This pre-solicitation notice announces an upcoming solicitation to replace an air handling unit at the Jesse Brown VA Medical Center in Chicago, Illinois. The project involves replacing the failed S10C air handling unit that serves the vascular lab, supply chain management, and urology departments. The work includes providing all tools, materials, labor, and supervision to complete the HVAC replacement and any other required trades work. The solicitation will be set aside for service-disabled veteran-owned small businesses and will be posted on April 9, 2021 on SAM.gov, with bids due on June 8, 2021. A pre-bid site visit will also be held. The project value is estimated between $1-2 million. The NAICS code is 238220 for plumbing, heating, and air conditioning contractors, with a size standard of $16.5 million. Offerors must represent that they are an eligible SDVOSB at the time of submission.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

100% Bid Documents Jesse Brown VA Medical Center S10C AHU Replacement VA Project # 537‐18‐142

February 19, 2021 www.atigroupinc.com www.c2ae.com

S10C AHU Replacement

Department of Veterans Affairs

VA Project # 537‐18‐142 i February 19, 2021

TABLE OF CONTENTS

EXECUTIVE SUMMARY

PHASING PLAN

ASBESTOS REPORT

INFECTION AND DUST CONTROL MEASURES

SYSTEM NARRATIVES

Existing System Condition

Architectural

Mechanical Design

Plumbing

Structural

APPENDIX

Load Calculations

Mechanical Equipment Cutsheets

Submittals Register

Department of Veterans Affairs

VA Project # 537‐18‐142 1 February 19, 2021

EXECUTIVE SUMMARY

The goals of this project are to provide fast track design and construction to replace the existing S10C unit that serves a portion of First Floor Urology, Third Floor Offices and Fifth Floor Vascular Lab. The emphasis of the project is: ensuring the existing suite meet the VA Mechanical Guides for the existing space and type. This includes dry bulb temperature, wet bulb temperature (humidity), pressure differential, filtration and new open protocol BACnet controls.

Department of Veterans Affairs

VA Project # 537‐18‐142 2 February 19, 2021

PHASING PLAN

Description Duration

Pre‐Construction

1. Materials and Equipment submittal and review 3 weeks

2. Materials and Equipment procurement 2‐12 weeks

Phase 1

1. Install roof mounted return fan (RF‐S10C) and exterior RA ductwork. 3 weeks

2. First Floor Urology 4 weeks

a. Demolition of ceilings, lighting and ductwork.

b. Switch ductwork to S10B

c. Install new VAV boxes & control

d. Install new CV boxes & control

e. Reheat coil piping

f. Testing, Adjusting and Balancing.

g. Install new ceilings and lighting

Phase 2

1. AHU‐ S10C Replacement 3‐day weekend

2. Replace exterior supply air ductwork 3‐day weekend

3. Install AHU‐S10C controls. 3 weeks

Phase 3

1. Fifth Floor Vascular Lab 6 weeks

a. Demolition of ceilings and lighting.

b. Remove ductwork, fan coil units and exhaust fans

c. Install new ductwork, VAV boxes, CV boxes & controls

d. Reheat coil piping

e. Rework fire protection, plumbing, med gases

f. Testing, Adjusting and Balancing.

g. New ceilings, lighting, etc.

Department of Veterans Affairs

VA Project # 537‐18‐142 3 February 19, 2021

Phase 4

1. Third Floor Offices 6 weeks

a. Demolition of ceilings and lighting.

b. Remove ductwork and exhaust fans.

c. Install new ductwork, VAV boxes & controls

d. Reheat coil piping

e. Rework fire protection, plumbing, med gases

f. New ceilings, lighting, etc.

g. Remove existing finned tube radiation

h. Remove and reinstall second floor ceiling for mechanical work

i. Patch existing floor

Close‐Out

1. Final controls installation, programming, training 3 weeks and close‐out documentation.

Department of Veterans Affairs

VA Project # 537‐18‐142 4 February 19, 2021

ASBESTOS REPORT

The asbestos report provided by the VA does not indicate asbestos on any of the mechanical systems affected by this project.

Department of Veterans Affairs

VA Project # 537‐18‐142 5 February 19, 2021

INFECTION AND DUST CONTROL MEASURES

The construction project type required for this project falls under Type C; Work that generates a moderate to high level of dust or requires demolition or removal of any fixed building components or assemblies. The first floor Urology suite is a highest patient risk group, while the third floor office suite is low and fifth floor vascular suite is medium risk. Based on the Type C category and the highest patient risk group, the infection control class for the Urology suite would be III/IV.

The infection control class for the vascular lab is class III and the office suite is class II. The specifications cover the exact procedures and regulations that the contractors will have to follow for the different infection control classes.

Department of Veterans Affairs

VA Project # 537‐18‐142 6 February 19, 2021

SYSTEM NARRATIVES

Existing System Condition

The existing S10C air handling unit is a 100% outside air unit with filters, a pre‐heat coil, heating coil, chilled water coil, humidifier and supply air fan. The unit is located in a mechanical penthouse on the first floor roof. S10C serves three distinct areas of the building; First Floor: Urology imaging/procedure room and adjacent office, corridor and storage rooms. Third Floor: Office space on the south end of Building 1A. Fifth Floor: Vascular Lab including six (6) doppler imaging rooms, offices and a waiting room. The duct distribution system provides constant volume air distribution with a reheat coil located in the duct that serves each floor.

The first floor Urology imaging room has pressure monitoring and control with volume control boxes that control supply and exhaust air to the space. There is an office, a corridor and two storage rooms that are also served from the S10C supply and exhaust ductwork. These adjacent spaces have no evident means of zone control. The area surrounding the

Urology imaging room is served by air handling unit S10B, which is located next to S10C in the penthouse. The existing

100% outside air system is not required for this type of space and the lack of zone control can cause temperature control issues.

A separate supply air duct extends from S10C, through the floor and approximately thirty feet north where it penetrates the first floor roof and extends up the exterior wall to the third and fifth floor. This exterior duct is deteriorating and duct leaks were noticed at a number of duct joints. The third floor office space operates as single zone with one reheat coil located in the supply air duct. The diffusers and grilles have been taped over by the occupants due to issues with temperature control. Three exhaust fans are located above the ceiling and discharge out a louver in the east wall.

Perimeter finned tube radiation is located under the exterior windows. The existing 100% outside air system is not required for this type of space and the lack of zone control is causing temperature control issues. Duct layout drawings were provided by the VA’s commissioning agent for this floor and these appeared to be fairly accurate.

The fifth floor Vascular Lab has six (6) doppler imaging rooms, two offices and a waiting room. All areas, with the exception of three (3) imaging rooms, are served by four‐pipe fan coil units. The fan coil units are supplied with ventilation air from the S10C supply air duct which has a single heating coil. The remaining three (3) imaging rooms, are served by constant volume boxes and exhaust fans to provide room pressure control. The exhaust fans discharge through a louver in the south exterior wall. The fan coil units, constant volume boxes and exhaust fans are nearly 30 years old and have exceeded their life expectancy. Temperature controls appear to be pneumatic. Perimeter finned tube radiation is located under the exterior windows. The existing 100% outside air system is not required for this type of

Department of Veterans Affairs

VA Project # 537‐18‐142 7 February 19, 2021 space. Due to the inaccessibility of the hard ceiling, it was difficult to verify duct routing. However, the diffuser and fan coil locations appeared to closely match the duct layout drawings that were provided by the VA’s commissioning agent for this floor.

Department of Veterans Affairs

VA Project # 537‐18‐142 8 February 19, 2021

Architectural

The first, third, and fifth floor will include existing ceiling removal where mechanical ductwork is to be replaced. We shall provide a new 2x2 suspended ceiling system where existing suspended ceiling has been removed. The extent of removal and replacement can be found on the drawings.

We shall provide wall patching and new paint finish where the ceilings have been removed and replaced to freshen up the space. Actual paint color and suspended ceiling system to be determined by VA Interior Designer during the 100%

Construction Document phase.

Locations where existing windows are to have louvers removed due to mechanical work, new glazing infill to match existing will be installed. New ductwork penetrations from the exterior of the building to the interior shall be accommodated by modifying existing wall openings. The third floor shall receive new gypsum board partition walls to hide ductwork transitions while accounting for ADA clearances. To accommodate the removal of finned tube radiation access to the second floor ceiling will be required during evenings and / or weekends and flooring will require patch and repair.

Department of Veterans Affairs

VA Project # 537‐18‐142 9 February 19, 2021

Mechanical Design

References and Standards

The mechanical design shall follow the latest versions of relevant industry standards and references including:

VA HAVC Design Manual (November 2017)

ASHRAE Standard 62.1 UV‐C

ASHRAE Standard 170 (2017): Ventilation of Health Care Facilities

HVAC system shall comply with NFPA 72, 90A, 99 and 101

USVA Specifications

Design

The planned replacement of air handling unit S10C also provides opportunities to correct issues with energy inefficiencies, dated equipment, poor controls and mis‐applied systems. Air handling unit S10C should be replaced with a new VAV unit that has a return/exhaust fan, filters, heating coil, cooling coil, humidifier and a supply fan. Ultra‐violet, UV‐C, lights will be provided downstream of the cooling coil. Both the supply and return/exhaust fans will be supplied with plenum fans and electronically commutated motors (ECM). The new return/exhaust fan, with exhaust/return/outside air dampers, will be located on the roof of the penthouse with the discharge connected to S10C below. A new system return air duct will be routed across the penthouse roof to the south facing wall of Building 1A. The return air duct will be routed up the exterior wall to the ceiling space of the third and fifth floor.

The first floor Urology area, currently served by S10C, would be better served from air handling unit S10B which serves all of the surrounding space. This unit has the capacity to pick‐up this relatively minor load. The supply and return ductwork will be switched from S10C to S10B within the penthouse. A constant volume supply air valve with a reheat coil and a variable air volume return air valve will be added to the existing ductwork that serves the Urology imaging room. This equipment will provide the needed pressure and temperature control for the space. The adjacent office, corridor and storage rooms will need new VAV boxes to provide zone control. The new VAV and constant volume air valves will be provided with hot water reheat coils. The Urology imaging room will be provided with new pressure monitoring and controls. The new controls will be integrated with the existing S10B controls. This work could be performed at night, but it would be easier to vacate the space while the work is completed.

Department of Veterans Affairs

VA Project # 537‐18‐142 10 February 19, 2021

The new S10C air handling unit will serve only the third and fifth floor. The existing, exterior supply air duct is in poor shape and should be replaced. The third floor main supply air duct will also be replaced to accommodate the new design air flow rates. The remaining branch and exhaust ductwork will need to be removed to provide space for VAV boxes that will provide zone control to the various offices. The new VAV boxes will be provided with reheat coils and controls.

Exhaust fans will no longer be required and the existing units will be removed. Return air will be provided from a new exterior return air duct that will be installed on the south face of the exterior wall. This return air duct will extend up the wall to the fifth floor ceiling space and down the wall to the roof of the S10C penthouse. The ceilings will need to be removed and replaced to allow the installation of new ductwork, VAV boxes, piping and controls. Existing fire protection, plumbing and active med gases above the ceilings will be reworked as needed. This area of the third floor should be vacated of equipment, furniture and personnel for the duration of construction.

The fifth floor requires a larger supply air duct which will be included in the designed replacement of the exterior supply air duct. All ductwork at the fifth floor Vascular Lab will be removed and replaced to accommodate the new VAV system.

This will necessitate the removal and replacement of all ceilings. The fan coil units have exceeded their expected life and do not integrate well with a VAV system, so they will be removed. The new VAV boxes will be provided with reheat coils and controls. The space renovation will require the rework of existing fire protection, plumbing and active med gases located above the ceiling. The existing restroom exhaust fan and ductwork will remain. This area of the fifth floor should be vacated of equipment, furniture and personnel for the duration of construction.

Department of Veterans Affairs

VA Project # 537‐18‐142 11 February 19, 2021

Plumbing

1. The following publications shall be used as reference for design of the plumbing systems on this project:

A. VA Plumbing design manual (November 2014, Rev May 2018)

B. 2018 International Building Code

C. 2021 International Plumbing Code

Department of Veterans Affairs

VA Project # 537‐18‐142 12 February 19, 2021

Electrical

Power Systems

There are three electrical systems utilized within the spaces involved in this project – the normal power system, the critical power system and the life safety power system, all operating at either 277/480V or 120/208V, three‐phase. In general, existing panelboard and motor control center circuits will be reused to supply power to the new loads within the project area. Where circuits are demolished, conductors and raceways will be removed back to their power source.

The following codes and standards are applicable to this project:

NFPA‐70 – National Electrical Code – 2020.

VA Electrical Design Manual – December 1, 2019.

VA Lighting Design Manual – December, 2015.

Lighting Systems

Where existing ceilings are removed and replaced, new lighting fixtures will be installed. The new fixtures will utilize

LEDs.

The lighting in the Mechanical spaces will remain unchanged.

New lighting levels and lighting fixtures will comply with the requirements of the VA Lighting Design Manual. Existing lighting controls will be reconnected to the new fixtures. Lighting calculations will be performed once the new ceiling grid layout is established.

Fire Alarm System

The existing Siemens fire alarm system will be modified as required for the new equipment installed as part of this project. Existing fire alarm system devices will be salvaged and reused where possible. New initiation or notification appliances compatible with the existing system will be provided if additional devices are required.

Special Systems

The existing Nurse Call, Intercom, Voice/Data cabling, CCTV, Card Reader/Door Access, Public Address/Code Blue Paging system cabling and devices will be removed and reinstalled.

Department of Veterans Affairs

VA Project # 537‐18‐142 13 February 19, 2021

Structural

Existing Structural Systems

The existing floor and roof construction is cast in place reinforced concrete slab supported by concrete encased steel beam framing laterally resisted by moment frames. An existing penthouse structure on the roof of Building 1 houses the air handling unit proposed to be replaced.

Loads from the new/replacement equipment do not exceed existing structure capacity. Structural reinforcement is not needed. Miscellaneous steel framing is required for curb support and floor opening support as shown on the framing plans.

The following codes and standards are applicable to this project:

ASCE 7‐16 Minimum Design Loads and Associated Criteria for Buildings and Other Structures, American Society of Civil Engineers

VA Seismic Design Requirements H‐18‐8

Category of Facility – Critical, Risk Category – IV, Occupancy – Hospital

Seismic Design Category C, therefore section 4.0 of H‐18‐8 is applicable for the equipment being added/replaced. Nonstructural components have an importance factor (Ip) of 1.5 and shall be assigned Special

Seismic Certification.

Job Number: 3C7AQ8 Page Prepared Date: 1/7/2021 Job Name: Jesse Brown VA 1 of 39 www.DaikinApplied.com

DESIGN DATA

for

Jesse Brown VA

Job Number: 3C7AQ8 Customer PO#:

Prepared by

Cory R Petersen

1/7/2021

Job Name: Jesse Brown VA

2 of 39 www.DaikinApplied.com

Table of Contents

Technical Data Sheet for AHU S10C

Drawing for AHU S10C

Fan Curve for AHU S10C

Technical Data Sheet for EF AHUS10C

Drawing for EF AHUS10C

Fan Curve for EF AHUS10C

Technical Data Sheet for AHU S10C

Job Name: Jesse Brown VA 3 of 39 www.DaikinApplied.com

Technical Data Sheet for AH U S10 C

Job Information Technical Data Sheet

Job Name Jesse Brown VA

Date January 07 2021

Submitted By CP

Software Version 12.43

Unit Tag AHU S10C

Unit Overview

Model Number

Supply

Air Volume cfm

Static Pressure External Dimensions

External inWc

Total inWc

Height in

Width in

Length in

CAH013GDQM 5500 2.50 4.06 42* 66* 180

*Not including base rails, coil connectors, drain connectors and control boxes.

Unit

Model Number: CAH013GDQM Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label)

Outer Panel: 24 gauge G90 Galvanized Steel (unpainted)

Liner: 24 gauge Galvanized Steel (unless noted per section)

Insulation: R-13 Injected Foam

Unit Configuration: Inline horizontal Drive (Handling) Location: Left

Base: 6" formed channel Wall Thickness: 2 in

Shipping Stretch Wrap: Yes Altitude: 0 ft

Parts Warranty:

Additional One Year, Two Year Total

Plenum Section Component: 1 Length: 18 in Shipping Section: 1

Opening Location Opening Size Air Pressure Drop

Top 14.00" x 62.00" 0.05 inWc

Door

Location Width Opening

Drive side 14 in Outward

Job Name: Jesse Brown VA 4 of 39 www.DaikinApplied.com

Combination Filter Component: 2 Length: 22 in Shipping Section: 1

Access Face Velocity Face Area Air Volume

Side 417 ft/min 13.2 ft² 5500 cfm

Portion Type Efficiency Air Pressure Drop Number of Filters

Height Width Depth Clean Air Mean Air Dirty Air

Pre-Filter Pleated MERV 8 0.18 inWc 0.59 inWc 1.00 inWc 3 24 in 20 in 2 in

2 12 in 24 in 2 in

Filter Varicel SH cartridge

MERV 14 0.44 inWc 0.97 inWc 1.50 inWc 3 24 in 20 in 12 in

2 12 in 24 in 12 in

Door

Location Width Opening

Drive side 18 in Outward

Special Options

Pre-Filter Gauge Final-Filter Gauge

Minihelic Minihelic

Special Text

Final filter Intersept Antimicrobial treatment

Hot Water Coil Component: 3 Length: 24 in Shipping Section: 2

Coil Model Total Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row)

5WH0802B 303433 Btu/hr 1 2 8 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air Pressure Drop

Finned Height Finned Length Face Area Face Velocity Entering Leaving Dry Bulb Dry Bulb

5500 cfm 45.0 °F 95.5 °F 0.15 inWc 33 in 50 in 11.46 ft² 480 ft/min

Water Flow Rate Pressure Drop Velocity Volume Weight Entering Leaving

180.0 °F 149.7 °F 20.00 gpm 1.60 ftHd 1.90 ft/s 4.0 gal 38.00 lb

Connection [Data Per Coil] Min. Fin Surface Temp.

Min. Tube Wall Surface Temp.

Fouling Factor Type Size Location Material

Threaded 2.50 in Drive side Carbon steel 149.7 °F 149.7 °F 0.000

Material Fin Tube Header Case

Aluminum .0075 in Copper .020 in Copper Galv. steel

AHRI 410 Certification

Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the

Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Door

Drive side 12 in Outward

Job Name: Jesse Brown VA 5 of 39 www.DaikinApplied.com

Humidifier Section Component: 4 Length: 26 in Shipping Section: 2

Number of Coils Number of Rows

1 2 Coil Air Pressure Drop Distributor Height Distributor Width Face Area Face Velocity

0.02 inWc 30 in 50 in 10.4 ft² 530 ft/min Connection Location Connection Material

Drive side Carbon steel Humid Model Drain Pan Drain Pan Side

Neptronic (see supporting data) Stainless steel Drive side

AHRI 410 Certification

Coil is NOT certified by AHRI

Door

Chilled Water Coil Component: 5 Length: 44 in Shipping Section: 3

Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing (Face x Row)

5WL0708B 261809 Btu/hr 165584 Btu/hr 1 8 7 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air Pressure

Drop

Finned Height

Finned Length

Face Area Face Velocity Entering Leaving

Dry Bulb Wet Bulb Dry Bulb Wet Bulb

5500 cfm 82.0 °F 69.0 °F 54.5 °F 53.9 °F 0.67 inWc 33 in 53 in 12.15 ft² 453 ft/min

Water Flow Rate Pressure Drop Velocity Volume Weight Entering Leaving

45.0 °F 55.1 °F 52.10 gpm 8.30 ftHd 3.40 ft/s 13.0 gal 113.00 lb

Connection [Data Per Coil] Min. Fin Surface Temp.

Min. Tube Wall Surface Temp.

Fouling Factor Type Size Location Material

Threaded 2.50 in Drive side Carbon steel 45.0 °F 45.0 °F 0.000

Material Drain Pan Drain Side Fin Tube Header Case

Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Drive side

AHRI 410 Certification

Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the

Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Door

Drive side 24 in Outward

Job Name: Jesse Brown VA 6 of 39 www.DaikinApplied.com

Supply Fan Array Component: 6 Length: 22 in Shipping Section: 4

Fan Performance

Air Volume*

Static Pressure Fan Energy Index(FEI)*

Total Input Power*

Fan Shaft Power*

Speed Redundancy(N-1) Fan Circuit

External Total Cabinet

Operating Maximum

MOP MCA

2750 cfm 2.50 inWc 4.06 inWc 0.00 inWc - - 3.26 HP 2442 rpm 3170 rpm 90.8 % 25.0 A 17.7 A

Fan Data

Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Discharge Motor Location

1x2 : 2 Airfoil / N/A 2 15.74 in Axial Integral-Front

Motor Data

Power* Electrical Supply Speed Control Signal Supplier Lock Rotor Current* Full Load Current*

7.5 HP 460/60/3

V/Hz/Phase 3170 rpm 0-10V Q-PAC 7.86 A 7.86 A

Fan Options

Isolation Backdraft Dampers: None Block Off Plate: Provided Isolator Type: Rigid

Control/Disconnect Data

Selection Type: Premium (BACnet DDC) Vendor: Q-PAC

Voltage: 460 V External Power Panel:

Height x Width x Depth 20.00 in x 16.00 in x 10.00 in

Mounting: Drive Side Internal Quick Connect Panel:

Height x Width x Depth 18.00 in x 6.50 in x 6.00 in

Enclosure: NEMA 1

Panel

Location Width Opening

Removable panels - in Outward

Notes

* after a unit label denotes the data for an individual fan.

Plenum Section Component: 7 Length: 24 in Shipping Section: 4

Air Pressure Drop

0.05 inWc

Custom Openings

Custom Opening Location Width Height Rainhood w/Screen

1 Top 62 in 14 in None

Door

Location Width Opening Window Type Light

Drive side 20 in Inward Round LED marine light kit and switch only

Special Options

Tread Plate Floor Liner

Tread plate installed

Unit Sound Power (dB)

Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Radiated: 70 73 72 65 64 56 46 51

Unit Discharge: 75 78 84 80 80 78 73 70

Unit Return: 70 73 72 65 64 56 46 51

Job Name: Jesse Brown VA 7 of 39 www.DaikinApplied.com

Shipping Section Details

Section Length in

Weight lb

Corner Weights (lb) Center of Gravity (in)

P1 P2 P3 P4 XX YY ZZ

1 40 477 101 101 138 138 23 33 24

2 50 664 182 187 150 145 22 34 22

3 44 849 256 274 168 151 17 34 23

4 46 810 253 253 152 152 17 33 22

Entire Unit

NOTE: Special components aren't included in the corner weights and center of gravity data.

Supply Static Pressure Drop

Component Option Static Pressure Drop

Plenum Section Plenum Section 0.05 insWg

Panel and Cartridge Filter Panel and Cartridge Filter 0.62 insWg

Hot Water Coil Hot Water Coil 0.15 insWg

DX Coil DX Coil 0.02 insWg

Chilled Water coil Chilled Water coil 0.67 insWg

Supply Fan Cabinet -

Plenum Section Plenum Section 0.05 insWg

External Static External Static 2.50 insWg

Total Supply Static 4.06 insWg

AHRI Certification

The air-handler is selected outside of the scope of AHRI Standard 430/431

Standard

1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2016. The approving authority is responsible for compliance of multi - component building systems.

P L E N

U M

P B F

IL

T

H W

C

D X C

C W

C

F A N

A R

R A Y

P L E N

U M

Elevation View

X Z

Jo b

N am e

Jo b

N u m b e r:

D raw in g fo r A H

U S1

0C

Je sse B ro w n V

A

C

A

Q o f 3 age re p are d D ate w w .D aikin A p p lied .co m

/7

/2

Drawing for AH U S10C

N am e

Jo b

N u m b in g fo r A H

U ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r A H

U ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r A H

U ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r A H

U ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r A H

U ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r A H

U ro w n

A o p are d D w .D aikin A p p lied

/2

Fan Curve for AHU S10C

Job Name: Jesse Brown VA 15 of 39 www.DaikinApplied.com

Fan Curve for AH U S10 C

1200 rpm 1400 rpm

1600 rpm

1800 rpm

2000 rpm

2200 rpm

2400 rpm

2600 rpm

2800 rpm

3000 rpm 3200 rpm

VAV System Line

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0

S T

A T

IC

P

R E

S S

U R

E

(IN

. O F

W A

T E

R

.0

.0

.0

.0

.0

.0

.0

.0

CFM (IN 1,000's) Green line = fan curve for 1 fan(s) at max speed Red line = BHP curve for 1 fan(s) at max power of selected motor

QPAC49 (2 Fans) Supply Fan at Standard Conditions

Daikin AHU Fan Curve

Air volume 5500 cfm Total static 4.06 insWg Total Fan Shaft Power 6.5 hp

Fan speed 2442 rpm Max speed 3170 rpm Efficiency 54.2 %

Minimum CFM 1166 cfm Minimum Fan Speed 1044 rpm Redundancy 90.8 % Motor Speed 3170 rpm Fan Energy Index(FEI) 1.29 Unit tagging AHU S10C Job name Jesse Brown VA

Date January-07-2021 Time 10:03

Technical Data Sheet for EF AHUS10C

Job Name: Jesse Brown VA 16 of 39 www.DaikinApplied.com

Technical Data Sheet for EF AH US10C

Job Information Technical Data Sheet

Job Name Jesse Brown VA

Date January 07 2021

Submitted By CP

Software Version 12.43

Unit Tag EF AHUS10C

Unit Overview

Model Number

Supply Return/Exhaust

Air Volume cfm

Static Pressure External Dimensions Air Volume cfm

Static Pressure External Dimensions

External inWc

Total inWc

Height in

Width in

Length in

External inWc

Total inWc

Height in

Width in

Length in

OAC014GVQM 5500 1.50 0.00 50* 62* 148** 5500 1.50 1.60 50* 62* 148**

*Not including base rails, coil connectors, drain connectors, vestibule sections, control boxes and hoods.

**The supply and return lengths display total unit length (not including hoods).

Unit

Model Number: OAC014GVQM

Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label)

Outer Panel: Painted 24 gauge G60 Galvanized Steel

Liner: 24 gauge Galvanized Steel (unless noted per section)

Insulation: R-13 Injected Foam

Unit Configuration: Inline horizontal Drive (Handling) Location: Left

Base: Unitized curb ready base Wall Thickness: 2 in

Roof Curb Kit: 16 in Altitude: 0 ft

Parts Warranty:

Additional One Year, Two Year Total

Plenum Section Component: 1 Length: 18 in Shipping Section: 1

End upper 14.00" x 58.00" 0.06 inWc

Door

Job Name: Jesse Brown VA 17 of 39 www.DaikinApplied.com

Return/Exhaust Fan Array Component: 2 Length: 22 in Shipping Section: 1

Fan Performance

Air Volume*

Static Pressure Fan Energy Index(FEI)*

Total Input Power*

Fan Shaft Power*

Speed Redundancy(N-1) Fan Circuit

External Total Cabinet

Operating Maximum

MOP MCA

2750 cfm 1.50 inWc 1.60 inWc 0.00 inWc - - 1.53 HP 1874 rpm 3170 rpm 100.0 % 25.0 A 17.7 A

Fan Data

Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Discharge Motor Location

1x2 : 2 Airfoil / N/A 2 15.74 in Axial Integral-Front

Motor Data

Power* Electrical Supply Speed Control Signal Supplier Lock Rotor Current* Full Load Current*

7.5 HP 460/60/3

V/Hz/Phase 3170 rpm 0-10V Q-PAC 7.86 A 7.86 A

Fan Options

Isolation Backdraft Dampers: None Block Off Plate: None Isolator Type: Rigid

Control/Disconnect Data

Selection Type: Premium (BACnet DDC) Vendor: Q-PAC

Voltage: 460 V External Power Panel:

Height x Width x Depth 24.00 in x 16.00 in x 10.00 in

Mounting: Drive Side Internal Quick Connect Panel:

Height x Width x Depth 18.00 in x 6.50 in x 6.00 in

Enclosure: NEMA 4

Panel

Location Width Opening

Removable panels - in Outward

* after a unit label denotes the data for an individual fan.

Economizer Component: 3 Length: 88 in Shipping Section: 1 & 1

Portion Damper Blade Action Rated CFM Air Pressure Drop

Quantity Hoods Size (length x width) Location Type

Overall Opening

Outside Air 40 in x 40 in 36 in x 30 in Right UltraSeal Low Leak

Parallel 5500 cfm 0.04 inWc 1 Fitted - Field installed

Return Air 30 in x 42 in 26 in x 32 in Internal UltraSeal Low Leak

Parallel 5500 cfm 0.07 inWc 1 N/A

Exhaust Air 40 in x 40 in 36 in x 30 in Left UltraSeal Low Leak

Parallel 5500 cfm 0.04 inWc 1 Fitted - Field installed

Mixing Chamber Door

Location Width Opening

Drive side 30 in Outward

Return Chamber Door

Non-drive side 30 in Outward

Plenum Section Component: 4 Length: 20 in Shipping Section: 1

Bottom 16.00" x 54.00" 0.11 inWc

Door

Drive side 16 in Outward

Job Name: Jesse Brown VA 18 of 39 www.DaikinApplied.com

Unit Sound Power (dB)

Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Radiated: 64 70 59 56 54 45 46 51

Unit Discharge: 73 80 77 77 76 73 70 64

Unit Return: 68 73 68 66 60 57 54 51

Shipping Section Details

Section Length in

Weight lb

Corner Weights (lb) Center of Gravity (in)

P1 P2 P3 P4 XX YY ZZ

1 148 2399 633 640 566 559 69 31 24

Entire Unit

Roof Curb

NOTE: Special components aren't included in the corner weights and center of gravity data.

Supply Static Pressure Drop

Economizer Mixing/Outside Air Damper 0.07 insWg

Plenum Section Plenum Section 0.11 insWg

External Static External Static 1.50 insWg

Total Supply Static -

Exhaust Static Pressure Drop

Plenum Section Plenum Section 0.06 insWg

Return Fan Cabinet -

Economizer Return/Exhaust Damper 0.04 insWg

External Static External Static 1.50 insWg

Total Return/Exhaust Static 1.60 insWg

AHRI Certification

The air-handler is selected outside of the scope of AHRI Standard 430/431

Standard

1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2013. The approving authority is responsible for compliance of multi - component building systems.

L E N

U M

F A N

A R

R A Y

R E T C

H A M

B E R

M

IX

C H

A M

B E R

P L E N

U M

Elevation View

X Z

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

Drawing for EF AHUS 10C

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

N am e

Jo b

N u m b in g fo r EF A H

U S1 ro w n

A o p are d D w .D aikin A p p lied

/2

Fan Curve for EF AHUS10C

Job Name: Jesse Brown VA 27 of 39 www.DaikinApplied.com

Fan Curve for EF AH US10C

1200 rpm 1400 rpm

1600 rpm

1800 rpm

2000 rpm

2200 rpm

2400 rpm

2600 rpm

2800 rpm

3000 rpm 3200 rpm

VAV System Line

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0

S T

A T

IC

P

R E

S S

U R

E

(IN

. O F

W A

T E

R

.0

.0

.0

.0

.0

.0

.0

.0

CFM (IN 1,000's) Green line = fan curve for 1 fan(s) at max speed Red line = BHP curve for 1 fan(s) at max power of selected motor

QPAC49 (2 Fans) Ret/Exh Fan at Standard Conditions

Daikin AHU Fan Curve

Air volume 5500 cfm Total static 1.60 insWg Total Fan Shaft Power 3.1 hp

Fan speed 1874 rpm Max speed 3170 rpm Efficiency 45.4 %

Minimum CFM 918 cfm Minimum Fan Speed 808 rpm Redundancy 100.0 % Motor Speed 3170 rpm Fan Energy Index(FEI) 1.30 Unit tagging EF AHUS10C Job name Jesse Brown VA

Date January-07-2021 Time 10:03

Fan Curve for EF AHUS10C

Job Name: Jesse Brown VA 28 of 39 www.DaikinApplied.com

Humidifier Supporting Data

Product and Option Schedule:

Tag

Air Conditions H-1(Hum-1)

External Temperature -2.20°F

R.H. 54%

Entering Temperature

R.H.

Indoor Temperature 72.0°F

R.H. 50%

Outdoor Air Economizer

Mechanical Total Air Flow

Outside Air

Economizer Total Air Flow 5500CFM

Mixed Air Temp. 55.000°F

Natural Building Volume

Air Changes/hr

Humidifier Selection

Calculated Load 78.3lb/hr

Humidifier Capacity 78.3lb/hr

Humidifier Model SKD

Signal Modulating

Power

Voltage/Phase/Cycle 24/1/60hz

Amperage

Dispersion Selection

Dimensions Duct/AHU

Width 55.00"

Height 30.00"

Air Temp. before humidification 55.0°F

R.H.

Entering 54.0%

Leaving 87.5%

Dispersion Model (# of tubes) Multi Steam (8) H

Absorption distance 21"

Controls and Accessories

NF SHS80, SF SKDMS-SD,

SW APS

Product Description:

Tag: H-1

Standard Features:

Supply a direct steam injection humidifier, Neptronic model SKD. The construction of the grid type manifold must be in stainless steel 304, without condensate drip or objectionable steam noise. The SKD consists of a number of vertical steam dispersion tubes connected to a horizontal header which is custom built for any duct size. Steam is emitted into the air stream though brass nozzles, located on the vertical tubes, designed to provide even dry steam distribution across the entire area of the duct or plenum.

Electronic Steam Controller (ESC): The ESC shall have a micro-processor based with backlit LCD display to automatically control the humidification system for a dry operation and energy saving cycles. It will display in the scroll mode the humidity set point, the humidity level, the humidity demand and output, the temperature value from the sensors. It will also indicate special diagnostic parameters such as abnormal operation and alarms. The ESC shall be programmable using the menu UP/DOWN buttons to program %R.H. set point, control parameters and indication on number of actual service hours. . In conjunction with the temperature sensor installed at the outlet of the steam separator, the ESC will insure that the system has reached the adequate temperature prior to opening the control valve for an optimum operation of the system.

Temperature Sensor: Provide RTD temperature sensor inserted in a brass thermal well to monitor the media temperature inside the piping and to prevent cold operation of the humidifier.

Control Valve: Provide brass construction steam control globe valve, with equal percentage flow characteristics.

Valve shall be normally closed when not powered. Valve Actuator: Electric, 24vac, 2-10vdc and with failsafe feature.

Actuator must have a variable speed stroke to achieve a slower opening of the steam valve to prevent condensate accumulation to be injected into the air stream.

Trap: Provide float-and-thermostatic steam trap, sized for maximum condensate flow with cast iron body.

Separator: Provide stainless steel separator with internal baffles and silencing chamber to receive steam at operating pressure, and to ensure dry steam supply to the control valve. Provide connections for steam inlet, control valve, and drain.

Strainer: Provide strainer with cast iron body.

Modulation Control: Modulation is achieved though variation of the position of seat opening of the steam supply globe valve.

Capacity Reduction: The maximum output can be programmed from 0 to 100% by using the Working Capacity feature (ESC).

Technical Specification:

Multi-Steam Humidifier

Steam pressure

Steam capacity

Valve capacity

Dimensions (in)

Piping dimensions (in) psi lb/hr lb/hr A B C #tube D E F H

H-1 8 78.26 130 51 26 8 1/2 3/4 3/4

STR AIN ER

(H)

C O N TR O LE VALVE

(D)

TEM PER ATU R E SEN SO R

FO R SEPAR ATO R

(3/4" N PT)

FLO AT AN D TH ER M O STATIC

STEAM TR AP

(3/4" N PT)

VEN TILATIO N

D U C T

M U LTI-STEAM

D ISTR IBU TO R

A

SEPAR ATO R

3/4 '' N PT

F

B STEAM IN LET

D R AIN

O U TLET

STEAM TR AP

(3/4" N PT)

FLO AT AN D TH ER M O STATIC

D A SH ED LIN ES (ELB O W S, C O U PLIN G S, TEES)

IN D IC A TE PR O VID ED B Y IN STA LLER

O PEN

FLO O R

D R AIN

Steam Valve

Specifications Each unit is comprised of a linear actuator that is directly coupled to the valve.

Globe Valve Type Brass Trim (B) Stainless Steel Trim (S)

Flow Type Equal percentage Modified Equal

Material

Body Bronze Bronze

Seat Bronze Stainless Steel

Stem Stainless Steel Stainless Steel

Plug Brass Stainless Steel

Packing Spring Loaded TFE Spring Loaded TFE

Disc Composition Teflon

ANSI Pressure Class 250psig (16 Bar) 250psig (16 Bar)

Maximum Inlet Pressure Steam 35 psig (241kPa) 100 psig (690kPa)

Differential Pressure 20 psi (138kPa) 35 psi (241kPa)

Installation Install the valve with the flow direction as indicated on the body. The valve should be installed in an accessible position and location for easy servicing.

Flow Curve

Tag Valve model Valve Trim

Nominal Ratio

Cv

Valve Body Dimensions

A B C in mm in mm in mm

H-1 SF SKDA0044SAM SS 40:1 4.4 3 77 8.16 208 1.06 27

A AB

4.8" (122m m ) 3.6" (92m m )

Electric Actuator

Specifications The linear actuator delivers a maximum of 100 pounds (450N) force at rated voltage.

Technical Data

Fail safe - Enerdrive Yes

Power consumption 20VA Peak, 6VA

Running time to ½ inch 60 sec force dependant

Force 100 lb. [450 N] at rated voltage

Feedback 4 to 20 mA or 2 to 10 VDC adjustable

Power supply 22 to 26 VAC or 28 to 32 VDC

Electrical connection 18 AWG [0.8 mm2] minimum

Inlet bushing 2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]

Control signal Analog

Direction Normally down position (close)

Ambient temperature 0ºF to +122ºF [-18ºC to +50ºC]

Storage temperature -22ºF to +122ºF [-30ºC to +50ºC]

Relative Humidity 5 to 95 % non condensing.

Weight 2 lbs. [0.9 kg]

Installation & Wiring Diagram

Install the actuated valve with the flow direction as indicated on the body. The actuated valve must be installed horizontally with a 20 to 30 degree angle, in an accessible position and location for easy servicing.

Horizontal mounting

1. Pay attention to system particularity; be sure that the expansions, contractions of the system and its medium as well as operating pressures are within the tolerances.

2. When plumbing, the motorized valve should be situated in an easily accessible place and sufficient space should be allowed for the removal of the actuator.

3. To prevent moisture from collecting in the motor casing, install the motorized valve such that the actuator is superior to the valve, at 20-30º angle / at vertical. Avoid mounting the valve so that the valve stem is below horizontal.

Analog

20-30º

1 2 3 4 5

COM M ON (-)

SUPPLY (+)

FEEDBACK

4 to 20 m A

2 to 10 VDC

Separator

Specifications Stainless steel construction, the high quality steam separator minimizes moisture and carryover.

No moving part.

No maintenance and no spare parts requirements.

Low pressure drop.

Installation Steam from the boiler is supply from the top (C), the dry steam outlet is on the left (D) and condensate is evacuate at the bottom of the separator (E).

Dimensions

A height B width C steam inlet D steam outlet E condensate in mm in mm in mm In mm in mm

H-1 8.25 210 4 102 0.75 20 0.75 20 0.75 20

B

D

E

Steam Trap

Specifications Float and thermostatic with internal air vent.

Cast iron body ASTMA126B with all stainless steel internal components.

Four possible hook-up combinations for maximum installation flexibility.

Balanced pressure thermostatic element, allows venting of non-condensibles while operating at design pressure.

Installation Steam traps should be installed in an accessible position and location for easy servicing. The maximum differential pressure stamped on product name plate must be greater than the maximum pressure differential across the trap. Be sure to install trap straight, plumb and in a level position to insure proper operation.

A B C D E Weight

Inch 6.25 5.5 3.31 3 5.75 9 lbs mm 159 140 84 76 146 4.1kg

Y Type Strainer

Specifications Operation pressure: ASME Class 250 NPT, rated 500psig (34bar) at 450˚F (232˚C).

One piece cast body with stainless steel mesh.

Upper and lower machined seats

Generous screen area and properly proportioned straining chamber to minimize initial pressure drop while maximizing time between cleanings.

Drain/Blow-off connection furnished with plug.

Installation Install the strainer with the flow direction as indicated on the body. To facilitate servicing, the strainer must be accessible for cleaning the screen.

Inlet

Dimensions and weights

Size A B C Weight in mm in mm in mm in mm lb kg

H-1 3/4 19 3.8 97 2.7 69 3.7 94 2.5 1.1

Temperature Sensor

Specifications RTD temperature sensor for two wires connection.

Brass thermal well for an efficient heat transfer.

Inside a black malleable 3/4" NPT female fitting.

Installation Install the temperature sensor as indicated by the manufacturer installation instructions.

The electrical box must be located on the top of the assembly. The temperature sensor should be installed in an accessible position and location for easy servicing.

3/4”NPT fem ale

Brass therm al well

E lectrica l box

ESC Steam Controller

Features:

• Attractive modern look with large LCD and backlight

• Icons driven information and 2 line of text information

• Programmable parameters

• Selectable Fahrenheit or Celsius scale

• Multi level lockable access menu

• Selectable internal or external control

• Programmable proportional control band & dead band

ESC Terminal Description

SKDESCM

T B

T B

T B

T

B

A n a lo g

O u tp u ts T e m p e ra tu re

S e n s o r In p u ts

A n a lo g In p u ts

24VAC

AO1

COM

AO2

AI1

COM

AI2

AI3

COM

AI4

TS1

COM

TS2

TS3

COM

TS4

TS5

COM

TS6

T B

T B

NC

KCOM

NO

24VAC

COM

NC

KCOM

NO

T B

T B

T B

T

B

TO3

COM

TO2

COM

TO1

24VAC

DI4

DI3

COM

DI2

DI1

S u p p ly S te a

R la y

A la rm la y D ig it a l In p u t

Temperature Sensor Separator

Common

S1

External Demand/Setpoint1

Room Humidity Sensor

High Limit Humidity Sensor2

0 – 10 Volts

Steam Control Valve Actuator

AM060-ESC

Common -1

24 Vac -2

Control Signal -3

Not used -4

Not used -5

Interlock

PD Switch On/Off

High Limit (digital)2 NC

NC

NO

Control Valve Signal

Common

Alarm Relay

Steam on Relay Status

O n

/O ff

5 Interlock: Contact opening = alarm and unit shutdown

4 Hi Limit: Contact opening = alarm and unit shutdown

3 COM

2 PD Switch: Contact closure = alarm and unit shutdown

1 Demand: Contact closure = Override and force 100% demand

24 Vac

24 Vac

Common or 24 Vac

IN A+

IN B-

COM

OUT A+

OUT B-

T B

N e tw o rk

* Network available only on

ES0B or ESCD

Controls & Accessories

Item Model Description

APS Air pressure switch, SPDT, 0.05"WC set point

BACnet®

This product provides a BACnet® network interface between BACnet® client devices and NEP Humidifier Series devices. NEPIC uses the BACnet® Master Slave/Token

Passing (MS/TP) protocol at the BACnet® MAC layer.

Submittal ESV-1.0 01-22-2020

ESV

Single Duct Terminal Unit Digital, Analog or Electric Control, Pressure Independent

Right hand unit shown. All dimensions are in inches.

Size CFM Range H L WD (H x W) F G M

5E 6E 7E 8E 1E 2E 4E

0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 0-2000 0-4000 0-8000 0-350 0-500 0-650 0-900 0-1400 0-2000 0-3000

3 7/8 4 7/8 5 7/8 6 7/8 7 7/8 8 7/8 9 7/8

11 7/8 13 7/8 15 7/8

7 1/2 x 12 1/4 7 1/2 x 23 3/4

15 7/8 x 23 7/8 4 7/8 5 7/8 6 7/8 7 7/8 9 7/8

11 7/8 13 7/8

2 1/8 2 1/8 2 1/8 1 1/8 1 1/8

1/4 1/4

1 1/8 2 1/8 2 1/8 1 1/8 1 1/8

7 3/8 7 3/8 7 3/8 7 3/8 7 3/8 5 3/8 5 3/8 5 3/8 3 3/8 3 3/8

5 3/8 7 3/8 7 3/8 5 3/8 5 3/8 5 3/8 3 3/8 3 3/8

12 1/2 12 1/2

17 1/2

12 1/2 12 1/2

17 1/2

15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2

15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2

5 3/8 5 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8

27 1/4

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

CH CWCL

12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 10 1/4 10 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4 12 1/4

15 1/4 15 1/4

6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2 6 1/2

Digital Control, DESV Analog Control, AESV Electric Control, EESV

CW

CH

CL

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Jim Highlight

Submittal ESV-2.0 01-22-2020

ESV

Single Duct Terminal Unit Pneumatic Control, Pressure Independent

Right hand unit shown. All dimensions are in inches.

Size CFM Range H L WD (H x W) F M

0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 0-1800 0-4000 0-8000

3 7/8 4 7/8 5 7/8 6 7/8 7 7/8 8 7/8 9 7/8

11 7/8 13 7/8 15 7/8

7 1/2 x 12 1/4 7 1/2 x 23 3/4 23 7/8 x 15 7/8

2 1/8 2 1/8 2 1/8 1 1/8 1 1/8

1 1/8 1/4

1 1/8

12 1/2 12 1/2

17 1/2

15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2 15 1/2

5 3/8 5 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8 3 3/8

27 1/4

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

Pneumatic Control, PESV

Submittal ESV-4.0 01-22-2020

Accessories (Optional) Check if provided.

24 V Control Transformer Dust Tight Enclosure Seal Fibre Free Liner

SteriLoc Liner

Bottom Access Door

Hanger Brackets

UltraLoc Liner1" Fiberglass Liner

Disconnect Switch

Removable Air Flow Sensor 1" EcoShield Liner

½” Fibre Free Liner

½” EcoShield Liner (Foil Face) 1” EcoShield Liner (Foil Face)

½” EcoShield Liner

1" Fibre Free Liner Low Leakage Seal/Test/Certify

OSP & IBC -S Seismic Certification Red List Compliant “Google” Gasketing

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

General Description

• Heavy gauge steel housing.

Mechanically sealed and gasketed, leak resistant construction. Less than 2% of nominal cfm at 1.5" sp wg.

• Dual density internal insulation, treated to resist air erosion.

Meets requirements of NFPA 90A and UL 181.

• Units equipped with the Titus II velocity controller can either be direct acting or reverse acting, with the damper either normally open or normally closed.

Controller maintains constant span and start point. (Span and start point are adjustable.)

• Model DESV without coils can be installed horizontally, vertically, or at any angle.

Operation is not affected by position. For units with coils, consult technical support.

• Gauge tees for cfm measurement.

• OSHPD Seismic Certification: OSP-0352-

• Only Titus Alpha digital and pneumatic controls approved for seismic installation.

• Rectangular discharge opening is designed for slip and drive cleat duct connection.

• Multipoint center averaging inlet velocity sensor.

• Control packages can be factory mounted by Titus.

• Choice of right hand or left hand control location.

• Units equipped with the Titus I velocity controller are available in both direct acting / normally open and reverse acting / normally closed operating modes.

Integral Sound Attenuator

DESV, AESV, EESV

PESV

ESV-4.0 01-22-2020

Accessories (Optional)

Electric Coil Section

Fuse Block Standard Features

• Single side access to low voltage, high voltage, and electric heater controls.

• Automatic reset thermal cutouts, one per element

• Manual reset secondary protection.

• Positive pressure flow switch

• Magnetic contactor for each step.

• Slip and drive cleat discharge duct connection.

Options

Disconnect switch, door interlock type

Dust tight construction

Supply Voltage

208V, 1 ph, 60Hz 240V, 1 ph, 60Hz

277V, 1 ph, 60Hz 208V, 3 ph, 60Hz

480V, 3 ph, 60Hz (4 wire wye standard)

Mercury contactors

The total length of the ESV unit is the summation of the unit length (with or without attenuator) and the length of the optional water coil.

This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies, Inc.

Size H W L (1-2 Row)

7 1/2 7 1/2

12 1/2 12 1/2

17 1/2

27 1/4

L (3-4 Row)

7 1/4 7 1/4 7 1/4 7 1/4 7 1/4 7 1/4 7 1/4 7 1/4 9 3/4 9 3/4 7 1/4 7 1/4 7 1/4

Water Coil

Optional SCR Controlled Electric Heater Optional Lynergy Controlled Electric Heater

120V, 1 ph, 60Hz

Hot Water Coil Section

1 Row 2 Row

• Aluminum ripple fins, 10 per inch

• Coil pipe connections are male, sweat, type

“L” copper. Connection sizes on unit sizes 04- 08 are 1/2” OD for 1 row coil and 5/8" on 2 row coils. All other coils have 7/8" OD.

• Coil is installed at discharge of unit.

• On units with attenuators, coil are installed at the discharge of attenuator.

• Coils rated and certified to AHRI Standard

3 Row 4 Row

DESV, AESV, EESV

PESV

Jim Highlight

Jim Highlight

ESV Terminal Unit

Insulation type specified per order

Gasket (Access door is sealed with foam gasket material)

Access Door (Insulated)

Submittal ESV-ACD-1.0 10-24-14

Single Duct Terminal Access Door Option Model: ESV

Right Hand Unit Shown

Basic Unit (Bottom View)

Basic Unit w/attenuator (Bottom View)

General Description

• All ESV access doors for unit sizes 4 through 16 have a 6" x 9" opening

• Access door is always insulated and sealed with gasket.