RFQ example.xlsx
XLSX spreadsheet 497 KB Posted
- Attached to
- GNAS BATTERIES ACQUISITION AND INSTALLATION Federal contract opportunity
- Solicitation number
- DTFAAC-16-R-00235
About this file
RFQ example (xlsx)
View the file
Other files for this federal contract opportunity
Show all 50
GNAS BATTERIES ACQUISITION AND INSTALLATION has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Requirements
| Due date XX/XX/XX | SAMPLE REQUEST FOR QUOTE (RFQ) REQUIREMENTS | ||||||||||||||||||
| Verify access requirements, new battery electrical integration with existing equipment, and new battery physical integration with available facility space. Provide project work scope and/or schedule to site personnel where requested. Provide FAA forms to facility personnel in advance of site visit and work with personnel to complete forms including but not limited to safety checklists, electrical work permits, asbestos work permit, CAIs etc. | |||||||||||||||||||
| JCN | Site ID | Fac Type | Location | Ship-to address: Note Contact Site to Confirm Shipping Address | POC | System | Existing batteries | Qty | Install date | Scope CLINs | Battery Monitoring CLIN | Battery Requirement CLIN | Batt Qty | Rack and spill kit CLIN | New Breaker enclosure | New Circuit Breaker with NO/NC aux contacts | New UVR or Shunt Trip on each breaker | Terminal Covers CLIN | Site Survey CLIN B0100 |
| 1401438 | BAM | ARSR | Battle Mountain, NV | Fallon LRR SSC |
Fallon Naval Air Station
| Fallon, NV 89406 | Adam Smith 202-267-0000 | Battery Charging Power Supply | |
| & Eaton UPS | Deka HR5500ET | 40 | 1. Replacement batteries and installation shall adhere to Common Scope elements (see Scope tab). |
2. Old batteries shall be uninstalled in accordance with OEM removal instructions.
3. New batteries shall be installed in rack in accordance with OEM installation instructions.
4. Batteries shall be tested to confirm correct installation and operation (including, but not limited to, 10 minutes service test at no less than facility load).
5. Removed batteries shall be disposed of in accordance with disposal instructions.
6. Existing battery monitoring system shall be uninstalled; Items 1, 2, 5, 6, 7, and 8 of BDS-40 equipment shall be installed; and Items 3 and 4 of BDS-40 equipment shall be provided in accordance with instructions (see R&R BMS tab).
7. SSC shall retain possession of removed battery monitor equipment. Contractor shall obtain property disposition documents from the SSC that authorize equipment removal before removing any equipment from the site.
8. New Battery monitor shall be commissioned/tested to confirm correct installation and operation.
9. Installation drawings shall include new battery monitoring equipment electrical details showing battery string and battery monitoring connections as well as cable/conduit routing and sizes.
10. Battery string AFHA labels shall be provided based the battery energy and calculations from the battery OEM or an engineer. Label format and content shall follow the example shown on the applicable AFHA tab.
11. Existing battery racks shall be evaluated to confirm condition and whether they are adequately installed.
12. Battery project shall include requirements listed on site survey TAB.
13. UPS programming shall be provided where required.
14. Battery monitoring shall be integrated into UPS where required.
15. Seismic reports shall be provided to confirm adequate anchoring for new rack installations. 1. (1) ea. Alber BDS-40 base unit.
2. (1) ea. BMDM software, network card, installation kit, temp. sensor, CT, harnesses w/ sense leads.
3. BDS-40 commissioning.
4. One full day of BDS-40 training.
5. (1) ea. mini-UPS, APC BN-4001.
6. (1) ea. laptop workstation, Atlantic Metal WLAP2016 (Grainger item # 3CTD3).
7. (1) ea. Alber-compatible laptop computer.
8. (1) ea. Cable lock, Office Depot # 196957 or eq.
9. Alber SVA-APM-1 CAL.
East Penn HR3500ET
Conversion Kit Braided Strabs Tab washers 40 N/A N/A N/A N/A Yes No
09-21-16
Scope
| COMMON SCOPE (CLINs ) | |
| 1. Batteries shall ship to site fully charged. | |
| 2. Factory date codes shall be in accordance with Section J, Attachment J2, section x.x. | |
| 3. Batteries and other equipment will be shipped with standard vendor documentation and installation hardware, including installation instructions in accordance with Section J, Attachment J1, section 7. | |
| 4. All battery deliveries shall be made utilizing trucks equipped with lift gates and pallet jacks. | |
| 5. Each site POC shall be contacted at least 48 hours prior to delivery to coordinate site access and availability. | |
| 6. Each shipment will include battery MSDS and factory data sheet. | |
| 7. Vendors will provide the appropriate "LOCK-OUT/TAG-OUT" devices for each battery disconnect circuit breaker provided. Specify make/model in quote. | |
| 8. Where specified, one day of Alber BDS-40/BMDM training shall be provided in accordance with "BDS-40, BMDM, & Field Replacement Training" | |
| BDS-40, BMDM, & Field Replacement Training | |
| 1. Alber will calibrate and commission the BDS-40 per Alber factory procedures and FAA specified settings. | |
| 2. Alber will program NO critical alarm contacts to close on detection of a critical battery failure. | |
| 3. Where specified, one day of Alber BDS-40/BMDM training shall be provided in accordance with "BDS-40, BMDM, & Field Replacement Training" | |
| 4. This training is designed for the system owner and basic users of the equipment. Six primary topics are covered in this one day program to introduce the attendees to a functional description of the equipment, how it works and the use of the Battery Monitor Data Manager software. | |
| a. Battery monitoring theory | |
| b. Monitoring system basics | |
| c. BDS-40 system overview | |
| d. System computer | |
| e. Battery Monitor Data Manager software | |
| o Navigation | |
| o Viewing and extracting data | |
| o Trending, analysis and report generation | |
| f. Field replacement | |
| o Procedure review | |
| o Unit settings/functionality verification | |
| 5. Each student is provided with a complete set of handout materials. An electronic certificate of completion will be provided to all students that complete the course. |
09-21-16
Site Survey
| SITE SURVEY REQUIREMENTS | |||||
| 1. Projects that install new equipment shall have site surveys and reports unless otherwise noted by the program office. | Replacement Actions | ||||
| 2. The survey report should summarize facility name/location, replacement actions and provide battery equipment installation drawings. | SITE | SITE ID / EQMT | DATE | ||
| 3. The battery equipment installation drawing should include the following items A though E: | Details | ||||
| A. Existing equipment elevation/layout details showing dimensions between existing battery equipment and surrounding objects (equipment, doors, walls etc.,) as necessary to reflect existing working clearances and designated spaces. | |||||
| B. Existing battery equipment electrical details showing battery string and battery monitoring connections as well as cable/conduit routing and sizes. | Removed Existing | ||||
| Provide Details of existing equipment. Use N/A when not applicable. | Make: | ||||
| C. New battery equipment elevation/layout details showing new equipment (battery cabinet, disconnect, monitoring system, eyewash, etc.) with dimensions between new equipment and surrounding objects (equipment, doors, walls, etc.) as necessary to reflect working clearances and designated spaces. | Model: | ||||
| D. New battery equipment electrical details showing battery string and battery monitoring connections as well as cable/conduit routing and sizes. | Cell Qty: | ||||
| E. If new battery rack is required, rack anchor details need to be provided including ref to a seismic report with a PE stamp included. | Rack: | ||||
| 4. The site survey, 3900-17 and 3900-18 shall be submitted approximately 6 weeks days before the project starts unless authorized otherwise by the program office. | Spill Kit: | ||||
| 5. During the project, any field changes need to be approved before implementation. All field changes should be captured and submitted as redlines to the site and program office at the project conclusion. | Monitoring: | ||||
| Other (explain): | |||||
| Install New (details) | |||||
| Provide Details of new equipment. Use N/A when not applicable. | Make: | ||||
| Model: | |||||
| Cell Qty: | |||||
| Rack: | |||||
| Spill Kit: | |||||
| Monitoring: | |||||
| Other (explain): | |||||
| Differences | |||||
| Provide rationale for why the replacement is not like-for-like. Use N/A when no applicable. | Make/Model: | ||||
| Jar Size: | |||||
| String Count: | |||||
| Rack / Spill Kit: | |||||
| Monitor: | |||||
| Other (explain): | |||||
| Prepared By |
09-21-16
AFHA Label CAT 0
AFHA Label Other CAT Editable version of this label available seperately
R&R BMS
| REMOVE & REPLACE EXISTING BATTERY MONITORING SYSTEM |
| The BDS-40 shall be configurable to support the current battery strings or any future string sizes, additional wiring harnesses or battery equipment. |
| The contractor will remove existing battery monitoring system. |
| The contractor will add dual tab washers as required by the BDS-40 systems per drawing and properly torque all battery terminal connections. |
| The contractor will mount the BDS-40 on top of the battery rack. |
| Unless the contractor has previous BDS-40 installation experience, the contractor will subcontract Alber to install the BDS-40. |
| The contractor will verify if a single wall outlet 120VAC 20A circuit for the Eaton single-phase UPS is available. This single-phase Eaton UPS will power the BDS-40. |
| If a single phase 120V 20A wall outlet is not available, the contractor will install the outlet. |
| The contractor will install the single-phase UPS to a 120V wall outlet. |
| The contractor will install a ¾-inch conduit from the UPS to the BDS-40 for the contact circuit. This does not apply to Mitsubishi UPSs. |
| The contractor will install a #18 twisted shielded pair between the UPS CSB mini-connector terminals 7 and 8 (building Alarm 6) and the BDS-40 (see attached wiring diagram). This does not apply to Mitsubishi UPSs. |
| The contractor will leave the BDS-40 end unterminated but with sufficient length to reach the BDS-40 alarm terminals (see attached BDS-40 Terminal location diagram). This does not apply to Mitsubishi UPSs. |
| The contractor will mount the GFE locking cabinet for the BDS-40 laptop to the wall in a location convenient to the BDS-40 (see site design drawing for location). |
| NOTE: The laptop should be located as far away as possible relative to the battery string in order to protect the technician/operator in the event of a battery safety incident. |
| The contractor will subcontract Alber to calibrate, and commission the BDS-40 per Alber factory procedures and Alber FAA required system settings. |
| Alber will program Normally Open (NO) critical alarm contacts to close on detection of a critical battery failure. |
| The contractor will subcontract Alber to provide a one-day on-site training seminar to site personnel. |
| The contractor will subcontract an Eaton UPS CSE to program the UPS Building alarm contacts #6 to monitor the BDS-40 Alarm contacts. This does not apply to Mitsubishi UPSs. |
BDS-40 Training
| BDS-40, BMDM, & Field Replacement Training |
| 1. Alber will calibrate and commission the BDS-40 per Alber factory procedures and FAA specified settings. |
| 2. Alber will program NO critical alarm contacts to close on detection of a critical battery failure. |
| 3. Where specified, one day of Alber BDS-40/BMDM training shall be provided in accordance with "BDS-40, BMDM, & Field Replacement Training" |
| 4. This training is designed for the system owner and basic users of the equipment. Six primary topics are covered in this one day program to introduce the attendees to a functional description of the equipment, how it works and the use of the Battery Monitor Data Manager software. |
| a. Battery monitoring theory |
| b. Monitoring system basics |
| c. BDS-40 system overview |
| d. System computer |
| e. Battery Monitor Data Manager software |
| o Navigation |
| o Viewing and extracting data |
| o Trending, analysis and report generation |
| f. Field replacement |
| o Procedure review |
| o Unit settings/functionality verification |
| 5. Each student is provided with a complete set of handout materials. An electronic certificate of completion will be provided to all students that complete the course. |
Project Installation Schedule Battery System Replacement and Removal Schedule Vendor shall provide a replacement schedule for each battery replacement/removal site. The schedule format is vendor selected, either a MS Word document listing steps/procedures in chronological order, or the Vendor may use an MS Project software program to create a schedule.
Purpose: Facility managers must know how the battery replacement will impact their facility.At a minimum the battery replacement schedule must show the following:
• Name and phone number of Vendor’s on-site supervisor that has an FAA Contractor security badge. This is the Vendor’s representative escorting battery replacement work crew members while on Government property.
• Battery system models and types used in the replacement, and any special tools associated with the replacement battery.
• Safety procedures and work permits.
• Battery system delivery (date/time/location)
• DC Power disconnect. (Only FAA Technicians can disconnect and reenergize power from facility equipment.) (Date/Time)
• Battery system removal from racks and palletizing for shipment. (Date/time)
• Installation of new battery system and reinstallation of battery monitoring system. (Date/Time)
• Energizing DC power to charge the new batteries. (FAA Technician reenergizes UPS and DC Power) (date/Time)
• Testing new batteries following charging step. (date/time)
• Commissioning Automated Battery Monitoring system. (date/time)
• Clean-up and shipment of old batteries to recycle facility.
• Contractor Acceptance Inspection (CAI) with FAA representative. Provide revised Site Survey Report, battery warranty information, battery testing data, battery documentation, and signed CAI.
Notes:
1. If actual calendar date is not established then the Vendor shall use a designation “Day 1, Day 2, etc” and replace with actual calendar dates when project start date is assigned.
2. The installation schedule shall note any after-hours work, weekend work or federal holiday work.
3. Vendor must expect to revise the installation schedule following review by the Government.
| BATTERY SYSTEM PROJECT MILESTONE/DELIVERABLE TABLE | |||||||||||||
| DELIVERABLES | PROJECT MILESTONES | ||||||||||||
| Quotes | Task Order Award | Initial Site Contact Phone Call | Follow up email to SSC manager and stakeholders | Site Survey with Site SOC | Core Project Documentation | Stakeholder and Program Offce Review | Pre-installation conference call with SSC POC and stakeholders to confirm readiness | Equipment arrival at facility or SSC staging area | Battery System Installation/Testing (including UPS re-programming where required) | Property Recycling and/or Disposition | Battery Monitoring System Commissioning and familiarization | Battery monitoring System PM | |
| DUE DATE REQUIREMENTS | |||||||||||||
| Due as specified on RFQ. | Contact is due no less then one week after task order award. | Email is due no more that 1 week after initial site contact phone call. | Site survey is due after follow up email and 8 weeks in advance of installation. | Due after site survey and no less than 6 weeks before installation date. | Stakeholder and Program Offce Review | Due after core project documentation and 1 to 2 weeks before Installation. | Equipment arrival date shall be specified and have SSC concurrence in advance. Prolonged equipment storage at facility or SSC should be avoided. | 3900-18 is due before starting installation. Other documents are due upon installation completion. | Due within two weeks after installation. | Commissioning is due no more than 4 weeks after installation and reports are due within one week of commissioning. | PM is due between 6 to 8 months after commissioning and report is due within 1 week of PM. | ||
| BATTERY PROJECT DELIVERABLE TABLE | x | ||||||||||||
| Blank 3900s | x | ||||||||||||
| RFQ without pricing | x | ||||||||||||
| Request property disposition document if scrapping rack or monitor | x | ||||||||||||
| Site Survey Report | x | ||||||||||||
| Battery System COTS IO&M | x | ||||||||||||
| Seismic Survey1 | x | ||||||||||||
| Battery system warranty documents | x | ||||||||||||
| Asbestos work practices1 | x | ||||||||||||
| Installation procedures | x | ||||||||||||
| Project schedule | x | ||||||||||||
| Battery MSDS | x | ||||||||||||
| Completed and signed 3900-17 | x | ||||||||||||
| Electrical work permit1 | x | ||||||||||||
| Asbestos work permit1 | x | ||||||||||||
| Completed and signed 3900-18 | x | ||||||||||||
| Battery system equipment and installation | x | ||||||||||||
| Signed CAI | x | ||||||||||||
| UPS Service Report1 | x | ||||||||||||
| Completed test Data | x | ||||||||||||
| Recycling certificate | x | ||||||||||||
| Property disposition document1 | x | ||||||||||||
| Battery monitoring system commissioning report & training certificates | x | ||||||||||||
| Battery monitoring system PM report | x | ||||||||||||
| 1 Required where applicable |
09-21-16
Project Cost Estimate
| CLIN | ITEM | Unit | Est. Qty | Price Per Unit | Item Total |
| A0100 | FCB VOR | STRING | See Table 1 | $0.00 |
A0200 FCB UPS STRING See Table 2 $0.00
A0300 FCB DCBUS STRING See Table 3 $0.00
A0400 FCB Control Power NiCad STRING See Table 4 $0.00
A0500 VRLA VOR STRING See Table 5 $0.00
A0600 VRLA UPS STRING See Table 6 $0.00
A0700 VRLA DCBUS STRING See Table 7 $0.00
A0800 VRLA Control Power STRING See Table 8 $0.00
A0900 SECL STRING See Table 9 $0.00
B0100 Site Surve and Report EACH 0 $0.00 $0.00
B0200 Seismic Report EACH 0 $0.00 $0.00
B0300 Standard Installation EACH 0 $0.00 $0.00
B0400 Delivery EACH 0 $0.00 $0.00
B0500 Disposal EACH 0 $0.00 $0.00
B0600 Testing EACH 0 $0.00 $0.00
C0100 Program Management Report EACH 0 $300.00 $0.00
| C0200 | Conferences and Meetings | ||||
| C0201 | Program Manager | HOUR | 0 | $0.00 | $0.00 |
| C0202 | Administrative Support | HOUR | 0 | $0.00 | $0.00 |
| Travel and Subsistence Support (Per Diem) | |||
| D0100 | Travel | TRIP | $0.00 |
| D0101 | Subsistence Support (Per Diem) | TRIP | $0.00 |
E0100 Special Or Unique NAS Battery Requirements EACH
BASE CONTRACT PERIOD TOTAL $0.00
| CLIN | FCB VOR | ||||
| A0101A | Battery (2nd Gen VORTAC w/ LPTA with EG) | 0 | $ - 0 | $0.00 | |
| A0101B | Rack (2nd Gen VORTAC w/ LPTA with EG) | 0 | $ - 0 | $0.00 | |
| A0101C | Spill Containment (2nd Gen VORTAC w/ LPTA with EG) | 0 | $ - 0 | $0.00 | |
| A0102A | Battery (2nd Gen VORTAC w/o LPTA with EG / VOR/DME with EG) | 0 | $ - 0 | $0.00 | |
| A0102B | Rack (2nd Gen VORTAC w/o LPTA with EG / VOR/DME with EG) | 0 | $ - 0 | $0.00 | |
| A0102C | Spill Containment (2nd Gen VORTAC w/o LPTA with EG / VOR/DME w EG) | 0 | $ - 0 | $0.00 | |
| A0103A | Battery (2nd Gen VOR or DME / Decom VOR/DME with EG) | 0 | $ - 0 | $0.00 | |
| A0103B | Rack (2nd Gen VOR or DME / Decom VOR/DME with EG) | 0 | $ - 0 | $0.00 | |
| A0103C | Spill Containment (2nd Gen VOR or DME / Decom VOR/DME with EG) | 0 | $ - 0 | $0.00 | |
| A0104A | Battery (2nd Gen VORTAC w/ LPTA without EG) | 0 | $ - 0 | $0.00 | |
| A0104B | Rack (2nd Gen VORTAC w/ LPTA without EG) | 0 | $ - 0 | $0.00 | |
| A0104C | Spill Containment (2nd Gen VORTAC w/ LPTA without EG) | 0 | $ - 0 | $0.00 | |
| A0105A | Battery (2nd Gen VORTAC w/o LPTA with EG / VOR/DME without EG) | 0 | $ - 0 | $0.00 | |
| A0105B | Rack (2nd Gen VORTAC w/o LPTA with EG / VOR/DME without EG) | 0 | $ - 0 | $0.00 | |
| A0105C | Spill Containment (2nd Gen VORTAC w/o LPTA w EG / VOR/DME w/o EG) | 0 | $ - 0 | $0.00 | |
| A0106A | Battery (2nd Gen VOR without EG) | 0 | $ - 0 | $0.00 | |
| A0106B | Rack (2nd Gen VOR without EG) | 0 | $ - 0 | $0.00 | |
| A0106C | Spill Containment (2nd Gen VOR without EG) | 0 | $ - 0 | $0.00 | |
| A0107A | Battery (2nd Gen DME / Decom VOR/DME without EG) | 0 | $ - 0 | $0.00 | |
| A0107B | Rack (2nd Gen DME / Decom VOR/DME without EG) | 0 | $ - 0 | $0.00 | |
| A0107C | Spill Containment (2nd Gen DME / Decom VOR/DME without EG) | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0100 | $0.00 |
| CLIN | FCB UPS | ||||
| A0201A | Battery (480V Flooded ACEPS and TRACON) | 0 | $ - 0 | $0.00 | |
| A0201B | Rack (480V Flooded ACEPS and TRACON) | 0 | $ - 0 | $0.00 | |
| A0201C | Spill Kit (480V Flooded ACEPS and TRACON) | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0200 | $0.00 |
| CLIN | FCB DCBUS | ||||
| A0301A | Battery (24VDC DCBUS Single String) | 0 | $ - 0 | $0.00 | |
| A0301B | Rack (24VDC DCBUS Single String) | 0 | $ - 0 | $0.00 | |
| A0301C | Spill Containment (24VDC DCBUS Single String) | 0 | $ - 0 | $0.00 | |
| A0302A | Battery (24VDC DCBUS Dual String, Dual Rack) | 0 | $ - 0 | $0.00 | |
| A0302B | Rack (24VDC DCBUS Dual String, Dual Rack) | 0 | $ - 0 | $0.00 | |
| A0302C | Spill Containment (24VDC DCBUS Dual String, Dual Rack) | 0 | $ - 0 | $0.00 | |
| A0303A | Battery (24VDC DCBUS Dual String, Single Rack) | 0 | $ - 0 | $0.00 | |
| A0303B | Rack (24VDC DCBUS Dual String, Single Rack) | 0 | $ - 0 | $0.00 | |
| A0303C | Spill Containment (24VDC DCBUS Dual String, Sngl Rack) | 0 | $ - 0 | $0.00 | |
| A0304A | Battery (48VDC DCBUS) | 0 | $ - 0 | $0.00 | |
| A0304B | Rack (48VDC DCBUS) | 0 | $ - 0 | $0.00 | |
| A0304C | Spill Containment (48VDC DCBUS) | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0300 | $0.00 |
| CLIN | FCB Control Power NiCad | ||||
| A0401A | Battery (NiCad DR/CRPDS Control) | 0 | $ - 0 | $0.00 | |
| A0401B | Rack (NiCad DR/CRPDS Control) | 0 | $ - 0 | $0.00 | |
| A0401C | Spill Kit (NiCad DR/CRPDS Control) | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0400 | $0.00 |
| CLIN | VRLA VOR | ||||
| A0501A | 2nd Gen VORTAC w/ LPTA with EG | 0 | $ - 0 | $0.00 | |
| A0502A | 2nd Gen VORTAC w/o LPTA with EG / VOR/DME with EG | 0 | $ - 0 | $0.00 | |
| A0503A | 2nd Gen VOR or DME / Decom VOR/DME with EG | 0 | $ - 0 | $0.00 | |
| A0504A | 3rd Gen VOR with EG | 0 | $ - 0 | $0.00 | |
| A0505A | 2nd Gen VORTAC w/ LPTA without EG | 0 | $ - 0 | $0.00 | |
| A0506A | 2nd Gen VORTAC w/o LPTA with EG / VOR/DME without EG | 0 | $ - 0 | $0.00 | |
| A0507A | 2nd Gen VOR without EG | 0 | $ - 0 | $0.00 | |
| A0508A | 2nd Gen DME / Decom VOR/DME without EG | 0 | $ - 0 | $0.00 | |
| A0509A | 3rd Gen VOR without EG | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0500 | $0.00 |
| CLIN | VRLA UPS | ||||
| A0601A | Battery (20KVA w/ 18 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0601B | Standard (20KVA w/ 18 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0601C | Seismic (20KVA w/ 18 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0602A | Battery (30kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0602B | Standard (30kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0602C | Seismic (30kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0603A | Battery (40kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0603B | Standard (40kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0603C | Seismic (40kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0604A | Battery (65kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0604B | Standard (65kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0604C | Seismic (65kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0605A | Battery (80kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0605B | Standard (80kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0605C | Seismic (80kVA w/ 32 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0606A | Battery (75kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0606B | Standard (75kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0606C | Seismic (75kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0607A | Battery (100kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0607B | Standard (100kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0607C | Seismic (100kVA w/ 30 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0608A | Battery (40kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0608B | Standard (40kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0608C | Seismic (40kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0609A | Battery (65kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0609B | Standard (65kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0609C | Seismic (65kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0610A | Battery (80kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0610B | Standard (80kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0610C | Seismic (80kVA w/ 36 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0611A | Battery (80kVA w/ 40 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0611B | Standard (80kVA w/ 40 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0611C | Seismic (80kVA w/ 40 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0612A | Battery (75kVA w/ 40 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0612B | Standard (75kVA w/ 40 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0612C | Seismic (75kVA w/ 40 HR3500 batteries) | 0 | $ - 0 | $0.00 | |
| A0613A | Battery (75kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0613B | Standard (75kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0613C | Seismic (75kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0614A | Battery (100kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0614B | Standard (100kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0614C | Seismic (100kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0615A | Battery (120kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0615B | Standard (120kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0615C | Seismic (120kVA w/ 30 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0616A | Battery (100kVA w/ 32 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0616B | Standard (100kVA w/ 32 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0616C | Seismic (100kVA w/ 32 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0617A | Battery (120kVA w/ 32 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0617B | Standard (120kVA w/ 32 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0617C | Seismic (120kVA w/ 32 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0618A | Battery (100kVA w/ 36 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0618B | Standard (100kVA w/ 36 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0618C | Seismic (100kVA w/ 36 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0619A | Battery (120kVA w/ 36 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0619B | Standard (120kVA w/ 36 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0619C | Seismic (120kVA w/ 36 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0620A | Battery (150kVA w/ 40 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0620B | Standard (150kVA w/ 40 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0620C | Seismic (150kVA w/ 40 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0621A | Battery (100kVA w/ 40 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0621B | Standard (100kVA w/ 40 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0621C | Seismic (100kVA w/ 40 HR5500 batteries) | 0 | $ - 0 | $0.00 | |
| A0622A | Battery (75kVA w/ 30 NSB12-170 batteries) | 0 | $ - 0 | $0.00 | |
| A0622B | Standard (75kVA w/ 30 NSB12-170 batteries) | 0 | $ - 0 | $0.00 | |
| A0622C | Seismic (75kVA w/ 30 NSB12-170 batteries) | 0 | $ - 0 | $0.00 | |
| A0623A | Battery (40kVA w/ 30 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0623B | Standard (40kVA w/ 30 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0623C | Seismic (40kVA w/ 30 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0624A | Battery (40kVA w/ 32 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0624B | Standard (40kVA w/ 32 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0624C | Seismic (40kVA w/ 32 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0625A | Battery (40kVA w/ 36 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0625B | Standard (40kVA w/ 36 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0625C | Seismic (40kVA w/ 36 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0626A | Battery (40kVA w/ 40 NSB12-170 batteries) | 0 | $ - 0 | $0.00 | |
| A0626B | Standard (40kVA w/ 40 NSB12-170 batteries) | 0 | $ - 0 | $0.00 | |
| A0626C | Seismic (40kVA w/ 40 NSB12-170 batteries) | 0 | $ - 0 | $0.00 | |
| A0627A | Battery (50kVA w/ 32 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0627B | Standard (50kVA w/ 32 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0627C | Seismic (50kVA w/ 32 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0628A | Battery (50kVA w/ 36 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0628B | Standard (50kVA w/ 36 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0628C | Seismic (50kVA w/ 36 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0629A | Battery (50kVA w/ 40 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0629B | Standard (50kVA w/ 40 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0629C | Seismic (50kVA w/ 40 NSB12-245 batteries) | 0 | $ - 0 | $0.00 | |
| A0630A | Battery (65kVA w/ 30 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0630B | Standard (65kVA w/ 30 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0630C | Seismic (65kVA w/ 30 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0631A | Battery (65kVA w/ 32 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0631B | Standard (65kVA w/ 32 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0631C | Seismic (65kVA w/ 32 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0632A | Battery (65kVA w/ 36 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0632B | Standard (65kVA w/ 36 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0632C | Seismic (65kVA w/ 36 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0633A | Battery (65kVA w/ 40 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0633B | Standard (65kVA w/ 40 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0633C | Seismic (65kVA w/ 40 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0634A | Battery (80kVA w/ 30 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0634B | Standard (80kVA w/ 30 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0634C | Seismic (80kVA w/ 30 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0635A | Battery (80kVA w/ 32 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0635B | Standard (80kVA w/ 32 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0635C | Seismic (80kVA w/ 32 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0636A | Battery (80kVA w/ 36 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0636B | Standard (80kVA w/ 36 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0636C | Seismic (80kVA w/ 36 NSB12-425 batteries) | 0 | $ - 0 | $0.00 | |
| A0637A | Battery (80kVA w/ 40 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0637B | Standard (80kVA w/ 40 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0637C | Seismic (80kVA w/ 40 NSB12-365 batteries) | 0 | $ - 0 | $0.00 | |
| A0638A | Battery (100kVA w/ 32 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0638B | Standard (100kVA w/ 32 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0638C | Seismic (100kVA w/ 32 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0639A | Battery (100kVA w/ 36 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0639B | Standard (100kVA w/ 36 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0639C | Seismic (100kVA w/ 36 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0640A | Battery (100kVA w/ 40 NSB12-450 batteries) | 0 | $ - 0 | $0.00 | |
| A0640B | Standard (100kVA w/ 40 NSB12-450 batteries) | 0 | $ - 0 | $0.00 | |
| A0640C | Seismic (100kVA w/ 40 NSB12-450 batteries) | 0 | $ - 0 | $0.00 | |
| A0641A | Battery (120kVA w/ 30 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0641B | Standard (120kVA w/ 30 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0641C | Seismic (120kVA w/ 30 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0642A | Battery (120kVA w/ 32 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0642B | Standard (120kVA w/ 32 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0642C | Seismic (120kVA w/ 32 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0643A | Battery (120kVA w/ 36 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0643B | Standard (120kVA w/ 36 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0643C | Seismic (120kVA w/ 36 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0644A | Battery (120kVA w/ 40 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0644B | Standard (120kVA w/ 40 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0644C | Seismic (120kVA w/ 40 NSB12-650 batteries) | 0 | $ - 0 | $0.00 | |
| A0645A | Battery (160kVA w/ 40 NSB12-730 batteries) | 0 | $ - 0 | $0.00 | |
| A0645B | Standard (160kVA w/ 40 NSB12-730 batteries) | 0 | $ - 0 | $0.00 | |
| A0645C | Seismic (160kVA w/ 40 NSB12-730 batteries) | 0 | $ - 0 | $0.00 | |
| A0646A | 30 UPS12-150MR | 0 | $ - 0 | $0.00 | |
| A0647A | 30 UPS12-210MR | 0 | $ - 0 | $0.00 | |
| A0648A | 30 UPS12-300MR | 0 | $ - 0 | $0.00 | |
| A0649A | 30 UPS12-350MR | 0 | $ - 0 | $0.00 | |
| A0650A | 30 UPS12-400MR | 0 | $ - 0 | $0.00 | |
| A0651A | 30 UPS12-490MR | 0 | $ - 0 | $0.00 | |
| A0652A | 30 UPS12-600MR | 0 | $ - 0 | $0.00 | |
| A0653A | 40 UPS12-150MR | 0 | $ - 0 | $0.00 | |
| A0654A | 40 UPS12-210MR | 0 | $ - 0 | $0.00 | |
| A0655A | 40 UPS12-300MR | 0 | $ - 0 | $0.00 | |
| A0656A | 40 UPS12-350MR | 0 | $ - 0 | $0.00 | |
| A0657A | 40 UPS12-400MR | 0 | $ - 0 | $0.00 | |
| A0658A | 40 UPS12-490MR | 0 | $ - 0 | $0.00 | |
| A0659A | 40 UPS12-600MR | 0 | $ - 0 | $0.00 | |
| A0660A | 450kW w/ 192 MS Endure II AT-23P | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0600 | $0.00 |
| CLIN | VRLA DCBUS | ||||
| A0701A | 24VDC GNB Absolyte GP 24 Volt 50G05 | 0 | $ - 0 | $0.00 | |
| A0702A | 24VDC GNB Absolyte GP 24 Volt 50G07 | 0 | $ - 0 | $0.00 | |
| A0703A | 24VDC GNB Absolyte GP 24 Volt 50G09 | 0 | $ - 0 | $0.00 | |
| A0704A | 24VDC GNB Absolyte GP 24 Volt 50G13 | 0 | $ - 0 | $0.00 | |
| A0705A | 24VDC GNB Absolyte GP 24 Volt 90G07 | 0 | $ - 0 | $0.00 | |
| A0706A | 24VDC GNB Absolyte GP 24 Volt 90G09 | 0 | $ - 0 | $0.00 | |
| A0707A | 24VDC GNB Absolyte GP 24 Volt 90G11 | 0 | $ - 0 | $0.00 | |
| A0708A | 24VDC GNB Absolyte GP 24 Volt 90G13 | 0 | $ - 0 | $0.00 | |
| A0709A | 24VDC GNB Absolyte GP 24 Volt 90G15 | 0 | $ - 0 | $0.00 | |
| A0710A | 24VDC GNB Absolyte GP 24 Volt 100G13 | 0 | $ - 0 | $0.00 | |
| A0711A | 24VDC GNB Absolyte GP 24 Volt 100G15 | 0 | $ - 0 | $0.00 | |
| A0712A | 24VDC GNB Absolyte GP 24 Volt 100G17 | 0 | $ - 0 | $0.00 | |
| A0713A | 24VDC GNB Absolyte GP 24 Volt 100G19 | 0 | $ - 0 | $0.00 | |
| A0714A | 24VDC GNB Absolyte GP 24 Volt 100G21 | 0 | $ - 0 | $0.00 | |
| A0715A | 24VDC GNB Absolyte GP 24 Volt 100G23 | 0 | $ - 0 | $0.00 | |
| A0716A | 24VDC GNB Absolyte GP 24 Volt 100G25 | 0 | $ - 0 | $0.00 | |
| A0717A | 24VDC GNB Absolyte GP 24 Volt 100G27 | 0 | $ - 0 | $0.00 | |
| A0718A | 24VDC GNB Absolyte GP 24 Volt 100G29 | 0 | $ - 0 | $0.00 | |
| A0719A | 24VDC GNB Absolyte GP 24 Volt 100G31 | 0 | $ - 0 | $0.00 | |
| A0720A | 24VDC GNB Absolyte GP 24 Volt 100G33 | 0 | $ - 0 | $0.00 | |
| A0721A | 24VDC GNB Absolyte GP 24 Volt 100G39 | 0 | $ - 0 | $0.00 | |
| A0722A | 24VDC GNB Absolyte GP 24 Volt 100G45 | 0 | $ - 0 | $0.00 | |
| A0723A | 48VDC GNB Absolyte GP 24 Volt 50G05 | 0 | $ - 0 | $0.00 | |
| A0724A | 48VDC GNB Absolyte GP 24 Volt 50G07 | 0 | $ - 0 | $0.00 | |
| A0725A | 48VDC GNB Absolyte GP 24 Volt 50G09 | 0 | $ - 0 | $0.00 | |
| A0726A | 48VDC GNB Absolyte GP 24 Volt 50G13 | 0 | $ - 0 | $0.00 | |
| A0727A | 48VDC GNB Absolyte GP 24 Volt 90G07 | 0 | $ - 0 | $0.00 | |
| A0728A | 48VDC GNB Absolyte GP 24 Volt 90G09 | 0 | $ - 0 | $0.00 | |
| A0729A | 48VDC GNB Absolyte GP 24 Volt 90G11 | 0 | $ - 0 | $0.00 | |
| A0730A | 48VDC GNB Absolyte GP 24 Volt 90G13 | 0 | $ - 0 | $0.00 | |
| A0731A | 48VDC GNB Absolyte GP 24 Volt 90G15 | 0 | $ - 0 | $0.00 | |
| A0732A | 48VDC GNB Absolyte GP 24 Volt 100G13 | 0 | $ - 0 | $0.00 | |
| A0733A | 48VDC GNB Absolyte GP 24 Volt 100G15 | 0 | $ - 0 | $0.00 | |
| A0734A | 48VDC GNB Absolyte GP 24 Volt 100G17 | 0 | $ - 0 | $0.00 | |
| A0735A | 48VDC GNB Absolyte GP 24 Volt 100G19 | 0 | $ - 0 | $0.00 | |
| A0736A | 48VDC GNB Absolyte GP 24 Volt 100G21 | 0 | $ - 0 | $0.00 | |
| A0737A | 48VDC GNB Absolyte GP 24 Volt 100G23 | 0 | $ - 0 | $0.00 | |
| A0738A | 48VDC GNB Absolyte GP 24 Volt 100G25 | 0 | $ - 0 | $0.00 | |
| A0739A | 48VDC GNB Absolyte GP 24 Volt 100G27 | 0 | $ - 0 | $0.00 | |
| A0740A | 48VDC GNB Absolyte GP 24 Volt 100G29 | 0 | $ - 0 | $0.00 | |
| A0741A | 48VDC GNB Absolyte GP 24 Volt 100G31 | 0 | $ - 0 | $0.00 | |
| A0742A | 48VDC GNB Absolyte GP 24 Volt 100G33 | 0 | $ - 0 | $0.00 | |
| A0743A | 48VDC GNB Absolyte GP 24 Volt 100G39 | 0 | $ - 0 | $0.00 | |
| A0744A | 48VDC GNB Absolyte GP 24 Volt 100G45 | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0700 | $0.00 |
| CLIN | VRLA Control Power | ||||
| A0801A | ACEPS 48VDC Control Power DDm 50-13 | 0 | $ - 0 | $0.00 | |
| A0802A | ACEPS 48VDC Control Power DDm 50-17 | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0800 | $0.00 |
| CLIN | SECL | ||||
| A0901A | Battery Lift | 0 | $ - 0 | $0.00 | |
| A0902A | Spill Kit Base for < 2 gallons | 0 | $ - 0 | $0.00 | |
| A0903A | Spill Kit Base for 2+ gallons | 0 | $ - 0 | $0.00 | |
| A0904A | Eyewash 1 Gallon | 0 | $ - 0 | $0.00 | |
| A0905A | Eyewash 15 minute | 0 | $ - 0 | $0.00 | |
| A0906A | Flex Bus Bars 50 - 300A, 360VDC | 0 | $ - 0 | $0.00 | |
| A0907A | Flex Bus Bars 350 - 600A, 360VDC | 0 | $ - 0 | $0.00 | |
| A0908A | Flex Bus Bars 50 - 300A, 384VDC | 0 | $ - 0 | $0.00 | |
| A0909A | Flex Bus Bars 350 - 600A, 384VDC | 0 | $ - 0 | $0.00 | |
| A0910A | Flex Bus Bars 50 - 300A, 432VDC | 0 | $ - 0 | $0.00 | |
| A0911A | Flex Bus Bars 350 - 600A, 432VDC | 0 | $ - 0 | $0.00 | |
| A0912A | Flex Bus Bars 50 - 300A, 480VDC | 0 | $ - 0 | $0.00 | |
| A0913A | Flex Bus Bars 350 - 600A, 480VDC | 0 | $ - 0 | $0.00 | |
| A0914A | Front-Access Kit Black 150Ah/550W-100Ah/350W, 360-384V | 0 | $ - 0 | $0.00 | |
| A0915A | Front-Access Kit Beige 150Ah/550W-100Ah/350W, 360-384V | 0 | $ - 0 | $0.00 | |
| A0916A | Front-Access Kit Black 150Ah/550W-100Ah/350W, 432-480V | 0 | $ - 0 | $0.00 | |
| A0917A | Front-Access Kit Beige 150Ah/550W-100Ah/350W, 432-480V | 0 | $ - 0 | $0.00 | |
| A0918A | Front-Access Kit Black 100Ah/350W-150Ah/550W, 360-384V | 0 | $ - 0 | $0.00 | |
| A0919A | Front-Access Kit Beige 100Ah/350W-150Ah/550W, 360-384V | 0 | $ - 0 | $0.00 | |
| A0920A | Front-Access Kit Black 100Ah/350W-150Ah/550W, 432-480V | 0 | $ - 0 | $0.00 | |
| A0921A | Front-Access Kit Beige 100Ah/350W-150Ah/550W, 432-480V | 0 | $ - 0 | $0.00 | |
| A0922A | Disconnect Side-Mount Enclosure | 0 | $ - 0 | $0.00 | |
| A0923A | ABM 360 - 480V Monitor | 0 | $ - 0 | $0.00 | |
| A0924A | ABM 360 - 480V Additional Monitor Unit | 0 | $ - 0 | $0.00 | |
| A0925A | ABM 360 - 480V Temp. Sensor | 0 | $ - 0 | $0.00 | |
| A0926A | ABM 360 - 480V CT | 0 | $ - 0 | $0.00 | |
| A0927A | ABM 360 - 480V Laptop | 0 | $ - 0 | $0.00 | |
| A0928A | ABM 360 - 480V Laptop Workstation | 0 | $ - 0 | $0.00 | |
| A0929A | ABM 360 - 480V Laptop Lock | 0 | $ - 0 | $0.00 | |
| A0930A | ABM 360 - 480V Mini-UPS APC | 0 | $ - 0 | $0.00 | |
| A0931A | ABM 360 - 480V Mini-UPS Eaton | 0 | $ - 0 | $0.00 | |
| A0932A | ABM 360 - 480V 30 Mod Harness | 0 | $ - 0 | $0.00 | |
| A0933A | ABM 360 - 480V 32 Mod Harness | 0 | $ - 0 | $0.00 | |
| A0934A | ABM 360 - 480V 36 Mod Harness | 0 | $ - 0 | $0.00 | |
| A0935A | ABM 360 - 480V 40 Mod Harness | 0 | $ - 0 | $0.00 | |
| A0936A | ABM 24 & 48V Monitor | 0 | $ - 0 | $0.00 | |
| A0937A | ABM 24 & 48V Additional Monitor Unit | 0 | $ - 0 | $0.00 | |
| A0938A | ABM 24 & 48V Software Xplorer Enterprise | 0 | $ - 0 | $0.00 | |
| A0939A | ABM 24 & 48V Installation Kit | 0 | $ - 0 | $0.00 | |
| A0940A | ABM 24 & 48V Temperature Sensor Ambient | 0 | $ - 0 | $0.00 | |
| A0941A | ABM 24 & 48V Temperature Sensor Each Negative Cell | 0 | $ - 0 | $0.00 | |
| A0942A | ABM 24 & 48V Laptop | 0 | $ - 0 | $0.00 | |
| A0943A | ABM 24 & 48V Laptop Lockbox | 0 | $ - 0 | $0.00 | |
| A0944A | ABM 24 & 48V 12 Cell Harness | 0 | $ - 0 | $0.00 | |
| A0945A | ABM 24 & 48V 18 Cell Harness | 0 | $ - 0 | $0.00 | |
| A0946A | ABM 24 & 48V 24 Cell Harness | 0 | $ - 0 | $0.00 | |
| ITEM TOTAL ENTRY FOR CLIN 0900 | $0.00 |
&14(project title, location)&"Arial,Bold" PROJECT COST ESTIMATE
Date: Page &P of &N 09-21-16
RR BMS
| REMOVE & REPLACE EXISTING BATTERY MONITORING SYSTEM |
| The contractor will remove existing battery monitoring system, add dual tab washers as required by the BDS-40 |
| systems per drawing and properly torque all battery terminal connections. |
| The contractor will mount the BDS-40 on top of the battery rack. No connections will be made to the BDS-40 by the |
| contractor. |
| The contractor will verify a single wall outlet 120VAC 20A circuit for the Eaton single-phase UPS is available. The |
| single-phase UPS will power the BDS-40. |
| The contractor will install a ¾-inch conduit from the UPS to the BDS-40 for the contact circuit. (FOR EATON UPS ONLY) |
| The contractor shall install a #18 twisted shielded pair between the UPS CSB mini-connector terminals 7 and 8 (FOR EATON UPS ONLY) |
| (building Alarm 6) and the BDS-40 (see attached wiring diagram). Leave the BDS-40 end unterminated but with sufficient (FOR EATON UPS ONLY) |
| length to reach the BDS-40 alarm terminals (see attached BDS-40 Terminal location diagram). |
| The contractor will mount the GFE locking cabinet for the BDS-40 laptop to the wall in a location convenient to the |
| BDS-40 (see site design drawing for location). If a 120V wall outlet is not available, the contractor is required to |
| install the outlet. |
| The contractor will install the single-phase UPS to a 120V wall outlet. |
| The installation of the BDS-40 may be accomplished by the contractor if the contractor has previous experience with |
| the Alber BDS-40. |
| Alber will install the BDS-40, calibrate, and commission it per Alber factory procedures. See attached Alber report FAA |
| required system settings. |
| Alber will program NO critical alarm contacts to close on detection of a critical battery failure. |
| Alber will provide a one-day on-site training seminar to site personnel. |
| An Eaton UPS CSE will program the UPS Building alarm contacts #6 to monitor the BDS-40 Alarm contacts. (FOR EATON UPS ONLY) |
R&R BMS
| REMOVE & REPLACE EXISTING BATTERY MONITORING SYSTEM |
| The contractor will remove existing battery monitoring system, add dual tab washers as required by the BDS-40 |
| systems per drawing and properly torque all battery terminal connections. |
| The contractor will mount the BDS-40 on top of the battery rack. No connections will be made to the BDS-40 by the |
| contractor. |
| The contractor will verify a single wall outlet 120VAC 20A circuit for the Eaton single-phase UPS is available. The |
| single-phase UPS will power the BDS-40. |
| The contractor will install a ¾-inch conduit from the UPS to the BDS-40 for the contact circuit. (FOR EATON UPS ONLY) |
| The contractor shall install a #18 twisted shielded pair between the UPS CSB mini-connector terminals 7 and 8 (FOR EATON UPS ONLY) |
| (building Alarm 6) and the BDS-40 (see attached wiring diagram). Leave the BDS-40 end unterminated but with sufficient (FOR EATON UPS ONLY) |
| length to reach the BDS-40 alarm terminals (see attached BDS-40 Terminal location diagram). |
| The contractor will mount the GFE locking cabinet for the BDS-40 laptop to the wall in a location convenient to the |
| BDS-40 (see site design drawing for location). If a 120V wall outlet is not available, the contractor is required to |
| install the outlet. |
| The contractor will install the single-phase UPS to a 120V wall outlet. |
| The installation of the BDS-40 may be accomplished by the contractor if the contractor has previous experience with |
| the Alber BDS-40. |
| Alber will install the BDS-40, calibrate, and commission it per Alber factory procedures. See attached Alber report FAA |
| required system settings. |
| Alber will program NO critical alarm contacts to close on detection of a critical battery failure. |
| Alber will provide a one-day on-site training seminar to site personnel. |
| An Eaton UPS CSE will program the UPS Building alarm contacts #6 to monitor the BDS-40 Alarm contacts. (FOR EATON UPS ONLY) |
Battery Replacement Form Battery Replacement Form
Microsoft_Word_Document1.docx Arc Flash and Shock Hazard
Appropriate PPE Required
ARC FLASH HAZARD
Category 0
36 inches
PPE Category
Arc Flash Boundary
This label is not applicable to service entrance equipment.
SHOCK HAZARD
DC, < 100V
Not Specified
Not Specified
Nominal Voltage
Glove Class
Limited Approach
Restricted Approach
Part No. 5462-15-LMC05
DC, < 100V
Equipment ID:
WARNING