ATTCH_chiller_performance_summary.pdf

PDF 278 KB Posted

Attached to
Training Ship GOLDEN BEAR AC Chiller Replacement
Solicitation number
DTMA94Q1600023
Issued by

About this file

Chiller Performance Summary

View the file

Other files

File Type Posted
ATTCH_SOW_updated_dates.pdf PDF
ATTCH_foundation_drwg.pdf PDF
ATTCH_chiller_replacement_guide.pdf PDF
ATTCH_ABS_comments.pdf PDF
solicitation_Q1600023.pdf PDF
ATTCH_electrial_drwg.pdf PDF
wage_determination_Solono_Co_2005_rev_17.pdf PDF
ATTCH__Carrier_chiller_specs.pdf PDF
ATTCH_Rev_Resp_task.pdf PDF
ATTCH_Rev_E_pip_diag.pdf PDF
ATTCH_Quote_submittal.xlsx XLSX spreadsheet
ATTCH_terms_and_conditions.pdf PDF
ATTCH_CLAUSES.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

30 Series Chillers Performance Summary Project Name: Untitled 4/22/2013 Company Name: Carrier Marine Systems 2:22:53 PM

Untitled

Location

Buyer P.O.

Date 4/22/2013

Version 2.94

Unit Size 30HXC146RY-6--MAR

Capacity, Tons 131.2

Compressor Input Power, kw 125.8

Unit Input Power, kw 125.8

Capacity control steps 6

Minimum Capacity, % 20.0

Input kw/Ton .959

Unit EER 12.51

Refrigerant R134a

Cooler Data

Fluid Type Fresh Water

Fluid Entering Temperature, °F 54.0

Fluid Leaving Temperature, °F 44.0

Fluid Flow Rate, gpm 314.4

Fluid Pressure Drop, ft wg 13.6

Fluid Velocity, ft/s 5.3

Fouling Factor, (hr-sqft-F)/BTU 0.0001

Foul. Fact. Temp. Adj., °F .47

Saturated Suction Temp., °F

Circuit A 43.3

Circuit B 41.3

Outside Surface Area, sqft 230.1

Condenser Data

Fluid Type Sea Water

Fluid Entering Temperature, °F 90.0

Fluid Leaving Temperature, °F 102.0

Fluid Flow Rate, gpm 335.7

Fluid Pressure Drop, ft wg 12.5

Fluid Velocity, ft/s 5.7

Fouling Factor, (hr-sqft-F)/BTU 0.0005

Foul. Fact. Temp. Adj., °F 1.26

Saturated Discharge Temp., °F

Circuit A 110.7

Circuit B 113.1

Outside Surface Area, sqft 723.9

Factory Options

Flow Control Type EXV

Chiller Electrical Data

Nameplate Voltage, volts 460

Elec. Power Frequency, hertz 60

Power supply to control circuit, volts 115

Power supply to control circuit, phases

Minimum circuit amps 198

MOCP, amps 250

Max Instant. Current Flow (ICF), amps

Control circuit fuse amps 15

Factory Installed Options

Suction Service Valve No

Evaporator Passes Standard

Condenser Passes Standard

Start option Wye delta

Minimum load control None

Control transformer None

30 Series Chillers Performance Summary Project Name: Untitled 4/22/2013 Company Name: Carrier Marine Systems 2:22:53 PM

ARI Rating

Unit is outside of the scope of AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P).

Quote Control Special Cu-Ni Cond.