CR 153 (Cypress Lake Road) Over Dry Branch BF.pdf
PDF 6 MB Posted
- Solicitation number
- PE-61600-NONST-2026-000000056
- Issued by
- Brooks County, Georgia
About this file
Bridge Foundation Investigation Report Summary
This Bridge Foundation Investigation (BFI) report, prepared by NOVA Engineering and Environmental, LLC for Heath & Lineback Engineers, Inc., documents the geotechnical findings for the CR 153 (Cypress Lake Road) Over Dry Branch bridge replacement project in Bulloch County, Georgia (County Project No. E15). The investigation was conducted through two soil test borings (B-01 and B-02) performed on December 1-2, 2025, drilled to depths of 110-116 feet below existing grades near the proposed bridge replacement Bents 1 and 4. The subsurface profile consists of approximately 4 inches of asphaltic concrete surface material, followed by fill soils extending to 5.5 feet, alluvial soils in limited locations, and coastal plain soils (sandy fat clay, poorly graded sand, silty sand, and clayey sand) extending to auger refusal depths. The site is classified as AASHTO LRFD Site Class D, with groundwater measured at approximately 9 feet below the existing surface in Boring B-01. Soil cave-in was observed at depths of 10-16 feet below surface in both borings.
The bridge foundation design utilizes Metal Shell (MS) piles with 45 ksi yield strength at all four bents, with 18-inch diameter piles at end bents (1 and 4) and 24-inch diameter piles at intermediate bents (2 and 3). Design loads range from 225 kips (strength limit state for end bents) to 315 kips (intermediate bents), with driving resistance capacities of 347-521 kips depending on pile size and location. Estimated pile tip elevations range from 101-113 feet (NAVD 88), with scour considerations incorporated for a theoretical 500-year event. The report specifies requirements for Dynamic Pile Analyzer (PDA) testing at three locations (Bent 1 right, Bent 2 left, and Bent 3 right), implementation of epoxy coating for corrosion protection, use of Option 1 friction pile closure plates, and provisions for freeze bearing procedures if dynamic bearing is not achieved within 2 feet of estimated tip elevation. Special provisions address the existing bridge closure due to prior accident damage, existing underground and overhead utility conflicts that must be mitigated during construction, and the erratic pile lengths expected during installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRIDGE FOUNDATION
INVESTIGATION REPORT (LRFD)
CR 153 (Cypress Lake Road) Over Dry Branch Bulloch County, Georgia
PREPARED FOR:
Heath & Lineback Engineers, Inc.
2390 Canton Road Marietta, Georgia 30066
County Project No. E15 NOVA Project No. 10102-2025112
March 4, 2026
P R O F E S S I O N A L | P R A C T I C A L | P R O V E N
3 9 0 0 K e n n e s a w 7 5 P a r k w a y , S u i t e 1 0 0 , K e n n e s a w , G e o r g i a 3 0 1 4 4 t . 7 7 0 . 4 2 5 . 0 7 7 7 / f . 7 7 0 . 4 2 5 . 1 1 1 3 / u s a n o v a . c o m
HEATH & LINEBACK ENGINEERS, INC.
2390 Canton Road Marietta, Georgia 30066
Attention: Randy Boykin, PE, SE, CBI Senior Structural Project Manager
Subject: Bridge Foundation Investigation Report (LRFD) CR 153 (Cypress Lake Road) Over Dry Branch
Bulloch County, Georgia
Dear Mr. Boykin:
NOVA Engineering and Environmental, LLC (NOVA) has completed the referenced Bridge Foundation Investigation (BFI). The results of the Bridge Foundation Investigation with supporting documents are included with this letter. The Bridge Foundation Investigation was performed in general accordance with GDOT requirements as outlined in the GDOT OMAT Geotechnical Manual.
We appreciate being part of the Heath & Lineback Engineers, Inc. team for this important project. If you have questions, please contact us.
Thank you.
Sincerely, NOVA Engineering and Environmental, LLC
Ezequiel Q. Segismundo, P.E. Eric K. Tay, P.E.
Project Engineer Principal Engineer GA P.E. License No. 051012 GA P.E. License No. 022183
Bridge Foundation Investigation (LRFD)
Bulloch County, Georgia County Project No. E15
NOVA Project No 10102-2025112
LOCATION See attached Figures 1 and 2 in Appendix B for project site location and topographic map, respectively.
GENERAL INFORMATION
GEOLOGIC FORMATION Based on the Regional Geology Map, the site is underlain by Neogene Undifferentiated Formation of the Georgia Coastal Plain Region. See Figure 3 in Appendix B.
SUBSURFACE FEATURES The subsurface information was obtained from two NOVA soil test borings designated as B-01 and B-02. These test borings with Standard Penetration Testing (SPT) were performed on December 1, 2025, and December 2, 2025, and were drilled to approximated depths ranging from 110 to 116 feet below the existing grades (approximate elevations ranging from 39 to 33 feet). Test borings B-01 and B-02 were drilled from the asphalt roadway surface along CR 153 (Cypress Lake Road) and close to the proposed bridge replacement end Bents 1 and 4, respectively.
At the ground surface, approximately 4 inches of asphaltic concrete was encountered in test borings B-01 and B-02.
Graded Aggregate Base (GAB) course material was not observed.
Below the surficial asphaltic concrete in test boring B-01 and B-02, existing fill soils described primarily as silty SAND and poorly graded SAND with silt were encountered to approximate depths of 5.5 feet below the existing grades (approximate elevation of 144 feet). The uncorrected SPT resistances ranged from 14 to 20 blows per foot (bpf).
Alluvial soils described primarily as silty SAND with uncorrected SPT resistance of 8 bpf was encountered below the existing fill soils in test boring B-02 to an approximate depth of 8 feet below the existing grade (approximate elevation of 141 feet).
Beneath the existing fill soils in test boring B-01 and beneath the alluvial soils in test boring B-02, coastal plain soils described primarily as sandy fat CLAY, poorly graded SAND with silt, silty SAND and clayey SAND were encountered to approximate depths ranging from 110 to 116 feet below the existing grades (approximate elevations ranging from 39 to 33 feet). The uncorrected SPT resistances ranged from Weight of Hammer (WOH) to 50 blows for 1 inch of penetration.
BFI – CR 153 (Cypress Lake Road) Over Dry Branch March 4, 2026 Bulloch County, Georgia (County Project No. E15) NOVA Project No. 10102-2025112
Auger refusal materials were encountered test borings B-01 and B-02 at approximate depths ranging from 110 to 116 feet below the existing grades (approximate elevations ranging from 39 to 33 feet). Auger refusal materials are very hard or very dense material which cannot be penetrated by a power auger.
Groundwater during drilling and after the completion of drilling were not recorded due to the presence of injected drilling fluids from mud rotary drilling method. The groundwater level after 24 hours of drilling completion was measured in test boring B-01 at an approximate depth of 9 feet below the existing ground surface (approximate elevation of 140 feet).
Upon completion of drilling and 24-hour groundwater measurement, soil cave-in was measured in test borings B-01 and B-02 at approximate depths ranging from 10 to 16 feet below the existing ground surface (approximate elevations ranging from 139 to 133 feet).
For additional information, see Appendix B for Figures 4-1 to 4-3 (Boring Location Plans), Appendix C for Subsurface Profiles, Test Boring Record Summary and Test Boring Records, and Appendix D for Laboratory Testing Results.
SITE CLASSIFICATION We recommend a site class of D per AASHTO LRFD (9th Edition, 2020) 3.10.3.1.
Bents Pile Bent (Type)
1 through 4 MS - Metal Shell (Fy = 45 ksi)
1.1 -- PILE PROPERTIES
Pile Type
Pile Size (in)
Nominal Compression
Stress (ksi)
Nominal Tension Stress (ksi) Diameter Wall Thickness
MS 18 0.3125 40.5 40.5
MS 24 0.5000 40.5 40.5
1.2 -- DESIGN LOADS
Bents Foundation
Type
Maximum Factored Strength Limit State
Load (kips)
Maximum Factored Service Limit State
Load (kips)
Factored Extreme Event I Limit State
Load (kips)
1 Pile End Bent 225 155 110 2 Pile Bent 315 240 265 3 Pile Bent 315 240 265 4 Pile End Bent 225 155 110
2.0 -- FOUNDATION DESIGN
2.1 -- PILE FOUNDATION DESIGN
Bents Pile Type Size (in) Down Drag **
(kips) Scour
(kips)
Driving Resistance1 *
(kips)
1 MS 18 0 0 347
2 MS 24 - 36 521
3 MS 24 - 15 500
4 MS 18 0 0 347
Note1: Driving resistance is equivalent to pile capacity during construction. Post-construction pile capacity is reduced by the scour load if a 500-year scour event occurs.
3.0 -- FOUNDATION ELEVATIONS
Bents Reference Boring Minimum Pile Tip (feet-NAVD 88)
Estimated Pile Tip (feet-NAVD 88)
1 B-01 113 101 2 B-01 113 101 3 B-02 101 101 4 B-02 101 101
1.0 -- FOUNDATION RECOMMENDATIONS
4.0 -- GENERAL NOTES
Elevations Control Point No. PNT #25004 (rebar with cap) located approximately at
STA. 104+47.01, 27.44 ft. RT. with elevation of 143.95 feet-NAVD88 and coordinates at 32.393798° and -81.856093° was used in determining the existing grade elevations at locations of as-drilled test borings B-01 and B-02.
Waiting Period None required.
Staged Construction None required.
Theoretical Scour Appears feasible for the material encountered
As Built Foundation
Information The as-built foundation information should be forwarded to the Bulloch County Engineering Department upon completion of the foundation system.
Special Problems The existing bridge has been closed to traffic due to sustained damage from a car accident. As such, test borings were not drilled at the proposed bridge replacement Bent 2 and 3 locations due to safety concerns.
Existing underground and overhead utilities were identified at and adjacent to the existing bridge and should be considered during construction to mitigate any potential conflicts and associated risks.
4.1 -- PILE FOUNDATION NOTES
PDO Driving resistance after minimum tip elevations are achieved in conjunction with GDOT Standard Specification 520.3.05.D.2 and Special Provision 523 Dynamic Pile Testing. For this bridge, a total of three PDA tests will be required. Perform one PDA test each at Bent 1 right, Bent 2 left, and Bent 3 right.
* Nominal Bearing
Resistance of Single Pile
Driving resistance is based on the following field verification method and resistance factor φdyn AASHTO LRFD 2020 (10.5.5.2.3-1):
Resistance Determination Method Resistance Factor Driving criteria established by dynamic testing of at least two piles per site condition, but no less than 2% of the production piles.
0.65
**Downdrag Downdrag is not anticipated for the piles at the end bents since these bents will be constructed after removing a section of the existing approach embankment. Also, downdrag is not anticipated at intermediate pile bents.
Drivability Drivability analyses have been completed for the piles at Bents 1 through
4 to their respective estimated tips using DELMAG D 30-23 hammer.
Freeze Bearing
Piles should not be overdriven at this site. If dynamic bearing has not been achieved by 2 feet above the estimated tip elevation, pile driving should be stopped for a minimum of 24 hours and re-started with a warm hammer to check for freeze bearing.
Pile Protection
All exposed MS piles should be painted with a 2P epoxy coating as protection against corrosion.
Metal Shell Piles Metal Shell piles are recommended for use at this site due to the potential for excessive pile length required for PSC piles. PSC piles that are too long are not easily handled or driven. In addition, hard driving is anticipated through dense soil layers and this presents potential problems of overstressing and cracking PSC piles. We also understand that MS piles were used as the foundation type for the nearby (approximately 0.5-mile East) CR 145 (Cypress Lake Road) Over Wateringhole Branch bridge.
Closure Plates Option 1 (friction pile) closure plates should be used on all metal shell piles.
Special Problems Erratic pile lengths can be expected.
5.0 – QA / QC
Prepared By:
Ezequiel Q. Segismundo, P.E.
Project Engineer GA P.E. License No. 051012
Naveen S. Thakur, P.E.
Principal Engineer GA P.E. License No. 051185
Reviewed By:
Daniel C. Brahana, P.E.
GA P.E. License No. 018053
Eric K. Tay. P.E.
GA P.E. License No. 022183
Appendix A GDOT Special Provision
• Special Provision Section 523 – Dynamic Pile Testing
Appendix B Figures and Maps
• Figure 1 – Site Location Map
• Figure 2 – Topographic Map
• Figure 3 – Regional Geology Map
• Figures 4-1 to 4-3 – Boring Location Plans
Appendix C Subsurface Data
• Subsurface Profile
• Test Boring Record Summary
• Key to Symbols and Classifications
• Test Boring Records
Appendix D Laboratory Testing Results
• Laboratory Testing Summary
• Atterberg Limits and Mechanical Sieve Analyses Results
Appendix E Seismic Site Class Calculations
Appendix F Foundation Design Loads
Appendix G Axial Pile Resistance Analyses (APILE)
Appendix H WEAP Analyses (GRLWEAP)
Appendix I Drill Rig Energy Calibration
Appendix J Important Information about this Geotechnical Engineering Report
APPENDIX A
GDOT SPECIAL PROVISION
• Special Provision Section 523 – Dynamic Pile Testing (PDA)
Revised February 15, 2016
2.14
DEPARTMENT OF TRANSPORTATION
STATE OF GEORGIA
SPECIAL PROVISION
SECTION 523 - DYNAMIC PILE TESTING
523.1 General Description
The work consists of performing dynamic pile testing using the Pile Driving Analyzer (PDA) to monitor the driving of piles with accelerometer and strain gauges attached to the piles. Piles to be dynamically tested will be identified in the Special Provision or on the Plans. Prior to pile driving, the Engineer will determine production or test piles to be dynamically tested. Perform the dynamic pile testing in accordance with ASTM D4945-12.
Take dynamic measurements during driving of any required piles. Drive the pile as shown in the Special Provisions or on the Plans.
523.2 Materials
Furnish measuring instruments for dynamic pile testing. Attach instruments near the top of the piles with bolts placed in drilled holes. Furnish materials, labor and equipment necessary for installation of the instruments.
523.3 Construction Requirements
Measure wave speed prior to driving piles. Wave speed measurements will not be required for Steel H piles or metal shell piles. When wave speed measurements are performed, place the piles in a horizontal position not in contact with other piles.
Perform dynamic pile testing during driving. Modify the driving to reduce the stress and/or eliminate the damage, should the recommended stress level be exceeded or if damage occurs (determined visually or as indicated by the instrumentation).
Do not exceed the following maximum driving stresses, as determined by the dynamic pile testing:
1. For Steel piles:
0.9 Fy, where Fy = Yield strength of steel
2. For Prestressed Concrete Piles:
Compression:
Tension in Normal Environments:
Tension in Severe Corrosive Environments:
where;
σ dr = maximum allowed driving stress, ksi f ′c= specified minimum 28-day compressive strength of concrete, ksi f pe= effective prestress in concrete, ksi, (after all losses) at the time of driving taken as
0.78 times the initial prestress force
Re-drive friction piles that do not obtain bearing after a freeze period of a minimum of 24 hours or for a period designated on the Plans, whichever is longer. Reset the gauges if required. Re-strike the pile with a warm hammer until a maximum penetration of 3 inches (76 mm) or 40 blows is reached, whichever occurs first. The Engineer may modify the Pile Driving Objective based on the results of the PDA work.
Provide two weeks’ notice prior to the driving of designated piles and cooperate with the Engineer in connection with the performance of Dynamic Pile Testing.
Provide a complete report consisting of but not limited to PDA field monitoring data, results of CAPWAP computer analyses, and recommendations such as pile lengths, hammer fuel setting, and valid driving criteria. Valid driving criteria is defined as having the required hammer having a hammer set greater than 3 blows per inch and less than 10 blows per inch at the driving resistance for that pile. Submit the report electronically in PDF format and the electronic data files of the PDA analysis and CAPWAP to the Geotechnical Bureau and allow seven (7) calendar days for review and approval before proceeding with driving production piles.
523.4 Measurement
The Dynamic Pile Tests performed in accordance with these Specifications will be counted separately for payment. (Refer to plans summary sheet for the required amount of PDA testing.)
523.5 Payment
The Dynamic Pile Test completed and accepted will be paid for at the Contract unit Price. This payment will be full compensation for all costs of complying with this specification, including incidentals, additional work, and any delays incurred in conjunction therewith.
Payment will be made under:
𝜎𝜎𝑑𝑑𝑑𝑑 = (0.85𝑓𝑓′𝑐𝑐 − 𝑓𝑓𝑝𝑝𝑝𝑝) 𝜎𝜎𝑑𝑑𝑑𝑑 = (0.095�𝑓𝑓′𝑐𝑐 + 𝑓𝑓𝑝𝑝𝑝𝑝) 𝜎𝜎𝑑𝑑𝑑𝑑 = 𝜑𝜑𝑑𝑑𝑑𝑑𝑓𝑓𝑝𝑝𝑝𝑝
Item No. 523. Dynamic Pile Test . . . . . . . . . . . . . . . . . . . . . . . . . . . Per Each
APPENDIX B
FIGURES AND MAPS
• Figure 1 – Site Location Map
• Figure 2 – Topographic Map
• Figure 3 – Regional Geology Map
• Figures 4-1 to 4-3 – Boring Location Plans
FIGURE 1 – SITE LOCATION MAP
SOURCE: Google Earth Aerial Photos
Date: Map Data @ 2025 SCALE: As Shown
CR 153 (Cypress Lake Road) Over Dry Branch
Bulloch County, Georgia
Project Site
FIGURE 2 – TOPOGRAPHIC MAP
SOURCE: USGS National Map Advanced
Viewer 7.5 Minute Topo Nevils, Pulaski, Register &
Statesboro GA 2020 Date Retrieved: 12/01/2025
SCALE: As Shown
CR 153 (Cypress Lake Road) Over Dry Branch
Bulloch County, Georgia
0 1000 2500 5000
FEET
17º 18º
82º
83º
10000
84º
85º
86º
19º 20º
87º
21º
FIGURE 3 - REGIONAL GEOLOGY MAP
SOURCE: Geologic Map of Georgia, Georgia Department of Natural Resources, 1976 SCALE: As Shown
CR 153 (Cypress Lake Road) Over Dry Branch
Bulloch County, Georgia
0 1 5 10 miles
AEOLIAN SAND DEPOSTIS
parabolic dunes (Qpd) formless deposits (Qas)
PLEISTOCENE-PLIOCENE
SANDS AND GRAVELS
NEOGENE UNDIFFERENTIATED
FIGURE 4-1 – BORING LOCATION PLANS
STA. 99+80.00 to STA. 105+50.00
SCALE: As Shown PROVIDED BY: Heath & Lineback Engineers, Inc.
TITLE: Construction Plan (13-0001) DATE: October 13, 2025
APPROX. AS-DRILLED LOCATIONS OF NOVA BFI BORINGS
FIGURE 4-2 – BORING LOCATION PLANS
STA. 105+50.00 to STA. 108+70.00
SCALE: As Shown PROVIDED BY: Heath & Lineback Engineers, Inc.
TITLE: Construction Plan (13-0002) DATE: October 13, 2025
FIGURE 4-3 – BORING LOCATION PLANS
STA. 103+38.00 to STA. 104+66.00
SCALE: As Shown PROVIDED BY: Heath & Lineback Engineers, Inc.
TITLE: Preliminary Layout (35-0001) DATE: October 2025
APPENDIX C
SUBSURFACE DATA
• Subsurface Profile
• Test Boring Record Summary
• Key to Symbols and Classifications
• Test Boring Records nt
E le va tio n in
F ee t-N A
V D
E levation in Feet-N A
V D
AR – Auger Refusal;
Paving
FILL
Alluvial Soils clayey SAND (SC) silty SAND (SM)
FAT CLAY (CH)
Poorly Graded SAND with silt (SP-SM)
CR 153 (Cypress Lake Road) Over Dry Branch Bulloch County, Georgia
TEST BORING RECORD SUMMARY
Bridge Foundation Investigation
Bulloch County, Georgia
Notes: Elevations and Depths should be considered as approximate; GW – Groundwater; N/M – Not Measured; N/E – Not Encountered;
* = measured groundwater readings and elevation after 24-hours;
BORING
NUMBER
EXISTING
GROUND
SURFACE
ELEVATION
(ft., NAVD88)
DEPTH TO GW *
(ft.)
APPROXIMATE
ELEVATION OF
GW *
(ft., NAVD88)
DEPTH TO
FILL SOILS
(ft.)
APPROXIMATE
ELEVATION OF
FILL
(ft., NAVD88)
DEPTH TO
ALLUVIAL SOILS
(ft.)
APPROXIMATE
ELEVATION OF
ALLUVIUM
(ft., NAVD88)
DEPTH TO
COASTAL PLAIN
SOILS
(ft.)
APPROXIMATE
ELEVATION OF
COASTAL PLAIN
(ft., NAVD88)
DEPTH TO
AUGER
REFUSAL
(ft.)
APPROXIMATE
ELEVATION OF
AUGER
REFUSA:L
(ft., NAVD88)
DEPTH TO
BORING
TERMINATION
(ft.)
APPROXIMATE
ELEVATION OF
BORING
TERMINATION
(ft., NAVD88)
B-01 149.1 9.0 140.1 0.3 148.8 N/E -- 5.5 143.6 110.0 39.1 110.0 39.1
B-02 149.3 N/M -- 0.3 149.0 5.5 143.8 8.0 141.3 116.0 33.3 116.0 33.3
KEY TO SYMBOLS AND CLASSIFICATIONS
DRILLING SYMBOLS
100/2”
NX, NQ
REC
RQD
MC
N/E
N/M
C
Standard Penetration Testing Sample
Undisturbed Sample (UD)
Auger without Sampling Rock Core Sample
Standard Penetration Resistance (ASTM D1586)
Dynamic Cone Penetrometer (DCP) Resistance Water Table at least 24 Hours after drilling
Water Table one (1) Hour or less after drilling
Number of Blows (100) to Drive the Spoon a Number of Inches (2)
Core Barrel Sizes: 2⅛- and 2-Inch Diameter Rock Core, Respectively
Percentage of Rock Core Recovered
Rock Quality Designation - Percentage of Recovered Core Segments 4 or more Inches Long
Loss of Drilling Water
Moisture Content Test Performed
Not Encountered
Not Measured
Caving
STRATA SYMBOLS
Silt - ML
Low Plasticity
Clay - CL
High Plasticity
Paving
Gravel / Graded
Aggregate Base
Fill
Topsoil
Alluvium
Poorly Graded
Sand - SP
Well Graded
Sand - SW
Clay - CH
Partially Weathered
Rock (PWR)
Rock
Elastic Silt - MHSilty Sand - SM
Clayey Sand - SC
Poorly graded silty, clayey sand - SM/SC
Clayey Sand and Gravel - SC/GC
Silty Sand and Gravel - SM/GM
�Z/>>/E'�WZK���hZ�^
^Žŝů� ƐĂŵƉůŝŶŐ� ĂŶĚ� ƐƚĂŶĚĂƌĚ� ƉĞŶĞƚƌĂƚŝŽŶ� ƚĞƐƚŝŶŐ� ƉĞƌĨŽƌŵĞĚ� ŝŶ� ĂĐĐŽƌĚĂŶĐĞ� ǁŝƚŚ� �^dD� �ϭϱϴϲͲϲϳ͘� dŚĞ� ƐƚĂŶĚĂƌĚ� ƉĞŶĞƚƌĂƚŝŽŶ�ƌĞƐŝƐƚĂŶĐĞ�ŝƐ�ƚŚĞ�ŶƵŵďĞƌ�ŽĨ�ďůŽǁƐ�ŽĨ�Ă�ϭϰϬ�ƉŽƵŶĚ�ŚĂŵŵĞƌ�ĨĂůůŝŶŐ�ϯϬ�ŝŶĐŚĞƐ�ƚŽ�ĚƌŝǀĞ�Ă�ϮͲŝŶĐŚ�K͘�͕͘�ϭбͲ ŝŶĐŚ� /͘�͘� ƐƉůŝƚ� ƐƉŽŽŶ� ƐĂŵƉůĞƌ� ŽŶĞ� ĨŽŽƚ͘� �ŽƌĞ� ĚƌŝůůŝŶŐ�ƉĞƌĨŽƌŵĞĚ�ŝŶ� ĂĐĐŽƌĚĂŶĐĞ� ǁŝƚŚ� �^dD� �ϮϭϭϯͲϬϴ͘� dŚĞ� ƵŶĚŝƐƚƵƌďĞĚ� ƐĂŵƉůŝŶŐ�ƉƌŽĐĞĚƵƌĞ� ŝƐ�ĚĞƐĐƌŝďĞĚ�ďLJ��^dD��ϭϱϴϳͲϬϴ� ;ϮϬϭϮͿ͘�hŶůĞƐƐ�ŽƚŚĞƌ�ĂƌƌĂŶŐĞŵĞŶƚƐ� ĂƌĞ�ŵĂĚĞ͕� EKs��ǁŝůů�ĚŝƐƉŽƐĞ�ŽĨ�Ăůů�ƐŽŝů�ĂŶĚ�ƌŽĐŬ�ƐĂŵƉůĞƐ�ƌĞŵĂŝŶŝŶŐ�Ăƚ�ƚŚĞ�ƚŝŵĞ�ŽĨ�ƌĞƉŽƌƚ�submission͘
50/2" (50)
DRILLING PROCEDURES
Soil sampling and standard penetration testing performed in general accordance with ASTM D1586-18e1. The standard penetration resistance (N-value) is the number of blows of a 140 pound hammer falling 20 inches to drive a 2-inch O.D., 1.375-inch I.D. split-barrel sampler one foot. Core drilling performed in general accordance with ASTM D2113-14. The undisturbed sampling procedure is described by ASTM D1587-15. Unless other arrangements are made, NOVA will dispose of all soil and rock samples remaining at the time of report submission.
Fluid N/E Not Encountered N/M Not Measured
C Boring Cave-in Depth
WOH Weight of Hammer
Water Table 1 Hour or less after drilling
Bulk Sample
100/2”
NX, NQ
REC
RQD
MC
N/E
N/M
C
Standard Penetration Resistance (ASTM D1586)
Dynamic Cone Penetrometer (DCP) Resistance Water Table at least 24 Hours after drilling
Water Table one (1) Hour or less after drilling
Number of Blows (100) to Drive the Spoon a Number of Inches (2)
Core Barrel Sizes: 2⅛- and 2-Inch Diameter Rock Core, Respectively
Percentage of Rock Core Recovered
Rock Quality Designation - Percentage of Recovered Core Segments 4 or more Inches Long
Loss of Drilling Water
Moisture Content Test Performed
Not Encountered
Not Measured
Caving
50/2" (50)
Fluid N/E Not Encountered N/M Not Measured
C Boring Cave-in Depth
WOH Weight of Hammer
Water Table 1 Hour or less after drilling
�KZZ�>�d/KE�K&�W�E�dZ�d/KE�Z�^/^d�E���t/d,�Z�>�d/s����E^/dz��E���KE^/^d�E�z
EƵŵďĞƌ�ŽĨ��ůŽǁƐ͕�͞E͟ �ƉƉƌŽdžŝŵĂƚĞ ZĞůĂƚŝǀĞ��ĞŶƐŝƚLJ
^�E�^
Ϭ�ʹ ϰ ϱ�ʹ ϭϬ ϭϭ�ʹ ϯϬ ϯϭ�ʹ ϱϬ KǀĞƌ�ϱϬ sĞƌLJ�>ŽŽƐĞ
>ŽŽƐĞ
DĞĚŝƵŵ��ĞŶƐĞ
�ĞŶƐĞ
sĞƌLJ��ĞŶƐĞ
EƵŵďĞƌ�ŽĨ��ůŽǁƐ͕�͞E͟ �ƉƉƌŽdžŝŵĂƚĞ �ŽŶƐŝƐƚĞŶĐLJ
^/>d^
ĂŶĚ
�>�z^
Ϭ�ʹ Ϯ sĞƌLJ�^ŽĨƚ ϯ�ʹ ϰ ^ŽĨƚ ϱ�ʹ ϴ &ŝƌŵ ϵ�ʹ ϭϱ ^ƚŝĨĨ ϭϲ�ʹ ϯϬ sĞƌLJ�^ƚŝĨĨ ϯϭ�ʹ ϱϬ ,ĂƌĚ KǀĞƌ�ϱϬ sĞƌLJ�,ĂƌĚ
^K/>��>�^^/&/��d/KE��,�Zd�
�K�Z^��'Z�/E�� ^K/>^
'Z�s�>^ �ůĞĂŶ�'ƌĂǀĞů ůĞƐƐ�ƚŚĂŶ�ϱй�ĨŝŶĞƐ
't tĞůů�ŐƌĂĚĞĚ�ŐƌĂǀĞů 'W WŽŽƌůLJ�ŐƌĂĚĞĚ�ŐƌĂǀĞů
'ƌĂǀĞůƐ�ǁŝƚŚ�&ŝŶĞƐ ŵŽƌĞ�ƚŚĂŶ�ϭϮй�ĨŝŶĞƐ
'D ^ŝůƚLJ�ŐƌĂǀĞů '� �ůĂLJĞLJ�ŐƌĂǀĞů
^�E�^ �ůĞĂŶ�^ĂŶĚ ůĞƐƐ�ƚŚĂŶ�ϱй�ĨŝŶĞƐ
^t tĞůů�ŐƌĂĚĞĚ�ƐĂŶĚ ^W WŽŽƌůLJ�ŐƌĂĚĞĚ�ƐĂŶĚ
^ĂŶĚƐ�ǁŝƚŚ�&ŝŶĞƐ ŵŽƌĞ�ƚŚĂŶ�ϭϮй�ĨŝŶĞƐ
^D ^ŝůƚLJ�ƐĂŶĚ ^� �ůĂLJĞLJ�ƐĂŶĚ
&/E��'Z�/E�� ^K/>^
^/>d^��E���>�z^ >ŝƋƵŝĚ >ŝŵŝƚ ůĞƐƐ�ƚŚĂŶ�ϱϬ
/ŶŽƌŐĂŶŝĐ �> >ĞĂŶ�ĐůĂLJ D> ^ŝůƚ
KƌŐĂŶŝĐ K> KƌŐĂŶŝĐ�ĐůĂLJ�ĂŶĚ�Ɛŝůƚ ^/>d^��E���>�z^
>ŝƋƵŝĚ�>ŝŵŝƚ ϱϬ�Žƌ�ŵŽƌĞ
/ŶŽƌŐĂŶŝĐ �, &Ăƚ�ĐůĂLJ D, �ůĂƐƚŝĐ�Ɛŝůƚ
KƌŐĂŶŝĐ K, KƌŐĂŶŝĐ�ĐůĂLJ�ĂŶĚ�Ɛŝůƚ ,/',>z�KZ'�E/��
^K/>^ KƌŐĂŶŝĐ�ŵĂƚƚĞƌ͕�ĚĂƌŬ� ĐŽůŽƌ͕�ŽƌŐĂŶŝĐ�ŽĚŽƌ Wd WĞĂƚ
W�Zd/�>��^/���/��Ed/&/��d/KE�
'Z�s�>^ �ŽĂƌƐĞ в�ŝŶĐŚ�ƚŽ�ϯ�ŝŶĐŚĞƐ &ŝŶĞ EŽ͘�ϰ�ƚŽ�в�ŝŶĐŚ
^�E�^ �ŽĂƌƐĞ EŽ͘�ϭϬ�ƚŽ�EŽ͘�ϰ DĞĚŝƵŵ EŽ͘�ϰϬ�ƚŽ�EŽ͘�ϭϬ &ŝŶĞ EŽ͘�ϮϬϬ�ƚŽ�EŽ͘�ϰϬ
^/>d^��E���>�z^ WĂƐƐŝŶŐ�EŽ͘�ϮϬϬ
TEST BORING
RECORD
B-01
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393901
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856453
LOCATION STA. 103+33, 2 ft. LT. ELEVATION 149.13' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/01/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS 9' CAVING 10'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
ASPHALT: Approx. 4 inches FILL: Medium dense brown poorly graded SAND with silt (SP-SM)
COASTAL PLAIN: Medium dense light gray to brown poorly graded SAND with silt (SP-SM)
COASTAL PLAIN: Stiff gray medium to fine sandy FAT CLAY (CH)
COASTAL PLAIN: Medium dense to loose light gray brown poorly graded SAND with silt (SP-SM)
Medium dense gray poorly graded SAND with silt (SP-SM)
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
N
TS
(U
C
O R
R
EC
TE
D
-V
AL
U E)
6-10-10 (20)
4-6-8 (14)
3-6-7 (13)
3-5-6 (11)
4-11-6 (17)
2-4-5 (9)
4-5-9 (14)
3-4-4 (8)
4-7-5 (12)
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
Assumed No Scour at Bent 1
Theoretical 500-year Scour EL. @ 128 feet (Bent 2)
Min. Depth of Pile Tip @ EL. 113 feet (Bents 1 & 2)
B-01
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393901
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856453
LOCATION STA. 103+33, 2 ft. LT. ELEVATION 149.13' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/01/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS 9' CAVING 10'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
Medium dense gray poorly graded SAND with silt (SP-SM) COASTAL PLAIN: Loose to medium dense gray green to yellowish gray fine clayey SAND (SC)
Dense to medium dense gray green fine clayey SAND (SC)
Medium dense to loose gray brown fine clayey SAND (SC)
(No Recovery on SPT Sample taken at a depth of 63.5 to 65.0 feet)
COASTAL PLAIN: Medium dense gray silty medium to fine SAND (SM)
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
C
O R
R
EC
AL
U E)
2-3-5 (8)
3-6-8 (14)
8-19-26 (45)
8-10-13 (23)
5-4-7 (11)
2-4-5 (9)
9-12-14 (26)
7-9-12 (21)
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
Est. Depth of Pile Tip @ EL. 101 feet (Bents 1 & 2)
B-01
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393901
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856453
LOCATION STA. 103+33, 2 ft. LT. ELEVATION 149.13' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/01/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS 9' CAVING 10'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
COASTAL PLAIN: Medium dense gray silty medium to fine SAND (SM)
COASTAL PLAIN: Very dense gray brown clayey medium to fine SAND (SC)
Medium dense gray fine clayey SAND (SC)
Very dense gray brown fine clayey SAND (SC)
COASTAL PLAIN: Very dense gray poorly graded clayey SAND with silt (SP-SM)
Auger Refusal at 110 ft.
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
C
O R
R
EC
AL
U E)
4-6-10 (16)
20-30-50/4"
50/6"
10-14-16 (30)
13-20-50/3"
17-25-42 (67)
50/1"
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
B-02
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393868
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856018
LOCATION STA. 104+68, CL. ELEVATION 149.29' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/02/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS N/M CAVING 16'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
ASPHALT: Approx. 4 inches FILL: Medium dense reddish brown to gray brown silty medium to fine SAND
(SM)
ALLUVIUM: Loose brownish gray silty medium to fine SAND (SM) with organic odor
COASTAL PLAIN: Medium dense to dense light gray silty medium to fine SAND
(SM)
Loose to medium dense light gray silty medium to fine SAND (SM)
COASTAL PLAIN: Very loose light gray clayey fine SAND (SC)
COASTAL PLAIN: Medium dense gray poorly graded SAND with silt (SP-SM)
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
C
O R
R
EC
AL
U E)
5-7-8 (15)
4-5-9 (14)
2-3-5 (8)
5-8-9 (17)
8-16-15 (31)
4-5-4 (9)
7-10-12 (22)
WOH-WOH
WOH
(0)
4-7-14 (21)
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
Assumed No Scour at Bent 4
Theoretical 500-year Scour EL. @ 126 feet (Bent 3)
B-02
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393868
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856018
LOCATION STA. 104+68, CL. ELEVATION 149.29' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/02/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS N/M CAVING 16'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
COASTAL PLAIN: Medium dense gray poorly graded SAND with silt (SP-SM) COASTAL PLAIN: Medium dense to loose green gray to light gray clayey fine
SAND (SC)
COASTAL PLAIN: Medium dense to dense gray silty medium to fine SAND (SM)
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
C
O R
R
EC
AL
U E)
6-8-8 (16)
6-10-15 (25)
4-8-12 (20)
4-10-11 (21)
4-4-5 (9)
5-8-9 (17)
8-12-13 (25)
12-18-20 (38)
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
Min. Depth of Pile Tip @ EL. 101 feet (Bents 3 & 4)
Est. Depth of Pile Tip @ EL. 101 feet (Bents 3 & 4)
B-02
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393868
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856018
LOCATION STA. 104+68, CL. ELEVATION 149.29' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/02/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS N/M CAVING 16'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
COASTAL PLAIN: Medium dense to dense gray silty medium to fine SAND (SM)
Medium dense gray silty medium to fine SAND (SM)
COASTAL PLAIN: Medium dense to dense gray clayey fine SAND (SC)
Very dense gray brown clayey fine SAND (SC)
Dense to very dense gray to green gray clayey fine SAND (SC)
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
C
O R
R
EC
AL
U E)
4-18-10 (28)
4-12-17 (29)
8-12-16 (28)
8-16-26 (42)
50/3"
13-19-30 (49)
17-32-50/2"
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
B-02
PROJECT NAME CR 153 (Cypress Lake Rd.) Over Dry Branch PROJECT NO. 10102-2025112
CLIENT Heath & Lineback Engineers, Inc. (County Project No. E15) LATITUDE 32.393868
PROJECT LOCATION Bulloch County, GA LONGITUDE -81.856018
LOCATION STA. 104+68, CL. ELEVATION 149.29' (NAVD88)
DRILLER Piedmont Environmental Drilling, Inc. (SN D50-442) LOGGED BY J. Powser
DRILLING METHOD Mud Rotary - Auto % ENERGY 84% DATE 12/02/2025
DEPTH TO-WATER INITIAL N/M AFTER 24 HOURS N/M CAVING 16'
EL
EV
AT
IO
N (f t)
D
EP
TH
(f t)
MATERIAL DESCRIPTION
Dense to very dense gray to green gray clayey fine SAND (SC)
Auger Refusal at 116 ft.
G R
AP
H
IC
L
O G
W
AT
ER
L
EV
EL
S (ft
SA
M
PL
E
TY
PE
BL
O
W C
O U
C
O R
R
EC
AL
U E)
50/4"
N-Value Plastic/Liquid Limit (%)
Moisture Content (%) Fines Content (%)
10 20 30 40 50 60 70 80 90
Notes: Boring elevation was determined with reference to PNT#25004 with elevation at 143.95 feet and located at STA. 104+47.01, 27.44 ft.
RT.
This information pertains only to this boring and should not be interpreted as being indicative of the site.
APPENDIX D
LABORATORY TESTING RESULTS
• Laboratory Testing Summary
• Atterberg Limits and Mechanical Sieve
Analysis Results
BO
RI
N G
N O.
SA
M
PL
E
TY
PE
LI
QU
ID
L
IM
IT
PL
AS
TI
C
LI
M
IT
PL
AS
TI
CI
TY
IN
EX
PE
RC
EN
T
FI
ER
#4
PE
RC
EN
T
FI
ER
#2
US
CS
CL
AS
SI
FI
CA
TI
ON
M
OI
ST
UR
E
CO
N
TE
T
3.5 - 5.0 NP NP NP 75.2 8.8 SP-SM 4.7
18.5 - 20.0 74 18 56 85.8 62.9 CH 56.1
43.5 - 45.0 41 19 22 98.2 35.9 SC 27.0
58.5 - 60.0 33 17 16 95.5 34.0 SC 26.3
73.5 - 75.0 NP NP NP 94.1 13.8 SM 31.4
93.5 - 95.0 61 20 41 99.7 46.6 SC 37.0
103.5 - 105.0 NP NP NP 99.4 9.5 SP-SM 24.1
1.0 - 2.5 NP NP NP 82.4 16.8 SM 8.6
6.0 - 7.5 NP NP NP 92.3 13.3 SM 23.3
18.5 - 20.0 NP NP NP 76.5 13.5 SM 25.6
28.5 - 30.0 42 17 25 96.4 28.9 SC 39.4
48.5 - 50.0 36 17 19 99.7 46.7 SC 26.0
58.5 - 60.0 44 20 24 99.1 37.3 SC 36.7
73.5 - 75.0 NP NP NP 82.8 12.2 SM 27.1
93.5 - 95.0 48 20 28 96.8 37.8 SC 32.2
103.5 - 105.0 30 18 12 99.0 27.4 SC 22.0
Note : "NP" denotes the material as "Non-Plastic"; SS - Split Spoon Sample;
B-01/SS
B-02/SS
LABORATORY TESTING SUMMARY
NOVA Project No. 10102-2025112
CR 153 (Cypress Lake Rd.) Over Dry Branch
Bulloch County, Georgia County Project No. E15
Bridge Foundation Investigation
MECHANICAL SIEVE ANALYSES AND ATTERBERG LIMITS TEST RESULTS
SA
M
PL
E
D
EP
TH
(ft
Tested By: GH Checked By: MLS
LIQUID AND PLASTIC LIMITS TEST REPORT
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 3.5-5.0 ft. Sample Number: 2
Brown poorly graded SAND with silt NP NP NP 75.2 8.8 SP-SM
10102-2025112 Heath & Lineback Engineers, Inc.
12/29/25
CR 153 (Cypress Lake Rd.) Over Dry Branch
Tested By: LY Checked By: MLS
Particle Size Distribution Report
ASTM D6913
PE
RC
EN
T
FI
NE
R
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.2 24.6 66.4 8.8 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 3.5-5.0 ft.
Sample Number: 2
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Brown poorly graded SAND with silt
3/8 #4
#10 #20 #40 #60
#100 #140 #200
100.0 100.0
99.8 97.1 75.2 43.7 20.4 12.7 8.8
NP NP NP
0.6140 0.5346 0.3264
0.2790 0.1899 0.1212
0.0848 3.85 1.30
SP-SM A-3
NMC = 4.7%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 12/18/25
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 18.5-20.0 ft. Sample Number: 6
Gray medium to fine sandy fat CLAY 74 18 56 85.8 62.9 CH
10102-2025112 Heath & Lineback Engineers, Inc.
12/27/25
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.0 14.2 22.9 62.9 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 18.5-20.0 ft.
Sample Number: 6
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Gray medium to fine sandy fat CLAY
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0 100.0
97.3 85.8 77.4 67.6 63.6 62.9
18 74 56
0.5370 0.4042
CH A-7-6(32)
NMC = 56.1%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 43.5-45.0 ft. Sample Number: 11
Yellowish gray clayey fine SAND 41 19 22 98.2 35.9 SC
10102-2025112 Heath & Lineback Engineers, Inc.
12/19/25
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.1 1.7 62.3 35.9 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 43.5-45.0 ft.
Sample Number: 11
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Yellowish gray clayey fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0
99.9 99.0 98.2 96.5 67.8 42.8 35.9
19 41 22
0.2079 0.1918 0.1349 0.1189
SC A-7-6(3)
NMC = 27.0%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 58.5-60.0 ft. Sample Number: 14
Gray clayey fine SAND 33 17 16 95.5 34.0 SC
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.1 4.4 61.5 34.0 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 58.5-60.0 ft.
Sample Number: 14
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Gray clayey fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0
99.9 97.2 95.5 93.0 72.3 43.7 34.0
17 33 16
0.2184 0.1906 0.1292 0.1158
SC A-2-6(1)
NMC = 26.3%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 73.5-75.0 ft. Sample Number: 17
Gray silty medium to fine SAND NP NP NP 94.1 13.8 SM
10102-2025112 Heath & Lineback Engineers, Inc.
12/18/25
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.0 5.9 80.3 13.8 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 73.5-75.0 ft.
Sample Number: 17
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Gray silty medium to fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0 100.0
98.1 94.1 85.8 47.0 20.1 13.8
NP NP NP
0.2826 0.2459 0.1755
0.1558 0.1227 0.0825
SM A-2-4(0)
NMC = 31.4%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 93.5-95.0 ft. Sample Number: 21
Gray clayey fine SAND 61 20 41 99.7 46.6 SC
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.0 0.3 53.1 46.6 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 93.5-95.0 ft.
Sample Number: 21
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Gray clayey fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0 100.0
99.9 99.7 99.4 79.1 53.8 46.6
20 61 41
0.1829 0.1665 0.1170 0.0942
SC A-7-6(14)
NMC = 37.0%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-01 Depth: 103.5-105.0 ft. Sample Number: 23
Gray poorly graded SAND with silt NP NP NP 99.4 9.5 SP-SM
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.0 0.6 89.9 9.5 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-01 Depth: 103.5-105.0 ft.
Sample Number: 23
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Gray poorly graded SAND with silt
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0 100.0
99.8 99.4 89.8 20.5 11.0
9.5
NP NP NP
0.2508 0.2349 0.1971
0.1858 0.1635 0.1367
0.0938 2.10 1.45
SP-SM A-3
NMC = 24.1%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 1.0-2.5 ft. Sample Number: 1
Reddish brown silty medium to fine SAND NP NP NP 82.4 16.8 SM
10102-2025112 Heath & Lineback Engineers, Inc.
12/22/25
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.1 17.5 65.6 16.8 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-02 Depth: 1.0-2.5 ft.
Sample Number: 1
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Reddish brown silty medium to fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0
99.9 97.1 82.4 58.6 32.5 21.5 16.8
NP NP NP
0.5551 0.4612 0.2573
0.2117 0.1407
SM A-2-4(0)
NMC = 8.6%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
770-425-0777 12/22/25
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 6.0-7.5 ft. Sample Number: 3
Brownish gray silty medium to fine SAND NP NP NP 92.3 13.3 SM
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.1 7.6 79.0 13.3 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-02 Depth: 6.0-7.5 ft.
Sample Number: 3
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Brownish gray silty medium to fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0
99.9 98.5 92.3 73.2 36.0 20.4 13.3
NP NP NP
0.3866 0.3273 0.2065
0.1823 0.1344 0.0823
SM A-2-4(0)
NMC = 23.3%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 18.5-20.0 ft. Sample Number: 6
Light gray silty medium to fine SAND NP NP NP 76.5 13.5 SM
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.3 23.2 63.0 13.5 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-02 Depth: 18.5-20.0 ft.
Sample Number: 6
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Light gray silty medium to fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0
99.7 96.7 76.5 31.4 16.6 14.4 13.5
NP NP NP
0.5873 0.5070 0.3468
0.3133 0.2439 0.1294
SM A-2-4(0)
NMC = 25.6%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 28.5-30.0 ft. Sample Number: 8
Light gray clayey fine SAND 42 17 25 96.4 28.9 SC
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.1 3.5 67.5 28.9 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-02 Depth: 28.5-30.0 ft.
Sample Number: 8
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Light gray clayey fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0
99.9 99.6 96.4 88.6 68.0 39.9 28.9
17 42 25
0.2647 0.2214 0.1351
0.1210 0.0779
SC A-2-7(2)
NMC = 39.4%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 48.5-50.0 ft. Sample Number: 12
Light gray clayey fine SAND 36 17 19 99.7 46.7 SC
10102-2025112 Heath & Lineback Engineers, Inc.
12/23/25
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.0 0.3 53.0 46.7 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-02 Depth: 48.5-50.0 ft.
Sample Number: 12
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Light gray clayey fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0 100.0 100.0
99.7 98.5 78.8 55.0 46.7
17 36 19
0.1868 0.1687 0.1154 0.0897
SC A-6(5)
NMC = 26.0%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 58.5-60.0 ft. Sample Number: 14
Light gray clayey fine SAND 44 20 24 99.1 37.3 SC
10102-2025112 Heath & Lineback Engineers, Inc.
12/23/25
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium
% Sand
Fine Silt
% Fines
Clay
0.0 0.0 0.0 0.0 0.9 61.8 37.3 in in in
1½ in in
¾ in
½ in
3/ in
#4 #1
#2
#3
#4
#6
#1
#1
#2
Test Results (ASTM D6913) Material Description
Atterberg Limits
Coefficients
Classification
Test Remarks
Sample Date:
Source of Sample: B-02 Depth: 58.5-60.0 ft.
Sample Number: 14
Client:
Project:
Project No: Date Tested
Sieve Size or
Diam. (mm.)
Finer
Spec.*
Out of Spec.
Pct.
of
Fines
Light gray clayey fine SAND
3/8 #4
#10 #20 #40 #60 #100 #140 #200
100.0 100.0 100.0
99.9 99.1 96.8 72.3 44.2 37.3
20 44 24
0.2024 0.1840 0.1293 0.1156
SC A-7-6(4)
NMC = 36.7%
Heath & Lineback Engineers, Inc.
CR 153 (Cypress Lake Rd.) Over Dry Branch
10102-2025112
PL= LL= PI=
D90= D85= D60= D50= D30= D15= D10= Cu= Cc=
USCS= AASHTO=
* (no specification provided)
NOVA ENGINEERING
PL
AS
TI
CI
TY
IN
DE
X
LIQUID LIMIT
0 10 20 30 40 50 60 70 80 90 100 110
CL-ML
CL o r O
L
CH o r O
H
ML or OL MH or OH
Dashed line indicates the approximate upper limit boundary for natural soils
MATERIAL DESCRIPTION LL PL PI %<#40 %<#200 USCS
Project No. Client: Remarks:
Project:
NOVA ENGINEERING
Kennesaw, Georgia
770-425-0777 Date Tested
Source of Sample: B-02 Depth: 73.5-75.0 ft. Sample Number: 17
Gray silty medium to fine SAND NP NP NP 82.8 12.2 SM
10102-2025112 Heath & Lineback Engineers, Inc.
ASTM D6913
PE
RC
EN
T
FI
N
ER
GRAIN SIZE - mm.
0.0010.010.1110100
% +3" Coarse
% Gravel
Fine Coarse Medium