This solicitation seeks a general contractor to complete infrastructure improvements at the Hot Springs VA Medical Center in South Dakota. The scope of work includes demolishing over 14,000 phone lines, upgrading electrical panels and generators, renovating HVAC and fire suppression systems, expanding and renovating building spaces, migrating from 50 telecommunications closets to 29 rooms, upgrading the data center, installing new data cabling and outlets, and completing physical security and hazardous material abatement work. Key aspects of the project involve phasing upgrades to minimize downtime for hospital operations and security, addressing technical complexities associated with integrating various systems, and maintaining clean work areas in accordance with regulatory standards. Offerors are advised to review meeting and documentation requirements for project coordination, material lead times, and background investigations required for non-escorted access to telecommunications rooms during construction.

View the file

Other files for this federal contract opportunity

Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER

ARCHITECT

TELECOMMUNICATIONS

ENGINEER, PROJECT LEAD

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

A&E ARCHITECTS

608 NORTH 29th STREET

BILLINGS, MT 59101

406.248.2633

BLACK HILLS VA HEALTHCARE SYSTEM

HOT SPRINGS VAMC

GDM - PUGET SOUND DISTRICT OFFICE

1584 McNEIL ST., SUITE 200

DUPONT, WA 98327

541.380.1237

GDM - PUGET SOUND DISTRICT OFFICE

1584 McNEIL ST., SUITE 200

DUPONT, WA 98327

360.539.1755

RSA

670 W. FIREWEED LN, SUITE 200

ANCHORAGE, ALASKA 99503

907.865.0564

PROJECT TEAM

RSA

670 W. FIREWEED LN, SUITE 200

ANCHORAGE, ALASKA 99503

907.865.0564

STRUCTURAL

KREMER, GHELEN, AND ASSOCIATES

400 COLUMBIA STREET, SUITE 240

VANCOUVER, WA 98660-3413

503.289.2661

GDM - ARCTIC DISTRICT OFFICE

1401 W 34TH AVE, SUITE 200

ANCHORAGE, ALASKA 99503

907.917.2957

CIVIL ENGINEER

GDM - COLUMBIA GORGE DISTRICT OFFICE

1000 W STEUBEN ST, UNIT THREE

BINGEN, WA 98605

541.436.4723

INDUSTRIAL HYGIENEFIRE PROTECTION ENGINEER

TERP CONSULTING

14241 E 4TH AVAENUE, SUITE 5-230

AURORA, CO 80011

720.779.0797

AB ANCHOR BOLT

ABV ABOVE

A/C AIR CONDITIONING

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ALUM ALUMINUM

ARCH ARCHITECT(URAL)

AWN AWNING

B/ BOTTOM OF

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BM BEAM OR BENCHMARK

BRG BEARING

BTWN BETWEEN

BUR BUILT-UP ROOF

CAB CABINET

CJ CONTROL JOINT

CL CENTERLINE

CLG CEILING

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS

CONST CONSTRUCTION

CG CORNER GUARD

CPT CARPET

CSMT CASEMENT

CT CERAMIC TILE

D DEEP

DF DRINKING FOUNTAIN

DH DOUBLE HUNG

DIM(S) DIMENSIONS

DISP DISPENSER

DN DOWN

DR DOOR

DS DOWNSPOUT

DTL DETAIL

DWG DRAWING

E EAST

EA EACH

EC EXISTING COLUMN

EJ EXPANSION JOINT

ELEC ELECTRICAL

EL ELEVATION

ELEV ELEVATOR

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION OR EXPOSED

EXT EXTERIOR

FACP FIRE ALARM CONTROL PANEL

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

F.F. FINISH FLOOR

FIN FINISH

FIXT FIXTURE

FLR FLOOR

FND FOUNDATION

FP FIRE PROTECTION

FR FRAME

FRMG FRAMING

FT FEET/FOOT OR FIRE TREATED

FTG FOOTING

FTNG FOOTING

FRP FIBERGLASS REINFORCED PANEL

FRT FIRE RETARDANT TREATED

GA GAUGE

GALV GALVANIZED

GB GYPSUM BOARD

GC GENERAL CONTRACTOR

GL GLASS, GLAZING

GWB GYPSUM WALL BOARD

GYP GYPSUM

HC HANDICAP

HDR HEADER

HDW HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

HTD HEATED

HVAC HEATING/VENTILATION & AIR

CONDITIONING

ID INSIDE DIAMETER

INFO INFORMATION

ISO ISOCYANURATE

INSUL INSULATE / INSULATED / INSULATION

INT INTERIOR

INV INVERT

JT JOINT

J-BOX JUNCTION BOX

KIT KITCHEN

L LONG / LENGTH

LAM LAMINATE(D)

LAV LAVATORY

LF LINEAR FEET

LT LIGHT

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MECH MECHANIC(AL)

MEZZ MEZZANINE

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTL METAL

N NORTH

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER OR

OVERFLOW DRAIN

OPNG OPENING

OPP OPPOSITE

OSB ORIENTED STRAND BOARD

OVHD OVERHEAD

PL PLATE

PLAM PLASTIC LAMINATE

PLUMB PLUMBING

PLYWD PLYWOOD

PNL PANEL

PNT PAINT

POLY POLYESTER OR POLYOLEFIN

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED OR POINT

PVMT PAVEMENT

QT QUARRY TILE

QTR QUARTER

QTY QUANTITY

R RADIUS

RA RETURN AIR

RB RUBBER BASE

RD ROOF DRAIN

RECY RECYCLE(D)

REF REFERENCE

REFRIG REFRIGERATOR OR

REFRIGERATION

REINF REINFORCE

REQD REQUIRED

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

S SOUTH

SC SOLID CORE

SCH SCHEDULE

SCHED SCHEDULED

SECT SECTION

SF SQUARE FEET

SFRM SPRAY APPLIED FIRE RESISTIVE

MATERIAL

SGL SINGLE

SHT SHEET

SHTG SHEATHING

SIM SIMILAR

SPECS SPECIFICATIONS

SOD SLAB ON DECK

SOG SLAB ON GRADE

SOH SAME OPPOSITE HAND

SS STAINLESS STEEL

ST STONE TILE

STD STANDARD

STND STANDARD

STL STEEL

STRUCT STRUCTURAL

TEMP TEMPERED

THK THICK

THRESH THRESHOLD

T.O. TOP OF

TOBM TOP OF BEAM

T.O.BM. TOP OF BEAM

T.O.P. TOP OF PLATE

T.O.S. TOP OF STEEL

T/ TOP OF

T&G TONGUE AND GROOVE

TEL TELEPHONE

THK THICK

TRANS TRANSOM

TV TELEVISION

TYP TYPICAL

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VP VENEER PLASTER

VR VAPOR RETARDER

VT VINYL TILE

VWC VINYL WALL COVERING

W WIDE OR WEST

W/ WITH

WC WATER CLOSET

WD WOOD

WDW WINDOW

WG WALL GUARD

WH WATER HEATER

W/IN WITHIN

W/O WITHOUT

WP WATERPROOF

WR WATER RESISTANT

WT WEIGHT

WWF WELDED WIRE FABRIC

# NUMBER OR POUND

@ AT

ARCHITECTURAL ABBREVIATIONS

TYPICAL SHEET VIEW NUMBERING LAYOUT

NUMBERING STARTS IN BOTTOM LEFT CORNER, MOVING

UPWARDS, SKIPPING NONE

ARCH E1 (30"x42")

WINDOW TAGROOM TAG

DOOR TAG KEYNOTE TAG

ASSEMBLY TAG

MATERIAL TAG

REVISION TAGREVISION CLOUD XXX

X

XX-XX

X

CEILING TAG VIEW REFERENCE

BUILDING

SECTION

WALL

SECTION

ELEVATION

GRID LINE

DETAIL

CALL OUT

INTERIOR

ELEVATION

EXTERIOR

ELEVATION

DETAIL

SECTION

#1

#2

#3

#4

POSITION OF VIEW ON SHEET

VIEW NAME

1 1/2" = 1'-0"

VIEW SCALE

VIEW NAME

A6.#1 A3.#

A3.#

A3.#

A4.#

A3.#

ROOM NAME

101.1

X

X'-X"

XXX-X

XXX

W D

HT

CASEWORK TAG

CABINET DESIGN SERIES NO.

EXPLANATION OF SYMBOLS

BLACK HILLS HEALTH CARE SYSTEM, HOT SPRINGS CAMPUS

ELECTRONIC HEALTH RECORD MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES - HOT SPRINGS, SOUTH DAKOTA

PROJECT NO.: 568A-21-702

CONTRACT NO.: 36C776210069

100% CONSTRUCTION DOCUMENTS

BLACK HILLS HEALTH CARE SYSTEM, HOT SPRINGS CAMPUS

500 N. 5TH ST.

HOT SPRINGS, SD 57747

THE SCOPE OF THIS PROJECT INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING INFRASTRUCTURE

IMPROVEMENTS: ELECTRICAL (ELECTRICAL PANEL UPGRADE, POWER [NORMAL, EMERGENCY]),

BONDING, UPS, BUILDING MANAGEMENT SYSTEM INTERFACES, ASSESS FOR NEW AND UPGRADES TO EXISTING HVAC, RECONFIGURATION, EXPANSION AND RENOVATION OF EXISTING SPACE (DEMO, NEW CONSTRUCTION, FINISHES), COMMUNICATION INFRASTRUCTURE (NEW DATA OUTLETS, PATCH PANELS, UPGRADE TO CAT 6A CABLE) IN BUILDINGS AS NECESSARY, PHYSICAL SECUITY UPGRADES, ASSESS AND UPGRADE FIBER INFRASTRUCTURE BACKBONE CAMPUS WIDE WITHIN BUILDINGS AND BETWEEN BUILDINGS, HAZARDOUS MATERIAL ABATEMENT. PROJECT BUILDING LOCATION INCLUDE: BUILDINGS 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 17, 18, 20 23, 29, 43, 53, 65, AND 66.

PROJECT DESCRIPTION

"OWNER": THE OWNER IS UNITED STATES GOVERNMENT - DEPARTMENT OF BETERANS AFFAIRS AND IS REFERRED TO THROUGOUT THE CONTACT DOCUMENTS AS IF SINGULAR IN NUMBER. THE TERM "OWNER"

MEANS THE OWNER OR THE OWNER'S CONTRACTING OFFICER'S AUTHORIZED REPRESENTATIVE.

"CONTRACTING OFFICER" OR "C.O.": THE OWNER'S AUTHORIZED REPRESENTATIVE RESPONSIBLE FOR

ADMINISTRATING THE CONTRACT BETWEEN THE GENERAL CONTRACTOR AND OWNER. THE TERM

INCLUDES CERTAIN AUTHORIZED REPRESENTATIVES OF THE CONTRACTING OFFICER ACTING WIHIN THE

LIMITS OF THEIR AUTHORITY AS DELEGATED BY THE CONTRACTING OFFICER.

"WORK": THE TERM "WORK" MEANS THE CONSTRUCION AND SERVICES REQUIRED BY THE CONTRACT DOCUMENTS, WHETHER COMPLETED OR PARTIALLY COMPLETED, AND INCLUDES ALL OTHER LABOR, MATERIALS, EQUIPMENT AND SERVICES PROVIDED BY THE CONTRACTOR TO FULFILL THE CONTRACTOR'S

OBLIGATIONS. THE WORK MAY CONSTITUTE THE WHOLE OR A PART OF THE PROJECT.

"PROJECT": THE TOTAL CONSTRUCTION OF WHICH THE WORK PERFORMED UNDER THE CONTRACT

DOCUMENTS

"DRAWINGS", "SHOP DRAWINGS", OR "PLANS": THE GRAPHIC AND PICTORIAL PORTIONS OF CONTRACT

DOCUMENTS, WHENEVER LOCATED AND WHERENEVER ISSUED, SHOWNING DESIGN, LOCATIONAND

DIMENSIONS OF THE WORK, GENERALLY INCLUDING PLANS, ELEVATIONS, ASECTIONS, DETAILS, SCHEDULES AND DIAGRAMS.

"PROJECT SUPERVISOR" OR "SUPERVISOR": MEANS THE ON-SITE SUPERVISION REPRESENTATIVE OF THE

PROJECT.

"ARCHITECT" OR "ENGINEER": MEANS THE VA'S ARCHITECTS, ENGINEERS AND OTHER DESIGN AND ENGINEERS PROFESSIONALS FOR THIS PROJECT, AND REFERRED THROUGHOUT THE DRAWINGS AS IF

SINGULAR IN NUMBER.

"TRADE CONTRACTOR" OR "CONTRACTOS": MEANS THE ENTITY UNDER CONTRACT AGREEMENT WITH

THE GENERAL CONTRACTOR TO PROVIDE THE SPECIFIED GENERAL AND OR SPECIALTY WORK IN

CONNECTION WITH THIS PROJECT.

"FURNISHED" OR "FURNISHED": MEANS PROVIDING ALL MATERIALS, SHOP DRAWINGS, TRANSPORTATION INSURANCE, FIELD MEASUREMENTS,EXPEDITING, SHIPPING, HANDLING, PACKAGING, STORAGE, TOUCH-UP MATERIALS, OWNER'S MANUALS, TRAINING AND ANY OTHER ACCESSORIES REQUIRED FOR A COMPLETE

INSTALLATION.

"INSTALL" OR "INSTALLED": MEANS COMPLETING ALL WORK AND COSTS ASSOCIATED WITH UNLOADING, UNPACKING, HOISTING, STORAGE, HANGERS, SUPPORTS, SLEEVES, SCAFFOLDING, COORDINATION, LAYOUT, SHOP DRAWINGS, EXCAVATION, BACKFILL, DEWATERING, INSTALLATION, CUTTING AND PATCHING, FIRESTOPPING, CLENA-UP, INSPECTION, DOCUMENTATION, PROTECTION OF SCOPE OF WORK AND ALL ACCESSORIES, SERVICE AND FACILITIES REQUIRED FOR A COMPLETE INSTALLATION.

"PROVIDE" OR "PROVIDED": MEANS TO FURNISH AND INSTALL AND SHALL INCLUDE, WITHOUT LIMITATION, ALL LABOR, MATERIALS, EQUIPMENTS, TRANSPORTATION SERVICES, AND OTHER ITEMS REQUIRED TO

COMPLETE THE REFERENCED TASK.

"BY OWNER", "BY VAMC" OR "BY VA": MEANS ITEMS WILL BE ORDERED, PAID FOR, SHIPPED TO THE JOB

SITE AND INSTALLED BY THE OWNER.

"NOT IN CONTRACT" OR "N.I.C.": MEANS MATERIALS OR EQUIPMENT NOT IN THE CONTRACT, BUT MAY REQUIRE PROVISIONS IN THE CONSTUCTION FOR FUTURE INSALLATION AS SPECIFIFIED OR SHOWN.

OTHER DEFINITIONS OF WORDS AND TERMS USED IN THE DRAWINGS AND SPECIFICATIONS CAN BE FOUND IN THE LEGENDS AND SYSMBOLS DRAWINGS FOR EACH DISCIPLINE AND IN DISION 0 AND 1 OF THE

PROJECT MANUAL.

BASIC DEFINITIONS

1. THE CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS AND SPECIFICATION AND RELATED CONTRACT DOCUMENTS, VISIT SITE OF WORK, AND RESEARCH ALL EXISTING CONDITIONS, FACILITES, RESTRICTIONS AND OTHER MATTERS WHICH CAN AFFECT THE WORK OR THE COST THEREOF;

FAILURE OR OMISSION OF ANY CONTRACTOR TO VISIT THE SITE AND ACQUAINT THEMSELVES WITH THE EXISTING CONDITIONS, SHALL IN NO WAY RELEIVE THEM FROM ANY OBLIGATION WITH RESPECT TO THEIR CONTRACT AND NO EXTRA COMPENSATION WILL BE ALLOWED BY REASON OF ANY THING OR MATTER CONCERNING WHICH THE CONTRACTOR SHOULD HAVE FULLY INFORMED THEMSELVES PRIOR TO BIDDING. GENERAL CONTRACTOR

SHALL COORDINATE ALL ASPECTS OF THE BUILDING CONSTRUCTION.

2. THE CONTRACTOR SHALL NOT CONSIDER CONSTRUCTION NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE INTENT OF THE CONTRACT DOCUMENTS. CONTRACTOR SHALL COORDINATE ARCHITECTURAL CONSTRUCTION DRAWING AND NOTES WITH CIVIL, STRUCTURAL AND MECHANICAL, ELECTRICAL & PLUMBING NOTES AND DRAWINGS.

3. THE DRAWINGS SHALL BE WORKED IN CONJUNCTION WITH THE TECHNICAL SPECIFICATIONS AND CONDITIONS OF THE PROJECT INCLUDED IN THE PROJECT MANUAL WHICH FORM A PART OF THE CONTRACT DOCUMENTS AND CONTAINS ADDITIONAL INFORMATION REQUIRED TO CONSTRUCT THE WORK OF THIS CONTRACT. IN THE EVENT OF A CONFLICT BETWEEN THE DRAWINGS AND THE SPECIFICATION NOTIFY THE COR FOR CLARIFICATION

SEVEN DAYS BEFORE BEGINNING WORK ON THE AFFECTED ACTIVITIES.

4. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO THE START OF THE WORK. NOTIFY THE COR OF ANY

SIGNIFICANT CHANGES IN DIMENSIONS OR CONDITIONS.

5. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, TOOLS, EQUIPMENT AND NECESSARY FACILITIES, AND PERFORM ALL LABOR AND SERVICES OF EVERY DESCRIPTION AS MAY BE NECESSARY TO COMPLETE THE SCOPE OF WORK DEFINED ON THE DRAWINGS AND SPECIFICATIONS.

6. THE CONTRACTOR SHALL ARRANGE FOR AND OBTAIN ALL VA ISSUED PERMITS (HOTWORK, ICRA, WEEKENDS, HOLIDAYS, SHUTDOWN, ETC), CERTIFICATES, INSPECTIONS, DEPARTMENT APPROVAL, ETC. FOR WORK PERFORMED UNDER THIS CONTRACT. PROVIDE COPIES OF ALL REQUIRED

PERMITS, CERTIFICATES, INSPECTIONS AND AGENCY APPROVALS TO THE COR.

7. FABRICATE AND INSTALL ALL WORK IN STRICT ACCORDANCE WITH THE SPECIFICATIONS, ALL APPLICABLE STATE AND LOCAL CODES, AND THE GENERAL

AND SUPPLEMENTARY CONDITIONS OF THE CONTRACT.

8. U.L. ASSEMBLIES DESCRIBED ARE FOR REFERENCE ONLY. THE GENERAL CONTRACTOR SHALL COORDINATE AND VERIFY THE INSTALLATION OF THE

DESCRIBED SYSTEM(S) .

9. ALL CONTRACTORS AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR THE PROPER PERFORMANCE OF THEIR WORK, COORDINATING WITH OTHER

TRADES, MEANS AND METHODS OF CONSTRUCTION, SAFETY AND SECURITY ON SITE.

10. CUTTING AND PATCHING SHALL BE PERFORMED BY EACH TRADE AS NECESSARY FOR THE PERFORMANCE AND INSTALLATION OF THE WORK. CUTTING AND PATCHING SHALL BE PERFORMED IN A WORKMANLIKE MANNER CONSISTENT WITH INDUSTRY STANDARDS FOR FINISHES AND SUBSTRATES

AFFECTED.

11. THE CONTRACTOR SHALL PROTECT THE FACILITY FROM WEATHER AND MAINTAIN SECURITY DURING ALL CONSTRUCTION WORK.

12. PROTECT EXISTING PROPERTY DURING CONSTRUCTION. REPAIR OR REPLACE, WITHOUT ADDITIONAL CHARGE TO THE OWNER, ANY EXISTING WORK

DAMAGED DURING THE COURSE OF CONSTRUCTION.

13. THE WORK SHALL BE COORDINATED IN GOOD FAITH WITH THE COR AND ALL GOVERNMENT EMPLOYEES 14 DAYS IN ADVANCE OF BEGINNING EACH

CONSTRUCTION ACTIVITY.

14. UNLESS ITEMS OF MATERIAL, EQUIPMENT OR WORK ARE SPECIFICALLY NOTED TO BE PROVIDED OR FURNISHED BY OTHERS, THEY SHALL BE PROVIDED

UNDER THIS CONTRACT.

15. ALL WORK SHALL BE PERFORMED BY SKILLED WORKERS IN A WORKMANLIKE AND PROFESSIONAL MANNER CONSISTENT WITH INDUSTRY STANDARDS.

16. THE CONTRACTOR SHALL LEAVE THE SITE AND ALL BUILDINGS AND STRUCTURES IN PROPER WORKING ORDER AND SHALL, WITHOUT ADDITIONAL CHARGE, REPLACE ANY WORK, MATERIALS, OR EQUIPMENT FURNISHED AND INSTALLED UNDER THE CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FROM ORDINARY WEAR AND TEAR, WITHIN ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER.

17. CONTRACTOR SHALL SCHEDULE, COORDINATE, AND FACILITATE ALL POWER OUTAGES AND SHUTDOWNS. POWER OUTAGES AND SHUTDOWNS MUST BE

SCHEDULED WITH THE COR ONE (1) WEEK PRIOR TO OUTAGE.

18. FIELD VERIFY ALL EXISTING CONDITIONS INCLUDING BUT NOT LIMITED TO REGULATED MATERIALS ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, EQUIPMENT, AND ALL OTHER EXISTING SYSTEMS. MAKE NECESSARY PROVISIONS TO MAINTAIN THE INTEGRITY OF SAID SYSTEMS PRIOR TO THE COMMENCEMENT OF DEMOLITION, IF ANY. SEE MECHANICAL, ELECTRICAL, TELECOMMUNICATIONS, AND ARCHITECTURAL DRAWINGS FOR ANY SYSTEM OR PORTIONS THEREOF TO BE REMOVED, RELOCATED, REVISED OR ABANDONED.

19. ANY CONSTRUCTION INSTALLED IN CONFLICT WITH THE CONTRACT DOCUMENTS SHALL BE CORRECTED AT NO EXPENSE TO THE OWNER OR ARCHITECT

/ ENGINEER OF RECORD (EOR).

20. ALL REQUIRED EXITS FROM OCCUPIED PORTIONS OF THE BUILDING MUST BE MAINTAINED AT ALL TIMES. ESTABLISH PROCEDURES TO MINIMIZE CIRCULATION OF CONSTRUCTION PERSONNEL AND MATERIALS THROUGH OCCUPIED PORTIONS OF THE BUILDING. KEEP ALL AREAS ADJACENT TO THE

WORK AREA CLEAN.

21. PRIOR TO DELIVERY OF MATERIALS TO THE CONSTRUCTION ZONE AND REMOVAL OF WASTE FROM THE SITE, VERIFY WITH THE COR FOR AN ACCEPTABLE ACCESS ROUTE AND TIME. UNDER NO CIRCUMSTANCES SHALL ANY AREA OUTSIDE THE CONSTRUCTION ZONE BE USED WITHOUT PRIOR APPROVAL FROM THE COR. ALL BUILDING INTERIOR STAGING AREAS SHALL BE PROTECTED WITH FIRE RESISTANT PLYWOOD ENCLOSURES. ALL TRASH SHALL BE REMOVED FROM THE BUILDING DAILY. CONSTRUCTION MATERIALS SHALL NOT BE STORED IN CORRIDORS AT ANY TIME.

22. FIELD VERIFY ALL EXISTING DIMENSIONS, SERVICES, AND POINTS OF CONNECTION PRIOR TO START OF WORK.

23. THE DESIGN ADEQUACY, SAFETY, AND ERECTION OF BRACING, SHORING, SCAFFOLDING, AND TEMPORARY SUPPORTS AND RESTRAINS IS THE SOLE

RESPONSIBILITY OF THE CONTRACTOR.

24. NOTIFY THE FACILITY OF TIMES WHEN THE CONSTRUCTION NOISE WILL BE EXCESSIVE. RESCHEDULE SUCH WORK IF SO REQUIRED BY THE FACILITY.

25. NOTIFY THE COR OF ANY DISCREPANCIES DISCOVERED IN THE FIELD THAT REQUIRE CORRECTIVE ACTION.

26. FOR EXISTING FLOORS, CEILINGS, PARTITIONS, AND SERVICES TO REMAIN, PROTECT ALL FINISHES AND MATERIALS, AND REPAIR OR REPLACE ALL ITEMS THAT ARE DAMAGED OR SOILED DURING THE COURSE OF CONSTRUCTION. ALL FINISHES AND MATERIALS SHALL E PROPERLY INTEGRATED TO

NSUTE A UNIFORM APPEARANCE AND SEAMESS TRANSITION.

27. ALL ITEMS TO BE REMOVED AND REPLACED SHALL BE HANDLED WITH PROPER CARE AND STORED IN A SAFE PLACE TO PREVENT DAMAGE; WHEN

DAMAGED, REPLACE AT NO EXPENSE TO THE OWNER.

28. ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED OR BRACED IN ACCORDANCE WITH PROVISIONS OF THE TECHNICAL SPECIFICATIONS.

29. ALL DRAWINGS, THOUGH NOTED TO SCALE, ARE FOR ILLUSTRATION ONLY. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS. ITEMS

WRONGLY LOCATED BY DRAWINGS SCALING SHALL BE CORRECTED.

30. SIGNAGE CONSTRUCTION, FONT AND SIZE SHALL BE CONSISTENT WITH THE FACILITY'S EXISTING SIGNAGE SYSTEMS. REFER TO SPECIFICATIONS FOR CODE REQUIRED SIGNAGE. PROVIDE ADDITIONAL SIGNAGE AS MAY BE REQUIRED BY REQUEST OF THE FIRE MARSHAL AND/OR BUILDING CODE

OFFICIAL.

31. EXERCISE CARE DURING CONSTRUCTION TO MINIMIZE DISRUPTION OF THE MEDICAL CENTER ROUTINE, COORDINATE SEQUENCE OF WORK AND PHASING WITH THE COR TO MINIMIZE DISRUPTION OF THE MEDICAL CENTER. MANY OF THE WORK ITEMS REQUIRE THE WORK TO BE PERFORMED ONLY

AT NIGHT, WEEKENDS, OR HOLIDAYS AT NO ADDITIONAL COST TO THE GOVERNMENT.

32. PRIOR TO DRILLING OR CORING EXISTING CONCRETE, CONTRACTOR SHALL LOCATE EXISTING REINFORCEMENT TO MAINTAIN ADEQUATE CLEARANCES FROM AND AVOID DAMAGE TO EXISTING REINFORCEMENT. CONTRACTOR SHALL USE NON-DESTRUCTIVE TESTING (NDT) TO LOCATE REINFORCEMENT.

WHENEVER FEASIBLE, CONTRACTOR SHALL USE GROUND PENETRATING RADAR (GPR) OR MEANS OTHER THAN X-RAY. WHERE X-RAY IS REQUIRED, CONTRACTOR SHALL PROVIDE WRITTEN REQUEST AT LEAST THREE (3) WEEKS PRIOR TO EVENT: WORK MAY BE REQUIRED TO BE PERFORMED OUTSIDE NORMAL WORK HOURS AND SHALL BE DOCUMENTED ON THE THREE (3) WEEK LOOK-AHEAD SCHEDULE.

33. PROTECT EXISTING FIRE SUPPRESSION SYSTEMS DURING CONSTRUCTION.

34. IN THE EVENT THE CONTRACTOR DISCOVERS HAZARDOUS MATERIALS WHICH ARE NOT AVOIDABLE BY REROUTING THE WORK AND HAVE NOT BEEN DESCRIBED IN THE CONTRACT, THE CONTRACTOR IS TO NOTIFY THE COR AND THE A/E FOR DIFFERING SITE CONDITION ACKNOWLEDGEMENT.

REMEDIATION WOULD BE COMPENSATED BY ADDITIONAL MONEY AND ADDITIONAL TIME FOR CRITICAL PATH ACTIVITIES.

35. CONTRACTOR SHALL PROVIDE STAFF THAT WILL UNDERGO TRAINING AND CERTIFICATION TO ALLOW UN-ESCORTED ACCESS TO IT CLOSETS. THE CONTRACTOR SHALL CERTIFY SUFFICIENT NUMBER OF STAFF TO ACCOMMODATE PROPOSED SCHEDULE WITHOUT RELYING ON VA STAFF TO ACCOMPANY AS ESCORTS. THIS WILL REQUIRE PIV BADGING REQUIREMENT INCLUDING BACKGROUND INVESTIGATIONS. SEE "CONTRACTOR BACKGROUND INVESTIGATIONS REQUEST" FORM. COORDINATE WITH CO/CS REGARDING SUBMITTING THE FORM.

GENERAL PROJECT NOTES

PROJECT SITE

VA MEDICAL CENTER

PROJECT VICINITY MAP

HOT SPRINGS, SD

PROJECT

NORTH

SITE LEGEND

TRUE

NORTH

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

B

IM

/2

V A

M e d ic a l C e n te r

H o t S p ri n g s S

D /2

G

E N

E R

A L

I N

F O r2

.r v t

/3

/2

:0

:4

P M

00-GI-000.1

COVER SHEET VOLUME 1

GDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

A&E DESIGN

124 NORTH 29TH STREET, #100

BILLINGS, MONTANA 59101

406.248.2633

T. MARCELLO PIERROTTET, AIA

EHRM INFRASTRUCTURE

UPGRADES

HOT SPRINGS, SOUTH DAKOTA

568A4-21-702

Project Director

AHTMP02/23/2022

100% CD FINAL SOLUTIONARCHITECTA/E:

FULLY SPRINKLERED

VOLUME 1

CIVIL STRUCTURAL ARCHITECTURAL

Revisions: Date:

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

B

IM

/2

V A

M e d ic a l C e n te r

H o t S p ri n g s S

D /2

G

E N

E R

A L

I N

F O r2

.r v t

/4

/2

:0

:5

A

M

00-GI-001

INDEX OF DRAWINGS

GDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

A&E DESIGN

124 NORTH 29TH STREET, #100

BILLINGS, MONTANA 59101

406.248.2633

T. MARCELLO PIERROTTET, AIA

EHRM INFRASTRUCTURE

UPGRADES

HOT SPRINGS, SOUTH DAKOTA

568A4-21-702

Project Director

TMPTMP02/23/2022

100% CD FINAL SOLUTIONARCHITECTA/E:

FULLY SPRINKLERED

DRAWING INDEX

EK-101 POWER ONE-LINE DIAGRAM EMERGENCY BRANCH -DOM

EK-102 POWER 0NE-LINE DIAGRAM NORMAL BRANCH -DOM

EK-103 POWER ONE-LINE DIAGRAM -BUILDING 12

EK-104 POWER ELEVATIONS AND DETAILS

EK-105 BUILDING 1 -PANEL SCHEDULES

EK-106 BUILDING 1 & 2 -PANEL SCHEDULES

EK-107 BUILDING 2, 3 & 4 -PANEL SCHEDULES

EK-108 BUILDING 4 -PANEL SCHEDULES

EK-109 BUILDING 6 & 7-PANEL SCHEDULES

EK-110 BUILDING 8 & 11 -PANEL SCHEDULES

EK-111 BUILDING 12 -PANEL SCHEDULES

EK-112 BUILDING 12 -PANEL SCHEDULES

EK-113 BUILDING 12 -PANEL SCHEDULES

EK-114 BUILDING 14, 17 & 18 -PANEL SCHEDULES

EK-115 BUILDING 18, 20 & 23 -PANEL SCHEDULES

EK-116 BUILDING 29 & 43 -PANEL SCHEDULES

EK-117 BUILDING 53 -PANEL SCHEDULES

EK-118 BUILDING 65 & 66 -PANEL SCHEDULES

EK-119 ELECTRICAL LOAD CALCULATIONS

EK-120 ELECTRICAL LEGEND AND NEW LIGHT FIXTURE SCHEDULE

EP-0B1 ELECTRICAL REMODEL PLAN -ARCADE

001-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 1 BASEMENT

001-EP-011 ELECTRICAL REMODEL PLAN -BLDG 1 FIRST FLOOR

001-EP-021 ELECTRICAL REMODEL PLAN -BLDG 1 SECOND FLOOR

001-EP-031 ELECTRICAL REMODEL PLAN -BLDG 1 THIRD FLOOR

002-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 2 BASEMENT

002-EP-021 ELECTRICAL REMODEL PLAN -BLDG 2 SECOND FLOOR

003-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 3

004-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 4 LAYOUTS

004-EP-0B2 ELECTRICAL REMODEL PLAN -BLDG 4 ENLARGED PLANS

005-EP-021 ELECTRICAL REMODEL PLAN -BLDG 5 SECOND FLOOR

006-EP-011 ELECTRICAL REMODEL PLAN -BLDG 6 FIRST FLOOR

007-EP-011 ELECTRICAL REMODEL PLAN -BLDG 7 FIRST FLOOR

008-EP-011 ELECTRICAL REMODEL PLAN -BLDG 8 FIRST FLOOR

010-EP-0B1 BUILDING 10 ELECTRICAL PLANS

011-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 11

012-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 12 BASEMENT

012-EP-0B1A ELECTRICAL REMOD -BLDG 12 BASEMENT A ENLARGED

012-EP-0B1D ELECTRICAL REMODEL -BLDG 12 BASEMENT C/D

012-EP-001 ELECTRICAL REMODEL PLAN -BLDG 12 GROUND FLOOR

012-EP-001A ELECTRICAL REMOD -BLDG 12 GROUND FLOOR A ENLARGED

012-EP-001B ELECTRICAL REMOD -BLDG 12 GROUND FLOOR B ENLARGED

012-EP-001D ELECTRICAL REMOD -BLDG 12 GROUND FLOOR C/D ENLARGED

012-EP-011 ELECTRICAL REMODEL PLAN -BLDG 12 FIRST FLOOR

012-EP-011A ELECTRICAL REMOD -BLDG 12 FIRST FLOOR A ENLARGED

012-EP-011D ELECTRICAL REMOD -BLDG 12 FIRST FLOOR C/D ENLARGED

012-EP-021 ELECTRICAL REMODEL PLAN -BLDG 12 SECOND FLOOR

012-EP-021D ELECTRICAL REMOD -BLDG 12 SECOND FLOOR C/D ENLARGED

012-EP-031 ELECTRICAL REMODEL PLAN -BLDG 12 THIRD FLOOR

012-EP-031B ELECTRICAL REMOD -BLDG 12 THIRD FLOOR B ENLARGED

012-EP-041 ELECTRICAL REMODEL PLAN -BLDG 12 FOURTH FLOOR

014-EP-0G1 ELECTRICAL REMODEL PLAN -BLDG 14

017-EP-011 ELECTRICAL REMODEL PLAN -BLDG 17 FIRST FLOOR

018-EP-011 ELECTRICAL REMODEL PLAN -BLDG 18

020-EP-011 ELECTRICAL REMODEL PLAN -BLDG 20

023-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 23

029-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 29

043-EP-011 ELECTRICAL REMODEL PLAN -BLDG 43

053-EP-0B1 ELECTRICAL REMODEL PLAN -BLDG 53

065-EP-011 ELECTRICAL REMODEL PLAN -BLDG 65

065-EP-012 ENLARGED ELECTRICAL REMODEL PLAN -ROOM 109

065-EP-012.1 VA MCR POWER DETAILS

065-EP-013 ENLARGED LIGHTING REMODEL PLAN -ROOM 109

066-EP-011 ELECTRICAL REMODEL PLAN -BLDG 66

GENERAL

CIVIL

ARCHITECTURAL - DEMOLITION

ARCHITECTURAL - NEW CONSTRUCTION

STRUCTURAL

MECHANICAL

VOLUME 1

VOLUME 3

SHEET NO. SHEET NAME

11-AE-502 11-PLAN AND SECTION DETAILS

12-AE-101 12-BASEMENT & GROUND FLOOR OVERALL LIFE SAFETY PLAN

12-AE-102 12-FIRST & SECOND FLOOR OVERALL LIFE SAFETY PLAN

12-AE-103 12-THIRD AND FOURTH FLOOR OVERALL LIFE SAFETY PLANS

12-AE-201 12-BASEMENT FLOOR PLAN

12-AE-201A 12-BASEMENT FLOOR ENLARGED PLANS SECTOR A

12-AE-201CD 12-BASEMENT FLOOR ENLARGED PLANS SECTORS C AND D

12-AE-202 12-GROUND FLOOR PLAN

12-AE-202A 12-GROUND FLOOR ENLARGED PLAN SECTOR A

12-AE-202BCD 12-GROUND FLOOR ENLARGED PLANS SECTORS B, C, AND D

12-AE-203 12-FIRST FLOOR PLAN

12-AE-203A 12-FIRST FLOOR ENLARGED PLAN - SECTOR A

12-AE-203BCD 12-FIRST FLOOR ENLARGED PLANS - SECTORS B, C, AND D

12-AE-204 12-SECOND FLOOR PLAN

12-AE-204A 12-SECOND FLOOR ENLARGED PLANS SECTOR A

12-AE-204BCD 12-SECOND FLOOR ENLARGED PLANS - SECTORS B, C, AND D

12-AE-205 12-THIRD AND FOURTH FLOOR PLANS

12-AE-205BCD 12-THIRD FLOOR ENLARGED PLANS SECTORS B, C, AND D

12-AE-206 12-FOURTH FLOOR ENLARGED PLAN

12-AE-301 12-ENLARGED PBX FLOOR PLAN & RCP

12-AE-302 12-ENLARGED TR PLANS

12-AE-601 12-ENLARGED TR ELEVATIONS

12-AE-602 12-ENLARGED TR ELEVATIONS

12-AE-603 12-ENLARGED TR ELEVATIONS

14-AE-201 14- FLOOR PLANS

18-AE-201 18-FLOOR PLANS

43-AE-201 43 - FIRST FLOOR PLANS

53-AE-201 53-FLOOR PLANS

53-AE-301 ENLARGED FLOOR PLANS & ELEVATIONS

65-AE-201 65-FLOOR PLAN

65-AE-301 65-FLOOR PLANS

66-AE-201 66-FLOOR PLAN

66-AE-202 ENLARGED FLOOR PLANS

66-AE-401 66-ELEVATIONS AND SECTION

66-AE-501 66-PLAN AND SECTION DETAILS

66-AE-601 TR ELEVATIONS

SHEET NO. SHEET NAME

00-DOM-AE-101 00-DOM-FLOOR PLANS

01-AE-101 01-BASEMENT & FIRST FLOOR LIFE SAFETY PLAN

01-AE-102 01-SECOND & THIRD FLOOR LIFE SAFETY PLANS

01-AE-200 01-BASEMENT FLOOR PLAN

01-AE-201 01-FIRST FLOOR PLAN

01-AE-202 01-SECOND FLOOR PLAN

01-AE-203 01-THIRD FLOOR PLAN

01-AE-204 01-ROOF PLAN AND ROOF DETAILS

01-AE-205 01-SLAB EDGE PLANS

01-AE-401 01-OVERALL ELEVATIONS

01-AE-402 01-ENLARGED ELEVATIONS

01-AE-501 01-WALL SECTIONS

01-AE-502 01-WALL SECTIONS

01-AE-503 01-SECTION DETAILS

01-AE-504 01-SECTION DETAILS

01-AE-505 01-PLAN DETAILS

01-AE-601 01-TR ELEVATIONS

01-AE-602 01-TR ELEVATIONS

01-AE-801 01-STAIR SECTIONS

01-AE-802 01-STAIR DETAILS

02-AE-200 02-FLOOR PLANS

02-AE-601 02-ENLARGED TR PLANS & INTERIOR ELEVATIONS

03-AE-201 03-BASEMENT, FIRST, AND SECOND FLOOR PLANS

03-AE-202 03-TR PLANS AND ELEVATIONS

04-AE-200 04-BASEMENT, FIRST, & SECOND FLOOR PLANS

05-AE-201 05-BASEMENT, FIRST. & SECOND FLOOR PLANS

05-AE-601 05-ENLARGED TR & ELEVATIONS

06-AE-200 06-BASEMENT, FIRST, & SECOND FLOOR PLANS

06-AE-601 ENLARGED TR PLANS & ELEVATIONS

07-AE-200 07-BASEMENT, FIRST, & SECOND FLOOR PLANS

07-AE-201 07- ENLARGED TR PLANS & ELEVATIONS

08-AE-200 08-BASEMENT, FIRST, AND SECOND FLOOR PLANS

08-AE-201 08-ENLARGED TR PLANS AND INTERIOR ELEVATIONS

09-AE-201 09-FLOOR & ROOF PLANS

10-AE-200 10-FLOOR PLANS

11-AE-200 11-GROUND, FIRST, AND SECOND FLOOR PLANS

11-AE-301 11-ENLARGED PLANS & INT ELEVATIONS

11-AE-501 11-EXTERIOR SECTIONS AND ELEVATIONS

SHEET NO. SHEET NAME

01-AD-201 01-BASEMENT & FIRST FLOOR DEMOLITION PLANS

01-AD-202 01-SECOND AND THIRD FLOOR DEMOLITION PLANS

02-AD-201 02-DEMOLITION PLANS

03-AD-201 03-DEMOLITION FLOOR PLANS

04-AD-201 BUILDING 4 DEMOLITION FLOOR PLANS

05-AD-201 05-DEMOLITION FLOOR PLANS

06-AD-201 06-DEMOLITION PLANS

07-AD-201 07-DEMOLITION FLOOR PLANS

08-AD-201 08-DEMOLITION FLOOR PLANS

10-AD-201 DEMOLITION FLOOR PLANS

11-AD-201 11-DEMOLITION PLANS

12-AD-201A 12-DEMOLITION BASEMENT FLOOR ENLARGED PLAN SECTOR A

12-AD-201B 12-DEMOLITION BASEMENT FLOOR ENLARGED PLAN SECTOR D

12-AD-202A 12-DEMOLITION GROUND FLOOR ENLARGED PLAN SECTOR A

12-AD-202BCD 12-DEMOLITION GROUND FLOOR ENLARGED PLAN SECTORS B, C, AND D

12-AD-203 12-DEMOLITION FIRST FLOOR ENLARGED PLAN SECTOR A

12-AD-204 12-DEMOLITION SECOND FLOOR ENLARGED PLAN SECTOR A

12-AD-205D 12-DEMOLITION THIRD FLOOR ENLARGED PLAN SECTORS B, C, AND D

12-AD-206 12-DEMOLTION FOURTH FLOOR ENLARGED PLAN SECTOR D

14-AD-201 14- DEMOLITION FLOOR PLANS

53-AD-201 53-DEMOLITION FLOOR PLANS

65-AD-201 65-DEMOLITION PLAN

66-AD-201 66-FIRST FLOOR DEMOLITION PLAN

END OF VOLUME 4

END OF VOLUME 3

SHEET NO. SHEET NAME

CI0001 GENERAL NOTES

RC0001 EXISTING CONDITIONS PLAN

CS0001 SECONDARY FIBER OPTICS SITE PLAN

CU0100 SECONDARY FIBER OPTICS PLAN AND PROFILE

CU0101 SECONDARY FIBER OPTICS PLAN AND PROFILE

CG0100 BUILDING 1 TELECOM GRADING PLAN

CG0101 BUILDING 1 TELECOM EROSION CONTROL PLAN

CG0200 BUILDING 66 TELECOM GRADING PLAN

CG0300 BUILDING 11 TELECOM GRADING PLAN

CJ0001 DETAILS

CJ0002 DETAILS

CJ0003 DETAILS

SHEET NO. SHEET NAME

00-SN-001 STRUCTURAL NOTES

00-SN-002 STRUCTURAL NOTES

01-SF-100 01- PLANS

01-SD-100 DETAILS

01-SD-101 DETAILS

01-SD-102 DETAILS

11-SF-100 11 - PLANS

11-SD-100 DETAILS

66-SF-100 66 - PLANS

66-SD-100 DETAILS

TELECOMMUNICATIONS

ARCHITECTURAL - NEW CONSTRUCTION (CONTINUED)

END OF VOLUME 1

VOLUME 2

SHEET NO. SHEET NAME

001-TN-0B1 TELECOM REMODEL PLAN -BLDG 1 BASEMENT

001-TN-0B1.1 TELECOM DISTANCE ASSESMENT -BLDG 1 BASEMENT

001-TN-011 TELECOM REMODEL PLAN -BLDG 1 FIRST FLOOR

001-TN-021 TELECOM REMODEL PLAN -BLDG 1 SECOND FLOOR

001-TN-031 TELECOM REMODEL PLAN -BLDG 1 THIRD FLOOR

002-TN-0B1 TELECOM REMODEL PLAN -BLDG 2 SUB-BASEMENT/BASEMENT

002-TN-0B1.1 TELECOM DISTANCE ASSESMENT -BLDG 2 BASEMENT

002-TN-011 TELECOM REMODEL PLAN -BLDG 2 FIRST & SECOND FLOORS

002-TN-021.1 TELECOM DISTANCE ASSESMENT -BLDG 2 SECOND FLOOR

003-TN-0B1 TELECOM REMODEL PLAN -BLDG 3 FLOOR LAYOUTS

003-TN-0B1.1 TELECOM DISTANCE ASSESMENT -BLDG 3 FIRST FLOOR

005-TN-011 TELECOM REMODEL PLAN -BLDG 5

005-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 5 SECOND FLOOR

006-TN-0B1 TELECOM REMODEL PLANS -BLDG 6

006-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 6 FIRST FLOOR

007-TN-B1 TELECOM REMODEL PLAN -BLDG 7 BASEMENT

007-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 7 FIRST FLOOR

008-TN-B1 TELECOM REMODEL PLAN -BLDG 8 BASEMENT

008-TN-011 TELECOM DISTANCE ASSESMENT -BLDG 8 FIRST & SECOND FLOOR

008-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 8

009-TN-B1 TELECOM REMODEL PLAN -BLDG 9

010-TN-001 TELECOM REMODEL PLAN -BLDG 10

011-TN-0B1 TELECOM REMODEL PLAN -BLDG 11

011-TN-0B1.1 TELECOM DISTANCE ASSESMENT -BLDG 11 BASEMENT

012-TJ-0B1A TELECOM REMODEL PLAN -BLDG 12 BASEMENT A ENLARGED

012-TJ-0B1C TELECOM REMODEL PLAN -BLDG 12 BASEMENT C/D ENLARGED

012-TJ-001A TELECOM REMODEL PLAN -BLDG 12 GROUND A ENLARGED

012-TJ-001B TELECOM REMODEL PLAN -BLDG 12 GROUND B ENLARGED

012-TJ-001C TELECOM REMODEL PLAN -BLDG 12 GROUND C/D ENLARGED

012-TJ-011A TELECOM REMODEL PLAN -BLDG 12 FIRST FLOOR A ENLARGED

012-TJ-011B TELECOM REMODEL PLAN -BLDG 12 FIRST FLOOR B ENLARGED

012-TJ-011C TELECOM REMODEL PLAN -BLDG 12 FIRST FLOOR C/D ENLARGED

012-TJ-021A TELECOM REMODEL PLAN -BLDG 12 SECOND FLOOR A ENLARGED

012-TJ-021B TELECOM REMODEL PLAN -BLDG 12 SECOND FLOOR B ENLARGED

012-TJ-021C TELECOM REMODEL PLAN -BLDG 12 SECOND FLR C/D ENLARGED

012-TJ-031B TELECOM REMODEL PLAN -BLDG 12 THIRD FLOOR B ENLARGED

012-TJ-031C TELECOM REMODEL PLAN -BLDG 12 THIRD FLOOR C/D ENLARGED

012-TN-0B1 TELECOM REMODEL PLAN -BLDG 12 BASEMENT

012-TN-0B1.1 TELECOM DISTANCE ASSESMENT -BLDG 12 BASEMENT

012-TN-001 TELECOM REMODEL PLAN -BLDG 12 GROUND

012-TN-001.1 TELECOM DISTANCE ASSESSMENT -BLDG 12 GND FLR

012-TN-001.2 TELECOM DISTANCE ASSESSMENT -BLDG 12 GND FLR

012-TN-001.3 TELECOM DISTANCE ASSESSMENT -BLDG 12 GND FLR

012-TN-011 TELECOM REMODEL PLAN -BLDG 12 FIRST FLOOR

012-TN-011.1 TELECOM DISTANCE ASSESSMENT -BLDG 12 1ST FLR

012-TN-011.2 TELECOM DISTANCE ASSESSMENT -BLDG 12 1ST FLR

012-TN-021 TELECOM REMODEL PLAN -BLDG 12 SECOND FLOOR

012-TN-021.1 TELECOM DISTANCE ASSESSMENT -BLDG 12 2ND FLR

012-TN-031 TELECOM REMODEL PLAN -BLDG 12 THIRD FLOOR

012-TN-031.1 TELECOM DISTANCE ASSESSMENT -BLDG 12 3RD FLR

012-TN-041 TELECOM REMODEL PLAN -BLDG 12 FOURTH FLOOR

012-TN-041.1 TELECOM DISTANCE ASSESSMENT -BLDG 12 4TH FLR

013-TN-011 TELECOM REMODEL PLAN -BLDG 13 FIRST FLOOR

014-TN-0G1 TELECOM REMODEL PLAN -BLDG 14

014-TN-0G1.1 TELECOM DISTANCE ASSESMENT -BLDG 14 FIRST FLOOR

017-TN-011 TELECOM REMODEL PLAN -BLDG 17 FIRST FLOOR

017-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 17 FIRST FLOOR

018-TN-011 TELECOM REMODEL PLAN -BLDG 18

018-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 18

020-TN-011 TELECOM REMODEL PLAN -BLDG 20

020-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 20

023-TN-0B1 TELECOM REMODEL PLAN -BLDG 23

023-TN-0B1.1 TELECOM DISTANCE ASSESSMENT -BLDG 23

029-TN-0B1 TELECOM REMODEL PLAN -BLDG 29

029-TN-0B1.1 TELECOM DIST ASSESSMENT-BLDG 29 BASEMENT

043-TN-011 TELECOM REMODEL PLAN -BLDG 43

043-TN-011.1 TELECOM DISTANCE ASSESSMENT -BLDG 43

053-TN-0B1 TELECOM REMODEL PLAN -BLDG 53

053-TN-021.1 TELECOM DISTANCE ASSESSMENT -BLDG 53

065-TN-011 TELECOM REMODEL PLAN -BLDG 65

065-TN-011.1 TELECOM DISTANCE ASSESSMENT -BLDG 65

065-TN-012 ENLARGED TELECOM REMODEL PLAN -ROOM 109

065-TN-012.1 VA MCR DETAILS

065-TN-012.2 VA MCR DETAILS

065-TN-012.3 VA MCR DETAILS

066-TN-011 TELECOM REMODEL PLAN -BLDG 66

066-TN-011.1 TELECOM DISTANCE ASSESMENT -BLDG 66

SHEET NO. SHEET NAME

00-GI-000.3 COVER SHEET VOLUME 3

00-GI-001 INDEX OF DRAWINGS

001-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 1 BASEMENT & 1ST FLOOR

001-ED-021 ELECTRICAL DEMOLITION PLAN -BLDG 1 SECOND & THIRD FLOOR

002-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 2 BASEMENT

002-ED-021 ELECTRICAL DEMOLITION PLAN -BLDG 2 SECOND FLOOR

003-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 3

004-ED-0B1 ELECTRICAL DEMO PLAN -BLDG 4 LAYOUTS

004-ED-0B2 ELECTRICAL DEMOLITION PLAN -BLDG 4 ENLARGED PLANS

005-ED-021 ELECTRICAL DEMOLITION PLAN -BLDG 5 SECOND FLOOR

006-ED-0B1 ELECTRICAL DEMOLITION PLANS -BLDG 6

006-ED-0B2 ENLARGED ELECTRICAL DEMOLITION PLANS -BLDG 6

007-ED-0B1 ELECTRICAL DEMOLITION PLANS - BLDG 7

008-ED-011 ELECTRICAL DEMOLITION PLAN - BLDG 8 FIRST FLOOR

011-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 11

012-ED-0B1 ELECTRICAL DEMOLITION -BLDG 12 BASEMENT

012-ED-0B1D ELECTRICAL DEMOLITION -BLDG 12 BASEMENT C/D

012-ED-001 ELECTRICAL DEMOLITION -BLDG 12 GROUND FLOOR

012-ED-001A ELECTRICAL DEMO -BLDG 12 GROUND A ENLARGED

012-ED-001D ELECTRICAL DEMO -BLDG 12 GROUND C/D ENLARGED

012-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 12 FIRST FLOOR

012-ED-011A ELECTRICAL DEMO -BLDG 12 FIRST FLOOR A ENLARGED

012-ED-011D ELECTRICAL DEMO -BLDG 12 FIRST FLOOR C/D ENLARGED

012-ED-021 ELECTRICAL DEMOLITION PLAN -BLDG 12 SECOND FLOOR

012-ED-021D ELECTRICAL DEMO -BLDG 12 SECOND FLOOR C/D ENLARGED

012-ED-031 ELECTRICAL DEMOLITION PLAN -BLDG 12 THIRD FLOOR

012-ED-031B ELECTRICAL DEMO PLAN -BLDG 12 THIRD FLOOR ENLARGED

012-ED-041 ELECTRICAL DEMO PLAN -BLDG 12 FOURTH FLOOR

013-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 13 FIRST FLOOR

014-ED-0G1 ELECTRICAL DEMOLITION PLAN -BLDG 14

017-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 17 FIRST FLOOR

018-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 18

020-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 20

023-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 23

029-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 29

043-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 43

053-ED-0B1 ELECTRICAL DEMOLITION PLAN -BLDG 53

065-ED-011 ELECTRICAL DEMOLITION PLAN -BLDG 65

065-ED-012 ENLARGED ELECTRICAL DEMOLITION PLAN -ROOM 109

065-ED-013 ENLARGED LIGHTING DEMOLITION PLAN -ROOM 109

ELECTRICAL

VOLUME 4

SHEET NO. SHEET NAME

00-GI-000.3 COVER SHEET VOLUME 3

00-GI-001 INDEX OF DRAWINGS

001-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 1 BASEMENT

001-TD-011 TELECOM DEMOLITION PLAN -BLDG 1 FIRST FLOOR

001-TD-021 TELECOM DEMOLITION PLAN -BLDG 1 SECOND FLOOR

001-TD-031 TELECOM DEMOLITION PLAN -BLDG 1 THIRD FLOOR

002-TD-0B1 TELECOM DEMO PLAN -BLDG 2 SUB-BASEMENT/BASEMENT

002-TD-011 TELECOM DEMOLITION PLAN -BLDG 2 FIRST & SECOND FLOORS

003-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 3 FLOOR LAYOUTS

005-TD-011 TELECOM DEMOLITION PLAN -BLDG 5

006-TD-0B1 TELECOM DEMOLITION PLANS -BLDG 6

006-TD-011 TELECOM DEMOLITION PLAN -BLDG 6 FIRST FLOOR

007-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 7

007-TD-011 ENLARGED TELECOM DEMOLITION PLAN -BLDG 7

008-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 8 BASEMENT

008-TD-011 TELECOM DEMOLITION PLAN -BLDG 8 FIRST & SECOND FLOOR

009-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 9

010-TD-001 TELECOM DEMOLITION PLAN -BLDG 10

011-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 11

012-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 12 BASEMENT

012-TD-0B1A TELECOM DEMO -BLDG 12 BASEMENT A ENLARGED

012-TD-0B1C FILE A TELECOM DEMO -BLDG 12 BASEMENT C/D ENLARGED

012-TD-001 TELECOM DEMOLITION PLAN -BLDG 12 GROUND

012-TD-001A TELECOM DEMO PLAN -BLDG 12 GROUND A ENLARGED

012-TD-001B TELECOM DEMO PLAN -BLDG 12 GROUND B ENLARGED

012-TD-001C TELECOM DEMO PLAN-BLDG 12 GROUND C/D ENLARGED

012-TD-011 TELECOM DEMOLITION PLAN -BLDG 12 FIRST FLOOR

012-TD-011A TELECOM DEMO PLAN -BLDG 12 FIRST FLOOR A ENLARGED

012-TD-011B TELECOM DEMO PLAN -BLDG 12 FIRST FLOOR B ENLARGED

012-TD-011C TELECOM DEMO PLAN -BLDG 12 FIRST FLOOR C/D ENLARGED

012-TD-021 TELECOM DEMOLITION PLAN -BLDG 12 SECOND FLOOR

012-TD-021A TELECOM DEMO PLAN -BLDG 12 SECOND FLOOR A ENLARGED

012-TD-021B TELECOM DEMO PLAN -BLDG 12 SECOND FLOOR B ENLARGED

012-TD-021C TELECOM DEMO PLAN -BLDG 12 SECOND FLOOR C/D ENLARGED

012-TD-031 TELECOM DEMOLITION PLAN -BLDG 12 THIRD FLOOR

012-TD-031B TELECOM DEMO PLAN -BLDG 12 THIRD FLOOR B ENLARGED

012-TD-031C TELECOM DEMO PLAN -BLDG 12 THIRD FLOOR C/D ENLARGED

012-TD-041 TELECOM DEMOLITION PLAN -BLDG 12 FOURTH FLOOR

013-TD-011 TELECOM DEMOLITION PLAN -BLDG 13 FIRST FLOOR

014-TD-0G1 TELECOM DEMOLITION PLAN -BLDG 14

017-TD-011 TELECOM DEMOLITION PLAN -BLDG 17 FIRST FLOOR

018-TD-011 TELECOM DEMOLITION PLAN -BLDG 18

020-TD-011 TELECOM DEMOLITION PLAN -BLDG 20

023-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 23

029-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 29

043-TD-011 TELECOM DEMOLITION PLAN -BLDG 43

053-TD-0B1 TELECOM DEMOLITION PLAN -BLDG 53

065-TD-011 TELECOM DEMOLITION PLAN -BLDG 65

065-TD-012 ENLARGED TELECOM DEMOLITION PLAN -ROOM 109

066-TD-011 TELECOM DEMOLITION PLAN -BLDG 66

SHEET NO. SHEET NAME

TJ-001 GENERAL TELECOM NOTES

TK-101 TELEPHONE BACKBONE CABLING PLAN

TK-102 TELECOM SCHEDULES

TK-103 VOICE GATEWAY 1 SCHEDULE

TK-104 VOICE GATEWAY 2 SCHEDULE

TK-105 VOICE GATEWAY 3 SCHEDULE

TK-106 TELECOM DUCTBANK AND MAN HOLE ONE LINE

TK-107 DUCT BANK SCHEDULE

TK-108 PATCH PANEL SCHEDULES

SHEET NO. SHEET NAME

MK-001 MECHANICAL GENERAL INFORMATION

MK-002 MECHANICAL SITE PLAN

MK-003 DETAILS

MK-004 MECHANICAL SCHEDULES

MK-005 MECHANICAL CONTROLS INFORMATION

001-MD-0B1 01-BASEMENT HVAC DEMOLITION PLANS

001-MD-011 01-FIRST FLOOR HVAC DEMOLITION PLANS

001-MD-021 01-SECOND FLOOR HVAC DEMOLITION PLANS

001-MD-031 01-THIRD FLOOR HVAC DEMOLITION PLANS

002-MD-0B1 02-BASEMENT HVAC DEMOLITION PLANS

003-MD-011 03-FIRST FLOOR HVAC DEMOLITION PLANS

004-MD-0B1 04-HVAC DEMOLITION FLOOR PLANS

004-MD-0B2 04-ENLARGED HVAC DEMOLITION PLANS

005-MD-021 05-SECOND FLOOR HVAC DEMOLITION PLANS

006-MD-011 06-FIRST FLOOR HVAC DEMOLITION PLANS

SHEET NO. SHEET NAME

00-GI-000.1 COVER SHEET VOLUME 1

00-GI-001 INDEX OF DRAWINGS

00-GI-002 PROJECT CODE SUMMARY

00-GI-003 GENERAL NOTES

00-GI-004 PROJECT SITE PLAN

00-GI-005 PROJECT ASSEMBLY TYPES

00-GI-006 DOOR SCHEDULE AND DETAILS

00-GI-007 PARTITION DETAILS

00-GI-008 FIRE PROTECTION

END OF VOLUME 2

Revisions: Date:

SHEET NO. SHEET NAME

00-HA-000.1 GENERAL NOTES & QUANTITIES FOR HAZARDS ABATEMENT PLANS

000-HA-0B1 00-BASEMENT & FIRST FLOOR HAZARDS ABATEMENT PLANS

001-HA-0B1 01-BASEMENT HAZARDS ABATEMENT PLANS

001-HA-011 01-FIRST FLOOR HAZARDS ABATEMENT PLANS

001-HA-021 01-SECOND FLOOR HAZARDS ABATEMENT PLANS

001-HA-031 01-THIRD FLOOR HAZARDS ABATEMENT PLANS

002-HA-0B1 02-BASEMENT & SUB-BASEMENT HAZARDS ABATEMENT PLANS

002-HA-011 02-FIRST & SECOND FLOOR HAZARDS ABATEMENT PLANS

003-HA-0B1 03-BUILDING 03 HAZARDS ABATEMENT PLANS

004-HA-0B1 04-BUILDING 04 HAZARDS ABATEMENT PLANS

005-HA-0B1 05-BUILDING 05 HAZARDS ABATEMENT PLANS

006-HA-0B1 06-BUILDING 06 HAZARDS ABATEMENT PLANS

007-HA-0B1 07-BUILDING 07 HAZARDS ABATEMENT PLANS

008-HA-0B1 08-BUILDING 08 HAZARDS ABATEMENT PLANS

009-HA-0B1 09-BUILDING 09 HAZARDS ABATEMENT PLANS

010-HA-0B1 10-BUILDING 10 HAZARDS ABATEMENT PLANS

011-HA-0B1 11-BUILDING 11 HAZARDS ABATEMENT PLANS

012-HA-0BA 12-BASEMENT HAZARDS ABATEMENT PLANS

012-HA-0BD 12-BASEMENT SECTOR D HAZARDS ABATEMENT PLANS

012-HA-0GA 12-GROUND FLOOR SECTOR A HAZARDS ABATEMENT PLANS

012-HA-0GB 01-BASEMENT & FIRST FLOOR HAZARDS ABATEMENT PLANS

012-HA-0GCD 12-GROUND FLOOR SECTORS C&D HAZARDS ABATEMENT PLANS

012-HA-01A 12-FIRST FLOOR SECTOR A HAZARDS ABATEMENT PLANS

012-HA-01B 12-FIRST FLOOR SECTOR B HAZARDS ABATEMENT PLANS

012-HA-01CD 12-FIRST FLOOR SECTORS C&D HAZARDS ABATEMENT PLANS

012-HA-02A 12-SECOND FLOOR SECTOR A HAZARDS ABATEMENT PLANS

012-HA-02B 12-SECOND FLOOR SECTOR B HAZARDS ABATEMENT PLANS

012-HA-02CD 12-SECOND FLOOR SECTORS C&D HAZARDS ABATEMENT PLANS

012-HA-03BCD 12-THIRD FLOOR HAZARDS ABATEMENT PLANS

012-HA-04 12-FOURTH FLOOR HAZARDS ABATEMENT PLANS

013-HA-011 13-BUILDING 13 HAZARDS ABATEMENT PLANS

014-HA-0G1 14-BUILDING 14 HAZARDS ABATEMENT PLANS

017-HA-011 14-BUILDING 14 HAZARDS ABATEMENT PLANS

018-HA-011 01-BASEMENT & FIRST FLOOR HAZARDS ABATEMENT PLANS

020-HA-0B1 20-BUILDING 20 HAZARDS ABATEMENT PLANS

023-HA-0B1 23-BUILDING 23 HAZARDS ABATEMENT PLANS

029-HA-0B1 29-BUILDING 29 HAZARDS ABATEMENT PLANS

043-HA-011 43-BUILDING 43 HAZARDS ABATEMENT PLANS

053-HA-0G1 53-BUILDING 53 HAZARDS ABATEMENT PLANS

065-HA-011 65-BUILDING 65 HAZARDS ABATEMENT PLANS

066-HA-011 66-BUILDING 66 HAZARDS ABATEMENT PLANS

GENERAL

SHEET NO. SHEET NAME

007-MD-011 07-FIRST FLOOR HVAC DEMOLITION PLANS

008-MD-011 08-FIRST FLOOR HVAC DEMOLITION PLANS

010-MD-0B1 10-BASEMENT HVAC DEMOLITION PLANS

011-MD-001 11-GROUND FLOOR HVAC DEMOLITION PLANS

012-MD-0B1 12-BASEMENT HVAC DEMOLITION PLANS - SECTOR A

012-MD-001 12-GROUND FLOOR HVAC DEMOLITION PLANS - SECTOR C/D

012-MD-011 12-FIRST FLOOR HVAC DEMOLITION PLANS - SECTOR A

012-MD-012 12-FIRST FLOOR HVAC DEMOLITION PLANS - SECTOR C/D

012-MD-021 12-SECOND FLOOR HVAC DEMOLITION PLANS - SECTOR C/D

012-MD-031 12-THIRD FLOOR HVAC DEMOLITION PLANS - SECTOR C/D

012-MD-041 12-FOURTH FLOOR HVAC DEMOLITION PLANS - SECTOR C/D

014-MD-001 14-GROUND FLOOR HVAC DEMOLITION PLANS

018-MD-011 18-FIRST FLOOR HVAC DEMOLITION PLANS

023-MD-0B1 23-BASEMENT HVAC DEMOLITION PLANS

053-MD-011 53-FIRST FLOOR HVAC DEMOLITION PLANS

065-MD-011 65-FIRST FLOOR HVAC DEMOLITION PLANS

001-MH-0B1 01-BASEMENT HVAC PLANS

001-MH-011 01-FIRST FLOOR HVAC PLANS

001-MH-021 01-SECOND FLOOR HVAC PLANS

001-MH-031 01-THIRD FLOOR HVAC PLANS

001-MH-041 01-ROOF HVAC PLANS

002-MH-0B1 02-BASEMENT HVAC PLANS

002-MH-021 02-SECOND FLOOR AND ROOF HVAC PLANS

003-MH-0B1 03-BASEMENT AND FIRST FLOOR HVAC PLANS

004-MH-0B1 04-HVAC FLOOR PLANS

004-MH-0B2 04-ENLARGED HVAC PLANS

005-MH-0B1 05-BASEMENT AND SECOND FLOOR HVAC PLANS

006-MH-0B1 06-BASEMENT AND FIRST FLOOR HVAC PLANS

007-MH-011 07-FIRST FLOOR HVAC PLANS

008-MH-011 08-FIRST FLOOR HVAC PLANS

010-MH-0B1 10-BASEMENT HVAC PLANS

011-MH-001 11-GROUND FLOOR HVAC PLANS

012-MH-0B1 12-BASEMENT HVAC PLANS - SECTOR A

012-MH-001 12-GROUND FLOOR HVAC PLANS - SECTOR A

012-MH-002 12-GROUND FLOOR HVAC PLANS - SECTOR C/D

012-MH-011 12-FIRST FLOOR HVAC PLANS - SECTOR A

012-MH-012 12-FIRST FLOOR HVAC PLANS - SECTOR C/D

012-MH-021 12-SECOND FLOOR HVAC PLANS - SECTOR A

012-MH-022 12-SECOND FLOOR HVAC PLANS - SECTOR C/D

012-MH-031 12-THIRD FLOOR HVAC PLANS - SECTOR C/D

012-MH-041 12-FOURTH FLOOR AND ROOF HVAC PLANS - SECTOR C/D

014-MH-001 14-GROUND FLOOR HVAC PLANS

018-MH-011 18-FIRST FLOOR AND MEZZANINE HVAC PLANS

023-MH-011 23-BASEMENT AND FIRST FLOOR HVAC PLANS

053-MH-011 53-FIRST FLOOR AND ROOF HVAC PLANS

065-MH-011 65-FIRST FLOOR HVAC PLANS

066-MH-011 66-FIRST FLOOR HVAC PLANS

SHEET NO. SHEET NAME

TK-109 PATCH PANEL SCHEDULES

TK-110 PATCH PANEL SCHEDULES

TK-111 PATCH PANEL SCHEDULES

TK-112 PATCH PANEL SCHEDULES

TK-113 PATCH PANEL SCHEDULES

TK-114 PATCH PANEL SCHEDULES

TK-115 PATCH PANEL SCHEDULES

TK-116 PATCH PANEL SCHEDULES

TK-117 PATCH PANEL SCHEDULES

TK-118 PATCH PANEL SCHEDULES

TK-119 PATCH PANEL SCHEDULES

TK-120 PATCH PANEL SCHEDULES

TK-121 PATCH PANEL SCHEDULES

TK-122 PATCH PANEL SCHEDULES

TK-123 PATCH PANEL SCHEDULES

TK-124 PATCH PANEL SCHEDULES

TK-125 PATCH PANEL SCHEDULES

TK-126 TELECOM GROUNDING DETAILS

TK-127 TELECOM GROUNDING DETAILS

TK-128 FIBER SITE REMODEL ONE LINE -PRIMARY PATHWAYS

TK-129 FIBER SITE REMODEL ONE LINE -SECONDARY PATHWAYS

TK-130 ANALOG SITE REMODEL

TK-131 TELECOM RACK BONDING DETAILS

TK-132 TELECOM RACK BONDING DETAILS

TK-133 TELECOM RACK BONDING DETAILS

TK-134 TELECOM DETAILS

TK-135 NEW PATCH PANEL SCHEDULE -BLDG 1

TK-136 NEW PATCH PANEL SCHEDULE -BLDG 1 & 2

TK-137 NEW PATCH PANEL SCHEDULE -BLDG 3 & 5

TK-138 NEW PATCH PANEL SCHEDULE -BLDG 6, 7, 8, & 11

TK-139 NEW PATCH PANEL SCHEDULE -BLDG 12

TK-140 NEW PATCH PANEL SCHEDULE -BLDG 12

TK-141 NEW PATCH PANEL SCHEDULE -BLDG 12

TK-142 NEW PATCH PANEL SCHEDULE -BLDG 12

TK-143 NEW PATCH PANEL SCHEDULE -BLDG 12

TK-144 NEW PATCH PANEL SCHEDULE -BLDG 14, 17, 18, 20, 23, 29 & 43

TK-145 NEW PATCH PANEL SCHEDULE -BLDG 53, 65 & 66

TS-001 TELECOM SITE PLAN

TS-002 EXISTING BLOW IN FIBER SITE PLAN

VOLUME 2 - CONTINUED VOLUME 3 - CONTINUED

MECHANICAL

SHEET NO. SHEET NAME

00-GI-000.2 COVER SHEET VOLUME 2

00-GI-001 INDEX OF DRAWINGS

HAZARD ABATEMENT

BUILDING CONSTRUCTION

INCLUDES ALL CONDITIONED BUILDING AREAS INCLUDING MECHANICAL SHAFTS, ELEVATOR

SHAFTS, AND STAIRWELLS

BUILDING FOOTPRINT = 10,600 S.F.

GROUND FLOOR = 10,600 SF

FIRST FLOOR = 9680 SF

SECOND FLOOR = 7300 SF

THIRD FLOOR = 5885 SF

TOTAL BUILDING SF = 33,465 SF

GENERAL BUILDING HEIGHTS AND AREAS

B

NUMBER OF

STORIES /

ALLOWABLE

PRIMARY

OCCUPANCY

CLASSIFICATION

TYPE OF

CONSTRUCTION

BUILDING

HEIGHT /

ALLOWABLE

4 / 4 PER UBC

504.2

VA 48.5' / 70' PER

UBC 504.2

NFPA 101/5000 AND PER IBC TABLES 504.3,

504.4

AREA /

ALLOWABLE

4,000 GSF /

18,000 GSF

CONSTRUCTION TYPE: NFPA: V(111) IBC: VA, FULLY SPRINKLERED

REQUIRED FIRE RESISTANCE PER TABLE 601:

PRIMARY STRUCTURAL FRAME: 1 HR (BEAMS UL DES N759; COLUMNS

UL DES X790)

BEARING WALLS

EXTERIOR: 1 HR

INTERIOR: 1 HR

NONBEARING WALLS AND PARTITIONS PER TABLE 6002:

EXTERIOR: 0 HR

NONBEARING WALLS AND PARTITIONS:

INTERIOR: 0 HR

FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS: 1 HR (UL DES D925)

ROOF CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS: 1 HR (ROOF DECK: UL DES P719, ROOF BEAMS: UL DES S721)

SEPARATION DISTANCES PER TABLE 705.5:

FIRE SEPARATION DISTANCE

FIRE DISTANCE OCCUPANCY (B)

X<5' 1- HR

5' < X < 10 1- HR

10 < X < 30 1- HR

X > 30 0- HR

BUILDING 01

BUILDING 02

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 03

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 04

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 05

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 06

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 07

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 08

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

BUILDING 09

BUILDING 10

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING CONSTRUCTION

INCLUDES ALL CONDITIONED BUILDING AREAS INCLUDING MECHANICAL SHAFTS, ELEVATOR

SHAFTS, AND STAIRWELLS

GROUND FLOOR 00 = 3995 SF

FIRST FLOOR 01 = 3905 SF

SECOND LEVEL 02 = 1610 SF

TOTAL BUILDING SF = 9510 SF

GENERAL BUILDING HEIGHTS AND AREAS

NUMBER OF

STORIES /

ALLOWABLE

PRIMARY

OCCUPANCY

CLASSIFICATION

TYPE OF

CONSTRUCTION

BUILDING

HEIGHT /

ALLOWABLE

NFPA 101/5000 AND PER IBC TABLES 504.3, 504.4

AREA /

ALLOWABLE

BUILDING 11

B 4 / 4 PER UBC

504.2

VA 50.5' / 70' PER

UBC 504.2

10,674 GSF /

18,000 GSF

CONSTRUCTION TYPE: NFPA: V(111) IBC: VA, FULLY SPRINKLERED

REQUIRED FIRE RESISTANCE PER TABLE 601:

PRIMARY STRUCTURAL FRAME: 1 HR

(BEAMS UL DES N759; COLUMNS UL DES X790)

BEARING WALLS

EXTERIOR: 1 HR

INTERIOR: 1 HR

NONBEARING WALLS AND PARTITIONS PER TABLE 6002:

EXTERIOR: 0 HR

NONBEARING WALLS AND PARTITIONS:

INTERIOR: 0 HR

FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS: 1 HR (UL DES D925)

ROOF CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS: 1 HR

(ROOF DECK: UL DES P719, ROOF BEAMS: UL DES S721)

SEPARATION DISTANCES PER TABLE 705.5:

FIRE SEPARATION DISTANCE

FIRE DISTANCE OCCUPANCY (B)

X<5' 1- HR

5' < X < 10 1- HR

10 < X < 30 1- HR

X > 30 0- HR

BUILDING 12

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 13

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

BUILDING 14

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 17

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

CABINET REPLACEMENT ONLY

BUILDING 18

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

CABINET REPLACEMENT ONLY

BUILDING 20

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

CABINET REPLACEMENT ONLY

BUILDING 29

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

CABINET REPLACEMENT ONLY

BUILDING 43

NO ARCHITECTURAL WORK CONDUCTED IN THIS BUILDING, SEE ELECTRICAL AND

TELECOMMUNICATION DRAWINGS FOR EXTENT OF WORK

BUILDING 53

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING 65

INTERIOR REMODEL ONLY, NO EFFECT ON EGRESS OR OCCUPANCY

BUILDING CONSTRUCTION

INCLUDES ALL CONDITIONED BUILDING AREAS INCLUDING MECHANICAL SHAFTS, ELEVATOR

SHAFTS, AND STAIRWELLS

MAIN LEVEL 01 = 4840 SF

TOTAL BUILDING SF = 4840 SF

GENERAL BUILDING HEIGHTS AND AREAS

B

NUMBER OF

STORIES /

ALLOWABLE

PRIMARY

OCCUPANCY

CLASSIFICATION

TYPE OF

CONSTRUCTION

BUILDING

HEIGHT /

ALLOWABLE

1 / 3 VB 22'-9" / 60'-0"

PER IBC TABLES 504.3, 504.4

AREA /

ALLOWABLE

4840 SF / 22,000 SF

CONSTRUCTION TYPE: NFPA: V(000) IBC: VB

REQUIRED FIRE RESISTANCE PER TABLE 601:

PRIMARY STRUCTURAL FRAME: 0 HR

BEARING WALLS

EXTERIOR: 0 HR

INTERIOR: 0 HR

NONBEARING WALLS AND PARTITIONS PER TABLE 6002:

EXTERIOR: 0 HR

NONBEARING WALLS AND PARTITIONS:

INTERIOR: 0 HR

FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS: 0 HR

ROOF CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS: 0 HR

SEPARATION DISTANCES PER TABLE 705.5:

FIRE SEPARATION DISTANCE

FIRE DISTANCE OCCUPANCY (B)

X<5' 1- HR

5' < X < 10 1- HR

10 < X < 30 1- HR

X > 30 0- HR

BUILDING 66

APPLICABLE CODES AND ORDINANCES

BUILDING OCCUPANCY DATA

ENERGY CODE - BUILDING ENVELOPE

2021 NFPA 101, LIFE SAFETY CODE

2022 NFPA 13, STANDARD FOR THE INSTALL ATION OF SPRINKLER SYSTEMS

2020 NFPA 25, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER-

BASED FIRE PROTECTION SYSTEMS

2020 NFPA 70, NATIONAL ELECTRICAL CODE

2022 NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE

2020 NFPA 75, STANDARD FOR THE FIRE PROTECTION OF INFORMATION TECHNOLOGY

EQUIPMENT

2021 INTERNATIONAL BUILDING CODE (IBC) WHERE NFPA 101 AND ASSOCIATED DOCUMENTS

ARE SILENT

2021 INTERNATIONAL ENERGY CONSERVATION CODE

2021 INTERNATIONAL FIRE CODE (IFC), WHERE NFPA STANDARDS AND CODES ARE SILENT

2021 INTERNATIONAL MECHANICAL CODE (IMC)

2021 INTERNATIONAL FUEL GAS CODE (IFGC)

2021 UNIFORM PLUMBING CODE

2009 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES (ICC/ANSI 117.1)

use NFPA OCCUPANCY AND CONSTRUCTION TYPES

ASSEMBLY GROUP A-3 (PER IBC 303.X) - Building(s)

BUSINESS GROUP B (PER IBC 304.1) - Building(s)

FACTORY GROUP F-1 (PER IBC 306.X) - Building(s)

HIGH HAZARD GROUP H (PER IBC 307.X) - Building(s)

INSTITUTIONAL GROUP I-2 (PER IBC 308.X) - Building(s)

RESIDENTIAL GROUP R-X (PER IBC 310.X) - Building(s)

PER 2018 IECC TABLE C402.2:

INSULATION ENTIRELY ABOVE DECKROOFS

METAL FRAMEDWALLS, ABOVE GRADE

BELOW- GRADE WALLWALLS, BELOW GRADE

UNHEATED SLABSSLAB- ON- GRADE FLOORS

SWINGING

OPAQUE DOORS

REQUIRED PROVIDED

ROLL- UP OR SLIDING

NORTH DAKOTA - CLIMATE ZONE 06

R-30ci

R-13 + R-7.5ci

R-7.5ci

R-10 FOR 24" BELOW

U-0.37

R-4.75

R-30ci (MIN.)

R-22 + R-7.5ci

R-7.5ci

R-15 TO T.O. FOUNDATION

U-0.37

R-4.75

BUILDING ELEMENT

FIXED FENESTRATION

OPERABLE FENESTRATION

ENTRANCE DOORS

U-0.36; SHGC-0.40

U-0.43; SHGC-0.40

U-0.77; SHGC-0.40

U-0.33 MIN;

GLAZING SHGC 0.27 MIN

N/A

U-0.33 MIN;

GLAZING SHGC 0.27 MIN

2018 INTERNATIONAL ENERGY CODE SUMMARIES AND REFERENCE SECTIONS BELOW ARE

This is the start of the file's text. The full file is on GovTribe.