ATTCH_chiller_performance_summary.pdf
PDF 278 KB Posted
- Attached to
- Training Ship GOLDEN BEAR AC Chiller Replacement
- Solicitation number
- DTMA94Q1600023
About this file
Chiller Performance Summary
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ATTCH_SOW_updated_dates.pdf | ||
| ATTCH_foundation_drwg.pdf | ||
| ATTCH_chiller_replacement_guide.pdf | ||
| ATTCH_ABS_comments.pdf | ||
| solicitation_Q1600023.pdf | ||
| ATTCH_electrial_drwg.pdf | ||
| wage_determination_Solono_Co_2005_rev_17.pdf | ||
| ATTCH__Carrier_chiller_specs.pdf | ||
| ATTCH_Rev_Resp_task.pdf | ||
| ATTCH_Rev_E_pip_diag.pdf | ||
| ATTCH_Quote_submittal.xlsx | XLSX spreadsheet | |
| ATTCH_terms_and_conditions.pdf | ||
| ATTCH_CLAUSES.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
30 Series Chillers Performance Summary Project Name: Untitled 4/22/2013 Company Name: Carrier Marine Systems 2:22:53 PM
Untitled
Location
Buyer P.O.
Date 4/22/2013
Version 2.94
Unit Size 30HXC146RY-6--MAR
Capacity, Tons 131.2
Compressor Input Power, kw 125.8
Unit Input Power, kw 125.8
Capacity control steps 6
Minimum Capacity, % 20.0
Input kw/Ton .959
Unit EER 12.51
Refrigerant R134a
Cooler Data
Fluid Type Fresh Water
Fluid Entering Temperature, °F 54.0
Fluid Leaving Temperature, °F 44.0
Fluid Flow Rate, gpm 314.4
Fluid Pressure Drop, ft wg 13.6
Fluid Velocity, ft/s 5.3
Fouling Factor, (hr-sqft-F)/BTU 0.0001
Foul. Fact. Temp. Adj., °F .47
Saturated Suction Temp., °F
Circuit A 43.3
Circuit B 41.3
Outside Surface Area, sqft 230.1
Condenser Data
Fluid Type Sea Water
Fluid Entering Temperature, °F 90.0
Fluid Leaving Temperature, °F 102.0
Fluid Flow Rate, gpm 335.7
Fluid Pressure Drop, ft wg 12.5
Fluid Velocity, ft/s 5.7
Fouling Factor, (hr-sqft-F)/BTU 0.0005
Foul. Fact. Temp. Adj., °F 1.26
Saturated Discharge Temp., °F
Circuit A 110.7
Circuit B 113.1
Outside Surface Area, sqft 723.9
Factory Options
Flow Control Type EXV
Chiller Electrical Data
Nameplate Voltage, volts 460
Elec. Power Frequency, hertz 60
Power supply to control circuit, volts 115
Power supply to control circuit, phases
Minimum circuit amps 198
MOCP, amps 250
Max Instant. Current Flow (ICF), amps
Control circuit fuse amps 15
Factory Installed Options
Suction Service Valve No
Evaporator Passes Standard
Condenser Passes Standard
Start option Wye delta
Minimum load control None
Control transformer None
30 Series Chillers Performance Summary Project Name: Untitled 4/22/2013 Company Name: Carrier Marine Systems 2:22:53 PM
ARI Rating
Unit is outside of the scope of AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P).
Quote Control Special Cu-Ni Cond.