97'

(-3.33")

FD ETR

FD ETR

REMOVE EXISTING

FLOOR DRAIN

UNDER WALL

PARTITION

REMOVE EXIST

SANITARY

PIPE UNDER

SLAB

(E)4" SANITARY TO

SEPTIC SYSTEM (NIS)

FD ETR

GENERAL NOTES

1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL

OTHER TRADES.

2. ANY DAMAGE TO THE ITEMS NOT IN SCOPE OF WORK SHALL BE

REPAIRED / REPLACED TO MATCH EXISTING CONDITIONS AT NO

EXTRA COST TO THE OWNER.

SHEET KEY NOTES

1. PROVIDE A DUPLEX PACKAGED SEWAGE EJECTOR PUMP

SYSTEM WITH BASIN, ZOELLER, MODEL 282 OR EQUIVALENT

PUMPS, COMPLETE WITH BASINS, GRINDER, RAILS, CONTROLS

AND ACCESSORIES PER MANUFACTURER RECOMMENDATIONS.

2. PROVIDE 10" WIDE TRENCH DRAIN WITH HEAVY DUTY CI

GRATE, JAY R. SMITH FIG. 9812 OR EQUIVALENT COMPLETE

WITH ALL ACCESSORIES WITH MANUFACTURER

RECOMMENDATIONS.

3. PROVIDE A FIBERGLASS CATCHBASIN WITH STAINLESS STEEL

BASKET STRAINER, WITH DUCTILE IRON GRATE COMPLETE

WITH ALL ACCESSORIES PER MANUFACTURER

RECOMMENDATIONS - JAY R. SMITH FIG. NO. 9812-880-cb24 OR

EQUIVALENT.

4. PROVIDE A 2" SUPPLY FROM FLUSH VALVE TO TRENCH DRAIN

END CONNECTOR.

5. FLUSH VALVE CABINET WITH FLUSH VALVE ASSEMBLY.

6. PROVIDE NEW INLINE BACKWATER VALVE WITH CLEANOUT

ACCESS COVER.

7. 2" PVC SCH. 40 POST BASIN DRAIN PIPING UNDER SLAB.

INSTALL AT MIN. 2% SLOPE TOWARD CATCH BASIN.

8. 2" POST DRAIN BASIN. SEE DETAILS.

FV

EXISTING LIQUID

SEWAGE STORAGE

BASINS, TO REMAIN

IE 738.97'

(-3.33")

FD ETR

SEWAGE

EJECTOR

BASIN

2" VENT

P-TRAP WITH

FLUSHING HEEL

CONNECTION

CATCH

BASIN

FV

FD ETR

FLUSH VALVE (TYP)

FLUSHING PIPE

UNDER SLAB (TYP)

CENTER CATCH BASIN

WITH REMOVABE STAINLESS

STEEL BASKET

STRAINER(TYP)

FV

REMOVE EXISTING

FLOOR DRAIN

UNDER WALL

PARTITION

(E)4" SANITARY TO

SEPTIC SYSTEM (NIS)

TRENCH

DRAIN (TYP)

4"BWV

FV

P-TRAP WITH

FLUSHING HEEL

CONNECTION

PIPE DOWN TO CONNECT

TO EXIST SANITARY

BELOW FLOOR.

2" PUMP

DISCHARGE AT

MIN 14'-0" AFF

FV

FLUSH VALVE

(TYP)

FV

(TYP)

(TYP)

2"

(TYP)

2"

(TYP)

SK-1

2" Ø

4" Ø4" Ø

4" Ø

4" FD

2" V

SCALE:

PLUMBING NEW WORK PLAN - SANITARY - DEMOLITION

1/8" = 1'-0"

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:19 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P102.dwg Save Date: 04/24/2018 11:50 AM

4'0 8' 16'

NORTH

1/8" = 1'-0"

SCALE:

PLUMBING NEW WORK PLAN - SANITARY - NEW WORK

WDSDSD

PLUMBING NEW WORK PLAN

- SANITARY

P102

GROUND FLOOR

ROOF

(E) GAS METER &

REGULATOR TO REMAIN

GAS EQUIPMENT SCHEDULE

FIXTURE QUANTITY NEW EQUIPMENT

CFH RATING

REQUIRED INLET PRESSURE PIPE SIZE CONNECTION

EQUIPMENT

LOCATION

MAU 1

UH 5

UH-1B

IRH

TOTAL

GAS SERVICE TO

LOW PRESSURE SYSTEM #2: FROM PRV TO APPLIANCES:

1. SIZING BASED ON SCHEDULE 40 BLACK STEEL.

2. SYSTEM PRESSURE: 10.5 INCHES WC.

3. MAXIMUM LENGTH OF RUN: NOT TO EXCEED 20 FEET OF LENGTH.

4. MAXIMUM PRESSURE DROP: NOT TO EXCEED 0.5 INCHES WC.

NATURAL GAS PIPING SIZED PER IFGC 2012 TABLE 402.4 (2) PIPE SIZED TO MAXIMUM

DEVELOPED LENGTH OF 500 FEET INCLUDING FITTING PRESSURE LOSSES.

GAS SERVICE

LOW PRESSURE SYSTEM #1: FROM GAS METER TO PRV.

1. SIZING BASED ON SCHEDULE 40 BLACK STEEL.

2. SYSTEM PRESSURE: 10.5 INCHES WC.

3. MAXIMUM LENGTH OF RUN: NOT TO EXCEED 500 FEET OF LENGTH.

4. MAXIMUM PRESSURE DROP: NOT TO EXCEED 0.5 INCHES WC.

NATURAL GAS PIPING SIZED PER IFGC 2012 TABLE 402.4 (2) PIPE SIZED TO MAXIMUM

DEVELOPED LENGTH OF 500 FEET INCLUDING FITTING PRESSURE LOSSES.

(E) GAS SERVICE (E) DIRT LEG

G

UH-1A

325 CFH

500 CFH

130 CFH

130 CFH

300 CFH

RTU 1 175 CFH ---

UH

(250 CFH) (E)

EXISTING ANIMAL

BEHAVIORAL ROOM

UH

(250 CFH) (E)

IRH

(50 CFH) (E)

IRH

(50 CFH) (E)

IRH

(50 CFH) (E)

RELOCATED

IRH

(50 CFH) (E)

IRH

(50 CFH) (E)

RELOCATED

IRH

(50 CFH) (E)

GFU

(100 CFH) (E)

RTU

(175 CFH) (E)

MAU-1

(325 CFH) (N)

UH-1A

(130 CFH) (N)

UH-1B

(130 CFH) (N)

(N) 2" GAS

1-1/4" G1-1/4" G1-1/2" G

2" G

1-1/4" G 3/4" G3/4" G 1" G

1560 CFH

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:23 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P501.dwg Save Date: 04/24/2018 12:58 PM

SCALE:

GAS RISER DIAGRAM

NOT TO SCALE

PLUMBING RISER DIAGRAMS

P501

WALL MOUNTED

FLUSH VALVE

10" WIDE SLOPING

FIBERGLASS

TRENCH (TYP.)

CATCH BASIN WITH

STAINLESS STEEL

BASKET STRAINER

WALL MOUNTED

FLUSH VALVE

2" SUPPLY

FROM

FLUSHING

VALVE (TYP)

1%

1%

1%

1%

SLOPE SLOPE

1%

1%

4" Ø

27"

CATCH

BASIN

TRENCH DRAIN SLOPE

36" Ø X 72"

DEEP FIBER GLASS BASIN

GAS TIGHT

BASIN COVER

VENT THRU

ROOF

DUPLEX SEWAGE

EJECTOR PUMP

ANTI FLOTATION BASE

1%

4" OUTLET

STAINLESS STEEL

BASKETTRENCH

CATCH BASIN

STAINLESS STEEL

BASKET

TRENCH

4"PD

2" PD

1/2 HP SEWAGE GRINDER

36"Ø X 72" DEEP BASIN W/

GAS TIGHT COVER 2" VENT

TO OUT SIDE

FROM WALL MOUNT FLUSH

WATER SUPPLY. SEE DETAIL

4 ON THIS DRAWING

4"

BWV

1%

TRENCH DRAIN DETAILS

NOT TO SCALE

2" INLET FROM

FLUSH VALVE

4" ELBOW WITH LOW

HEEL 2" INLET

CATCH BASIN WITH

REMOVABLE STAINLESS

STEEL BASKET SCREEN

CATCH BASIN

GRATING

COVER

TRENCH COVER

SLOPING FIBERGLASS

TRENCH DRAIN

TRENCH DRAIN END CAP

WITH 4" INLET

4X2 ECCENTRIC

REDUCER

2"FROM

FLUSH VALVE

4" GRAVITY TO SUMP

BASIN

NO HUB COUPLING (TYP)

2" FROM

FLUSH VALVE

1/ 4" BEND, NO-HUB

CAST IRON WITH LOW HEEL INLET

FLUSH VALVE AND PIPING DETAIL

NOT TO SCALE

1" COLD

WATER SUPPLY

RECESSED CABINET,

STAINLESS STEEL

RECESSED FLUSH VALVE

PUSH BUTTON

FLUSH STARTER

1" DISCHARGE

2 X 1 NO-HUB FERNCO

COUPLING

2" DRAIN TO TRAP

CLEANING / FLUSHING

SYSTEM

SCHEMATIC PLAN VIEW

NOT TO SCALE

SCHEMATIC SEWAGE EJECTOR DIAGRAM

NOT TO SCALE

SCHEMATIC SECTION VIEW

NOT TO SCALE

3CATCH BASIN DRAIN PIPING DETAIL

NOT TO SCALE

1" BALL SHUT-OFF VALVE

CUTOUT IN COVER TO

ACCESS THE PUSH BUTTON

BACKWATER

VALVE (TYP)

SEE DETAIL 5 ON

THIS DRAWING

4" BOTTOM

OUTLET

EXISTING PRESSURE

GAUGES

EXISTING 1" BACK PRESSURE

REGULATOR & BY-PASS

RELIEF VALVE

FROM EXISTING 1" WATER

SERVICE PIPING

TO WATER

DISTRIBUTION PIPING

FROM EXISTING 1" WATER

SERVICE PIPING

TO WATER

DISTRIBUTION PIPING

EXISTING WATER

HAMMER ARRESTOR

TO REMAIN

DOMESTIC WATER PIPING - REMOVALS

BOOSTER PUMP PIPING DIAGRAM

NOT TO SCALE

NOTE:

INSTALL THE PRESSURE TANK PER

MANUFACTURER RECOMMENDATIONS.

DOMESTIC WATER PIPING - NEW WORK

EXISTING WATER

HAMMER ARRESTOR

TO REMAIN

NEW PRESSURE

GAUGE W/ GAUGE

COCK (TYP)

NEW PRE-CHARGED

PRESSURE TANK, 82 GAL.

CAPACITY, FLOTEC,

MODEL FP7110 OR

APPROVED EQUAL

4" Ø

27"

CATCH

BASIN

TRENCH DRAINSLOPE

BACKWATER

VALVE.

SCORIATED COVER

BACKWATER VALVE

1%1%

1%1%

2" SUPPLY FROM

FLUSHING VALVE

(TYP)

4"4"2"

WALL MOUNTED

FLUSH VALVE

4" GRAVITY DRAIN

TO SUMP BASIN

NO-HUB

COUPLING

EXTENSION

RISER

SCORIATED

CLEANOUT

COVER

CATCH

BASIN

CATCH BASIN

GRATING

COVER

1%

SLOPE

36" x 72" DEEP

FIBERGLASS BASIN

CHECK

VALVE

SHUT-OFF

BALL VALVE

BACKWATER

VALVE

CATCH BASIN WITH

BASKET STRAINER

27" SQUARE X 27" DEEP

9' SLOPING

TRENCH SECTION

(TYP)

2" FROM

FLUSHING

VALVE (TYP)

2" VENT

1"

1"

1"

PIPE UNION

EXISTING DOMESTIC

WATER BOOSTER PUMP

TO REMAIN

EXISTING DOMESTIC

WATER BOOSTER PUMP

TO REMAIN

EXISTING PRESSURE

SWITCH TO REMAIN

POST DRAIN BASIN DETAIL

NOT TO SCALE

12" SQUARE CONCRETE

FILLED BACKFILL AROUND

BASIN SUPPORT.PLAN

2" Ø POST DRAIN BASIN.

SECTION

2" Ø x 10" LONG SCH40

GALV. STEEL SUPPORT

EMBEDDED IN CONC.

BASIN.

2" Ø FERNCO COUPLING

2" Ø x 2" LONG

PVC SCH. 40

2" Ø PVC ELBOW

2" Ø PVC SCH. 40

TO CATCH BASIN

SLOPE AT MIN.

2% SLOPE.

FINISH

FLOOR

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:27 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P701.dwg Save Date: 04/24/2018 11:27 AM

PLUMBING DETAILS

P701

SYMBOLSGENERAL MECHANICAL NOTES

OPEN END DUCT WITH CAP

DUCTWORK WITH ROUND DUCT TAKE-OFF

DUCTWORK WITH DUCT BRANCH

RETURN OR EXHAUST AIR DEVICE

SUPPLY AIR DEVICE

ELBOW WITH TURNING VANES

RETURN AIR DUCT TO DROP DOWN

RETURN AIR DUCT TO RISE UP

SUPPLY AIR DUCT TO DROP DOWN

SUPPLY AIR DUCT TO RISE UP

MANUAL VOLUME DAMPER

FLEXIBLE DUCT CONNECTOR

DUCT WORK WITH TRANSITION

12x10

FIRE DAMPER

FD

VD

VD

VD

NEW DUCT (1ST DIMENSION INDICATES TOP SHOWN,

INSIDE CLEAR DIMENSIONS).

EXISTING DUCTWORK OR EQUIPMENT TO REMAIN

EXISTING DUCTWORK OR

EQUIPMENT TO BE REMOVED

CEILING SUPPLY AIR DIFFUSER

EXHAUST AIR GRILLE

THERMOSTAT / TEMPERATURE SENSOR

RECTANGULAR/SQUARE DUCT TO ROUND

DUCT SIZE TRANSITION

EXHAUST DUCT TO DROP DOWN

EXHAUST DUCT TO RISE UP

EXHAUST AIR DEVICE

REVISION NUMBER

KEYED DRAWING NOTE

EQUIPMENT DESIGNATION TAG

AIR DEVICE TAG

DIFFUSER TYPE

AIR VOLUME IN CFM

UNDERCUT DOOR

NEW TO EXISTING

REMOVE TO EXISTING

NOTE:

ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.

AC AIR CONDITIONING UNIT

AFF ABOVE FINISHED FLOOR

APD AIR PRESSURE DROP

ARCH ARCHITECTURAL

BHP BRAKE HORSE POWER

BLDG BUILDING

BLW BELOW

BTUH BRITISH THERMAL UNIT PER HOUR

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

CU CONDENSING UNIT

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

DB DRY BULB

DIA DIAMETER

DN DOWN

DWG DRAWING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILL

EQUIP EQUIPMENT

ERV ENERGY RECOVERY VENTILATOR

ETR EXISTING TO REMAIN

EA. EXISTING

EXT EXTERNAL

F FAHRENHEIT

FD FIRE DAMPER

FCU FAN COIL UNIT

FPM FEET PER MINUTE

FT FEET

HP HORSE POWER / HEAT PUMP

HR HOUR

IN INCH

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LB POUNDS

LF LINEAR FEET

MAX MAXIMUM

MBH 1000 BTUH

MECH MECHANICAL

MIN MINIMUM

MTD MOUNTED

(N) NEW WORK

NC NOISE CRITERIA

NOM NOMINAL

No. NUMBER

OA OUTSIDE AIR

OAT OUTSIDE AIR TEMPERATURE

(R) RELOCATED

RA RETURN AIR

RAT RETURN AIR TEMPERATURE

RG RETURN GRILL

RPM REVOLUTION PER MINUTE

SA SUPPLY AIR

SAT SUPPLY AIR TEMPERATURE

SG SUPPLY GRILL

SR SUPPLY REGISTER

TS TEMPERATURE SENSOR

TYP TYPICAL

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

W WATT

WB WET BULB

WC WATER COLUMN

WG WATER GAUGE

WPD WATER PRESSURE DROP

W/ WITH

W/O WITHOUT

ABBREVIATIONS

1. THE INTENT OF THE CONTRACT DOCUMENTS IS TO PROVIDE FINISHED WORK, TESTED AND READY

FOR OPERATION. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF FIRST RATE QUALITY.

2. WORK INDICATED ON THESE DRAWINGS IS DIAGRAMMATIC AND SHOULD NOT BE SCALED TO

ESTABLISH LOCATION OF WORK. THE DRAWINGS ARE INTENDED TO CONVEY THE SCOPE OF

WORK AND INDICATE GENERAL ARRANGEMENTS OF ENGINEERED SYSTEMS. THE CONTRACTOR

SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD AND MAKE ADJUSTMENTS AS NECESSARY

TO COMPLETE THE WORK.

3. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND SERVICES FOR ALL WORK, IN

ACCORDANCE WITH PROVISIONS OF THE CONTRACT DOCUMENTS. ALTHOUGH SUCH WORK IS NOT

SPECIFICALLY INDICATED, FURNISH AND INSTALL ALL SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTENANCES AND DEVICES INCIDENTAL TO OR NECESSARY FOR A SOUND, SECURE AND

COMPLETE INSTALLATION, AT NO ADDITIONAL COST TO THE OWNER.

4. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH

MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND

REGULATIONS.

5. IN ADHERENCE WITH THE INTENT OF THESE CONTRACT DOCUMENTS, PROVIDE FINISHED WORK, TESTED AND READY FOR OPERATION. WHEREVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN

"FURNISHED, INSTALL, BALANCE, ADJUST AND TEST, COMPLETE AND READY FOR USE".

6. CONTRACTOR IS RESPONSIBLE FOR COMPLETE COORDINATION BETWEEN ALL

SUB-CONTRACTORS, SUPPLIERS, GOVERNMENT AUTHORITIES HAVING JURISDICTION, BUILDING

PERSONNEL, CODE ENFORCEMENT OFFICIALS, ARCHITECT/ENGINEER AND BUILDING OWNER.

7. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS.

COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING

DIMENSIONS BEFORE FABRICATION.

8. ALL PIPES SHALL BE INSTALLED IN A NEAT AND ORDERLY APPEARANCE AND FREE FROM CONTACT

WITH STRUCTURE OR INSTALLED ITEMS. RUN PIPING PARALLEL TO WALLS AND FLOORS OF

BUILDING UNLESS OTHERWISE INDICATED.

9. PROVIDE REFRIGERANT PIPING IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S

RECOMMENDATIONS. VERIFY LINE SIZES FOR EQUIPMENT FURNISHED.

10. INSULATE REFRIGERANT SUCTION PIPING WITH CLOSED-CELL FLEXIBLE ELASTOMERIC INSULATION (REFER TO SPECIFICATIONS FOR THICKNESS) UNLESS OTHERWISE NOTED. PROVIDE A WEATHER

RESISTANT FINISH ON INSULATION EXPOSED TO OUTDOORS. INSTALLATION TO BE IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

11. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH

ALL OTHER TRADES INVOLVED.

12. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE

STOPPED. PRODUCT USED MUST MEET TEST METHODS BY ASTM E814 OR NFPA 251 FOR FIRE

RATING. PROVIDE UL LABELED FIRE DAMPERS AT ALL DUCT PENETRATIONS INTO FIRE RATED

STRUCTURES.

13. REFER TO SPECIFICATIONS FOR WARRANTY REQUIREMENTS.

14. THE CONTRACTOR SHALL NOT CORE DRILL CONCRETE SLAB WITHOUT THE KNOWLEDGE AND

WRITTEN CONSENT OF THE STRUCTURAL ENGINEER AND THE BUILDING OWNER. CORE DRILLING

SHALL BE SCHEDULED WITH THE BUILDING OWNER.

15. THERMOSTAT AND TEMPERATURE SENSORS SHALL BE INSTALLED 4'-0" (ADA COMPLIANCE) ABOVE

FINISHED FLOOR WHERE SHOWN ON PLANS UNLESS NOTED OTHERWISE.

16. MAXIMUM LENGTH OF FLEXIBLE DUCTWORK SHALL NOT EXCEED 5'-0" UNLESS OTHERWISE NOTED.

17. PROVIDE SINGLE THICKNESS TURNING VANES IN ALL DUCTWORK ELBOWS (45° & 90°). TURNING

VANES SHALL COMPLY WITH SMACNA STANDARDS, 2005 EDITION.

18. ALL NEW DUCTWORK MUST BE FIELD VERIFIED PRIOR TO FABRICATION, PURCHASE, OR

INSTALLATION. NO ALLOWANCE WILL BE MADE FOR DUCTWORK THAT IS NOT USED.

19. PROVIDE ALL NECESSARY ACCESSORIES TO ALLOW FOR PROPER AIR BALANCE. UPON

COMPLETION OF THE INSTALLATION, ALL AIR SYSTEMS SHALL BE ADJUSTED AND BALANCED TO

PROVIDE THE AIR FLOW RATE INDICATED. CONTRACTOR SHALL PROVIDE VOLUME DAMPERS,

SPLITTER DAMPERS AND/OR VOLUME EXTRACTORS AS INDICATED OR REQUIRED FOR BALANCING.

BALANCING WORK SHALL BE PERFORMED BY A CERTIFIED BALANCING CONTRACTOR WHO IS A

MEMBER IN GOOD STANDING OF AABC OR SMACNA. BALANCING WORK SHALL BE IN COMPLIANCE

WITH THE STANDARD PROCEDURE MANUAL PUBLISHED BY THE TESTING AND BALANCING

ORGANIZATION AFFILIATED WITH THE BALANCING CONTRACTOR. PRIOR TO ACCEPTANCE OF THE WORK, CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER ALL APPROPRIATE FIELD DATA

ON STANDARD FORMS OF THE TESTING AND BALANCING ORGANIZATION IN ACCORDANCE WITH

STANDARD PROCEDURES.

20. ALL EQUIPMENT (INCLUDING DUCTWORK AND PIPING) SHALL BE SECURELY SUPPORTED FROM

THE BUILDING STRUCTURE IN AN APPROVED MANNER. EQUIPMENT SHALL NOT GENERATE NOISE

GREATER THAN CATALOG RATINGS. ALL EQUIPMENT AND APPURTENANCES SHALL NOT TRANSMIT

NOISE OR VIBRATION TO THE OCCUPIABLE SPACES.

21. PROVIDE FIRE SAFING APPROVED BY THE AUTHORITY HAVING JURISDICTION, AROUND ALL PIPING

AND DUCTWORK PENETRATIONS THROUGH BUILDING CONSTRUCTION TO MAINTAIN FIRE, SMOKE,

AND SOUND RATINGS.

22. THE CONTRACTOR SHALL FURNISH AND INSTALL ACCESS PANELS WHERE REQUIRED FOR ACCESS TO EQUIPMENT, VALVES, DAMPERS, CONTROLS, ETC. IN DUCTWORK AND/OR CONCEALED BEHIND

FINISHES NOT INTENDED TO BE REMOVED; COORDINATE WITH THE ARCHITECT PRIOR TO ANY

INSTALLATION.

23. MECHANICAL CONTRACTOR SHALL PROVIDE ALL MOTOR STARTERS, DISCONNECTS ETC. AS

REQUIRED BY THE MECHANICAL EQUIPMENT; THE ELECTRICAL CONTRACTOR SHALL INSTALL AND

PROVIDE FINAL CONNECTIONS. WHERE THE MECHANICAL SYSTEMS COME WITH INTEGRAL

STARTERS, DISCONNECTS, ETC., THE ELECTRICAL CONTRACTOR SHALL PROVIDE FINAL

CONNECTIONS.

24. ALL EQUIPMENT MUST BE INSTALLED SUCH THAT FACTORY REQUIRED CLEARANCES FOR

SERVICEABILITY ARE MAINTAINED. NOTIFY THE ENGINEER IMMEDIATELY SHOULD ANY EQUIPMENT HAVE ACCESS LIMITED BECAUSE OF FIELD CONDITIONS, EQUIPMENT ORIENTATION, ETC. DO NOT

INSTALL THIS EQUIPMENT UNTIL THE SITUATION HAS BEEN RESOLVED.

25. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE

AND FUNCTIONAL SYSTEM, INCLUDING BUT NOT LIMITED TO, WIRING, TRANSFORMERS,

HARDWARE, PARTS AND ACCESSORIES INCLUDING ALL SAFETY DEVICES REQUIRED IN

ACCORDANCE WITH ALL CODE REQUIREMENTS. THE CONTROLS CONTRACTOR SHALL PROVIDE

POWER TO ALL CONTROL DEVICES AND EQUIPMENT FROM THE NEAREST ELECTRICAL PANEL

DESIGNATED FOR CONTROLS. THE CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER

REQUIREMENTS. DEVICES PROVIDED BY UNIT MANUFACTURERS SHALL BE INSTALLED AND WIRED

BY THE CONTROLS CONTRACTOR UNLESS INDICATED OTHERWISE.

26. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES, AND STATE CODES.

27. CONTRACTOR SHALL COMPLY WITH ALL OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

(OSHA) AND ENVIRONMENTAL PROTECTION AGENCY (EPA) REQUIREMENTS.

28. CONTRACTOR SHALL COMPLY WITH RULES AND REGULATIONS OF THE GOVERNMENT.

29. CLEAN UP ALL WASTE AND DEBRIS AT THE END OF EACH WORKING DAY AND AS REQUIRED TO

KEEP ALL BUILDING AREAS CLEAN, CLEAR AND UNOBSTRUCTED. AT THE COMPLETION OF THE

PROJECT, THE CONTRACTOR SHALL REMOVE ALL TOOLS, APPLIANCES, SURPLUS MATERIAL AND

SCRAP FROM THE JOB SITE.

30. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND

ELECTRICAL UFGS.

NOTE:

ALL SYMBOLS MAY NOT APPEAR ON THE DRAWINGS.

DETAIL NUMBER

WHERE THE DETAIL IS DRAWN

MECHANICAL GENERAL

NOTES, SYMBOLS &

ABBREVIATIONS

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:33 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M001.dwg Save Date: 04/23/2018 05:54 PM

M001

GENERAL NOTES

1. EXISTING WORK SHOWN IS BASED ON AVAILABLE DOCUMENTATION

AND SPOT CHECKS ON SURVEY. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS AND COORDINATE WITH ENGINEER PRIOR TO

PROCEEDING WITH WORK.

2. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL HVAC DEVICES

WITHIN THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE

CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING

CONDITIONS WITH IN THE PROJECT AREA. ANY DISCREPANCIES OR

CONDITIONS NOT SHOWN ON THIS PLAN SHALL BE COORDINATED.

3. CONTRACTOR TO FIELD COORDINATED ALL REMOVAL/ STORAGE/

DISPOSAL OF EXISTING EQUIPMENT WITH THE OWNERS.

4. WHERE DUCTWORK, PIPING, AND EQUIPMENT ARE INDICATED TO BE

REMOVED, REMOVE EXISTING CONCRETE INSERTS AND

STRUCTURAL ATTACHMENTS, AND PATCH CONCRETE SURFACE TO

MATCH ADJACENT.

5. CONTRACTOR SHALL SCHEDULE ALL WORK IN ACCORDANCE WITH

OWNER'S REQUIREMENTS.

SHEET KEY NOTES

1. EXISTING RADIANT GAS HEATER TO BE RELOCATED. DISCONNECT

GAS LINE. FOR NEW LOCATION SEE M101.00 REUSE ROOF OPENING

FOR NEW FLUE TIE-IN. SALVAGE THERMOSTATS FOR REUSE.

SCALE:

MECHANICAL DEMOLITION FLOOR PLAN

1/8" = 1'-0"

MECHANICAL DEMOLITION

FLOOR PLAN

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:38 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_MD101.dwg Save Date: 04/23/2018 05:53 PM

NORTH

1/8" = 1'-0"

4'0 8' 16'

MD101

EF-1A

SG-1

200 CFM

TYP. FOR 20

MAU-1

CRG-1

2000 CFM

EF-2

UH-1B

UH-1A

EF-1B

CRG-1

2000 CFM

CRG-1

1200 CFM

14"Ø

"Ø

18"Ø

18"Ø

"Ø

"x

TRANSITION

FROM SQUARE

TO ROUND

SEE DETAIL 6

ON M-701 FOR

CONCRETE PAD

DETAIL.

GENERAL NOTES

1. REFER TO DRAWING M-001.00 FOR GENERAL NOTES, SYMBOLS &

ABBREVIATIONS.

2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL NECESSARY

DUCTWORK DROPS, RISERS OR TRANSITIONS REQUIRED FOR

COORDINATION WITH STRUCTURAL BEAMS, SPRINKLER HEADS,

SPRINKLER PIPING & LIGHTING FIXTURES.

3. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN

ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS AND

CODE REQUIREMENTS.

4. PROVIDE MANUFACTURER RECOMMENDED EQUIPMENT

CLEARANCES FOR MAINTENANCE PURPOSES FOR ALL EQUIPMENT.

5. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LOCATIONS AND

CLEARANCES PRIOR TO START OF CONSTRUCTION.

6. FOR TYPE & SIZE OF MECHANICAL EQUIPMENTS REFER TO

SCHEDULE ON DWG. M-601.00.

SHEET KEY NOTES

1. RELOCATE EXISTING GAS FIRED RADIANT HEATERS TO LOCATION

SHOWN.

2. CONTRACTOR TO PROVIDE NEW MAU. PROVIDE CONCRETE PAD

3. PROVIDE NEW EXHAUST FAN, INTERCONNECT WITH MAU

OPERATION. PROVIDE VIBRATION ISOLATION AND ALL NECESSARY

ACCESSORIES

4. PROVIDE NEW EXHAUST FAN WITH MANUAL CONTROLS. PROVIDE

VIBRATION ISOLATION AND ALL NECESSARY ACCESSORIES.

5. PROVIDE GAS FIRED UNIT HEATER WITH A THERMOSTAT

6. PROVIDE GALVANIZED STEEL ROUND SUPPLY DUCT

SCALE:

MECHANICAL NEW WORK FLOOR PLAN

1/8" = 1'-0"

MECHANICAL NEW WORK

FLOOR PLAN

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:43 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M101.dwg Save Date: 04/23/2018 05:55 PM

NORTH

1/8" = 1'-0"

4'0 8' 16'

M101

MECHANICAL SCHEDULES

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:47 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M601.dwg Save Date: 04/23/2018 05:56 PM

MAKE UP AIR UNIT

UNIT NO LOCATION SERVICE

AIR CAPACITY

(CFM)

FAN DATA HEATING GAS

PRESSURE

(MIN / MAX)

INCHES

ELECTRICAL DATA

UNIT

WEIGHTS LBS BASIS OF DESIGNESP HP RPM FLA

INPUT

MBH OUTPUT MBH

TEMP RISE

(F) VOLTS PHASE CYCLE (HZ)

MAU-1 GROUND

NEW ANIMAL

BEHAVIORAL

LABS

4,000 1.5 2 1,100 3 400 324 230 1 60 805 REZNOR RDH-400A

NOTES:

1. PROVIDE MAKE UP AIR UNIT WITH 18" PRE FABRICATED ROOF CURB.

2. FANS SHALL BE INTERNALLY ISOLATED.

3. PROVIDE UNTIS WITH DISCONNECT SWITCHES SUTIABLE FOR OUTDOOR INSTALLATION.

4. PROVIDE UNITS WITH VARIABLE FREQUENCY DRIVE AND TIE IT IN WITH EMS PLUS DEMAND CONTROL SYSTEM .

EXHAUST FAN SCHEDULE

UNIT NO TYPE SERVICE DRIVE TYPE CFM

ESP (IN.

WG)

MOTOR

RPM MOTOR SIZE

ELECTRICAL

WEIGHT

(LBS)

SONES

METHOD OF CONTROL BASIS OF DESIGN REMARKSVOLTS PHASE HERTZ FLA (A) INLET RADIATED

EF-1A INLINE BEHAVIORAL ROOM DIRECT 2,000 1 1,100 0.37BHP 115 1 60 14.2 122 4.4 - INTERLOCK WITH MAU-1 OPERATION GREENHECK CSP-A3600 1,2

EF-1B INLINE BEHAVIORAL ROOM DIRECT 2,000 1 1,100 0.37BHP 115 1 60 14.2 122 4.4 - INTERLOCK WITH MAU-1 OPERATION GREENHECK CSP-A3600 1,2

EF-2 INLINE FEED ROOM DIRECT 1,200 1 1,450 0.32BHP 115 1 60 7.8 59 4.8 - MANUAL GREENHECK CSP-A1410 1,2

NOTES:

1. PROVIDE EXHAUST FANS WITH GRAVITY BALANCED BACKDRAFT DAMPER.

2. PROVIDE FAN WITH NEMA RATED DISCONNECT SWITCH WITH WEATHERPROOF COVER SUITABLE FOR WET LOCATION.

AIR DEVICE SCHEDULE

UNIT SERVICE CFM RANGE MAX SP (IN WG) MAX NC NECK SIZE (IN) SIZE DEVICE TYPE BASIS OF DESIGN REMARKS

SG-1 SUPPLY 0-200 0.046 13 N/A 12X6 SUPPLY GRILLE TITUS 1,2,3,4,6

EG-1 EXHAUST 1000-2000 0.23 36 22X22 24X24 EXHAUST GRILLE TITUS 1,3,6

NOTES:

1. ALL SUPPLY DIFFUSERS SHOULD BE PROVIDED WITH ADJUSTABLE PATTERN FOR VERTICAL AND HORIZONTAL DISCHARGE.

2. PROVIDE OPPOSED BLADE DAMPERS TO ADJUST THE AIRFLOW THROUGH THE FACE OF THE REGISTER.

3. DIFFUSER SHALL BE CONSTRUCTED OF 24 GAUGE STEEL.

4. GRILLE SHALL BE PROVIDED WITH BORDER FRAME.

5. THERMAFUSERS SHALL BE PROVIDED WITH 30% SETTING AND WITHOUT RELIEF RING.

6. DIFFUSER/GRILLE SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASHRAE STANDARD 70-2006.

GAS UNIT HEATER SCHEDULE

UNIT MARK LOCATION TYPE KW BTUH FLA VOLTS/PH/HZ BASIS OF DESIGN REMARKS

UH-1A RESEARCH LAB SUSPENDED 44 150,000 1.9 208/1/60 REZNOR SC150 SEE NOTES

UH-1B RESEARCH LAB SUSPENDED 44 150,000 1.9 208/1/60 REZNOR SC150 SEE NOTES

NOTES:

1. THERMAL CUTOUT SHALL BE PROVIDED WITHIN THE UNITS BY THE MANUFACTURER.

2. PROVIDE UNIT WITH LOCAL SWITCH AND BUTTON TYPE TEMPERATURE SENSOR IN VESTIBULE AREA SET AT 70⁰ F.

3. PROVIDE UNIT WITH 3-SPEED CONTROL

M601

MAXIMUM ALLOWABLE HANGER

LOAD

STRAPS LBS RODS LBS

2-1"x22 GA 520 2-1/4" Ø 540

2-1"x20 GA 640 2-3/8" Ø 1360

2-1"x18 GA 840 2-1/2" Ø 2500

2-1"x16 GA 1400 2-5/8" Ø 4000

TURN STRAP

SECURE STRAP HANGER

TO STRUCTURE

1"x18 GAGE STRAP HANGERS UP THRU 30"Ø 1"x1/8" ABOVE 30"Ø AT 10' OFF

CENTER

ROUND DUCT

SHEET METAL

SCREWS

SHEET METAL

SCREWS

1"x1/8" STRAPS

1-1/4"x1/8" RING

SECURE

STRAPS TO

BEAM WITH LAG

SCREWS

DUCT-SEE PROJECT

PLANS FOR SIZE

ROUND DUCT

SCALE:

ROUND DUCT HANGER DETAIL

NOT TO SCALE

M-701

BIRDPROOF & RAINPROOF

CAP

CAULK WEATHERTIGHT

ROOF FLASHING SET IN

CAULK - WATER TIGHT &

SCREW TO SHEET METAL

ROOF

PROVIDE 18 GA ANGLE

BRACKETS TO SUPPORT

STACK SUPPORT BRACKET

STACK SUPPORT

BRACKET

TYPE B GAS VENT

EXISTING FORMED METAL

WALL PANELS

CAULK WEATHER TIGHT

ALIGN HOOD WITH BOT.

OF EXISTING TRUSSES

PAINT WITH MINIMUM TWO

COATS OF ALUMINIZED

WEATHERPROOFING

PAINT

FRAMING & BLOCKING

AS REQ'D

MOTORIZED SHUTTER 115V

[SIMILAR TO FAN JET

SYSTEM INTAKE]

26" x 26" [.66 x .66 M]

SCALE:

GAS VENT DETAIL

NOT TO SCALE

M701

SCALE:

WALL INTAKE DETAIL

NOT TO SCALE

M701

2' -0

.6

M

[M

IN

SCALE:

INLINE FAN DETAIL

NOT TO SCALE

M-701

NOTES:

1. FAN SHALL BEAR THE AMCA SEAL FOR AIR AND SOUND PERFORMANCE.

2. UNIT SHALL HAVE FACTORY MOUNTED TERMINAL BOX.

INTAKE AIR

SUPPORT ROD FROM

STRUCTURE FROM

ABOVE (TYP OF 4)

DUCTWORK

FORWARD CURVED FAN WHEEL

FAN HOUSING

REMOVABLE ACCESS PANEL

1/2" ACOUSTIC LINING

GALVANIZED

STEEL HOUSING

FLEXIBLE CONNECTION

(TYP)

STEEL SPRING & RUBBER

IN SHEAR TYPE VIBRATION

ISOLATORS (TYP OF 4)

AIR OUT

SCALE:

TYPICAL EXHAUST GRILLE DETAIL

NOT TO SCALE

M-701

MAIN EXHAUST

DUCT

AIR FLOW

MAX. HANGER SPACING

METAL DUCT

* 10 FT (3M) RECTANGULAR.

* 12 FT (3.7M) ROUND.

WIRE MESH SCREEN

SCALE:

OUTDOOR EQUIPMENT PAD DETAIL

NOT TO SCALE

M701

1' - 0"

2'

6" M

IN

#4 CONT.

2 12" CLR.

5" S

.O .G

2-#4 CONT.

#4 @ 18"

2 12" CLR.

2 (MIN.)

30"

6" 6x6 WELDED

WIRE FABRIC

12" MAX,

8" MIN

MIN 4” COMPACTED

GRAVEL BASE

MECHANICAL DETAILS

M701

Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:52 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M701.dwg Save Date: 04/23/2018 05:58 PM

ELECTRICAL GENERAL NOTES

I. GENERAL:

A. BEFORE SUBMITTING BID. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

VISITING THE SITE TO VERIFY/EXAMINE THE EXACT EXTENT OF EXISTING CONDITIONS. NO

CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR

FOR ANY ALLEGED MISUNDERSTANDING OF WORK TO BE PERFORMED. THE CONTRACTOR

SHALL INCLUDE IN HIS BID PRICE ALL LABOR AND MATERIAL THAT MAY EFFECT HIS WORK.

B. THE GENERAL EXTENT OF EXISTING ELECTRICAL WORK TO BE DISMANTLED AND REMOVED

OR RELOCATED IS INDICATED ON THE DRAWINGS.

C. ALL COMPONENTS ASSOCIATED WITH SYSTEMS AND EQUIPMENT TO BE REMOVED OR

RELOCATED MAY NOT BE SPECIFICALLY INDICATED. REMOVE ALL ASSOCIATED ELECTRICAL

COMPONENTS, HANGERS, WIRING, CABLING, CONDUIT, BOXES, DEVICES AND ALL OTHER

ITEMS RELATED TO EQUIPMENT AND MATERIALS WHICH ARE INDICATED TO BE REMOVED OR

RELOCATED. REMOVE ALL WIRING/CONDUIT BACK TO THE SOURCE IN EXISTING CIRCUITS

WHICH ARE BEING DEMOLISHED. UNLESS SPECIFICALLY INDICATED, NO EQUIPMENT,

MATERIALS OR ASSOCIATED COMPONENTS SHALL BE ABANDONED IN PLACE.

D. ABANDONED ALL CONDUITS WHICH ARE CONCEALED IN CONCRETE WALLS OR SLABS AND

REMOVE ALL WIRING/CABLES FROM ABANDONED CONDUITS.

II. DISPOSAL OF DEMOLITION:

A. CONTRACTOR SHALL CLEAN THE PROJECT SITE AT THE END OF EACH WORKING DAY.

CONTRACTOR SHALL NOTIFY BUILDING OWNER PRIOR TO DISPOSAL OF ALL DEMOLISHED

MATERIALS TO ALLOW THE OWNER TO SALVAGE ANY USABLE MATERIALS. AFTER INSPECTING

FROM THE OWNER'S REPRESENTATIVE ALL UNUSED MATERIALS SHALL BE REMOVED FROM

THE JOB SITE WITH DISPOSAL IN ACCORDANCE WITH APPLICABLE SPECIFICATIONS AND

REGULATIONS.

III. PROTECTION:

A. PROTECT FROM DAMAGE ALL EXISTING WORK TO REMAIN. ANY EXISTING TO REMAIN OR

EXISTING TO BE RELOCATED MATERIALS AND EQUIPMENT DAMAGED DURING THE COURSE

OF THE WORK SHALL BE REPLACED WITH MATERIALS AND EQUIPMENT CONFORMING TO

THESE SPECIFICATIONS AT NO ADDITIONAL COST TO THE OWNER. CARE MUST TAKEN IN

REMOVING ALL EXISTING MATERIALS.

IV. TERMINATION AND PATCHING:

A. DISCONNECT EXISTING TO BE REMOVED OR EXISTING TO BE RELOCATED CONDUIT, WIRING, CABLING, AND EQUIPMENT FROM EXISTING TO REMAIN POINT INDICATED. IF NOT INDICATED

ON THE PLANS, VERIFY WITH THE DESIGN ENGINEERS OR BUILDING OWNER'S

REPRESENTATIVE PRIOR TO DISCONNECTION.

B. WHERE EXISTING FLOORS, WALLS AND ROOFS MUST BE CUT OR ARE DAMAGED DURING

REMOVAL OR RELOCATION OF ELECTRICAL WORK, PATCH THE CUT OR DAMAGED AREAS TO

MATCH ADJACENT CONSTRUCTION.

C. THE CONTINUITY OF ALL EXISTING CONDUITS AND FEEDERS SERVICING AREAS TO REMAIN

SHALL BE MAINTAINED. MODIFY THE EXISTING CIRCUITS IF REQUIRED IN ORDER TO MAINTAIN

THE EXISTING CIRCUITRY.

ELECTRICAL GENERAL DEMOLITION NOTES

REFER TO THE LIGHTING FIXTURE SCHEDULE ON DRAWINGS E600 FOR LIGHTING FIXTURE SPECIFICATIONS.

WALL-MOUNTED DUPLEX OR QUAD RECEPTACLE, 20A, 125V, NEMA 5-20R.

OUTLETS MAY HAVE THE FOLLOWING SUBSCRIPTS:

WALL-MOUNTED ABOVE COUNTER DUPLEX OR QUAD RECEPTACLE, 20A, 125V, NEMA 5-20R

FLUSH FLOOR MOUNTED DUPLEX / QUADRUPLEX NEMA 5-20R RECEPTACLE, 20A, 125V

POKE THRU OUTLET. COORDINATE POKE THRU FINISH SPECIFICATION AND EXACT LOCATION

WITH ARCHITECT.

FLUSH MOUNTED ADA COMPLIANT COMBINATION DUPLEX/QUADRUPLEX POWER AND

TELE-DATA-AV POKE THRU OUTLET. REFER TO TECHNOLOGY PATHWAY DRAWINGS FOR

TELE-DATA-AV OUTLET REQUIREMENTS. COORDINATE POKE THRU FINISH, SPECIFICATION AND

EXACT LOCATION WITH ARCHITECT AND TECHNOLOGY CONSULTANT. BASIS OF

DESIGN, WIREMOLD EVOLUTION 8AT SERIES

RECESSED CEILING MOUNTED DUPLEX OR QUADRUPLEX NEMA 5-20R RECEPTACLE, 20A, 125V

WALL-MOUNTED DUPLEX OR QUADRUPLEX TAMPER PROOF RECEPTACLE, 20A, 125V,

NEMA 5-20R.

WALL/FLOOR/CEILING MOUNTED COMBINATION TELEPHONE/DATA OUTLET

SINGLE POLE TOGGLE SWITCH

3 - WAY SWITCH

3-WAY DUAL SWITCH WITH 50% STEP DIMMING BALLASTS

KEY OPERATED SWITCH

DIMMER SWITCH RATED FOR 2000 WATTS. PROVIDE NECESSARY MODULES FOR LED

LAMP SOURCE

MOTOR RATED SWITCH WITH THERMAL OVERLOAD CURRENT PROTECTION.

MOUNTED @ 48" AFF OR UNIT MOUNTED

WALL/CEILING MOUNTED LOW VOLTAGE OCCUPANCY SENSOR SWITCH CONFIGURED AS

AUTO-ON, AUTO-OFF, UON. CONFIGURE TIME-OUT SETTING FOR 15 UNLESS OTHERWISE

NOTED. DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:

2 : DUAL SWITCH

WALL/CELING/FLOOR MOUNTED JUNCTION BOX. FIELD COORDINATE EXACT LOCATION

AND MOUNTING HEIGHT.

MD : INDICATES MOTORIZED DAMPER

NON-FUSIBLE DISCONNECT SWITCH

FUSIBLE DISCONNECT SWITCH.

COMBINATION STARTER DISCONNECT SWITCH.

MOTOR - SEE FLOOR PLANS AND MECHANICAL SCHEDULE FOR RATING

DRY TYPE TRANSFORMER, SEE FLOOR PLANS AND POWER RISER FOR SIZE

120/208V ELECTRICAL PANEL

CIRCUIT HOMERUN TO DESIGNATED PANEL. NUMBER OF ARROWS INDICATE NUMBER

OF CIRCUITS AND TEXT DENOTES PANELBOARD. TICK MARKS INDICATE NUMBER OF AWG

WIRES CONTAINED IN CONDUIT WHEN MORE THAN TWO. TICK MARKS WITH:

( ) DENOTES SEPARATE EQUIPMENT GROUND WIRE.

( ) DENOTES SEPARATE ISOLATED GROUND WIRE.

EACH CIRCUIT HOMERUN SHALL BE PROVIDED WITH DEDICATED

NEUTRAL

UNDERGROUND OR PLATFORM WIRING/CONDUIT

KEYED DRAWING NOTE

SPLIT CIRCUIT

WALL MOUNTED TELEPHONE OUTLET.

WALL/FLOOR/CEILING MOUNTED DATA OUTLET.

480/277V ELECTRICAL PANEL

CS CURRENT SENSOR

DUAL SWITCH WITH 50% STEP DIMMING BALLASTS

CONDUIT UP

CONDUIT DOWN

CONTINUOUS CIRCUITAA

C : COPIER

GFI : GROUND FAULT INTERRUPTER

WP : WEATHER PROOF OUTLET WITH PROTECTIVE COVER

ELECTRICAL SYMBOL LIST

A AMPERE

AFF ABOVE FINISHED FLOOR

AWG AMERICAN WIRE GAUGE

BRK BREAKER

C CONDUIT

CB CIRCUIT BREAKER

D EXISTING TO BE DEMOLISHED

DISC. SW. DISCONNECT SWITCH

DWG DRAWING

E, EX EXISTING TO REMAIN

EM DEVICE ON EMERGENCY CIRCUIT

EMT ELECTRICAL METALLIC TUBING

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FLA FULL LOAD AMPS

G GROUND

GFI GROUND FAULT INTERRUPTER

GRS GALVANIZED RESISTIVE CONDUIT

HP HORSE POWER

IG ISOLATED GROUND

KVA KILOVOLT-AMPS

KW KILOWATT

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

MDP MAIN DISTRIBUTION PANEL

N NEW

NEC NATIONAL ELECTRICAL CODE

NFSS NON FUSED SAFETY SWITCH

NL NIGHT LIGHT FIXTURE

NTS NOT TO SCALE

P POLE

PH, Ø PHASE

PNL PANEL

R RELOCATED AT NEW LOCATION

RR REMOVE AND RELOCATE

S/N SOLID NEUTRAL

SWBD SWITCHBOARD

XFMR TRANSFORMER

TYP. TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTS

W WATTS

WP WEATHERPROOF

(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT)

T a

3 3

K

D

M

ABBREVIATIONS

(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)

a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE IDENTIFICATION.

a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR

30 MINUTE ROTARY TYPE TIMER SWITCH WITH HOLD-ON OPTION

T

WALL/CEILING MOUNTED LOW VOLTAGE VACANCY SENSOR SWITCH CONFIGURED AS

MANUAL ON, AUTO OFF, UON. CONFIGURE TIME-OUT SETTING FOR 15 UNLESS OTHERWISE

NOTED. DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:

LP-2

GROUND BUS BAR

D : DIMMER SWITCH

2 : DUAL SWITCH

a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR

D : DIMMER SWITCH

WALL/FLOOR MOUNTED POWER WHIP

HOMERUN WIRING WITHOUT TICK MARKS SHALL INCLUDE 2#12+1#12G-3/4"C

REF : REFRIGERATOR

USB : COMBINATION DUPLEX RECEPTACLE WITH 2-USB CHARGING PORTS. (BLUE COLOR)

DW : DISHWASHER

1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING

REGULATIONS, CODES, ETC.

A. LOCAL CODES AND ORDINANCES

B. THE EDITION OF THE NATIONAL ELECTRICAL CODE NFPA 70 (NEC) IN EFFECT.

2. PRIOR TO BEGINNING ANY WORK, SECURE NECESSARY PERMITS OR CLEARANCES FROM

THE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL LABOR AND MATERIALS FOR A

COMPLETE INSTALLATION. WORK SHALL BE EXECUTED BY EXPERIENCED ELECTRICIANS

WHO ARE LICENSED IN THE JURISDICTION WHERE THE PROJECT IS LOCATED.

3. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BE MAINTAINED.

4. THE ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. COORDINATE ELECTRICAL

EQUIPMENT LOCATION AND INSTALLATION WITH EQUIPMENT BEING SERVED. PROVIDE

ALL POWER AND TELECOMMUNICATION FINAL CONNECTIONS TO THE SYSTEM

FURNITURE AS REQUIRED.

5. ALL EQUIPMENT SUCH AS RELAYS, SWITCHES, PANELS, AND OTHER APPURTENANCES

SHALL HAVE IDENTIFICATION PLATES OF BLACK LAMINATED PLASTIC WITH 1/2" WHITE

LETTERS. ALL JUNCTION BOXES IN CEILING CAN BE MARKED WITH BLACK PERMANENT

MARKER ON COVER PLATES AS PANEL DESIGNATION AND CIRCUIT NUMBER FROM WHICH

THEY ARE FED.

6. ALL CONDUCTORS SHALL BE IDENTIFIED. ALL WIRING DEVICES SHALL BE USED WITH

TYPED LABEL ON THE COVER PLATE IDENTIFYING THE PANEL DESIGNATION AND CIRCUIT

NUMBER FROM WHICH THEY ARE FED.

7. ALL EQUIPMENT SHALL BE "UL" LISTED.

8. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL

ELECTRICAL CODE.

9. ALL CONNECTIONS TO DEVICES SHALL BE TAPED WITH SCOTCH 33 ELECTRICAL TAPE.

10. ALL CONDUITS AND JUNCTION BOXES SHALL BE CONCEALED IN FINISHED AREAS. PRIOR

TO CONCEALMENT OF NEW CONSTRUCTION, ALL WORK BEHIND FINISHED SURFACES

SHALL BE INSPECTED BY THE OWNER'S REPRESENTATIVE.

11. CONTRACTOR SHALL INFORM THE OWNER'S REPRESENTATIVE PRIOR TO BEGINNING

CONSTRUCTION AND PRIOR TO COMPLETION OF CONSTRUCTION TO ALLOW SUFFICIENT

TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION

WORK.

12. CONTROL WIRING SHALL BE TAGGED AT EACH END AND TERMINATED WHERE WORK HAS

BEEN PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURES SPECIFICATIONS.

13. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR

SHALL BE LIABLE FOR ITS REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE OR

IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE MATERIAL OR EQUIPMENT

DOES NOT MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS.

14. THE CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST, ANY LABOR,

MATERIALS, SERVICES, APPARATUS, AND DRAWINGS IN ADDITION TO CONTRACT

DOCUMENTS, IN ORDER TO COMPLY WITH ALL APPLICABLE LAWS, INDICATED AND/OR

SPECIFIED. PROVIDE ALL ELECTRICAL EQUIPMENT WITH ALL NECESSARY ASSOCIATED

ACCESSORIES AND CONDUIT INFRASTRUCTURE AS REQUIRED…