Exhibit E - Electrical O-M Manual.pdf
PDF 3 MB Posted
- Attached to
- Design-Build Miscellaneous Repairs Federal contract opportunity
- Solicitation number
- 12505B21R0002
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign In Sheets.pdf | ||
| SF-30 Amendment 01.pdf | ||
| ARS Facilities Design Standards.pdf | ||
| Exhibit A - Drawings for Recent Work.pdf | ||
| Exhibit B - Specifications for Recent Work.pdf | ||
| Exhibit F - Test and Balance Report.pdf | ||
| ARS-371.pdf | ||
| SF-1442 with Clauses and Provisions.pdf | ||
| Statement of Work.pdf | ||
| Exhibit C - Make Up Air Unit O-M Manual Part 1.pdf | ||
| Exhibit D - Make Up Air Unit O-M Manual Part 2.pdf | ||
| Wage Determination.pdf | ||
| ARS-372.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Siemens Submittal Package
USDA LBRU ANIMAL HOLDING AREA
10/19/2018Date :
usa.siemens.com/COMPAS
To: ADVANCED TECHNOLOGIES IN ELECTRICAL AND
COMMUNICATIONS INC (ATEC INC)
419 RANSDELL RD
LEBANON, IN, 46052
US
Job Name:
Quote Name:
ATEC
USDA LBRU ANIMAL HOLDING AREA
Quote Number:
Distributor:
nagldx00c_01101700_25_00_M00
KIRBY RISK CORP
ADVANCED TECHNOLOGIES IN ELECTRICAL
AND COMMUNICATIONS INC (ATEC INC)
Contractor:
Drawings are for: Approval Record
Please find enclosed 1 Copy of the below listed materials for the above referenced job.
Contents:
Molded Case Circuit Breakers IEC/OEM Control Components Panelboards
Upon the return of 1 Copy of “Approved “ or “No Exceptions Noted” drawings with release, it will be considered fact that the material as shown meets the requirements of the plans and specifications. For drawings returned indicating “Approved as Noted” or “Exceptions as Noted”, the cost of any additional equipment not included in the original quotation will be reflected in the total invoice price. Any changes other than those shown on these returned drawings will not be considered the responsibility of Siemens. It must be noted that these drawings and descriptive literature incorporate Siemens’ interpretation of the plans and specifications and are subject to corrections of errors. The above material is on “Hold for Release” status and will not be released until the receipt of signed submittals having one of the above notations with formal release. These drawings along with release should be returned as soon as possible so as not to cause any delays in shipping and/or escalation that might be incurred due to these delays.
Approval Drawings:
These drawings reflect the products manufactured by Siemens for this job.
Record Drawings:
10/19/2018Date:TRANSMITTAL LETTER
Bill of Material
To:
419 RANSDELL RD
LEBANON, IN 46052
USA
From:
4025 E. Cotton Center Suite 200
USA
Phoenix, AZ 85040
ADVANCED TECHNOLOGIES IN
ELECTRICAL AND COMMUNICATIONS INC
(ATEC INC)
Siemens Industry, Inc.
Job Name:
Quote Number:
ATEC
USDA LBRU ANIMAL HOLDING AREA
nagldx00c_01101700_25_00_M00
Quote Name:
Distributor: ADVANCED TECHNOLOGIES IN ELECTRICAL AND COMMUNICATIONS INC (ATEC INC)Contractor: ADVANCED TECHNOLOGIES IN ELECTRICAL AND COMMUNICATIONS INC (ATEC INC)Consultant:
DescriptionQuantityLine No.
20000 1 A3--PANELBOARD P1
1 SECTION
P1A18ML125CTST, System Voltage: 120/240 1Ø 3W GND Neutral AC, IR @ 22,000 AIC, Top Feed, Surface Mount, Bus Rating: 250A, Bus Material:
Copper, Plating: Tin, NEMA 1 INDOOR.
1 INTERIOR W/ 125A MAIN LUG-
(1)#6-350Kcmil1 - Subfeed/Feedthru Provision1 - 20" Wide NEMA 1 Indoor Enclosure1 - Card Holder-Std Plastic Sleeve1 - Certification - UL1 - Std Al/Cu Gnd Connector1 -
3 20A /2P-BLH-
Catalog #: B220H1 -
12 20A /1P-BLH-
Catalog #: B120H1 -
Enclosure, Catalog Number B32 Front, Catalog Number S32B
10 2 Standard Product--BREAKER 70A 2P 120/240V 22K BLH Catalog No.: B270H
11 2 UH-1 & UH-2--STARTER,MANUAL,TOGGLE SWITCH W/P.LIGHT
Catalog No.: SMFFG2P
12 2 UH-1 & UH-2--CLASS SMF HEATER ELEMENT,4.08-4.32 AMP
Catalog No.: SMFH36
13 4 EF-1A, EF-1B, EF-2 & P-1--STARTER,MANUAL,TOGGLE SWITCH W/P.LIGHT
Catalog No.: SMFFG1P
Bill of Material Date: 10/19/2018
1nagldx00c_01101700_25_00_M00
14 1 P-1--CLASS SMF HEATER ELEMENT,8.99-9.67 AMP
Catalog No.: SMFH45
15 3 EF-1A, EF-1B & EF-2--CLASS SMF HEATER ELEMENT,0.97-1.04 AMP
Catalog No.: SMFH19
Bill of Material Date: 10/19/2018
2nagldx00c_01101700_25_00_M00
Panelboards
A3
KIRBY RISK CORP
nagldx00c nagldx00c_01101700_25_00_M00-20000-1
1 2
ATEC
ADVANCED TECHNOLOGIES IN ELECTRICAL AND COMMUNICATIONS INC (ATEC INC)
A3
KIRBY RISK CORP
nagldx00c nagldx00c_01101700_25_00_M00-20000-1
1 2
ATEC
ADVANCED TECHNOLOGIES IN ELECTRICAL AND COMMUNICATIONS INC (ATEC INC)
A3
PANELBOARD NOTES
SECTION :1 OF 1
PANEL TYPE :P1
CATALOG NUMBER :P1A18ML125CTST
ENCLOSURE :1 Indoor SYSTEM VOLTAGE :120/240 1Ø 3W GND Neutral AC
IR RATING :22 K AIC
MAIN BUS :125 A
BUS MATERIAL :Tin Plated Copper FEED :Top MOUNTING :Surface SE LABEL :No SERIES RATED :No
CONDUIT AREA :N/A
*INDICATES POSITIONING NUMBERS TO HELP WITH
THE MANUAL PLACEMENT OF BREAKERS ON THE
MECHANICAL VIEW
PANELBOARD COMPONENTS
Main :
1 - 125A MAIN LUG
1-(1)#6-350Kcmil
Branches :
3 - 20A /2P-BLH
12 - 20A /1P-BLH
Options :
1-Subfeed/Feedthru Provision 1-Card Holder-Std Plastic Sleeve 1-NP Location - Trim 1-Certification - UL 1-Std Al/Cu Gnd Connector
9.0
K
IT
.0BLH 9 20A/1P
BLH1220A/1P
BLH 15 20A/1P
BLH1820A/1P
BLH
20A/2P
BLH620A/1P
BLH1020A/1P
BLH 13 20A/1P
BLH1620A/1P
BLH
20A/2P
BLH820A/1P
BLH 11 20A/1P
BLH1420A/1P
BLH 17 20A/1P
BLH
20A/2P
SUB FEED
PROVISION
125 A
MLO
20.05.75 Deep
DESIGNATION(S): PANELBOARD NOTES
NO. REVISIONS DATEDRAWN BY
1 0 10-17-2018nagldx00c
PANELBOARD COMPONENTS
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
10-17-2018
1OF
CONSLTCONTR
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
10-17-2018
1OF
CONSLTCONTR
KIRBY RISK CORP
nagldx00c nagldx00c_01101700_25_00_M00-20000-2
2 2
ATEC
ADVANCED TECHNOLOGIES IN ELECTRICAL AND COMMUNICATIONS INC (ATEC INC)
A3
KIRBY RISK CORP
nagldx00c nagldx00c_01101700_25_00_M00-20000-2
2 2
ATEC
ADVANCED TECHNOLOGIES IN ELECTRICAL AND COMMUNICATIONS INC (ATEC INC)
A3
ABBREVIATIONS
'MLO' MAIN LUGS ONLY
PANELBOARD NOTES
SECTION :1 OF 1
PANEL TYPE :P1
CATALOG NUMBER :P1A18ML125CTST
ENCLOSURE :1 Indoor SYSTEM VOLTAGE :120/240 1Ø 3W GND Neutral AC
IR RATING :22 K AIC
MAIN BUS :125 A
BUS MATERIAL :Tin Plated Copper FEED :Top MOUNTING :Surface SE LABEL :No SERIES RATED :No
CONDUIT AREA :N/A
*INDICATES POSITIONING NUMBERS TO HELP WITH
THE MANUAL PLACEMENT OF BREAKERS ON THE
MECHANICAL VIEW
A C
A C
A C
A C
A
9BLH 20A/1P
12 BLH 20A/1P
15BLH 20A/1P
18 BLH 20A/1P
BLH 20A/2P
6 BLH 20A/1P
10 BLH 20A/1P
13BLH 20A/1P
16 BLH 20A/1P
BLH 20A/2P
8 BLH 20A/1P
11BLH 20A/1P
14 BLH 20A/1P
17BLH 20A/1P
BLH 20A/2P
(1)#6-350KCMIL/PH AND N
125A
ABBREVIATIONS
'MLO' MAIN LUGS ONLY
PANELBOARD NOTES
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
10-17-2018
1OF
CONSLTCONTR
JOB
P.O.
TIE
S.O.
CUST.
ENG. LOC.BY
DATE
APP.
APP.
MFG. LOC.
DWG. FILE
DESIGNATION
DWG. NO.
REV.
SHEETNorcross, Georgia
Siemens Industry, Inc.
10-17-2018
1OF
CONSLTCONTR
usa.siemens.com/panelboards
- 30, 42 and 54 circuits for 400A (FT & NFT), also 66 circuit NFT
- 56”, 62”, 68” and 74” standard Enclosures are used.
• Suitable for use as service entrance given compliance with NEC.
• Bonding provisions are shipped with each panel.
• 240V and 480Y / 277V versions utilize identical boxes & fronts
Enclosure – Standard Type 1 enclosure is 20” wide x 5.75” deep.
Box Height is determined only by the number of circuits and FT or NFT selection, not by main lug or main circuit breaker. See charts P1-3 and P1-5 for box height.
Voltage – 480Y/277 Vac max. (Limited options for 600Y / 347V)
Amperage – 400 amp max.
Short Circuit Rating – 200 KAIC max. symmetrical or equal to the lowest rated device installed unless a series rating is indicated.
Panels with subfeed or feed-thru lugs without a main device, circuit breaker or fusible unit, are limited to a three-cycle rating.
The three-cycle rating for the P1 panel is limited to 22 KAIC. Note that the main device may be mounted remote from the panel.
Bussing – The P1 panel meets the majority of the markets bussing requirements. The standard bussing is temperature rated aluminum. The rating is per the requirements of UL 67– the standard for panelboards. All aluminum bussing is tin-plated.
Optional bussing for the P1 panel is temperature rated copper.
The copper bus option for this panel is tin-plated.
Weight – Approximate Total panelboard weight when filled with a normal quantity of breakers and accessories is about 3 lbs. (1.36 kg) per inch (54g per
mm) of box height.
Table P1-1 – Box Material Gauge Width Height (inches) Gauge Steel
20” (250A) 26, 32, 38, 44, 50, 56 #16 (#17 for endwalls)
(400A) 56, 62, 68, 74 #16 (#17 for endwalls)
Table P1-2 – Trim Material Gauge 20” (250A) 26, 32, 38, 44, 50, 56 #14
(400A) 56, 62, 68, 74 #14
Note: Tables in this document are numbered to match tables in Revised P1 S&A guide for consistency.
P1 Panelboards
The P1 Panelboards are available in both Feed-thru (FT) and Non-Feed-thru (NFT) variations. There is a savings of 6” of box height when a NFT version is selected which eliminates the sub-feed space. The Sub-Feed Space is where the Feed-thru Lugs, sub-feed breaker or a Surge Protection Device (SPD) is installed. The interior part number will end with a "T" for FT panels and will end with an "N" for NFT panels.
The P1 Panelboards also have Extended Circuit variations with 54 circuits and 66 circuits available.
Feed-thru (FT) panels are pre-engineered to accept the most common modifications without increasing box height. The enclosure size is determined by the number of circuits as shown in the Main Lug Table P1-5 or the Main Circuit Breaker Table P1-3.
All P1 FT main lug or main breaker panelboards have space built-in to accept either feed-thru lugs equal to the panel rating (or) one subfeed circuit breaker up to 250 amperes (or) a surge suppressor (SPD) without increasing box height. (When ordered with sub-feed space the interior part # will end with a “T”).
Non-Feed-thru (NFT) panels do not have a sub-feed space and cannot accept feed-thru lugs (or) sub-feed Breakers (or) SPD/TVSS devices.
(NFT panel interior part # will end in “N”).
Note the following features, all found in the innovative P1 lighting panelboards:
• Symmetrical 250A FT Interiors – To change from top to bottom-feed (or vice-versa), simply invert the interior. The deadfront labeling is always legible, even on the NFT panels when inverted.
- 400A are not symmetrical, but they are invertable.
• First in the Industry Ratings of 125 through 400A main lug and main breaker. Field convertible from main lug to main breaker and vice versa – with no increase in enclosure height.
• Field adaptability of feed-thru lugs (or) sub-feed circuit breaker without increasing enclosure size. (FT panels only)
• Neutral system is field upgradeable to 200% capacity – another industry first. (also 2/0 neutrals are available as a field install kit)
• Extended circuit panels are now available – up to 66 circuits.
- 18, 30, 42, 54 and 66 circuits for 250A (FT & NFT)
- 26”, 32”, 38”, 44”, 50” and 56” standard Enclosures are used.
Max Ampere rating
Main Breaker Types
Connections suitable for Cu or Al
Max # Poles FT a
Max # Poles
NFT
Dimensions in inches (mm) Unit Space Box Height
B Weight in
Lbs. (kg)
FT
A
NFT
A
100 BLb, BLHb, HBLb, BQDb
#8-#6 AWG Cu or Al #8-6 AWG Cu or #8-4 AWG Al #8-#1 AWG Cu or #6-#1/0 AWG Al
18 – 9 26 (661) 90 (41) 18 30 9 15 32 (813) 105 (48) 30 42 15 21 38 (965) 120 (55) 42 54 21 27 44 (1118) 135 (61) 54 66 27 33 50 (1270) 150 (67) 66 – 33 – 56 (1423) 165 (73)
NGBb, HGBb, LGBb
15-30 amp: #14-#6 Cu or #12-#6 Al 35-125 amp: #6-1/0 Cu #4-2/0 Al
18 – 9 26 (661) 95 (43)
ED4
ED6, HED4
#14-#10 AWG Cu or #12-10 AWG Al
#3-3/0 Cu or #1-2/0 Al #3-3/0 Cu or #1-2/0 Al
18 30 9 15 32 (813) 110 (50) 30 42 15 21 38 (965) 125 (57) 42 54 21 27 44 (1118) 140 (64) 54 66 27 33 50 (1270) 155 (71) 66 – 33 – 56 (1423) 170 (78)
QJ2, QJH2,
QJ2H, QR2,
QRH2, HQR2,
HQR2H
#6 AWG-300 Kcmil (Cu) or #4 AWG-300 Kcmil (Al)
18 – 9 26 (661) 95 (43) 18 30 9 15 32 (813) 110 (50) 30 42 15 21 38 (965) 125 (57)
250 FXD6, FD6,
HFD6, HFXD6
#6 AWG-350 Kcmil (Cu) or #4 AWG-350 Kcmil (Al)
42 54 21 27 44 (1118) 140 (64) 54 66 27 33 50 (1270) 155 (71) 66 – 33 – 56 (1423) 170 (78)
400 JD6, JXD6,
HJD6, HJXD6
3/0-500 Kcmil (Cu) or 4/0-500 Kcmil (Al)
– 30 – 15 56 (1423) 172 (78) 30 42 15 21 62 (1575) 190 (86) 42 54 21 27 68 (1728) 208 (95) 54 66 27 33 74 (1880) 226 (104)
Note: Main breakers use breaker connectors. For sizes, see breaker connector chart. 400A MLO Panels have wire bend space for 600kcmil CU & AL wire when using standard lugs. With optional 750kcmil AL/CU connectors, wire bend space is available for up to 750kcmil AL wire, but is still limited to 600kcmil CU wire.
a
Maximum Ampere rating
Max # Poles
FT
Max # Poles
NFT
Dimensions in inches (mm)
MLO Connectors Suitable for
Unit Space Box Height B"
Weight in Lbs. (kg)
FT
A
NFT
A
(or)
18 – 9 26 (661) 90 (41)
(1) #6 AWG - 350 kcmil (CU or AL)
18 30 9 15 32 (813) 105 (48) 30 42 15 21 38 (965) 120 (55) 42 54 21 27 44 (1118) 135 (61) 54 66 27 33 50 (1270) 150 (67) 66 – 33 – 56 (1423) 165 (73)
– 30 – 15 56 (1423) 120 (55) AL (2) 1/0 - 250 kcmil or
(1) #2 AWG - 600 kcmil CU (2) 1/0 - 4/0 or
(1) #2 AWG - 600 kcmil
30 42 15 21 62 (1575) 135 (61) 42 54 21 27 68 (1728) 150 (68) 54 66 27 33 74 (1880) 165 (75)
Typical Panelboard Wiring Diagrams
Application Type P1 Panelboards
Table P1-3 – Main Breaker Panel Size Selector – P1
400A 66 circuit only available with non-feed thru versions.
b BL, BLH, HBL, BQD, and xGB mount in unit space and count in max. # of poles.
Table P1-5 - Main Lug Panel Size Selector - P1
Application Type P1 Panelboards
Table P1-6 – Branch Circuit Breakers Max.
Amp Rating
Breaker Type
Number of Poles
Max. Interrupting Rating (kA) Available Trip Values
Connections Suitable for Cu or AI120V 120/240V 240V 277V 480/277V
BL
1 10 – – – – 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70
15-20A #14-#10 AWG Cu #12-#10 AWG Al 25-35A #8-#6 AWG Cu #8-#6 AWG Al 40-50A #8-#6 AWG Cu #8-#4 AWG Al 55-70A #8-#4 AWG Cu #8-#2 AWG Al 80-100A #4-#1/0 AWG Cu #2-#1/0 AWG Al
2 – 10 – – – 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 3 – – 10 – – 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
BLR 2 – – 10 – – 15, 20, 30, 40, 50, 60, 70, 90, 100
BL, HID
1 10 – – – – 15, 20, 30 2 – 10 – – – 15, 20, 30
BLH
1 – 22 – – – 15, 20, 30, 40, 50, 55, 60, 70 2 – 22 – – – 15, 20, 30, 40, 50, 60, 70, 90, 100 3 – – 22 – – 15, 20, 30, 40, 50, 60, 70, 80, 90, 100
HBL
1 – 65 – – – 15, 20, 30, 40, 50 2 – 65 – – – 15, 20, 30, 40, 50, 60, 70 3 – – 65 – – 15, 20, 30, 40, 50, 60, 70, 80, 90, 100
BLF2
BLFB
1 10 – – – – 15, 20, 30 2 – 10 – – – 15, 20, 30, 40, 50, 60
BLHF2
BLHFB
1 22 – – – – 15, 20, 30 2 – 22 – – – 15, 20, 30, 40, 50, 60
HBLF2 1 65 – – – – 15, 20, 30
BG a 2 10 – – – – 15, 20, 30 3 – 10 – – – 15, 20, 30
BLE
1 10 – – – – 15, 20, 30 2 – 10 – – – 15, 20, 30, 40, 50, 60
BLEH
1 22 – – – – 15, 20, 30 2 – 22 – – – 15, 20, 30, 40, 50, 60
BAF 1 10 – – – – 15, 20
BAFH 1 22 – – – – 15, 20
BQD
1 – 65 – 14 – 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 15-40A #14-#6 AWG Cu #12-#6 AWG Al 45-100A #8-#1 AWG Cu #6-#1/0 AWG Al
2 – 65 – – 14 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
3 – – 65 – 14 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
NGB bc
1 100 – – 25 – 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
15-30A #14-#6 Cu #12-#6 Al 35-125 #6-1/0 Cu #4-2/0 Al
2 – 100 100 – 25 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
3 – 100 100 – 25 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
HGB bc
1 100 – – 35 – 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
2 – 100 100 – 35 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
3 – 100 100 – 35 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
LGB bc
1 100 – – 65 – 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
2 – 100 100 – 65 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c
3 – 100 100 – 65 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 125 c a Two-pole breaker is one phase and neutral. Three-pole is two phases and neutral.
b P1 panel with NGB/HGB/LGB branch devices will not accept BL or BQD frames in the same panel as branch devices.
c The New Revised P1 (18 circuit 250A only) is limited to 100A per connection (200A per pair) when installing Branch Breakers across from one another.
All other configurations allow 125A per connection max. (250A per pair max.)
Note: BL, HBL and BQD breakers are mounted in common mountings in 3” or (6) pole increments.
Application Type P1 Panelboards
400 amp kit is for main—only, not allowed for subfeed breaker.
Table P1-7 – Subfeed Breakers Breaker Type
Number of Poles
Max. Interrupting Rating (kA) Available Trip Values240V 480Y/277V
QJ2 2, 3 10 – 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJH2 2, 3 22 – 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2H 2, 3 42 – 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QR2 2, 3 10 – 100, 110, 125, 150, 175, 200, 225
QRH2 2, 3 25 – 100, 110, 125, 150, 175, 200, 225
HQR2 2, 3 65 – 100, 110, 125, 150, 175, 200, 225
HQR2H 2, 3 100 – 100, 110, 125, 150, 175, 200, 225
ED4 2, 3 65 18 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70, 80, 90, 100, 110, 125
ED6 2, 3 65 25 15, 20, 25, 30, 35, 40 50, 60, 70, 80, 90, 100, 110, 125
HED4 2, 3 100 42 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70, 80, 90, 100, 110, 125
HHED6 2, 3 100 65 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125
FXD6 2, 3 65 35 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
FD6 2, 3 65 35 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
HFD6 2, 3 100 65 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
HFXD6 2, 3 100 65 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
Answers for industry.
Circuit breakers
Panelboard mounted, non-interchageable trip, molded case circuit breakers Types BL, BLH, HBL,BLF, BLHF, BLE, BLEF, BAF, BAFH, BG 125A Frame
Specifications:
• 120, 120/240, 240Vac max.
• UL Listed, File # E82615
• CSA and NOM Certified
• HACR Rated
• 40C Calibration
• Thermal / Magnetic Trip
• Molded Case Switch, 2 pole 30 - 60 Amperes
• HID Lighting, 1 & 2 pole 15, 20, 30 Amperes
• SWD duty--1 pole
15 - 20 Amperes
Enclosures: Not Applicable
Interruption ratings
Breaker Type No. of Poles Ampere Rating
UL A.I.R. (kA) RMS Symmetrical Amperes
Volts AC (50/60 Hz)
120 120/240 240
BL
1 10 - 70 10 10
2* 15 - 100 10
2 10 - 125 10
3 10 - 100 10
BLH
1 15 - 70 22 22
2 15 - 125 22
3 15 - 100 22
HBL
1 15 - 70 65 65
2 15 - 125 65
3 15 - 100 65
* UL listed for use on 3-phase grounded "B" systems
Ground-Fault Protection Class A - 5mA
Breaker Type No. of Poles Ampere Rating
UL A.I.R. (kA) RMS Symmetrical Amperes
Volts AC (50/60 Hz)
120 120/240 240
BLF
1 15 - 30 10 10 -
2 15 - 60 - 10 -
BLHF
1 15 - 30 22 22 -
2 15 - 60 - 22 -
Ground-Fault Protection 30mA
BLE
1 15 - 30 10 10 -
2 15 - 60 - 10 -
BLEH
1 15 - 30 22 22 -
2 15 - 60 - 22 -
Arc-Fault Circuit Interrupter
(AFCI)
BAF
1 15 - 20 10 10 -
2 15 - 20 - 10 -
BAFH
1 15 - 20 22 22 -
2 15 - 20 - 22 -tararj Text Box
Factory Added Options For all Factory Modifications Consult Siemens for cost adders
Description
External Accessories
Field installable Padlocking Device for 1, 2, and 3 poles Handle Blocking Device
Pressure Wire Connectors Load Side terminal factory installed only non-UL 50C calibration
400 Hz Calibration
415V, 50Hz Calibration
Fungus Proofing Ampere Rating
Cables Per Lug
Wire Range UL listed 5kA max. A.I.R.
non-UL 1 & 2 poles only
External Accessories (Factory Installed only)
15 - 20 1 #14 - #10 AWG Cu.
1 #12 - #10 AWG Al
25 - 35 1 #14 - #6 AWG Cu.
1 #12 - #6 AWG Al.
Shunt Trip Auxiliary Switch 40 - 50 1 #8 - #6 AWG Cu.
1 #8 - #4 AWG Al.
1 0 55 - 70
1 #8 - #4 AWG Cu.
0 1 1 #8 - #2 AWG Al.
(adds 1 pole width to left side of circuit breaker) 80 - 100
1 #4 - #1/0 AWG Cu.
1 #2 - #1/0 AWG Al.
110 - 125 1 #2 - #1/0 AWG Cu.
1 #1/0 - #2/0 AWG Al.
Note: Molded Case Circuit Breakers having a rated ampacity of 125 amperes or less are to be connected with 60 or 75C wire. Exceptions of this rule are outlined in article 110-12 C of the National Electrical Code.
Switching Neutrals
Breaker Type No. of Poles Ampere Rating
UL A.I.R. (kA) RMS Symmetrical Amperes
Volts AC (50/60 Hz)
120 120/240 240
BG
2 15 - 30 10 - -
3 15 - 30 - 10 -
Subject to change without prior notice Order No.: CBSS-BLCUT-0709
All rights reserved Printed in USA © 2009 Siemens Energy & Automation, Inc.
Siemens Energy & Automation, Inc.
Industry Sector 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com
The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract.
All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.
tararj Text Box
T im e in
S ec o n d s
SIEMENS 20 A
Current in Amperes X 10 814614-TC20 rev. 0P September 2016
Siemens Industry Inc. Norcross, GA, 30092
For Max. Interrupting Rating
See table above.
For application and coordination purposes only. Based on 40°C ambient cold start. Connected with 4 feet of rated wire (75°C) per terminal. Tested in open air with current.
Types QP, BL, QT, QPH, BLH, HQP, HBL 60Hz 120/240 Volts
Interrupting Ratings
10 kA
22 kA
65 kA
Instantaneous Trip Table
QP, BL, QT
QPH, BLH
HQP, HBL
15 - 20
Time Current Characteristics Curve
Types QP, BL, QT, QPH, BLH, HQP, HBL 1 Pole
Rating Amperes Fixed Instantaneous Trip Amperes 185 - 320
Breaker Type Symetrical RMS Amperes
Circuit Breakers
Answers for industry.
Circuit breakers
Panelboard mounted, non-interchageable trip, molded case circuit breakers Types BL, BLH, HBL,BLF, BLHF, BLE, BLEF, BAF, BAFH, BG 125A Frame
Specifications:
• 120, 120/240, 240Vac max.
• UL Listed, File # E82615
• CSA and NOM Certified
• HACR Rated
• 40C Calibration
• Thermal / Magnetic Trip
• Molded Case Switch, 2 pole 30 - 60 Amperes
• HID Lighting, 1 & 2 pole 15, 20, 30 Amperes
• SWD duty--1 pole
15 - 20 Amperes
Enclosures: Not Applicable
Interruption ratings
Breaker Type No. of Poles Ampere Rating
UL A.I.R. (kA) RMS Symmetrical Amperes
Volts AC (50/60 Hz)
120 120/240 240
BL
1 10 - 70 10 10
2* 15 - 100 10
2 10 - 125 10
3 10 - 100 10
BLH
1 15 - 70 22 22
2 15 - 125 22
3 15 - 100 22
HBL
1 15 - 70 65 65
2 15 - 125 65
3 15 - 100 65
* UL listed for use on 3-phase grounded "B" systems
Ground-Fault Protection Class A - 5mA
Breaker Type No. of Poles Ampere Rating
UL A.I.R. (kA) RMS Symmetrical Amperes
Volts AC (50/60 Hz)
120 120/240 240
BLF
1 15 - 30 10 10 -
2 15 - 60 - 10 -
BLHF
1 15 - 30 22 22 -
2 15 - 60 - 22 -
Ground-Fault Protection 30mA
BLE
1 15 - 30 10 10 -
2 15 - 60 - 10 -
BLEH
1 15 - 30 22 22 -
2 15 - 60 - 22 -
Arc-Fault Circuit Interrupter
(AFCI)
BAF
1 15 - 20 10 10 -
2 15 - 20 - 10 -
BAFH
1 15 - 20 22 22 -
2 15 - 20 - 22 -
Factory Added Options For all Factory Modifications Consult Siemens for cost adders
Description
External Accessories
Field installable Padlocking Device for 1, 2, and 3 poles Handle Blocking Device
Pressure Wire Connectors Load Side terminal factory installed only non-UL 50C calibration
400 Hz Calibration
415V, 50Hz Calibration
Fungus Proofing Ampere Rating
Cables Per Lug
Wire Range UL listed 5kA max. A.I.R.
non-UL 1 & 2 poles only
External Accessories (Factory Installed only)
15 - 20 1 #14 - #10 AWG Cu.
1 #12 - #10 AWG Al
25 - 35 1 #14 - #6 AWG Cu.
1 #12 - #6 AWG Al.
Shunt Trip Auxiliary Switch 40 - 50 1 #8 - #6 AWG Cu.
1 #8 - #4 AWG Al.
1 0 55 - 70
1 #8 - #4 AWG Cu.
0 1 1 #8 - #2 AWG Al.
(adds 1 pole width to left side of circuit breaker) 80 - 100
1 #4 - #1/0 AWG Cu.
1 #2 - #1/0 AWG Al.
110 - 125 1 #2 - #1/0 AWG Cu.
1 #1/0 - #2/0 AWG Al.
Note: Molded Case Circuit Breakers having a rated ampacity of 125 amperes or less are to be connected with 60 or 75C wire. Exceptions of this rule are outlined in article 110-12 C of the National Electrical Code.
Switching Neutrals
Breaker Type No. of Poles Ampere Rating
UL A.I.R. (kA) RMS Symmetrical Amperes
Volts AC (50/60 Hz)
120 120/240 240
BG
2 15 - 30 10 - -
3 15 - 30 - 10 -
Subject to change without prior notice Order No.: CBSS-BLCUT-0709
All rights reserved Printed in USA © 2009 Siemens Energy & Automation, Inc.
Siemens Energy & Automation, Inc.
Industry Sector 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com
The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract.
All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.
tararj Text Box
T im e in
S ec o n d s
SIEMENS 20 A
Current in Amperes X 10 814614-TC20 rev. 0P September 2016
Siemens Industry Inc. Norcross, GA, 30092
For Max. Interrupting Rating
See table above.
For application and coordination purposes only. Based on 40°C ambient cold start. Connected with 4 feet of rated wire (75°C) per terminal. Tested in open air with current.
Types QP, BL, QT, QPH, BLH, HQP, HBL 60Hz 120/240 Volts
Interrupting Ratings
10 kA
22 kA
65 kA
Instantaneous Trip Table
QP, BL, QT
QPH, BLH
HQP, HBL
15 - 20
Time Current Characteristics Curve
Types QP, BL, QT, QPH, BLH, HQP, HBL 1 Pole
Rating Amperes Fixed Instantaneous Trip Amperes 185 - 320
Breaker Type Symetrical RMS Amperes
Manual Switch
Manual Control Fractional HP starters, Class SMF
Class SMF Class SMF fractional horsepower starters provide overload protection as well as manual on-off control for small horsepower motors in a variety of industrial and commercial applications. Available in one or two pole versions, these devices are suitable for use with AC single phase motors up to 1 HP. Two pole starters can also be used with DC motors up to 3⁄4 HP. Typical applications include fans, conveyors, pumps and small machine tools.
Continuous Current Rating
• 16 amperes
Overload Trip Assembly Motor protection is provided by a Class SMFH heater element which must be installed before the starter will operate.
Enclosures Class SMF, NEMA Type 1 surface mounting enclosures are sheet steel with a thermo-plastic wrap-around cover for convenience in wiring. A zinc alloy die casting is used for NEMA Type 4 enclosures.
Mounting Open types without a pilot light fit standard single gang switch boxes, and can be used with any cover plate having a standard toggle cutout.
Volts
Maximum horsepower
AC Single phase DC
1-Pole 2-Pole 2-Pole
115–230 1 1 3⁄4
277 1 1 —
Accessories – Class SMF
Description Catalog Number
Handle guard kit with padlock provision SMFFL1
Starter – Class SMF, Single Phase 1
Type of operator
No of Poles
Starter Features
Open Type
NEMA Type 1
General Purpose enclosure, surface mounting
NEMA Type 3R, 4 & 12 watertight, dust-tight, metallic enclosure with clear cover
NEMA Type 4 watertight, dust-tight, metallic enclosure
Catalog Number Catalog Number Catalog Number Catalog Number
Toggle
Standard SMFF01 SMFFG1 SMFFWN1 —
Red Pilot Light SMFF01P SMFFG1P —
Standard SMFF02 SMFFG2 SMFFWN2 —
Red Pilot Light SMFF02P SMFFG2P —
Handle with Handle Guard/Lock-off – Class SMF, Single Phase 1
Toggle 1 Standard — SMFFG5 — SMFFW12
Red Pilot Light — SMFFG5P — SMFFW1P 2
Class SMF Starter in a NEMA Type 1 Enclosure without Pilot Light
1 One heater element required.
2 Furnished with (1) 3⁄4" NPT Outlet in bottom (reversible for top feed).
Ordering Information
1. Determine number of heater elements required from Table A.
2. Determine motor full load current and service factor.
3. If the motor and controller are in the same ambient temperature:
a. For 1.15 to 1.25 service factor motors, use 100% of motor full load current for heater element selection.
b. For 1.0 service factor motors use 90% of motor full load current for heater element selection.
c. Heater elements are class 20.
4. If the motor and controller are in different ambient temperatures, multiply motor full load current by the multiplier in Table B. Use the resultant full load current for heater element selection.
5. Select proper heater element from table below.
6. All tables are based on the operation of the motor and controller in the same ambient temperature, 40°C (104°F) or less. Always be certain the correct heater element is installed in the starter before operating the motor.
Heater Elements Class SMF
Catalog Number
Motor Full-Load Current (Amps)
SMFH01 0.157–0.173
SMFH02 0.174–0.192
SMFH03 0.193–0.212
SMFH04 0.213–0.235
SMFH05 0.236–0.261
SMFH06 0.262–0.289
SMFH07 0.290–0.321
SMFH08 0.322–0.355
SMFH09 0.356–0.399
SMFH10 0.41–0.44
SMFH11 0.45–0.49
SMFH12 0.50–0.53
SMFH13 0.54–0.58
SMFH14 0.59–0.65
SMFH15 0.66–0.71
SMFH16 0.72–0.78
SMFH17 0.79–0.85
SMFH18 0.86–0.96
SMFH19 0.97–1.04
SMFH20 1.05–1.16
SMFH21 1.17–1.25
SMFH22 1.30–1.39
SMFH23 1.38–1.54
SMFH24 1.48–1.63
SMFH25 1.57–1.75
SMFH26 1.66–1.86
Catalog Number
Motor Full-Load Current (Amps)
SMFH27 1.80–1.99
SMFH28 1.96–2.15
SMFH29 2.16–2.38
SMFH30 2.39–2.75
SMFH31 2.76–2.84
SMFH32 2.85–3.06
SMFH33 3.07–3.45
SMFH34 3.46–3.70
SMFH35 3.71–4.07
SMFH36 4.08–4.32
SMFH37 4.33–4.90
SMFH38 4.91–5.35
SMFH39 5.36–5.85
SMFH40 5.86–6.41
SMFH41 6.42–6.79
SMFH42 6.80–7.57
SMFH43 7.58–8.15
SMFH44 8.16–8.98
SMFH45 8.99–9.67
SMFH46 9.68–9.95
SMFH47 9.96–10.8
SMFH48 10.9–12.1
SMFH49 12.2–13.1
SMFH50 13.2–13.9
SMFH51 14.0–15.0
SMFH52 15.1–16.0
Heater Motor Full-Load List
Device
Number of Heater Elements Notes
SMFF*1
SMFF*2
SMFF*3
SMFF*4
SMFF*5
SMFF*6
All single pole and two pole SMF starters require only one Heater Element.
SMFF*22
SMFF*44
2 Duplex Unit. One Heater Element per starter.
SMFF*11
SMFF*22
Two Speed Starter. One Heater Element per speed.
Ambient Temperature of Motor
Continuous Duty Motor Service Factor
Same as Controller Ambient
Constant 10ºC (18ºF) Higher than Controller Ambient
Constant 10ºC (18ºF) Lower than Controller Ambient
1.15 to 1.25 1.0 0.9 1.05
1.0 0.9 0.8 0.95
Table A – Number of Heater Elements
Table B – Special Applications Heater Element Selection
Starter – Class SMF, Single Phase 1
Type of operator
No of Poles
Starter Features
Open Type
NEMA Type 1
General Purpose enclosure, surface mounting
NEMA Type 3R, 4 & 12 watertight, dust-tight, metallic enclosure with clear cover
NEMA Type 4 watertight, dust-tight, metallic enclosure
Catalog Number Catalog Number Catalog Number Catalog Number
Toggle
Standard SMFF01 SMFFG1 SMFFWN1 —
Red Pilot Light SMFF01P SMFFG1P —
Standard SMFF02 SMFFG2 SMFFWN2 —
Red Pilot Light SMFF02P SMFFG2P —
Handle with Handle Guard/Lock-off – Class SMF, Single Phase 1
Toggle 1 Standard — SMFFG5 — SMFFW12
Red Pilot Light — SMFFG5P — SMFFW1P 2
Manual Control Heater Elements, Class SMF
USDA Animal Holding Area
10/19/2018 18-56134-2
LIGHT SOURCE
8719 CASTLE PARK DR
INDIANAPOLIS, IN 46256-1272
Phone: 317-598-6900 Fax: 317-598-6910 Contact: Foreman, Andrew
GT8 F 2 32 FW A12 120 DMHL3D
LP835
L1 ABL-Lithonia Lighting
GT8 F 2 32 FW A12 120 DMHL3D
EL LP835
L1-EM ABL-Lithonia Lighting
ECC R M6X ABL-Lithonia Lighting
MA-R-IVDIM R LUTRON
MRF2-F6AN-DV-IVDIM M LUTRON
Catalog NumberManufacturer/BrandType
Project 18-56134-2 USDA Animal Holding Area
Submitted By
LIGHT SOURCE
FEATURES & SPECIFICATIONS
INTENDED USE —Static T8 fixtures provide general illumination for recessed applications; idea for restricted plenum spaces.
ATTRIBUTES — Designed exclusively for use with T8 lamps, electronic ballasts and sockets.
CONSTRUCTION — Smooth hemmed sides and smooth, inward formed end flanges for safe handling.
Lighter weight fixture allows for safe, easy installation.
Standard steel door frame has superior structural integrity with premium extruded appearance and precision flush mitered corners. Powder painted, steel latches provide easy, secure door closure.
Superior mechanical light seal requires no foam gasketing. Integral T-bar clips secure fixture to T-bar system. Housing formed from cold-rolled steel. Acrylic shielding material 100% UV stabilized. No asbestos is used in this product.
FINISH — Five-stage iron-phosphate pretreatment ensures superior paint adhesion and rust resistance.
Painted parts finished with high-gloss, baked white enamel.
OPTICAL — Broad range of lens options available.
ELECTRICAL — Standard ballast is electronic, thermally protected, resetting, Class P, HPF, non-PCB, UL Listed, CSA certified ballast, universal voltage and sound rated A.
Luminaire is suitable for damp locations. AWM, TFN or THHN wire used throughout, rated for required temperatures.
LISTING — Standard: UL. Optional: Canada — CSA or cUL; Mexico — NOM.
WARRANTY — 1-year limited warranty. Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
US patents: 6,210,025; 6,231,213; 2,288,471.
Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.
Static Troffer
GT8 1'x4' 1, 2 or 3 Lamps
Specifications
Length: 48 (121.8)
Width: 12 (30.5)
Depth: 4-1/2 (11.4)
Weight: 17 lbs (7.7 kg) All dimensions are inches (centimeters).
NOTES:
1. Available with flush door frames only.
2. MVOLT standard for 120-277V applications, 50-60hz operations require voltage specified.
3. Must specify voltage 120 or 277.
GT8
Series Trim type Number of lamps Lamp type Door frame Diffuser type Voltage Options
GT8 1' wide (blank) Grid F Overlapping flanged
Not included
32 32W T8 (48") (blank) Flush steel, white
FN Flush aluminum, natural
FM Flush aluminum, matte black
FW Flush aluminum, white
RN Regressed aluminum, natural
RW Regressed aluminum, white
A12 #12 pattern acrylic
A12125 #12 pattern acrylic, .125" thick
A19 #19 pattern acrylic, .156" thick
A15 #15 pattern acrylic, .2" thick
PC1S 1/2" x 1/2" x 1/2" plastic cube louver, silver
PC2S 1-1/2" x 1-1/2" x 1" plastic cube louver, silver w/ flange1
MVOLT2
Others available
1/3 One 3-lamp ballast GEB10IS Electronic ballast, <10% THD, instant start GEB10RS Electronic ballast, <10% THD, rapid start EL 500 nominal lumen battery pack (non-CEC compliant) EL14 1400 nominal lumen battery pack (non-CEC compliant) EL14 T20C 1400 nominal lumen battery pack, CEC compliant GLR Internal fast-blow fuse3 GMF Internal slow-blow fuse3 LST Tandem-wired fixture pairs
(shared ballasts) PWS1836 6' prewire, 3/8" dia., 18-gauge, 1 circuit LP_ Lamped, specify lamp type and color PAF Painted after fabrication
(white enamel) SSR Specular silver interior finish
(95% reflective) CRE Flanged trim for continuous row mounting (end) CRM Flanged trim for continuous row mounting (middle) JP Palletized and stretch-wrapped without individual cartons; grid trim only
CSA CSA Certified NOM NOM Certified
ORDERING INFORMATION For shortest lead times, configure products using bolded options. Example: GT8 2 32 A12 MVOLT GEB10IS
Catalog Number
Notes
Type
FLUORESCENT: GT8-1X4
D
L
PS
PROVIDED WITH ECO 10 DRIVER-DMHL3D
F 2 32 A12 DMHL3D LP835120
Catalog Number
GT8 F 2 32 FW A12 120 DMHL3D LP835
Notes
Type
L1 Project 18-56134-2 USDA Animal Holding Area
MOUNTING DATA
Continuous row mounting of flanged units requires CRE and CRM trim options (see Options).
GT8 1'x4' Static Troffer
DIMENSIONS
All dimensions are inches (centimeters) unless otherwise indicated.
NOTE:
1 Recommended rough-in dimensions for F-trim fixtures 12"x48" (Tolerance is +1/4"-0"). Swing-gate range
1-9/16" to 3-3/4". Swing-gate span 10-3/4" to 14-3/4".
PHOTOMETRICS
Calculated using the zonal cavity method in accordance with IESNA LM41 procedure. Floor reflectances are 20%.
Lamp configurations shown are typical. Full photometric data on these and other configurations available upon request.
GT8-1X4
FLUORESCENT: One Lithonia Way Conyers, GA 30012 Phone: 800-858-7763 Fax: 770-929-8789 www.lithonia.com ©2009-2017 Acuity Brands Lighting, Inc. All rights reserved. Rev. 10/27/17
4-1/2 (11.4)
12 (30.5)
2-1/2 (6.4)
LC
4-1/2 (11.4)
12 (30.5)
2-1/2 (6.4)
LC
Coefficients of Utilization pf 20% pc 80% 50% 30% pw 70% 50% 30% 50% 30% 10% 50% 30% 10%
R C
R
Zonal Lumen Summary
Zone Lumens % Lamp % Fixture 0° - 30° 0° - 40° 0° - 60° 0° - 90° 90° - 180° 0° - 180°
25.8 41.2 66.3 77.7 0.0 77.7
33.2 53.0 85.3
100.0 0.0
100.0
Report:
LUMENS PER LAMP:
LTL12536
Luminaire Efficiency: 77.7%
GT8 2 32 A12
Catalog Number
GT8 F 2 32 FW A12 120 DMHL3D LP835
Notes
Type
L1 Project 18-56134-2 USDA Animal Holding Area
FEATURES & SPECIFICATIONS
INTENDED USE —Static T8 fixtures provide general illumination for recessed applications; idea for restricted plenum spaces.
ATTRIBUTES — Designed exclusively for use with T8 lamps, electronic ballasts and sockets.
CONSTRUCTION — Smooth hemmed sides and smooth, inward formed end flanges for safe handling.
Lighter weight fixture allows for safe, easy installation.
Standard steel door frame has superior structural integrity with premium extruded appearance and precision flush mitered corners. Powder painted, steel latches provide easy, secure door closure.
Superior mechanical light seal requires no foam gasketing. Integral T-bar clips secure fixture to T-bar system. Housing formed from cold-rolled steel. Acrylic shielding material 100% UV stabilized. No asbestos is used in this product.
FINISH — Five-stage iron-phosphate pretreatment ensures superior paint adhesion and rust resistance.
Painted parts finished with high-gloss, baked white enamel.
OPTICAL — Broad range of lens options available.
ELECTRICAL — Standard ballast is electronic, thermally protected, resetting, Class P, HPF, non-PCB, UL Listed, CSA certified ballast, universal voltage and sound rated A.
Luminaire is suitable for damp locations. AWM, TFN or THHN wire used throughout, rated for required temperatures.
LISTING — Standard: UL. Optional: Canada — CSA or cUL; Mexico — NOM.
WARRANTY — 1-year limited warranty. Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
US patents: 6,210,025; 6,231,213; 2,288,471.
Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.
Static Troffer
GT8 1'x4' 1, 2 or 3 Lamps
Specifications
Length: 48 (121.8)
Width: 12 (30.5)
Depth: 4-1/2 (11.4)
Weight: 17 lbs (7.7 kg) All dimensions are inches (centimeters).
NOTES:
1. Available with flush door frames only.
2. MVOLT standard for 120-277V applications, 50-60hz operations require voltage specified.
3. Must specify voltage 120 or 277.
GT8
Series Trim type Number of lamps Lamp type Door frame Diffuser type Voltage Options
GT8 1' wide (blank) Grid F Overlapping flanged
Not included
32 32W T8 (48") (blank) Flush steel, white
FN Flush aluminum, natural
FM Flush aluminum, matte black
FW Flush aluminum, white
RN Regressed aluminum, natural
RW Regressed aluminum, white
A12 #12 pattern acrylic
A12125 #12 pattern acrylic, .125" thick
A19 #19 pattern acrylic, .156" thick
A15 #15 pattern acrylic, .2" thick
PC1S 1/2" x 1/2" x 1/2" plastic cube louver, silver
PC2S 1-1/2" x 1-1/2" x 1" plastic cube louver, silver w/ flange1
MVOLT2
Others available
1/3 One 3-lamp ballast GEB10IS Electronic ballast, <10% THD, instant start GEB10RS Electronic ballast, <10% THD, rapid start EL 500 nominal lumen battery pack (non-CEC compliant) EL14 1400 nominal lumen battery pack (non-CEC compliant) EL14 T20C 1400 nominal lumen battery pack, CEC compliant GLR Internal fast-blow fuse3 GMF Internal slow-blow fuse3 LST Tandem-wired fixture pairs
(shared ballasts) PWS1836 6' prewire, 3/8" dia., 18-gauge, 1 circuit LP_ Lamped, specify lamp type and color PAF Painted after fabrication
(white enamel) SSR Specular silver interior finish
(95% reflective) CRE Flanged trim for continuous row mounting (end) CRM Flanged trim for continuous row mounting (middle) JP Palletized and stretch-wrapped without individual cartons; grid trim only
CSA CSA Certified NOM NOM Certified
ORDERING INFORMATION For shortest lead times, configure products using bolded options. Example: GT8 2 32 A12 MVOLT GEB10IS
Catalog Number
Notes
Type
FLUORESCENT: GT8-1X4
D
L
PS
PROVIDED WITH ECO 10 DRIVER-DMHL3D
F 2 32 A12 DMHL3D EL LP835120
Catalog Number
GT8 F 2 32 FW A12 120 DMHL3D EL LP835
Notes
Type
L1-EM
Project 18-56134-2 USDA Animal Holding Area
MOUNTING DATA
Continuous row mounting of flanged units requires CRE and CRM trim options (see Options).
GT8 1'x4' Static Troffer
DIMENSIONS
All dimensions are inches (centimeters) unless otherwise indicated.
NOTE:
1 Recommended rough-in dimensions for F-trim fixtures 12"x48" (Tolerance is +1/4"-0"). Swing-gate range
1-9/16" to 3-3/4". Swing-gate span 10-3/4" to 14-3/4".
PHOTOMETRICS
Calculated using the zonal cavity method in accordance with IESNA LM41 procedure. Floor reflectances are 20%.
Lamp configurations shown are typical. Full photometric data on these and other configurations available upon request.
GT8-1X4
FLUORESCENT: One Lithonia Way Conyers, GA 30012 Phone: 800-858-7763 Fax: 770-929-8789 www.lithonia.com ©2009-2017 Acuity Brands Lighting, Inc. All rights reserved. Rev. 10/27/17
4-1/2 (11.4)
12 (30.5)
2-1/2 (6.4)
LC
4-1/2 (11.4)
12 (30.5)
2-1/2 (6.4)
LC
Coefficients of Utilization pf 20% pc 80% 50% 30% pw 70% 50% 30% 50% 30% 10% 50% 30% 10%
R C
R
Zonal Lumen Summary
Zone Lumens % Lamp % Fixture 0° - 30° 0° - 40° 0° - 60° 0° - 90° 90° - 180° 0° - 180°
25.8 41.2 66.3 77.7 0.0 77.7
33.2 53.0 85.3
100.0 0.0
100.0
Report:
LUMENS PER LAMP:
LTL12536
Luminaire Efficiency: 77.7%
GT8 2 32 A12
Catalog Number
GT8 F 2 32 FW A12 120 DMHL3D EL LP835
Notes
Type
L1-EM
Project 18-56134-2 USDA Animal Holding Area
Catalog Number
Notes
Type
CONTRACTOR SELECT ECC Page 1 of 2
ECC
Low Profile Emergency Light/Exit Combo
The low-profile, Lithonia Ligthing® ECC, LED light, is a combination of exit and emergency lighting. It's low profile design with small, unobtrusive dual lamp heads makes the ECC ideal for safely illuminating the path of egress above-the-door in small spaces at lower mounting heights while providing 90 minutes of emergency power. Available in red and green letters.
FEATURES:
¡ Test switch and status indicator
¡ UL Indoor damp location 50° to 104°F (10°C to 40°C) listed standard
¡ For use with Dual voltage 120/277VAC
Accessories: Order as separate catalog number.
ERE SGL Single, indoor remote head, white, 0.75W, 3.6V. See spec sheet ERE.
ERE T Twin, indoor remote head, white, 1.75W, 3.6V. See spec sheet ERE.
ERE GY SGL WP Single, weather-proof remote head, gray, 1W, 3.6V-12V voltage sensing. See spec sheet ERE.
ELA WG3 Wireguard, 30" W x 13-1/2" H x 6" D. See spec sheet ELA-WG.
ELA WG2M Wireguard, 21-1/4" W x 15" H x 12" D. See spec sheet ELA-WG.
Contractor Select™
Catalog Number UPC Description Supply Voltage
Input Wattage Input Amps Pallet Qty
Carton Qty120 277 120 277
ECC R M6 191848035597 LED Exit/Unit Combo Red 120/277V 1.1W 1.3W .08 .09 360 6
ECC R REM M6 191848035702 LED Exit/Unit Combo Red with 2W of remote capacity 120/277V 1.6W 1.6W .10 .11 360 6
ECC G M6 191848035733 LED Exit/Unit Combo Green 120/277V 1.1W 1.3W .08 .09 360 6
ECC G REM M6 191848035740 LED Exit/Unit Combo Green with 2W of remote capacity 120/277V 1.6W 1.6W .10 .11 360 6
Battery Total Capacity Maximum# Remote Lamp Heads*
3.6V 4W
2 - ERE SGL M24
1 - ERE T M24
2 - ERE GY SGL WP M12
* Remotes are in addition to the lamp heads on the product.
Battery Capacity and Loading (REM only)
Catalog Number
ECC R M6
Notes
Type
X Project 18-56134-2 USDA Animal Holding Area
One Lithonia Way, Conyers, GA 30012 | 800-334-8694 | techsupport-emergency@acuitybrands.com | www.lithonia.com © 2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/08/18 Page 2 of 2
CONTRACTOR SELECT ECC
INTENDED USE:
Provides a minimum of 90 minutes illumination for the rated wattage upon loss of AC power to meet code required emergency lighting. Ideal for applications requiring low profile, emergency unit for lower mounting heights.
CONSTRUCTION:
The housing is a standard white thermoplastic with a compact and low-profile design with all-inclusive lamp, reflector and lens assembly. It is 5VA flame rated and impact-resistant.
OPTICS:
The typical life of the LED is 10 years. One, 0.75W white LED per lamp head.
ELECTRICAL:
Dual-voltage 120/277 standard.
Bi-color LED status indicator for battery condition. (Green-normal, Red-check battery).
Two and a half watts of additional remote capacity with ECC R REM M6 and ECC G REM M6.
BATTERY: 3.6V Maintenance-free, rechargeable, nickel-cadmium.
INSTALLATION:
Top, side and back mount. Mounting pattern on canopy (top and side mount) and back plate (back mount) fits most standard size junction boxes.
LISTINGS:
UL Listed. Meets all applicable requirements for UL 924, NFPA 101 (current Life Safety Code), NFPA 70 (NEC), FCC and OSHA.
Indoor damp location 50° to 104°F (10°C to 40°C) listed.
WARRANTY:
2-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
Specifications Dimensions
Length: 16 (40.64) Depth: 11.94 (33.33) Height: 7.25 (18.52) Weight: 2.15lbs (.98kg)
All dimensions are inches (centimeters) unless otherwise indicated.
Catalog Number
ECC R M6
Notes
Type
X Project 18-56134-2 USDA Animal Holding Area
MAESTRO CONTROLS
Smart Dimmers Smart Remotes
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
JOB NAME AREA CONTROLLED
LOCATION JOB NUMBER
TITLE PAGE NO.
STANDARDS
SPECIFICATION SUBMITTAL
PRODUCT FAMILY FEATURES
• High-tech “Smart Dimmer” with microprocessor technology for a standard designer wallplate opening
• Features a clean, flush, stylish appearance
• Special Features! Two taps on the switch brings lights on to full brightness; press and hold the switch to slowly fade lights to off over 10 seconds
• LED’s indicate light level and glow softly as a locator light in the dark
• Multi-location dimming from up to 10 locations
• Uses standard single-pole and 3-way wiring for easy installation in any home
• Raise from off
SPECIFICATION FEATURES
• Power- failure memory
• Frequency compensation
• Includes Radio Frequency Interference suppression
• Front accessible service switch (FASSTM) to disconnect load power
• Electrostatic discharge tested
• Precise color matching across all controls
The High-Tech Multi-Location Dimmer
Smart Dimmer
Switch
Rocker Switch
Jacks Ports
Custom Multigang Wallplates
15A Receptacle
15A GFCI
Receptacle
Single Telephone Jack
Cable
TV
Jack
2-gang to 6-gang wallplates
6-Port Frame
® Controls www.lutron.com/maestro
One tap on to selected light level/off; two taps full bright;
press & hold for 10-second fade off Press rocker to adjust light level Front accessible service switch
(FASSTM)
LED’S indicate light level, glow softly
CLARO ACCESSORIES
Note: For multi-location dimming only-use one Smart Dimmer (left) with up to nine Smart Remotes
Receptacles
Catalog Number
MA-R-IV
Notes
Type
DIM R
Project 18-56134-2 USDA Animal Holding Area
2 Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
Description Model #
SMART DIMMERS
Incandescent Preset Smart Dimmers
Single Pole/Multi-Location 600W MA-600-
Single Pole/Multi-Location 1000W MA-1000- Products above: For multi-location dimming, use one Maestro Smart Dimmer with up to nine Maestro Smart Remotes, MA-R-. Not for use with mechanical 3-way or 4-way switches. Minimum load on dimmer is 40W. Derating required if ganged, see page 5.
Electronic Low Voltage Preset Smart Dimmers
Single Pole/Multi-location 600W MAELV-600- Products above: For multi-location dimming, use one Maestro Smart Dimmer with up to nine Maestro Smart Remotes, MA-R-. Requires neutral wire connection. Not for use with mechanical 3-way or 4-way switches. Minimum load on dimmer is 5W. Derating required if ganged, see page 5.
Magnetic Low Voltage Preset Smart Dimmers
Single Pole/Multi-Location 600VA (450W 1) MALV-600-
Single Pole/Multi-Location 1000VA (800W 1) MALV-1000- Products Above: For Multi-location dimming, use one Maestro Smart Dimmer with up to nine Maestro Smart Remotes, MA-R-. Not for use with mechanical 3-way or 4-way switches. Minimum load on dimmer is 40W. Derating required if ganged, see page 5.
Fluorescent For control of fluorescent loads, use Lutron Hi-lume®, Eco 10TM line voltage, or Tu-Wire® electronic dimming ballasts with MA-600- and Hi-Power 2• 4•6 dimming module. For a coordinated look, consider using Spacer System dimmers for controlling fluorescent loads.
HI-POWER 2•4•6TM DIMMING MODULES
To increase load capacity up to 30,000W/VA in most popular sources, use one MA-600- and add up to five dimming modules.
SMART REMOTES
Provide Multi-Location Dimming from up to Nine Additional Locations.
Smart Remotes
Smart Remotes MA-R- For multi-location dimming, use up to nine Smart Remotes with only one of the following Maestro multi-location dimmers: MA-600-, MA-1000-, MAELV-600-, MALV-600-, or MALV-1000-. No derating required if ganged. Maximum traveler wiring run for multi-location applications is 250’ (76.2m).
® Controls www.lutron.com/maestro
1. Actual lamp wattages.
Catalog Number
MA-R-IV
Notes
Type
DIM R
Project 18-56134-2 USDA Animal Holding Area
6 Have Questions? Call the Lutron Hotline 800-523-9466
Wiring Diagram 2 Multi-Location Wiring Model #
MA-R-
MA-600-
MA-1000-
MALV-600-
MALV-1000-
OR
Control Line Side
Neutral
Red
Blue
Multi-Location Dimmer
Smart Remote
Smart Remote
Smart Remote
Black BlackHot
Up to Nine Total Auxiliary Switches/Remotes
120VAC
60Hz Green Green Green GreenBlue
Red Black
Blue
Red Black
Blue Lighting Load
Red
Grou
Wire
Smart Remote
Smart Remote
Smart Remote
Up to Nine Total Auxiliary Switches/Remotes
GreenGreenGreenGreen
Neutral
Black
Blue
Multi-Location Dimmer
Red RedHot
120VAC
60Hz Blue
Black Red
Blue
Black Red
Blue Lighting Load
Black
Control Load Side
Ground
Wire Connectors
Ground
Wire Connectors
WIRING DIAGRAMS
Wiring Diagram 1 Single-Location Wiring Model #
MA-600-
MA-1000-
MALV-600-
MALV-1000-
® Controls www.lutron.com/maestro
Green
Dimmer/ TapSwitch™
Black Red
Blue Cap Off Lighting
Load
Neutral
Hot
120VAC
60Hz
Ground
Wire Connectors
Catalog Number
MA-R-IV
Notes
Type
DIM R
Project 18-56134-2 USDA Animal Holding Area
7 Have Questions? Call the Lutron Hotline 800-523-9466
® Controls www.lutron.com/maestro
Wiring Diagram 6 Telephone Jack Wiring Model #
CA-PJH-
Wiring Diagram 7 Receptacle Wiring Model #
CAR-15H-
Wiring Diagram 8 GFCI Receptacle Wiring Model #
CAR-15-GFCIH-
WIRING DIAGRAMS
Wiring Diagram 4 Multi-Location Control with Neutral Used for Single-Location Wiring Model #
MAELV-600-
Wiring Diagram 5 Multi-Location Wiring Model #
MAELV-600-
MA-R-
Ground
Neutral
Hot
Black
White
Green or Screw Terminal
Green or Screw Terminal
Green or Screw Terminal
Black
White
120VAC
60Hz
GFCI
Receptacle (15A Shown)
NPNP PP PP
Line Load
Wire ConnectorsP-Protected NP-Not Protected
Building Ground (To Metal Box)
Smart Remote
Multi-Location Dimmer
Green Green Lighting Load
Neutral
Black
Blue
White
BlackRed YellowHot
120VAC
60Hz Blue
Up to Nine Total MA-R Units
Control Load Side
Ground
Wire Connectors
Neutral
Green
Black
Dimmer/ TapSwitch
Yellow
Blue
Hot
120VAC
60Hz
Lighting LoadWhite
Cap Off
Ground
Wire Connectors
6-Conductor Telephone Jack*
Wire Color
Jack Position
1 White 2 Black 3 Red 4 Green 5 Yellow 6 Blue
* accepts most…
This is the start of the file's text. The full file is on GovTribe.