Exhibit A - Drawings for Recent Work.pdf
PDF 5 MB Posted
- Attached to
- Design-Build Miscellaneous Repairs Federal contract opportunity
- Solicitation number
- 12505B21R0002
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign In Sheets.pdf | ||
| SF-30 Amendment 01.pdf | ||
| SF-1442 with Clauses and Provisions.pdf | ||
| Statement of Work.pdf | ||
| Exhibit C - Make Up Air Unit O-M Manual Part 1.pdf | ||
| Exhibit D - Make Up Air Unit O-M Manual Part 2.pdf | ||
| ARS Facilities Design Standards.pdf | ||
| Exhibit B - Specifications for Recent Work.pdf | ||
| Exhibit E - Electrical O-M Manual.pdf | ||
| Exhibit F - Test and Balance Report.pdf | ||
| ARS-371.pdf | ||
| Wage Determination.pdf | ||
| ARS-372.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
600 N.
750 N.
500 N.
ANIMAL
BEHAVIOR
LAB
S A
LI
S
B U
R Y
S T.
UNION
ST.
LAFAYETTE
WEST
LAFAYETTE
CO.RD 750 NORTH
U S
SCALE:
SITE LOCATION PLAN
NTS
SCALE:
VICINITY PLAN
NTS
ANIMAL
BEHAVIOR LAB
WABASH RIVER
NORTHWESTERN
AVE
MAIN ST.
LIST OF DRAWINGS
SHEET DWG. TITLE
AD101 ARCHITECTURAL DEMO3
A101 FIRST FLOOR PLAN - NEW CONSTRUCTION4
A401 BUILDING AND WALL SECTIONS
A402 EXISTING BUILDING SECTIONS AND DETAILS
P001
P101
PLUMBING REMOVAL PLAN
P102
PLUMBING NEW WORK FLOOR PLAN - GAS AND WATER
PLUMBING PLANS - SANITARY - DEMOLITION AND NEW WORK
P501 PLUMBING GAS RISER DIAGRAM AND DETAILS
P701 PLUMBING DETAILS
PD101
15 M001 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
M101
MECHANICAL DEMOLITION FLOOR PLAN
17 MECHANICAL NEW WORK FLOOR PLAN
M601 MECHANICAL SCHEDULES
M701 MECHANICAL DETAILS
MD101
E001
22 E101
ELECTRICAL DEMOLITION PLAN
ELECTRICAL LIGHTING PLAN
E501 ELECTRICAL POWER RISER DIAGRAM AND PANEL SCHEDULES
E701 ELECTRICAL DETAILS
ED101
E201 ELECTRICAL POWER PLAN
1 CS COVER SHEET
ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
PLUMBING GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
A001 ARCHITECTURAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
A102 DOOR SCHEDULE, FINISH SCHEDULE
A103 ARCHITECTURAL DETAILS
Xref O:\2017\SAGQ178056.02\90-SAGQ178056.02_XREF\178056.02 _TB-36x24.dwg
COVER SHEET
CS
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:29:58 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_COVER SHEET.dwg Save Date: 04/24/2018 12:23 PM
USDA AGRICULTURAL RESEARCH SERVICE
FY17-MWA-1
LBRU ANIMAL HOLDING AREA
WEST LAFAYETTE, IN
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:01 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A001.dwg Save Date: 04/24/2018 01:28 PM
GENERAL NOTES, SYMBOLS
AND ABBREVIATIONS
A001
1/8" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:08 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_AD101.dwg Save Date: 04/23/2018 04:57 PM
ARCHITECTURAL DEMO
AD101
Plotted By: Plot Date: 4/24/2018 1:30:17 PM Saved By: Save Date:
1-1/2" = 1'-0"
1/8" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:17 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A101.dwg Save Date: 04/24/2018 11:39 AM
FIRST FLOOR PLAN NEW
CONSTRUCTION
A101
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:22 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A102.dwg Save Date: 04/24/2018 11:40 AM
DOOR AND FINISH
SCHEDULE
A102
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:32 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A103.dwg Save Date: 04/24/2018 11:47 AM
ARCHITECTURAL DETAILS
A103
1/4" = 1'-0"
3/4" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:44 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A401.dwg Save Date: 04/23/2018 05:35 PM
BUILDING AND WALL
SECTIONS
A401
1/4" = 1'-0"
3/4" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:30:58 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\10-SAGQ178056.02_ARCH\178056.02_A402.dwg Save Date: 04/24/2018 11:30 AM
EXISTING BUILDING
SECTIONS & DETAILS
A402
ABBREVIATIONS
AAV AIR ADMITTANCE VALVE
ABV ABOVE
AD AREA DRAIN
ADA AMERICAN DISABILITY ACT
AFF ABOVE FINISHED FLOOR
AP ACCESS PANEL
ARCH ARCHITECTURAL
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASSE AMERICAN SOCIETY OF SANITARY ENGINEERS
BLDG BUILDING
BLW BELOW
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWV BACK WATER VALVE
CA COMPRESSED AIR
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CONT CONTINUATION
CW COLD WATER
DD DECK DRAIN
DFU DRAINAGE FIXTURE UNIT
DIA DIAMETER
DMR DISTRIBUTED METER ROOM
DN DOWN
DWG DRAWING
DWH DOMESTIC WATER HEATER
DF DRINKING FOUNTAIN
E EXISTING
EA EACH
EQUIP EQUIPMENT
ERD EMERGENCY ROOF DRAIN
ERD(G) EMERGENCY ROOF DRAIN-GREEN ROOF
EST EMERGENCY STORM
EST(G) EMERGENCY STORM-FROM GREEN ROOF
ET EXPANSION TANK
ETR EXISTING TO REMAIN
F WATER FILTER
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FL FLOOR
FS FLOW SWITCH
FT FEET
FM FORCED MAIN
GAL GALLON
GCO GRADE CLEAN OUT
GD GARBAGE DISPOSAL
GH GARDEN HYDRANT
GPM GALLONS PER MINUTE
HB HOSE BIB
HDPE HIGH DENSITY POLYETHYLENE
HP HORSE POWER
HW HOT WATER SUPPLY
HWR HOT WATER RETURN
HPCW HIGH PRESSURE COLD WATER
HWSH HOT WATER STORAGE/HEATER
IN INCH
INV INVERT
KW KILOWATT
LAV LAVATORY
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MECH MECHANICAL
MFR MANUFACTURER
MGCV MASTER GAS CONTROL VALVE
MIN MINIMUM
MS MOP SINK
MTD MOUNTED
N NEW
NC NORMALLY CLOSED
NFWH NON FREEZE WALL HYDRANT
NG NATURAL GAS
NIC NOT IN CONTRACT
NO. NUMBER
NO NORMALLY OPEN
NT ACID NEUTRALIZATION TANK
ORD OVERFLOW ROOF DRAIN
ORD(G) OVERFLOW ROOF DRAIN-GREE ROOF
OSD OPEN SITE DRAIN
P PUMP
PD PLANTER DRAIN
PDD POOL DECK DRAIN
PDI PLUMBING AND DRAINAGE INSTITUTE
PH PHASE (ELECTRICAL)
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
RCV RISER CONTROL VALVE
REF REFRIGERATOR
RD ROOF DRAIN
RD(G) ROOF DRAIN-GREEN ROOF
RH ROOF HYDRANT
RPM REVOLUTIONS PER MINUTE
RR RAINWATER REUSE
RW RAIN WATER
RWC RAIN WATER CONDUCTOR
SA SHOCK ABSORBER
SAN SANITARY/WASTE PIPE
SF SQUARE FEET
SFU SUPPLY FIXTURE UNIT
SS STAINLESS STEEL
SS SERVICE SINK
ST STORM WATER
ST(G) STORM-FROM GREEN ROOF
STRUC STRUCTURAL
TD TRENCH DRAIN
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER TUBE
TW TEMPERED WATER
TYP TYPICAL
UR URINAL
V VENT PIPE
VTR VENT THRU ROOF
W WATT
WD WASTE DISPOSER
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT
WM WATER METER
WTR WATER
W/ WITH
W/O WITHOUT
PLUMBING SYMBOLS
NOTE: ALL SYMBOLS MAY NOT APPEAR ON THE DRAWINGS.
REDUCED PRESSURE ZONE BACKFLOW PREVENTER (ASSE1013)
BALL VALVE
CHECK VALVE
DOUBLE CHECK VALVE BACKFLOW PREVENTER (ASSE 1015,1048)
SOLENOID VALVE
GATE VALVE
PRESSURE REDUCING VALVE
THERMOSTATIC MIXING VALVE
PLUG VALVE
BACKFLOW PREVENTER (ASSE 1015 &1024)
PUMP
WATER HAMMER ARRESTOR ('A' = PDI SIZE)
PRESSURE GAUGE
THERMOMETER GAUGE
AQUASTAT VALVE
BALANCING VALVE
PIPE VALVES AND ACCESSORIES
VACUUM RELIEF VALVE
STRAINER
REDUCER/INCREASER
CAPPED CONNECTION
PIPE UNION
ELBOW TURNED UP
TEE UP
TEE DOWN
SHUT-OFF VALVE IN RISER
ELBOW TURNED DOWN
PIPE FITTINGS
COLD WATER PIPING
HOT WATER PIPING
HOT WATER RETURN PIPING
GAS PIPING
SANITARY PIPING ABOVE GROUND
VENT PIPING
STORM WATER PIPING ABOVE GROUND
PIPE REPRESENTATION
STORM WATER PIPING BELOW GROUND
SANITARY PIPING BELOW GROUND
G
STORM WATER PIPING FROM GREEN ROOF ABOVE GROUND
STORM WATER PIPING FROM GREEN ROOF BELOW GROUND
GENERAL PLUMBING NOTES
1. ALL PLUMBING WORK SHALL COMPLY WITH THE 2012 INTERNATIONAL PLUMBING CODE.
2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES AND TAXES.
3. CONTRACTOR SHALL MAKE NO CHANGES WITHOUT THE WRITTEN PERMISSION FROM THE ARCHITECT.
4. CONTRACTOR ASSUMES RESPONSIBILITY FOR PROPER ARRANGEMENT OF PIPE, FIXTURES, ETC TO CONNECT APPROVED EQUIPMENT IN A PROPER AND APPROVED MANNER. CONTRACTOR SHALL FOLLOW EQUIPMENT MANUFACTURER'S DETAILED INSTRUCTIONS AND THE CONTRACT DOCUMENTS. NOTIFY THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH ALL WORK.
NO EQUIPMENT INSTALLATION OR CONNECTIONS SHALL BE MADE IN A MANNER THAT VOIDS THE MANUFACTURER'S
WARRANTY.
5. BEFORE POURING CONCRETE FLOORS INSTALL ALL REQUIRED SLEEVES.
6. DO NOT CUT STRUCTURAL MEMBERS WITHOUT THE APPROVAL OF THE ARCHITECT/ENGINEER, AND PERFORM CUTTING IN A
MANNER AS DIRECTED BY A/E.
7. PROVIDE SLEEVES FOR ALL FLOOR PENETRATIONS WITH TOP OF SLEEVE 2' ABOVE FINISHED FLOOR.
8. PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL PLUMBING FIXTURES COMPLETELY AS SPECIFIED ON DRAWINGS.
9. PROVIDE SHUT-OFF VALVES ON ALL EQUIPMENT AND ANGLE STOPS IN HOT AND COLD WATER PIPING TO ALL PLUMBING
FIXTURES.
10. FLOOR TO BE SLOPED 1/8" TO FLOOR DRAINS. TOP OF DRAIN FLUSH WITH FINISHED FLOOR.
11. MIXING VALVES SHALL BE USED TO TEMPER HOT WATER AT ALL PUBLIC LAVATORIES AND HAND WASHING FACILITIES. SET AT
105 DEGREES F.
12. CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR ALL VALVES AND MECHANICAL EQUIPMENT.
13. MAINTAIN WORK AREA CLEAN AT ALL TIMES DURING CONSTRUCTION. AFTER COMPLETING INSTALLATION OF WORK, CLEAN ALL
FIXTURES OF ALL RUBBISH, PLASTER, DIRT AND OTHER DEBRIS.
14. TEST ALL SYSTEMS. ALL FIXTURES SHALL OPERATE SATISFACTORILY AS DESIGNED AND INTENDED. REPORT ANY DEFICIENCIES
TO THE ARCHITECT/ENGINEER.
15. ALL POTABLE WATER PIPING SHALL BE DISINFECTED AND FLUSHED IN FULL ACCORDANCE WITH THE LOCAL AUTHORITIES
HAVING JURISDICTION.
16. ALL PIPING SYSTEMS SHALL BE TESTED AT DESIGN PRESSURES FOR A PERIOD OF TIME AS PRESCRIBED BY THE LOCAL
AUTHORITIES HAVING JURISDICTION.
17. CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS, EQUIPMENT, LAYOUT DRAWINGS, AND ALL OTHER RELATED DRAWINGS AS REQUIRED FOR DIMENSIONS, DETAILS, ETC. PLUMBING LAYOUT SHOWN ON THIS DRAWING IS FOR GENERAL ARRANGEMENT ONLY. CONTRACTOR SHALL COORDINATE ALL WORK WITH FIELD CONDITIONS AND ALL OTHER TRADES INVOLVED AS REQUIRED. DO NOT SCALE DIMENSIONS FROM THIS DRAWING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN
FIELD AS REQUIRED.
18. CONTRACTOR SHALL REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND CUT SHEETS AS REQUIRED FOR
INSTALLATION OF EQUIPMENT.
19. CONTRACTOR SHALL FURNISH AND INSTALL ALL PIPING, FITTINGS, VALVES, PARTS AND ACCESSORIES REQUIRED FOR PROPER INSTALLATION AND OPERATION OF PLUMBING SYSTEM. (INCLUDING ALL FITTINGS AND DEVICES REQUIRED BY CODE, SUCH AS CHECK VALVES, VACUUM BREAKERS, SAFETY RELIEF VALVES, VACUUM RELIEF, ETC. ALL FLOOR DRAINS, WHERE REQUIRED BY
CODES AND REGULATIONS, SHALL BE PROVIDED WITH TRAP PRIMER VALVE AND FITTINGS.
20. ALL PIPING SHALL BE HUNG, FIRMLY ANCHORED AND SUPPORTED IN ACCORDANCE WITH MSS SP-58 MSS SP-69.
21. CONTRACTOR SHALL FURNISH AND INSTALL WATER SHOCK ARRESTORS DOWN STREAM OF SOLENOID AND QUICK CLOSING VALVES. AIR CHAMBERS SHALL NOT BE CONSIDERED AN EQUAL TO WATER ARRESTORS AS SPECIFIED.
22. PLUMBING CONTRACTOR SHALL PROVIDE ACCESS PANELS WHERE REQUIRED FOR ACCESS TO VALVES IN CEILINGS AND
WALLS.
23. VALVES AND FITTINGS SHALL BE OF THE SAME SIZE AS THE LINE ON WHICH THEY ARE LOCATED, UNLESS OTHERWISE
INDICATED ON DRAWINGS.
24. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY SUPPORTING DEVICES FOR ALL FIXTURES INCLUDED IN
CONTRACT OR HEREIN SPECIFIED OR OTHERWISE.
25. CONTRACTOR SHALL SLEEVE ALL PIPING CROSSING THROUGH OR UNDERNEATH STRUCTURAL MEMBERS. NOTIFY ARCHITECT AND ENGINEERS PRIOR TO PROCEEDINGS WITH WORK TO ASSURE STRUCTURAL SUPPORT WILL NOT BE AFFECTED.
26. DOMESTIC WATER SHALL BE SLOPED TO DRAIN POINTS.
27. ALL SANITARY DRAINAGE PIPING 3" AND LARGER SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/8" FALL PER 1'-0" OF RUN
OTHERWISE NOTED.
28. ALL SANITARY DRAINAGE PIPING 2" AND LESS SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/4" FALL PER 1'-0" OF RUN
OTHERWISE NOTED.
29. ALL STORM DRAINAGE PIPE SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/8" FALL PER 1'-0" OF RUN OTHERWISE NOTED.
30. ALL ILLUSTRATED DRAINAGE PIPING IS BELOW THE FLOOR ON WHICH IT IS DRAWN UNLESS OTHERWISE NOTED. ALL DOMESTIC WATER AND VENT PIPING ILLUSTRATED IS ABOVE OR AT THE CEILING ON WHICH IT IS DRAWN UNLESS OTHERWISE NOTED.
31. PROVIDE PRODUCTS AND FIXTURES AS SPECIFIED OR EQUIVALENT.
32. AT FLOOR DRAIN TRAP SEALS SHALL BE MAINTAINED BY AN APPROVED TRAP PRIMER.
33. MAKE FINAL CONNECTIONS AFTER FIXTURES AND EQUIPMENT ARE SET IN PLACE. ALL REQUIRED TRIM, FAUCETS AND MINOR ITEMS NECESSARY FOR A COMPLETE FUNCTIONING INSTALLATION, SUCH AS STRAINERS, TRAPS, TAILPIECES, ESCUTCHEONS, ETC., SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE WITH EQUIPMENT REQUIREMENTS. ALL
FAUCETS TO BE HEAVILY CHROME-PLATED.
34. CONTRACTOR ASSUMES RESPONSIBILITY FOR PROPER ARRANGEMENT OF PIPE, FIXTURES, ETC TO CONNECT APPROVED EQUIPMENT IN A PROPER AND APPROVED MANNER. CONTRACTOR SHALL FOLLOW EQUIPMENT MANUFACTURER'S DETAILED INSTRUCTIONS AND THE CONTRACT DOCUMENTS. NOTIFY THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH ALL WORK.
NO EQUIPMENT INSTALLATION OR CONNECTIONS SHALL BE MADE IN A MANNER THAT VOIDS THE MANUFACTURER'S
WARRANTY.
35. SUBMIT OPERATING AND MAINTENANCE MANUALS AND WARRANTY CERTIFICATES TO OWNER.
36. WATER HAMMER ARRESTERS SHALL BE INSTALLED IN FRONT OF ALL QUICK CLOSING VALVES SUCH AS MECHANICAL
EQUIPMENT AND AUTOMATIC CLOTHES WASHERS.
37. THE DOMESTIC WATER SYSTEM SHALL BE DISINFECTED AND FLUSHED IN FULL ACCORDANCE WITH THE LOCAL AUTHORITIES
HAVING JURISDICTION.
BACK WATER VALVE
GREASE SANITARY ABOVE GROUND
GREASE SANITARY BELOW GROUND
GR
GR
DESIGN CRITERIA
NOTE: ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.
DETAIL NUMBER
DETAIL NUMBER
WHERE THE DETAIL IS DRAWN
WHERE THE DETAIL IS DRAWN
WHERE THE DETAIL REFERENCED
DETAIL ANNOTATIONS
DOMESTIC WATER RISER DESIGNATION
SANITARY WATER RISER DESIGNATION
STORM RISER DESIGNATION
GAS RISER DESIGNATION
REVISION NUMBER
ANNOTATIONS
POINT OF DEMOLITION
POINT OF CONNECTION
AREA DRAIN
FLOOR DRAIN
GARAGE DRAIN
OVER FLOW ROOF DRAIN
ROOF DRAIN
FLOOR CLEAN OUT
FLOOR SINK DRAIN
DRAINS
HORIZONTAL CLEANOUT
WALL HYDRANT
HOSE BIB
MISCELLANEOUS
GAS METER
WATER METER
WATER FILTER
VACCUM BREAKER
TEMPERATURE AND PRESSURE RELIEF VALVE
TRAP PRIMER
DIRT LEG
TRENCH DRAIN
BREAK PIPE BELOW
X"
X"
PIPE SIZE
PIPE SIZE/NOTE
OPEN SITE DRAIN
FUNNEL FLOOR DRAIN
GREEN STORM RISER DESIGNATION
VENT RISER DESIGNATION
ROOF DRAIN-GREEN ROOF
EMERGENCY ROOF DRAIN
EMERGENCY ROOF DRAIN-GREEN ROOF
EMERGENCY STORM RISER DESIGNATION
EMEREGENCY GREEN STORM RISER DESIGNATION
OVER FLOW ROOF DRAIN-GREEN ROOF
GRADE CLEAN OUT
ROOF HYDRANT
GARDEN HYDRANT
TRAP PRIMER TUBE
INDIRECT DRAINAGE PIPE
EMERGENCY STORM WATER PIPING ABOVE GROUND
EMERGENCY STORM WATER PIPING BELOW GROUND
EMERGENCY STORM WATER PIPING FROM GREEN ROOF ABOVE GROUND
EMERGENCY STORM WATER PIPING FROM GREEN ROOF BELOW GROUND
GAS PIPING
ST
ST
ST(G)
ST(G)
EST
EST
EST(G)
EST(G)
ID
TP
2012 INTERNATIONAL BUILDING CODE
2012 INTERNATIONAL PLUMBING CODE
2012 INTERNATIONAL MECHANICAL CODE
2012 INTERNATIONAL FUEL GAS CODE
EQUIPMENT DESIGNATIONEQPM
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:02 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P001.dwg Save Date: 04/24/2018 12:23 PM
PLUMBING GENERAL NOTES,
SYMBOLS & ABBREVIATIONS
P001
EXISTING LIQUID
SEWAGE STORAGE
BASINS, TO REMAIN
IE 738.97'
(-3.33")
FD ETR
EXISTING 4"
CLEANOUTS
FD ETR
REMOVE EXIST SANITARY
PIPE UNDER SLAB UP TO
EXISTING FLOOR DRAIN
(E)4" SANITARY TO
SEPTIC SYSTEM (NIS)
EXISTING FD
EXISTING FD
EXISTING 4"
CLEANOUT
EXISTING FD
EXISTING 4"
CLEANOUT
EXISTING FD
EXISTING FD
EXISTING UNDERGROUND
CW PIPING TO REMAIN. SEE DETAIL ON P-701 FOR
WORK AT BOOSTER PUMP
CAP PIPE AT
SOURCE
SHEET KEY NOTES
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE TO ENSURE THAT THE EXISTING
UNDERGROUND PIPING IS NOT DAMAGED DURING THE REMOVAL
OF EXISTING GUTTER.
1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL
OTHER TRADES.
2. ANY DAMAGE TO THE ITEMS NOT IN SCOPE OF WORK SHALL BE
REPAIRED / REPLACED TO MATCH EXISTING CONDITIONS AT NO
EXTRA COST TO THE OWNER.
SCALE:
PLUMBING NEW WORK PLAN - SANITARY
1/8" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:09 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_PD101.dwg Save Date: 04/23/2018 05:31 PM
4'0 8' 16'
NORTH
1/8" = 1'-0"
PLUMBING - REMOVALS PLAN
PD-101
SHEET KEY NOTES
(E)1" G
(50 CFH)
(E)1-1/4" G
250(CFH)
(E)1" G
(50 CFH)
(E)1" G
(100 CFH)
(E)1-1/4" G
(250 CFH)
(E)1-1/2" G
(500 CFH)
(E)1" G
(250 CFH)
(E)2" G
(250 CFH)
(N)1" G
(100 CFH)
(E)2" G
475(CFH)
(E)1" G
(175 CFH)
1-1/4" G
(130 CFH)
1-1/4" G
(130 CFH)
MAU-1
325 CFH
NATURAL GAS SERVICE
EXISTING TO REMAIN.
1-1/2" G
(325 CFH)
1-1/4" G
(130 CFH)
UH-1A
130 CFH
UH-1A
130 CFH
IRH
50 CFH
IRH
50 CFH
UH
250 CFH
IRH
250 CFH
RTU-175 CFH
(E)1-1/2" G
(425 CFH)
2" G
(585 CFH)
2" G
(585 CFH)
RELOCATED
IRH
50 CFH
GM
IRH
50 CFH
IRH
50 CFH
GFU
100 CFH
(E)1-1/4" G
(250 CFH)
UH
250 CFH
FV
FV
TRENCH DRAIN
FLUSH VALVE
AND CABINET
(TYP)
FV
FV
EXISTING UNDERGROUND
CW PIPING TO REMAIN.
3/4" G
(50 CFH)
3/4" G
(50 CFH)
FD ETR
FD ETR
SEE DETAIL ON P-701 FOR
WORK AT BOOSTER PUMP GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL
OTHER TRADES.
2. ANY DAMAGE TO THE ITEMS NOT IN SCOPE OF WORK SHALL BE
REPAIRED / REPLACED TO MATCH EXISTING CONDITIONS AT NO
EXTRA COST TO THE OWNER.
1. PROVIDE FLUSH VALVE, WHITEHALL MODEL WH2803-1 OR
EQUIVALENT, COMPLETE WITH ACCESSORIES TO BE
INSTALLED PER MANUFACTURER RECOMMENDATIONS.
2. NEW PRECHARGED BLADDER TANK. SEE DETAIL P-701 FOR
PIPING ARRANGEMENT OF BLADDER TANK.
3. 1-1/4" PRESSURIZED WATER SUPPLY TO THE TRENCH DRAIN
FLUSH VALVE SYSTEM VIA A 1 14" REDUCED PRESSURE ZONE
BACKFLOW PREVENTER (ASSE-1013).
4. FLUSH VALVE WITHIN A RECESSED WALL CABINET.
5. 1/2" HOT + COLD WATER (INSULATED) SUPPLY TO NEW LAB
SINK CONNECT TO HOUSE HOT AND COLD WATER SUPPLY
SYSTEM.
CAP PIPE AT
SOURCE
FF 742.30
FV
FV
FLUSH VALVE (TYP)
FV
1"1"
1-1/4"
1"
1-1/4"
1"
1 1/4"
1"
1"
SCALE:
PLUMBING NEW WORK FLOOR PLAN - GAS AND WATER
1/8" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:14 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P101.dwg Save Date: 04/24/2018 11:50 AM
4'0 8' 16'
NORTH
1/8" = 1'-0"
PLUMBING NEW WORK FLOOR
PLAN - GAS AND WATER
P101
EXISTING LIQUID
SEWAGE STORAGE
BASINS, TO REMAIN
IE 738.97'
(-3.33")
FD ETR
FD ETR
REMOVE EXISTING
FLOOR DRAIN
UNDER WALL
PARTITION
REMOVE EXIST
SANITARY
PIPE UNDER
SLAB
(E)4" SANITARY TO
SEPTIC SYSTEM (NIS)
FD ETR
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL
OTHER TRADES.
2. ANY DAMAGE TO THE ITEMS NOT IN SCOPE OF WORK SHALL BE
REPAIRED / REPLACED TO MATCH EXISTING CONDITIONS AT NO
EXTRA COST TO THE OWNER.
SHEET KEY NOTES
1. PROVIDE A DUPLEX PACKAGED SEWAGE EJECTOR PUMP
SYSTEM WITH BASIN, ZOELLER, MODEL 282 OR EQUIVALENT
PUMPS, COMPLETE WITH BASINS, GRINDER, RAILS, CONTROLS
AND ACCESSORIES PER MANUFACTURER RECOMMENDATIONS.
2. PROVIDE 10" WIDE TRENCH DRAIN WITH HEAVY DUTY CI
GRATE, JAY R. SMITH FIG. 9812 OR EQUIVALENT COMPLETE
WITH ALL ACCESSORIES WITH MANUFACTURER
RECOMMENDATIONS.
3. PROVIDE A FIBERGLASS CATCHBASIN WITH STAINLESS STEEL
BASKET STRAINER, WITH DUCTILE IRON GRATE COMPLETE
WITH ALL ACCESSORIES PER MANUFACTURER
RECOMMENDATIONS - JAY R. SMITH FIG. NO. 9812-880-cb24 OR
EQUIVALENT.
4. PROVIDE A 2" SUPPLY FROM FLUSH VALVE TO TRENCH DRAIN
END CONNECTOR.
5. FLUSH VALVE CABINET WITH FLUSH VALVE ASSEMBLY.
6. PROVIDE NEW INLINE BACKWATER VALVE WITH CLEANOUT
ACCESS COVER.
7. 2" PVC SCH. 40 POST BASIN DRAIN PIPING UNDER SLAB.
INSTALL AT MIN. 2% SLOPE TOWARD CATCH BASIN.
8. 2" POST DRAIN BASIN. SEE DETAILS.
FV
EXISTING LIQUID
SEWAGE STORAGE
BASINS, TO REMAIN
IE 738.97'
(-3.33")
FD ETR
SEWAGE
EJECTOR
BASIN
2" VENT
P-TRAP WITH
FLUSHING HEEL
CONNECTION
CATCH
BASIN
FV
FD ETR
FLUSH VALVE (TYP)
FLUSHING PIPE
UNDER SLAB (TYP)
CENTER CATCH BASIN
WITH REMOVABE STAINLESS
STEEL BASKET
STRAINER(TYP)
FV
REMOVE EXISTING
FLOOR DRAIN
UNDER WALL
PARTITION
(E)4" SANITARY TO
SEPTIC SYSTEM (NIS)
TRENCH
DRAIN (TYP)
4"BWV
FV
P-TRAP WITH
FLUSHING HEEL
CONNECTION
PIPE DOWN TO CONNECT
TO EXIST SANITARY
BELOW FLOOR.
2" PUMP
DISCHARGE AT
MIN 14'-0" AFF
FV
FLUSH VALVE
(TYP)
FV
(TYP)
(TYP)
2"
(TYP)
2"
(TYP)
SK-1
2" Ø
4" Ø4" Ø
4" Ø
4" FD
2" V
SCALE:
PLUMBING NEW WORK PLAN - SANITARY - DEMOLITION
1/8" = 1'-0"
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:19 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P102.dwg Save Date: 04/24/2018 11:50 AM
4'0 8' 16'
NORTH
1/8" = 1'-0"
SCALE:
PLUMBING NEW WORK PLAN - SANITARY - NEW WORK
WDSDSD
PLUMBING NEW WORK PLAN
- SANITARY
P102
GROUND FLOOR
ROOF
(E) GAS METER &
REGULATOR TO REMAIN
GAS EQUIPMENT SCHEDULE
FIXTURE QUANTITY NEW EQUIPMENT
CFH RATING
REQUIRED INLET PRESSURE PIPE SIZE CONNECTION
EQUIPMENT
LOCATION
MAU 1
UH 5
UH-1B
IRH
TOTAL
GAS SERVICE TO
LOW PRESSURE SYSTEM #2: FROM PRV TO APPLIANCES:
1. SIZING BASED ON SCHEDULE 40 BLACK STEEL.
2. SYSTEM PRESSURE: 10.5 INCHES WC.
3. MAXIMUM LENGTH OF RUN: NOT TO EXCEED 20 FEET OF LENGTH.
4. MAXIMUM PRESSURE DROP: NOT TO EXCEED 0.5 INCHES WC.
NATURAL GAS PIPING SIZED PER IFGC 2012 TABLE 402.4 (2) PIPE SIZED TO MAXIMUM
DEVELOPED LENGTH OF 500 FEET INCLUDING FITTING PRESSURE LOSSES.
GAS SERVICE
LOW PRESSURE SYSTEM #1: FROM GAS METER TO PRV.
1. SIZING BASED ON SCHEDULE 40 BLACK STEEL.
2. SYSTEM PRESSURE: 10.5 INCHES WC.
3. MAXIMUM LENGTH OF RUN: NOT TO EXCEED 500 FEET OF LENGTH.
4. MAXIMUM PRESSURE DROP: NOT TO EXCEED 0.5 INCHES WC.
NATURAL GAS PIPING SIZED PER IFGC 2012 TABLE 402.4 (2) PIPE SIZED TO MAXIMUM
DEVELOPED LENGTH OF 500 FEET INCLUDING FITTING PRESSURE LOSSES.
(E) GAS SERVICE (E) DIRT LEG
G
UH-1A
325 CFH
500 CFH
130 CFH
130 CFH
300 CFH
RTU 1 175 CFH ---
UH
(250 CFH) (E)
EXISTING ANIMAL
BEHAVIORAL ROOM
UH
(250 CFH) (E)
IRH
(50 CFH) (E)
IRH
(50 CFH) (E)
IRH
(50 CFH) (E)
RELOCATED
IRH
(50 CFH) (E)
IRH
(50 CFH) (E)
RELOCATED
IRH
(50 CFH) (E)
GFU
(100 CFH) (E)
RTU
(175 CFH) (E)
MAU-1
(325 CFH) (N)
UH-1A
(130 CFH) (N)
UH-1B
(130 CFH) (N)
(N) 2" GAS
1-1/4" G1-1/4" G1-1/2" G
2" G
1-1/4" G 3/4" G3/4" G 1" G
1560 CFH
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:23 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P501.dwg Save Date: 04/24/2018 12:58 PM
SCALE:
GAS RISER DIAGRAM
NOT TO SCALE
PLUMBING RISER DIAGRAMS
P501
WALL MOUNTED
FLUSH VALVE
10" WIDE SLOPING
FIBERGLASS
TRENCH (TYP.)
CATCH BASIN WITH
STAINLESS STEEL
BASKET STRAINER
WALL MOUNTED
FLUSH VALVE
2" SUPPLY
FROM
FLUSHING
VALVE (TYP)
1%
1%
1%
1%
SLOPE SLOPE
1%
1%
4" Ø
27"
CATCH
BASIN
TRENCH DRAIN SLOPE
36" Ø X 72"
DEEP FIBER GLASS BASIN
GAS TIGHT
BASIN COVER
VENT THRU
ROOF
DUPLEX SEWAGE
EJECTOR PUMP
ANTI FLOTATION BASE
1%
4" OUTLET
STAINLESS STEEL
BASKETTRENCH
CATCH BASIN
STAINLESS STEEL
BASKET
TRENCH
4"PD
2" PD
1/2 HP SEWAGE GRINDER
36"Ø X 72" DEEP BASIN W/
GAS TIGHT COVER 2" VENT
TO OUT SIDE
FROM WALL MOUNT FLUSH
WATER SUPPLY. SEE DETAIL
4 ON THIS DRAWING
4"
BWV
1%
TRENCH DRAIN DETAILS
NOT TO SCALE
2" INLET FROM
FLUSH VALVE
4" ELBOW WITH LOW
HEEL 2" INLET
CATCH BASIN WITH
REMOVABLE STAINLESS
STEEL BASKET SCREEN
CATCH BASIN
GRATING
COVER
TRENCH COVER
SLOPING FIBERGLASS
TRENCH DRAIN
TRENCH DRAIN END CAP
WITH 4" INLET
4X2 ECCENTRIC
REDUCER
2"FROM
FLUSH VALVE
4" GRAVITY TO SUMP
BASIN
NO HUB COUPLING (TYP)
2" FROM
FLUSH VALVE
1/ 4" BEND, NO-HUB
CAST IRON WITH LOW HEEL INLET
FLUSH VALVE AND PIPING DETAIL
NOT TO SCALE
1" COLD
WATER SUPPLY
RECESSED CABINET,
STAINLESS STEEL
RECESSED FLUSH VALVE
PUSH BUTTON
FLUSH STARTER
1" DISCHARGE
2 X 1 NO-HUB FERNCO
COUPLING
2" DRAIN TO TRAP
CLEANING / FLUSHING
SYSTEM
SCHEMATIC PLAN VIEW
NOT TO SCALE
SCHEMATIC SEWAGE EJECTOR DIAGRAM
NOT TO SCALE
SCHEMATIC SECTION VIEW
NOT TO SCALE
3CATCH BASIN DRAIN PIPING DETAIL
NOT TO SCALE
1" BALL SHUT-OFF VALVE
CUTOUT IN COVER TO
ACCESS THE PUSH BUTTON
BACKWATER
VALVE (TYP)
SEE DETAIL 5 ON
THIS DRAWING
4" BOTTOM
OUTLET
EXISTING PRESSURE
GAUGES
EXISTING 1" BACK PRESSURE
REGULATOR & BY-PASS
RELIEF VALVE
FROM EXISTING 1" WATER
SERVICE PIPING
TO WATER
DISTRIBUTION PIPING
FROM EXISTING 1" WATER
SERVICE PIPING
TO WATER
DISTRIBUTION PIPING
EXISTING WATER
HAMMER ARRESTOR
TO REMAIN
DOMESTIC WATER PIPING - REMOVALS
BOOSTER PUMP PIPING DIAGRAM
NOT TO SCALE
NOTE:
INSTALL THE PRESSURE TANK PER
MANUFACTURER RECOMMENDATIONS.
DOMESTIC WATER PIPING - NEW WORK
EXISTING WATER
HAMMER ARRESTOR
TO REMAIN
NEW PRESSURE
GAUGE W/ GAUGE
COCK (TYP)
NEW PRE-CHARGED
PRESSURE TANK, 82 GAL.
CAPACITY, FLOTEC,
MODEL FP7110 OR
APPROVED EQUAL
4" Ø
27"
CATCH
BASIN
TRENCH DRAINSLOPE
BACKWATER
VALVE.
SCORIATED COVER
BACKWATER VALVE
1%1%
1%1%
2" SUPPLY FROM
FLUSHING VALVE
(TYP)
4"4"2"
WALL MOUNTED
FLUSH VALVE
4" GRAVITY DRAIN
TO SUMP BASIN
NO-HUB
COUPLING
EXTENSION
RISER
SCORIATED
CLEANOUT
COVER
CATCH
BASIN
CATCH BASIN
GRATING
COVER
1%
SLOPE
36" x 72" DEEP
FIBERGLASS BASIN
CHECK
VALVE
SHUT-OFF
BALL VALVE
BACKWATER
VALVE
CATCH BASIN WITH
BASKET STRAINER
27" SQUARE X 27" DEEP
9' SLOPING
TRENCH SECTION
(TYP)
2" FROM
FLUSHING
VALVE (TYP)
2" VENT
1"
1"
1"
PIPE UNION
EXISTING DOMESTIC
WATER BOOSTER PUMP
TO REMAIN
EXISTING DOMESTIC
WATER BOOSTER PUMP
TO REMAIN
EXISTING PRESSURE
SWITCH TO REMAIN
POST DRAIN BASIN DETAIL
NOT TO SCALE
12" SQUARE CONCRETE
FILLED BACKFILL AROUND
BASIN SUPPORT.PLAN
2" Ø POST DRAIN BASIN.
SECTION
2" Ø x 10" LONG SCH40
GALV. STEEL SUPPORT
EMBEDDED IN CONC.
BASIN.
2" Ø FERNCO COUPLING
2" Ø x 2" LONG
PVC SCH. 40
2" Ø PVC ELBOW
2" Ø PVC SCH. 40
TO CATCH BASIN
SLOPE AT MIN.
2% SLOPE.
FINISH
FLOOR
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:27 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\22-SAGQ178056.02_P\178056.02_P701.dwg Save Date: 04/24/2018 11:27 AM
PLUMBING DETAILS
P701
SYMBOLSGENERAL MECHANICAL NOTES
OPEN END DUCT WITH CAP
DUCTWORK WITH ROUND DUCT TAKE-OFF
DUCTWORK WITH DUCT BRANCH
RETURN OR EXHAUST AIR DEVICE
SUPPLY AIR DEVICE
ELBOW WITH TURNING VANES
RETURN AIR DUCT TO DROP DOWN
RETURN AIR DUCT TO RISE UP
SUPPLY AIR DUCT TO DROP DOWN
SUPPLY AIR DUCT TO RISE UP
MANUAL VOLUME DAMPER
FLEXIBLE DUCT CONNECTOR
DUCT WORK WITH TRANSITION
12x10
FIRE DAMPER
FD
VD
VD
VD
NEW DUCT (1ST DIMENSION INDICATES TOP SHOWN,
INSIDE CLEAR DIMENSIONS).
EXISTING DUCTWORK OR EQUIPMENT TO REMAIN
EXISTING DUCTWORK OR
EQUIPMENT TO BE REMOVED
CEILING SUPPLY AIR DIFFUSER
EXHAUST AIR GRILLE
THERMOSTAT / TEMPERATURE SENSOR
RECTANGULAR/SQUARE DUCT TO ROUND
DUCT SIZE TRANSITION
EXHAUST DUCT TO DROP DOWN
EXHAUST DUCT TO RISE UP
EXHAUST AIR DEVICE
REVISION NUMBER
KEYED DRAWING NOTE
EQUIPMENT DESIGNATION TAG
AIR DEVICE TAG
DIFFUSER TYPE
AIR VOLUME IN CFM
UNDERCUT DOOR
NEW TO EXISTING
REMOVE TO EXISTING
NOTE:
ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.
AC AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
APD AIR PRESSURE DROP
ARCH ARCHITECTURAL
BHP BRAKE HORSE POWER
BLDG BUILDING
BLW BELOW
BTUH BRITISH THERMAL UNIT PER HOUR
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CU CONDENSING UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
DB DRY BULB
DIA DIAMETER
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILL
EQUIP EQUIPMENT
ERV ENERGY RECOVERY VENTILATOR
ETR EXISTING TO REMAIN
EA. EXISTING
EXT EXTERNAL
F FAHRENHEIT
FD FIRE DAMPER
FCU FAN COIL UNIT
FPM FEET PER MINUTE
FT FEET
HP HORSE POWER / HEAT PUMP
HR HOUR
IN INCH
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LB POUNDS
LF LINEAR FEET
MAX MAXIMUM
MBH 1000 BTUH
MECH MECHANICAL
MIN MINIMUM
MTD MOUNTED
(N) NEW WORK
NC NOISE CRITERIA
NOM NOMINAL
No. NUMBER
OA OUTSIDE AIR
OAT OUTSIDE AIR TEMPERATURE
(R) RELOCATED
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RG RETURN GRILL
RPM REVOLUTION PER MINUTE
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
SG SUPPLY GRILL
SR SUPPLY REGISTER
TS TEMPERATURE SENSOR
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
W WATT
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
WPD WATER PRESSURE DROP
W/ WITH
W/O WITHOUT
ABBREVIATIONS
1. THE INTENT OF THE CONTRACT DOCUMENTS IS TO PROVIDE FINISHED WORK, TESTED AND READY
FOR OPERATION. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF FIRST RATE QUALITY.
2. WORK INDICATED ON THESE DRAWINGS IS DIAGRAMMATIC AND SHOULD NOT BE SCALED TO
ESTABLISH LOCATION OF WORK. THE DRAWINGS ARE INTENDED TO CONVEY THE SCOPE OF
WORK AND INDICATE GENERAL ARRANGEMENTS OF ENGINEERED SYSTEMS. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD AND MAKE ADJUSTMENTS AS NECESSARY
TO COMPLETE THE WORK.
3. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND SERVICES FOR ALL WORK, IN
ACCORDANCE WITH PROVISIONS OF THE CONTRACT DOCUMENTS. ALTHOUGH SUCH WORK IS NOT
SPECIFICALLY INDICATED, FURNISH AND INSTALL ALL SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTENANCES AND DEVICES INCIDENTAL TO OR NECESSARY FOR A SOUND, SECURE AND
COMPLETE INSTALLATION, AT NO ADDITIONAL COST TO THE OWNER.
4. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH
MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND
REGULATIONS.
5. IN ADHERENCE WITH THE INTENT OF THESE CONTRACT DOCUMENTS, PROVIDE FINISHED WORK, TESTED AND READY FOR OPERATION. WHEREVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN
"FURNISHED, INSTALL, BALANCE, ADJUST AND TEST, COMPLETE AND READY FOR USE".
6. CONTRACTOR IS RESPONSIBLE FOR COMPLETE COORDINATION BETWEEN ALL
SUB-CONTRACTORS, SUPPLIERS, GOVERNMENT AUTHORITIES HAVING JURISDICTION, BUILDING
PERSONNEL, CODE ENFORCEMENT OFFICIALS, ARCHITECT/ENGINEER AND BUILDING OWNER.
7. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS.
COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING
DIMENSIONS BEFORE FABRICATION.
8. ALL PIPES SHALL BE INSTALLED IN A NEAT AND ORDERLY APPEARANCE AND FREE FROM CONTACT
WITH STRUCTURE OR INSTALLED ITEMS. RUN PIPING PARALLEL TO WALLS AND FLOORS OF
BUILDING UNLESS OTHERWISE INDICATED.
9. PROVIDE REFRIGERANT PIPING IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S
RECOMMENDATIONS. VERIFY LINE SIZES FOR EQUIPMENT FURNISHED.
10. INSULATE REFRIGERANT SUCTION PIPING WITH CLOSED-CELL FLEXIBLE ELASTOMERIC INSULATION (REFER TO SPECIFICATIONS FOR THICKNESS) UNLESS OTHERWISE NOTED. PROVIDE A WEATHER
RESISTANT FINISH ON INSULATION EXPOSED TO OUTDOORS. INSTALLATION TO BE IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
11. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH
ALL OTHER TRADES INVOLVED.
12. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE
STOPPED. PRODUCT USED MUST MEET TEST METHODS BY ASTM E814 OR NFPA 251 FOR FIRE
RATING. PROVIDE UL LABELED FIRE DAMPERS AT ALL DUCT PENETRATIONS INTO FIRE RATED
STRUCTURES.
13. REFER TO SPECIFICATIONS FOR WARRANTY REQUIREMENTS.
14. THE CONTRACTOR SHALL NOT CORE DRILL CONCRETE SLAB WITHOUT THE KNOWLEDGE AND
WRITTEN CONSENT OF THE STRUCTURAL ENGINEER AND THE BUILDING OWNER. CORE DRILLING
SHALL BE SCHEDULED WITH THE BUILDING OWNER.
15. THERMOSTAT AND TEMPERATURE SENSORS SHALL BE INSTALLED 4'-0" (ADA COMPLIANCE) ABOVE
FINISHED FLOOR WHERE SHOWN ON PLANS UNLESS NOTED OTHERWISE.
16. MAXIMUM LENGTH OF FLEXIBLE DUCTWORK SHALL NOT EXCEED 5'-0" UNLESS OTHERWISE NOTED.
17. PROVIDE SINGLE THICKNESS TURNING VANES IN ALL DUCTWORK ELBOWS (45° & 90°). TURNING
VANES SHALL COMPLY WITH SMACNA STANDARDS, 2005 EDITION.
18. ALL NEW DUCTWORK MUST BE FIELD VERIFIED PRIOR TO FABRICATION, PURCHASE, OR
INSTALLATION. NO ALLOWANCE WILL BE MADE FOR DUCTWORK THAT IS NOT USED.
19. PROVIDE ALL NECESSARY ACCESSORIES TO ALLOW FOR PROPER AIR BALANCE. UPON
COMPLETION OF THE INSTALLATION, ALL AIR SYSTEMS SHALL BE ADJUSTED AND BALANCED TO
PROVIDE THE AIR FLOW RATE INDICATED. CONTRACTOR SHALL PROVIDE VOLUME DAMPERS,
SPLITTER DAMPERS AND/OR VOLUME EXTRACTORS AS INDICATED OR REQUIRED FOR BALANCING.
BALANCING WORK SHALL BE PERFORMED BY A CERTIFIED BALANCING CONTRACTOR WHO IS A
MEMBER IN GOOD STANDING OF AABC OR SMACNA. BALANCING WORK SHALL BE IN COMPLIANCE
WITH THE STANDARD PROCEDURE MANUAL PUBLISHED BY THE TESTING AND BALANCING
ORGANIZATION AFFILIATED WITH THE BALANCING CONTRACTOR. PRIOR TO ACCEPTANCE OF THE WORK, CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER ALL APPROPRIATE FIELD DATA
ON STANDARD FORMS OF THE TESTING AND BALANCING ORGANIZATION IN ACCORDANCE WITH
STANDARD PROCEDURES.
20. ALL EQUIPMENT (INCLUDING DUCTWORK AND PIPING) SHALL BE SECURELY SUPPORTED FROM
THE BUILDING STRUCTURE IN AN APPROVED MANNER. EQUIPMENT SHALL NOT GENERATE NOISE
GREATER THAN CATALOG RATINGS. ALL EQUIPMENT AND APPURTENANCES SHALL NOT TRANSMIT
NOISE OR VIBRATION TO THE OCCUPIABLE SPACES.
21. PROVIDE FIRE SAFING APPROVED BY THE AUTHORITY HAVING JURISDICTION, AROUND ALL PIPING
AND DUCTWORK PENETRATIONS THROUGH BUILDING CONSTRUCTION TO MAINTAIN FIRE, SMOKE,
AND SOUND RATINGS.
22. THE CONTRACTOR SHALL FURNISH AND INSTALL ACCESS PANELS WHERE REQUIRED FOR ACCESS TO EQUIPMENT, VALVES, DAMPERS, CONTROLS, ETC. IN DUCTWORK AND/OR CONCEALED BEHIND
FINISHES NOT INTENDED TO BE REMOVED; COORDINATE WITH THE ARCHITECT PRIOR TO ANY
INSTALLATION.
23. MECHANICAL CONTRACTOR SHALL PROVIDE ALL MOTOR STARTERS, DISCONNECTS ETC. AS
REQUIRED BY THE MECHANICAL EQUIPMENT; THE ELECTRICAL CONTRACTOR SHALL INSTALL AND
PROVIDE FINAL CONNECTIONS. WHERE THE MECHANICAL SYSTEMS COME WITH INTEGRAL
STARTERS, DISCONNECTS, ETC., THE ELECTRICAL CONTRACTOR SHALL PROVIDE FINAL
CONNECTIONS.
24. ALL EQUIPMENT MUST BE INSTALLED SUCH THAT FACTORY REQUIRED CLEARANCES FOR
SERVICEABILITY ARE MAINTAINED. NOTIFY THE ENGINEER IMMEDIATELY SHOULD ANY EQUIPMENT HAVE ACCESS LIMITED BECAUSE OF FIELD CONDITIONS, EQUIPMENT ORIENTATION, ETC. DO NOT
INSTALL THIS EQUIPMENT UNTIL THE SITUATION HAS BEEN RESOLVED.
25. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE
AND FUNCTIONAL SYSTEM, INCLUDING BUT NOT LIMITED TO, WIRING, TRANSFORMERS,
HARDWARE, PARTS AND ACCESSORIES INCLUDING ALL SAFETY DEVICES REQUIRED IN
ACCORDANCE WITH ALL CODE REQUIREMENTS. THE CONTROLS CONTRACTOR SHALL PROVIDE
POWER TO ALL CONTROL DEVICES AND EQUIPMENT FROM THE NEAREST ELECTRICAL PANEL
DESIGNATED FOR CONTROLS. THE CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER
REQUIREMENTS. DEVICES PROVIDED BY UNIT MANUFACTURERS SHALL BE INSTALLED AND WIRED
BY THE CONTROLS CONTRACTOR UNLESS INDICATED OTHERWISE.
26. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES, AND STATE CODES.
27. CONTRACTOR SHALL COMPLY WITH ALL OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
(OSHA) AND ENVIRONMENTAL PROTECTION AGENCY (EPA) REQUIREMENTS.
28. CONTRACTOR SHALL COMPLY WITH RULES AND REGULATIONS OF THE GOVERNMENT.
29. CLEAN UP ALL WASTE AND DEBRIS AT THE END OF EACH WORKING DAY AND AS REQUIRED TO
KEEP ALL BUILDING AREAS CLEAN, CLEAR AND UNOBSTRUCTED. AT THE COMPLETION OF THE
PROJECT, THE CONTRACTOR SHALL REMOVE ALL TOOLS, APPLIANCES, SURPLUS MATERIAL AND
SCRAP FROM THE JOB SITE.
30. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND
ELECTRICAL UFGS.
NOTE:
ALL SYMBOLS MAY NOT APPEAR ON THE DRAWINGS.
DETAIL NUMBER
WHERE THE DETAIL IS DRAWN
MECHANICAL GENERAL
NOTES, SYMBOLS &
ABBREVIATIONS
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:33 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M001.dwg Save Date: 04/23/2018 05:54 PM
M001
GENERAL NOTES
1. EXISTING WORK SHOWN IS BASED ON AVAILABLE DOCUMENTATION
AND SPOT CHECKS ON SURVEY. CONTRACTOR TO FIELD VERIFY
EXISTING CONDITIONS AND COORDINATE WITH ENGINEER PRIOR TO
PROCEEDING WITH WORK.
2. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL HVAC DEVICES
WITHIN THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE
CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING
CONDITIONS WITH IN THE PROJECT AREA. ANY DISCREPANCIES OR
CONDITIONS NOT SHOWN ON THIS PLAN SHALL BE COORDINATED.
3. CONTRACTOR TO FIELD COORDINATED ALL REMOVAL/ STORAGE/
DISPOSAL OF EXISTING EQUIPMENT WITH THE OWNERS.
4. WHERE DUCTWORK, PIPING, AND EQUIPMENT ARE INDICATED TO BE
REMOVED, REMOVE EXISTING CONCRETE INSERTS AND
STRUCTURAL ATTACHMENTS, AND PATCH CONCRETE SURFACE TO
MATCH ADJACENT.
5. CONTRACTOR SHALL SCHEDULE ALL WORK IN ACCORDANCE WITH
OWNER'S REQUIREMENTS.
SHEET KEY NOTES
1. EXISTING RADIANT GAS HEATER TO BE RELOCATED. DISCONNECT
GAS LINE. FOR NEW LOCATION SEE M101.00 REUSE ROOF OPENING
FOR NEW FLUE TIE-IN. SALVAGE THERMOSTATS FOR REUSE.
SCALE:
MECHANICAL DEMOLITION FLOOR PLAN
1/8" = 1'-0"
MECHANICAL DEMOLITION
FLOOR PLAN
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:38 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_MD101.dwg Save Date: 04/23/2018 05:53 PM
NORTH
1/8" = 1'-0"
4'0 8' 16'
MD101
EF-1A
SG-1
200 CFM
TYP. FOR 20
MAU-1
CRG-1
2000 CFM
EF-2
UH-1B
UH-1A
EF-1B
CRG-1
2000 CFM
CRG-1
1200 CFM
14"Ø
"Ø
18"Ø
18"Ø
"Ø
"x
TRANSITION
FROM SQUARE
TO ROUND
SEE DETAIL 6
ON M-701 FOR
CONCRETE PAD
DETAIL.
GENERAL NOTES
1. REFER TO DRAWING M-001.00 FOR GENERAL NOTES, SYMBOLS &
ABBREVIATIONS.
2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL NECESSARY
DUCTWORK DROPS, RISERS OR TRANSITIONS REQUIRED FOR
COORDINATION WITH STRUCTURAL BEAMS, SPRINKLER HEADS,
SPRINKLER PIPING & LIGHTING FIXTURES.
3. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS AND
CODE REQUIREMENTS.
4. PROVIDE MANUFACTURER RECOMMENDED EQUIPMENT
CLEARANCES FOR MAINTENANCE PURPOSES FOR ALL EQUIPMENT.
5. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LOCATIONS AND
CLEARANCES PRIOR TO START OF CONSTRUCTION.
6. FOR TYPE & SIZE OF MECHANICAL EQUIPMENTS REFER TO
SCHEDULE ON DWG. M-601.00.
SHEET KEY NOTES
1. RELOCATE EXISTING GAS FIRED RADIANT HEATERS TO LOCATION
SHOWN.
2. CONTRACTOR TO PROVIDE NEW MAU. PROVIDE CONCRETE PAD
3. PROVIDE NEW EXHAUST FAN, INTERCONNECT WITH MAU
OPERATION. PROVIDE VIBRATION ISOLATION AND ALL NECESSARY
ACCESSORIES
4. PROVIDE NEW EXHAUST FAN WITH MANUAL CONTROLS. PROVIDE
VIBRATION ISOLATION AND ALL NECESSARY ACCESSORIES.
5. PROVIDE GAS FIRED UNIT HEATER WITH A THERMOSTAT
6. PROVIDE GALVANIZED STEEL ROUND SUPPLY DUCT
SCALE:
MECHANICAL NEW WORK FLOOR PLAN
1/8" = 1'-0"
MECHANICAL NEW WORK
FLOOR PLAN
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:43 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M101.dwg Save Date: 04/23/2018 05:55 PM
NORTH
1/8" = 1'-0"
4'0 8' 16'
M101
MECHANICAL SCHEDULES
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:47 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M601.dwg Save Date: 04/23/2018 05:56 PM
MAKE UP AIR UNIT
UNIT NO LOCATION SERVICE
AIR CAPACITY
(CFM)
FAN DATA HEATING GAS
PRESSURE
(MIN / MAX)
INCHES
ELECTRICAL DATA
UNIT
WEIGHTS LBS BASIS OF DESIGNESP HP RPM FLA
INPUT
MBH OUTPUT MBH
TEMP RISE
(F) VOLTS PHASE CYCLE (HZ)
MAU-1 GROUND
NEW ANIMAL
BEHAVIORAL
LABS
4,000 1.5 2 1,100 3 400 324 230 1 60 805 REZNOR RDH-400A
NOTES:
1. PROVIDE MAKE UP AIR UNIT WITH 18" PRE FABRICATED ROOF CURB.
2. FANS SHALL BE INTERNALLY ISOLATED.
3. PROVIDE UNTIS WITH DISCONNECT SWITCHES SUTIABLE FOR OUTDOOR INSTALLATION.
4. PROVIDE UNITS WITH VARIABLE FREQUENCY DRIVE AND TIE IT IN WITH EMS PLUS DEMAND CONTROL SYSTEM .
EXHAUST FAN SCHEDULE
UNIT NO TYPE SERVICE DRIVE TYPE CFM
ESP (IN.
WG)
MOTOR
RPM MOTOR SIZE
ELECTRICAL
WEIGHT
(LBS)
SONES
METHOD OF CONTROL BASIS OF DESIGN REMARKSVOLTS PHASE HERTZ FLA (A) INLET RADIATED
EF-1A INLINE BEHAVIORAL ROOM DIRECT 2,000 1 1,100 0.37BHP 115 1 60 14.2 122 4.4 - INTERLOCK WITH MAU-1 OPERATION GREENHECK CSP-A3600 1,2
EF-1B INLINE BEHAVIORAL ROOM DIRECT 2,000 1 1,100 0.37BHP 115 1 60 14.2 122 4.4 - INTERLOCK WITH MAU-1 OPERATION GREENHECK CSP-A3600 1,2
EF-2 INLINE FEED ROOM DIRECT 1,200 1 1,450 0.32BHP 115 1 60 7.8 59 4.8 - MANUAL GREENHECK CSP-A1410 1,2
NOTES:
1. PROVIDE EXHAUST FANS WITH GRAVITY BALANCED BACKDRAFT DAMPER.
2. PROVIDE FAN WITH NEMA RATED DISCONNECT SWITCH WITH WEATHERPROOF COVER SUITABLE FOR WET LOCATION.
AIR DEVICE SCHEDULE
UNIT SERVICE CFM RANGE MAX SP (IN WG) MAX NC NECK SIZE (IN) SIZE DEVICE TYPE BASIS OF DESIGN REMARKS
SG-1 SUPPLY 0-200 0.046 13 N/A 12X6 SUPPLY GRILLE TITUS 1,2,3,4,6
EG-1 EXHAUST 1000-2000 0.23 36 22X22 24X24 EXHAUST GRILLE TITUS 1,3,6
NOTES:
1. ALL SUPPLY DIFFUSERS SHOULD BE PROVIDED WITH ADJUSTABLE PATTERN FOR VERTICAL AND HORIZONTAL DISCHARGE.
2. PROVIDE OPPOSED BLADE DAMPERS TO ADJUST THE AIRFLOW THROUGH THE FACE OF THE REGISTER.
3. DIFFUSER SHALL BE CONSTRUCTED OF 24 GAUGE STEEL.
4. GRILLE SHALL BE PROVIDED WITH BORDER FRAME.
5. THERMAFUSERS SHALL BE PROVIDED WITH 30% SETTING AND WITHOUT RELIEF RING.
6. DIFFUSER/GRILLE SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASHRAE STANDARD 70-2006.
GAS UNIT HEATER SCHEDULE
UNIT MARK LOCATION TYPE KW BTUH FLA VOLTS/PH/HZ BASIS OF DESIGN REMARKS
UH-1A RESEARCH LAB SUSPENDED 44 150,000 1.9 208/1/60 REZNOR SC150 SEE NOTES
UH-1B RESEARCH LAB SUSPENDED 44 150,000 1.9 208/1/60 REZNOR SC150 SEE NOTES
NOTES:
1. THERMAL CUTOUT SHALL BE PROVIDED WITHIN THE UNITS BY THE MANUFACTURER.
2. PROVIDE UNIT WITH LOCAL SWITCH AND BUTTON TYPE TEMPERATURE SENSOR IN VESTIBULE AREA SET AT 70⁰ F.
3. PROVIDE UNIT WITH 3-SPEED CONTROL
M601
MAXIMUM ALLOWABLE HANGER
LOAD
STRAPS LBS RODS LBS
2-1"x22 GA 520 2-1/4" Ø 540
2-1"x20 GA 640 2-3/8" Ø 1360
2-1"x18 GA 840 2-1/2" Ø 2500
2-1"x16 GA 1400 2-5/8" Ø 4000
TURN STRAP
SECURE STRAP HANGER
TO STRUCTURE
1"x18 GAGE STRAP HANGERS UP THRU 30"Ø 1"x1/8" ABOVE 30"Ø AT 10' OFF
CENTER
ROUND DUCT
SHEET METAL
SCREWS
SHEET METAL
SCREWS
1"x1/8" STRAPS
1-1/4"x1/8" RING
SECURE
STRAPS TO
BEAM WITH LAG
SCREWS
DUCT-SEE PROJECT
PLANS FOR SIZE
ROUND DUCT
SCALE:
ROUND DUCT HANGER DETAIL
NOT TO SCALE
M-701
BIRDPROOF & RAINPROOF
CAP
CAULK WEATHERTIGHT
ROOF FLASHING SET IN
CAULK - WATER TIGHT &
SCREW TO SHEET METAL
ROOF
PROVIDE 18 GA ANGLE
BRACKETS TO SUPPORT
STACK SUPPORT BRACKET
STACK SUPPORT
BRACKET
TYPE B GAS VENT
EXISTING FORMED METAL
WALL PANELS
CAULK WEATHER TIGHT
ALIGN HOOD WITH BOT.
OF EXISTING TRUSSES
PAINT WITH MINIMUM TWO
COATS OF ALUMINIZED
WEATHERPROOFING
PAINT
FRAMING & BLOCKING
AS REQ'D
MOTORIZED SHUTTER 115V
[SIMILAR TO FAN JET
SYSTEM INTAKE]
26" x 26" [.66 x .66 M]
SCALE:
GAS VENT DETAIL
NOT TO SCALE
M701
SCALE:
WALL INTAKE DETAIL
NOT TO SCALE
M701
2' -0
.6
M
[M
IN
SCALE:
INLINE FAN DETAIL
NOT TO SCALE
M-701
NOTES:
1. FAN SHALL BEAR THE AMCA SEAL FOR AIR AND SOUND PERFORMANCE.
2. UNIT SHALL HAVE FACTORY MOUNTED TERMINAL BOX.
INTAKE AIR
SUPPORT ROD FROM
STRUCTURE FROM
ABOVE (TYP OF 4)
DUCTWORK
FORWARD CURVED FAN WHEEL
FAN HOUSING
REMOVABLE ACCESS PANEL
1/2" ACOUSTIC LINING
GALVANIZED
STEEL HOUSING
FLEXIBLE CONNECTION
(TYP)
STEEL SPRING & RUBBER
IN SHEAR TYPE VIBRATION
ISOLATORS (TYP OF 4)
AIR OUT
SCALE:
TYPICAL EXHAUST GRILLE DETAIL
NOT TO SCALE
M-701
MAIN EXHAUST
DUCT
AIR FLOW
MAX. HANGER SPACING
METAL DUCT
* 10 FT (3M) RECTANGULAR.
* 12 FT (3.7M) ROUND.
WIRE MESH SCREEN
SCALE:
OUTDOOR EQUIPMENT PAD DETAIL
NOT TO SCALE
M701
1' - 0"
2'
6" M
IN
#4 CONT.
2 12" CLR.
5" S
.O .G
2-#4 CONT.
#4 @ 18"
2 12" CLR.
2 (MIN.)
30"
6" 6x6 WELDED
WIRE FABRIC
12" MAX,
8" MIN
MIN 4” COMPACTED
GRAVEL BASE
MECHANICAL DETAILS
M701
Plotted By: SHARI SHARAFI Plot Date: 4/24/2018 1:31:52 PM Saved By: SHARI.SHARAFI File: O:\2017\SAGQ178056.02\23-SAGQ178056.02_M\178056.02_M701.dwg Save Date: 04/23/2018 05:58 PM
ELECTRICAL GENERAL NOTES
I. GENERAL:
A. BEFORE SUBMITTING BID. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
VISITING THE SITE TO VERIFY/EXAMINE THE EXACT EXTENT OF EXISTING CONDITIONS. NO
CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR
FOR ANY ALLEGED MISUNDERSTANDING OF WORK TO BE PERFORMED. THE CONTRACTOR
SHALL INCLUDE IN HIS BID PRICE ALL LABOR AND MATERIAL THAT MAY EFFECT HIS WORK.
B. THE GENERAL EXTENT OF EXISTING ELECTRICAL WORK TO BE DISMANTLED AND REMOVED
OR RELOCATED IS INDICATED ON THE DRAWINGS.
C. ALL COMPONENTS ASSOCIATED WITH SYSTEMS AND EQUIPMENT TO BE REMOVED OR
RELOCATED MAY NOT BE SPECIFICALLY INDICATED. REMOVE ALL ASSOCIATED ELECTRICAL
COMPONENTS, HANGERS, WIRING, CABLING, CONDUIT, BOXES, DEVICES AND ALL OTHER
ITEMS RELATED TO EQUIPMENT AND MATERIALS WHICH ARE INDICATED TO BE REMOVED OR
RELOCATED. REMOVE ALL WIRING/CONDUIT BACK TO THE SOURCE IN EXISTING CIRCUITS
WHICH ARE BEING DEMOLISHED. UNLESS SPECIFICALLY INDICATED, NO EQUIPMENT,
MATERIALS OR ASSOCIATED COMPONENTS SHALL BE ABANDONED IN PLACE.
D. ABANDONED ALL CONDUITS WHICH ARE CONCEALED IN CONCRETE WALLS OR SLABS AND
REMOVE ALL WIRING/CABLES FROM ABANDONED CONDUITS.
II. DISPOSAL OF DEMOLITION:
A. CONTRACTOR SHALL CLEAN THE PROJECT SITE AT THE END OF EACH WORKING DAY.
CONTRACTOR SHALL NOTIFY BUILDING OWNER PRIOR TO DISPOSAL OF ALL DEMOLISHED
MATERIALS TO ALLOW THE OWNER TO SALVAGE ANY USABLE MATERIALS. AFTER INSPECTING
FROM THE OWNER'S REPRESENTATIVE ALL UNUSED MATERIALS SHALL BE REMOVED FROM
THE JOB SITE WITH DISPOSAL IN ACCORDANCE WITH APPLICABLE SPECIFICATIONS AND
REGULATIONS.
III. PROTECTION:
A. PROTECT FROM DAMAGE ALL EXISTING WORK TO REMAIN. ANY EXISTING TO REMAIN OR
EXISTING TO BE RELOCATED MATERIALS AND EQUIPMENT DAMAGED DURING THE COURSE
OF THE WORK SHALL BE REPLACED WITH MATERIALS AND EQUIPMENT CONFORMING TO
THESE SPECIFICATIONS AT NO ADDITIONAL COST TO THE OWNER. CARE MUST TAKEN IN
REMOVING ALL EXISTING MATERIALS.
IV. TERMINATION AND PATCHING:
A. DISCONNECT EXISTING TO BE REMOVED OR EXISTING TO BE RELOCATED CONDUIT, WIRING, CABLING, AND EQUIPMENT FROM EXISTING TO REMAIN POINT INDICATED. IF NOT INDICATED
ON THE PLANS, VERIFY WITH THE DESIGN ENGINEERS OR BUILDING OWNER'S
REPRESENTATIVE PRIOR TO DISCONNECTION.
B. WHERE EXISTING FLOORS, WALLS AND ROOFS MUST BE CUT OR ARE DAMAGED DURING
REMOVAL OR RELOCATION OF ELECTRICAL WORK, PATCH THE CUT OR DAMAGED AREAS TO
MATCH ADJACENT CONSTRUCTION.
C. THE CONTINUITY OF ALL EXISTING CONDUITS AND FEEDERS SERVICING AREAS TO REMAIN
SHALL BE MAINTAINED. MODIFY THE EXISTING CIRCUITS IF REQUIRED IN ORDER TO MAINTAIN
THE EXISTING CIRCUITRY.
ELECTRICAL GENERAL DEMOLITION NOTES
REFER TO THE LIGHTING FIXTURE SCHEDULE ON DRAWINGS E600 FOR LIGHTING FIXTURE SPECIFICATIONS.
WALL-MOUNTED DUPLEX OR QUAD RECEPTACLE, 20A, 125V, NEMA 5-20R.
OUTLETS MAY HAVE THE FOLLOWING SUBSCRIPTS:
WALL-MOUNTED ABOVE COUNTER DUPLEX OR QUAD RECEPTACLE, 20A, 125V, NEMA 5-20R
FLUSH FLOOR MOUNTED DUPLEX / QUADRUPLEX NEMA 5-20R RECEPTACLE, 20A, 125V
POKE THRU OUTLET. COORDINATE POKE THRU FINISH SPECIFICATION AND EXACT LOCATION
WITH ARCHITECT.
FLUSH MOUNTED ADA COMPLIANT COMBINATION DUPLEX/QUADRUPLEX POWER AND
TELE-DATA-AV POKE THRU OUTLET. REFER TO TECHNOLOGY PATHWAY DRAWINGS FOR
TELE-DATA-AV OUTLET REQUIREMENTS. COORDINATE POKE THRU FINISH, SPECIFICATION AND
EXACT LOCATION WITH ARCHITECT AND TECHNOLOGY CONSULTANT. BASIS OF
DESIGN, WIREMOLD EVOLUTION 8AT SERIES
RECESSED CEILING MOUNTED DUPLEX OR QUADRUPLEX NEMA 5-20R RECEPTACLE, 20A, 125V
WALL-MOUNTED DUPLEX OR QUADRUPLEX TAMPER PROOF RECEPTACLE, 20A, 125V,
NEMA 5-20R.
WALL/FLOOR/CEILING MOUNTED COMBINATION TELEPHONE/DATA OUTLET
SINGLE POLE TOGGLE SWITCH
3 - WAY SWITCH
3-WAY DUAL SWITCH WITH 50% STEP DIMMING BALLASTS
KEY OPERATED SWITCH
DIMMER SWITCH RATED FOR 2000 WATTS. PROVIDE NECESSARY MODULES FOR LED
LAMP SOURCE
MOTOR RATED SWITCH WITH THERMAL OVERLOAD CURRENT PROTECTION.
MOUNTED @ 48" AFF OR UNIT MOUNTED
WALL/CEILING MOUNTED LOW VOLTAGE OCCUPANCY SENSOR SWITCH CONFIGURED AS
AUTO-ON, AUTO-OFF, UON. CONFIGURE TIME-OUT SETTING FOR 15 UNLESS OTHERWISE
NOTED. DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:
2 : DUAL SWITCH
WALL/CELING/FLOOR MOUNTED JUNCTION BOX. FIELD COORDINATE EXACT LOCATION
AND MOUNTING HEIGHT.
MD : INDICATES MOTORIZED DAMPER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH.
COMBINATION STARTER DISCONNECT SWITCH.
MOTOR - SEE FLOOR PLANS AND MECHANICAL SCHEDULE FOR RATING
DRY TYPE TRANSFORMER, SEE FLOOR PLANS AND POWER RISER FOR SIZE
120/208V ELECTRICAL PANEL
CIRCUIT HOMERUN TO DESIGNATED PANEL. NUMBER OF ARROWS INDICATE NUMBER
OF CIRCUITS AND TEXT DENOTES PANELBOARD. TICK MARKS INDICATE NUMBER OF AWG
WIRES CONTAINED IN CONDUIT WHEN MORE THAN TWO. TICK MARKS WITH:
( ) DENOTES SEPARATE EQUIPMENT GROUND WIRE.
( ) DENOTES SEPARATE ISOLATED GROUND WIRE.
EACH CIRCUIT HOMERUN SHALL BE PROVIDED WITH DEDICATED
NEUTRAL
UNDERGROUND OR PLATFORM WIRING/CONDUIT
KEYED DRAWING NOTE
SPLIT CIRCUIT
WALL MOUNTED TELEPHONE OUTLET.
WALL/FLOOR/CEILING MOUNTED DATA OUTLET.
480/277V ELECTRICAL PANEL
CS CURRENT SENSOR
DUAL SWITCH WITH 50% STEP DIMMING BALLASTS
CONDUIT UP
CONDUIT DOWN
CONTINUOUS CIRCUITAA
C : COPIER
GFI : GROUND FAULT INTERRUPTER
WP : WEATHER PROOF OUTLET WITH PROTECTIVE COVER
ELECTRICAL SYMBOL LIST
A AMPERE
AFF ABOVE FINISHED FLOOR
AWG AMERICAN WIRE GAUGE
BRK BREAKER
C CONDUIT
CB CIRCUIT BREAKER
D EXISTING TO BE DEMOLISHED
DISC. SW. DISCONNECT SWITCH
DWG DRAWING
E, EX EXISTING TO REMAIN
EM DEVICE ON EMERGENCY CIRCUIT
EMT ELECTRICAL METALLIC TUBING
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FLA FULL LOAD AMPS
G GROUND
GFI GROUND FAULT INTERRUPTER
GRS GALVANIZED RESISTIVE CONDUIT
HP HORSE POWER
IG ISOLATED GROUND
KVA KILOVOLT-AMPS
KW KILOWATT
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MDP MAIN DISTRIBUTION PANEL
N NEW
NEC NATIONAL ELECTRICAL CODE
NFSS NON FUSED SAFETY SWITCH
NL NIGHT LIGHT FIXTURE
NTS NOT TO SCALE
P POLE
PH, Ø PHASE
PNL PANEL
R RELOCATED AT NEW LOCATION
RR REMOVE AND RELOCATE
S/N SOLID NEUTRAL
SWBD SWITCHBOARD
XFMR TRANSFORMER
TYP. TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
W WATTS
WP WEATHERPROOF
(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT)
T a
3 3
K
D
M
ABBREVIATIONS
(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)
a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE IDENTIFICATION.
a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR
30 MINUTE ROTARY TYPE TIMER SWITCH WITH HOLD-ON OPTION
T
WALL/CEILING MOUNTED LOW VOLTAGE VACANCY SENSOR SWITCH CONFIGURED AS
MANUAL ON, AUTO OFF, UON. CONFIGURE TIME-OUT SETTING FOR 15 UNLESS OTHERWISE
NOTED. DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:
LP-2
GROUND BUS BAR
D : DIMMER SWITCH
2 : DUAL SWITCH
a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR
D : DIMMER SWITCH
WALL/FLOOR MOUNTED POWER WHIP
HOMERUN WIRING WITHOUT TICK MARKS SHALL INCLUDE 2#12+1#12G-3/4"C
REF : REFRIGERATOR
USB : COMBINATION DUPLEX RECEPTACLE WITH 2-USB CHARGING PORTS. (BLUE COLOR)
DW : DISHWASHER
1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING
REGULATIONS, CODES, ETC.
A. LOCAL CODES AND ORDINANCES
B. THE EDITION OF THE NATIONAL ELECTRICAL CODE NFPA 70 (NEC) IN EFFECT.
2. PRIOR TO BEGINNING ANY WORK, SECURE NECESSARY PERMITS OR CLEARANCES FROM
THE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL LABOR AND MATERIALS FOR A
COMPLETE INSTALLATION. WORK SHALL BE EXECUTED BY EXPERIENCED ELECTRICIANS
WHO ARE LICENSED IN THE JURISDICTION WHERE THE PROJECT IS LOCATED.
3. THE CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN SHALL BE MAINTAINED.
4. THE ELECTRICAL PLANS ARE DIAGRAMMATIC ONLY. COORDINATE ELECTRICAL
EQUIPMENT LOCATION AND INSTALLATION WITH EQUIPMENT BEING SERVED. PROVIDE
ALL POWER AND TELECOMMUNICATION FINAL CONNECTIONS TO THE SYSTEM
FURNITURE AS REQUIRED.
5. ALL EQUIPMENT SUCH AS RELAYS, SWITCHES, PANELS, AND OTHER APPURTENANCES
SHALL HAVE IDENTIFICATION PLATES OF BLACK LAMINATED PLASTIC WITH 1/2" WHITE
LETTERS. ALL JUNCTION BOXES IN CEILING CAN BE MARKED WITH BLACK PERMANENT
MARKER ON COVER PLATES AS PANEL DESIGNATION AND CIRCUIT NUMBER FROM WHICH
THEY ARE FED.
6. ALL CONDUCTORS SHALL BE IDENTIFIED. ALL WIRING DEVICES SHALL BE USED WITH
TYPED LABEL ON THE COVER PLATE IDENTIFYING THE PANEL DESIGNATION AND CIRCUIT
NUMBER FROM WHICH THEY ARE FED.
7. ALL EQUIPMENT SHALL BE "UL" LISTED.
8. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL
ELECTRICAL CODE.
9. ALL CONNECTIONS TO DEVICES SHALL BE TAPED WITH SCOTCH 33 ELECTRICAL TAPE.
10. ALL CONDUITS AND JUNCTION BOXES SHALL BE CONCEALED IN FINISHED AREAS. PRIOR
TO CONCEALMENT OF NEW CONSTRUCTION, ALL WORK BEHIND FINISHED SURFACES
SHALL BE INSPECTED BY THE OWNER'S REPRESENTATIVE.
11. CONTRACTOR SHALL INFORM THE OWNER'S REPRESENTATIVE PRIOR TO BEGINNING
CONSTRUCTION AND PRIOR TO COMPLETION OF CONSTRUCTION TO ALLOW SUFFICIENT
TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION
WORK.
12. CONTROL WIRING SHALL BE TAGGED AT EACH END AND TERMINATED WHERE WORK HAS
BEEN PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURES SPECIFICATIONS.
13. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR
SHALL BE LIABLE FOR ITS REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE OR
IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE MATERIAL OR EQUIPMENT
DOES NOT MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS.
14. THE CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST, ANY LABOR,
MATERIALS, SERVICES, APPARATUS, AND DRAWINGS IN ADDITION TO CONTRACT
DOCUMENTS, IN ORDER TO COMPLY WITH ALL APPLICABLE LAWS, INDICATED AND/OR
SPECIFIED. PROVIDE ALL ELECTRICAL EQUIPMENT WITH ALL NECESSARY ASSOCIATED
ACCESSORIES AND CONDUIT INFRASTRUCTURE AS REQUIRED…
This is the start of the file's text. The full file is on GovTribe.