This document appears to be a service report for testing the heating and cooling water loops at the Orchard Combat Training Center (OCTC) in Boise, Idaho, which is operated by the State of Idaho Military Division. The report provides details on the water quality parameters, including conductivity, copper, freeze point, glycol percentage, iron, nitrite, and pH, for several buildings and facilities at the OCTC. The report indicates that the water quality is generally within the acceptable ranges, with a few recommendations to add additional CSC-402 to two of the loops to address elevated nitrite levels. The report was prepared on March 9, 2023, and includes the report number, the name of the technician who recorded the information, and contact information for the OCTC.
The document does not appear to be related to a state or local contract opportunity, as it is focused on the maintenance and monitoring of the OCTC's heating and cooling water systems rather than a procurement process. There are no details provided about any contract, solicitation, or bidding requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Administration Document (2).docx | DOCX document | |
| Signature Page RFQ August 2020.pdf | ||
| Exhibit B Price Sheet.xlsx | XLSX spreadsheet | |
| 1_Arrivos-OnBase Integration.pdf | ||
| 4_PERSI_OnBase-Statistics_September-2024.pdf | ||
| PERSI OnBase report.pdf | ||
| Insurance Requirements 2023.docx | DOCX document | |
| solicitation_instructions Jan 2017.pdf | ||
| IDOL's OnBase Screenshots for RFP.docx | DOCX document | |
| Standard Terms and Conditions_May 2021.pdf | ||
| 2_Arrivos WorkFlow Table .xlsx | XLSX spreadsheet | |
| 3_PERSI-DocTypes-with-Annual-Volume.xlsx | XLSX spreadsheet | |
| Labor OnBase Licenses.pdf | ||
| RFP Event 204 Administrative Document.docx | DOCX document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Test OCTC Dining
HWL
OCTC Dining
CWL
OCTC
Barracks #1
HWL
OCTC
Barracks #1
CWL
OCTC
Barracks #2
HWL
OCTC
Barracks #2
CWL
OCTC
Barracks #3
HWL
OCTC
Barracks #3
CWL
Conductivity (uMhos) 1035 600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
Copper (ppm) 0.10
0.3 max
0.07
0.3 max
0.10
0.3 max
0.05
0.3 max
0.03
0.3 max
0.07
0.3 max
0.07
0.3 max
0.03
0.3 max
Freeze Point (F) 8 15 max
-5 15 max
15 max
15 max
15 max
-5 15 max
15 max
-10 15 max
Glycol % 32 25 min
25 min
25 min
25 min
25 min
25 min
25 min
25 min
Iron (ppm) 0.024
0.3 max
0.11
0.3 max
0.23
0.3 max
0.05
0.3 max
0.04
0.3 max
0.04
0.3 max
0.08
0.3 max
0.19
0.3 max
Nitrite (ppm) 1100 600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500 pH 8.71 9 - 10
9.29 9 - 10
8.43 9 - 10
8.78 9 - 10
9.48 9 - 10
9.11 9 - 10
8.54 9 - 10
9.27 9 - 10
Test OCTC Officer
QTR HWL
OCTC Officer
QTR CWL
OCTC
Battalion HQ
HWL
OCTC
Battalion HQ
CWL
OCTC Admin Supply HWL
OCTC Admin Supply CWL
ASP HWL
Conductivity (uMhos) 1619 600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
600 - 3500
Copper (ppm) 0.05
0.3 max
0.04
0.3 max
0.04
0.3 max
0.06
0.3 max
0.08
0.3 max
0.06
0.3 max
0.07
0.3 max
Freeze Point (F) -5 15 max
-10 15 max
-5 15 max
15 max
15 max
-10 15 max
Glycol % 42 25 min
25 min
25 min
25 min
25 min
25 min
Iron (ppm) 0.15
0.3 max
0.20
0.3 max
0.16
0.3 max
0.04
0.3 max
0.07
0.3 max
0.10
0.3 max
0.04
0.3 max
Nitrite (ppm) 1650 600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500
600 - 1500 pH 9.02 9 - 10
9.50 9 - 10
9.04 9 - 10
9.08 9 - 10
9.72 9 - 10
8.82 9 - 10
9.01 9 - 10
OCTC Barracks #2 HWL Online
Nitrite (ppm) I recommend adding 5 gallons CSC-402 to this loop.
OCTC Barracks #3 CWL Online
Nitrite (ppm) I recommend adding 5 gallons CSC-402 to this loop.
Closing Comment
Service Report OCTC loop testing
Thursday, March 9, 2023 3:37 PM MST
State of Idaho Military Division OCTC Boise 33400 Orchard Access Road Boise Idaho 83716-5040
(208) 272-4175
Report Number: 123456 Recorded By: Technician
Contact Information
Orchard Combat Training Center - Loops
At the time of service loop waters are in range. Iron and copper levels and corrosion rates are low. Two of the above loops could use some additional CSC-402 see above notes. All other loops are good.
Signature
Service Report OCTC loop testing
Thursday, March 9, 2023 3:37 PM MST
State of Idaho Military Division OCTC Boise 33400 Orchard Access Road Boise Idaho 83716-5040
(208) 272-4175
Report Number: 1234567 Recorded By: Technician
Contact Information
Orchard Combat Training Center - Loops