Attch02 - BD_Drawings 537-18-142 19Feb21.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25221B0012
About this file
This pre-solicitation notice provides key details for an upcoming construction project at the Jesse Brown VA Medical Center in Chicago, Illinois. The project involves replacing an existing S10C air handling unit that serves the vascular, SCM, and urology departments, and moving air handling service for urology to the existing S10B unit. The solicitation will be set aside for service-disabled veteran-owned small businesses and is estimated to have a value between $1-2 million. The notice of solicitation is expected to be posted on April 9, 2021, with bids due on June 8, 2021. The awarded contractor must complete the work within 291 calendar days of receiving a notice to proceed. Interested parties are encouraged to attend a pre-bid site visit, with details to be included in the forthcoming solicitation package.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAMPUS MAP
NOT TO SCALE
GARAGE
OFFICE
11A
11B
1-B 1-A
PARKING
PATIO
TAYLOR STREET
SO
UT
H
DA
ME
N
AV
EN
UE
POLK STREET
OGDEN AVENUE
VICINITY MAP
NOT TO SCALE
Roosevelt Rd.
W. Harrison St.
S.
M ich iga n A ve
S.
S tat e S
t. S.
C olu mb us D r.
S.
C an al
St
S.
R ac ine
A ve
S.
A sh lan d A ve
W. Jackson Blvd.
W. Adams St.
W. Monroe St.
W. Madison St.
S.
Og den Av e.
S.
La ke S ho re
D r.
CHICAGO
LOCATION MAP
NOT TO SCALE
Chicago
Peoria
Springfield
Decatur
Champaign
Bloomington
Naperville
Rockford
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NO
T
FO
R
CO
NS
TR
UC
TI
ON
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
EXCELLENCEHEALTH
CARE
DEPARTMENT OF VETERANS AFFAIRS - JESSE BROWN VA MEDICAL CENTER
CHICAGO, ILLINOIS
C:
\R ev it\2
0\2
8_ A_ mi ch ell e.b urr i.rv t 2/1
8/2
1 1 1:3
5:5 9 P
M
G-001
COVER SHEET S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
S10C AHU REPLACEMENT
537-18-142
02/19/2021
100% BID DOCUMENTS
SHEET
NO. SHEET NAME
GENERAL
G-001 COVER SHEET
G-101 PHASING PLANS
STRUCTURAL
S-001 GENERAL NOTES AND LEGENDS
S-101 FRAMING PLANS - PENTHOUSE
ARCHITECTURAL
A-001 ARCHITECTURAL LEGENDS, SYMBOLS, AND ABBREVIATIONS
AD101 RCP DEMOLITION PLAN - FIRST & SECOND LEVEL
AD102 RCP DEMOLITION PLAN - THIRD & FIFTH LEVEL
A-101 FLOOR PLAN - FIRST & SECOND LEVEL
A-102 FLOOR PLAN - THIRD & FIFTH LEVEL
A-103 ROOM FINISH & MATERIALS SCHEDULES
A-111 REFLECTED CEILING PLAN - FIRST & SECOND LEVEL
A-112 REFLECTED CEILING PLAN - THIRD & FIFTH LEVEL
A-120 ROOF PLAN - SECOND LEVEL NORTH PENTHOUSE
MECHANICAL
M-001 MECHANICAL LEGENDS
MD101 MECHANICAL DEMOLITION PLANS
MD102 MECHANICAL DEMOLITION PLANS
M-101 MECHANICAL PLANS
M-102 MECHANICAL PLANS
M-103 MECHANICAL ROOF PLANS
M-501 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-801 MECHANICAL CONTROLS
ELECTRICAL
E-001 GENERAL NOTES AND LEGENDS
ED101 DEMOLITION PLAN - FIRST AND SECOND LEVELS
ED102 DEMOLITION PLAN - THIRD AND FIFTH LEVELS
E-101 ELECTRICAL PLANS - FIRST, SECOND AND ROOF LEVELS
E-102 ELECTRICAL PLANS - THIRD AND FIFTH LEVELS
TOTAL SHEETS: 27
Revisions: Date:
8 7 6 5 4
A
4.2
MINOR OR
SURGERY RM
RECOVERY RM
1108SUPPLY RM
UROLOGY
OFFICE
CLINICS
CORRIDOR
C1105
NURSE INTAKE
1107NURSE INTAKE
TOILET
TELECOM
11T1
PHASE 1
SEAL EXISTING DOOR TO PROVDE
TEMPORARY INFECTION CONTROL
MEASURES. COMPLY WITH SPECIFICATIONS
REGARDING INFECTION CONTROL
NORTH
PENTHOUSE
BUILDING 30
PHASE 2
SEAL EXISTING DOOR TO PROVIDE
TEMPORARY INFECTION CONTROL
MEASURES. COMPLY WTIH
SPECIFICATIONS REGARDING
INFECTION CONTROL
E
8 7 6 5 4
D
C
B
A
E.1
4.2
OFFICE
CUBICLE
SPD
SUPERVISOR
ADMIN OFFICE
3403 CORRIDOR
C3405
SYSTEM
ANALYST
STORAGE
OFFICE
CUBICLE
DIALYSIS RM
SOCIAL WORK
NURSE MGR
3412STAIR
NO 2
PHASE 4
E
8 7 6 5 4
D
C
B
A
E.1
4.2
EQUIPMENT
STORAGE
WAITING
TEAM RM
LOCKER
CORRIDOR
C5405
RECEPTION
AREA
LOUNGE
TREATMENT
BED 5
TREATMENT
BED 4
TREATMENT
BED 1
TREATMENT
BED 2
TREATMENT
BED 3
PHASE 3
SEAL EXISTING DOOR TO PROVIDE
TEMPORARY INFECTION CONTROL
MEASURES. COMPLY WITH SPECIFICATIONS
REGARDING INFECTION CONTROL
PHASE 2
1. VA PREFERS THE USE OF HARD WALL PARTITIONS OVER THE USE OF PLASTIC
SHEETING FOR SEPARATION BETWEEN CONSTRUCTION AND EXISTING SPACES
TO REMAIN FUNCTIONING. CONTRACTOR TO SUBMIT PROPOSED PLAN FOR
TEMPORARY CONSTRUCTION PARTITION LOCATIONS FOR COR APPROVAL.
TEMPORARY PARTITION LOCATIONS SHOWN HERE ARE RECOMMENDED
LOCATIONS BASED ON WORK NEEDIN TO BE COMPLETED, BUT DOES NOT
CONSTITUTE FINAL LOCATIONS OR QUANITITIES.
GENERAL PHASING NOTES:
PHASING LEGEND:
PHASE 3
PHASE 2
PHASE 1
PHASE 4
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 6:
P
M
G-101
PHASING PLANS S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
1/8" = 1'-0"
PHASING PLAN - FIRST LEVEL
1/8" = 1'-0"
PHASING PLAN - SECOND LEVEL NORTH PENTHOUSE
1/8" = 1'-0"
PHASING PLAN - THIRD LEVEL
1/8" = 1'-0"
PHASING PLAN - FIFTH LEVEL
1/8" = 1'-0"
PHASING PLAN - SECOND LEVEL ROOF NORTH PENTHOUSE
CONCRETE:
1. ALL CONCRETE WORK TO BE PERFORMED IN CONFORMANCE WITH THE MOST RECENT
EDITION OF ACI 301 & ACI 318 CODE REQUIREMENTS AND DETAILING STANDARDS.
2. SEE SPECIFICATIONS FOR REQUIRED 28 DAY COMPRESSIVE STRENGTH (F'c).
3. ALL REINFORCING BARS, DOWELS, ANCHOR BOLTS AND OTHER INSERTS SHALL BE
SECURED IN POSITION PRIOR TO PLACING OF THE CONCRETE.
4. ALL HORIZONTAL BARS IN CONCRETE WALLS AND GRADE BEAMS SHALL BE
CONTINUOUS AND BENT AT ALL CORNERS AND INTERSECTIONS. PRE-BENT "CORNER"
BARS SUBSTITUTED FOR CONTINUOUS BENT BARS SHALL BE OF SAME SPACING AS
HORIZONTAL BARS AND SHALL BE OF SUFFICIENT LENGTH TO PROVIDE REQUIRED
LAP SPLICE LENGTHS.
5. DETAILING BENDING AND PLACING OF REINFORCING STEEL SHALL BE IN ACCORDANCE
WITH THE MOST RECENT EDITION OF THE ACI CODE.
6. ALL CONCRETE FORMWORK SHALL BE ADEQUATELY TIED TOGETHER AND BRACED TO
FORM TRUE LINES, SQUARE CORNERS, AND PLUMB WALLS.
7. NO CONCRETE SHALL BE POURED SUBJECT TO FREEZING CONDITIONS, OR ON FROZEN
GROUND.
8. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, OR
ACCESSORIES REQUIRED TO BE CAST INTO CONCRETE, AND FOR LOCATIONS OF FLOOR
FINISHES AND SLAB DEPRESSIONS.
9. FOOTINGS SHALL BE LOCATED ON THE CENTERLINE OF WALLS, PIERS, OR COLUMNS,
UNLESS NOTED OTHERWISE.
10. LOCATE ALL SLEEVES, OPENINGS, EMBEDDED ITEMS, ETC. WHICH ARE INDICATED
ON DESIGN DRAWINGS. CHECK WITH OTHER TRADES TO VERIFY THAT ALL SLEEVES,
OPENINGS, AND EMBEDDED ITEMS ARE IN PLACE AND LOCATED CORRECTLY PRIOR
TO PLACEMENT OF CONCRETE.
11. PIPE MAY PASS THROUGH STRUCTURAL CONCRETE IN SLEEVES, BUT SHALL NOT BE
EMBEDDED THEREIN. SLEEVES SHALL BE WRAPPED WITH EXPANSION JOINT FILLER
MATERIAL TO ALLOW CONCRETE TO CURE WITHOUT RESTRAINT. PIPES OR CONDUITS
WITH DIAMETER EXCEEDING ONE THIRD THE SLAB OR WALL THICKNESS SHALL NOT BE IN
STRUCTURAL CONCRETE UNLESS SPECIFICALLY DETAILED AS SUCH. SEE MECHANICAL
AND/OR ELECTRICAL DRAWINGS FOR LOCATIONS OF SLEEVES, ACCESSORIES, ETC.
12. THE SURFACE OF ALL CONSTRUCTION JOINTS SHALL BE CLEANED TO REMOVE ALL
DUST, CHIPS, OR OTHER FOREIGN MATTER PRIOR TO THE PLACEMENT OF ADJACENT
CONCRETE.
13. SLAB CONTROL JOINTS SHALL BE INSTALLED WITH JOINT FORMERS WHEN THE SLAB
IS POURED , OR SAWCUT AS SOON AS THE CONCRETE WILL ALLOW WITHOUT DAMAGE.
14. ALL EMBEDDED ITEMS SHALL BE PLACED IN THE FORMWORK PRIOR TO PLACING
CONCRETE. DRILLING AND GROUTING IS ACCEPTABLE SUBJECT TO ENGINEER
APPROVAL.
15. CONCRETE WALLS MAY BE BACKFILLED TO TWO-THIRDS THE WALL HEIGHT ONCE 75%
OF THE 28 DAY COMPRESSIVE DESIGN STRENGTH HAS BEEN ACHIEVED. WALLS WITH
TOP SLABS MAY BE BACKFILLED TO ONE-HALF OF THE WALL HEIGHT PRIOR TO CASTING
THE TOP SLAB.
REINFORCING STEEL:
1. ALL REINFORCING STEEL SHALL BE HIGH STRENGTH DEFORMED BARS, GRADE 60,
ASTM A615, WITH 60,000 PSI MINIMUM YIELD STRENGTH, UNLESS NOTED OTHERWISE.
2. REINFORCEMENT PROTECTION: (U.N.O.)
A. CONCRETE POURED AGAINST EARTH = 3"
B. CONCRETE POURED IN FORMS BUT EXPOSED = 2"
TO WEATHER, EARTH OR LIQUID
C. SLABS AND WALLS NOT EXPOSED TO WEATHER OR EARTH = 1 1/2"
D. BEAMS, GIRDERS, AND COLUMNS NOT EXPOSED TO
WEATHER, OR IN CONTACT WITH EARTH = 1 1/2"
3. WELDING OF REINFORCING BARS IS NOT PERMITTED, UNLESS NOTED OTHERWISE.
MASONRY:
1. CONCRETE MASONRY UNITS (CMU) ARE TO CONFORM TO ASTM C-90.
2. SEE SPECIFICATIONS FOR UNIT WEIGHT AND STRENGTH.
3. ALL MASONRY REINFORCING SHALL BE PLACED AND SUPPORTED IN CONFORMANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF ACI 530.1/ASCE-6/TMS 602.
4. ALL VERTICAL REINFORCING STEEL IN CMU WALLS SHALL BE CONTINUOUS FROM
THE FOOTING TO THE BOND BEAM, AND TERMINATED IN END HOOKS. WHERE BOND
BEAMS ARE NOT AT THE TOP OF A WALL, REINFORCING SHALL BE CONTINUOUS
THROUGH THE BOND BEAM TO TOP WALL.
5. ALL REINFORCING BARS MARKED "CONTINUOUS" SHALL BE SPLICED A MINIMUM OF 50
BAR DIAMETERS, BUT NOT LESS THAN 24 INCHES.
6. ALL MASONRY WORK BELOW GRADE SHALL HAVE CORES GROUTED SOLID WITH GROUT
CONFORMING TO ASTM C476. BELOW GRADE MASONRY SHALL USE TYPE M OR S
MORTAR.
7. SEE LINTEL SCHEDULE FOR LINTEL SIZES. ALL STEEL LINTELS IN EXTERIOR WALLS
SHALL BE HOT-DIP GALVANIZED, UNLESS NOTED OTHERWISE.
8. MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM TO ALL REQUIREMENTS
OF "SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1/ASCE-6/TMS-602)," EXCEPT
AS MODIFIED BY THE REQUIREMENTS OF THESE CONTRACT DRAWINGS.
9. CONTROL JOINTS SHALL BE INSTALLED AT LOCATIONS SHOWN ON THESE DRAWINGS. IN
AREAS NOT NOTED ON DRAWINGS, A MINIMUM PLACEMENT OF ONE SIDE ABOVE ALL
OPENINGS 6'-0" WIDE OR LESS, AND AT BOTH SIDES OF ALL OTHER OPENINGS, OR AT
20'-0" O.C.MAX.
10. MISCELLANEOUS LINTELS ARE NOT SHOWN ON STRUCTURAL PLANS. CONTRACTOR SHALL
VERIFY AND INCLUDE IN THEIR BID MISCELLANEOUS LINTELS FOR DOOR OPENINGS, DUCT
PENETRATIONS, ETC. REFER TO MISCELLANEOUS LINTEL SCHEDULE AND DETAILS. STRUCTURAL DESIGN INFORMATION:
DESIGN DATA BASED ON ASCE 7-10
RISK CATEGORY: IV
1. SNOW LOAD:
SNOW EXPOSURE FACTOR (Ce) 1.0 THERMAL FACTOR (Ct) 1.0 SNOW IMPORTANCE FACTOR (Is) 1.2 GROUND SNOW LOAD (Pg) 25 PSF FLAT ROOF SNOW LOAD (Pf) 21 PSF SLOPED ROOF FACTOR (Cs) 1.0
2. PENTHOUSE ROOF LIVE LOAD: 150 PSF (PER EXISTING DRAWINGS)
PENTHOUSE FLOOR LIVE LOAD: 100 PSF (PER EXISTING DRAWINGS)
3. WIND LOADS:
BASIC WIND SPEED 120 MPH
WIND IMPORTANCE FACTOR (Iw) 1.00
WIND EXPOSURE CATEGORY 'C'
4. SEISMIC LOADS:
SEISMIC IMPORTANCE FACTOR (Ie) 1.5
SITE CLASS 'D'
SEISMIC DESIGN CATEGORY 'C'
BASIC SEISMIC FORCE RESISTING SYSTEM:
STEEL ORDINARY MOMENT FRAMES.
STRUCTURAL STEEL:
1. STRUCTURAL AND MISC. STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE MOST RECENT EDITION OF AISC STEEL CONSTRUCTION
MANUAL AND CODE OF STANDARD PRACTICE. STEEL JOISTS SHALL CONFORM TO THE
MOST RECENT EDITION OF STANDARD SPECIFICATIONS OF THE STEEL JOIST INSTITUTE.
METAL DECK SHALL CONFORM TO THE MOST RECENT EDITION OF THE STANDARD
SPECIFICATION OF THE STEEL DECK INSTITUTE.
3. USE BOLTED CONNECTIONS AS SPECIFIED IN FRAMING DETAIL FOR SIZE AND NUMBER
OF BOLTS AND WELDS FOR ALL STRUCTURAL STEEL CONNECTIONS. ALL BOLTED
CONNECTIONS SHALL BE STANDARD ROUND HOLES (UNLESS NOTED OTHERWISE).
IF DETAIL IS NOT PROVIDED:
ALL BOLTED CONNECTIONS SHALL BE BEARING TYPE "N", 3/4" DIA. BOLTS (BRG. TYPE)
OR WELDED EQUIVALENT, UNLESS OTHERWISE NOTED. SELECT CONNECTIONS TO
SUPPORT ONE HALF THE TOTAL LOAD CAPACITY FOR EACH GIVEN BEAM AND SPAN.
THE EFFECT OF CONCENTRATED LOADS SHALL ALSO BE CONSIDERED.
4. CONNECTIONS MADE WITH HIGH STRENGTH STEEL BOLTS SHALL CONFORM IN ALL
RESPECTS TO THE CURRENT SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM
A325 BOLTS AS ENDORSED BY THE AISC. NO PAINT ON FAYING SURFACES.
5. WELDING SHALL BE DONE IN ACCORDANCE WITH THE "AMERICAN WELDING SOCIETY"
(AWS) D1.1, USING E70 ELECTRODES. WELDING SHALL BE PERFORMED BY AN
APPROVED CERTIFIED WELDER.
6. NO CHANGES SHALL BE MADE IN THE STEEL STRUCTURE NOR ANY MATERIAL CUT IN THE
FIELD (UNLESS NOTED AS "FIELD CUT OR TRIM" ON DRAWINGS), WITHOUT THE
WRITTEN PERMISSION OF THE ENGINEER.
7. NO CUTTING, BURNING, OR HOLES OTHER THAN THOSE SPECIFICALLY DETAILED SHALL
BE ALLOWED THROUGH STRUCTURAL STEEL MEMBERS WITHOUT THE PRIOR CONSENT
OF THE ENGINEER. BOLT HOLES SHALL CONFORM WITH THE GOVERNING AISC
SPECIFICATION, AND SHALL BE STANDARD HOLES UNLESS NOTED OTHERWISE.
8. THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES BETWEEN
THE DESIGN AND ACTUAL CONDITIONS NOTED IN THE FIELD.
9. CONTRACTOR SHALL PROVIDE NECESSARY LABOR, MATERIAL, AND EQUIPMENT TO
ERECT ALL MISCELLANEOUS IRON AND STEEL AS DETAILED ON THESE DRAWINGS.
10. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION.
11. UNLESS OTHERWISE INDICATED, ROOF OPENINGS MADE IN EXISTING ROOF STRUCTURE
SHALL BE SUPPORTED ON ALL EDGES BY L4x4x1/4" FOR SPANS OF 5’-0" OR LESS; AND BY
C8X11.5 FOR SPANS BETWEEN 5’-0” AND 10’-0”. SPANS EXCEEDING 10’-0” SHALL REQUIRE
SECTIONS APPROVED BY THE ENGINEER. CONNECTIONS SHALL BE WELDED IN
ACCORDANCE WITH AWS D1.1 AND AISC, OR MINIMUM 2-BOLT CONNECTIONS
ACCORDING TO AISC.
GENERAL STRUCTURAL NOTES
1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL DIMENSIONS AND CONDITIONS
AT THE JOB SITE AND TO CROSS-CHECK DETAILS AND DIMENSIONS ON THE STRUCTURAL
DRAWINGS WITH THE RELATED REQUIREMENTS ON THE ARCHITECTURAL, MECHANICAL,
ELECTRICAL, AND PLUMBING PLANS. FLOOR AND WALL OPENINGS, SLEEVES AND OTHER
ARCH., MECH., ELEC., REQUIREMENTS MUST BE COORDINATED BEFORE THE CONTRACTOR
PROCEEDS WITH CONSTRUCTION.
2. ALL ENGINEERING DESIGN, CONSTRUCTION, AND TESTING SHALL CONFORM TO THE
REQUIREMENTS OF THE MOST RECENT EDITION OF THE INTERNATIONAL BUILDING CODE.
3. ALL STRUCTURAL WORK MUST BE TEMPORARILY BRACED AND SUPPORTED UNTIL THE
STRUCTURE IS SUFFICIENTLY COMPLETED AND CAN SAFELY CARRY THE DESIGN AND
CONSTRUCTION LOADS.
4. REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN ON THE
STRUCTURAL DRAWINGS.
5. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING
DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
ENGINEER BEFORE PROCEEDING WITH ANY WORK THAT IS INVOLVED IN THE CONFLICT.
ABBREVIATIONS
TYPE DESCRIPTION
A.B. ANCHOR BOLT
ALT. ALTERNATE
ARCH. ARCHITECTURAL
AVG. AVERAGE
AFF ABOVE FINISH FLOOR
BFF BELOW FINISH FLOOR
BLDG. BUILDING
BM. BEAM
B.O. BOTTOM OF
BRG. BEARING
C.J. CONTROL JOINT
CMU CONCRETE MASONRY UNIT
CONC. CONCRETE
CONST. JT. CONSTRUCTION JOINT
CONT. CONTINUOUS
D DEPTH
DET. DETAIL
DTL. DETAIL
DIA. DIAMETER
EA. EACH
ELEV. ELEVATION
EQ. EQUAL
E.W. EACH WAY
EXIST. EXISTING
EXST. EXISTING
E.F. EACH FACE
F.F. FINISH FLOOR
FLR. FLOOR
FND. FOUNDATION
FNDTN. FOUNDATION
FTG. FOOTING
F.S. FAR SIDE
GA. GAUGE
GALV. GALVANIZED
HDG HOT DIPPED GALVANIZED
HORIZ. HORIZONTAL
HORZ. HORIZONTAL
H.P. HIGH POINT
INSUL. INSULATION
I.F. INSIDE FACE
TYPE DESCRIPTION
L LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG. LONGITUDINAL
L.P. LOW POINT
MAX. MAXIMUM
MECH. MECHANICAL
MEZZ. MEZZANINE
MANUF. MANUFACTURER
MNF. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
N.S. NEAR SIDE
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F OUTSIDE FACE
O.H. OVERHEAD
OHD OVERHEAD DOOR
O/O OUT TO OUT
PSF POUNDS PER SQUARE FT.
PSI POUNDS PER SQUARE IN.
R RADIUS
REINF. REINFORCING
SIM. SIMILAR
T&B TOP AND BOTTOM
T.O. TOP OF
T.O.B.L. TOP OF BRICK LEDGE
T.O.F TOP OF FOOTING
T.O.F.W. TOP OF FOUNDATION WALL
T.O.P. TOP OF PIER
T.O.S TOP OF STEEL
TRANS. TRANSVERSE
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT. VERTICAL
V.S.C VERTICAL SLOTTED CONN.
V.B.F. VERTICAL BRACED FRAME
WWF WELDED WIRE FABRIC
W WIDTH
W/ WITH
LAP CHART
BAR
SIZE
VERT. BARS
#3
#4
#5
#6
#7
#8
#9
#10
HORZ. BARS
4000 PSI CONCRETE
19"
25"
31"
38"
54"
62"
70"
79"
25"
33"
41"
49"
71"
81"
91"
102"
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C:
\R ev it\2
0\2
8_ S_ sp en ce r.te ss ma r.r vt
2/1 8/2
1 9
:59 :47
A M
S-001
GENERAL NOTES AND LEGENDS VA CH_Jesse Brown VA Medical Center
Chicago, Illinois
537-18-142
02/19/2021 ALM SJT
100% BID DOCUMENTS########
7 6 5 4
EXISTING EQUIPMENT PAD
CONCRETE EQUIPMENT PAD
EXTENSION. MATCH THICKNESS
OF EXISTING PAD. SEE NOTE 1.
7'
- 6
3' - 6" ±
EXISTING CONCRETE FLOOR ON STEEL FRAMING
31' - 6" ±
4"
0"
7 6 5 4
A
8' - 11 1/2"
COORD. W/ FINAL EQUIP.
11' - 11 3/4" ±
C8 X1
1.5
C8 X1
1.5
C8x11.5, TYP.
S-101
VE
RI
FY
W
/ M
EC
H.
CO
OR
D.
W
/ F
IN
AL
E
QU
IP
5'
- 2
ROOF OPENING
CURB SUPPORT CHANNEL, TYP. REFER
TO SECTION A-A OF DETAIL 1/S-101
EXISTING CONCRETE FLOOR ON STEEL FRAMING
9'
- 0
1' - 4" ± VERIFY W/ MECH.
4' - 9 1/2"
31' - 6" ±
4"
0"
C8X11.5
C8X11.5
VE
RI
FY
W
/ M
EC
H .
2'
- 1 0 1
/2" 4'
- 6
PLACE RTU BETWEEN EXISTING ROOF DRAINS.
COORDINATE WITH MECH/ARCH ROOF PLANS.
EXISTING W24x68, FIELD VERIFY
EXISTING W24x55, FIELD VERIFY
C8x11.5
3/16
3/16 TYP.
OPENING TO MEET MECH.
EQUIPMENT OPENING
REQUIREMENTS. VERIFY ALL
LOCATIONS W/ MECH. AND ARCH.
PLANS
EXISTING STEEL BEAM
A
A
SECTION A-A
EXISTING DECK PER PLAN
C8x11.5 CROSS MEMBER
EXISTING STEEL BEAM
PER ROOF FRAMING PLAN
L7x4x3/8" CLIP
ANGLE LLV
3/16
3/16 TYP.
C8x11.5
C8 x1
1.5
C8 x1
1.5
NOTE:
REMOVE AND REPLACE EXISTING
FIREPROOFING IN KIND
VARIES (MAX 2')
1 1/4" MIN. MODIFY PLATE SIZE AS REQUIRED FOR
ANCHORS TO BE PLACED MIN. 1 1/4" FROM
EDGE OF UNCUT DECK FLUTES, TYP.
3/8" STEEL PLATE ANCHORED TO BOTTOM OF
EXISTING CONCRETE FLOOR USING (4) 1/2" x 3"
LG. HILTI KH-EZ SCREW ANCHORS (OR EQUAL).
FILL OPENING WITH LIGHTWEIGHT CONCRETE
OR NON-SHRINK GROUT TO MATCH ADJACENT
CONSTRUCTION.
FOR OPENINGS LARGER THAN 12", ADHESIVE
SET #4 x 12" LG. AT 12" O.C. AROUND
PERIMETER. ADHESIVE TO BE HILTI HIT-HY 200
OR APPROVED EQUAL.
6"
NOTE:
USE THIS OPTION FOR OPENINGS NO LARGER THAN 2'x2'
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C:
\R ev it\2
0\2
8_ S_ sp en ce r.te ss ma r.r vt
2/1 8/2
1 9
:59 :47
A M
S-101
FRAMING PLANS - PENTHOUSE VA CH_Jesse Brown VA Medical Center
Chicago, Illinois
537-18-142
02/19/2021 ALM SJT
100% BID DOCUMENTS########
1/4" = 1'-0"
PENTHOUSE FLOOR FRAMING PLAN
1/4" = 1'-0"
PENTHOUSE ROOF FRAMING PLAN3/4" = 1'-0"1 FRAMING @ ROOF OPENING
NOTES
1. EQUIPMENT PAD APPROX. 4"± THICK. FIELD VERIFY. REINFORCE CONCRETE WITH
6x6 W2.1xW2.1 WWF, DOWEL INTO EXISTING PAD WITH #4 BARS x 12" LG. AT 12"
O.C. USING HILTI HIT-HY 200 (OR EQUAL). APPLY BONDING AGENT TO EXISTING
FLOOR PRIOR TO PLACEMENT OF PAD EXTENSION. FLOAT FINISH NEW SLAB.
1 1/2" = 1'-0"2 TYPICAL INFILL DETAIL
MOUNTING HEIGHT
COORDINATION
ARCHITECTURAL,
MECHANICAL &
ELECTRICAL TRADES
SHALL COORDINATE
LOCATIONS OF WALL
MOUNTED ITEMS TO ALIGN
EITHER VERTICALLY OR
HORIZONTALLY.
FINISH FLOOR LINE
DRAWING REFERENCE SYMBOLS RECOMMENDED MOUNTING HEIGHTS (UNLESS OTHERWISE NOTED)
MAX
REACH
DEPTH
MAX
REACH
HEIGHT
0.5"
48"
2"
46"
5"
42"
6"
40"
9"
36"
11"
34"
GENERAL MAXIMUM REACH DEPTH AND HEIGHT
FOR HAND DRYERS / TOWEL DISPENSERS
MAX REACH DEPTH
F O
R R
E A
C H
D E
P T
H M
A X
H E
IG
H
T
M
IR
R O
R O
R
M
IR
R O
R
S H
E
LF
(M
A X
T O
W E
L D
IS
P
E N
S E
M U
LT
I- P
U R
P O
S
U
N
IT
T O
W E
L D
IS
P
E N
S
E C
E P
T A
C
LE
W A
S T
C
E P
T A
C
LE
C O
A T H
O O
K S
S A
N
IT
A R
Y N
A P
K
IN
V
N
D O
R
S O
P
D
IS
P
E N
S E
R
M
A X
M O
P S
T R
IP
H E
LF
12"
A D
A
N D
A
E
LF
C
A T R
O D
M A
X
24"
BOTTOM OF
OUTLET
BOTTOM OF
LIGHT FIXTURE
M
A X
24" MIN
36" MAX
M
IN
M
IN
24" MIN
42" MAX
M
A X
36" MAX
M
IN
24" MIN
42" MAX
/2
M
IN
P R
O T R
U D
G
IL
E
T P
A P
P
E N
S
LO
A T
IO
N
R E
C E
S S
IL
E
T P
A P
P
E N
S
A T
IO
N
P R
O T R
U D
IL
E
T P
A P
P
E N
S
A T
IO
N
M
IN
7"-9"
M
A X
S A
N
IT
A
Y
P K
P O
S A
L
22"
/2
M
IN
P R
O T R
U D
IL
E
T P
A P
P
E N
S
A T
IO
N
E
LE
V A
T O
R W
LL
B
T
T O
N S
(M
IN
" S E
E E
L E
C T
E
LE
C T R
IC
N E
L C
A B
IN
E
T
P O
W E
R P
A N
E L
E
LE
C T R
IC
T E
LE
P
H O
N E
O R
T
LE
T
S W
IT
C
H
P U
S H
B U
T T O
N
F
IR
E A
LA
R
M B
O X
T H
E R
M O
S T A
T
C A
R D
R E
A D
E R
M E
C H
A N
IC
A
L P
A N
E
LS
I
F
IS
H
E D
S P
A C
E S
S E
LE
C
T O
R S
W
IT
C H
R
S
S W
IT
C
H O
R W
LL
T
LE
T
A B
O
B
IN
E T
SS
SEE PLAN
12" 12"
H A
N D
R A
IL
R A
M P
T O
C A
B
IN
E T
H A
N D
L E
F
IR
E E
X T
IN
G
U
IS
H E
R
F
IR
E E
X T
IN
G U
IS
H
B
IN
E
T F
IR
E H
O S
E
O R
C O
M B
IN
A
T
IO
B
IN
E T
54" MIN
GRAB BAR
GRAB BAR
'-8
M
A X
6" MAX 36"
(MIN)
18"
GRAB BAR
40"
13" MAX
42" 42"
W A
T E
R C
LO
S
E T
W A
T E
R C
LO
S
E T
(M A
X
(M
A X
B A
R R
IE
E E
U R
IN
A
L
S T A
N D
A R
IN
A L
GRAB BAR
18"
T R
A N
S F E
R
T Y
P E
S H
O W
E R
FOLDING
SHOWER SEAT
R O
LL
-I N
-T Y
O
W E
R
M
IN
T R
A N
S F E
R
T Y
P E
S H
O W
E R
(M
IN
(M A
X
T O
P S
P O
U T
M A
X S
IN
K
D E
P T
H
11"
(MIN)
17"
3" (MAX)
WALL
SPACE
AVAILABLE
NOTE:
WATER SUPPLY & DRAIN
PIPES BELOW LAVATORIES
AND SINKS MUST BE
INSULATED OR OTHERWISE
CONFIGURED TO PROTECT
AGAINST CONTACT.
E W
C
IN
K
U N
T A
IN
W A
LL
H
U N
G L
A V
B A
R R
IE
E E
L A
U
N T E
R
M
IN
MAX
0' - 4"
6" MAX
ALIGN WITH EDGE OF SEAT
6'
0"
ENLARGED PLAN OR DETAIL
WALL SECTION
X-###
X
X
X-###
BUILDING SECTION
EXTERIOR ELEVATIONS
INTERIOR ELEVATIONS
DEMO KEYNOTE##
REVISION CLOUD AND TAG
VIEW TITLE & REFERENCE
EXISTING COLUMN LINE
NEW COLUMN LINE
DETAIL
LEVEL OR ELEVATION
XX
DEMARCATION LINE
X-###
X-###
X-###
X-###
X-###
X-###
X## EQUIPMENT TAG
WALL TAG
###.# DOOR TAG
ROOM NAME
ROOM TAG
WINDOW TAG
X#
## ARCHITECTURAL KEYNOTE
#' - #" CEILING SPOT ELEVATION
XX# FURNITURE TAG
FINISH TAG
SPECIALITY EQUIPMENT TAG
XX-#
XX- #
VARIES
CONTINUOUS ACOUSTIC
SEALANT
CEILING - SEE ROOM
FINISH SCHEDULE.
METAL STUDS AT 1'-4" O.C.
METAL RUNNER
CHANNEL SECURE
TO FLOOR
SOUND ATTENUATION
BLANKET INSULATION
GYPSUM BOARD
NOTE: EXTEND GYPSUM
BOARD AND FINISHES TO
UNDERSIDE OF DECK (DO
NOT SECURE GYPSUM
BOAD TO TRACK)
UNDERSIDE OF DECK ABOVE
PARTITION TYPE 'F3'
(NON-RATED/ 4" METAL STUDS WITH 5/8"
GYPSUM BOARD ON ONE SIDE/INSULATED)
WALL BASE
CONTINUOUS
ACOUSTIC SEALANT
VARIES
CONTINUOUS ACOUSTIC
SEALANT
CEILING - SEE ROOM
FINISH SCHEDULE
METAL STUDS AT 1'-4" O.C.
METAL RUNNER
CHANNEL SECURE
TO FLOOR
SOUND ATTENUATION
BLANKET INSULATION
GYPSUM BOARD
NOTE: EXTEND GYPSUM
BOARD AND FINISHES TO
UNDERSIDE OF DECK (DO
NOT SECURE GYPSUM
BOAD TO TRACK)
UNDERSIDE OF DECK ABOVE
PARTITION TYPE 'S1'
(NON-RATED/ 4" METAL STUDS WITH 5/8"
GYPSUM BOARD ON BOTH SIDES /INSULATED)
WALL BASE
CONTINUOUS
ACOUSTIC SEALANT
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 5:
P
M
A-001
ARCHITECTURAL LEGENDS,
SYMBOLS, AND ABBREVIATIONS
S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
ABBREVIATIONS
ABBREV. FULL TEXT
T.O.F. OR T/F TOP OF FOOTING
T.O.M. OR T/M TOP OF MASONRY
T.O.P. OR T/P TOP OF PAVEMENT
T.O.S. OR T/S TOP OF STEEL
T.O.W. OR T/W TOP OF WALL
T/ TOP OF
TB TRUSS BEARING
TG TEMPERED GLASS
THK THICK
THRESH THRESHOLD
TLT TOILET
TP TOILET PARTITION
TR TRANSITION TRIM
TYP TYPICAL
TYP TYPICAL
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WC WALLCOVERING
WCO WALL CLEAN OUT
WCVR WALLCOVERING
WD WOOD
WP WATERPROOFING
WP WORKPOINT
WP WALL PROTECTION
WS WINDOW SHADE
WSCT WAINSCOT
WT WEIGHT
X-(MATERIAL) DENOTES EXISTING MATERIAL
REFRENCED
ABBREVIATIONS
ABBREV. FULL TEXT
SCWD SOLID CORE WOOD
SECT SECTION
SER.RECPT SERVICE RECEPTOR
SH SHELF
SHT SHEET
SHWR SHOWER
SIM SIMILAR
SLR CONCRETE SEALER
SLS SOLID SURFACE
SLV SHORT LEG VERTICAL
SPEC SPECIFICATION
SQ SQUARE
SQFT SQUARE FOOT
SS STAINLESS STEEL
SSK SERVICE SINK
SSM SOLID SURFACING MATERIAL
ST SMOKE-TIGHT PER CODE TO RESIST THE
PASSAGE OF SMOKE
STD STANDARD
STDW STANDARD WEIGHT (STEEL PIPE)
STL STEEL
STN STAIN
STOR STORAGE
STRL STRUCTURAL
SUPP SUPPORT
SUSP SUSPENDED
SYM SUSPENSION SYMMETRICAL
T TREAD
T&G TONGUE AND GROOVE
T.O.C. OR T/C TOP OF CONCRETE
ABBREVIATIONS
ABBREV. FULL TEXT
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLY PLYWOOD
PT PRESSURE TREATED
PT PORCELAIN TILE
PTB PORCELAIN TILE BASE
QT QUARRY TILE
QTB QUARTZ TILE BASE
QTZ QUARTZ
R RISER
RA RETURN AIR
RB RUBBER BASE
RC ROOF CONDUCTOR
RD ROOF DRAIN
RD ROUND
RECVG RECEIVING
REF REFRIGERATOR
REINF REINFORCED
REQ'D REQUIRED
RF RESILIENT FLOORING
RH RIGHT HAND
RL ROOF LADDER
RM ROOM
RO ROUGH OPENING
RS ROOF SUMP
RSN RESIN
RWD REDWOOD
RWD RIGID WALL PROTECTION
S SOUTH
S SPANDREL GLASS
SA SUPPLY AIR
SAB SOUND ATTENUATION BLANKETS
SC SOLID CORE
SCH SCHEDULE
SCONC SEALED CONCRETE
ABBREVIATIONS
ABBREV. FULL TEXT
MAX MAXIMUM
MBH THOUSAND BTU/HR
MC MEDICINE CABINET
MCA MINIMUM CIRCUIT AMPACITY
MCC MULTI-COLOR COATING
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMBWP MEMBRANE WATERPROOFING
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MFS MAXIMUM FUSE SIZE
MG MEDICAL GAS
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN. MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MM MISCELLANEOUS METALS
MO MASONRY OPENING
MOCP MAXIMUM OVERCRRENT PROTECTION
MPC MICHIGAN PLUMBING CODE
MR MANUFACTURER'S RECOMMENDATIONS
MT MARBLE TILE
MTD MOUNTED
MUL. MULLION
N NORTH
N.S. NEAR SIDE
NF NO FINISH
NIC NOT IN CONTRACT
NO NUMBER
NPSH NET POSITIVE SUCTION HEAD
NSNS NON SHRINK NON STAIN GROUT
NTS NOT TO SCALE
NTS NOT TO SCALE
O.C. OR OC ON CENTER
OBSGL OBSCURE GLASS
OD OUTSIDE DIAMETER
OHDR SECTIONAL OVERHEAD DOOR
OPNG OPENING
OPP OPPOSITE
P PAINT
PART PARTITION
PB PARTICLE BOARD
PC PRECAST
PCS PIECES
PERM PERMANENT
PL PLATE
ABBREVIATIONS
ABBREV. FULL TEXT
FV FIELD VERIFY
G.B. GRAB BAR, GRADE BEAM
G.O. GRILL OPENING
GA GAUGE
GALV GALVANIZED
GCT GLAZED CERAMIC TILE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GL GLASS
GND. GROUND
GR. GRADE
GRTG. GRATING
GSCFT GLAZED STRUCTURAL CLAY FACING TILE
GT GROUT
GYP. BD. GYPSUM BOARD
HC HOLLOW CORE
HCWD HOLLOW CORE WOOD
HDPB HIGH DENSITY PARTICLEBOARD
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HT HEIGHT
HWD HARDWARE
I.D. OR ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IG INSULATING GLASS
IN INCHES
INCL INCLUDING, INCLUSIVE
INSUL INSULATION
INT INTERIOR
IPS INTERIOR PAINT SYSTEM
JAN JANITOR
JT JOINT
kW KILOWATTS kWh KILOWATT HOURS
LAD LADDER
LAM LAMINATED
LAV LAVATORY
LF LINEAR FEET
LGTH LENGTH
LH LEFT HAND
LKR LOCKER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LO LOUVER OPENING
LP LIGHTING PANEL
LPG LIQUID PETROLEUM GAS
LPS LOW PRESSURE STEAM
LT LIGHT
LWT LEAVING WATER TEMPERATURE
MA MEDICAL AIR
MANUF MANUFACTURER
MAS MASONRY
MATL MATERIAL
ABBREVIATIONS
ABBREV. FULL TEXT
CTR COUNTER
CTSK COUNTERSINK
DEXS DOUBLE EXTRA STRONG (STEEL PIPE)
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DN DOWN
DO DOOR OPENING
DR DOOR
DS DOWN SPOUT
DT DRAIN TILE
DTL DETAIL
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EIFS EXTERIOR INSULATION AND FINISH
SYSTEMS
EJ EXPANSION JOINT
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR OR ELEVATION
ENCL ENCLOSURE
EP EPOXY PAINT
EPS EXTERIOR PAINT SYSTEM
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
EW EACH WAY
EWC ELECTRICAL WATER COOLER
EX EXISTING
EXGR EXISTING GRADE
EXP EXPANSION
EXS EXTRA STRONG (STEEL PIPE)
EXT EXTERIOR
FA FIRE ALARM
FAB FABRIC/UPHOLSTERY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FG FROSTED GLASS
FHC FIRE HOSE CABINET
FIN FINISH
FL FLOOR
FLL FLOOR LINE
FLUOR FLUORESCENT
FOC FACE OF COLUMN
FOCONC FACE OF CONCRETE
FRC FIBER REINFORCED CONCRETE
FRP FIELD REINFORCED PANEL
FRPFG FIREPROOFING
FS FULL SIZE
FT FIRE TREATED
FTG FOOTING
FUR FURRING
ABBREVIATIONS
ABBREV. FULL TEXT
AB ANCHOR BOLT
ABI ADDITIVE BID ITEM
AC ACOUSTICAL
ACB ACOUSTICAL CEILING BAFFLE
ACP ACOUSTICAL CEILING PANEL
ACS ACOUSTICAL CEILING SPRAY
AD AREA DRAIN
ADA ADA
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
ALUM ALUMINUM
AP ACCESS DOORS
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASPH ASPHALT
AWP ACOUSTICAL WALL PANEL
B/ BOTTOM OF
BD BOARD
BF BARRIER FREE
BIT BITUMINOUS
BL BUILDING LINE
BLDG BUILDING
BLKHD BULKHEAD
BOTT BOTTOM
BP BASE PLATE
BR BUMP RAIL
BS BOTH SIDES
BUR BUILT UP ROOFING
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CG CORNER GUARD
CH CHANNEL
CHKDPL CHECKERED PLATE
CJ CONTROL JOINT
CL CENTERLINE
CL TO CL CENTERLINE TO CENTERLINE
CLG CEILING
CLK CAULKING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMP COMPRESSIBLE
COMPO COMPOSITION
CONC CONCRETE
CONN CONNECT, CONNECTION
CONST CONSTRUCTION
CONST JT CONSTRUCTION JOINT
CONT CONTINUOUS
CONTR CONTRACTOR
CPT CARPET TILE
CS CONCRETE SEALER
DEMO PLAN LEGEND:
EXISTING WALL OR PARTITION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING BUILDING COMPONENT & STRUCTURE
TO REMAIN
EXISTING WALL/PARTITION OR EXISTING ITEMS
TO BE REMOVED
EXISTING DOOR & FRAME TO BE REMOVED
EXISTING ASSEMBLY TO BE REMOVED
EXISTING SUSPENDED CEILING TO BE REMOVED
EXISTING GYPSUM BOARD TO BE REMOVED
NOTE: ALL ITEMS SHOWN RED AND DASHED ARE
TO BE DEMOLISHED- U.N.O.
GENERAL DEMOLITION NOTES:
1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED
PRIOR TO DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME
THE PROPERTY OF THE DEMOLITION SUBCONTRACTOR.
2. FOR PLUMBING, FIRE PROTECTION, MECHANICAL, AND/OR ELECTRICAL
WORK, REFER TO ALL CONTRACT DOCUMENTS FOR ADDITIONAL DEMOLITION
NOTES AND INFORMATION. NOT ALL WORK IS SHOWN WITHIN
ARCHITECTURAL PLANS.
3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.
4. CONTRACTOR AND SUBCONTRACTORS SHALL VISIT THE SITE PRIOR TO
SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTING CONDITIONS
5. CONTRACTOR AND DEMOLITION SUBCONTRACTOR TO COORDINATE
DEMOLITION WORK WITH OWNER PRIOR TO START OF WORK.
MINOR OR
SURGERY RM
CORRIDOR
C1105
RECOVERY RM
D1
D1
D3
D3
REMOVE EXTENT OF CEILING FOR
NEW MECHANICAL DIFFUSER
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 5:
P
M
AD101
RCP DEMOLITION PLAN - FIRST &
SECOND LEVEL
S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
1/4" = 1'-0"
RCP DEMOLITION PLAN - FIRST LEVEL
DEMOLITION NOTES
KEY VALUE KEYNOTE TEXT
D1 REMOVE CEILING INCLUDING ALL BRACKETS, ANCHORS &
SUPPORTS. PATCH AND REPAIR ADJACENT SURFACES AT AREAS
OF REMOVAL TO MATCH EXISTING AND/OR AS REQUIRED FOR
PROPER INSTALLATION OF NEW FINISHES. PROVIDE NEW CEILING
TILES FOR ANY ADJACENT TILES THAT ARE TO REMAIN, THAT ARE
DAMAGED DURING DEMOLITION.
D2 REMOVE CEILING ACCESS PANEL IN ITS ENTIRETY.
D3 PREPARE ALL ABANDONED WALL PENETRATIONS DUE TO
DEMOLITION WORK FOR WALL INFILL. PATCH, REPAIR, AND/OR
REPLACE ADJACENT WALL FINISHES AT AREAS OF REMOVAL TO
MATCH EXISTING AND/OR AS REQUIRED FOR PROPER INSTALLATION
OF NEW FINISHES.
D5 REMOVE SLOPED BULKHEAD IN ITS ENTIRETY. PATCH AND REPAIR
ADJACENT SUFACES AS REQUIRED FOR PROPER INSTALLATION OF
NEW FINISHES.
D6 REMOVE DUCTWORK, LOUVER, AND/OR AIR CONDITIONING WINDOW
UNIT LOCATED WITH IN EXISTING WINDOW SYSTEM. PREPARE
WINDOW FRAME FOR NEW GLAZING INFILL. PATCH AND REPAIR
ADJACENT SUFACES AS REQUIRED FOR PROPER INSTALLATION OF
NEW FINISHES.
D7 EXTERIOR BLOCK WINDOW WALL TO BE REMOVED. PATCH AND
REPAIR ADJACENT SURFACES TO MATCH EXISTING AND/OR AS
REQUIRED FOR PROPER INSTALLATION OF NEW FINISHES.
DEMO PLAN LEGEND:
EXISTING WALL OR PARTITION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING BUILDING COMPONENT & STRUCTURE
TO REMAIN
EXISTING WALL/PARTITION OR EXISTING ITEMS
TO BE REMOVED
EXISTING DOOR & FRAME TO BE REMOVED
EXISTING ASSEMBLY TO BE REMOVED
EXISTING SUSPENDED CEILING TO BE REMOVED
EXISTING GYPSUM BOARD TO BE REMOVED
NOTE: ALL ITEMS SHOWN RED AND DASHED ARE
TO BE DEMOLISHED- U.N.O.
GENERAL DEMOLITION NOTES:
1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED
PRIOR TO DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME
THE PROPERTY OF THE DEMOLITION SUBCONTRACTOR.
2. FOR PLUMBING, FIRE PROTECTION, MECHANICAL, AND/OR ELECTRICAL
WORK, REFER TO ALL CONTRACT DOCUMENTS FOR ADDITIONAL DEMOLITION
NOTES AND INFORMATION. NOT ALL WORK IS SHOWN WITHIN
ARCHITECTURAL PLANS.
3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.
4. CONTRACTOR AND SUBCONTRACTORS SHALL VISIT THE SITE PRIOR TO
SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTING CONDITIONS
5. CONTRACTOR AND DEMOLITION SUBCONTRACTOR TO COORDINATE
DEMOLITION WORK WITH OWNER PRIOR TO START OF WORK.
E
8 7 6 5 4
D
C
B
A
E.1
4.2
OFFICE
CUBICLE
SPD
SUPERVISOR
ADMIN OFFICE
SYSTEM
ANALYST
CORRIDOR
C3405
ELECTRICAL
CLOSET
34E1
OFFICE
CUBICLE
STORAGE
DIALYSIS RM
D1
D1
D1 D1
D1
D1
D1
D1
D1
D1
CORRIDOR
C3405
CORRIDOR
C3404
D2
D2
D2
D2
D2
D2
D2
D2
D2
SLOPED BULKHEAD
SLOPED BULKHEAD
D3
D3
D3
D3
D3
D3
D3
D3
D5
D5
D1D3
D2
D2
D6
D6
D6
D6
D7
E
8 7 6 5 4
D
C
B
A
E.1
4.2
EQUIPMENT
STORAGE
WAITING
TEAM RM
5413LOCKER
UNISEX TOILET
CORRIDOR
C5405
TOILET
5406A
ELECTRICAL
CLOSET
54E1
TREATMENT
BED 5
RECEPTION
AREA
TREATMENT
BED 1
TREATMENT
BED 3
DIRTY LINEN
5400B
CLEAN LINEN
5400A
TREATMENT
BED 2
TREATMENT
BED 4
LOUNGE
NIC
D1
D1 D1
D1D1
D1D1
D1
D1
D1
D1 D1
D1
D1
D2
D2 D2
D2
D2
D2
D2
D2
D2 D2
D2
D2
D2
D2
D2 D2
D2
D2
D2
D2
D2
D2
D2D2
D2
D2
D2
D2
D2
D2
D3 D3
D3 D3
D3
D3 D3
D3
D3
D3
D3 D3
D3
D3
D3
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 5:
P
M
AD102
RCP DEMOLITION PLAN - THIRD &
FIFTH LEVEL
S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
1/4" = 1'-0"
RCP DEMOLITION PLAN - THIRD LEVEL
1/4" = 1'-0"
RCP DEMOLITION PLAN - FIFTH LEVEL
DEMOLITION NOTES
KEY VALUE KEYNOTE TEXT
D1 REMOVE CEILING INCLUDING ALL BRACKETS, ANCHORS &
SUPPORTS. PATCH AND REPAIR ADJACENT SURFACES AT AREAS
OF REMOVAL TO MATCH EXISTING AND/OR AS REQUIRED FOR
PROPER INSTALLATION OF NEW FINISHES. PROVIDE NEW CEILING
TILES FOR ANY ADJACENT TILES THAT ARE TO REMAIN, THAT ARE
DAMAGED DURING DEMOLITION.
D2 REMOVE CEILING ACCESS PANEL IN ITS ENTIRETY.
D3 PREPARE ALL ABANDONED WALL PENETRATIONS DUE TO
DEMOLITION WORK FOR WALL INFILL. PATCH, REPAIR, AND/OR
REPLACE ADJACENT WALL FINISHES AT AREAS OF REMOVAL TO
MATCH EXISTING AND/OR AS REQUIRED FOR PROPER INSTALLATION
OF NEW FINISHES.
D5 REMOVE SLOPED BULKHEAD IN ITS ENTIRETY. PATCH AND REPAIR
ADJACENT SUFACES AS REQUIRED FOR PROPER INSTALLATION OF
NEW FINISHES.
D6 REMOVE DUCTWORK, LOUVER, AND/OR AIR CONDITIONING WINDOW
UNIT LOCATED WITH IN EXISTING WINDOW SYSTEM. PREPARE
WINDOW FRAME FOR NEW GLAZING INFILL. PATCH AND REPAIR
ADJACENT SUFACES AS REQUIRED FOR PROPER INSTALLATION OF
NEW FINISHES.
D7 EXTERIOR BLOCK WINDOW WALL TO BE REMOVED. PATCH AND
REPAIR ADJACENT SURFACES TO MATCH EXISTING AND/OR AS
REQUIRED FOR PROPER INSTALLATION OF NEW FINISHES.
JJ
MINOR OR
SURGERY RM
RECOVERY RM
CORRIDOR
C1105
A1A1
A2A2
A1A1 A2A2
A1A1
A2A2
7 6 5 4
A
NORTH
PENTHOUSE
BUILDING 30
FIRST LEVEL ROOFFIRST LEVEL ROOF
FIRST LEVEL ROOF
ROOFTOP ACCESS LADDER
EXISTING CONCRETE PAD
EXISTING CONCRETE PAD
CONTRACTOR TO ACCESS
NORTH PENTHOUSE BY
DOOR LOCATED OFF OF
FIRST LEVEL ROOF
NEW CONCRETE PAD
EXTENTION, SEE
STRUCTURAL DRAWINGS
1. SUB-CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.
2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE
VERIFIED WITH THE OWNER'S REPRESENTATIVE OR THE MOST STRINGENT
PROVISIONS SHALL GOVERN.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS
SHALL BE VERIFIED WITH OWNER'S REPRESENTATIVE PRIOR TO
CONSTRUCTION OF THAT AREA.
4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS OR
DIMENSIONAL DISCREPANCIES SHALL BE VERIFIED WITH OWNER'S
REPRESENTATIVE.
5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE
CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,
ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT
INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE
OWNER'S REPRESENTATIVE FOR REVIEW PRIOR TO FABRICATION, ERECTION,
AND/OR CONSTRUCTION.
6. CONSTRUCTION MANAGER (CM) / GENERAL CONTRACTOR (GC) TO REVIEW
ENTIRE SET OF CONSTRUCTION DOCUMENTS AND SHALL COORDINATE WORK
BETWEEN ALL TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF
TRADES, CM / GC IS TO VERIFY CONFLICT WITH OWNER'S REPRESENTATIVE
PRIOR TO CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.
7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR
IMBEDDED ITEMS WERE REMOVED.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATIONS OF THE
WALLS AND CEILINGS FOR NEW FINISHES.
9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,
EMBEDMENTS, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE
CONTINUITY OF THE RATING
10. ALL DIMENSIONS ARE FROM FACE OF STUD, C.M.U., OR CONCRETE , U.N.O.
11. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN
CONTACT WITH ONE ANOTHER
12. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D. DUE TO
DEMOLITION WORK. MATCH ADJACENT MATERIAL & COLOR.
13. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS
WHERE MILLWORK, PLUMBING FIXTURES, EQUIP., ETC. ATTACH TO WALL OR
CEILING.
GENERAL NOTES:
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 5:
P
M
A-101
FLOOR PLAN - FIRST & SECOND
LEVEL
S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
1/4" = 1'-0"
FLOOR PLAN - FIRST LEVEL
1/4" = 1'-0"
FLOOR PLAN - SECOND LEVEL NORTH PENTHOUSE
ARCHITECTURE NOTES
KEY VALUE KEYNOTE TEXT
A1 INFILL ALL ABANDONED WALL PENETRATIONS DUE TO DEMOLITION WORK
WITH WALL CONSTRUCTION TO MATCH EXISTING. MAINTAIN EXISTING
FIRE RATINGS FOR CONTINUOUS COVERAGE.
A2 PATCH AND REPAIR ALL MINOR AND MAJOR BLEMISHES FOUND BETWEEN
THE FINISHED FLOOR AND CEILING AS REQUIRED TO MAKE LIKE NEW.
PREPARE FOR PROPER INSTALLATION OF NEW FINISHES.
A3 PATCH AND REPAIR WALL JAMB AROUND WINDOW TO MATCH EXISTING
WHERE PREVIOUSLY HIDDEN BY SLOPED BULKHEAD.
A4 PROVIDE NEW INSULATED GLAZING TO MATCH EXISTING WHERE
LOUVER, AIR CONDITIONER, AND/OR DUCT WAS PREVIOUSLY REMOVED,
MAKE AIRTIGHT. CONTRACTOR TO VERIFY SIZE AND CONDITION OF
EXISTING GLAZING AND FRAME.
A5 CONTRACTOR TO VERIFY IF WINDOW GLAZING & FRAME ARE
PREVIOUSLY PAINTED. IF CURRENTLY PAINTED, REPAINT TO MATCH
WALL.
D
C
B
A
E.1
4.2
OFFICE
CUBICLE
SPD
SUPERVISOR
ADMIN OFFICE
SYSTEM
ANALYST
CORRIDOR
C3405
STORAGE
ELECTRICAL
CLOSET
34E1
OFFICE
CUBICLE
DIALYSIS RM
A1A1 A2A2
A1A1 A2A2
A1A1 A2A2
A3A3 A4A4
A3A3
A4A4
A1A1
A2A2
A1A1 A2A2
A1A1 A2A2
A1A1 A2A2
A1A1
A5A5
A5A5
A5A5
A4A4
A4A4
A4A4
A-1031
F3
F3F3
F3
S1
A-103
1'
ALIGN
2' - 8"
ABOVE
A-103
ALIGN
INFILL FLOOR WHERE MECHANICAL PIPING
WAS REMOVED, PATCH AND REPAIR
FLOORING TO MATCH EXISTING, PATCH AND
REPAIR EXISTING SECOND LEVEL CEILING AS
REQUIRED FOR NEW WORK
NEW BASE
NEW BASE
F3
A2A2
E
8 7 6 5 4
D
C
B
A
E.1
4.2
WAITING
TEAM RM
LOCKER
RECEPTION
AREA
LOUNGE
UNISEX TOILET
ELECTRICAL
CLOSET
54E1
TOILET
5406A
TREATMENT
BED 5
CORRIDOR
C5405
TREATMENT
BED 1
TREATMENT
BED 4
TREATMENT
BED 3
TREATMENT
BED 2
CLEAN LINEN
5400A
DIRTY LINEN
5400B
A1A1 A2A2A1A1
A2A2
A1A1 A2A2
A1A1 A2A2
A1A1
A2A2
A1A1 A2A2
A1A1 A2A2
A1A1 A2A2
A1A1 A2A2
A1A1 A2A2A1A1
A2A2
A1A1 A2A2 A1A1
A2A2
A1A1 A2A2
EQUIPMENT
STORAGE
1. SUB-CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.
2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE
VERIFIED WITH THE OWNER'S REPRESENTATIVE OR THE MOST STRINGENT
PROVISIONS SHALL GOVERN.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS
SHALL BE VERIFIED WITH OWNER'S REPRESENTATIVE PRIOR TO
CONSTRUCTION OF THAT AREA.
4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS OR
DIMENSIONAL DISCREPANCIES SHALL BE VERIFIED WITH OWNER'S
REPRESENTATIVE.
5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE
CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,
ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT
INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE
OWNER'S REPRESENTATIVE FOR REVIEW PRIOR TO FABRICATION, ERECTION,
AND/OR CONSTRUCTION.
6. CONSTRUCTION MANAGER (CM) / GENERAL CONTRACTOR (GC) TO REVIEW
ENTIRE SET OF CONSTRUCTION DOCUMENTS AND SHALL COORDINATE WORK
BETWEEN ALL TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF
TRADES, CM / GC IS TO VERIFY CONFLICT WITH OWNER'S REPRESENTATIVE
PRIOR TO CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.
7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR
IMBEDDED ITEMS WERE REMOVED.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATIONS OF THE
WALLS AND CEILINGS FOR NEW FINISHES.
9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,
EMBEDMENTS, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE
CONTINUITY OF THE RATING
10. ALL DIMENSIONS ARE FROM FACE OF STUD, C.M.U., OR CONCRETE , U.N.O.
11. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN
CONTACT WITH ONE ANOTHER
12. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D. DUE TO
DEMOLITION WORK. MATCH ADJACENT MATERIAL & COLOR.
13. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS
WHERE MILLWORK, PLUMBING FIXTURES, EQUIP., ETC. ATTACH TO WALL OR
CEILING.
GENERAL NOTES:
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 5:
P
M
A-102
FLOOR PLAN - THIRD & FIFTH
LEVEL
S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
1/4" = 1'-0"
FLOOR PLAN - THIRD LEVEL
1/4" = 1'-0"
FLOOR PLAN - FIFTH LEVEL
ARCHITECTURE NOTES
KEY VALUE KEYNOTE TEXT
A1 INFILL ALL ABANDONED WALL PENETRATIONS DUE TO DEMOLITION WORK
WITH WALL CONSTRUCTION TO MATCH EXISTING. MAINTAIN EXISTING
FIRE RATINGS FOR CONTINUOUS COVERAGE.
A2 PATCH AND REPAIR ALL MINOR AND MAJOR BLEMISHES FOUND BETWEEN
THE FINISHED FLOOR AND CEILING AS REQUIRED TO MAKE LIKE NEW.
PREPARE FOR PROPER INSTALLATION OF NEW FINISHES.
A3 PATCH AND REPAIR WALL JAMB AROUND WINDOW TO MATCH EXISTING
WHERE PREVIOUSLY HIDDEN BY SLOPED BULKHEAD.
A4 PROVIDE NEW INSULATED GLAZING TO MATCH EXISTING WHERE
LOUVER, AIR CONDITIONER, AND/OR DUCT WAS PREVIOUSLY REMOVED,
MAKE AIRTIGHT. CONTRACTOR TO VERIFY SIZE AND CONDITION OF
EXISTING GLAZING AND FRAME.
A5 CONTRACTOR TO VERIFY IF WINDOW GLAZING & FRAME ARE
PREVIOUSLY PAINTED. IF CURRENTLY PAINTED, REPAINT TO MATCH
WALL.
ROOM FINISH GENERAL NOTES
1. DOOR FRAME COLOR CHANGES SHALL OCCUR ON STOP AS IF DOOR IS IN
CLOSED POSITION WITH THE DOOR AND FRAME SHOWING AS ONE COLOR.
2. ALL AREAS EXPOSED TO VIEW ABOVE THE CEILINGS ARE TO BE PAINTED.
REFER TO INTERIORS DOCUMENTS FOR COLOR .
3. ALL EXPOSED STRUCTURAL, PLUMBING, MECHANICAL & ELECTRICAL
ELEMENTS ARE TO BE PAINTED. REFER TO INTERIORS DOCUMENTS FOR
COLOR.
1. SUB-CONTRACTORS ARE TO COORDINATE WORK WITH ALL OTHER TRADES.
2. CONFLICTS BETWEEN NOTES, DETAILS, SPECIFICATIONS, ETC., SHALL BE
VERIFIED WITH THE OWNER'S REPRESENTATIVE OR THE MOST STRINGENT
PROVISIONS SHALL GOVERN.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
NATURE AS SHOWN FOR SIMILAR CONDITIONS. ANY UNCLEAR CONDITIONS
SHALL BE VERIFIED WITH OWNER'S REPRESENTATIVE PRIOR TO
CONSTRUCTION OF THAT AREA.
4. DRAWINGS ARE NOT TO BE SCALED. ANY UNCLEAR DIMENSIONS OR
DIMENSIONAL DISCREPANCIES SHALL BE VERIFIED WITH OWNER'S
REPRESENTATIVE.
5. ALL EXISTING CONDITIONS AND ALL RELATED DIMENSIONS INDICATED IN THE
CONTRACT DOCUMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION,
ERECTION, AND/OR CONSTRUCTION. ANY CONDITIONS THAT DIFFER FROM THAT
INDICATED IN THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE
OWNER'S REPRESENTATIVE FOR REVIEW PRIOR TO FABRICATION, ERECTION,
AND/OR CONSTRUCTION.
6. CONSTRUCTION MANAGER (CM) / GENERAL CONTRACTOR (GC) TO REVIEW
ENTIRE SET OF CONSTRUCTION DOCUMENTS AND SHALL COORDINATE WORK
BETWEEN ALL TRADES. IF CONFLICTS ARISE DUE TO COORDINATION OF
TRADES, CM / GC IS TO VERIFY CONFLICT WITH OWNER'S REPRESENTATIVE
PRIOR TO CONSTRUCTION / INSTALLATION OF CONFLICTING ITEMS.
7. PATCH ALL EXPOSED INTERIOR AND EXTERIOR WALLS WHERE ATTACHED OR
IMBEDDED ITEMS WERE REMOVED.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATIONS OF THE
WALLS AND CEILINGS FOR NEW FINISHES.
9. MAINTAIN FIRE RATING AT ALL ASSEMBLIES WHERE OPENINGS PENETRATIONS,
EMBEDMENTS, RECESSED EQUIPMENT, ACCESSORIES, ETC. DISRUPT THE
CONTINUITY OF THE RATING
10. ALL DIMENSIONS ARE FROM FACE OF STUD, C.M.U., OR CONCRETE , U.N.O.
11. PROVIDE ISOLATION MATERIAL BETWEEN DISSIMILAR MATERIALS THAT ARE IN
CONTACT WITH ONE ANOTHER
12. PATCH & REPAIR ALL MAJOR & MINOR BLEMISHES AS REQ'D. DUE TO
DEMOLITION WORK. MATCH ADJACENT MATERIAL & COLOR.
13. PROVIDE SOLID, CONTINUOUS, NON COMBUSTIBLE BLOCKING AT LOCATIONS
WHERE MILLWORK, PLUMBING FIXTURES, EQUIP., ETC. ATTACH TO WALL OR
CEILING.
GENERAL NOTES:
ADMIN OFFICE
FURNITURE NOT
IN CONTRACT
NEW WALL BASE,
MATCH EXISTING
EXISTING WALL BASE
5'
6"
3' - 8 3/4" +/-
GYP. BD. BULKHEAD
A-112
EXISTING WALL CONSTRUCTION TO REMAIN
EXISTING PERIMETER WINDOW
FRAME TO REMAIN
REMOVE EXISTING WINDOW INSIDE
PERIMETER FRAME, PROVIDE INSULATED
METAL PANEL TO SURROUND DUCT
PENETRATION AND TO FULLY INFILL
PERIMETER WINDOW FRAME. MAKE
WATER AND AIR TIGHT
BACKER ROD AND SEALANT
ALIGN GYP. BD. W/ EDGE OF
CENTER MULLION
EXISTING CENTER MULLION TO REMAIN
BREAK METAL TRIM, PAINT TO
MATCH WINDOW MULLION
WALL BELOW
SLOPED SILL TO REMAIN
PARTIAL HEIGHT STUD, WINDOW
SILL TO WINDOW HEAD
FULL HEIGHT STUD, FLOOR TO DECK ABOVE
PARTIAL HEIGHT WALL
DUCT PENETRATION - SEE MECHANICAL
DRAWINGS
EXISTING TO REMAIN
GLASS BLOCK TO BE
DEMOLISHED
MECHANICAL DUCT -
SEE MECHANICAL
DRAWINGS
INFILL WALL W/ BRICK
& CMU. MATCH
EXISTING. KEEP
EXISTING FIRE RATING
EXISTING STUD &
FURRING WALL TO
BE DEMOLISHED,
EXISTING BLOCK TO
REMAIN
EXISTING TO REMAIN
NEW JAMB & SILL
FLASHING
O V
E R
LA
P
8" M
IN
SELF-ADHERED
VAPOR BARRIER
BACKER ROD AND SEALANT,
ENTIRE PERIMETER
N
PARKING
GARAGE
OFFICE 11A
11B
1-B 1-A
KEY PLAN
NOT TO SCALE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
N O
T F
O R
C O
N S
T R
U C
T
IO
N
3419 PIERSON PLACE
FLUSHING, MI, 48433
(OFFICE) 810-230-6202
211 E. Water Street, Suite 213L Kalamazoo, MI 49007
269.216.0222
VA STATION
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
Jesse Brown VA Medical Center
820 S. Damen Ave.
Chicago, IL, 60612
C :\R ev it\
\2
8_
A _m ic he lle .b ur ri.
rv t
2/
/2
:3 5:
P
M
A-103
ROOM FINISH & MATERIALS
SCHEDULES
S10C AHU
REPLACEMENT
Chicago, Illinois
537-18-142
02/19/2021 TM MZ
100% BID DOCUMENTS200138 J0019
MATERIALS SCHEDULE
MARK MANUFACTURER STYLE PATTERN & COLOR
FINISH
NOTES MATERIAL
RB-1 Match Existing Match Existing Match Existing Match Existing Match Existing
ACOUSTICAL CEILING PANEL
ACP-1 Armstrong Ceilings
PAINT
P-1 Benjamin Moore
ROOM FINISH SCHEDULE
ROOM NO. ROOM NAME
FLOOR WALL DOOR
FRAME
CEILING
FINISH NOTESFINISH BASE NORTH SOUTH EAST WEST FINISH BULKHEAD
01.0
1108 RECOVERY RM Existing Existing P-1 P-1 P-1 P-1 ACP-1
1109 MINOR OR SURGERY RM Existing Existing P-1 P-1 P-1 P-1 ACP-1
C1105 CORRIDOR Existing Existing P-1 P-1 P-1 P-1 ACP-1
02.0 NORTH PENTHOUSE
2400 NORTH PENTHOUSE
BUILDING 30
Existing Existing Existing Existing Existing Existing Existing
03.0
34E1 ELECTRICAL CLOSET Existing Existing Existing Existing Existing Existing Exposed
3400 OFFICE CUBICLE Existing Existing P-1 P-1 P-1 P-1 ACP-1
3401 SPD SUPERVISOR Existing Existing P-1 P-1 P-1 P-1 ACP-1
3403 ADMIN OFFICE Existing Existing P-1 P-1 P-1 P-1 ACP-1
3404 SYSTEM ANALYST Existing Existing P-1 P-1 P-1 P-1 ACP-1
3406 STORAGE Existing Existing P-1 P-1 P-1 P-1 ACP-1
3407 OFFICE CUBICLE Existing Existing P-1 P-1 P-1 P-1 ACP-1
3408 DIALYSIS RM Existing Existing P-1 P-1 P-1 P-1 ACP-1
C3405 CORRIDOR Existing Existing P-1 P-1 P-1 P-1 ACP-1
05.0
54E1 ELECTRICAL CLOSET Existing Existing Existing Existing Existing Existing Exposed
5400 TREATMENT BED 2 Existing Existing P-1 P-1 P-1 P-1 ACP-1
5400A CLEAN LINEN Existing Existing P-1 P-1 P-1 P-1 ACP-1
5400B DIRTY LINEN Existing Existing P-1 P-1 P-1 P-1 ACP-1
5401 TREATMENT BED 3 Existing Existing P-1 P-1 P-1 P-1 ACP-1
5402 TREATMENT BED 4 Existing Existing P-1 P-1 P-1 P-1 ACP-1
5403 TREATMENT BED 5 Existing Existing P-1 P-1 P-1 P-1 ACP-1
5404 TREATMENT BED 1 Existing Existing P-1 P-1 P-1 P-1 ACP-1
5406 RECEPTION AREA Existing Existing P-1 P-1 P-1 P-1 ACP-1
5406A TOILET Existing Existing P-1 P-1 P-1 P-1 ACP-1
5408 UNISEX TOILET Existing Existing P-1 P-1 P-1 P-1 ACP-1
5410 WAITING Existing Existing P-1 P-1 P-1 P-1 ACP-1
5411 LOUNGE Existing Existing P-1 P-1 P-1 P-1 ACP-1
5412 LOCKER Existing Existing P-1 P-1 P-1 P-1 ACP-1
5413 TEAM RM Existing Existing P-1 P-1 P-1 P-1 ACP-1
5414 EQUIPMENT STORAGE Existing Existing P-1 P-1 P-1 P-1 ACP-1
C5405 CORRIDOR Existing Existing P-1 P-1 P-1 P-1 ACP-1
Revisions: Date:
1/2" = 1'-0"A-102
1 3403 ADMIN OFFICE WEST WALL
1 1/2" = 1'-0"A-102
3 BRICK INFILL DETAIL
1 1/2" = 1'-0"A-102
2 BRICK INFILL DETAIL
B
A
4.2
MINOR OR
SURGERY RM
RECOVERY RM
CORRIDOR
C1105 8' -
0"
MATCH E
XIS
TIN
G
PATCH CEILING TO MATCH
EXISTING.
REFLECTED CEILING PLAN…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .