Exhibit C.pdf

PDF 276 KB Posted

Attached to
Hydronic loop testing
Solicitation number
138
Issued by
Canyon County, Idaho

About this file

This document appears to be a service report for testing the heating and cooling water loops at the Orchard Combat Training Center (OCTC) in Boise, Idaho, which is operated by the State of Idaho Military Division. The report provides details on the water quality parameters, including conductivity, copper, freeze point, glycol percentage, iron, nitrite, and pH, for several buildings and facilities at the OCTC. The report indicates that the water quality is generally within the acceptable ranges, with a few recommendations to add additional CSC-402 to two of the loops to address elevated nitrite levels. The report was prepared on March 9, 2023, and includes the report number, the name of the technician who recorded the information, and contact information for the OCTC.

The document does not appear to be related to a state or local contract opportunity, as it is focused on the maintenance and monitoring of the OCTC's heating and cooling water systems rather than a procurement process. There are no details provided about any contract, solicitation, or bidding requirements.

View the file

Other files

File Type Posted
Administration Document (2).docx DOCX document
Signature Page RFQ August 2020.pdf PDF
Exhibit B Price Sheet.xlsx XLSX spreadsheet
1_Arrivos-OnBase Integration.pdf PDF
4_PERSI_OnBase-Statistics_September-2024.pdf PDF
PERSI OnBase report.pdf PDF
Insurance Requirements 2023.docx DOCX document
solicitation_instructions Jan 2017.pdf PDF
IDOL's OnBase Screenshots for RFP.docx DOCX document
Standard Terms and Conditions_May 2021.pdf PDF
2_Arrivos WorkFlow Table .xlsx XLSX spreadsheet
3_PERSI-DocTypes-with-Annual-Volume.xlsx XLSX spreadsheet
Labor OnBase Licenses.pdf PDF
RFP Event 204 Administrative Document.docx DOCX document
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test OCTC Dining

HWL

OCTC Dining

CWL

OCTC

Barracks #1

HWL

OCTC

Barracks #1

CWL

OCTC

Barracks #2

HWL

OCTC

Barracks #2

CWL

OCTC

Barracks #3

HWL

OCTC

Barracks #3

CWL

Conductivity (uMhos) 1035 600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

Copper (ppm) 0.10

0.3 max

0.07

0.3 max

0.10

0.3 max

0.05

0.3 max

0.03

0.3 max

0.07

0.3 max

0.07

0.3 max

0.03

0.3 max

Freeze Point (F) 8 15 max

-5 15 max

15 max

15 max

15 max

-5 15 max

15 max

-10 15 max

Glycol % 32 25 min

25 min

25 min

25 min

25 min

25 min

25 min

25 min

Iron (ppm) 0.024

0.3 max

0.11

0.3 max

0.23

0.3 max

0.05

0.3 max

0.04

0.3 max

0.04

0.3 max

0.08

0.3 max

0.19

0.3 max

Nitrite (ppm) 1100 600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500 pH 8.71 9 - 10

9.29 9 - 10

8.43 9 - 10

8.78 9 - 10

9.48 9 - 10

9.11 9 - 10

8.54 9 - 10

9.27 9 - 10

Test OCTC Officer

QTR HWL

OCTC Officer

QTR CWL

OCTC

Battalion HQ

HWL

OCTC

Battalion HQ

CWL

OCTC Admin Supply HWL

OCTC Admin Supply CWL

ASP HWL

Conductivity (uMhos) 1619 600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

600 - 3500

Copper (ppm) 0.05

0.3 max

0.04

0.3 max

0.04

0.3 max

0.06

0.3 max

0.08

0.3 max

0.06

0.3 max

0.07

0.3 max

Freeze Point (F) -5 15 max

-10 15 max

-5 15 max

15 max

15 max

-10 15 max

Glycol % 42 25 min

25 min

25 min

25 min

25 min

25 min

Iron (ppm) 0.15

0.3 max

0.20

0.3 max

0.16

0.3 max

0.04

0.3 max

0.07

0.3 max

0.10

0.3 max

0.04

0.3 max

Nitrite (ppm) 1650 600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500

600 - 1500 pH 9.02 9 - 10

9.50 9 - 10

9.04 9 - 10

9.08 9 - 10

9.72 9 - 10

8.82 9 - 10

9.01 9 - 10

OCTC Barracks #2 HWL Online

Nitrite (ppm) I recommend adding 5 gallons CSC-402 to this loop.

OCTC Barracks #3 CWL Online

Nitrite (ppm) I recommend adding 5 gallons CSC-402 to this loop.

Closing Comment

Service Report OCTC loop testing

Thursday, March 9, 2023 3:37 PM MST

State of Idaho Military Division OCTC Boise 33400 Orchard Access Road Boise Idaho 83716-5040

(208) 272-4175

Report Number: 123456 Recorded By: Technician

Contact Information

Orchard Combat Training Center - Loops

At the time of service loop waters are in range. Iron and copper levels and corrosion rates are low. Two of the above loops could use some additional CSC-402 see above notes. All other loops are good.

Signature

Service Report OCTC loop testing

Thursday, March 9, 2023 3:37 PM MST

State of Idaho Military Division OCTC Boise 33400 Orchard Access Road Boise Idaho 83716-5040

(208) 272-4175

Report Number: 1234567 Recorded By: Technician