Attch IV - 539-25-502 Install Card Reader Drawings.pdf

PDF 895 KB Posted

Attached to
Z1DA--Install Card Readers 539-25-502
Solicitation number
36C25025Q0476
Issued by

About this file

These construction documents detail a card reader installation project for the VA Cincinnati medical facility at 3200 Vine Street. The project (Number 539-25-502) involves installing dual authentication card readers in multiple locations across two buildings, including the FT Thomas and Cincinnati sites. Key technical specifications include removing existing alarm system panels, utilizing existing junction boxes and conduits, installing electric strikes, providing new access control card reader panels, and implementing a 120V-20A dedicated emergency circuit. The project has an infection control risk assessment (ICRA) Level 2, requiring HEPA cart usage when removing ceiling tiles and dust control measures. The period of performance is 120 days from notice to proceed, with work to be coordinated to minimize hospital interruptions. Specific areas for card reader installation include rooms like the Armory (155B), Canteen Offices (B103A, B103B), with block walls being a primary construction material.

View the file

Other files

File Type Posted
36C25025Q0476 0003.docx DOCX document
36C25025Q0476 0002.docx DOCX document
36C25025Q0476 0001.docx DOCX document
Attch V - JCI J-A Redacted.pdf PDF
Attch VII - RFI Form.pdf PDF
Attch VI - EMR.docx DOCX document
Attch I - Wage Determinations - Cincy.pdf PDF
Attch II - Wage Determinations - Ft. Thomas.pdf PDF
Attch III - 539-25-502 Specifications.pdf PDF
Attch VIII - VHA Directive 1192.01, Seasonal Influen..pdf PDF
36C25025Q0476.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

G100

COVER SHEET

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

INSTALL CARD READERS

3200 Vine Street, Cincinnati OH

539-25-502

64 & 1 Project Director

Issue date Chkd By Drwn By

INFECTION CONTROL PROJECT INFORMATION

INFECTION CONTROL GENERAL NOTES

A. PROVIDE TEMPORARY BARRIER WALLS, BASIS OF DESIGN: STARC

SYSTEMS, FOR ACTIVITIES CAUSING DUST AND/OR DEBRIS, OR AT

EXTERIOR LOCATIONS TO PREVENT PEOPLE OR WEATHER

INTRUSION. MAINTAIN 5' CLEAR IN CORRIDORS LESS THAN 7'6" WIDE,

AND 6' CLEAR IN LARGER CORRIDORS. PROVIDE ACCESS DOORS AS

NECESSARY.

CONSTRUCTION ACTIVITY - INFECTION RISK: Level II

PATIENT RISK GROUP: LOW RISK

CLASS OF PRECAUTION MATRIX: TYPE II. ICRA TO BE COMPLETED BY VA.

G100 COVER SHEET

1 FT THOMAS PLAN

2 CINCINNATI PLAN

3 SECURITY PLAN

SHEET

NUMBER SHEET NAME

SHEET INDEX

PHASING NARRATIVE

1. POP: 120 DAYS FROM NTP

2. WORK WITH VA COR TO DETERMINE LEAST INTERRUPTION TO HOSPITAL

INSTALL CARD READERS

539-25-502

VA Cincinnati 3200 Vine Street, Cincinnati, OH

Construction Documents

Copier 153 Clos.

155A

Police

Clos.

155B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

DEMO & NEW WORK FT THOMAS

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

INSTALL CARD READERS

3200 Vine Street, Cincinnati OH

539-25-502

Project Director

Issue date Chkd By Drwn By

PLAN NOTES

INFECTION CONTROL PLAN NOTES

1. ICRA LEVEL 2 - PROVIDE HEPA CART IF/WHEN REMOVING CEILING TILES.

2. VACUUM DUST WHILE WORKING ON BLOCK WALLS.

1. REMOVE EXISTING WALL MOUNTED ALARM SYSTEM PANEL. JUNCTION

BOX AND CONDUIT IN WALL TO REMAIN FOR REUSE. TRACE ALARM

PANEL WIRING BACK TO ELECTRICAL PANEL. DEMO WIRING AND ABOVE

CEILING CONDUIT BACK TO PANEL. IF ALARM SYSTEM WAS ON A

DEDICATED CIRCUIT, MARK BREAKER AS SPARE.

2. PROVIDE DUAL AUTHENTICATION CARD READER UTILIZING EXISTING

BOX AND CONDUIT FROM ALARM PANEL. PROVIDE ALL CABLING, WIRING,

CONDUIT, PROGRAMMING, ETC. AS NEEDED BACK TO CONTROL PANEL 9

IN ROOM C148B.

3. CUT FRAME AND PREP FOR ELECTRIC STRIKE. INSTALL ELECTRIC

STRIKE AND PROVIDE SURFACE MOUNTED CONDUIT ON INSIDE OF 155B

FOR WIRING.

4. WALLS ARE BLOCK.

IC#

B64 - NEW WORK PLAN4

NTS

Copier 153 Clos.

155A

Police

Clos.

155B

B64 - DEMO PLAN4

NTS

155B

3 Bedroom

Copier 153 Clos.

155A

Corridor C*1*5

Corridor C*1*6

Corridor C*1*7

Police

Elevator Lobby 148A

Clos.

148B

Stair #4 S*1*4

Stor.

M. Tlt.

Shower Room 156A

4 Bedroom

Office

Tlt.

Linen Rm.

4 Bedroom

Clos.

152A

Clos.

155B

Off.

151A

Dental Suite

Elec.

B103A Clerical

B102A

Office B103

Clerical B102

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

DEMO & NEW WORK CINCINNATI

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

INSTALL CARD READERS

3200 Vine Street, Cincinnati OH

539-25-502

Project Director

Issue date Chkd By Drwn By

PLAN NOTES

INFECTION CONTROL PLAN NOTES

1. ICRA LEVEL 2 - PROVIDE HEPA CART IF/WHEN REMOVING CEILING TILES

2. VACUUM DUST WHILE WORKING ON BLOCK WALLS.

1. REMOVE EXISTING WALL MOUNTED ALARM SYSTEM PANEL. JUNCTION

BOX AND CONDUIT IN WALL TO REMAIN FOR REUSE. TRACE ALARM

PANEL WIRING BACK TO ELECTRICAL PANEL. DEMO WIRING AND ABOVE

CEILING CONDUIT BACK TO PANEL. IF ALARM SYSTEM WAS ON A

DEDICATED CIRCUIT, MARK BREAKER AS SPARE

2. PROVIDE DUAL AUTHENTICATION CARD READER UTILIZING EXISTING

BOX AND CONDUIT FROM ALARM PANEL. PROVIDE ALL CABLING, WIRING,

CONDUIT, PROGRAMMING AS NEEDED.

3. CUT FRAME AND PREP FOR ELECTRIC STRIKE. INSTALL ELECTRIC

STRIKE AND PROVIDE SURFACE MOUNTED CONDUIT ON INSIDE OF

C103B FOR WIRING.

4. WALLS ARE BLOCK.

5. WALLS ARE DRYWALL.

6. REMOVE EXISTING WALL MOUNTED ALARM SYSTEM PANEL. TRACE AND

DEMO WIRING BACK TO PANEL. IF ON DEDICATED CIRCUIT, MARK

BREAKER AS SPARE. PROVIDE STAINLESS STEEL COVER PLATE ON

GANG BOX.

7. REMOVE EXISTING AVIGILON CAMERA. SAVE FOR REINSTALLATION.

8. RELOCATE EXISTING AVIGILON CAMERA WITH CLEAR VIEW OF SAFE

WHILE OPEN. COORDINATE WITH COR ON FINAL LOCATION.

9. PROVIDE NEW ACS CONTROL PANEL TO SUPPORT NEW CARD READER

EQUIPPED DOORS. PROVIDE CAT6A CONNECTION FOR CONTROL PANEL.

IC#

B1 - NEW WORK PLAN4

NTS

B1 - DEMO PLAN4

NTS

Elec.

B103A

Clerical B102A

Office B103

Clerical B102

2 4

2 5

B103A

B103B

KC

KC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

DOOR HARDWARE SCHEDULE &

SECURITY DETAILS

A

Fi le

P at h

/1 5/

1:

:0

AM

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

INSTALL CARD READERS

3200 Vine Street, Cincinnati OH

539-25-502

Project Director

Issue date Chkd By Drwn By

PLAN NOTES

INFECTION CONTROL PLAN NOTES

1. ICRA LEVEL 2 - PROVIDE HEPA CART IF/WHEN REMOVING CEILING TILES.

IC#

DOOR SCHEDULE - INSTALL CARD READERS

DOOR

NUMBER

ROOM

NAME

HARDWARE

SETWIDTH HEIGHT THICKNESS

COMMENTS

WIDTH HEIGHT THICKNESS

FRAMEDOOR

ETR Walls are block, believed to have lead lining.155B Armory 1ETR ETR ETR ETR ETR

ETRB103A Canteen Office 1ETR ETR ETR ETR ETR

ETRB103B 1ETR ETR ETR ETR ETRCanteen Office

D

CREDC

JJ

NOTE: THIS DIAGRAM IS SCHEMATIC IN NATURE ONLY. IT IS

REFER TO DRAWINGS AND SPECIFICATIONS FOR WORK REQUIRED.

INTENDED TO SHOW GENERAL CONFIGURATION OF THE SYSTEM.

MAIN

CONTROL

DOOR

CONTROL

PANEL

DOOR LOCK

POWER

SUPPLY

PANEL

1.

2.

3.

4.

5.

6.

120V-20A DEDICATED EMERGENCY CIRCUIT IN WALL MOUNTED JUNCTION

BOX. PROVIDE CONNECTION TO ALL SECURITY PANELS AS REQUIRED.

PROVIDE 120V DIRECT CONNECTION TO ALL SECURITY PANELS.

EXTEND DATA DROP FROM LOCAL SIGNALS CLOSET INTO NEW CONTROL

PANEL.

TYPICAL CONTROLLED DOOR DEVICES. REFER TO PLANS FOR LOCATIONS.

NEW ACCESS CONTROL CARD READER PANELS AS REQUIRED TO SUPPORT

NEW CARD READER LOCATIONS AS INDICATED ON PLANS.

PROVIDE DOOR LOCK LOW VOLTAGE REMOTE POWER SUPPLY PANEL.

COORDINATE DOOR LOCK VOLTAGE AND REQUIREMENTS WITH DOOR

HARDWARE PROVIDER.

DETAIL NOTES

5 6

1D

Walls are block.

Walls are block.

FINISH FLOOR

CEILING

NON-SECURE

SIDE

SECURE

SIDE

LATCH HINGE

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

DPDT DOOR POSITION SWITCH WITH WIRING TO SECURITY CONTROL PANELS.

PROVIDE 0.5" CONDUIT FROM DOOR FRAME TO LOCAL SECURITY WIRING JUNCTION BOX ABOVE

SECURE SIDE CEILING.

LOCAL SECURITY JUNCTION BOX ABOVE CEILING ON SECURE SIDE OF DOOR, MINIMUM 12"X12"X4" WITH

CONDUIT CONNECTIONS TO DOOR/READERS/ETC AND WIRING.

EXTEND DOOR CONTROL AND LOW VOLTAGE LOCK POWER WIRING TO DOOR CONTROL EQUIPMENT.

MECHANICAL DOOR HARDWARE PER DIVISION 01.

ELECTRIC DOOR HARDWARE PER DIVISION 01.

MORTISE BOX IN DOOR FRAME PER DIVISION 01.

PROVIDE WALL MOUNTED JUNCTION BOX AT DOOR FRAME CONNECTION POINT. COORDINATE WITH

DOOR FRAME PRIOR TO INSTALLATION.

ELECTROMAGNETIC DOOR LOCK WITH BONDING SENSOR FOR DOOR POSITION PER DIV-01.

PROVIDE 0.75" CONDUIT FROM DOOR FRAME TO LOCAL SECURITY JUNCTION BOX WITH WIRING.

REQUEST TO EXIT PIR MOTION DETECTOR ON SECURE SIDE OF DOOR FOR DOOR ALARM SHUNT.

PROVIDE WALL/CEILING MOUNT AS REQUIRED.

REQUEST TO EXIT ALARM SHUNT SWITCH INTEGRAL WITH DOOR HARDWRE.

POWER TRANSFER UNIT/ELECTRIFIED HINGE PER DIV-01. PROVIDE LOW VOLTAGE CONNECTION AND

WIRING.

ELECTRIC STRIKE UNIT PER DIV-01. PROVIDE LOW VOLTAGE CONNECTION AND WIRING.

WALL MOUNTED CREDENTIAL READER WITH BOX AND CONDUIT, 46"MH. REFER TO PLANS FOR

LOCATIONS.

DOOR ROUGH-IN DETAIL NOTES

A.

B.

THESE DETAILS ARE DIAGRAMATIC IN NATURE AND ARE INTENDED TO CONVEY THE GENERAL

REQUIREMENTS FOR A VARIETY OF DOOR APPLICATIONS. REFER TO DRAWINGS FOR SPECIFIC

DEVICES TO BE INSTALLED AT SPECIFIC DOORS.

FIELD VERIFY THE FINAL LOCATIONS OF ALL DOOR SECURITY EQUIPMENT AND CONDUIT CONNECTIONS

WITH DOOR FRAME/HARDWARE MANUFACTURERS PRIOR TO INSTALLATION.

DOOR ROUGH-IN GENERAL NOTES

EDC #

JB

7 8

15KC14

MD