Attachment B - ODF Klamath Falls Envelope Repairs Plans (002).pdf
PDF 9 MB Posted
- Solicitation number
- S-62900-00017741
- Issued by
- Oregon
About this file
This is a Design Contract Document package and permit issue set for building envelope rehabilitation work at the Oregon Department of Forestry (ODF) Klamath Falls facility located at 3200 Delap Road, Klamath Falls, Oregon. The project encompasses comprehensive exterior envelope repairs for Building A, the main office structure originally constructed in 1939, situated on a 12.05-acre campus containing eight buildings total. The scope of work includes 100% removal and replacement of existing quarter-log, hardboard, and vinyl wall cladding with fiber cement plank lap cladding and shingle panel cladding; removal and reinstallation of existing entry swing door units; complete removal and replacement of asphalt shingle roofing including underlayment and flashings; replacement of gutters and downspouts; removal of existing chimneys with roof deck infill; and installation of new ventilation provisions. An add alternate is available for removal and replacement of existing vinyl window units. The design is prepared at 95% completion for the Construction Documents (CD) issue review set dated July 30, 2026. Work is to be performed while buildings remain occupied, and rehabilitation shall occur as one single phase with coordination required between contractor and owner for scheduling and phasing.
The project is governed by applicable 2025 Oregon codes including the Structural Specialty Code, Energy Efficiency Specialty Code, Mechanical Specialty Code, Fire Code, Electrical Specialty Code, and Plumbing Specialty Code. The Building Envelope Consultant is Forensic Building Consultants located in Clackamas, Oregon, with Chris Miller serving as Project Manager. The Authority Having Jurisdiction is Klamath County Building Division. Work must comply with all federal, state, and local laws and regulations, and the contractor assumes responsibility for all permits, licenses, inspections, and testing. Safety requirements include segregation of work areas with six-foot chain-link fencing, maintenance of means of egress, proper storage of combustible materials, and maintenance of fire protection system access. The project emphasizes verification of existing conditions on-site prior to commencement, with contractor responsibility for layout and coordination with other trades. Paint colors specified are Sherwin Williams Tony Taupe (SW 7038) for main body siding and Sherwin Williams Forestwood (SW 7730) for window and door trim.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
N
PROJECT INFORMATION:
ADDRESS:
Oregon Department of Forestry Klamath Falls 3200 Delap Rd., Klamath Falls , OR 97601
LEGAL DESCRIPTION:
State of Oregon & Department of State Lands Township 39 Range 9 Section 7 - POR S2SE4NE4, Taxlot 01000, Acres 12.05
PROJECT SUMMARY:
This Design Contract Document package is for Permit Issue purposes and are for project construction. Refer to sheets A0.00, A1.00 Architectural Site Plan, and to the Project Manual Summary of Work section for full project scope, basis of design, and description.
Aerial View - Looking Northeast
07.30.2026 - 95% CD ISSUE REVIEW SET
Oregon Department of Forestry - Klamath Falls
Building Envelope Rehabilitation
PROJECT
LOCATION
EXISTING USE AND OCCUPANCY:
1. Zoning: RL (Residential Low-Density)
2. Zoning Overlay: n/a
3. Occupancy Groups: B, S, U
4. Construction Type: Type VB
5. County: Klamath
6. Property ID: 768609
7. Map & Tax Lot ID: 3909-00700-01000 (Included for Coordination)
8. Property Accounts: R-29187, R-29766, R-29775, R-885026
(Included for Coordination)
SITE AREAS AND BUILDING HEIGHTS:
7. Project Site Area: 12.05 AC. (524,898 SF) (Unchanged)
8. Number of Buildings: 8 (Unchanged)
9. Total Site Building Area: ± 20,950 SF (Unchanged) 10.Number of Stories: Varies (Existing) (Unchanged) 11.Existing Building Heights: (Existing) (Unchanged)
APPLICABLE PROJECT CODES:
1. BUILDING CODES IN EFFECT AT TIME OF REHABILITATION PROJECT:
· 2025 Oregon Structural Specialty Code (O.S.S.C.) Amendments (B.O. 2024 International Building Code)
· 2024 Oregon Energy Efficiency Specialty Code (OEESC)
· 2052 Oregon Mechanical Specialty Code (B.O. 2024 IMC & International Fuel Gas Code)
· 2023 Portland Fire Code and the 2022 Oregon Fire Code
· 2023 Oregon Electrical Specialty Code (B.O. 2020 NFPA 70 - National Electrical Code)
· 2023 Oregon Plumbing Specialty Code (B.O. 2021 Uniform Plumbing Code)
REHABILITATION:
1. IT IS THE OWNER'S INTENT TO PERFORM THE REHABILITATION
WITHIN THE LIMITS OF THE WORK AREA WHILE THE BUILDINGS ARE
OCCUPIED.
2. IT IS THE OWNER'S INTENT TO PERFORM A FULL REHABILITATION
OF ALL EXTERIOR WALL AREAS ALONG EACH IN SCOPE BUILDING
ELEVATION AS ONE SINGLE PHASE OF WORK. CONTRACTOR SHALL
COORDINATE WITH THE OWNER FOR SCHEDULE, PHASING, AND
WORK WITHIN OCCUPIED BUILDINGS.
3. BUILDING REHABILITATION MAY NOT OCCUR IN NUMERICAL ORDER
AS RELATED TO SITE, BUILDING IDENTIFIER OR BUILDING
ADDRESSES.
4. REFER TO THE SITE PLAN AND PROJECT MANUAL FOR IN SCOPE
BUILDINGS, PROJECT NOTES, ASSUMED LIMITS OF WORK, AND
FULL SUMMARY OF WORK.
PAINT COLORS AND LOCATIONS:
1. MAIN BODY SIDING: B.O.D COLOR SHERWIN WILLIAMS TONY TAUPE
(SW 7038)
2. WINDOW AND DOOR TRIM: B.O.D. COLOR SHERWIN WILLIAMS
FORESTWOOD (SW 7730)
REGARDING OWNER REQUESTED ADD ALTERNATE:
NOTE, IT WILL NOT BE POSSIBLE TO FLASH THE EXISTING
WINDOWS IN PLACE DUE TO THE CHARACTERISTIC NATURE OF
RETROFIT STYLE WINDOW UNITS. THIS CONDITION WILL RESULT IN
AN INCOMPLETE AND DISCONTINUOUS AIR-BARRIER. IF EXISTING
WINDOWS ARE TO REMAIN IN PLACE, THE INSTALLATION OF
ADJACENT TRIM, WRB, AND SAM SHALL BE CONSIDERED
SACRIFICIAL COMPONENTS UNTIL THE TIME OF WINDOW UNIT
REPLACEMENT. WHEN WINDOW REPLACEMENT IS DEEMED
NECESSARY, SOME EXTERIOR SIDING COMPONENTS, BEYOND THE
ROUGH OPENING AND TRIM, WILL ALSO REQUIRE REMOVAL AND
REPLACEMENT AS REQUIRED TO ADDRESS WINDOW FRAMING AND
INTEGRATION OF AIR BARRIER COMPONENTS.
PROJECT CODE ANALYSIS: PROJECT DESCRIPTION:
1. THE OREGON DEPARTMENT OF FORESTRY: KLAMATH FALLS CAMPUS IN
KLAMATH FALLS OREGON IS A COMPOUND OF SIX (6) FACILITY OPERATIONS
BUILDINGS. BUILDINGS WITHIN THE COMPOUND HAVE VARIED YEARS OF
DEVELOPMENT WITH LIMITED DOCUMENTATION RELATING TO ORIGINAL
DESIGN AND CONSTRUCTION. HOWEVER, INITIAL CONSTRUCTION OF THE
MAIN OFFICE BUILDING IS BELIEVED TO HAVE OCCURRED IN 1939 WITH
ADDITIONAL SITE BUILDINGS CONSTRUCTED IN 1950, 1970, AND 1978.
BUILDING ENCLOSURE WORK FOR THIS PROJECT IS SPECIFICALLY
DESIGNATED FOR THE BUILDING 'A' MAIN OFFICE.
2. BUILDING A: ELEVATIONS ARE SIMILAR IN ASSEMBLY CONFIGURATIONS, AND
ARE PREDOMINANTLY VARIED BY ENTRY LOCATIONS AND ROOF STYLE.
EXISTING BUILDING ENCLOSURE COMPONENTS ARE A COMBINATION OF
QUARTER-LOG SIDING ALONG MAIN ELEVATION WALLS, HARDBOARD
"MASONITE" COMPOSITE LAP SIDING AT GABLE END WALLS, AND VINYL LAP
PROFILE SIDING AT ROOF DORMER LOCATIONS. EXISTING TRIM CONSISTS OF
WOOD CORNER, FENESTRATION, AND TRANSITION MEMBERS WITH VINYL
CORNER TRIM AT OUTSIED DORMER WALL CORNERS. EXISTING WINDOWS
CONSIST OF FLANGLESS RETROFIT VINYL FRAMED UNITS INSTALLED INTO
EXISTING ORIGINAL WOOD FRAMES AND/OR BUCKS. EXISTING ROOF AREAS
ARE PITCHED ROOF AND GABLE CONFIGURATIONS WITH OVERHANGS AND
ARE CLAD IN COMPOSITION ASPHALT SHINGLE ROOFING.
2.1. THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL CONSIST
OF 100% REMOVAL, DISPOSAL, AND REPLACEMENT OF EXISTING SIDING
AND TRIM ALONG EACH BUILDING ELEVATION AND INCLUDE CONCEALED
BUILDING PAPER AND FLASHINGS. 100% REMOVAL AND REINSTALLATION
OF EXISTING ENTRY SWING DOOR UNITS. (ADD ALT. FOR) 100%
REMOVAL, DISPOSAL, AND REPLACEMENT OF EXISTING WINDOW UNITS.
100% REMOVAL AND REPLACEMENT OF EXISTING ROOFING, INCLUDING
UNDERLAYMENT AND FLASHINGS. ROOF WORK SHALL ALSO INCLUDE
INSTALLATION OF NEW STEP AND APRON FLASHING AT DORMER WALLS,
REMOVAL AND DISPOSAL OF EXISTING CHIMNEYS AND INSTALLATION OF
INFILL SHEATHING INFILL AT CHIMNEY LOCATIONS (TYP. OF 2),
INSTALLATION OF RETROFIT INTAKE VENTS ALONG EAVES AT TOP ROOF
DECK LOCATIONS, AND INSTALLATION OF ADDITIONAL EXHAUST VENTS
AT RIDGE LOCATIONS. ROOF WORK SHALL ALSO INCLUDE 100%
REPLACEMENT OF EXISTING GUTTERS AND DOWNSPOUTS.
GENERAL NOTES: GENERAL NOTES, CONT.:
1. READ DESIGN DOCUMENTS (DRAWINGS) IN CONJUNCTION WITH THE
PROJECT MANUAL (PRODUCT SPECIFICATIONS).
2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON SITE.
3. DRAWINGS OF ELEVATIONS AND SITE PLANS OF THE PROJECT ARE
REPRODUCED FROM BASE DRAWINGS PREPARED BY ORIGINAL
ARCHITECT. BRING DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND
ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE
BUILDING ENVELOPE CONSULTANT AND REQUEST A REVIEW.
4. EXECUTION OF THE CONTRACT BY THE CONTRACTOR IS A
REPRESENTATION THAT THE CONTRACTOR HAS VISITED THE SITE,
BECOME GENERALLY FAMILIAR WITH THE LOCAL CONDITIONS UNDER
WHICH THE WORK IS TO BE PERFORMED AND CORRELATED PERSONAL
OBSERVATIONS WITH REQUIREMENTS OF THE CONTRACT DOCUMENTS.
5. ALL WORK TO BE PERFORMED UNDER THIS SCOPE OF REPAIRS (WORK)
SHALL BE CONDUCTED IN FULL COMPLIANCE WITH ALL APPLICABLE
LOCAL, STATE, AND FEDERAL LAWS AND REGULATIONS. IT IS THE
CONTRACTOR'S DUTY TO BE FAMILIAR WITH ALL SUCH APPLICABLE
LOCAL, STATE, AND FEDERAL LAWS AND REGULATIONS. FURTHERMORE,
THE CONTRACTOR SHALL ENSURE THAT ALL ACTIVITIES PERFORMED BY
THE CONTRACTOR'S PERSONAL EMPLOYEES, SUBCONTRACTORS, AND
SUPPLIERS COMPLY WITH THESE LAWS AND REGULATIONS DURING THE
CONSTRUCTION PROCESS.
6. CONTRACT DRAWINGS ARE COMPLIMENTARY, AND WHAT IS REQUIRED
BY ANY ONE SHALL BE BINDING AS IF REQUIRED BY ALL. BEFORE
STARTING EACH PORTION OF THE WORK, CAREFULLY STUDY AND
COMPARE THE VARIOUS DRAWINGS AND OTHER CONTRACT DOCUMENTS
RELATIVE T0 THAT PORTION OF THE WORK, AS WELL AS INFORMATION
FURNISHED BY OWNER. TAKE FIELD MEASUREMENTS OF ANY EXISTING
CONDITIONS RELATED TO THAT PORTION OF THE WORK AND OBSERVE
CONDITIONS AT THE SITE AFFECTING IT. THESE OBLIGATIONS ARE FOR
THE PURPOSE OF FACILITATING CONSTRUCTION BY THE CONTRACTOR
AND NOT FOR THE PURPOSE OF DISCOVERING ERRORS, OMISSIONS, OR
INCONSISTENCIES IN THE CONTRACT DOCUMENTS; HOWEVER, REPORT
ERRORS, OMISSIONS, OR INCONSISTENCIES DISCOVERED BY THE
CONTRACTOR PROMPTLY TO THE CONSULTANT AS A REQUEST FOR
INTERPRETATION IN THE FORM PROVIDED IN THE PROJECT MANUAL.
7. REPORT DISCREPANCIES IN CONTRACT DOCUMENTS TO FORENSIC FOR
CLARIFICATION PRIOR TO COMMENCING WORK.
8. IMMEDIATELY NOTIFY BUILDING ENVELOPE CONSULTANT UPON
DISCOVERY OF ADDITIONAL UNFORESEEN DAMAGE TO EXISTING
CONSTRUCTION SCHEDULED TO REMAIN AND THAT IS OUTSIDE THE
CONTRACT. REQUEST A REVIEW. DO NOT COMMENCE RELATED WORK
TO NEARBY WORK WITHOUT CONSULTANT APPROVAL.
9. TRADE CONTRACTORS ARE RESPONSIBLE FOR THE LAYOUT OF THEIR
OWN WORK, AND TO SEE THAT ITS WORK COMES TOGETHER WITH THAT
OF OTHERS. REPORT DISCREPANCIES ON DRAWINGS TO BUILDING
ENVELOPE CONSULTANT FOR DECISIONS.
10. TRADE CONTRACTORS MUST ASSURE THEMSELVES THAT THEY HAVE
THE LATEST DRAWINGS ISSUED FOR CONSTRUCTION, SPECIFICATIONS,
MANUFACTURERS' INSTALLATION INSTRUCTIONS AND REFERENCE
STANDARDS IN THE CONTRACTOR'S OFFICE.
11. DURING REMEDIATION WORK, THE CONTRACTOR IS TO VERIFY AND
MAINTAIN RATED WALL ASSEMBLIES AT ALL EXISTING WALL LOCATIONS.
OVERSIGHT IS REQUIRED BY A LICENSED STRUCTURAL ENGINEER TO
PROVIDE FRAMING AND SHEATHING CONDITIONS ASSESSMENT
INCLUDING RATED WALLS WHERE REPAIR WORK IS IDENTIFIED DURING
ACTUAL WORK ON THE PROJECT. THE CONTRACTOR IS TO PROVIDE
AREA SPECIFIC ENGINEERED DRAWINGS SHOWING EXTENT, DETAILS,
AND CALCULATIONS TO THE AUTHORITY HAVING JURISDICTION FOR
REVIEW AND APPROVAL PRIOR TO REMEDIATION WORK.
CONCEALED BARRIER INSTALLATION:
1. CLEAN AND PREPARE SURFACES PRIOR TO INSTALLATION OF ALL
MEMBRANES IN ACCORDANCE TO PRODUCT MANUFACTURERS'
RECOMMENDATIONS AND AS DIRECTED BY BUILDING ENCLOSURE
CONSULTANT.
2. CONTRACTOR TO PROVIDE ISOMETRIC FLEXIBLE SADDLE
FLASHINGS AT MULTI-PLANE WALL, WALL OPENING, ROOF
TRANSITION, AND DECK TRANSITION AREAS AS OCCURS AND AS
DETAILED PER DESIGN DOCUMENTS.
MEMBRANE INSTALLATION:
1. SEAL WEATHER-RESISTIVE BARRIER AT ALL LAPS AND
TERMINATIONS TO CREATE AIR BARRIER. NOT ALL SEALANT
LOCATIONS ARE ILLUSTRATED.
2. PROVIDE FURRING STRIPS/RAIN SCREEN BEHIND ALL EXTERIOR
CLADDING AND TRIM IN ACCORDANCE WITH THE DRAWINGS,
SPECIFICATIONS, AND MANUFACTURER'S WRITTEN
INSTRUCTIONS.
METAL FLASHING:
1. PROVIDE AND INSTALL METAL HEAD FLASHING WITH FOLDED,
UPTURNED END DAMS OVER WINDOW, DOOR, AND SLIDING
GLASS DOORS TRIM. CONTRACTOR TO FIELD VERIFY THAT METAL
HEAD FLASHING DOES NOT INTERFERE WITH OPERATION OF THE
FENESTRATION.
2. FORM 100% OF THROUGH-WALL AND HEAD FLASHINGS WITH A
SLOPED HORIZONTAL SURFACE CONFORMING TO THE
FOLLOWING CRITERIA:
· ENSURE A 5% SLOPE AT GREATER THAN OR EQUAL TO A
1-1/2" WIDE HORIZONTAL SURFACE
· ENSURE A 10% SLOPE AT LESS THAN A 1-1/2" WIDE
HORIZONTAL SURFACE
3. CONTRACTOR TO PROVIDE 3-DIMENSIONAL METAL SADDLE
FLASHINGS AT MULTI-PLANE SUBSTRATE INTERSECTIONS, ROOF
TRANSITIONS, WALLS TRANSITIONS, DECK TRANSITIONS, AND AT
OTHER SIMILAR LOCATIONS AS OCCURS AND AS DETAILED PER
DESIGN DOCUMENTS.
EXTERIOR OPENINGS AND PENETRATIONS:
1. ALL SCHEDULES AND QUANTITIES OF WINDOWS, DOORS, VENT
PENETRATIONS, AND EXTERIOR FIXTURES, SUCH AS LIGHT
FIXTURES, CONVENIENCE RECEPTACLES, EXHAUST VENTS, PIPE
PENETRATIONS, HOSE BIBBS, ELECTRICAL OR METERS, ETC.,
THAT HAVE BEEN PROVIDED IN THE DOCUMENTS ARE
APPROXIMATE AND MUST BE VERIFIED BY THE CONTRACTOR ON
SITE. CONTRACTOR SHALL PERFORM OWN QUANTITY SURVEY
AND VERIFIED QUANTITIES OF ALL ITEMS INDICATED IN THE
DRAWINGS.
2. SEAL EXTERIOR WALL PENETRATIONS FOR AIR BARRIER
CONTINUITY WITH SCHEDULED MINIMALLY EXPANDING FOAM
INSULATION.
3. FORM EXTERIOR PERIMETER DYNAMIC SEALANT JOINTS, 1/2"
WIDE TYPICAL, WITH CONTINUOUS CLOSED CELL BACKER ROD
U.O.N., ENSURE BACKER ROD DIAMETER EXCEEDS JOINT WIDTH
BY 25% AND MAINTAIN A JOINT WIDTH-TO-DEPTH RATIO OF 2:1.
GENERAL NOTES, CONT.:
DRAWING TERMS:
1. DEMOLISH: (DEMO) TO COMPLETELY REMOVE AND LEGALLY
DISPOSE OF OFF-SITE IN A MANNER COMPLIANT WITH FEDERAL,
STATE, AND LOCAL PROTOCOLS.
2. SCHEDULED (ITEM): COMPONENTS CALLED OUT AS SCHEDULED
SHALL REMAIN IN PLACE, BE REMOVED AND REINSTALLED, BE
REMOVED AND REPLACED, BE INSTALLED AS A NEW
COMPONENT, OR REPLACED IF DAMAGED IS DISCOVERED.
REFER TO PROJECT MANUAL FOR CONDITION, ASSEMBLIES, AND
RELATED MATERIALS.
3. PROTECT (ITEM): A TERM USED ON DRAWINGS TO INDICATE AN
ITEM REQUIRES PROTECTION FROM THE WORK.
4. REMOVE (ITEM): A TERM USED ON DRAWINGS TO INDICATE A
SPECIFIC ITEM TO BE DETACHED FROM EXISTING CONSTRUCTION
AND LEGALLY DISPOSED OF OFF-SITE, UNLESS INDICATED
OTHERWISE TO BE REMOVED, SALVAGED, AND REINSTALLED.
5. REMOVE AND REINSTALL (ITEM): A TERM USED ON DRAWINGS TO
INDICATE A SPECIFIC ITEM TO BE DETACHED FROM EXISTING
CONSTRUCTION, PREPARED FOR REUSE, AND REINSTALLED
BACK IN ITS EXISTING LOCATION.
6. RELOCATE (ITEM): A TERM USED IN DRAWINGS TO INDICATE AN
EXISTING ITEM THAT HAS BEEN REMOVED, AND TO BE
REINSTALLED IN A NEW LOCATION
7. SALVAGE (ITEM): CAREFULLY DETACH FROM EXISTING
CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE READY FOR
REUSE. INCLUDE FASTENERS OR BRACKETS NEEDED FOR
REATTACHMENT IN ORIGINAL LOCATION OR ELSEWHERE.
8. EXISTING TO REMAIN (ITEM): A TERM USED ON DRAWINGS TO
INDICATE EXISTING ITEMS OF CONSTRUCTION THAT ARE NOT BE
REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE
REMOVED, SALVAGED, OR REMOVED AND REINSTALLED.
EXISTING TO REMAIN IS INDICATED BY GRAPHIC LINETYPE
SYMBOL.
9. PHASE: A PORTION OF THE WORK TO BE COMPLETED DURING A
SET PERIOD OF TIME, AS DEFINED IN THE PROJECT
SPECIFICATIONS.
10. REFER TO SPECIFICATIONS SUMMARY OF WORK, GENERAL
DESCRIPTION OF WORK, FOR SCOPE OF REPAIR ASSEMBLIES.
ALUM. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
BLDG. BUILDING
BOT BOTTOM
COL. COLUMN
CONC. CONCRETE
CONT. CONTINUOUS
CONST. CONSTRUCTION
C/W COMPLETE WITH
DIA. DIAMETER
DEFS DIRECT-APPLIED
FINISH SYSTEM
DIM. DIMENSION
DWG DRAWING
DS DOWNSPOUT
E. EAST
EA. EACH
ELEV. ELEVATION
ELEC. ELECTRICAL
EIFS EXTERIOR INSULATION &
FINISH SYSTEM
EQ. EQUAL
EQUIP. EQUIPMENT
EXIST. EXISTING
EXT. EXTERIOR
FC FIBER CEMENT
FIN. FINISH
ABBREVIATIONS:
F.O.S. FACE OF STUD
FLR. FLOOR
FRTW FIRE-RETARDANT
TREATED WOOD
FURR FURRING OR FURRED
GA GAUGE
GALV. GALVANIZED
GWB GYPSUM WALL BOARD
GYP. GYPSUM
HORIZ. HORIZONTAL
INT. INTERIOR
INSUL. INSULATION
MAX MAXIMUM
MEMB. MEMBRANE
MTL METAL
MIN. MINIMUM
MISC. MISCELLANEOUS
N. NORTH
N.I.C. NOT IN CONTRACT
(NOT IN SCOPE)
NTS NOT TO SCALE
O.C. ON CENTER
PLY PLYWOOD
P.T. PRESSURE TREATED (POST-TENSIONED
WHEN USED WITH CONCRETE)
R RADIUS
REF. REFERENCE
REINF REINFORCED
REQ'D REQUIRED
RD ROOF DRAIN
S. SOUTH
SAM SELF ADHESIVE
MEMBRANE (FLASHING)
SECT. SECTION
SIM. SIMILAR
SPEC SPECIFICATION
S.S. STAINLESS STEEL
STRUCT. STRUCTURAL
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TEMP TEMPERATURE
T.O.W. TOP OF WALL
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
VERT. VERTICAL
V.I.F. VERIFY IN FIELD
W. WEST
W/ WITH
W/O WITHOUT
WRB WEATHER-RESISTIVE
BARRIER
GYPSUM SHEATHING / GYPSUM WALLBOARD
BATT INSULATION
DETAIL HATCH PATTERN LEGEND:
TYPICAL LINE WEIGHT OF 'NEW' BUILDING ENVELOPE
COMPONENTS - WALLS, WINDOWS, DOORS, ETC.
SAM - SELF APPLIED MEMBRANE FLEXIBLE FLASHING,
OR MANUFACTURED FLASHING PANELS AS NOTED
WRB - WEATHER RESISTIVE BARRIER
MISC. COMPONENTS - DRAINAGE MAT, REINFORCING
MESH, BUG SCREEN, FASTENERS, SCREWS, NAILS
EXISTING ROOF UNDERLAYMENT, OTHER EXISTING
COMPONENTS
METAL FLASHING
SEALANT / ADHESIVE LAYER
LINETYPE LEGEND:
FIBER CEMENT CLADDING / CEMENT
BOARD / TILE ADHESIVE
CONCRETE
DECK COATING REINFORCEMENT MESH
DRAINAGE MAT
ACRYLIC REINFORCED CEMENTITIOUS DECK
COATING SYSTEM
POLYURETHANE DECK COATING / CONCRETE
DAMP-PROOFING
RIGID INSULATION / FOAM
STEEL / METAL
SCHEDULED WRB
SCHEDULED SAM
METAL FLASHING, COPING, AND SADDLES
APPLIED DECK COATING SYSTEM
SCHEDULED SEALANT
ISOMETRIC DETAIL HATCH PATTERN LEGEND:
TYPICAL LINE WEIGHT OF EXISTING BUILDING
ENVELOPE COMPONENTS
DYNAMIC SEALANT JOINT: SEALANT APPLIED OVER
CLOSED CELL BACKER ROD (2:1 RATIO)
CONTINUOUS SEALANT BEAD
PLYWOOD SHEATHING
PROJECT TEAM:
Main Building Side Elevation - Looking East
OCCUPANCY DURING CONSTRICTION SAFETY CRITERIA:
1. SEGREGATE EXTERIOR BUILDING AREA AROUND LIMITS OF WORK
FROM PUBLIC ACCESS WITH A 6'-0" HIGH CHAIN-LINK FENCE
INCLUDING SIGNAGE INDICATING "PROHIBITED AREA ACCESS".
2. REQUIRED MEANS OF EGRESS AND REQUIRED ACCESSIBLE
MEANS OF EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
THE COURSE OF THE PROPOSED PROJECT WORK.
3. COMBUSTIBLE AND OTHER MATERIALS ASSOCIATED WITH THE
PROPOSED SCOPE OF WORK SHALL NOT BE STORED IN EXITS,
ENCLOSURES FOR STAIRWAYS, OR EXIT ACCESS CORRIDORS.
4. ACCESS TO FIRE EXTINGUISHERS OR TO ON-SITE FIRE
PROTECTION SYSTEMS SHALL BE MAINTAINED AT ALL TIMES
DURING THE COURSE OF THE PROPOSED PROJECT WORK.
5. CONTRACTOR SHALL PROVIDE A SAFETY PLAN (UPDATED AT
LEAST ONCE PER MONTH), AND POSTED IN A CONSPICUOUS
LOCATION ALONG WITH OTHER PROJECT ESSENTIAL COMMUNITY
INFORMATION.
PROJECT PARAMETERS:
1. UNLESS ACCOMPANIED BY DOCUMENTATION STAMPED BY A
LICENSED PROFESSIONAL, THE WORK DESCRIBED WITHIN THESE
CONTRACT DOCUMENTS SHALL NOT INCLUDE THE FOLLOWING
CRITERIA (REFER TO ORS 671.030d):
· THE STRUCTURAL PART OF THE BUILDING, INCLUDING BUT
NOT LIMITED TO THE FOUNDATION WALLS, FLOORS, ROOF,
FOOTINGS, BEARING PARTITIONS, BEAMS, COLUMNS AND
JOISTS, IS NOT INVOLVED;
· THE BUILDING CODE CLASSIFICATION BY USE OR
OCCUPANCY OF THE BUILDING IS NOT CHANGED; AND
· THE BUILDING CODE CLASSIFICATION BY TYPE OF
CONSTRUCTION OF THE BUILDING IS NOT CHANGED.
2. NON-STRUCTURAL WORK DESCRIBED WITHIN THESE CONTRACT
DOCUMENTS SHALL FALL UNDER EXCEPTIONS: 2 OF OSSC
107.1IN THAT PLANS, SPECIFICATIONS, CALCULATIONS, DIAGRAMS
AND OTHER DATA PREPARED AND DESIGNED BY AN ENGINEER
OR ARCHITECT LICENSED BY THE STATE TO PRACTICE AS SUCH
ARE NOT REQUIRED FOR THE FOLLOWING WORK:
· 2.3 ALTERATIONS OR REPAIRS THAT DO NOT INVOLVE THE
STRUCTURAL PARTS OF THE BUILDING.
3. IT IS RECOGNIZED THAT THERE MAY BE SEPARATE TRADE
PERMITS RELATED TO PLUMBING OR UTILITY EXTENSIONS
AND/OR MINOR RECONFIGURATIONS OF EXTERIOR VENTILATION
AND ELECTRICAL PENETRATIONS RELATED TO THIS
REHABILITATION PROJECT. IT IS UNLIKELY THAT MECHANICAL
AND/OR FIRE LIFE SAFETY SYSTEMS INCLUDING ALARMS OR FIRE
SPRINKLER SYSTEMS WILL BE AFFECTED.
CLIENT:
Oregon Department of Forestry 2600 State Street, Building F Salem, OR 97310 Contact: Amelia Stirewalt, Construction Manager Phone: 971.375.5595 email: amelia.s.stirewalt@odf.oregon.gov
BUILDING ENVELOPE CONSULTANT:
Forensic Building Consultants 12901 SE 97th Ave., Suite 310 Clackamas, OR 97015 Phone: 503.772.1114 Contact: Chris Miller, Project Manager email: cmiller@forensicbuilding.com
Michael Green, Technical Design Manager email: michaelg@forensicbuilding.com
AUTHORITY HAVING JURISDICTION:
Klamath County Building Division 305 Main Street, Klamath Falls, OR 97601 Phone: 541.883.5121 Inspections: Oregon ePermitting website askbuildingdepartment@klamathcounty.org www.klamathcounty.org/174/Building-Division
Main Building Side Elevation - Looking West Main Building Front Elevation - Looking South
CONTRACTOR:
3200 DeLap Rd., Klamath Falls, OR 97601
Main Building Rear Elevation - Looking North
PROJECT DESIGN / ASSEMBLY GROUPS:
A0.00 COVER SHEET, GENERAL NOTES, ABBREVIATIONS &
SYMBOLS, CODE REVIEW, AND PROJECT DESCRIPTION
A0.10 SHEET SEQUENCE AND DETAIL INDEX
A1.00 SITE PLAN
A2.00 BUILDING ELEVATIONS PHOTO REFERENCES
A3.00 WALL AND ROOF DETAILS
A4.00 WALL OPENING DETAILS
PROJECT BASIS OF DESIGN
1. PROJECT BASE BID SCOPE OF REPAIR WORK COMPONENTS TO INCLUDE
THE FOLLOWING AREAS OF WORK:
· REMOVE AND DISPOSE OF QUARTER-LOG, HARDBOARD, AND
VINYL WALL CLADDING COMPONENTS
· *ADD ALTERNATE TO REMOVE AND DISPOSE OF VINYL WINDOW
ASSEMBLIES
· REMOVE AND STORE SWING DOOR ASSEMBLIES
· REMOVE AND DISPOSE OF ASPHALT SHINGLE ROOFING
· REMOVE AND DISPOSE OF GUTTERS AND DOWNSPOUTS
· REMOVE AND STORE ANTENNA, ACCESS LADDER, HVAC, AND
METROLOGICAL HARDWARE
2. SCHEDULED PROJECT COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO:
· WOOD FRAMING AND FURRING MEMBERS
· BATT, FOAM, AND CELLULOSE INSULATION (MATCH EXISTING)
· PLYWOOD WALLBOARD SHEATHING
· CODE COMPLIANT WEATHER-RESISTIVE BARRIER (WRB)
AND FLEXIBLE SAM FLASHING
· FIBER CEMENT SHINGLE PANEL CLADDING (AT UPPER GABLE END
WALLS) , PLANK LAP CLADDING (AT MAIN BUILDING WALLS), TRIM
MEMBERS, AND MOUNTING BLOCKS
· *ADD ALTERNATE TO INSTALL REPLACEMENT FLANGED VINYL
WINDOW UNITS
· ALUMINUM K-6 STYLE GUTTERS AND ROUND DOWNSPOUTS
· METAL TRANSITION FLASHING, DIVERTER FLASHING, AND
THREE-DIMENSIONAL METAL SADDLE FLASHINGS
· ROOF/ATTIC VENTILATION PROVISIONS
· COMPOSITION ASPHALT SHINGLE ROOFING AND UNDERLAYMENT
· SCHEDULED SEALANTS
· EXTERIOR PAINTING, REFER TO PAINT COLORS AND LOCATIONS
A0.00
COVER SHEET
CODE ANALYSIS
PROJECT DESCRIPTION
07.30.2026
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2026 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 26-043
95% CD Issue Review Set
O re go n
D ep ar tm en t o f F or es try
K la m at h Fa lls
B ui ld ib g E nc lo su re
R eh ab ili ta tio n (P
O -6
-0
7) O re go n De pa rtm en t o f F or es try
S ta te S tre et
, B ui ld in g F, S al em , O
R
D eL ap R d.
, K la m at h
Fa lls
, O R
1 SITE PLAN
1" = 60'-0" Oregon Department of Forestry - Klamath Falls mhg
SITE AREAS AND INFORMATION:
1. Total Site Area: 12.05 AC. (524,989 SF)
2. County: Klamath
3. Zoning: RL (Residential Low-Density)
6. Property ID: 768609 (Included for Coordination)
7. Tax Lot: 3909-00700-01000 (Included for Coordination)
SITE KEY NOTES:
EXISTING GRAVEL DRIVE/APRON/PARKING AREA: NOT IN PROJECT SCOPE
EXISTING CONCRETE PROPERTY ACCESS/DRIVES, ASPHALT PAVING, APRONS, WALKWAYS, AND FLATWORK AREAS: NOT IN
PROJECT SCOPE.
ALTERATION OF EXISTING UNIMPROVED/LANDSCAPED AREAS, VEGETATION, AND SITE TREES ARE NOT WITHIN THE SCOPE
OF THE PROPOSED REHABILITATION PROJECT.
THE PROPOSED BUILDING ENCLOSURE REHABILITATION SHALL BE CONSIDERED 'LIKE FOR LIKE' IN GENERAL APPEARANCE AND INCLUDE WORK TO CLADDING, ROOFING, AND FENESTRATIONS AS DESIGNATED ON SHEET A0.00.
APPROXIMATE LOCATION(S) OF EXISTING SEPTIC PROVISION, INCLUDING (3) TANKS AND (2) SEPTIC DRAIN FIELDS SHALL BE
PROTECTED FROM CONSTRUCTION ACTIVITIES THROUGHOUT THE DURATION OF PROPOSED WORK.
SITE LEGEND:
APPROXIMATE LOCATIONS OF EXISTING 'MAJOR' SITE TREES (FOR REFERENCE ONLY).
LIMITS OF PROPOSED WORK, REFER TO SHEET A0.00 AND PROJECT MANUAL SUMMARY OF
WORK FOR PROJECT DESCRIPTION AND SCOPE.
ASSUMED AND APPROXIMATE LOCATION OF EXISTING SEPTIC LEACH FIELD AND SUPPORT
INFRASTRUCTURE (NOT IN SCOPE) .
BUILDING LEGEND:
EXISTING OFFICE BUILDING - PROJECT BASE SCOPE
EXISTING SHOP BUILDING - NOT IN SCOPE
EXISTING STORAGE BUILDING - NOT IN SCOPE
EXISTING CREW QUARTERS BUILDING - NOT IN SCOPE
EXISTING AVIATION OFFICES BUILDING - NOT IN SCOPE
EXISTING STATE LANDS OFFICES BUILDING - NOT IN SCOPE
A
B
C
D
E
F
N
GENERAL SITE NOTES:
1. CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS TO BETTER UNDERSTAND THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS, ELEVATIONS AND CONDITIONS PRIOR TO BEGINNING ANY
WORK AND NOTIFY FORENSIC OF ANY DISCREPANCIES. DO NOT SCALE DRAWINGS.
2. SITE PLAN ARE CREATED USING INFORMATION REPRODUCED FROM BASE DRAWINGS ACQUIRED FROM PUBLIC RECORD, AND/OR PREPARED BY ORIGINAL/PREVIOUS ARCHITECT, DESIGNER, AND/OR CONSULTANT. BRING ANY DISCREPANCIES BETWEEN DESIGN DOCUMENTS AND ACTUAL PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE BUILDING ENCLOSURE CONSULTANT AND
REQUEST A REVIEW.
3. BUILDINGS OR AREAS DESIGNATED AS NOT IN CONTRACT (N.I.C.) ARE OUTSIDE OF THE LIMITS AND SCOPE OF THE PROPOSED WORK.
N.I.C. BUILDINGS MAY BE ANCILLARY OR NOT BE DIRECTLY ASSOCIATED WITH THE PROJECT PROPERTY AT ALL. N.I.C. DESIGNATED BUILDINGS AND AREAS ARE INCLUDED FOR SITUATIONAL REFERENCE TO THE BOUNDARIES OF THE PROJECT ONLY.
4. UNLESS OTHERWISE INDICATED ON THESE DRAWINGS OR IN THE PROJECT MANUAL AS BEING N.I.C. OR EXISTING, ALL ITEMS, MATERIALS, ETC. AND INSTALLATION OF THE SAME ARE PART OF THE CONTRACT DEFINED BY THESE DRAWINGS AND
SPECIFICATIONS.
5. AT EXISTING EXTERIOR BUILDING WALL ASSEMBLIES, THE CONTRACTOR IS TO VERIFY AND MAINTAIN, OR REPLACE EXISTING ASSEMBLIES AS NECESSARY TO MEET RATED WALL REQUIREMENTS. OVERSIGHT REQUIRED BY A LICENSED STRUCTURAL ENGINEER TO BE PROVIDED FOR FRAMING AND SHEATHING INCLUDING RATED WALL ASSEMBLIES WHERE REPAIR WORK IS IDENTIFIED DURING CONSTRUCTION. PROVIDE ENGINEERED DRAWINGS SHOWING EXTENT, DETAILS, AND CALCULATIONS TO THE AUTHORITY HAVING
JURISDICTION FOR REVIEW AND APPROVAL PRIOR TO REMEDIATION.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL PERMITS, LICENSES, INSPECTIONS AND TESTING AS
REQUIRED BY THE CONTRACT DOCUMENTS OR ANY GOVERNMENT AGENCY.
7. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOBSITE CONDITIONS. COMPLY WITH SAFETY REGULATIONS AND RESTRICTIONS AS REQUIRED FOR WORKER AND PEDESTRIAN PROTECTION DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT. PROVIDE PROTECTION AS REQUIRED TO PREVENT ANY DAMAGE TO EXISTING CONSTRUCTION WITHIN AND ADJACENT TO THE JOBSITE. WHERE DAMAGE OCCURS, REPAIR OR REPLACE DAMAGED AREA AND/OR MATERIAL AS REQUIRED TO THE OWNER'S APPROVAL AT NO ADDITIONAL COST. THESE REQUIREMENTS SHALL APPLY CONTINUOUSLY AND NOT BE
LIMITED TO NORMAL HOURS.
8. SHOULD ANY CONCRETE REQUIRE PATCHING ADJACENT TO IN SCOPE BUILDINGS, IT SHALL BE OF THE SAME SECTION AND DRAINAGE
PROFILE AS THE ADJACENT PAVED AREAS.
9. REFER TO UTILITY PENETRATION DETAILS AND TO SERVICE PROVIDER FOR COORDINATION OF MOUNTING BLOCK INSTALL, JUNCTION BOX LOCATIONS, AND CONDUIT ROUTING. THE CONTRACTOR SHALL COORDINATE THE CONNECTION OF THE EXISTING SERVICE
PROVIDER TO SCHEDULED INSTALLED COMPONENTS.
10. OWNER SHALL COORDINATE TRIMMING BACK OF LANDSCAPING AND TREES AS REQUIRED TO ALLOW ACCESS OF EXTERIOR
CLADDINGS AT THE EXISTING BUILDINGS WITHIN THE PROJECT SCOPE.
11. WHERE EXISTING GRADE ENCROACHES ON THE CLADDING, THE FINISH GRADE SHALL BE MODIFIED AND CORRECTED PER THE DESIGN DOCUMENT DETAILS AND ASSOCIATED CIVIL SCOPE FOR ALL BUILDINGS ON THE PROPERTY. IF A 6" MINIMUM DISTANCE IS NOT REASONABLY ATTAINABLE, FINISH GRADE AT THE BASE OF WALL SHALL BE MODIFIED AND RE-SLOPED AWAY FROM THE BUILDING (AT A 10-15 DEGREE SLOPE) SO AS THE BEST POSSIBLE CLEARANCE IS ACHIEVED. ADDITIONALLY, THE INCLUSION OF A CONTINUOUS 12" WIDE BY 12" DEEP GRAVEL FILLED FURROW SHALL BE INSTALLED 18" - 24" FROM THE BASE OF WALL RUNNING THE LENGTH OF THE NON-CONFORMING AREA. NOTE: GRAVEL SHALL EITHER BE 3/4" ROUND OR 3/4" MINUS CLEAN OPEN FACE CRUSHED ROCK.
2.
540.00'
2.
243.00' N89°18'30"W 132.00' N89°18'30"W
185' N89°18'30"W
2.
0°
'3 0"
E
2.
0°
'3 0"
W
200.00"
0.
DELA
P
R
OAD
SB
H W
Y
SO
UTH
OFF
R
AM
P)
HW
Y
S
A
B
C
D
E
F
HELI
PAD
3.
4.
.8
2'
ADJACENT
LOT 4201
(N.I.C.)
ADJACENT
LOT 4201
(N.I.C.)
ADJACENT
LOT 4201
(N.I.C.)
ADJACENT
LOT 4201
(N.I.C.)
ADJACENT
LOT 4201
(N.I.C.)
ADJACENT
LOT 4201
(N.I.C.)
GREENSPRINGS D
RIVE
5 5
A1.00
SITE PLAN
08.04.2025
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2026 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 25-095
Permit Issue Set
Bidding Issue Addenda - 05.18.2026
O re go n
D ep ar tm en t o f F or es try
Fo re st G ro ve
W ar eh ou se a nd F ire C ac he
C la dd in g an d W in do w R ep la ce m en t (
P O
-6
-0
7)
O re go n
De pa rtm en t o f F or es try
S ta te
S tre et , B ui ld in g
F, S al em
, O R
G al es C re ek
R d.
, F or es t G ro ve
, O R
EXISTING CONCRETE FOUNDATION WALLS TO REMAIN, REFER TO BASE OF WALL DETAILS FOR INTEGRATION
OF WRB AND FLASHING PROVISIONS.
ADD ALTERNATE: EXISTING VINYL WINDOW UNITS, INCLUDING ADJACENT TRIM AND CONCEALED COMPONENTS TO BE REMOVED AND LEGALLY DISPOSED OF. INSTALL SCHEDULED REPLACEMENT FLANGED VINYL WINDOW UNIT, INCLUDING RELATED SAM PRE AND POST WRAP FLASHING, METAL HEAD FLASHING, AND RELATED CONCEALED COMPONENTS, TYPICAL. INSTALL SCHEDULED DYNAMIC SEALANT JOINTS AND FIBER CEMENT TRIM ALONG 100% OF WINDOW PERIMETERS. REFER TO WALL OPENING DETAILS AND
PROJECT MANUAL.
ELEVATION KEYNOTES:
EXISTING EXTERIOR SIDING AND TRIM TO BE REMOVED AND LEGALLY DISPOSED OF. INSTALL SCHEDULED REPLACEMENT FIBER CEMENT PLANK LAP CLADDING (AT BUILDING MAIN WALL AREAS), FIBER CEMENT SHINGLE PANEL CLADDING (AT UPPER GABLE END WALLS), AND FIBER CEMENT TRIM (TYPICAL) INSTALLED OVER PRESSURE TREATED FURRING STRIPS WITH INSECT SCREENS AT HORIZONTAL TERMINATIONS, CODE COMPLIANT WRB, AND INTEGRATED SAM AND METAL FLASHINGS. REFER TO WALL DETAILS AND PROJECT
MANUAL.
REMOVE, LEGALLY DISPOSE OF, AND REPLACE 100% OF EXISTING GUTTER AND DOWNSPOUT ASSEMBLIES
AT EXISTING LOCATIONS, REFER TO PROJECT DESIGN DOCUMENTS AND PROJECT MANUAL.
EXISTING ENTRY SWING DOOR UNITS TO BE REMOVED, SAFELY STORED, AND REINSTALLED. REINSTALL DOOR UNITS WITH RELATED SAM PRE AND POST WRAP FLASHING, METAL HEAD AND SILL PAN FLASHING, AND RELATED CONCEALED COMPONENTS, TYPICAL. INSTALL SCHEDULED DYNAMIC SEALANT JOINTS AND FIBER CEMENT TRIM ALONG DOOR HEAD AND JAMB PERIMETERS. REFER TO DOOR SCHEDULE, WALL
OPENING DETAILS, AND PROJECT MANUAL.
IDENTIFIED LOCATION OF EXISTING UTILITY SERVICE CONNECTIONS. REFER TO WALL DETAILS.
1 BUILDING 'A' MAIN OFFICE FRONT (NORTH) ELEVATION
N.T.S. ORIENTED FACING EAST
mhg
4 BUILDING 'A' MAIN OFFICE SIDE (WEST) ELEVATION
N.T.S. ORIENTED FACING SOUTH / SOUTHEAST
mhg
3 BUILDING 'A' MAIN OFFICE REAR (SOUTH) ELEVATION
N.T.S. ORIENTED FACING EAST
mhg
2 BUILDING 'A' MAIN OFFICE SIDE (EAST) ELEVATIONS
N.T.S.
mhg
EXISTING COMPOSITION ASPHALT SHINGLE ROOFING, UNDERLAYMENT, STATIC VENTS, EXHAUST VENTS, AND ASSOCIATED ROOF AND FLASHING COMPONENTS TO BE REMOVED, DISPOSED OF, AND REPLACED.
WORK SHALL INCLUDE REMOVAL OF EXISTING CHIMNEYS AND REPAIR OF PENETRATIONS, REMOVAL AND REPLACEMENT OF INTAKE AND EXHAUST VENT PROVISIONS, PLUMBING STACK, AND HVAC VENTS.
EXISTING WALL MOUNTED LADDER ASSEMBLY TO BE REMOVED, SAFELY STORED, AND
REINSTALLED ON FLASHED MOUNTING BLOCKS.
ELEVATION NOTES:
1. PHOTO ELEVATIONS ARE INCLUDED FOR REFERENCE TO EXISTING CONDITIONS ONLY. CONTRACTOR SHALL
FIELD VERIFY ALL CONDITIONS PRIOR TO NOTICE TO PROCEED FROM OWNER, PRODUCT OR MATERIALS TAKE-OFFS, PRODUCT OR MATERIALS PROCUREMENT, OR FABRICATOR SHOP-DRAWING PRODUCTIONS.
2. COORDINATE DEMOLITION WITH EXTERIOR CLADDING, WINDOW AND ROOF REPLACEMENT PER THE DESIGN DOCUMENTS.
PERFORM SELECTIVE AND LIMITED DEMOLITION OF EXISTING EXTERIOR SHEATHING AS REQUIRED.
3. VERIFY CLEARANCE REQUIREMENTS AND MATCH ASSEMBLY OF EXISTING FIRE RATED WALLS AND ROOF
SYSTEMS WHERE REPAIRED DURING THE COURSE OF REQUIRED WORK.
4. REPLACE EXTERIOR PLYWOOD SHEATHING AS NECESSARY TO PERFORM REQUIRED WORK AND AS NECESSARY TO CHASE DAMAGE TO EXTINCTION. PATCH, REPAIR, AND MATCH PLANE OF EXISTING ADJACENT SURFACES.
5. CONTRACTOR TO VERIFY VENTILATION OF EXISTING BUILDING ATTIC AREA FOR VENTILATION REQUIREMENTS.
INSTALL ADDITIONAL INTAKE AT EAVE AND UPPER ROOF EXHAUST LOCATIONS AS REQUIRED.
PORTIONS OF EXISTING MASONRY BRICK CHIMNEYS EXTENDING ABOVE ROOF SHEATHING TO
BE REMOVED, DISPOSED OF, AND THE ROOF DECK OPENING INFILLED WITH NEW PLYWOOD
SHEATHING. PERFORM REPAIRS TO EXISTING AREAS OF ROOF PENETRATIONS AS REQUIRED
FOR INSTALLATION OF NEW ROOFING UNDERLAYMENT, AND COMPOSITIONS ASPHALT SHINGLE
ROOFING MATERIALS.
TYP.1
TYP.1
TYP.1
TYP.1
TYP.2
TYP.2
TYP.2
TYP.2
TYP.
TYP.2
TYP.2
TYP.
TYP.
TYP. 2
TYP.2
TYP.2
TYP.
TYP. 2
TYP.
TYP.3
TYP.
TYP.3
TYP.
TYP.
TYP.3
TYP.
TYP.
TYP.
TYP.
TYP.
5TYP.6
TYP.6
TYP. 6
TYP.6
TYP.7
TYP.7
TYP.7
TYP.
A2.01
BUILDING
ELEVATIONS
07.30.2026
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2026 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 26-043
95% CD Issue Review Set
O re go n
D ep ar tm en t o f F or es try
K la m at h Fa lls
B ui ld ib g E nc lo su re
R eh ab ili ta tio n (P
O -6
-0
7) O re go n De pa rtm en t o f F or es try
S ta te S tre et
, B ui ld in g F, S al em , O
R
D eL ap R d.
, K la m at h
Fa lls
, O R
3"
'-0
S
C A
LE
F
A C
TO
R
: 4
INSTALL 3 CONTINUOUS
BEADS OF 3/8" DIAMETER
SEALANT, TYPICAL
4" MIN.
OVERLAP
(6" RECOMMENDED)
NOTE:
SLIP FLASHING TOGETHER FOR A MORE
FINISHED APPEARANCE VERSUS STACKING
FLASHING
METAL FLASHING
NOTE:
VERIFY DOWN LEG OF FLASHING DOES NOT IMPEDE
WITH OPERATION OR VIEW OF WINDOW. DOWN LEG
DIMENSION TO BE VERIFIED DURING MOCK-UP
1 TYPICAL FLASHING PROFILE SECTION 2 TYPICAL FLASHING LAP JOINT
1/2" MIN.
DOWN LEG
1/2" HEMMED
KICK
1/2" END
DAM
4" UP
LEG
2" FASTENER
ZONE
5% SLOPE @ 1-1/2" WIDE
HEMMED DRIP EDGE
(REMOVE SHARP
EDGES)
10% SLOPE @ 1-1/2" WIDE
NOTES:
1. CONTRACTOR TO VERIFY COMPONENT CLEARANCE REQUIREMENTS AND MAINTAIN ALL RATED WALL ASSEMBLIES.
2. METAL THRU WALL FLASHING IS TO BE COMPLETE WITH UPTURNED ENDS AT TERMINATIONS AND CONTINUOUS
AROUND CORNERS. SLOPE HORIZONTAL LEGS TO DRAIN, MIN. 5%
3. APPLY PRIMER TO CONCRETE SUBSTRATE PRIOR TO APPLYING SAM.
4. SHEET METAL FLASHING IS TO FULLY COVER SAM AND ICE AND WATER SHIELD ENTIRELY FROM UV EXPOSURE.
5. ISOMETRIC DETAILS ARE INTENDED TO ILLUSTRATE THE RECOMMENDED SEQUENCE OF COMPONENT INSTALLATION
AND GENERAL SHAPE AND PROFILE CONCEPTS OF FLASHING, WATERPROOFING, AND TRANSITION ASSEMBLIES.
CERTAIN ADJACENT COMPONENTS HAVE NOT BEEN ILLUSTRATED FOR DETAIL CLARITY.
6. REFER TO PROJECT MANUAL, PRODUCT SPECIFICATIONS FOR SCHEDULED COMPONENT ASSEMBLIES.
7. PRIME AND PREP CLADDING AND TRIM AS REQUIRED TO RECEIVE SEALANT AND PAINT.
TYPICAL DYNAMIC SEALANT JOINTTYPICAL STATIC FILLET JOINT
SCHEDULED SEALANT1/2" TYP.
ENSURE 2:1 WIDTH TO DEPTH RATIO
AT MID POINT OF JOINT, TYPICAL
INSTALL CLOSED CELL NON-GASSING
SOFT BACKER ROD. ENSURE BACKER
MATERIAL IS 25% LARGER THAN JOINT
WIDTH
1/2
TYP
CONTINUOUS 3/8" DIA. BEAD
OF SCHEDULED SEALANT
OVERDRIVEN FASTENER LOCATIONS:
SEAL NAIL INDENTS AND ADD NAIL
ADJACENT TO OVERDRIVEN
FASTENER LOCATION
SNUG TO CLADDING FACE FLUSH TO CLADDING FACE
UNDER DRIVEN FASTENERS EXPOSED OVERDRIVEN FASTENERS USE OF STAPLES
CORRECT
INCORRECT
INTERIOR
EXTERIOR
1 TYPICAL THRU-WALL FLASHING
3" = 1'-0" PROFILE AND LAP ISOMETRIC DETAILS
mhg
4 TYPICAL SEALANT JOINT
N.T.S. CONFIGURATION AND APPLICATION
mhg
3 TYPICAL CLADDING FASTENER INSTALLATION
3" = 1'-0" mhg
3/8"
TYP.
FACE NAIL MAY BE REQUIRED AT NON-TYPICAL CLADDING INSTALL LOCATIONS
NOTE:
1. FACE NAILING MAY BE USED TO SECURE DAMAGED OR DISPLACED CLADDING
WHEN BLIND NAILING IS NOT FEASIBLE.
2. IF FACE NAILING IS REQUIRED FOR WIND LOAD, ENSURE THE FASTENING
PATTERN MEETS RELEVANT STATE AND LOCAL CODE REQUIREMENTS.
3. DRIVE FASTENERS ONLY THROUGH THE OVERLAPPING COURSES OF CLADDING.
4. FASTENERS FOR FACE NAILING SHOULD BE LOCATED BETWEEN 3/4" AND 1"
FROM THE BOTTOM OF THE BOARD.
5. ALL EXPOSED FACE NAIL HEADS SHOULD BE FILLED WITH SCHEDULED AND
COMPATIBLE SEALANT TO PREVENT MOISTURE INTRUSION.
FACE NAIL ONLY AS NECESSARY AND KEEP
3/8" FROM ENDS (ENSURE THE HEAD IS
SNUG BUT NOT OVERDRIVEN)
3/8"
3/4"-1"
1 1/4" TYP.
OVERLAP
2 TYPICAL FIBER CEMENT PLANK CLADDING
3" = 1'-0" BLIND / FACE NAIL LAP AND FASTENING DETAIL
mhg A3.00 Wall Detals - ODF Klamath Falls.dwg
6 TYPICAL SEALANT INSTALLATION AT
3" = 1'-0" AT EXTERIOR PLANK LAP CLADDING, TRIM AND MOUNTING BLOCK COMPONENTS
mhg A3.00 Wall Detals - ODF Klamath Falls.dwg
MAINTAIN A MIN 1/8"
CLEARANCE BETWEEN
SIDING AND TRIM AND/OR
MOUNTING BLOCKS. ENSURE
GAP DOES NOT EXCEED 1/4"
FILLET BEAD OF
SCHEDULED SEALANT
NOTE: REFERENCE PENETRATION
DETAILS FOR CONCEALED
COMPONENT INSTALLATION
INSTALL SEALANT AT SIDE END
DAMS, EXTEND FROM REAR
VERTICAL LEG, INTO END DAM
FOLD AND TO DEPTH OF
DRAINAGE GAP 1/2" WIDTH MAX.
SCHEDULED TRIM
SCHEDULED PLANK LAP CLADDING
SCHEDULED MOUNTING
BLOCK, REFER TO DESIGN
DOCUMENTS FOR
MATERIAL (INSTALL
WEATHERCUT 2-PIECE
BLOCK AS NECESSARY)
1/2" MIN.
UPTURNED
END DAMS
SCHEDULED 5/4x4 FIBER
CEMENT TRIM - PRIME PRIOR
TO INSTALLATION (TYP.)
SCHEDULED FIBER CEMENT PLANK
LAP CLADDING WITH 8" REVEAL
(DETAIL SIMILAR AT ALT. SHAKE
PROFILE PANEL CLADDING)
STATIC FILLET JOINT OF
SCHEDULED SEALANT,
TYP.
SCHEDULED FURRING STRIPS
(ALIGN WITH STUD FRAMING)
WITH INSECT SCREENS
INSTALLED AT TOP-OF-WALL
AND BASE OF WALL
TERMINATIONS
SCHEDULED WRB
SHEATHING TO MATCH
EXISTING PLYWOOD
SCHEDULED MIN. 9" SAM
CENTERED AT CORNER
4 1/2"
4 1/2"
FILLET BEAD OF SCHEDULED
SEALANT, TYPICAL
8 OUTSIDE CORNER JOINT CONDITION
3" = 1'-0" WITH FIBER CEMENT CLADDING OVER RAINSCREEN CAVITY
mhg
SEALANT SETTING BED
5 BASE OF WALL ASSEMBLY
3" = 1'-0" WITH FIBER CEMENT PLANK LAP CLADDING - ISOMETRIC DETAIL
mhg
26-GAUGE PRE-FINISHED METAL
(OR PVC) FLASHING PANEL AT
PLANK JOINTS, TYP., PANEL TO BE
6" MIN. WIDTH AND LAPPED ONTO
COURSE BELOW 1" MIN.
SCHEDULED WRB
SCHEDULED FIBER CEMENT
PLANK LAP CLADDING, INSTALL
OVER DRAINAGE PLANE CAVITY
OVERHANG STARTER STRIP
WITH PLANK
EXISTING WOOD
STUD FRAMING -
AT 24" O.C. MAX
EXISTING SHEATHING (GYPSUM
SHEATHING LAYER FOR RATED
WALLS AS OCCURS)
PLACE BLIND NAIL HEADS
3/4"-1" FROM TOP EDGE AND
OVERLAP BY 1 1/4"
SCHEDULED FURRING
STRIPS FOR DRAINAGE
PLANE CAVITY
METAL FLASHING TO PROTECT SAM FROM UV EXPOSURE
SCHEDULED SAM FLASHING SEAL AT BASE OF SHEATHING
1 1/4"
CONCRETE FOUNDATION WALL
6" MIN. CLEARANCE
FROM GRADE
SCHEDULED WRB
FILLET BEAD OF SCHEDULED SEALANT, TYPICAL
SHEATHING TO MATCH
EXISTING PLYWOOD
MIN. 9" WIDE STRIP OF SCHEDULED SAM
CENTERED AT CORNER
4 1/2"
4 1/2"
SCHEDULED FIBER CEMENT PLANK
LAP CLADDING WITH 8" REVEAL
(DETAIL SIMILAR AT ALT. SHAKE
PROFILE PANEL CLADDING)
SCHEDULED PRESSURE TREATED FURRING
STRIPS ALIGNED WITH STUDS WITH INSECT
SCREENS INSTALLED AT TOP-OF-WALL AND
BASE- OF-WALL TERMINATIONS, TYP.
9 INSIDE CORNER JOINT CONDITION
3" = 1'-0" WITH FIBER CEMENT CLADDING OVER RAINSCREEN CAVITY
mhg
SCHEDULED 2x CEDAR TRIM (INSIDE CORNER
JOINT ONLY) - PRIME ALL SIDES PRIOR TO
INSTALLATION, (TYP.)
10 BASE OF WALL CLADDING TERMINATION
3" = 1'-0" FLASHING AT EXPOSED CONCRETE STEM WALL
mhg
EXISTING SHEATHING
SCHEDULED WRB, LAP OVER SAM
AND BASE OF WALL FLASHING BELOW
SCHEDULED FIBER CEMENT
PLANK LAP CLADDING
SCHEDULED SAM (REFER
TO SHEET NOTES)
SCHEDULED PRESSURE TREATED
FURRING STRIP WITH INSECT SCREEN
AT HORIZONTAL TERMINATIONS
SCHEDULED 3/8" DIA. CONTINUOUS
BEAD OF SEALANT FOR AIR-SEAL
24-GAUGE 316 STAINLESS
STEEL FLASHING WITH
HEMMED RETURN
1/2"
4"
EXISTING CONCRETE
FOUNDATION WALL
2"
MIN.
2"
MIN.
2"
24" O.C. MAX
3/4"-1"
BASIS OF DESIGN SHALL BE TO BLIND NAIL ALL FIBER CEMENT PLANK LAP CLADDING
NOTE:
1. DRAINAGE PLANE MEDIUM NOT SHOWN FOR CLARITY.
2. FASTENERS FOR BLIND NAILING SHOULD BE LOCATED BETWEEN 1" AND 3/4"
FROM THE TOP OF THE BOARD.
SCHEDULED WRB
WOOD STUDS
EXTERIOR WALL
SHEATHING
BLIND NAIL, TYP. KEEP 3/8" FROM ENDS
METAL FLASHING SHINGLE
AT BUTT JOINTS, TYPICAL
3/8"
1 1/4" TYP.
OVERLAP
24" O.C. MAX
SCHEDULED WRB
WOOD STUDS
EXTERIOR WALL
SHEATHING
3 TYPICAL ALIGNED INSIDE CORNER 4 TYPICAL ADJOINED OUTSIDE CORNER
NOTE:
BASIS OF DESIGN: PREMANUFACTURED INSIDE
AND OUTSIDE CORNER FLASHING (OR POP-RIVET
CORNER OVERLAPS AND SEAL SEAMS, ENSURE
WATER TIGHT LAPS)
NOTE:
BASIS OF DESIGN: PREMANUFACTURED OUTSIDE
AND OUTSIDE CORNER FLASHING (OR POP-RIVET
CORNER OVERLAPS AND SEAL SEAMS, ENSURE
WATER TIGHT LAPS)
A EXTERIOR NON-RATED WALL ASSEMBLY
DESIGN GUIDELINE: N/A
FIRE RESISTANCE RATING: N/A
STC: N/A
INT. EXT.
INSTALL SCHEDULED FURRING STRIPS
WITH INSECT SCREENS AT TERMINATIONS,
TYP.
INSTALL SCHEDULED FIBER CEMENT
PLANK-LAP CLADDING (REPLACEMENT TO
MATCH EXISTING SIZE AND EXPOSURE)
EXISTING INTERIOR 5/8" TYPE 'X' GYPSUM
WALLBOARD TO REMAIN
SCHEDULED WRB PER PROJECT MANUAL
EXISTING PLYWOOD SHEATHING TO
REMAIN (REPLACEMENT TO MATCH
EXISTING APPLIED VERTICALLY )
EXISTING 2x STUD FRAMING AT 16" O.C.
WITH EXISTING R-21 BATT INSULATION,
TYP.
7 EXISTING WALL TYPE A
3" = 1'-0" AT EXTERIOR WALL ASSEMBLIES
mhg
1/
2"
'-0
S
C A
LE
F
A C
TO
R
: 8 1"
'-0
S C
A
LE
F A
C
TO
R : 1
A3.01
WALL DETAILS
07.30.2026
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2026 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 26-043
95% CD Issue Review Set
O re go n
D ep ar tm en t o f F or es try
K la m at h Fa lls
B ui ld ib g E nc lo su re
R eh ab ili ta tio n (P
O -6
-0
7) O re go n De pa rtm en t o f F or es try
S ta te S tre et
, B ui ld in g F, S al em , O
R
D eL ap R d.
, K la m at h
Fa lls
, O R
'-0
S
C A
LE
F
A C
TO
R
: 4
FILLET BEAD OF SEALANT,
TYPICAL
SCHEDULED SAM, EXTEND FULL HEIGHT
OF VERTICAL TRIM MEMBER, EXTEND
BEYOND TRIM EDGE AS INDICATED
SCHEDULED FIBER CEMENT
PLANK LAP CLADDING
SCHEDULED TRIM - SIZE
PER SPECIFICATIONS -
PRIME PRIOR TO SEALANT
INSTALLATION (TYP.)
1/2" - 1"
CLEAR
DOWNSPOUT (AS OCCURS)
EXISTING SHEATHING
SCHEDULED CODE COMPLIANT DRAINAGE WRB
4 SAME PLANE TRIM WITH BRACKETED
3" = 1'-0" DOWNSPOUT AT FIBER CEMENT CLADDING AND TRIM - PLAN VIEW
mhg
2" TYP.
EA. SIDE
1"
MIN.
1 1/4"
MIN.
4"
1 GRADE BASE OF WALL FLASHING
3" = 1'-0" WITH CLEARANCE AT FIBER CEMENT CLADDING OVER RAINSCREEN CAVITY
mhg
3 BASE OF WALL FLASHING WITH KERF CUT
3" = 1'-0" CONCRETE SLAB AND FIBER CEMENT CLADDING OVER RAINSCREEN CAVITY
mhg
1"
1 1/2"
MIN.
1 1/2"
2"
MIN.
4"
2"
MIN.
1" CLR.
24-GAUGE 316 STAINLESS STEEL
FLASHING SET INTO KERF CUT -
FILL WITH SEALANT PRIOR TO
INSTALLING FLASHING
SAM (REFER TO SHEET NOTES)
CONTINUOUS 3/8" DIA BEAD OF
SEALANT
SCHEDULED SHEATHING
SCHEDULED WRB, LAP OVER SAM
AND BASE OF WALL FLASHING
BELOW AND SEAL
SCHEDULED PRESSURE TREATED
FURRING STRIPS WITH INSECT
SCREENS AT TERMINATIONS
SCHEDULED FIBER CEMENT PLANK
LAP CLADDING
TRIM AND CAP SADDLE FLASHING - ISOMETRIC INSET
5 VERTICAL TRANSITION JOINT
3" = 1'-0" AT FIBER CEMENT CLADDING TO EXPOSED CONCRETE - PLAN VIEW
mhg
SAM - LAP OVER WRB ONTO UNDERLYING
SHEATHING AND ADJACENT CONCRETE
FILLET BEAD OF SEALANT (TYP.)
2"
MIN.
2"
MIN.
24-GAUGE 316 STAINLESS
STEEL FLASHING TO CLOSE
END OF CAVITY ON TOP OF
FURRING
2"
MIN.
1/2" DYNAMIC
SEALANT JOINT
(TYP.)
6" MIN.
SIZE TO SUIT
FIELD CONDITIONS
1" CONFIRM DURING MOCK-UP
SEAL EDGE OF SAM
WITH COMPATIBLE
SEALANT
SCHEDULED 5/4 PVC TRIM
SCHEDULED SHEATHING
SCHEDULED WRB
PRESSURE TREATED FURRING STRIPS, TYP.
SCHEDULED FIBER CEMENT PLANK LAP CLADDING
REFER TO
NOTE 8
LINE OF TRIM CAP FLASHING ABOVE
5"
4"
4"
EXTEND 1/2"
BELOW TOP
OF TRIM
4"
24-GAUGE PRE-FINISHED METAL
TRIM CAP SADDLE FLASHING,
INTEGRATE AND LAP WITH WRB
AND BASE OF WALL FLASHING.
(EXTEND OVER TRIM 1" MIN.)
6 INSIDE CORNER TRANSITION JOINT
3" = 1'-0" AT FIBER CEMENT CLADDING TO EXPOSED CONCRETE - PLAN VIEW
mhg
SCHEDULED SAM TO LAP OVER WRB
STATIC FILLET JOINT OF SCHEDULED SEALANT, TYP.
2"
MIN.
1/2" DYNAMIC SEALANT JOINT (TYP.)
24-GAUGE 316 STAINLESS STEEL
FLASHING WITH HEMMED RETURN
SCHEDULED 2x CEDAR TRIM - PRIME
PRIOR TO INSTALLATION, (TYP.)
SCHEDULED WRB
EXISTING SHEATHING
LAP SAM 2" MIN.
ONTO CONCRETE
REFER TO
NOTE 8
SEAL EDGE OF SAM
WITH COMPATIBLE
SEALANT SCHEDULED FURRING STRIPS, TYP.
SCHEDULED FIBER CEMENT PLANK LAP CLADDING
4"
SIZE
TO SUIT
CONDITION 1/2"
NOTES:
1. CONTRACTOR TO VERIFY COMPONENT CLEARANCE REQUIREMENTS AND MAINTAIN ALL RATED WALL ASSEMBLIES.
2. CAREFULLY REMOVE EXISTING CLADDING, TRIM, WRB, AND ASSOCIATED FLASHINGS ALONG ELEVATION AREAS TO BE REHABILITATED.
3. METAL THRU WALL FLASHING IS TO BE COMPLETE WITH UPTURNED ENDS AT TERMINATIONS AND CONTINUOUS AROUND CORNERS.
SLOPE HORIZONTAL LEGS TO DRAIN, REFER TO DETAIL 1/A3.01
4. APPLY PRIMER TO CONCRETE SLAB AND FOUNDATION WALL SUBSTRATES PRIOR TO SAM APPLICATION SAM.
5. SHEET METAL FLASHING IS TO FULLY COVER SAM AND ICE AND WATER SHIELD MATERIALS ENTIRELY FROM UV EXPOSURE.
6. INSTALL LOW EXPANDING FOAM AROUND ALL PENETRATIONS TO LIMIT AIR LEAKAGE.
7. IF PENETRATION DOES NOT FALL ALONG FRAMING, INSTALL STRAPPING OR BLOCKING AND INTERMEDIATE FURRING STRIPS AS
NEEDED FOR BLOCK AND SIDING TERMINATIONS.
8. PROVIDE EXTENSIONS WHERE NEEDED TO PIPES, DUCTS, AND OTHER PENETRATIONS TO ACCOMMODATE INCREASED THICKNESS OF
WALL ASSEMBLIES.
9. PRIME AND PREP CLADDING AND TRIM AS REQUIRED TO RECEIVE SEALANT AND PAINT.
10. ISOMETRIC DETAILS ARE INTENDED TO ILLUSTRATE THE RECOMMENDED SEQUENCE OF COMPONENT INSTALLATION AND GENERAL
SHAPE AND PROFILE CONCEPTS OF FLASHING, WATERPROOFING, AND TRANSITION ASSEMBLIES. CERTAIN ADJACENT COMPONENTS
HAVE NOT BEEN ILLUSTRATED FOR DETAIL CLARITY.
11. TREAT ALL CUT EDGES AT PRESSURE-TREATED LUMBER, INCLUDING KERF CUTS, WITH COMPATIBLE TREATMENT SOLUTION PER
AMERICAN WOOD PROTECTION ASSOCIATION - AWPA - M4.
12. REFER TO PROJECT MANUAL, PRODUCT SPECIFICATIONS FOR SCHEDULED COMPONENT ASSEMBLIES.
SCHEDULED 5/4x8 HORIZONTAL FIBER
CEMENT TRIM BAND OVER LAPPED
CLADDING BELOW - PRIME ALL CUT
AND NON-PRIMED FACES PRIOR TO
INSTALLATION
24-GAUGE STAINLESS STEEL HEAD
FLASHING WITH HEMMED DRIP EDGE
SET IN CONTINUOUS BED OF SEALANT
1"
1/2"
1/2"
4"
7 HORIZONTAL BELLY-BAND TRIM FLASHING
3" = 1'-0" TRANSITION AT FIBER CEMENT PLANK LAP TO SHINGLE PANEL CLADDING
mhg
2"
MIN.
2"
MIN.
SCHEDULED FIBER CEMENT SHINGLE
PANEL CLADDING
CONTINUOUS SEALANT
SCHEDULED WRB, LAP OVER WRB
AND THRU- WALL FLASHING
BELOW
5% MIN.
SLOPE
2"
MIN.
1/2"
2"
MIN.
6"
2"
MIN.
EXISTING GRADE
6"
MIN.
EXISTING SHEATHING
SCHEDULED COMMERCIAL WRB, LAP OVER SAM
AND BASE OF WALL FLASHING BELOW
SCHEDULED FIBER CEMENT PLANK LAP
CLADDING
CONTINUOUS 3/8" DIA. BEAD OF
SCHEDULED SEALANT
BUTYL SAM STARTER STRIP
1/2" BORATE TREATED WOOD FURRING STRIPS
ALIGNED WITH STUDS WITH INSECT SCREENS
INSTALLED AT HORIZONTAL TERMINATIONS, TYP.
24-GAUGE STAINLESS STEEL
FLASHING WITH BACK HEM
(REFER TO SHEET NOTES)
SCHEDULED FIBER CEMENT PLANK
LAP CLADDING
SEALANT FILLET BEAD
SCHEDULED WRB
SCHEDULED PRESSURE TREATED
FURRING STRIP WITH INSECT SCREEN
AT HORIZONTAL TERMINATIONS
EXISTING SHEATHING
2 DOWNSPOUT CLEANOUT ASSEMBLY
3" = 1'-0" AT GRADE CLEARANCE WITH FIBER CEMENT PLANK LAP CLADDING
mhg
EXISTING AT GRADE STORM
DRAIN CONNECTION TO
DOWNSPOUT, MODIFY AS
REQUIRED TO ACCOMMODATE
DOWNSPOUT DIAMETER 12
"-1 6"
A
BO
VE
G
RA
DE
(O R
CO
NC
RE
TE
A S
OC
CU
RS
REFER TO WALL DETAILS FOR FIBER
CEMENT PANEL CLADDING AND
CONCEALED COMPONENT ASSEMBLIES
INSTALL SCHEDULE 80 FLUSH PVC TEE
CONNECTION WITH DWV HUB x HUB x
FPT THREADED CLEANOUT PLUG
INSTALL PVC DOWNSPOUT EXTENSION
AS REQUIRED FOR COMPONENT
CONNECTION TO DOWNSPOUT ABOVE
EXISTING GRADE (SEE
NOTES FOR CONC. WALK)
INSTALL ROUND METAL DOWNSPOUT
FROM GUTTER ABOVE, MAINTAIN 1"
MIN. CLEAR STANDOFF FROM FIBER
CEMENT CLADDING
SCHEDULED 5/4x8 HORIZONTAL FIBER
CEMENT TRIM BAND OVER LAPPED
CLADDING BELOW - PRIME ALL CUT
AND NON-PRIMED FACES PRIOR TO
INSTALLATION
24-GAUGE STAINLESS STEEL HEAD
FLASHING WITH HEMMED DRIP EDGE
SET IN CONTINUOUS BED OF SEALANT
1"
1/2"
1/2"
4"
7 HORIZONTAL BELLY-BAND TRIM FLASHING
3" = 1'-0" TRANSITION AT FIBER CEMENT PLANK LAP TO SHINGLE PANEL CLADDING
mhg
2"
MIN.
2"
MIN.
SCHEDULED FIBER CEMENT SHINGLE
PANEL CLADDING
CONTINUOUS SEALANT
SCHEDULED WRB, LAP OVER WRB
AND THRU- WALL FLASHING
BELOW
5% MIN.
SLOPE
SCHEDULED FIBER CEMENT PLANK
LAP CLADDING
SEALANT FILLET BEAD
SCHEDULED WRB
SCHEDULED PRESSURE TREATED
FURRING STRIP WITH INSECT SCREEN
AT HORIZONTAL TERMINATIONS
EXISTING SHEATHING
1/
2"
'-0
S
C A
LE
F
A C
TO
R
: 8 1"
'-0
S C
A
LE
F A
C
TO
R : 1
A3.02
WALL DETAILS
07.30.2026
SHEET NAME
REVISIONS
ISSUE
REV. DATE
PROJECT NAME
CLIENT
PROJECT NUMBER
SHEET NUMBER
15 82nd Drive, Suite 10 Gladstone, OR 97027
TEL: 503.772.1114
FAX: 503.772.4039
www.forensicbuilding.com info@forensicbuilding.com
COPYRIGHT ©2026 FORENSIC
BUILDING CONSULTANTS
All Rights Reserved
PRINT ALL DETAILS IN
COLOR AT 24x36
OR CCB# 155496
WA FORENW C94308
UT #8334529-5501
(RE) 26-043
95% CD Issue Review Set
O re go n
D ep ar tm en t o f F or es try
K la m at h Fa lls
B ui ld ib g E nc lo su re
R eh ab ili ta tio n (P
O -6
-0
7) O re go n De pa rtm en t o f F or es try
S ta te S tre et
, B ui ld in g F, S al em , O
R
D eL ap R d.
, K la m at h
Fa lls
, O R
'-0
S
C A
LE
F
A C
TO
R
: 4 6 EXHAUST VENT PENETRATION
3" = 1'-0" WITH MOUNTING BLOCK AT FIBER CEMENT PLANK LAP CLADDING
mhg
1/2" 1/2"
1/2"
4"
INTEGRAL DRIP EDGE
PROVIDE SAME OR GREATER
FREE VENT AREA AS EXISTING
FIXTURE
2"
SCHEDULED SEALANT
SAM TO LAP OVER HEAD FLANGE
PRE-MANUFACTURED 'PRIMEX' VENT
HOOD WITH INTEGRAL FLANGES BY
PRIMEX - PROVIDE SAME OR GREATER
FREE VENT AREA AS EXISTING FIXTURE
1/2"
DYNAMIC SEALANT JOINT
EXISTING SHEATHING
SCHEDULED WRB, LAP OVER WRB
AND SAM BELOW AND SEAL
24-GAUGE STAINLESS STEEL HEAD
FLASHING FULLY BED IN SEALANT. FILL
CORNERS AT ENDS WITH SEALANT
CONTINUOUS FILLET BEAD OF SCHEDULED
SEALANT (TYP.)
2"
SCHEDULED PRESSURE TREATED
FURRING STRIP WITH INSECT SCREEN
AT HORIZONTAL TERMINATIONS
EXTEND PRESSURE TREATED FURRING
BEHIND TRIM
CONTINUOUS 3/8" DIA. BEAD OF
SCHEDULED SEALANT
SCHEDULED BUTYL BASED SAM
9"
SCHEDULED 5/4 FIBER CEMENT MOUNTING BLOCK -
PRIME PRIOR TO SEALANT INSTALLATION
NOTE: UPON DEMOLITION, CONTRACTOR TO
VERIFY THAT EXISTING DUCTWORK IS
NOMINAL 4" MINIMUM DIAMETER OR
GREATER, TYP.
5% MIN.
SLOPE
SCHEDULED FIBER CEMENT PLANK
LAP CLADDING
NOTES:
1. CONTRACTOR TO VERIFY COMPONENT CLEARANCE REQUIREMENTS AND MAINTAIN ALL RATED WALL ASSEMBLIES.
2. CAREFULLY REMOVE EXISTING CLADDING, TRIM, WRB, AND ASSOCIATED FLASHINGS ALONG ELEVATION AREAS TO BE REHABILITATED.
3. METAL THRU WALL FLASHING IS TO BE COMPLETE WITH UPTURNED ENDS AT TERMINATIONS AND CONTINUOUS AROUND CORNERS. SLOPE HORIZONTAL LEGS TO DRAIN, REFER TO DETAIL 1/A3.01
4. APPLY PRIMER TO CONCRETE SLAB AND FOUNDATION WALL SUBSTRATES PRIOR TO SAM APPLICATION SAM.
5. SHEET METAL FLASHING IS TO FULLY COVER SAM AND ICE AND WATER SHIELD MATERIALS ENTIRELY FROM UV EXPOSURE.
6. INSTALL LOW EXPANDING FOAM AROUND ALL PENETRATIONS TO LIMIT AIR LEAKAGE.
7. IF PENETRATION DOES NOT FALL ALONG FRAMING, INSTALL STRAPPING OR BLOCKING AND INTERMEDIATE FURRING STRIPS AS NEEDED FOR BLOCK AND SIDING TERMINATIONS.
8. PROVIDE EXTENSIONS WHERE NEEDED TO PIPES, DUCTS, AND OTHER PENETRATIONS TO ACCOMMODATE INCREASED THICKNESS OF WALL ASSEMBLIES.
9. PRIME AND PREP CLADDING AND TRIM AS REQUIRED TO RECEIVE SEALANT AND PAINT.
10. ISOMETRIC DETAILS ARE INTENDED TO ILLUSTRATE THE RECOMMENDED SEQUENCE OF COMPONENT INSTALLATION AND GENERAL SHAPE AND PROFILE CONCEPTS OF FLASHING, WATERPROOFING, AND TRANSITION ASSEMBLIES. CERTAIN ADJACENT COMPONENTS HAVE NOT BEEN ILLUSTRATED FOR DETAIL CLARITY.
11. TREAT ALL CUT EDGES AT PRESSURE-TREATED LUMBER, INCLUDING KERF CUTS, WITH COMPATIBLE TREATMENT SOLUTION PER AMERICAN WOOD PROTECTION ASSOCIATION - AWPA - M4.
12. REFER TO PROJECT MANUAL, PRODUCT SPECIFICATIONS FOR SCHEDULED COMPONENT ASSEMBLIES.
EXISTING ROOF CORBEL AND
TRIM TO BE REMOVED AND
REINSTALLED OVER
SCHEDULED WRB. ADD
BLOCKING AS NECESSARY FOR
REQUIRED TRIM EXTENSION
BEYOND ADJACENT CLADDING
SURFACE
SCHEDULED FIBER CEMENT
PLANK-LAP CLADDING
FILLET BEAD OF SCHEDULED
SEALANT AT BRACE TRIM
TRANSITION TO ADJACENT
CLADDING, TYPICAL EACH
SIDE AND BOTTOM
SCHEDULED SHEATHING
TYPICAL WALL ASSEMBLY
5 ROOF CORBEL BRACE TRIM
3" = 1'-0" AT FIBER CEMENT PLANK-LAP CLADDING
mhg
4 CORBEL FLASHING INTEGRATION DETAIL
3" = 1'-0" AT GABLE/RAKE FASCIA
mhg A3.00 Wall Detals - ODF Klamath Falls.dwg
EXISTING WOOD CORBEL TO BE
REMOVED AND REINSTALLED
OR RE-FABRICATED TO MATCH
EXISTING
24-GAUGE STAINLESS
STEEL CORBEL FLASHING
WITH HEMMED RETURN SET
IN COMPATIBLE SEALANT,
EXTEND AROUND OUTSIDE
CORNER AND INTEGRATE
WITH EXTERIOR WALL
CLADDING
2"
1/2"
2"
4"
V.I.F.
2 ROOF GABLE/RAKE FASCIA DETAIL
3" = 1'-0" AT TOP OF WALL
mhg
EXISTING METAL ROOF
EDGE FLASHING TO REMAIN
EXISTING COMPOSITION ASPHALT
SHINGLE AND UNDERLAYMENT TO REMAIN
EXISTING ROOF SHEATHING TO
REMAIN
SCHEDULED FIBER CEMENT
SHINGLE PANEL CLADDING
2"
MIN.
2"
MIN.
SCHEDULED 5/4 FIBER CEMENT
TRIM AT GABLE FASCIA
LOCATIONS, TYP.
SCHEDULED 4" STRIP OF BUTYL
SAM…
This is the start of the file's text. The full file is on GovTribe.