Daytona_Beach_Lift_Station_53_100p_Drawings_8-22-25_(1).pdf
PDF 14 MB Posted
- Attached to
- 2603ITB - Lift Station #53 Improvements
- Solicitation number
- 2603ITB
- Issued by
- Volusia County, Florida
About this file
This is a construction design document package for the City of Daytona Beach Lift Station #53 Replacement project located at 1317 Avenue D in Ormond Beach, Florida. The project involves complete demolition and reconstruction of an existing wastewater lift station with installation of two Flygt submersible pumps, an 8.0-foot diameter concrete wet well, and approximately 19,500 linear feet of new 6-inch PVC and 8-inch HDPE force main piping across four roadways (Avenue D, Pine Drive, Avenue C, and Palm Street). The drawings are preliminary 100 percent design documents dated August 2025 prepared by Halff Associates (engineer), Wekiva Engineering (structural), and Electrical Design Associates (electrical). Site improvements include roadway restoration per Volusia County standards, retaining wall construction with guard rails, grading and drainage work, and environmental controls including silt fencing and erosion protection measures. The non-mandatory pre-bid conference is scheduled for December 19, 2025, with a question submission deadline of January 8, 2026, and bid proposals due January 15, 2026, at 2:00 p.m. through the City's OpenGov procurement platform. The contract term is three years from City Commission approval with options to renew for two additional one-year terms.
The project requires contractors to hold an active Florida General Contractor license with a minimum of five years of experience and comply with comprehensive specifications including bypass pumping operations to maintain continuous lift station service during construction, FDEP permit requirements, and detailed construction documentation and testing. Bidders must provide a 10 percent bid bond with performance and payment bonds required if the contract exceeds $100,000. The solicitation specifies local vendor preference evaluation, with non-local vendors subject to best and final offer requirements if within 10 percent of the lowest local bid. The project requires integration with existing wastewater infrastructure and adherence to Volusia County development standards, Florida Department of Transportation specifications, and Florida Department of Environmental Protection regulations, with coordination required for utility locating, traffic control, maintenance of traffic plans, and inspections by county development engineering. No specific budget is disclosed in the available documents.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
V I C I N I T Y M A P
NOT TO SCALE
S
EW
N
A U
G U
S T
0% P
R E
LI
M
IN
A
R Y
S E
T (N
O T
FO
R
C O
N S
TR
U
C
TI
O N
PROJECT AREA
MAYOR
DISTRICT 5
DANNETTE HENRY
DISTRICT 6
PAULA R. REED
DISTRICT 2
DISTRICT 4
DERRICK L. HENRY
KEN STRICKLAND
STACY CANTU
DISTRICT 1
DISTRICT 3
MONICA PARIS
QUANITA MAY
OWNER/DEVELOPER:
ENGINEER/SURVEYOR:
ELECTRICAL:
Call 811 or www.sunshine 811.com two full business days before digging to have utilities located and marked.
Check positive response codes before you dig!
CITY OF DAYTONA BEACH
125 BASIN STREET, SUITE 204
DAYTONA BEACH, FL 32114
SHANNON PONITZ, UTILITIES DIRECTOR
(386) 671-8824
PONITZSHANNON@CODB.US
UTILITIES DIRECTOR
SHANNON PONITZ
CITY CLERK
LETITIA LAMAGNA
CITY MANAGER
DERIC C. FEACHER
HALFF ASSOCIATES, INC.
902 N SINCLAIR AVENUE
TAVARES, FL 32778
ROBERT A. ERN, PE
(352) 343-8481
RERN@HALFF.COM
FOR
CONSTRUCTION PLANS
LIFT STATION 53
REPLACEMENT
SECTION 29 TOWNSHIP 14S RANGE 32E
INDEX OF SHEETS
01 COVER SHEET
G-1 KEY MAP
G-2 GENERAL NOTES
G-3-5 DETAILS
C-1 EXISTING LIFT STATION DEMOLITION
C-2 PROPOSED LIFT STATION SITE PLAN
C-3 GRADING PLAN
C-4 MANHOLE CONVERSION
C-5 FORCE MAIN PLAN VIEW
C-6 FORCE MAIN PLAN VIEW
C-7 FORCE MAIN PROFILE VIEW AND MISC. CROSS SECTIONS
M-1 LIFT STATION PLAN VIEW
M-2 LIFT STATION SECTION VIEW
S-01 STRUCTURAL NOTES, ABB., AND SYMBOLS
S-02 LIFT STATION STRUCTURAL PLAN, SECTION
S-03 CIP RETAINING WALL PLAN AND DETAIL
S-04 STRUCTURAL DETAILS
E-1 ELECTRICAL NOTES, SYMBOLS & ABBREVIATIONS
E-2 LIFT STATION 53 ELECTRICAL DEMOLITION PLAN
E-3 LIFT STATION 53 ELECTRICAL SITE PLAN
E-4 SINGLE LINE DIAGRAM
E-5 EQUIPMENT RACK ELEVATION
E-6 LIFT STATION 53 ELECTRICAL PLAN
E-7 ELECTRICAL DETAILS 1
E-8 ELECTRICAL DETAILS 2
0 1 2 3 4 5
(INCHES)
ORIGINAL DOCUMENT SIZE 24"x36"
902 North Sinclair Ave.
Certificate of Authorization Number: 33380
Fax: 352.343.8495 Office: 352.343.8481
Tavares, Florida 32778
STRUCTURAL:
WEKIVA ENGINEERING
1320 WILFRED DRIVE
ORLANDO, FL 32803
DAVID MORRIS, PE
(407) 219-4454
DAVID@WEKIVAENGINEERING.COM
ELECTRICAL DESIGN ASSOCIATES
6965 PIAZZA GRANDE AVE, SUITE 311
ORLANDO, FL 32835
MICHAEL CAHILL, PE
(407) 745-6504
MCAHILL@GOEDA.COM
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
N o rt h
S in cl ai r A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
K E
Y M
A P
044787.001 FM &
BORE PROFILES.DWG
SHEET C-5 PANEL A
S H
E E
T C
-5 P
A N
E L
B
SHEET C-5 PANEL C SHEET C-6 PANEL A
SHEET C-6 PANEL B
SHEET C-6 PANEL C
060 60 120
LIFT STATION SITE
(SEE SHEET C-2)
SITE ADDRESS:
1317 AVENUE D
ORMOND BEACH
FL 32174
S H
E E
T C
-2
AVENUE D
AVENUE E
P
IN
E D
R
AVENUE B
AVENUE C
P A
LM
S
T
FLEMING AVE
JE
R
O M
E B
LVD
Sheet G-1
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
AUGUST 2025
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
P R
O
JE
C T
N O
. 6
TEM
CLM
RAE
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
ROBERT A. ERN, PE
Registered Eng 54013
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
Sheet G-2
G E
N E
R A
L N
O
TE
S
UTILITY CONSTRUCTION NOTES (DEP):
044787.001 Lift Station
53 - Construction Plan
NOTE:
CONTRACTOR TO FIELD LOCATE EXISTING UTILITIES PRIOR TO CONSTRUCTION.
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
AUGUST 2025
1. NOTIFY VOLUSIA COUNTY DEVELOPMENT ENGINEERING DIVISION AT (386) 736-5926 A MINIMUM OF 24 HOURS PRIOR TO THE START OF CONSTRUCTION. FAILURE OF THE PERMITTEE TO OBTAIN THE APPROPRIATE INSPECTIONS PRIOR TO PROCEEDING WITH WORK SHALL NOT RELIEVE THE PERMITEE FROM REEXCAVATION OR OTHER MEASURES NECESSARY FOR THE INSPECTION OF
WORK.
2. VOLUSIA COUNTY TRAFFIC ENGINEERING (386) 736-5968 IS NOT A MEMBER OF SUNSHINE ONE CALL. PLEASE CONTACT VCTE AT (386) 736-5968 A MINIMUM OF TWO (2) BUSINESS DAYS PRIOR TO
THE BEGINNING OF THE PROPOSED WORK TO REQUEST LOCATES.
3. COORDINATION WITH VOLUSIA COUNTY ENGINEERING'S INSPECTOR JIM PRICE AT (386) 561-8666 IS REQUIRED WITH A MINIMUM ADVANCED NOTICE OF SEVEN (7) DAYS PRIOR TO ANY SIDEWALK, LANE OR ROAD CLOSURE (INCLUDING FLAGGING OPERATIONS).
4. OPERATIONS WITHIN THE COUNTY RIGHT-OF-WAY SHALL NORMALLY BE CONDUCTED 7:00 A.M. TO 7:00 P.M., MONDAY THROUGH FRIDAY. ANY DEVIATION FROM THESE HOURS REQUIRES PRIOR APPROVAL FROM THE COUNTY DEVELOPMENT ENGINEER. EMERGENCY REPAIRS ARE EXCLUDED FROM THIS TIME RESTRICTION.
5. ALL EXISTING SIDEWALKS WITHIN COUNTY RIGHT-OF-WAY SHALL EITHER REMAIN OPEN OR BE PROVIDED A TEMPORARY WALKWAY IN ACCORDANCE WITH THE CURRENT VERSION OF FLORIDA DEPARTMENT OF TRANSPORTATION STANDARD INDEX NO. 660. ANY DAMAGE TO SIDEWALKS SHALL BE REPAIRED AND/OR REPLACED IN LIKE KIND BY THE CONTRACTOR. NEW SIDEWALKS AND SECTIONS THROUGH DRIVEWAYS MUST BE AT A 1.5% CROSS SLOPE AND 2% MAXIMUM CROSS SLOPE PER ADA STANDARDS.
6. DRIVING OR STAGING OF CONSTRUCTION VEHICLES OR MATERIALS IS NOT PERMITTED WITHIN THE COUNTY RIGHT-OF-WAY OR ON PEDESTRIAN WALKWAYS AND PATHS. THERE SHALL BE NO OVERNIGHT CONSTRUCTION VEHICLE RELATED PARKING, CONSTRUCTION MATERIAL PLACEMENT OR STORAGE OF ANY KIND PERMITTED WITHIN THE COUNTY RIGHT-OF-WAY.
7. NO TRENCH OR EXCAVATION SHALL BE LEFT OPEN OR UNATTENDED OVERNIGHT, UNLESS APPROVED BY THE COUNTY DEVELOPMENT ENGINEERING INSPECTOR. EXCAVATIONS SHALL MEET THE DROP OFF PROTECTION REQUIREMENTS OF THE LATEST FDOT DESIGN STANDARD INDEX NO. 600.
8. RESTORATION SHALL BE REQUIRED FOR ANY DAMAGE TO SIDEWALKS, CURBS, OR OTHER EXISTING STRUCTURES IN THE RIGHT-OF-WAY. ALL DISTURBED AREAS WITHIN THE COUNTY RIGHT-OF-WAY SHALL BE RE-GRADED AND SODDED. SEED AND MULCH IS NOT AN ACCEPTABLE ALTERNATIVE TO SODDING.
9. CONTRACTOR SHALL PROVIDE TO VOLUSIA COUNTY, PRIOR TO COMMENCING CONSTRUCTION, FOR APPROVAL, A MAINTENANCE OF TRAFFIC PLAN THAT MEETS OR EXCEEDS THE REQUIREMENTS OF THE FDOT STANDARD PLANS FOR ROAD AND BRIDGE CONSTRUCTION 102-600 INDEX SERIES.
10. ANY DAMAGE CAUSED TO EXISTING COUNTY TRAFFIC SIGNALS OR RELATED SIGNAL APPURTENANCES (DETECTION, FIBER, ETC.) WILL BE REPLACED IN KIND AT THE CONTRACTOR'S EXPENSE.
11. UNINTENTIONAL IMPACTS TO THE ITS NETWORK (COUNTY MAINTAINED FIBER) RESULTING IN A LOSS OF COMMUNICATION SHALL BE REPORTED IMMEDIATELY TO VOLUSIA COUNTY TRAFFIC ENGINEERING. THE AFFECTED DEVICES OR NETWORK SHALL BE RESTORED WITHIN 24 HOURS OF THE INITIAL BREAK.
12. THE APPLICANT AND/OR CONTRACTOR IS RESPONSIBLE FOR PROVIDING PRE/POST CONSTRUCTION VIDEOS, PHOTOS, ETC. OF THE WORK SITE.
13. THE APPLICANT AND/OR CONTRACTOR IS RESPONSIBLE FOR SURVEY ACCURACY OF ALL WORK PERFORMED WITHIN THE VOLUSIA COUNTY RIGHTS-OF-WAY; INCLUDING BUT NOT LIMITED TO, ANY PROPOSED OR EXISTING STRUCTURES.
14. DIRECTIONAL BORES, ROAD CUTS, AND PAVING OPERATIONS SHALL NOT BE PERFORMED WITHIN THE VOLUSIA COUNTY RIGHT-OF-WAY ON FRIDAY, SATURDAY, SUNDAY OR ANY DAY PRIOR TO
A HOLIDAT WITHOUT WRITTEN CDE/INSPECTOR APPROVAL.
15. THE VOLUSIA COUNTY STAMPED APPROVED PLANS AND PERMIT PLACARD MUST ALWAYS BE ONSITE.
16. ALL ASPHALT MIX DESIGNS MUST BE PRE-APPROVED BY VOLUSIA COUNTY BEFORE PLACEMENT.
17. PRIOR TO BEGINNING CONSTRUCTION, CONTRACTOR SHALL PROVIDE A DETAILED SEQUENCE OF CONSTRUCTION SCHEDULE AND MAINTENANCE OF TRAFFIC PLAN, SIGNED AND SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA.
18. ALL ASPHALT JOINTS WILL BE SAW CUT.
19. ROADWAYS SHALL BE MILLED AND REPAVED 50-FEET IN EACH DIRECTION FROM THE EDGE OF AN OPEN CUT.
VOLUSIA COUNTY CONSTRUCTION NOTES
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
Sheet G-3
D
ET
AI
LS
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
AUGUST 2025
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
Sheet G-4
D
ET
AI
LS
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
AUGUST 2025
70'
12' 12' **6'**6'
6"
35' R/W 35' R/W
6"
.05 FT/FT .02 FT/FT .02 FT/FT .05 FT/FT
*4' *4'
2' SOD 2' SOD
DITCH SLOPES AND
DEPTH VARIES
MAX 4:1
SEED & MULCH
VOLUSIA COUNTY TWO-LANE LOCAL STREET,
NOT TO SCALE
**8' for 750 ADT and Above
RURAL TYPICAL SECTION DETAIL
NOTE:
1. RECONSTRUCTION OF COUNTY ROADWAYS SHALL MEET VOLUSIA COUNTY LAND DEVELOPMENT
CODE SECTION 72-612.
2. STABILIZED SUB-GRADE TO A LBR 40 AND COMPACTED TO A 98% MAXIMUM DRY DENSITY PER
AASHTO T-180 IN ONE LIFT, "OR" IN LIEU OF STABILIZATION UTILIZE 12 PLAN THICKNESS OF STABILIZATION W/ SAME BASE MATERIALS USED, "BASE & A HALF", TO BE PLACED IN 2 LIFTS, COMPACTED TO 98% OF A T-180
12" STABILIZED SUB-GRADE
8" CRUSHED CONCRETE BASE,
COMPACTED 98 % MAX.
DENSITY (TYP.)
1-1/2" TYPE S.P. - 12.5
TL-C/TL-D ASPHALT @ MAX.
30% RECYCLED MATERIALS
ASPHALT PAVING DETAIL
NOT TO SCALE
12" STABILIZED SUB-GRADE
8" CRUSHED CONCRETE BASE,
COMPACTED 98 % MAX.
DENSITY (TYP.)
1-1/2" TYPE S.P. - 12.5
TL-C/TL-D ASPHALT @ MAX.
30% RECYCLED MATERIALS
NOTE:
1. STABILIZED SUB-GRADE TO A LBR 40 AND COMPACTED TO A
98% MAXIMUM DRY DENSITY PER AASHTO T-180 IN ONE LIFT,
"OR" IN LIEU OF STABILIZATION UTILIZE 12 PLAN THICKNESS OF
STABILIZATION W/ SAME BASE MATERIALS USED, "BASE & A
HALF", TO BE PLACED IN 2 LIFTS, COMPACTED TO 98% OF A
T-180
NOT TO SCALE
VOLUSIA COUNTY STREET SECTION DETAIL W/ DROP CURB
13'10'10'13'
25'25'
R/WR/W
1' (TYP)
CL
2' 2'
2% SLOPE2% SLOPE
2 ' DROP CURB
PER FDOT STD.
PLANS 520-001
1 1/2" SP 12.5
12" STABILIZED SUB-GRADE
8" CRUSHED CONCRETE
BASE, COMPACTED 98 % MAX.
DENSITY (TYP.)
1-1/2" TYPE S.P. - 12.5
TL-C/TL-D ASPHALT @ MAX. 30%
RECYCLED MATERIALS
NOTE:
1. STABILIZED SUB-GRADE TO A LBR 40 AND COMPACTED TO A 98% MAXIMUM DRY DENSITY PER
AASHTO T-180 IN ONE LIFT, "OR" IN LIEU OF STABILIZATION UTILIZE 12 PLAN THICKNESS OF STABILIZATION W/ SAME BASE MATERIALS USED, "BASE & A HALF", TO BE PLACED IN 2 LIFTS, COMPACTED TO 98% OF A T-180
NOTE:
OPEN CUT AND REPAIR OF FOUR VOLUSIA
COUNTY ROADWAYS IS PROPOSED:
- AVENUE D
- PINE DRIVE
- AVENUE C
- PALM STREET
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
NOT TO SCALE
CHAIN LINK FENCE DETAIL
12"
36"
FENCE DETAIL
10'-0" TO CENTER (MAX)
DOUBLE SWING GATE DETAIL
6"
6' -0
12" 6"
2"
6" 12"
6"
36"
12"
THRUST RESTRAINT DESIGN NOTES
3'
4'
2'
6'
5'
4'
TABLE OF THRUST RESTRAINT LENGTHS
P.V.C. (L)
16'
51'
22'
40'
29'
34'
DUCTILE
IRON (L)
28'
36'
50'
63'
43'
P.V.C. (L)
PIPE
(inches)
SIZE
90°
BEND
20'
9'12'
15'
21'
26'
18'
12'
17'
21'
14'
P.V.C. (L)
8'
BEND
45°
7'
IRON (L)
DUCTILE
4'6'
7'
10'
13'
9'
6'
8'
10'
7'
22 1/2°
IRON (L)
DUCTILE
BEND
P.V.C. (L)
4' 3'
90° BEND
22.5° BEND
L
L
L
L
REDUCER
DEAD END/PLUG
SMALLER MAIN
L
LARGER MAIN
L
ON LARGER MAIN
RESTRAINT REQ.
ONLY
40'
94'
74'
63'
52'
IRON (L)
DUCTILE
29'
TEES
33'2'
3'
5'
4'
3'
52'
116'
84'
68'
IRON (L)
DUCTILE
11 1/4"
BEND
2' 15'
P.V.C. (L)
63'21'
33'
54'
74'
43'
82'
148'
116'
98'
P.V.C. (L)IRON (L)
DUCTILE
10'
PLUG
DEAD END &
45'
34'8"x6"
10"x8"
16"x12"
12"x10"
33'
63'
34'
PIPE SIZES
6"x4"
REDUCER
P.V.C. (L)
33'
22'
21'
40'
22'
IRON (L)
DUCTILE
21'
TEE
11.25° BEND
45° BEND
L
L
L
L
@ ALL SIDES (TYP.)
B R
A N
C H
RESTRAINTS REQ.
(NO JOINTS ALLOWED)
8' MIN.
RUN
L
8' MIN.
(NO JOINTS ALLOWED)
70, 86'
75'
61'
70'
56'
36'
31'
29'
17'
15'
29'
25'
23'
14'
12'
14' 11' 131'
145'
173'
7'
9'
7'
6'
7'
6'
110'
92'
83'
178'
207'
163' 20"x18"
20"x20"113'
132'
103'
62'
33'
39'
21'
18"x16" 33' 21'
NOT TO SCALE
1. RESTRAINT JOINTS, FITTINGS, & VALVE REQUIREMENTS CALCULATED BY THE
THRUST RESTRAINT DESIGN PROGRAM PROVIDED BY UNI-FLANGE, THE FORD
METER BOX COMPANY, INC.
2. DATA BASED ON MAX. PRESSURE OF 150 P.S.I., THE UNIFIED SOILS
CLASSIFICATION SYSTEM (SOIL TYPE SP), THE PIPE BEDDED IN NATIVE SOIL W/A
MINIMUM OF 2.5' COMPACTED FILL OVER THE PIPE, AND USING A SAFETY
FACTOR OF 1.5 FOR THE DATA.
3. ALL FITTINGS & VALVES SHALL HAVE RESTRAINED JOINTS PER SPECIFICATIONS
& ALL BELL & SPIGOT JOINTS TO BE RESTRAINED WITH A RESTRAINING HARNESS
WITHIN THE REQUIRED LENGTH OF RESTRAINED PIPE (L).
4. THRUST BLOCKS SHALL BE USED ONLY AS SPECIFIED BY PROJECT ENGINEER.
SOIL
UNDISTURBED
(6"MIN.)
CONCRETE
(4"MIN.)
(4"MIN.)
(SEE NOTE 1)
BACKFILL
COMPACTED
SELECT MATERIAL
COMPACTED
BEDDING MATERIAL
COMPACTED GRANULAR
(4"MIN.)
CONCRETE
(6"MIN.)
Bc
Bc
Bc
Bc
Bc
Bc
Bc
Bc
" M
IN
IM
U M
Bd
SPECIAL CONDITIONS
CLASS "A" BEDDING
MATERIAL
BEDDING
GRANULAR
COMPACTED
A S
P O
S S
IB
LE
TO
B
E A
S V
E R
TI
C
A L
TR
E
N C
H W
A
LL
S
" M
IN
IM
U M
TR
E
N C
H W
A
LL
S V
E R
TI
C
A L
UNDISTURBED SOIL
0.5 Bc (TOTAL)
NORMAL TRENCH GRANULAR BEDDING
SEE
NOTE 2
Bc
Bc
BACKFILL
COMPACTED
SELECT MATERIAL
COMPACTED
Bd
(SEE NOTE 1)
CLASS "B" BEDDING
NORMAL CONDITIONS
NOTES: FOR BEDDING AND TRENCHING
T-180) top of backfill - 90% of modified proctor maximum dry density (AASHTO maximum dry density (AASHTO T-180). From 12" above top of pipe to bottom of trench to 12" above top of pipe - 95% of modified proctor material under all other areas shall be compacted as follows: From dirt drives), and parking areas shall be compacted to 98% of the modi-
3. All backfill and select material under all roadways, drives (including shall be 6" below bottom of utility.
suitable foundation. For rock or other non-cushioning material, depth
2. Depth for removal for unsuitable material shall be as required to reach
Minimum Bd = Maximum Dimension of Bell + 8" (Unsheeted Trench) Maximum Bd = Bc + 30" Dimension Bd = Trench Width at Top of Pipe
1. Dimension Bc = Pipe O.D.
fied proctor maximum dry density. (AASHTO T-180). Backfill and select
NOT TO SCALE
PIPE BEDDING
SANITARY SEWER
BOTTOM
TRENCH
NORMAL
6" IN THICKNESS
NOT EXCEEDING
PLACED IN LIFTS
BACKFILL TO BE
BEDDING AND
SELECTED BACKFILL
HAND PLACED
B A
C K
FI
LL
B E
D D
IN
G
M
IN
4"
"M
IN
IM
U M
12" MAX12" MAX
A.A.S.H.O. T-180 (ASTM D-1557)
DENSITY TO 95% MODIFIED PROCTOR
BEDDING AND BACKFILL COMPACTION
2B c
POST
REINFORCEMENT NETTING
FILTER FABRIC
GRANULAR BACKFILL
NATIVE SOIL
6"x6" TRENCH
BOTTOM 6" OF
FILTER FABRIC
DIRECTION
OF FLOW
NOTES:
1. TEMPORARY EROSION CONTROL STRUCTURE TO BE UTILIZED
DURING CONSTRUCTION AT AREAS DESIGNATED BY ENGINEER
OR AREAS ON-SITE WHERE UNSTABILIZED GRADES MAY CAUSE
EROSION PROBLEMS. EROSION CONTROL STRUCTURE MAY BE
REMOVED AFTER UPSLOPE AREA HAS BEEN STABILIZED BY SOD,
OR COMPACTED AS DETERMINED BY CONTRACTOR.
2. EROSION CONTROL STRUCTURE: WOVEN FILTER FABRIC SILT
FENCE IN ACCORDANCE WITH THE F.D.O.T. STANDARD
SPECIFICATIONS.
3. CONSTRUCT STORMWATER SYSTEMS BEFORE ANY BUILDING OR
ROAD CONSTRUCTION IS STARTED.
a) PROTECT SYSTEM FROM SILTING AND DEBRIS BY METHODS
PROVIDED IN DETAILS.
b) PROTECT SWALE BOTTOM FROM SEALING BY EXCAVATING
ALL SILT DEPOSITS DURING CONSTRUCTION. THIS SHALL BE
DONE BEFORE SOD & SEEDING & MULCHING IS FINISHED.
4. THE CONTRACTOR SHALL APPLY WITH AND OBTAIN NPDES
PERMIT FROM THE FLORIDA DEPT. OF ENVIRONMENTAL
PROTECTION (FDEP).
5. SILT FENCE SHOWN IS STRICTLY SCHEMATIC, FOR ILLUSTRATION
ONLY, ALL FENCE TO BE WITHIN THE PROPERTY LINE OF THE
PROJECT SITE.
THE FOLLOWING LIST REPRESENTS A BASIC EROSION AND SEDIMENT CONTROL PROGRAM WHICH IS TO BE IMPLEMENTED TO HELP PREVENT OFF-SITE SEDIMENTATION DURING AND AFTER CONSTRUCTION OF THE PROJECT.
PERMANENT EROSION AND SEDIMENT CONTROL MEASURES SHALL BE PROPOSEDED AT THE EARLIEST PRACTICAL TIME CONSISTENT WITH GOOD CONSTRUCTION PRACTICES. ONE OF THE FIRST CONSTRUCTION ACTIVITIES SHOULD BE THE PLACEMENT OF PERMANENT AND TEMPORARY EROSION AND SEDIMENT CONTROL MEASURES AROUND THE PERIMETER OF THE PROJECT OR THE INITIAL WORK AREA TO PROTECT THE PROJECT, ADJACENT PROPERTIES AND
WATER RESOURCES.
TEMPORARY EROSION AND SEDIMENT CONTROL MEASURES SHALL BE COORDINATED WITH PERMANENT MEASURES TO ASSURE ECONOMICAL, EFFECTIVE AND CONTINUOUS CONTROL THROUGHOUT THE CONSTRUCTION PHASE.
TEMPORARY MEASURES SHALL NOT BE CONSTRUCTED FOR EXPEDIENCY IN LIEU OF PERMANENT MEASURES.
EROSION AND SEDIMENT CONTROL MEASURES SHALL BE ADEQUATELY MAINTAINED TO PERFORM THEIR INTENDED
FUNCTION DURING CONSTRUCTION OF THE PROJECT.
NECESSARY REPAIRS TO BARRIERS OR REPLACEMENT OF BARRIERS SHALL BE ACCOMPLISHED PROMPTLY.
SEDIMENT DEPOSITS SHOULD BE REMOVED AFTER EACH RAINFALL. THEY MUST BE REMOVED WHEN THE LEVEL OF
DEPOSITION REACHES APPROXIMATELY ONE-HALF THE HEIGHT OF THE BARRIER.
MATERIAL FROM SEDIMENT TRAPS SHALL NOT BE STOCKPILED OR DISPOSED OF IN A MANNER WHICH MAKES THEM READILY SUSCEPTIBLE TO BEING WASHED INTO ANY WATERCOURSE BY RUNOFF OR HIGH WATER.
ANY SEDIMENT DEPOSITS REMAINING IN PLACE AFTER THE BARRIERS ARE NO LONGER REQUIRED SHALL BE
DRESSED TO CONFORM TO THE EXISTING GRADE, PREPARED AND SEEDED.
SILT BARRIER DETAIL
NOT TO SCALE
FILTER SOCKS
(TYP.)
INLET
ELEVATION
INLET PROTECTION DETAIL
SECTION
SILT FENCE DETAIL
SILT FLOW
FILTER FABRIC
PRINCIPLE POST POSITION
(CANTED 20° TOWARD FLOW)
OPTIONAL POST POSITIONS
VERTICAL
20°`
FILTER FABRIC (IN
CONFORMANCE WITH
SEC. 985 FDOT SPEC.)
POST OPTIONS: WOOD 2-1/2" MIN. 0
WOOD 2" x 4" OAK 1-1/2" x 1-1/2"
STEEL 1.33 LBS/FT. MIN.
8"
15" TO 18"
3' OR MORE
6' MAX.
12" MIN.
AREA TO BE PROTECTED
FILTERED
RUN-OFF
SEDIMENT
LADEN RUN-OFF
COMPACTED SOIL
TO PREVENT PIPING UPSLOPE
D
ET
AI
LS
Sheet G-5
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
HOSE BIBB
3/4" WATER SERVICE
3/4" GALV. STEEL PIPE
1 C.F. CONCRETE
w/ END CAP 4"x5' GALV. STEEL PIPE
" M
IN
. CONCRETE
SLAB
PIPE TO POST w/
STAINLESS STEEL
STRAP 1" ALUMINUM
3/4" HOSE BIBB
BANDING STRAP
NOT TO SCALE
AUGUST 2025
THRUST RESTRAINT DETAILS
BEDDING AND TRENCHING DETAILS
CD 12/12/12
ELM 15/12
PP
PP
X X
X X X X X X X X X
X
X
X X
X X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
SS
SS
SS
X
X
X
X
W W
W
W
W
W
W
W
W
W
W W
BEBEBEBE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
W
W
W
W
W W
W W
W W
W W
W W
W W
W
W
W
WWWWWWWWWWWWWWWWWWWWWWWWW
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
WM UW1
152022 19.93
W WSV
W WSV
EX. SANITARY MH
TOP = 20.29'
4" INV (W) = 16.39' (VCP)
4" inv (E) = 16.29' (VCP)
JUNCTION MANHOLE NOT FOUND
PROPERTY NOT ACCESSIBLE
DUE TO TERRITORIAL DOGS AND
NON RESPONSIVE RESIDENTS
EX. WET WELL
TOP = 19.57'
8" INV (NE) = 15.84' (PVC)
8" INV (S) = 12.46' (PVC)
8" INV (NW) = 9.96' (PVC)
BOTTON = 5.36'
4" EMERGENCY
PUMP OUT
POLE W/ELECTRIC METER
ELECTRIC METER
EX. WATER
MAIN
EX. FORCE
MAIN
SET SPKN BASE
PT. EL = 19.30
EXISTING
ABANDONED
WATER
SERVICE
FOUND 5/8" IRON
ROD NO ID
PALM 20"
PALM 18"
15"CMP
15"CMP
15"CMP
15"CMP
15"CMP
15"CMP
CONC.
DWY.
GRAVEL DWY.
DI
RT
D W
Y.
4' CLF
4' VINYL
FENCE
EOP
EOP
" R
CP
RC
P
25.00' 25.00'
N88°58'37"E 454.95' 455.00'(P)
ALT KEY
3116321.0000
ALT KEY
3116313.0000
LO
T
LI
N
E
LO
T
LI
N
E
LO
T
LI
N
E
LO
T
LI
N
E
ASPH
ASPH
MASONRY GATE
COLUMNS
ASPH
ASPH
EX. 15" INV = 19.05'
INV = 17.60'
CATCH BASIN
TOP = 19.51'
N. INV = 17.58'
S. INV = 17.61'
INV = 19.11'
INV = 19.55'
INV = 19.93'
INV = 19.84'
SITE BENCHMARK #301
FOUND SMALL NAIL NO DISK
N= 1790093.35 E = 628944.81
ELEV = 20.43
CATCH BASIN
TOP = 18.85'
W. INV = 17.20'
S. INV = 17.25'
INV = 18.67'
INV = 18.94' INV = 19.38' INV = 19.02'
INV = 19.03'
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
010 10 20
AVENUE D
PROPOSED CONSTRUCTION
ENTRANCE/EXIT
DEMOLISH EXISTING DRIVEWAY
APRON
SILT FENCE
(TYPICAL)
EX. CONCRETE PAD
TO BE DEMOLISHED
(355 SQ FT)
EX. LIFT STATION BUILDING, PUMPS
& PIPING TO BE DEMOLISHED
(SEE SHEET C-6)
EX. GRAVEL DRIVE TO BE
DEMOLISHED
SITE ADDRESS:
1317 AVENUE D
ORMOND BEACH FL 32174
SURVEY PREPARED BY :
SLIGER AND ASSOCIATES, INC
DATED JANUARY 25, 2022
ELEVATIONS REFER TO
NAVD1988 DATUM
REMOVE ABANDONED WATER
SERVICE
NOTES:
1. THE EXISTING LIFT STATION SHALL REMAIN IN SERVICE AT ALL TIMES UNLESS THE
CONTRACTOR HAS IMPLEMENTED BYPASS PUMPING OPERATIONS IN
ACCORDANCE WITH A BYPASS PUMPING PLAN THAT HAS BEEN APPROVED IN
ADVANCE BY THE CITY AND THE ENGINEER. SEE SPECIFICATION SECTION 11312
2. THE WASTEWATER FORCE MAIN SHALL BE CONSTRUCTED AND CLEARED FOR
SERVICE BY FDEP PRIOR TO PLACING THE PROPOSED LIFT STATION INTO SERVICE.
Sheet C-1
D
EM
O
LI
TI
O
N P
LA
N
CUT AND CAP ABANDONED WATER
SERVICE
CUT, CAP AND ABANDON EX. WATER
SERVICE
EX. 8" SANITARY SEWER (NW) TO BE
ABANDONED AND GROUT FILLED
EX. WATER SERVICE TO BE
REMOVED
EX. VALVES AND PUMP OUT
CONNECTION TO BE REMOVED
EX. BURIED ELECTRIC CABLE TO BE
REMOVED
EX. 4" FORCE MAIN TO BE ABANDONED AND
GROUT FILLED
CONTRACTOR SHALL LOCATE THE
CONTINUATION OF EXISTING 4" FORCE MAIN
AND ABANDON IT BY GROUTING UP TO THE
CONNECTION POINT
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
EX. 6" CLAY GRAVITY SEWER TO BE
ABANDONED AND GROUT FILLED
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
TREES TO BE REMOVED (TYP.)
REMOVE EXISTING FENCE
CLF 4
CLF 4
CLF 4
CLF 4
PP
PP
SS
SS
SS
WWWWWWWWWWWWWWWWWWWWWW
WM UW1
152022 19.93
EX. SANITARY MH
TOP = 20.29'
4" INV (W) = 16.39' (VCP)
4" inv (E) = 16.29' (VCP)
JUNCTION MANHOLE NOT FOUND
PROPERTY NOT ACCESSIBLE
DUE TO TERRITORIAL DOGS AND
NON RESPONSIVE RESIDENTS
EX. WET WELL
TOP = 19.57'
8" INV (NE) = 15.84' (PVC)
8" INV (S) = 12.46' (PVC)
8" INV (NW) = 9.96' (PVC)
BOTTON = 5.36'
ELECTRIC METER
FOUND 5/8" IRON
ROD NO ID
XXXXXXXX
X X
X X
X X
X X
X X
X
X X X X X X X X
X
X
X X
X X
X X
X X
X X
PALM 20"
PALM 18"
15"CMP
15"CMP
15"CMP
15"CMP
CONC.
DWY.
DI
RT
D W
Y.
4' CLF
4' VINYL
FENCE
EOP
CROWN
EOP
EOP
15"RCP
" R
CP
RC
P
25.00' 25.00'
N88°58'37"E 454.95' 455.00'(P)
ALT KEY
3116330.0000
ALT KEY
3116321.0000
ALT KEY
3116313.0000
ASPH
ASPH
ASPH
EX. 15" INV = 19.05'
INV = 17.60'
CATCH BASIN
TOP = 19.51'
N. INV = 17.58'
S. INV = 17.61'
INV = 19.11'
INV = 19.55'
INV = 19.93'
INV = 19.84'
SITE BENCHMARK #301
FOUND SMALL NAIL NO DISK
N= 1790093.35 E = 628944.81
ELEV = 20.43
CATCH BASIN
TOP = 18.85'
W. INV = 17.20'
S. INV = 17.25'
INV = 18.67'
INV = 18.94' INV = 19.38' INV = 19.02'
INV = 19.03'
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
G E
N E
R A
TO
R
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
EXISTING GRADE = 20.15'±
PROP. 6" PVC FORCE MAIN
EX. WATER MAIN
(CONTRACTOR TO VERIFY
PIPE SIZE AND ELEVATION)
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
010 10 20
EX. 4.0' WET WELL TO BE REHABILITATED
AND CONVERTED TO A 4.0' MANHOLE.
(SEE SHEET C-4)
PROP. 6" PVC
FORCE MAIN
EOP CONNECT TO EX.
WATER MAIN
PROP. 8.0'
WET WELL
PROP. 3/4" PE
WATER SERVICE
PROPOSED 6" PVC
FORCE MAIN
SEE PLAN SHEET
(SHEET 9)
SEE SHEET C-5
(PLAN SHEET)AVENUE D
PROP. 6' HIGH
CHAIN LINK FENCE
Sheet C-2
SI
TE
P
LA
N
REHABILITATED MANHOLE
EX. TOP = 19.57'
EX. 8" INV (NE) = 15.84' (PVC)
EX. 8" INV (S) = 12.46' (PVC)
EX. 8" INV (NW) = 9.96' (PVC)
PROP. 10" INV (NW) = 9.86' (PVC)
EX. BOTTOM =5.36'
C
C
PROP.RETAINING WALL
w/ 42" GUARD RAILS
20.61 EX. EL.
PROP. 59 LF OF 10"
PVC SANITARY SEWER
@ 0.4% SLOPE
PROP. 59 LF OF 10"
PVC SANITARY SEWER
@ 1% SLOPE
SEE CROSSING
DETAIL A
D
IP
P V
C
EX. METER TO
BE REMOVED
20.00'
15.00'
CONCRETE
DRIVEWAY
PROP.RETAINING WALL
27.50'
27.50'
50.00'
10.00'
50.00'
40.00'
30.00'
5'
49.50'
END RETAINING WALL
END RETAINING WALL
GENERAL NOTES:
(1) CONTRACTOR SHALL REFER TO SPECIFICATION SECTION 11312 FOR BYPASS
PUMPING REQUIREMENTS.
(2) CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS.
(3) THE PROPOSED FORCE MAIN SHALL BE CONSTRUCTED AND PLACED INTO SERVICE
PRIOR TO START-UP OF THE LIFT STATION.
PROP. WATER METER
NOTE:
THE PROPOSED FORCE MAIN SHALL HAVE A 3' MIN. GROUND COVER.
3.
0'
C O
V E
R
M
IN
FORCE MAIN/WATER MAIN CROSSING - SECTION VIEW
DETAIL A
EOP
PROPOSED 4' SWING GATE
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
EX. 6" CIP FORCE
MAIN TO BE
ABANDONED AND
GROUT FILLED
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
9' -3
15'-6"
5'-8"
8' DOUBLE SWING GATE
PROP. 3/4" REDUCED
PRESSURE BACKFLOW
PREVENTER
-1
7-
0%
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
ROAD TO BE
OPEN CUT AND
REPAIRED
AUGUST 2025
PROP. 6" PLUG
VALVE
10.00'
5'-3"
.4
2'
10.0000'
8" N
E
SA
NIT
AR
Y
SE
W
ER
8" S
A N
IT
A
R Y
S E
W E
R
CD 12/12/12
CLF 4
CLF 4
CLF 4
CLF 4
ELM 15/12
PP
PP
SS
SS
SS
WWWWWWWWWWWWWWWWWWWWWWWW
WM UW1
152022 19.93
EX. SANITARY MH
TOP = 20.29'
4" INV (W) = 16.39' (VCP)
4" inv (E) = 16.29' (VCP)
JUNCTION MANHOLE NOT FOUND
PROPERTY NOT ACCESSIBLE
DUE TO TERRITORIAL DOGS AND
NON RESPONSIVE RESIDENTS
EX. WET WELL
TOP = 19.57'
8" INV (NE) = 15.84' (PVC)
8" INV (S) = 12.46' (PVC)
8" INV (NW) = 9.96' (PVC)
BOTTON = 5.36'
POLE W/ELECTRIC METER
ELECTRIC METER
FOUND 5/8" IRON
ROD NO ID
XXXXXXXX
X X
X X
X X
X X
X X
X
X X X X X X X X
X
X
X X
X X
X X
X X
X X
PALM 20"
PALM 18"
15"CMP
15"CMP
15"CMP
15"CMP
15"CMP
CONC.
DWY.
GRAVEL DWY.
DI
RT
D W
Y.
4' CLF
4' VINYL
FENCE
EOP
EOP
" R
CP
RC
P
25.00' 25.00'
N88°58'37"E 454.95' 455.00'(P)
ALT KEY
3116321.0000
ALT KEY
3116313.0000
ASPH
ASPH
MASONRY GATE
COLUMNS
ASPH
ASPH
EX. 15" INV = 19.05'
INV = 17.60'
CATCH BASIN
TOP = 19.51'
N. INV = 17.58'
S. INV = 17.61'
INV = 19.11'
INV = 19.55'
INV = 19.93'
INV = 19.84'
SITE BENCHMARK #301
FOUND SMALL NAIL NO DISK
N= 1790093.35 E = 628944.81
ELEV = 20.43
CATCH BASIN
TOP = 18.85'
W. INV = 17.20'
S. INV = 17.25'
INV = 18.67'
INV = 18.94' INV = 19.38' INV = 19.02'
INV = 19.03'
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
G E
N E
R A
TO
R
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
010 10 20
11.0'
AVENUE D
Sheet C-3
G
RA
D
IN
G P
LA
N
TOP=24.0'
BOT=19.0'
TOP=24.0'
BOT=19.0'
TOP=24.0'
BOT=19.0'
TOP=24.0'
BOT=19.0'
TOP=23.30'
BOT=19.00'
TOP=22.80'
BOT=19.00'
TOP=22.30'
BOT=19.00'
TOP=21.75'
BOT=19.00'
TOP=21.75'
BOT=19.00'
TOP=22.30'
BOT=19.00'
TOP=22.80'
BOT=19.00'
TOP=23.30'
BOT=19.00'
21.40 EL.
24.0'
23.48'
22.95'
22.43'
21.90'
.0
' 18 .0
19.0'
18.0'
SIDE SLOPE=
4:1
TOP OF BANK ELEV.
TYPICAL POND SECTION
POND BOTTOM ELEV.
VARIES
SID
E S
LO
PE=
:1
4:119.00 18.00
NOTES:
1. MAXIMUM SIDE SLOPES NOT TO EXCEED 4:1.
2. SOD ALL SIDE SLOPES.
3. SOD BOTTOM.
4. GRADES REPRESENT TOP OF SOD.
TOP OF
BANK
ELEVATION
POND
BOTTOM
ELEVATION
SLOPE
(MAX.)
POND
32.00'
POND BOTTOM
5.00'
5.00'
6.00'
5.00'
PROP.RETAINING WALL
w/ 42" GUARD RAILS
PROP.RETAINING WALL
END OF WALL = 20.30'
END OF WALL = 20.30'
CONTRACTOR SHALL SOD ALL UNPAVED AREAS INSIDE THE
PROPERTY BOUNDARY AND ALL DISTURBED AREAS.
NOT TO SCALE
8" THICK CONCRETE DRIVE
EXPANSION JOINT NOTE:
1/2" BITUMINOUS COATED EXPANSION JOINT MATERIAL
TO BE USED AT ALL CURBS AND SIDEWALKS.
LONGITUDINAL CENTER JOINT @ 10' O.C., AND TRANSVERSE CONTRACTION JOINTS @ 20' O.C.
1/2" EXPANSION JOINTS 60' O.C. OR EVERY 3RD. TRANSVERSE JOINT TO BE AN EXPANSION
JOINT.
8" THICK @ 3,500 PSI CONCRETE
W/ 6"X6"-W2.9XW2.9
WELDED WIRE FABRIC
12" STABILIZED SUBGRADE
WITH A MINIMUM L.B.R. OF 40,
COMPACTED TO 98% OF MAXIMUM
DENSITY PER AASHTO T-180
20.61 EX. EL.
TOP=24.0'
BOT=19.0'
TOP=21.25'
BOT=20.10' E
G
TOP=21.25'
BOT=20.10' E
G
20.40 EX. EL.
20.30 EX. EL.
19.0'4.00'
19.0' 19.0'
2'
2'
2'
4.5'
19.0'
18.0'
.0
.0
19.0'
18.0'
.0
19.0'
.0
18.0'
18.0'
.0
19.0'
52.00'
POND BOTTOM
13.50' P
O N
D B
O
TTO
M
8.00'
POND
BOTTOM
4:
20.0'
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
C
PROPOSED WETWELL TO MANHOLE CONVERSION
SCALE: 3/4" = 1'
EL. 19.57'
EL. 5.36'
PROP. 10" PVC
INV. (NW) EL = 9.86'
044787.001 Lift Station
53 - Construction Plan
PROPOSED 6MM FIBERGLASS LINED
CONCRETE MANHOLE 3'-6" DIAMETER BY
FLOWTITE OR APPROVED EQUAL LINER
SHALL BE GROUTED IN PLACE. MANHOLE
RING AND COVER SHALL BE PROVIDED.
EXISTING 8" SS
INV. EL = 15.84' (NE)
EXISTING 8" SS
INV. EL = 9.96' (NW)
INSTALL WATERTIGHT MANHOLE RING
AND COVER COMPOSITE AS
MANUFACTURED BY COMPOSITE
ACCESS PRODUCTS, LP
EXISTING LIFT STATION
(TO BE DEMOLISHED)
(EXISTING WETWELL TO BE CONVERTED TO MANHOLE)
C
EXISTING WETWELL TO BE FILLED
SCALE: 3/4" = 1'
EL. 5.36'
EXISTING 8" SS
INV. EL = 12.46' (S)
EXISTING 8" SS
INV. EL = 15.84' (NE)
EL. 19.57'
EXISTING WETWELL TO BE FILLED WITH
CONCRETE CONTRACTOR TO FORM
MANHOLE BENCH INTO CONCRETE
EL. 9.86'
EXISTING 8" SS
INV. EL = 12.46' (S)
PROP. CONCRETE FILL
Sheet C-4
M
AN
H O
LE
S
EC
TI
O N
V
IE
W
EL. 9.86'
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
CONSTRUCT BENCH IN
ACCORDANCE WITH DETAIL S-12
AUGUST 2025
LOCK HOLE
TOP ARCH FOR
MOLDED INTO SUBSTRATE
CUSTOM MARKING
CUSTOM LOGO
OR TREAD PATTERN
MOLDED INTO
SUBSTRATE IN
CENTER POSITION
CONCEALED
PICK HOLE (2)
316 SS INSERTS
INSTALLED
1.50in
AASHTO M-306
DESIGNATION
LOCK HOLE
.50in DIA.
LOCK HOLE (3)
INSTALLED
NEOPRENE
GASKET
BOTTOM ARCH FOR
MOLDED INTO SUBSTRATE
CUSTOM MARKING Color = Black
COVER
Weight = 80lb ANCHOR HOLE 1.6in (4)
FRAME
Color = Black Weight = 47lb
26.5in
0in
2.5in 4.3in
(MM/DD/YY FORMAT)
DATE OF MANUFACTURE
0.38in
ALLEN HEAD
COMBO
BOLT
0.75in DIA
LOCK HOLE DIA
1.07in
FRAME
INSTALLED
NEOPRENE
GASKET
COVER
HOLE TO BOLT CLEARANCES STIFF PADDLE LOCK FEATURE
COMPOSITE ACCESS PRODUCTS, L.P. "JUST CAP THAT"
5216 N. 26TH STREET
MCALLEN, TX 78504
WEBSITE: www.justcapthat.com
(844) 344-CAP1 (2271)
MODEL # CAP ONE
COVER SIDE
1.07in 2.05in
4.6in 2.0in 0.9in
0in
SECTION A-A
24.1in
FRAME SECTION
34.0in
1. All hardware is 316 Stainless Steel.
2. Detectable by standard metal detectors.
3. Compression Molded Thermoset Composite - no metal reinforcement
4. PASSED M306 H20/H25 PROOF LOAD
5. All actual Weights and Dimensions are ±5% of drawing
Product Code
APPROVED BY:
DATE:
A-1BK24L3-C07DMDSS-H1 2024-09-23
2.7in
26.7in 28.5in
0.9in
3D MOLDED IN
LOWERED
LETTERING
INSTALLED 316 SS
LIFTING HOOK
A
MADE IN USA
SURFACE VISIBLE
A
DATE OF
MANUFACTURE
(MM/DD/YY FORMAT)
MA
DEIN
U S
A
PU SH
T UR
N
PU
SH
T U
RN
PUSHTUR
N
EXISTING 8" SS
INV. EL = 9.96' (NW)
PALM 20"
PALM 18" PALM 12"
15"CMP
15"CMP
15"CMP
15"CMP
15"CMP
15"CMP
CONC.
DWY.
GRAVEL DWY.
4' CLF
4' VINYL
FENCE
4' CLF
EOP
EOP
EOP
EO
P
EOP
EOP
EOP
EO
P
RC
P
18" RCP
"R
CP
STOP
SIGN
STOP
SIGN
N88°58'37"E 454.95' 455.00'(P)
.2
.2
.2
.6
.7
.9
.5
.3
.5
.3
.3
.2
.2
.1
.4
.9
.7
.2
.3
.6 22
.4
.021
.3
.3
.59
.97
.72
.80
.45
.66
.50
.63
.96
.95
.95
.70
.90
.72
.10
.08
ASPH
ASPH
MASONRY GATE
COLUMNS
ASPH
ASPH
EX. 15" INV = 19.05'
INV = 19.11'
INV = 19.55'
INV = 19.93'
INV = 19.84'
INV = 20.01'
SITE BENCHMARK #301
FOUND SMALL NAIL NO DISK
N= 1790093.35 E = 628944.81
ELEV = 20.43
CATCH BASIN
TOP = 18.85'
W. INV = 17.20'
S. INV = 17.25'
INV = 18.67'
INV = 18.94' INV = 19.38' INV = 19.02'
INV = 19.03'
INV = 19.68'
CATCH BASIN
TOP = 21.09'
18" INV = 19.09'
STORM MH
TOP = 21.99'
N. INV = 15.11'
E. INV = 17.34'
S. INV = 15.08'
FND N&D
"PSM 4002"
SITE CONTROL #5
SET 5/8" IRON & CAP "TRAV
HALFF"
N = 1790130.72 E = 629198.56
ELEV = 21.90'
FM FM FM FM FM FM FM FM FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
OA
K
6"
OA
K
6" PA
LM
6"
15"CMP
15"
CMP
12"CMP12"CMP
PINE DR.
4' CLF
4' CLF
STORM
M
ANHOLE
TOP=
23.87'
N.INV.=
14.19'
S.INV=
14.19'
EOP
EOP
EOP
EOP
EOP
EOP
EOP
EOP
EOP
EOP
STOP
SIGN
STOP
SIGN
STOP
SIGN
42"RCP
42"RCP
25.00'
25.00'
N01°30'58"E 262.33' 264.00'(P)
FN
D
N A
IL
N
O
ID
21.6 22.4
21.7
22.7
22.2
22.4
23.8
23.1
24.0
24.1
24.5
24.4
23.8
23.1
22.4
23.4
22.0
23.0
21.9
22.8
21.9
21.6
22.2
21.0
21.3
21.95
21.70
22.08 22.39
22.10
22.29
22.96
23.19
23.07
23.34
23.54
23.83
23.80
23.91
ASPH
ASPH
ASPH
ASPH
IN
V
21.64'
IN
V
21.52'
IN
V
21.86'
IN
V
21.90'
S
ITE
B E
N C
H M
A R
K
S
E T X
C U
T O N
TO
P
FLA
N
G E
B O
LT
N
1790349.00
E
629228.80 E
LE
V
27.40'
S E
T 5/8" IR
O
N
C A
P
"TR
A V
H A
LFF"
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
PALM 10" PALM 8" PALM 16"
CAMPHOR 2X24"
PALM 14"
PALM 18"
PALM 10"
DIRT
DWY
ASPHALT
MILLINGS
DWY
DIRT
DWY
CONC.
DWY 4' CLF
CONC.
DWY
DIRT
DWY
CONC.
DWY
CONC.
DWY
4' CLF
4' CLF
4' CLF
4' CLF
ASPHALT
DWY
ASPHALT
DWY DIRT
DWY
2' VALLEY CURB
2' VALLEY CURB
2' VALLEY CURB
2' VALLEY CURB
EOP EOP
EOP
25.00'
25.00'
N89°02'33"E 450.02' 450.00'(P)
.1
.5
.4
.2
.8
.3
.8
.3
.0
.6
.5
.3
.6
.4
.17
.30
.15
.91
.10
.93
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
N o rt h
S in cl ai r A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
FO
R
C E
M A
IN
P
LA
N
V
IE
W
STA. 2+27.43, 11.03' L
STA. 2+30.30, 13.84' L
INSTALL:
(2) 6" 45° BENDS
PROPOSED OPEN-CUT AND
REPAIR DIRT DRIVEWAY
(SEE SHEET G-4)
PROPOSED OPEN-CUT AND
REPAIR CONCRETE DRIVEWAY
(SEE SHEET G-4)
MATCHLINE STA. 4+85.22
M A
TC
H
LI
N
E S
TA
. 4
.2
MATCHLINE STA. 7+58.60
AVENUE D
P
IN
E D
R
PINE DR
A V
E N
U E
C
AVENUE C
PROPOSED 6" PVC
FORCE MAIN
PROPOSED 6" PVC
FORCE MAIN
PROPOSED 6" PVC
FORCE MAIN
STA: 4+76.30, 15.35' R
STA. 4+81.00, 21.01' R
INSTALL:
(2) 6" 45° BEND
010 10 20
010 10 20
010 10 20
SEE SHEET C-2
(SITE PLAN)
11'
ROAD TO BE OPEN
CUT AND REPAIRED
(SEE SHEET G-4)
4.
0'
PROPOSED OPEN CUT &
REPAIR ASPHALT DRIVEWAY
(SEE SHEET G-4)
PROPOSED OPEN CUT &
REPAIR ASPHALT DRIVEWAY
(SEE SHEET G-4)
M A
TC
H
LI
N
E S
TA
. 7
.6
M A
TC
H
LI
N
E S
TA
. 1
0+
.2
3.
0'
4.
PROPOSED OPEN CUT & REPAIR
ASPHALT MILLING DRIVEWAY
(SEE SHEET G-4)
PROPOSED OPEN-CUT AND
REPAIR DIRT DRIVEWAY
(SEE SHEET G-4)
DRIVEWAY TO BE OPEN
CUT AND REPAIRED
(SEE SHEET G-4)
Sheet C-5
PROPOSED OPEN CUT
AND REPAIR GRAVEL
DRIVEWAY (SEE SHEET G-4)
3.
0'
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
4.18'
044787.001 FM &
BORE PROFILES.DWG
STA 7+39.15, 20.19' L
INSTALL:
(1) 6" 45° BEND
STA 7+41.10, 22.03' L
INSTALL:
(1) 6" 45° BEND
STA 3+66.67, 13.89' L
INSTALL:
(1) 6" 45° BEND
STA 3+75.14, 22.32' L
INSTALL:
(1) 6" 45° BEND
EX.4" PVC FORCE MAIN
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
PROPOSED PALM TREE TO BE REMOVED
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
P R
O
JE
C T
N O
. 6
ROAD TO BE OPEN
CUT AND REPAIRED
(SEE SHEET G-4)
AUGUST 2025
NOTE:
1. FORCE MAIN SHALL BE INSTALLED WITH A
MINIMUM OF 3 FEET OF COVER
2. EXISTING FORCE MAIN TO BE GROUT FILLED
ROAD TO BE OPEN
CUT AND REPAIRED
(SEE SHEET G-4)43.19'
28.37'
.1
3'
19.96'
25.94'
5.99'
7.32'
20.44'
PALM 12"
OAK 5"
OAK 5"
CEDAR 12"
PINE 18"
CONC. WALK CONC. WALK
30 MPH
STOP SIGN
4' CLF
EOP
EOP
EOP
EOP
EO
P
EOP
EOP
.6
.5
.2
.5
.2
.2
.3
.6
.9
.25
.23
.8
.07
.82
.86
.96
.02
.28
.10
MONITORING WELL W/CONC PAD
MONITORING WELL ON CONC.
PAD
SITE BENCHMARK #3118
SET X CUT ON TOP FLANGE BOLT
N = 1790313.4
E = 629960.7
ELEV = 27.85'
CONC WALL
SITE CONTROL #2
SET 5/8" IRON ROD & CAP "TRAV HALFF"
N = 1790310.72
E = 629980.39
ELEV = 26.44'
CONC UTIL. PAD
CONC WALL
SOUTH R/W LINE OF FLEMING AVE AS NOW OCCUPIED
PER OFFICIAL RECORDS BOOK 4128, PAGE 375
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM FM FM FM FM FM
PALM 10"
PALM 12"
PALM 12"
OAK 2X"
PALM 12"
OAK 5"
CONC.
DWY
4' CLF
4' C
LF
STOP SIGN
STOP SIGN
STOP SIGN
4' CLF
DIRT
DWY
2' VALLEY CURB
CONC. WALK
CONC. WALK
EOP
EOP
EO
P
EO
P
EOP
.0
0'
.8
.1
.2
.5
.9
.6
.4
.8
.9
.6
.8
25.8
.7
.38
.6
.4
.77
.58
.84
.50
.26
.45
.46
.47
.4
.70
.8
.7
50' R/W PER
M.B. 10 PG. 41
25 MPH
FND 1" IP NO ID E = 629672.75
ELEV = 25.64
FND N&D (NO ID)
1.04'S, 9.25'W
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
PA
LM
0"
PALM 20"
4' CLF
4' CLF
ASPHALT AREA
ASPHALT
DWY
CONC. UTIL.
PADS (2)
EOP
EOP
EOP
HEADWALL
TOP=26.82'
INV.=16.01'
7.5'X10.5
CULVERT
.0
0'
.4
.4
.4
.1
.5
.7
.8
.8
.5
.5
.3
.65
.5
.16
.34
.16
.87
.85
.4
.68
.35
.68
.71 GUARDRAIL
CONC. WALK
6" ASPHALT CURB
2' VALLEY CURB
CONC. WALK
COMMUNICATION
CABINET
HEADWALL
TOP = 27.40'
INV = 16.10'
D
ITC
H
FND 1 1/2" IP
NO ID
ASPHALT
APRON
GUARDRAIL
SITE CONTROL #1
SET 5/8" IRON & CAP "TRAV HALFF"
N = 1790291.28
E = 630379.29
ELEV = 26.22
PLANTER FND 5/8" IRC
"LB 4335"
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
.25
.46
.36
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
N o rt h
S in cl ai r A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
PROPOSED OPEN-CUT AND
REPAIR ASPHALT ROAD
PROPOSED 6" PVC
FORCE MAIN
STA: 12+02.76, 17.44' L
INSTALL:
(1) 6" 11.25° BEND
STA: 19+52.66, 13.92' L
PROPOSED TRANSITION FROM
8" HDPE TO 6" PVC
INSTALL:
(1) 8"X6" MJ REDUCER & FUSED
ON 8" MJ COUPLING
010 10 20
010 10 20
010 10 20
M A
TC
H
LIN
E
S
TA
. 10+ 73.24
M A
TC
H
LI
N
E S
TA
. 1
3+
.2
STA 16+89.77, 13.85' L
PROPOSED TRANSITION FROM
6" PVC TO 8" HDPE
INSTALL:
(1) 8"X6" MJ REDUCER FUSED
ON 8" MJ COUPLING
PROPOSED DIRECTIONAL BORE,
8" HDPE FM (SEE SHEET C-9)
FLEMING AVE
JERO
M
E BLVD
M A
TC
H
LI
N
E S
TA
. 1
3+
.2
M A
TC
H
LI
N
E S
TA
. 1
6+
.1
PROPOSED 6" PVC
FORCE MAIN
4.02'
3.0'
M A
TC
H
LI
N
E S
TA
. 1
6+
.1
FLEMING AVE
FLEMING AVE
AVENUE C
P
LA
M S
TR
E
E T
5'
4.62'
9.15'
8.83'
STA 19+57.14, 12.42' L
INSTALL AIR RELEASE VALVE
PROPOSED OPEN-CUT AND
REPAIR VALLEY CURB
Sheet C-6
FO
R
C E
M A
IN
P
LA
N
V
IE
W
PROPOSED OPEN-CUT
AND REPAIR CONCRETE
DRIVEWAY
CONTRACTOR TO FIELD VERIFY
EXISTING BURIED TELE. LINE SIZE
AND ELEVATION AT UTILITY CROSSING
CONTRACTOR TO FIELD VERIFY
EXISTING CATV LINE SIZE AND
ELEVATION AT UTILITY CROSSING CONTRACTOR TO FIELD VERIFY
EXISTING BURIED TELE. LINE SIZE
AND ELEVATION AT UTILITY CROSSING
PROPOSED DIRECTIONAL
BORE, 8" HDPE FM
(SEE SHEET C-9)
STA 19+55.66, 13.87'L
INSTALL:
(1) 6" 45° BEND
(1) 6" PLUG VALVE
STA 19+58.63, 10.97'L
CUT IN EXISTING FORCE MAIN
INSTALL:
(1) 6" WYE
(1) 6" PLUG VALVE
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 FM &
BORE PROFILES.DWG
STA 11+00.00, 22.43' L
INSTALL:
(1) 6" 45° BEND
STA 11+07.00, 15.30' L
INSTALL:
(1) 6" 45° BEND
EX.4" PVC FORCE MAIN
EX.4" PVC FORCE MAIN
EX.4" PVC FORCE MAIN
EX.4" PVC FORCE MAIN
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
P R
O
JE
C T
N O
. 6
FM
FM
FM
FM
FM FM
FM FM FM
FM FM
FM FM
STA 10+95.33, 22.44' L
INSTALL AIR RELEASE VALVE
AUGUST 2025
STA 16+33.86, 16.62' L
INSTALL:
(1) 6" 45° BEND
STA 16+38.18, 12.37' L
INSTALL:
(1) 6" 45° BEND
NOTE:
1. FORCE MAIN SHALL BE INSTALLED WITH A
MINIMUM OF 3 FEET OF COVER
2. EXISTING FORCE MAIN TO BE GROUT FILLED
NOTE:
1. FORCE MAIN SHALL BE INSTALLED WITH A
MINIMUM OF 3 FEET OF COVER
2. EXISTING FORCE MAIN TO BE GROUT FILLED
NOTE:
1. FORCE MAIN SHALL BE INSTALLED WITH A
MINIMUM OF 3 FEET OF COVER
2. EXISTING FORCE MAIN TO BE GROUT FILLED
INSTALL AIR RELEASE VALVE
INSTALL AIR RELEASE VALVE
EXISTING GRADE OVER CENTERLINE OF FM
INSTALL 6" WYE &
TIE INTO EXISTING FM
(1) 6" 45° BEND
(1) 8" 11.25° BEND
(1) 8" 11.25° BEND
PROPOSED DIRECTIONAL
BORE, 8" HDPE
SCALE
HORIZONTAL: 1" = 10'
VERTICAL: 1" = 2'
3' M
IN
EXISTING FORCE MAIN INV EL. ± 23
(CONTRACTOR TO FIELD VERIFY PIPE
ELEVATION)
EXISTING STORM SEWER INV = 16.00±
EXISTING TOP ±17.5
EXISTING WATER MAIN
(CONTRACTOR TO FIELD VERIFY
PIPE ELEVATION)
INSTALL (1) 8"X6" MJ REDUCER
& FUSED ON 8" MJ COUPLING
INSTALL (1) 8"X6" MJ REDUCER
& FUSED ON 8" MJ COUPLING
ARV (SEE DETAILS-19 ON SHEET G-3)
18" M
IN
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
N o rt h
S in cl ai r A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
STA. 16+89.77, 13.85'L TO STA. 19+52.66, 13.92'L
DIRECTIONAL BORE PROFILE
Sheet C-7
FO
RC
E M
AI
N
P
RO
FI
LE
V
IE
W A
N D
M
IS
C
C
RO
SS
S
EC
TI
O N
S
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 FM &
BORE PROFILES.DWG
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
P R
O
JE
C T
N O
. 6
G E
N E
R A
TO
R
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
W S
1 2 3 4 5 6 7 8
044787.001
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
PROPOSED 8.0'
WETWELL
PROP. 6" DIP
FORCE MAIN
PROPOSED 6" TEE
W/ 6" BLIND FLANGE
PROP. 6" TEE
PROP. 6" CHECK
VALVE (TYPICAL)
PROP. 6" TEE
PROP. 6" PLUG
VALVE (TYPICAL)
PROP. 6" BAUER B STYLE
COUPLING
PROP. 60'' x 48'' ACCESS HATCH
(HALLIDAY SERIES S2R6048)
PROPOSED SUBMERSIBLE PUMP #1
PROPOSED SUBMERSIBLE PUMP #2
NP 3153 HT 3
4"
276 mm
HORSE POWER
R.P.M.
SUBMERSIBLE PUMPS
8.0 FEET
T.D.H.
3 PHASE
58311
60 HZ 240 VOLT
PROPOSED PUMP DATA
FLYGT
G.P.M.
ELECTRICAL REQUIREMENTS
MODEL NUMBER
WETWELL INSIDE DIA.
PUMP SIZE
IMPELLER
PROP. 4"Ø STAINLESS STEEL
PRESSURE GAUGE (OIL FILLED
W/DIAPHRAGM ISOLATED AND
PETCOCK VALVE (TYPICAL)
A 8
A 8
B
B
PUMP STATION NOTES:
(1) THE INTERIOR OF THE WETWELL SHALL BE LINED WITH 2 MM AGRU SURE GRIP
LINING SYSTEM.
(2) THE EXTERIOR OF THE WETWELL SHALL BE COATED WITH 10 MIL. EW-1 AQUAPOXY,
DRY FILM THICKNESS (DFT) - 2-COATS AT 5 MIL. EACH (RED & BLACK)
(3) RISER PIPE PENETRATIONS IN THE WETWELL TOP SLAB SHALL BE SEALED WITH
SIKAFLEX.
PROP. 3/4" POLY
WATER SERVICE
PROP. HOSE BIBB
Sheet M-1
PL
AN
V
IE
W
PROP. CONTROL PANEL
(SEE ELECTRICAL SHEETS)
PROP. GENERATOR
PROP. 59 LF OF 10" PVC SANITARY
SEWER @ 0.4% SLOPE
5.0'
4.
0'
PROP. 6" PLUG VALVE
PROPOSED 4" TYPE 316 STAINLESS STEEL
VENT WITH 1/4" HARDWARE SCREEN
2" SCH 40 PVC DRAIN LINE TO BE
SLOPED TOWARDS WETWELL
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
044787.001 Lift Station
53 - Construction Plan
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
AUGUST 2025
PROPOSED 6"
90° BEND
(TYPICAL)
12'' DIAMETER OPENINGS FOR RISER PIPE
(SEE NOTE 3)
01 1 2
TYPE 316 STAINLESS STEEL SEWAGE
COMBINATION AIR/VACUUM RELEASE
VALVE, A.R.I. MODEL D-025 STST OR
APPROVED EQUAL,VENT TO WET
WELL W/2" SCH 40 PVC
PROPOSED 6"
90° BEND
R E
V
IS
IO
N
D A
T E
JOB NO.:
CHECKED BY:
DRAWN BY:
DATE:
DESIGNED BY:
FILE NAME:
LI
FT
S
TA
TI
O
N
R
E P
LA
C
E M
E N
T
N o rt h S in cl ai r
A ve
C er tif ic at e o f
A ut h o ri za tio n
N um b er
: 3
Fa x:
.3
.8
O ff ic e:
.3
.8
Ta va re s, F lo ri d a
C
IT
Y O
F D
A Y
TO
N
A B
E A
C H
SCALE: 3/4" = 1'
PROPOSED 6" DIP
FORCE MAIN
PROPOSED 6"
TEE
PROPOSED
6" TEE
PROPOSED 6" PLUG
VALVE (TYPICAL)
PROPOSED 6" CHECK
VALVE (TYPICAL)
PROPOSED 60'' x 48''
ACCESS HATCH
(HALLIDAY SERIES S2R6048)
PROPOSED 6"
90° BEND
PROPOSED 6"
90° BEND
PROPOSED 4"
BASE ELBOW
316 STAINLESS STEEL SCH. 40 PUMP GUIDE
RAILS (2) PER PUMP BY PUMP MANUFACTURER
6" TYPE 316 STAINLESS
STEEL SCH. 40 RISER PIPE
TYPE 316 STAINLESS STEEL PIPE
SUPPORT (TYPICAL)
PROPOSED 4" TYPE 316 STAINLESS STEEL
VENT WITH 1/4" HARDWARE SCREEN
HIGH WATER ALARM
HIGH-HIGH EL = 10.12'
EL = 24.00' EL = 24.00'
PROPOSED 4"Ø STAINLESS STEEL
PRESSURE GAUGE (OIL FILLED W/DIAPHRAGM
ISOLATED AND PETCOCK VALVE (TYPICAL)
SEAL CONDUIT
END IN WETWELL
STAINLESS STEEL PUMP
GRIP-EYE CABLE
EL = 5.00'
CL EL = 15.75'
A
SECTION
2" SCH 40 PVC
UNION (TYP.)
2" SCH 40 PVC
90° BEND
2" STAINLESS STEEL
BALL VALVE
6" X 2" SERVICE SADDLE
TYPE 316 STAINLESS STEEL SEWAGE
COMBINATION AIR/VACUUM RELEASE
VALVE, A.R.I. MODEL D-025 STST OR
APPROVED EQUAL,VENT TO WET
WELL W/2" SCH 40 PVC
1-1/4" THREAD x 2"
SLIP SCH 40 PVC
PROPOSED STAINLESS
STEEL PIPE SUPPORT
(TYPICAL)
2" SCH 40 PVC DRAIN LINE TO BE
SLOPED TOWARDS WETWELL
PROPOSED STAINLESS
STEEL PIPE SUPPORT
(TYPICAL)
PROPOSED 6" TEE
PROPOSED 6" PLUG
VALVE (TYPICAL)
PROPOSED 6" TEE
SCALE: 3/4" = 1'
B
SECTION
PROPOSED SUBMERSIBLE
FLYGT PUMP
CL EL = 27.50'
Sheet M-2
SE
C
TI
O
N V
IE
W
PROP. 6'' BAUER B STYLE COUPLING
8"
-2
9-
P R
E
LI
M
IN
A R
Y S
E T, N O
T
FO
R C
O N
S
TR
U C
TI
O
N
PUMP STATION NOTES:
1. PUMPS SHALL BE FLYGT SUBMERSIBLE PUMPS. PUMPS SHALL HAVE(2) 2" TYPE 316 STAINLESS STEEL GUIDE
RAILS PER PUMP
2. WET WELL ACCESS COVERS SHALL HAVE CLEAR OPENING OF 60" X 48" AS MANUFACTURED BY HALLIDAY PRODUCTS OR APPROVED EQUAL. ACCESS FRAME AND COVER SHALL HAVE A 1/4" THICK ONE-PIECE, MILL FINISH, EXTRUDED ALUMINUM FRAME, INCORPORATING A CONTINUOUS CONCRETE ANCHOR. DOOR PANEL(S) SHALL BE 1/4" ALUMINUM DIAMOND PLATE, REINFORCED TO WITHSTAND A LIVE LOAD OF 300 PSF. DOOR(S) SHALL OPEN TO 90° AND AUTOMATICALLY LOCK WITH STAINLESS STEEL HOLD OPEN ARMS WITH ALUMINUM RELEASE HANDLES. DOOR(S) SHALL CLOSE FLUSH WITH THE FRAME. UNIT SHALL LOCK WITH A NONCORROSIVE LOCKING BAR. FRAME SHALL SUPPORT GUIDE RAILS AND CABLE HOLDER FOR ELECTRICAL WIRING. FALL
PROTECTION SHALL BE PROVIDED.
3. ALL FASTENERS ON FLANGES AND ETC. INSIDE WET WELL SHALL BE 316 STAINLESS STEEL.
4. ALL DIMENSIONS AND LOCATIONS OF UTILITIES TO BE FIELD VERIFIED BY CONTRACTOR.
5. PRESSURE GAUGES SHALL BE STAINLESS STEEL WITH STAINLESS STEEL DIAPHRAGM, LIQUID FILLED, 4 1/2" DIAMETER DIAL WITH 0-100 PSI RANGE. GAUGES SHALL BE AS MANUFACTURED BY WIKA, LOWER MOUNT, TYPE
233.30 AND DIAPHRAGMS SHALL BE AS MANUFACTURED BY CITY APPROVED MANUFACTURERS.
6. BACKFILL AROUND WET WELL IN 12” LIFTS COMPACTED TO A MINIMUM OF 98%.
7. LOCATIONS WHERE RISER PIPES LEAVE THE WET WELL SHALL BE MADE WATERTIGHT WITH SIKAFLEX-1A
CLOSURES SEALED FOR THE PROPER SEALING RANGE.
8. INSTALL PUMP BASE ELBOWS, GUIDE RAILS AND DISCHARGE PIPING PLUMB, LEVEL AND SQUARE.
9. INSTALL BENCH FOR PUMP BASE ELBOW IF NECESSARY, PER MANUFACTURER'S APPROVED SHOP DRAWINGS.
10. COAT ALL METALS THAT ARE NOT STAINLESS STEEL AND ARE LOCATED IN THE WETWELL WITH 10 MILS (DRY FILM THICKNESS) OF BLACK, HIGH GLOSS EPOXY, (TNEMEC SERIES 69 HI-BUILD EPOXYLINE II OR SHERWIN WILLIAMS MACROPOXY). COATING SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATION AND SHALL NOT BE IMMERSED UNTIL FULL CURE IS ACHIEVED.
11. COAT ALL ALUMINUM SURFACES IN CONTACT WITH CONCRETE WITH TWO COATS OF ZINC CHROMATE PRIMER
PRIOR TO INSTALLATION.
12. PUMP BASE ELBOWS, PUMP ANCHOR BOLTS, UPPER AND INTERMEDIATE GUIDE RAIL BRACKETS, GUIDE RAILS, CABLE HANGER, PUMP LIFTING CABLES, CONTROL PANEL AND FLOAT SWITCHES TO BE APPROVED BY PUMP
SUPPLIER.
13. INSTALL INTERMEDIATE GUIDE RAIL BRACKETS AS REQUIRED BY PUMP MANUFACTURER.
14. DUCTILE IRON PIPE SHALL COMPLY WITH AWWA C115 AND SHALL BE LINED WITH PROTECTO 401 EPOXY
COATING.
15. DUCTILE IRON FITTINGS SHALL COMPLY WITH AWWA C110 OR C153 WITH AND BE LINED WITH PROTECTO 401
EPOXY COATING.
16. PAINT EXTERIOR PIPE, VALVES AND FITTINGS WITH AN ALIPHATIC, ACRYLIC POLYURETHANE SYSTEM, COLOR
GREEN, TNEMEC SERIES 74 OR AN EQUIVALENT PRODUCT. COMPLY WITH ALL MANUFACTURER'S
RECOMMENDATIONS.
17. FIELD TESTING: THE CONTRACTOR SHALL FURNISH THE SERVICES OF THE SYSTEM SUPPLIER'S SERVICEMAN, ALL SPECIAL TOOLS, CALIBRATION EQUIPMENT, AND LABOR TO PERFORM THE TESTS. CERTIFIED COPIES OF
THE TESTS SHALL BE FURNISHED TO THE ENGINEER PRIOR TO FINAL APPROVAL.
18. THE INTERIOR OF THE WETWELL SHALL BE LINED WITH 2 MM AGRU SURE GRIP LINING SYSTEM.
19. THE EXTERIOR OF THE WETWELL SHALL BE COATED WITH 10 MIL. EW-1 AQUAPOXY, DRY FILM THICKNESS
(DFT) - 2-COATS AT 5 MIL. EACH (RED & BLACK)
044787.001 Lift Station
53 - Construction Plan
TEM
CLM
RAE
ROBERT A. ERN, PE
Registered Eng 54013
P R
O
JE
C T
N O
. 6
-1 7-
0% P
R E
LI
M
IN
A
R Y
S E
T, N
O T
FO
R
C O
N S
TR
U
C
TI
O N
INV. EL = 9.62'
AUGUST 2025
PROPOSED 6" x 4"
REDUCER
VEGAPULS C21
2" SCH 40 PVC
90° BEND
2" STAINLESS STEEL
BALL VALVE
2" X 6" COMPANION
FLANGE
TYPE 316 STAINLESS STEEL SEWAGE
COMBINATION AIR/VACUUM RELEASE
VALVE, A.R.I. MODEL D-025 STST OR
APPROVED EQUAL,VENT TO WET
WELL W/2" SCH 40 PVC
2" SCH 40 PVC DRAIN LINE TO BE
SLOPED TOWARDS WETWELL
2" MIN.
2" MIN.
PUMP BASE ANCHOR PLATE
NTS
4" MIN.
4" MIN.
PUMP SIDE
8" X 3/4" S.S. ANCHOR
BOLTS EPOXIED IN OR J
BOLTS CAST IN PLACE
PUMP BASE
18" X 22" (MIN.)
1" THICK STEEL PLATE
3/4" DIA. S.S. BOLTS TO
BE WELDED TO BOTTOM
SIDE OF STEEL PLATE.
FOR DIMENSIONS SEE
MANUFACTURER'S
SPECIFICATIONS
STANDARD HOOK DEVELOPMENT
LENGTH
BAR SIZE
#3
#4
#5
#6
#7
#8
#9
#10
#11
90° STD
HOOK "A"
6"
8"
10"
1'-0"
1'-2"
1'-4"
1'-7"
1'-10"
2'-0"
6"
7"
9"
10"
1'-0"
1'-2"
1'-3"
1'-5"
1'-7"
90° HOOK
BA
R
D
IA
A
180° HOOK
BA
R
D
IA
4 BAR DIA.
OR
2" MIN.
4 BAR DIA. (#3 TO #8 BAR)
5 BAR DIA. (#9 TO #11 BAR)
ld ldh ldh
J
MIN. LAP LENGTH
*SPACING NOT TO BE GREATER THAN 1/5
LAP LENGTH OR 6IN. WHICH EVER IS LESS
180° STD
HOOK "J"
3"
4"
5"
6"
7"
8"
4"
1'-11 4"
1'-23 4"
DEVELOPMENT
LENGTH,
ldh
*FOR STD HOOK BAR GEOMETRY
NOT SHOWN REFER TO MINIMUM ACI
REQUIREMENTS
BAR SIZE
#3
OTHER BARS
#4
#5
#6
#7
#8
#9
#10
#11
TOP BARS
DEVELOPMENT LENGTH, ld
1'-7"
2'-1"
2'-7"
3'-1"
4'-6"
5'-2"
5'-10"
6'-6"
7'-3"
1'-3"
1'-7"
2'-0"
2'-4"
3'-6"
3'-11"
4'-6"
5'-0"
5'-7"
CONCRETE STRENGTH f`c= 4,000 PSI OR GREATER
NOTES:
1. GRADE 60 UNCOATED REINFORCEMENT
2. SPLICE LENGTHS GIVEN ABOVE ARE TO BE USED
UNLESS NOTED OTHERWISE ON DESIGN DRAWINGS.
TOP BARS
LAP LENGTH (CLASS B SPLICE)
2'-0"
2'-8"
3'-4"
4'-0"
5'-10"
6'-8"
7'-6"
8'-6"
9'-6"
1'-7"
2'-0"
2'-7"
3'-1"
4'-6"
5'-2"
5'-10"
6'-6"
7'-3"
OTHER BARS
REBAR MINIMUM TENSION DEVELOPMENT & LAP LENGTHS
MAXIMUM BAR SPACING AT NON-CONTACT LAPS:
BAR SIZE
#3
#4
#5
#6
#7
#8
#9
#10
#11
DETAIL A
TYPNTS
STANDARD REINFORCEMENT DETAILS
GENERAL CONDITIONS
1. ALL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE MECHANICAL, CIVIL, ELECTRICAL, HVAC, AND SHOP DRAWINGS AND SPECIFICATIONS.
2. THE CONTRACTOR SHALL REVIEW AND VERIFY DIMENSIONS SHOWN IN ALL PLANS AND REVIEW
ALL FIELD CONDITIONS THAT MAY AFFECT THE WORK DEPICTED ON THE DRAWINGS. SHOULD
DISCREPANCIES APPEAR, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING TO OBTAIN
ENGINEER'S CLARIFICATION BEFORE COMMENCING WITH THE WORK.
3. FOR ALL ITEMS EMBEDDED IN OR PASSING THROUGH CONCRETE, THE CONTRACTOR SHALL
INITIALLY REFER TO MECHANICAL, HVAC, AND PLUMBING DRAWINGS FOR TYPE, SIZE, LOCATION, AND SPECIAL INSTALLATION REQUIREMENTS FOR THESE ITEMS.
4. THE CONTRACTOR SHALL TAKE ALL NECESSARY MEASURES TO PROTECT EXISTING STRUCTURES
FROM DAMAGE WHEN WORKING IN AND AROUND EXISTING STRUCTURES PERFORMING WORK
SUCH AS DEMOLITION, FOUNDATION EXCAVATIONS, AND OTHERS.
5. SIZE AND LOCATION OF EQUIPMENT PADS AND ANCHOR BOLTS SHALL BE PER EQUIPMENT
MANUFACTURER'S REQUIREMENTS.
6. ANY CONSTRUCTION EQUIPMENT THAT MAY INDUCE VIBRATION TO THE STRUCTURE SHALL BE
ADEQUATELY ISOLATED FROM THE STRUCTURE.
7. ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL
BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT
WHERE A DIFFERENT DETAIL IS SHOWN.
DESIGN CRITERIA
BUILDING CODES AND REFERENCES:
1. 2023 FLORIDA BUILDING CODE (FBC) EIGHT EDITION
2. REINFORCED CONCRETE: ACI 318-19 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE"
3. STRUCTURAL STEEL: AISC MANUAL OF STEEL CONSTRUCTION 15TH EDITION
4. LIVE LOADS:
WETWELL TOP SLAB 300 PSF & AASHTO H-20
(NON-CONCURRENT)
5. WIND DESIGN CRITERIA:
RISK CATEGORY III
ULTIMATE DESIGN WIND SPEED, VULT 146 MPH
NOMINAL DESIGN WIND SPEED, VASD 113 MPH
EXPOSURE CATEGORY D
FOUNDATIONS
GEOTECHNICAL REPORT:
1. SUBSURFACE EXPLORATION "GEOTECHNICAL INVESTIGATION, PROPOSED NEW LIFT STATION
LS-33, AVENUE D & PINE DRIVE, DAYTONA BEACH, VOLUSA COUNTY, FLORIDA" PREPARED BY
ANDREYEV ENGINEERING, INC. PROJECT NO. GPGT-22-121, DATED NOVEMBER 7, 2022. ANY
INTERPRETATION OF THE CONTENTS OF THE GEOTECHNICAL REPORT IS THE RESPONSIBILITY OF
THE CONTRACTOR.
FOUNDATION DESIGN:
1. ALLOWABLE NET BEARING PRESSURE FOR FOUNDATIONS: 1,500 PSF
CONCRETE (CAST-IN-PLACE)
1. ALL MATERIALS AND METHODS OF CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI 318
REQUIREMENTS.
2. ALL CONCRETE SHALL BE AIR-ENTRAINED WITH A MINIMUM OF 4,000 PSI COMPRESSIVE STRENGTH
AT 28 DAYS UNLESS OTHERWISE NOTED.
3. WATER REDUCING AGENT SHALL BE IN ACCORDANCE WITH ASTM C494.
4. ALL CONCRETE SURFACES EXPOSED TO AIR, UNLESS OTHERWISE NOTED IN THE SPECIFICATIONS, SHALL BE TREATED WITH AN APPROPRIATE CURING METHOD AS SOON AS FINISHING IS
COMPLETED OR FORMS ARE REMOVED.
5. ALL EXPOSED CORNERS SHALL HAVE A MINIMUM CHAMFER OF 3/4" UNLESS OTHERWISE NOTED.
6. THE CONTRACTOR SHALL OBTAIN…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .