Attch IV - 539-25-502 Install Card Reader Drawings.pdf
PDF 895 KB Posted
- Attached to
- Z1DA--Install Card Readers 539-25-502
- Solicitation number
- 36C25025Q0476
About this file
These construction documents detail a card reader installation project for the VA Cincinnati medical facility at 3200 Vine Street. The project (Number 539-25-502) involves installing dual authentication card readers in multiple locations across two buildings, including the FT Thomas and Cincinnati sites. Key technical specifications include removing existing alarm system panels, utilizing existing junction boxes and conduits, installing electric strikes, providing new access control card reader panels, and implementing a 120V-20A dedicated emergency circuit. The project has an infection control risk assessment (ICRA) Level 2, requiring HEPA cart usage when removing ceiling tiles and dust control measures. The period of performance is 120 days from notice to proceed, with work to be coordinated to minimize hospital interruptions. Specific areas for card reader installation include rooms like the Armory (155B), Canteen Offices (B103A, B103B), with block walls being a primary construction material.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25025Q0476 0003.docx | DOCX document | |
| 36C25025Q0476 0002.docx | DOCX document | |
| 36C25025Q0476 0001.docx | DOCX document | |
| Attch V - JCI J-A Redacted.pdf | ||
| Attch VII - RFI Form.pdf | ||
| Attch VI - EMR.docx | DOCX document | |
| Attch I - Wage Determinations - Cincy.pdf | ||
| Attch II - Wage Determinations - Ft. Thomas.pdf | ||
| Attch III - 539-25-502 Specifications.pdf | ||
| Attch VIII - VHA Directive 1192.01, Seasonal Influen..pdf | ||
| 36C25025Q0476.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
G100
COVER SHEET
A
Fi le
P at h
/1 5/
1:
:0
AM
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
INSTALL CARD READERS
3200 Vine Street, Cincinnati OH
539-25-502
64 & 1 Project Director
Issue date Chkd By Drwn By
INFECTION CONTROL PROJECT INFORMATION
INFECTION CONTROL GENERAL NOTES
A. PROVIDE TEMPORARY BARRIER WALLS, BASIS OF DESIGN: STARC
SYSTEMS, FOR ACTIVITIES CAUSING DUST AND/OR DEBRIS, OR AT
EXTERIOR LOCATIONS TO PREVENT PEOPLE OR WEATHER
INTRUSION. MAINTAIN 5' CLEAR IN CORRIDORS LESS THAN 7'6" WIDE,
AND 6' CLEAR IN LARGER CORRIDORS. PROVIDE ACCESS DOORS AS
NECESSARY.
CONSTRUCTION ACTIVITY - INFECTION RISK: Level II
PATIENT RISK GROUP: LOW RISK
CLASS OF PRECAUTION MATRIX: TYPE II. ICRA TO BE COMPLETED BY VA.
G100 COVER SHEET
1 FT THOMAS PLAN
2 CINCINNATI PLAN
3 SECURITY PLAN
SHEET
NUMBER SHEET NAME
SHEET INDEX
PHASING NARRATIVE
1. POP: 120 DAYS FROM NTP
2. WORK WITH VA COR TO DETERMINE LEAST INTERRUPTION TO HOSPITAL
INSTALL CARD READERS
539-25-502
VA Cincinnati 3200 Vine Street, Cincinnati, OH
Construction Documents
Copier 153 Clos.
155A
Police
Clos.
155B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
DEMO & NEW WORK FT THOMAS
A
Fi le
P at h
/1 5/
1:
:0
AM
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
INSTALL CARD READERS
3200 Vine Street, Cincinnati OH
539-25-502
Project Director
Issue date Chkd By Drwn By
PLAN NOTES
INFECTION CONTROL PLAN NOTES
1. ICRA LEVEL 2 - PROVIDE HEPA CART IF/WHEN REMOVING CEILING TILES.
2. VACUUM DUST WHILE WORKING ON BLOCK WALLS.
1. REMOVE EXISTING WALL MOUNTED ALARM SYSTEM PANEL. JUNCTION
BOX AND CONDUIT IN WALL TO REMAIN FOR REUSE. TRACE ALARM
PANEL WIRING BACK TO ELECTRICAL PANEL. DEMO WIRING AND ABOVE
CEILING CONDUIT BACK TO PANEL. IF ALARM SYSTEM WAS ON A
DEDICATED CIRCUIT, MARK BREAKER AS SPARE.
2. PROVIDE DUAL AUTHENTICATION CARD READER UTILIZING EXISTING
BOX AND CONDUIT FROM ALARM PANEL. PROVIDE ALL CABLING, WIRING,
CONDUIT, PROGRAMMING, ETC. AS NEEDED BACK TO CONTROL PANEL 9
IN ROOM C148B.
3. CUT FRAME AND PREP FOR ELECTRIC STRIKE. INSTALL ELECTRIC
STRIKE AND PROVIDE SURFACE MOUNTED CONDUIT ON INSIDE OF 155B
FOR WIRING.
4. WALLS ARE BLOCK.
IC#
B64 - NEW WORK PLAN4
NTS
Copier 153 Clos.
155A
Police
Clos.
155B
B64 - DEMO PLAN4
NTS
155B
3 Bedroom
Copier 153 Clos.
155A
Corridor C*1*5
Corridor C*1*6
Corridor C*1*7
Police
Elevator Lobby 148A
Clos.
148B
Stair #4 S*1*4
Stor.
M. Tlt.
Shower Room 156A
4 Bedroom
Office
Tlt.
Linen Rm.
4 Bedroom
Clos.
152A
Clos.
155B
Off.
151A
Dental Suite
Elec.
B103A Clerical
B102A
Office B103
Clerical B102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
DEMO & NEW WORK CINCINNATI
A
Fi le
P at h
/1 5/
1:
:0
AM
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
INSTALL CARD READERS
3200 Vine Street, Cincinnati OH
539-25-502
Project Director
Issue date Chkd By Drwn By
PLAN NOTES
INFECTION CONTROL PLAN NOTES
1. ICRA LEVEL 2 - PROVIDE HEPA CART IF/WHEN REMOVING CEILING TILES
2. VACUUM DUST WHILE WORKING ON BLOCK WALLS.
1. REMOVE EXISTING WALL MOUNTED ALARM SYSTEM PANEL. JUNCTION
BOX AND CONDUIT IN WALL TO REMAIN FOR REUSE. TRACE ALARM
PANEL WIRING BACK TO ELECTRICAL PANEL. DEMO WIRING AND ABOVE
CEILING CONDUIT BACK TO PANEL. IF ALARM SYSTEM WAS ON A
DEDICATED CIRCUIT, MARK BREAKER AS SPARE
2. PROVIDE DUAL AUTHENTICATION CARD READER UTILIZING EXISTING
BOX AND CONDUIT FROM ALARM PANEL. PROVIDE ALL CABLING, WIRING,
CONDUIT, PROGRAMMING AS NEEDED.
3. CUT FRAME AND PREP FOR ELECTRIC STRIKE. INSTALL ELECTRIC
STRIKE AND PROVIDE SURFACE MOUNTED CONDUIT ON INSIDE OF
C103B FOR WIRING.
4. WALLS ARE BLOCK.
5. WALLS ARE DRYWALL.
6. REMOVE EXISTING WALL MOUNTED ALARM SYSTEM PANEL. TRACE AND
DEMO WIRING BACK TO PANEL. IF ON DEDICATED CIRCUIT, MARK
BREAKER AS SPARE. PROVIDE STAINLESS STEEL COVER PLATE ON
GANG BOX.
7. REMOVE EXISTING AVIGILON CAMERA. SAVE FOR REINSTALLATION.
8. RELOCATE EXISTING AVIGILON CAMERA WITH CLEAR VIEW OF SAFE
WHILE OPEN. COORDINATE WITH COR ON FINAL LOCATION.
9. PROVIDE NEW ACS CONTROL PANEL TO SUPPORT NEW CARD READER
EQUIPPED DOORS. PROVIDE CAT6A CONNECTION FOR CONTROL PANEL.
IC#
B1 - NEW WORK PLAN4
NTS
B1 - DEMO PLAN4
NTS
Elec.
B103A
Clerical B102A
Office B103
Clerical B102
2 4
2 5
B103A
B103B
KC
KC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
DOOR HARDWARE SCHEDULE &
SECURITY DETAILS
A
Fi le
P at h
/1 5/
1:
:0
AM
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
INSTALL CARD READERS
3200 Vine Street, Cincinnati OH
539-25-502
Project Director
Issue date Chkd By Drwn By
PLAN NOTES
INFECTION CONTROL PLAN NOTES
1. ICRA LEVEL 2 - PROVIDE HEPA CART IF/WHEN REMOVING CEILING TILES.
IC#
DOOR SCHEDULE - INSTALL CARD READERS
DOOR
NUMBER
ROOM
NAME
HARDWARE
SETWIDTH HEIGHT THICKNESS
COMMENTS
WIDTH HEIGHT THICKNESS
FRAMEDOOR
ETR Walls are block, believed to have lead lining.155B Armory 1ETR ETR ETR ETR ETR
ETRB103A Canteen Office 1ETR ETR ETR ETR ETR
ETRB103B 1ETR ETR ETR ETR ETRCanteen Office
D
CREDC
JJ
NOTE: THIS DIAGRAM IS SCHEMATIC IN NATURE ONLY. IT IS
REFER TO DRAWINGS AND SPECIFICATIONS FOR WORK REQUIRED.
INTENDED TO SHOW GENERAL CONFIGURATION OF THE SYSTEM.
MAIN
CONTROL
DOOR
CONTROL
PANEL
DOOR LOCK
POWER
SUPPLY
PANEL
1.
2.
3.
4.
5.
6.
120V-20A DEDICATED EMERGENCY CIRCUIT IN WALL MOUNTED JUNCTION
BOX. PROVIDE CONNECTION TO ALL SECURITY PANELS AS REQUIRED.
PROVIDE 120V DIRECT CONNECTION TO ALL SECURITY PANELS.
EXTEND DATA DROP FROM LOCAL SIGNALS CLOSET INTO NEW CONTROL
PANEL.
TYPICAL CONTROLLED DOOR DEVICES. REFER TO PLANS FOR LOCATIONS.
NEW ACCESS CONTROL CARD READER PANELS AS REQUIRED TO SUPPORT
NEW CARD READER LOCATIONS AS INDICATED ON PLANS.
PROVIDE DOOR LOCK LOW VOLTAGE REMOTE POWER SUPPLY PANEL.
COORDINATE DOOR LOCK VOLTAGE AND REQUIREMENTS WITH DOOR
HARDWARE PROVIDER.
DETAIL NOTES
5 6
1D
Walls are block.
Walls are block.
FINISH FLOOR
CEILING
NON-SECURE
SIDE
SECURE
SIDE
LATCH HINGE
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
DPDT DOOR POSITION SWITCH WITH WIRING TO SECURITY CONTROL PANELS.
PROVIDE 0.5" CONDUIT FROM DOOR FRAME TO LOCAL SECURITY WIRING JUNCTION BOX ABOVE
SECURE SIDE CEILING.
LOCAL SECURITY JUNCTION BOX ABOVE CEILING ON SECURE SIDE OF DOOR, MINIMUM 12"X12"X4" WITH
CONDUIT CONNECTIONS TO DOOR/READERS/ETC AND WIRING.
EXTEND DOOR CONTROL AND LOW VOLTAGE LOCK POWER WIRING TO DOOR CONTROL EQUIPMENT.
MECHANICAL DOOR HARDWARE PER DIVISION 01.
ELECTRIC DOOR HARDWARE PER DIVISION 01.
MORTISE BOX IN DOOR FRAME PER DIVISION 01.
PROVIDE WALL MOUNTED JUNCTION BOX AT DOOR FRAME CONNECTION POINT. COORDINATE WITH
DOOR FRAME PRIOR TO INSTALLATION.
ELECTROMAGNETIC DOOR LOCK WITH BONDING SENSOR FOR DOOR POSITION PER DIV-01.
PROVIDE 0.75" CONDUIT FROM DOOR FRAME TO LOCAL SECURITY JUNCTION BOX WITH WIRING.
REQUEST TO EXIT PIR MOTION DETECTOR ON SECURE SIDE OF DOOR FOR DOOR ALARM SHUNT.
PROVIDE WALL/CEILING MOUNT AS REQUIRED.
REQUEST TO EXIT ALARM SHUNT SWITCH INTEGRAL WITH DOOR HARDWRE.
POWER TRANSFER UNIT/ELECTRIFIED HINGE PER DIV-01. PROVIDE LOW VOLTAGE CONNECTION AND
WIRING.
ELECTRIC STRIKE UNIT PER DIV-01. PROVIDE LOW VOLTAGE CONNECTION AND WIRING.
WALL MOUNTED CREDENTIAL READER WITH BOX AND CONDUIT, 46"MH. REFER TO PLANS FOR
LOCATIONS.
DOOR ROUGH-IN DETAIL NOTES
A.
B.
THESE DETAILS ARE DIAGRAMATIC IN NATURE AND ARE INTENDED TO CONVEY THE GENERAL
REQUIREMENTS FOR A VARIETY OF DOOR APPLICATIONS. REFER TO DRAWINGS FOR SPECIFIC
DEVICES TO BE INSTALLED AT SPECIFIC DOORS.
FIELD VERIFY THE FINAL LOCATIONS OF ALL DOOR SECURITY EQUIPMENT AND CONDUIT CONNECTIONS
WITH DOOR FRAME/HARDWARE MANUFACTURERS PRIOR TO INSTALLATION.
DOOR ROUGH-IN GENERAL NOTES
EDC #
JB
7 8
15KC14
MD
File details come from the government source that posted it. Updated .