Attachment 8 Travis AFB Fire Suppression Building 54 Final Drawings.pdf

PDF 5 MB Posted

Attached to
Renovate Travis AFB B243/B54 Fire Suppression Systems Federal contract opportunity
Solicitation number
FA442720R0022
Issued by
Department of the Air Force Air Mobility Command

About this file

This solicitation seeks proposals to renovate the fire suppression systems in two server rooms at Travis Air Force Base to comply with technical guidance. The work includes upgrading existing wet pipe systems with clean agent extinguishing systems as a supplement in Building 243, Bay A and Building 54. For both locations, the contractor must provide all professional services, permits, equipment, labor, materials and ancillary items to complete the renovations according to the design documents. The Department of the Air Force Air Mobility Command is the issuing agency. Proposals are due by the date specified in the solicitation, and the agency intends to award a firm-fixed price contract for the work.

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Travis AFB B243/B54 Fire Suppression Systems, newest first.
File Type Posted
Pre-Bid RFIs 11-19 Combined B243 B54 Fire Supp Final.pdf PDF
Solicitation Amendment FA442720R00220002 SF 30.pdf PDF
B54 As-Builts.pdf PDF
Pre-Bid RFIs Combined - B243 B54 Fire Supp - Final.pdf PDF
Solicitation Amendment FA442720R00220001 SF 30.pdf PDF
Attachment 2 Travis AFB Fire Suppression Building 243 Final Design Analysis.pdf PDF
Attachment 14 TAFB Security Requirements.pdf PDF
Attachment 12 2008 Travis Design Guide FEG.PDF PDF
Attachment 13 Wage Determination Applicability.pdf PDF
Attachment 5 Vicinity Map 243.pdf PDF
Solicitation - FA442720R0022 Request for Proposal.pdf PDF
Attachment 6 SOW Renovate Fire Supp B54 XDAT 15 1124.pdf PDF
Attachment 4 Travis AFB Fire Suppression Building 243 Final Specifications.pdf PDF
Attachment 1 SOW Renovate Fire Supp B243 XDAT 15 1123.pdf PDF
Attachment 10 Vicinity Map 54.pdf PDF
Attachment 7 Travis AFB Fire Suppression Building 54 Final Design Analysis.pdf PDF
Past Performance Questionnaire.pdf PDF
Attachment 11 Engineering Technical Letter ETL 01 18 Fire Protection Engineering.pdf PDF
Attachment 3 Travis AFB Fire Suppression Building 243 Final Drawings.pdf PDF
Attachment 9 Travis AFB Fire Suppression Building 54 Final Specifications.pdf PDF
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL

1 G1.0 COVER AND SHEET INDEX

2 G1.1

ABBREVIATIONS, SYMBOLS & GENERAL NOTES

G1.2

GENERAL NOTES

SHEET INDEX

SHEET TITLE

PROJECT SCOPE:

RENOVATE THE FIRE PROTECTION SYSTEM IN BUILDING 54 (SWITCH

ROOM) TO COMPLY WITH THE UNIFIED FACILITIES CRITERIA (UFC)

3-600-01 AND AIR FORCE ENGINEERING TECHNICAL LETTER (ETL) 01-18.

THESE DESIGN FEATURES INCLUDE:

A. FOR CONSTRUCTION OF A CLEAN AGENT FIRE SUPPRESSION

SYSTEM TO INCLUDE, BUT NOT LIMITED TO:

1. PROVIDE STAND-ALONE (NOT DEPENDENT UPON THE

BUILDING FIRE ALARM SYSTEM FOR OPERATION) CONTROL

PANELS THAT ARE LISTED FOR RELEASING DEVICE SERVICE

AND MONITORED BY THE BUILDING FIRE ALARM SYSTEM.

2. THE SYSTEM SHALL INCLUDE MANUALLY ACTIVATED

EXHAUST TO FACILITATE THE EXTRACTION OF ANY

REMAINING CLEAN AGENT AFTER THE REQUIRED HOLD TIME OF

THE TOTAL FLOODING CLEAN AGENT.

3. VERY EARLY WARNING SMOKE DETECTION SYSTEM MUST

BE USED TO ACTIVATE A CLEAN AGENT FIRE EXTINGUISHING

SYSTEM.

NOTE: THESE STATEMENTS ARE OF GENERAL NATURE AND NOT TO BE

UNDERSTOOD AS A SOLE SOURCE OF PROJECT DELINEATION. THE

CONTRACTOR IS RESPONSIBLE FOR THOROUGH REVIEW OF THE PLANS

AND SPECIFICATIONS TO UNDERSTAND THE COMPLETE SCOPE OF THE

PROJECT.

2020 E. 1ST STREET, SUITE 525

SANTA ANA, CALIFORNIA 92705

(714) 689-0298

ARCHITECTURE PROJECT MANAGEMENT

DEVELOPMENT ONE, INC.

P.O. BOX 2034

HUNTINGTON BEACH, CALIFORNIA 92647

(714) 840-4418

FIRE PROTECTION ENGINEER

MUDRY & ASSOCIATES

PROJECT TEAM:

FIRE SUPPRESSION DRAWINGS

F1.0

FIRE PROTECTION PLAN

ARCHITECTURAL

A1.0

FLOOR PLAN

A1.1

REFLECTED CEILING PLAN

A2.0

DETAILS

A3.0

PHOTO SHEET

VICINITY MAP

PROJECT SITE ,

BUILDING B54

BASE MAP

SAN

FRANCISCO,

CALIFORNIA

NORTH NORTH

NORTH

LOS ANGELES,

CALIFORNIA

TRAVIS AFB,

CALIFORNIA

VICINITY MAP

RENOVATE WET FIRE SUPPRESSION TO DRY,

SERVER ROOM, B54

XDAT 15-1124

FINAL DESIGN DOCUMENTS

TRAVIS AIR FORCE BASE

690 AIRMAN DRIVE

TRAVIS AFB, CA 94535

AREA MAP: TRAVIS AFB, CALIFORNIA

CODE REFERENCES

N/A

COVER AND SHEET INDEX

G1.0

Architecture | Project Management

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE

CODES, REGULATIONS AND TRAVIS AIR FORCE BASE FACILITY STANDARDS

AS LISTED BELOW:

ASTM STANDARDS

ANSI STANDARDS

OSHA REGULATIONS

UL SAFETY STANDARDS

APPLICABLE STATE, CITY AND COUNTY CODES AND REGULATIONS

2018 INTERNATIONAL BUILDING CODE (IBC)

2018 INTERNATIONAL MECHANICAL CODE (IMC)

2018 INTERNATIONAL PLUMBING CODE (IPC)

2017 NATIONAL ELECTRICAL CODE (NFPA 70)

2018 NATIONAL ELECTRICAL SAFETY CODE (ANSI C2)

2019 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72

NATIONAL FIRE ALARM AND SIGNALING CODE

2019 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13

STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEM

2018 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 90A

2018 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101

LIFE SAFETY CODE

2015 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

UNIFORM FEDERAL ACCESSIBILITY STANDARDS, (UFAS)

ETL 94-7 EPA GUIDELINE ITEMS IN CONSTRUCTION AND OTHER CIVIL

ENGINEERING SPECIFICATIONS 14 DEC 94

PRESIDENTIAL MEMORANDUM 26 APR 94 - ENVIRONMENTAL

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES

AIR FORCE ENGINEERING TECHNICAL LETTER (ETL) 01-18

SAFETY AND HEALTH PROGRAMS 29 CFR PARTS 1910, 1926, AND 40 CFR

PARTS 61, 261, 761 AND 763

DEPARTMENT OF DEFENSE (DoD):

MIL-HDBK-1008, FIRE PROTECTION FOR

FACILITIES ENGINEERING, DESIGN AND

CONSTRUCTION

DEPARTMENT OF DEFENSE (DoD):

DEPARTMENT OF DEFENSE INSTRUCTION

(DoDI) 6055.6, DEPARTMENT OF DEFENSE

FIRE PROTECTION PROGRAM

G1.0A1.0

OVERALL

FLOOR PLAN

G1.0 A1.1

REFLECTED

CEILING PLAN

MECHANICAL

8 M0.1 MECHANICAL LEGEND NOTES & SCHEDULES

9 M1.1 MECHANICAL FLOOR PLAN

M2.1

MECHANICAL DETAILS

ELECTRICAL

11 E0.1 ELECTRICAL LEGENDS

12 E0.2 ELECTRICAL NOTES

E1.1

ELECTRICAL FLOOR PLAN

275 W. HOSPITALITY LANE, SUITE 100

SAN BERNARDINO, CALIFORNIA 92408

(909) 890-3700

MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER

DESIGN WEST ENGINEERING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FAIRFIELD

AutoCAD SHX Text

VACAVILLE

AutoCAD SHX Text

TRAVIS AFB

AutoCAD SHX Text

TO SAN FRANCISCO

AutoCAD SHX Text

TO SACRAMENTO

AutoCAD SHX Text

HANGAR AVE

AutoCAD SHX Text

AIR BASE PKWY

AutoCAD SHX Text

BURGAN BLVD

AutoCAD SHX Text

WALTERS RD

AutoCAD SHX Text

HWY 12

AutoCAD SHX Text

PEABODY RD

AutoCAD SHX Text

GATE

AutoCAD SHX Text

RAGSDALE ST.

AutoCAD SHX Text

TWIN PEAKS, DR.

AutoCAD SHX Text

ILLINOIS AVE.

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DRAWING NUMBER

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text APPROVED (Commander)

AutoCAD SHX Text RECOMMENDED (Base Engineer)

AutoCAD SHX Text SUBMITTED (Chief Engineer)

AutoCAD SHX Text

AIR MOBILITY COMMAND

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text

TRAVIS AIR FORCE BASE

AutoCAD SHX Text

SEQ NO.

AutoCAD SHX Text

SHEET NUMBER:%%U

AutoCAD SHX Text

IF SHEET IS LESS THAN 22" X 34" IT IS A REDUCED PRINT - SCALE ACCORDINGLY

AutoCAD SHX Text

BUILDING - B54 SERVER ROOM

AutoCAD SHX Text

2020 E. FIRST STREET, SUITE 525 SANTA ANA, CALIFORNIA 92705

AutoCAD SHX Text

(714) 689-0298 www.developmentone.net

AutoCAD SHX Text

2016 COPYRIGHT DEVELOPMENT ONE, INC.

AutoCAD SHX Text THIS DRAWING AND ITS CONTENTS ARE INSTRUMENTS OF SERVICE AND ARE THE COPYRIGHTED PROPERTY OF DEVELOPMENT ONE, INC. THE USE IS EXPRESSLY INTENDED FOR THE PROJECT NOTED BELOW AND MAY NOT BE REUSED OR REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN PERMISSION OF ITS PRINCIPALS.

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

65%%% DESIGN SUBMITTAL

AutoCAD SHX Text 02/15/19

AutoCAD SHX Text A

AutoCAD SHX Text

35%%% PRELIMINARY DESIGN SUBMITTAL

AutoCAD SHX Text 06/06/19

AutoCAD SHX Text C

AutoCAD SHX Text

FINAL DESIGN DOCUMENTS

AutoCAD SHX Text 09/30/19

AutoCAD SHX Text

DM

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text 01-23-2019

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

XDAT 15-1124

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text J

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text Renewal Date

AutoCAD SHX Text C23740

AutoCAD SHX Text Signature

AutoCAD SHX Text 10/31/19

Architecture | Project Management

GENERAL NOTES

ELEVATION VIEW REFERENCES

SECTION VIEW REFERENCES

KEYNOTE MARKER

A

B

C

D

ELEVATION VIEW

DETAIL NUMBER

SHEET ON WHICH INTERIOR

ELEVATIONS ARE SHOWN

SHEET ON WHICH DETAIL

IS REFERENCED

A2.0 A3.0

DETAIL NUMBER

SHEET ON WHICH

DETAIL IS SHOWN

SHEET ON WHICH DETAIL

IS REFERENCED

A2.0 A3.0

DETAIL NUMBER

SHEET ON WHICH DETAIL

IS REFERENCED

SHEET ON WHICH

DETAIL IS SHOWN

A2.0 A3.0

A2.0 A5.0

DETAIL NUMBER

SHEET ON WHICH

DETAIL IS SHOWN

SHEET ON WHICH DETAIL

IS REFERENCED

PHOTO VIEW NUMBER

SHEET ON WHICH PHOTO IS

SHOWN

SHEET ON WHICH PHOTO IS

REFERENCED

A1.0 A7.0

PHOTO VIEW REFERENCE

DETAIL REFERENCE

PLAN REFERENCES

SYMBOL LEGEND

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

BD BOARD

BLDG BUILDING

BLK(G) BLOCK(ING)

BOT BOTTOM

CBC CALIFORNIA BUILDING CODE

C.L. CENTER LINE

CLG. CEILING

CLR CLEAR

CONC CONCRETE

CONT CONTINUOUS

DIA DIAMETER

DR DOOR

DWG DRAWING

E EXISTING

ETR EXISTING TO REMAIN

EA EACH

ELEC ELECTRICAL

EQ. EQUAL

EXIST EXISTING

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FIN FINISH(ED)

FL FLOOR

F.O.M FACE OF MASONRY

FT FEET

GA GAUGE

GALV GALVANIZED

GWB GYPSUM WALL BOARD

GYP GYPSUM

HM HOLLOW METAL

HORIZ HORIZONTAL

HT HEIGHT

HVAC HEATING, VENTILATION, AIR CONDITIONING

IN INCH

INS INSULATION

INT INTERIOR

LT LIGHT

MAX MAXIMUM

MECH MECHANICAL

MIN MINIMUM

MTD MOUNTED

MTL METAL

N NEW

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OAE OR APPROVED EQUAL

O.C. ON CENTER

OPCI OWNER PROVIDED, CONTRACTOR INSTALLED

OPOI OWNER PROVIDED, OWER INSTALLED

PL PLASTER

PLAM PLASTIC LAMINATE

PNL PANEL

PT PAINT

R RE-USED / RELOCATED

REC RECESSED

RM ROOM

ROW RIGHT OF WAY

SIM SIMILAR

SQ. SQUARE

ST STEEL

STD STANDARD

SUSP SUSPENDED

THLD THRESHOLD

T.O. TOP OF

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

VIF VERIFY IN FIELD

WD WOOD

WT WEIGHT

ABBREVIATIONS

STORAGE

ROOM NAME AND NUMBER

G1.1

N/A

1.1 All work noted "N.I.C." or "not in contract" is to be excluded from the construction agreement.

1.2 Data contained in these drawings and specifications must not be used for any purpose other than as a guide in the construction for the referenced project. Any other use or reuse shall be at the sole risk of the Contractor and without liability or legal exposure to the Government. The Contractor must make no claim and waives to the fullest extent permitted by law, any claim or cause of action of any nature aginst the Government, its agents or sub consultants that may arise out of, or in connection with the mis-use of these documents. The Contractor must, to the fullest extent permtted by law, indemnify and hold the Government harmless against all damages, liabilities or costs, including reasonable attorney's fees and defense costs, arising out of or resulting from the use of these documents for any purpose not related to this project.

1.3 All proprietary products, finishes, and equipment noted herein are proposed to be provided by the Contractor. Products specified are in accordance with the requirements established by the design intent drawings provided by the

Contracting Officer. It shall be understood that a proprietary product may be substituted with an equivalent product if said product is determined by the

Contracting Officer and approved to be of equal performance specifications to the basis of design product contained herein.

1.4 All symbols and abbreviations are considered to be construction standards. If any clarification is needed, the contractor shall contact the Contracting Officer before work, manufacturing and/or fabrication commences.

1.5 Do not scale drawings; written dimensions take precedence. Large scale details govern over small scale details

1.6 All building, structural, electrical, plumbing, HVAC, accessibility and shop drawings used in conjunction with the architectural drawings shall be each contractor's specific and exclusive responsibility, to verify all existing conditions and dimensions before manufacturing and/or fabrication of work.

1.7 Project drawings and specifications shall be considered of equal weight and importance. The Contractor is responsible for obtaining clarification from the

Contracting Officer for any questions before proceeding with the work.

1.8 The Contractor may request drawings files for creation of shop drawings. The entire set of source drawings will not be provided. Request only the specific drawing number needed to prepare the shop drawing.

1.9 All construction materials shall be stored within the project space or designated areas as authorized by the Contracting Officer.

1.10 "ALIGN" as used in these documents shall mean to accurately locate finish faces in the same plane and/or to provide new construction adjacent to the existing construction without visible joints or surface irregularities.

1.11 "TYPICAL" or "TYP." as used in these documents shall mean that the conditions or dimensions are the same or representative for similar conditions throughout.

1.12 "SIMILAR” or "SIM." as used in these documents shall mean that the conditions or dimensions are the same or representative for similar conditions throughout.

1.13 “MINIMUM” or “MIN.” as used in these documents shall mean that the condition as built may not vary to a dimension or quantity less than that shown without the approval of the architect/engineer.

1.14 “MAXIMUM” or “MAX.”, as used in these documents shall mean that the condition as built may not vary to a dimension or quantity greater than that shown without the approval of the architect/engineer.

1.15 "+/-" as used in these documents shall mean the dimensions or quantity is slightly adjustable to accommodate actual conditions.

1. DRAWING AND DOCUMENT NOTES

2.1 The Contractor is responsible for examining all contract documents and field conditions, and confirming that work may be constructed as shown before proceeding with construction. If there are any questions, the Contractor is responsible for obtaining a clarification from the Contracting Officer before proceeding with the work.

2.2 The Contractor shall verify all conditions and dimensions at the job site prior to bidding and start of construction. If any discrepancies are found, notify

Contracting Officer in writing for clarification.

2.3 The Contractor shall provide a cost loaded construction schedule, which shall be updated, as noted in the contract documents. The contractor shall coordinate and supervise the work of all trades and is responsible for adherence to all contract documents, timely performance of the work and maintaining the job site in a safe and clean manner.

2.4 The Contractor shall provide and keep an updated record set of drawings and specifications for as-built documentation.

2.5 The Contractor shall provide for and be solely responsible for the provision of all required or necessary blocking, backing, bracing, framing hangers and/or other support for all construction, fixtures, equipment, cabinetry, furnishings and all items requiring the same.

2.6 The Contractor is to maintain the integrity of all building systems (structural, mechanical, plumbing, electrical and fire protection) that are uncovered during the demolition and are not otherwise addressed in the construction documents.

2. CONTRACTOR'S RESPONSIBILITIES

3.1 All required means of egress shall be maintained during construction; and in their final construction, all required exit doors shall be operable from inside spaces without the use of a key, special effort or knowledge, and shall be provided with illuminated “exit” signs as required by applicable codes and ordinances.

3.2 The Contractor shall erect and maintain temporary bracing, barricades, signs and other measures as necessary to protect the public, workers and other persons and adjoining property from damage from demolition and construction work in accordance with applicable codes and regulations.

3. HEALTH AND SAFETY NOTES

2. CONTRACTOR'S RESPONSIBILITIES (CONTINUED)

2.7 It is the responsibility of the Contractor to field verify existing conditions and dimensions prior to fabrication and construction. Any discrepancies shall be called to the attention of the Architect and/ or Engineer.

2.8 It is the responsibility of the Contractor to ensure the continuity and integrity of sound and fire rated assemblies as indicated.

2.9 Each installer shall examine substrate and/or conditions under which the work will be installed and report to the contractor in writing any conditions detrimental to the proper and timely execution of that installer's work. Do not proceed until unsatisfactory conditions are corrected. Installation shall signify acceptance of the substrate and/or conditions.

2.10 The Contractor shall be responsible for leaving all finished surfaces clean at the completion of the work, and shall remove all excess material and debris from the job site during construction.

2.11 The Contractor is to provide noise and dust abatement as required to prevent disturbance and nuisance to adjacent premises and surrounding areas.

Demolition and removal work shall be done in a manner which will minimize the spread of dust and flying particles. Removed materials and debris shall become the property of the contractor and shall be disposed of in a legal manner. The operational procedure shall be determined by and are the responsibility of the contractor.

2.12 The Contractor shall provide a waste management plan to comply with the following, or meet requirements of local ordinance, whichever is more stringent

- Recycle or salvage 50% of the non-hazardous construction and demolition waste by diverting material from disposal through efficient use of recycling, reuse or salvage for future use or sale.

- Documentation shall be provided which includes identification of the waste management agency and verification that the percentage of the demolition and construction waste materials divert from landfill complies with 2016 Ed.

CalGreen code, section 5.408.1.

2.13 The Contractor shall protect all existing building elements and furnishings adjacent to the work, and shall replace, patch or repair to like new condition any building element damaged as a result of his work in the process of construction or demolition at no additional cost to the government.

2.14 The Contractor shall notify 60 CES/CEIE Water Manager (707 424-3587) in advance if releasing water outside of the building.

ABBREVIATIONS, SYMBOLS & GENERAL NOTES

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DRAWING NUMBER

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text APPROVED (Commander)

AutoCAD SHX Text RECOMMENDED (Base Engineer)

AutoCAD SHX Text SUBMITTED (Chief Engineer)

AutoCAD SHX Text

AIR MOBILITY COMMAND

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text

TRAVIS AIR FORCE BASE

AutoCAD SHX Text

SEQ NO.

AutoCAD SHX Text

SHEET NUMBER:%%U

AutoCAD SHX Text

IF SHEET IS LESS THAN 22" X 34" IT IS A REDUCED PRINT - SCALE ACCORDINGLY

AutoCAD SHX Text

BUILDING - B54 SERVER ROOM

AutoCAD SHX Text

2020 E. FIRST STREET, SUITE 525 SANTA ANA, CALIFORNIA 92705

AutoCAD SHX Text

(714) 689-0298 www.developmentone.net

AutoCAD SHX Text

2016 COPYRIGHT DEVELOPMENT ONE, INC.

AutoCAD SHX Text THIS DRAWING AND ITS CONTENTS ARE INSTRUMENTS OF SERVICE AND ARE THE COPYRIGHTED PROPERTY OF DEVELOPMENT ONE, INC. THE USE IS EXPRESSLY INTENDED FOR THE PROJECT NOTED BELOW AND MAY NOT BE REUSED OR REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN PERMISSION OF ITS PRINCIPALS.

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

65%%% DESIGN SUBMITTAL

AutoCAD SHX Text 02/15/19

AutoCAD SHX Text A

AutoCAD SHX Text

35%%% PRELIMINARY DESIGN SUBMITTAL

AutoCAD SHX Text 06/06/19

AutoCAD SHX Text C

AutoCAD SHX Text

FINAL DESIGN DOCUMENTS

AutoCAD SHX Text 09/30/19

AutoCAD SHX Text

DM

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text 01-23-2019

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

XDAT 15-1124

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text J

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text Renewal Date

AutoCAD SHX Text C23740

AutoCAD SHX Text Signature

N/A

GENERAL NOTES

G1.2

GENERAL NOTES

3. HEALTH AND SAFETY NOTES (CONTINUED)

3.3 Safety and Health Programs: The contractor shall have written safety and health programs in compliance with 29 CFR Parts 1910 and 1926. The contractor shall submit for approval copies of the project safety and health programs as applicable to the work scope including but not necessarily limited to the following:

a. Occupational Noise Exposure

b. Fall Protection

c. Personal Protective Equipment

d. Control of Hazardous Energy

e. Electrical Safety Related Work Practices

f. Lead

g. Asbestos

h. Respirator Protection

i. Confined Spaces

3.4 Compliance with Regulations: The work including contact with or handling of hazardous materials, disturbance or dismantling of structures containing hazardous materials, and disposal of hazardous materials, shall comply with the applicable requirements of 29 CFR Parts 1910 and 1926, and 40 CFR Parts 61, 261, 761 and 763. Work shall additionally comply with applicable state and local safety and health regulations. In case of a conflict between applicable regulations, the more stringent requirements shall apply.

3.5 The Contractor shall assume full responsibility and liability for compliance with all applicable codes, standards, and regulations pertaining to the health and safety of personnel and the general public, during execution of the work.

3.6 Contractor’s Safety Plan: In addition, to specific safety and health programs applicable to the project, contractor shall submit firm’s general safety plan listing emergency procedures.

3.7 Protection of Personnel: The Contractor shall take all necessary precautions to prevent injury to the public, occupants or damage to the property of others. The public and occupants includes all persons not employed by the Contractor or sub-contractor.

a. Wherever practical, the work area shall be fenced, barricaded or blocked off from the public or occupants to prevent unauthorized entry. If exits are to be blocked to prevent evacuation of the building occupants, alternative egress routes are to be provided, the Authority Having Jurisdiction (AHJ) in Travis Air Force Base, (Fire Protection Engineers, Safety and

Environmental Branch), shall review, authorize and approve or disapprove prior to the Work commencing.

b. Store, position and use equipment, tools, materials, scraps and trash in a manner that does not present a hazard to the public or occupants by accidental shifting, ignition or other hazardous activity.

c. Store and transport refuse and debris in a manner to prevent unsafe or unhealthy conditions for the public or occupants. Cover refuse containers and remove refuse on a frequent regular basis acceptable to the

Contracting Officer or the Contracting Officer’s authorized representative. Use tarpaulins or other means to prevent loose transported materials from dropping from trucks.

4. PROJECT SPECIFIC NOTES

4.1 The contractor shall limit the number of utility or alarm system shut downs to the minimum extent possible to complete the work. Contracting Officer must be notified 72 hours prior to any system shut-downs to allow for coordination with base security and opertations.

4.2 The Contractor shall install all manufactured items, materials and equipment in strict accordance with the manufacturers specifications.

4.3 Security clearances are required of all contractor staff and workers to be allowed on the jobsite. Coordination and timely scheduling of contractor employee and subcontractor security clearances is the full responsibility of the contractor and is required for the successful performance of this project.

4.4 Locations of manual activation and shut-off switches must be approved by the contracting officer prior to installation.

4.5 Provide fire stopping system at penetrations through rated partitions and walls.

Systems shall be compatible with wall construction.

4.6 Dissimilar metal materials shall be isolated with non-metal separator.

6.1 Asbestos Containing Materials (ACM) & Lead-Based Paint (LBP) are present in the project area. Refer to 'Asbestos & Lead Survey' by Ninyo & Moore, dated April 5, 2019, for detailed information regarding amount & location of known ACM/LBP.

6.2 Prior to renovation activities which would disturb the identified ACM, a licensed abatement removal contractor shall remove the ACM. The abatement contractor must maintain current licenses as required by state and local jurisdictions for the removal, transporting, and disposal of ACM or any other regulated activities.

6.3 The Contractor shall provide an asbestos abatement plan for contracting officer hygienist review. Allow 10 days for contracting officer to review. Prior to starting work, contractor must receive approval of submitted plan.

6.4 The Contractor shall abate and dispose of all hazardous materials found and/ or disturbed during demolition and/or construction, including but not limited to ACM, in accordance with all applicable regulations.

6.5 The contracting officer shall provide 3rd party air testing / monitoring during ACM abatement work to verify other portions of the building will not become contaminated. The

Contractor shall coordinate performance of work with 3rd party air testing / monitoring throughout project.

6.6 ACM abatement scope is limited to the removal of all existing such materials that are, or will become exposed due to demolition or construction activities as shown within the project documents.

6.7 Applicable laws and regulations shall be followed, including those provisions requiring notification to regulatory agencies, building occupants, renovation contractors, and workers of the presence of asbestos.

6.8 An in-place Operations & Maintenance program shall be prepared by the abatement contractor for any remaining intact ACM after renovations.

6.9 Lead - Containing Material Survey is governed by the Environmental Protection Agency

(EPA). The EPA stipulates what concentrations of lead in non-volatile components of surface coatings or materials indicate whether a material is considered to be lead-containing. The EPA stipulates that paint containing an amount equal to or in excess of 1 milligram per square centimeter (1.0 mg/ cm²), or more than half of one percent (0.5%) by weight (or milligrams per kilogram [mg/kg]), constitute a lead-based paint (LBP).

Coatings with any detectable amount of reported lead would be considered lead-containing paint (LCP), dated April 5, 2019.

6. ASBESTOS CONTAINING MATERIALS (ACM) & LEAD BASED PAINT (LBP) NOTES

5.1 All interior finishes (wall coverings, etc.) shall comply with the criteria of the IBC

2018 for flame spread and smoke development ratings and shall meet interior finish requirements.

5.2 All equipment and wiring (communication, power, fire alarm, etc) installed in a plenum shall be listed for installation in such areas.

5.3 All flexible air ducts installed in a plenum shall meet the requirements of NFPA 90A, 2-3.2 in construction and installation.

5.4 All special locking hardware (cipher, keycard, etc.) must comply with NFPA 101,

7.2.1.6 and be operable with no more than one releasing operation from the direction of egress.

5.5 Smoking shall be prohibited except in approved areas which complies with Section

3304 of 2016 California Fire Code.

5.6 Combustible debris, rubbish, and waste shall not be accumulated within buildings, and shall be removed from buildings at the end of each shift of work, and properly disposed of per Section 3304.2 of the 2016 California Fire Code.

5.7 Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in a listed disposal container.

5.8 Combustible debris, rubbish and waste material shall not be disposed of by burning on the site.

5.9 Impairments to any fire protection system shall be in accordance with 2016

California Fire Code 901.

5.10 Coverings placed on or over fire protection devices to protect them from damage during construction processes shall be immediately removed upon completion of the construction processes in the room or area in which the devices are installed.

5.11 The fire sprinkler and fire alarm systems affected by the alternation work of this project shall be designed, installed and tested in accordance with NFPA 13, NFPA

70 and NFPA 72. The contractor shall submit fire sprinkler and fire alarm shop drawings to the Contracting Officer Representative for review and approval prior to ordering systems or fixtures.

5.12 The work includes design and installation of a Clean Agent Fire Extinguishing system.

The installation shall be made in accordance with the requirements of NFPA 2001 2018.

5.13 Design shall be by a NICET Level IV Technician or a Registered Fire Protection Engineer.

Installation shall be performed by a certified Clean Agent Fire Extinguishing system contractor or a specialist who is experienced in the design and installation of a Clean

Agent Fire Extinguishing systems (minimum 3 years). Provide system Flow Calculations and Design Concentration requirements.

5.14 All System components shall be designed and provided in accordance with NFPA 2001, 2018.

5.15 Manufacturer's data shall be provided and annotated to show the specific model, type and size of each item.

5.16 Shop Drawings: Submit detailed shop drawings, in accordance with NFPA 2001 and section 21 22 00. 00 40, to the Contracting Officer for review and approval. Information shall include but not be limited to the following:

A. Layout indicating details, plan view, elevations and sections of the system piping.

Indicate the location of Clean Agent discharge nozzle heads and piping in relation to the ceiling layout, showing pipe lengths and sizes.

B. Detailed riser diagram showing schematic of systems supply, supply connection, devices, valves, pipe and fittings.

5. FIRE PROTECTION NOTES

C. The signature and seal of a registered Professional Fire Protection Engineer, registered Professional Engineer with a minimum of two years fire protection design experience, or a NICET Level IV Technician.

5.17 Final Inspection and Testing:

A. The final test shall be witnessed by the TAFB fire protection engineer. The Contractor and an authorized representative from each supplier of equipment shall be in attendance at the final test.

B. Provide all equipment, services and labor to properly perform all required tests.

5.18 Submit as-built drawings to the Contracting Officer upon completion of the project. These drawings shall indicate changes from the original layout, marked in red.

5. FIRE PROTECTION NOTES - CONTINUED

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DRAWING NUMBER

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text APPROVED (Commander)

AutoCAD SHX Text RECOMMENDED (Base Engineer)

AutoCAD SHX Text SUBMITTED (Chief Engineer)

AutoCAD SHX Text

AIR MOBILITY COMMAND

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text

TRAVIS AIR FORCE BASE

AutoCAD SHX Text

SEQ NO.

AutoCAD SHX Text

SHEET NUMBER:%%U

AutoCAD SHX Text

IF SHEET IS LESS THAN 22" X 34" IT IS A REDUCED PRINT - SCALE ACCORDINGLY

AutoCAD SHX Text

BUILDING - B54 SERVER ROOM

AutoCAD SHX Text

2020 E. FIRST STREET, SUITE 525 SANTA ANA, CALIFORNIA 92705

AutoCAD SHX Text

(714) 689-0298 www.developmentone.net

AutoCAD SHX Text

2016 COPYRIGHT DEVELOPMENT ONE, INC.

AutoCAD SHX Text THIS DRAWING AND ITS CONTENTS ARE INSTRUMENTS OF SERVICE AND ARE THE COPYRIGHTED PROPERTY OF DEVELOPMENT ONE, INC. THE USE IS EXPRESSLY INTENDED FOR THE PROJECT NOTED BELOW AND MAY NOT BE REUSED OR REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN PERMISSION OF ITS PRINCIPALS.

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

65%%% DESIGN SUBMITTAL

AutoCAD SHX Text 02/15/19

AutoCAD SHX Text A

AutoCAD SHX Text

35%%% PRELIMINARY DESIGN SUBMITTAL

AutoCAD SHX Text 06/06/19

AutoCAD SHX Text C

AutoCAD SHX Text

FINAL DESIGN DOCUMENTS

AutoCAD SHX Text 09/30/19

AutoCAD SHX Text

DM

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text 01-23-2019

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

XDAT 15-1124

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text J

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text Renewal Date

AutoCAD SHX Text C23740

AutoCAD SHX Text Signature

KITCHENETTE

RESTROOM

SWITCH BOARD OPERATIONS

TELEPHONE SWITCH ROOM

BATTERY ROOM

TELPHONE VAULT

STORAGE ROOM

POWER ROOM

BOILER ROOM

TRAINING AREA

BREAK ROOM

LOBBY

RESTROOM

UNISEX

DIRECTORY CLERK

MAIN DISTRIBUTION FRAME

OPERATOR SUPERVISOR

MAIN DISTRIBUTION FRAME2

26'-0"15'-9" 25'-7"

71'-8"

EQ. EQ.

12"

4'-4"

28'-9"

TYPICAL AT

PERIMETER

F.O.M

F.O.M

F O

M

F O

M

F O

M

F O

M

F O

M

A1.0 A3.0

A1.0 A3.0

A1.0 A3.0

A1.0 A3.0

A1.0 A3.0

A1.0 A3.0

SHEET NOTES

1. REFER TO G1.2, SECTION 6 FOR ACM AND LEAD

BASED PAINT NOTES.

1A. 12" VINYL FLOOR TILE WITHIN TELEPHONE

SWITCH ROOM AND BATTERY ROOM

CONTAIN ACM. DO NOT DISTURB.

2. CONTRACTOR SHALL ENLIST QUALIFIED

PERSONNEL TO CONDUCT A PRESSURIZED FAN

BLOWER TEST IN ACCORDANCE WITH NFPA

2001, ANNEX C REQUIREMENTS FOR THE

INSTALLATION OF A CLEAN AGENT FIRE

EXTINGUISHING SYSTEM.

3. SEAL ALL PENETRATIONS AND OPENINGS IN

THE PERIMETER OF THE CLEAN AGENT

SUPPRESSION AREA, INCLUDING ALL WALLS,

CEILING AND FLOOR OPENINGS. SEE DETAIL

5/A2.0. THIS INCLUDES, BUT IS NOT LIMITED TO:

A. HVAC DUCTS

B. PIPES

C. CONDUITS

D. LOW - VOLTAGE WIRING

E. POWER RECEPTACLES

F. SWITCHES

G. THERMOSTATS

4. ALL DOORS LOCATED AT CLEAN AGENT

PERIMETER ENVELOPE MUST NORMALLY BE IN

THE CLOSED POSITION WITH A WORKING

LATCH SUCH THAT THE ROOM PRESSURIZATION

CANNOT OPEN THE DOOR.

EXISTING CMU WALLS TO REMAIN

(E) DOOR TO REMAIN

LEGEND

KEYNOTES

AREA OUTSIDE OF PROJECT SCOPE

RETROFIT (E) EXTERIOR DOOR WITH THE FOLLOWING:

1. DROP BOTTOM SEAL. SEE DETAIL 4/A2.0

NOVEC 1230 FIRE SYSTEM AGENT CONTAINER.

REFER TO THE FIRE PROTECTION PLAN FOR

ADDITIONAL INFORMATION

RETROFIT (E) INTERIOR DOOR WITH THE FOLLOWING:

1. OVERHEAD DOOR CLOSER. SEE DETAIL 1/A2.0

2. GASKETING AT DOOR HEAD, JAMBS, AND THRESHOLD

SEE DETAILS 1/A2.0, 2/A2.0, 3/A2.0

RETROFIT (E) INTERIOR FLOOR - MOUNTED ACCESS

PANELS WITH SMOKE/FIRE RATED GASKETS - BASIS OF

DESIGN IS PEMKO AM44

SEAL PERIMETER OF CLEAN AGENT SUPPRESSION AREA

SEE SHEET NOTE 3 FOR ADDITIONAL INFORMATION

(ETR) SERVER CABINETS

(ETR) HVAC DUCTWORK ENTRY POINT - LOCATED AT

FLOOR LEVEL - PROVIDE SMOKE/ FIRE DAMPER

(ETR) EPO - EMERGENCY POWER OFF

(N) MANUAL RELEASE CLEAN AGENT AND ABORT CLEAN

AGENT EMERGENCY SHUTOFF

(N) FIRE SUPPRESSION CONTROL PANEL AND

KEY MAINTENANCE SWITCH

CLEAN AGENT FIRE SUPPRESSION STROBE / ALARM.

REFER TO THE FIRE PROTECTION PLAN FOR

ADDITIONAL INFORMATION.

(ETR) BATTERY STORAGE

(ETR) ELECTRICAL EQUIPMENT

(ETR) STORAGE LOCKERS

(ETR) METAL DOOR AND FRAME CONTAINS LEAD

BASED PAINT - SEE G1.2, SECTION 6 FOR

ABATEMENT NOTES

(ETR) HVAC UNIT - INSTALL SMOKE/ FIRE

DAMPERS SEE MECHANICAL

(ETR) WALL MOUNTED HUMIDIFIER SYSTEM - SEE

MECHANICAL

SCALE:

1/8" = 1'-0"

FLOOR PLAN

G1.0A1.0

Architecture | Project Management

1/8" = 1'-0"

FLOOR PLAN

A1.0

8 6 4 2 0 84 16

TRUE NORTH

PROJECT NORTH

AutoCAD SHX Text

FS

AutoCAD SHX Text

FS

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DRAWING NUMBER

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text APPROVED (Commander)

AutoCAD SHX Text RECOMMENDED (Base Engineer)

AutoCAD SHX Text SUBMITTED (Chief Engineer)

AutoCAD SHX Text

AIR MOBILITY COMMAND

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text

TRAVIS AIR FORCE BASE

AutoCAD SHX Text

SEQ NO.

AutoCAD SHX Text

SHEET NUMBER:%%U

AutoCAD SHX Text

IF SHEET IS LESS THAN 22" X 34" IT IS A REDUCED PRINT - SCALE ACCORDINGLY

AutoCAD SHX Text

BUILDING - B54 SERVER ROOM

AutoCAD SHX Text

2020 E. FIRST STREET, SUITE 525 SANTA ANA, CALIFORNIA 92705

AutoCAD SHX Text

(714) 689-0298 www.developmentone.net

AutoCAD SHX Text

2016 COPYRIGHT DEVELOPMENT ONE, INC.

AutoCAD SHX Text THIS DRAWING AND ITS CONTENTS ARE INSTRUMENTS OF SERVICE AND ARE THE COPYRIGHTED PROPERTY OF DEVELOPMENT ONE, INC. THE USE IS EXPRESSLY INTENDED FOR THE PROJECT NOTED BELOW AND MAY NOT BE REUSED OR REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN PERMISSION OF ITS PRINCIPALS.

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

65%%% DESIGN SUBMITTAL

AutoCAD SHX Text 02/15/19

AutoCAD SHX Text A

AutoCAD SHX Text

35%%% PRELIMINARY DESIGN SUBMITTAL

AutoCAD SHX Text 06/06/19

AutoCAD SHX Text C

AutoCAD SHX Text

FINAL DESIGN DOCUMENTS

AutoCAD SHX Text 09/30/19

AutoCAD SHX Text

DM

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text 01-23-2019

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

XDAT 15-1124

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text J

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text Renewal Date

AutoCAD SHX Text C23740

AutoCAD SHX Text Signature

KITCHENETTE

RESTROOM

SWITCH BOARD OPERATIONS

TELEPHONE SWITCH ROOM

BATTERY ROOM

TELPHONE VAULT

STORAGE ROOM

POWER ROOM

BOILER ROOM

TRAINING AREA

BREAK ROOM

LOBBY

RESTROOM

UNISEX

DIRECTORY CLERK

MAIN DISTRIBUTION FRAME

OPERATOR SUPERVISOR

MAIN DISTRIBUTION FRAME

10'-11"

10'-11"

10'-11"

26'-0"15'-9" 25'-7"

71'-8"

77 7

4'-4"

A1.1 A3.0

A1.1 A3.0

A1.1 A3.0

A1.1 A3.0

A1.1 A3.0

A1.1 A3.0

TYP. AT

CEILING

A1.1 A3.0

E Q

E

Q

SHEET NOTES

1. CONTRACTOR SHALL ENLIST A QUALIFIED

PERSONNEL TO CONDUCT A PRESSURIZED FAN

BLOWER TEST IN ACCORDANCE WITH NFPA

2001, ANNEX C REQUIREMENTS FOR THE

INSTALLATION OF A CLEAN AGENT FIRE

EXTINGUISHING SYSTEM.

2. SEAL ALL PENETRATIONS AND OPENINGS IN THE

PERIMETER OF THE CLEAN AGENT

SUPPRESSION AREA, INCLUDING ALL WALLS,

CEILING AND FLOOR OPENINGS. SEE DETAIL

5/A2.0. THIS INCLUDES, BUT IS NOT LIMITED TO:

A. HVAC DUCTS

B. PIPES

C. CONDUITS

D. LOW - VOLTAGE WIRING

E. POWER RECEPTACLES

F. SWITCHES

G. THERMOSTATS

3. EXISTING FIRE SUPPRESSION SPRINKLER

SYSTEM TO REMAIN IN PLACE. CLEAN AGENT

SYSTEM TO BE SUPPLEMENTAL PER THE UFC

3-600-01, SECTION 4-11.5.1. REFER TO THE FIRE

PROTECTION PLAN 1/F1.0

LEGEND

KEYNOTES

(ETR) FIRE SPRINKLER HEAD

SEAL ALL PENETRATIONS AT EXPOSED CEILING/ ROOF

ASSEMBLY OF CLEAN AGENT SUPPRESSION AREA.

SEE SHEET NOTE 2.

PREPARE (E) OPENING FOR SMOKE/ FIRE DAMPERS

SEE MECHANICAL DRAWINGS

PROVIDE SEALANT AT (E) DUCT PENETRATION PER

DETAIL 5/A2.0

AREA OUTSIDE OF PROJECT SCOPE

(ETR) PENDANT MOUNTED 2' X 4' LIGHT FIXTURE

(ETR) CONCRETE ROOF STRUCTURE TO REMAIN

PROVIDE OPENING IN (E) CONCRETE WALL FOR (N)

EXHAUST VENT AND SMOKE/ FIRE DAMPER. REFER

TO MECHANICAL DRAWINGS. TOP OF OPENING SHALL

BE 9'-6" A.F.F. MAX. AND CENTERED BETWEEN ROOF

JOISTS. CORE THE CORNERS, AND DO NOT OVER

CUT THE OPENING.

X'-X"

(ETR) CEILING HEIGHT - CEILING HEIGHT IS

TAKEN FROM THE BOTTOM OF THE CONCRETE

RIB AT THE RIDGELINE.

RETROFIT (ETR) HVAC GRILL WITH THE FOLLOWING:

1. GASKETING AT PERIMETER EDGES

2. SMOKE/ FIRE DAMPERS

(ETR) CABLE TRAY ABOVE - SEAL PENETRATION PER

DETAIL 5/A2.0

(ETR) HVAC EQUIPMENT SEE MECHANICAL DRAWINGS

(ETR) EXHAUST DUCT - PROVIDE PERIMETER SEALANT

AROUND EXHAUST DUCT. SEE DETAIL 5/A2.0

SCALE:

1/8" = 1'-0"

REFLECTED CEILING PLAN

G1.0 A1.1

Architecture | Project Management

1/8" = 1'-0"

REFLECTED CEILING PLAN

A1.1

8 6 4 2 0 84 16

TRUE NORTH

PROJECT NORTH

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DRAWING NUMBER

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text APPROVED (Commander)

AutoCAD SHX Text RECOMMENDED (Base Engineer)

AutoCAD SHX Text SUBMITTED (Chief Engineer)

AutoCAD SHX Text

AIR MOBILITY COMMAND

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text

TRAVIS AIR FORCE BASE

AutoCAD SHX Text

SEQ NO.

AutoCAD SHX Text

SHEET NUMBER:%%U

AutoCAD SHX Text

IF SHEET IS LESS THAN 22" X 34" IT IS A REDUCED PRINT - SCALE ACCORDINGLY

AutoCAD SHX Text

BUILDING - B54 SERVER ROOM

AutoCAD SHX Text

2020 E. FIRST STREET, SUITE 525 SANTA ANA, CALIFORNIA 92705

AutoCAD SHX Text

(714) 689-0298 www.developmentone.net

AutoCAD SHX Text

2016 COPYRIGHT DEVELOPMENT ONE, INC.

AutoCAD SHX Text THIS DRAWING AND ITS CONTENTS ARE INSTRUMENTS OF SERVICE AND ARE THE COPYRIGHTED PROPERTY OF DEVELOPMENT ONE, INC. THE USE IS EXPRESSLY INTENDED FOR THE PROJECT NOTED BELOW AND MAY NOT BE REUSED OR REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN PERMISSION OF ITS PRINCIPALS.

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

65%%% DESIGN SUBMITTAL

AutoCAD SHX Text 02/15/19

AutoCAD SHX Text A

AutoCAD SHX Text

35%%% PRELIMINARY DESIGN SUBMITTAL

AutoCAD SHX Text 06/06/19

AutoCAD SHX Text C

AutoCAD SHX Text

FINAL DESIGN DOCUMENTS

AutoCAD SHX Text 09/30/19

AutoCAD SHX Text

DM

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text 01-23-2019

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

XDAT 15-1124

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text J

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text Renewal Date

AutoCAD SHX Text C23740

AutoCAD SHX Text Signature

SCALE:EXTERIOR THRESHOLD

6" = 1'-0"

A1.0 A2.0

(ETR) HOLLOW METAL FRAME

(ETR) HOLLOW METAL DOOR

(ETR) CONCRETE SLAB

(ETR) DOOR THRESHOLD

AUTOMATIC DOOR BOTTOM -

BASIS OF DESIGN - PEMKO

4131_PKL OR APPROVED

EQUAL

(ETR) HOLLOW

METAL FRAME

(ETR) WOOD DOOR

SCALE:

6" = 1'-0"

A1.0 A2.0

(ETR) WALL ASSEMBLY

PERIMETER DOOR GASKETING

- BASIS OF DESIGN - PEMKO

297_V STANDARD OR

APPROVED EQUAL

FIRE/ SMOKE GASKETING -

BASIS OF DESIGN - PEMKO

S88 OR APPROVED EQUAL

(ETR) WOOD DOOR

SCALE:

6" = 1'-0"

A1.0 A2.0INTERIOR DOOR HEAD

SCALE:

6" = 1'-0"

A1.0 A2.0

(ETR) WOOD DOOR

(ETR) WALL ASSEMBLY

(ETR) HOLLOW METAL

DOOR FRAME

PERIMETER DOOR

GASKETING - BASIS OF

DESIGN - PEMKO 297_V

STANDARD OR APPROVED

EQUAL

INTERIOR THRESHOLD

INTERIOR DOOR JAMB

(ETR) HARDSCAPE

(ETR) DOOR

THRESHOLD

AUTOMATIC DOOR

BOTTOM - BASIS OF

DESIGN - PEMKO

4131_PKL OR

APPROVED EQUAL

(ETR) CONCRETE SLAB

DOOR CLOSER - BASIS OF

DESIGN - YALE 3000 SERIES

OR APPROVED EQUAL

FIRE/ SMOKE GASKETING -

BASIS OF DESIGN - PEMKO

S88 OR APPROVED EQUAL

CONTINUOUS SEALANT A

DOOR FRAME AND WALL, TYP.

(ETR) HOLLOW METAL FRAME

CONTINUOUS SEALANT

A DOOR FRAME AND

WALL, TYP.

ELECTRICAL BOXES -

SWITCHES / OUTLETS,

ETC.

SCALE:

1-1/2" = 1'-0"

A1.0 A2.0ENVELOPE PERIMETER SEAL

CABLE TRAY OR

OTHER LARGE

PENETRATION

NEEDING PERIODIC

RECONFIGURATION OF

CABLES

PIPE OR CABLE

PENETRATION

SLAB ON GRADE

FIRE SEALANT

REMOVABLE /

REPOSITIONABLE

FIRESTOP PILLOWS

FIRE TAPE AND

SEALANT OR PUTTY

AUTOMATIC AIR

DAMPER PER

MECHANICAL

DRAWINGS

DUCT PENETRATION

FIRE TAPE AND

SEALANT

FOR GAPS OVER 2"

INSTALL 5/8" TYPE 'X'

GYPSUM BOARD

FOR GAPS OVER 2"

INSTALL 5/8" TYPE 'X'

GYPSUM BOARD OR

FIRESTOP BOARD

FIRE TAPE AND

SEALANT

TOP OF WALL GAPS

GREATER THAN 2"

TOP OF WALL GAPS

2" OR LESS

FIRE TAPE AND

SEALANT

ROOF/ CEILING

ASSEMBLY

CLEAN AGENT

ENVELOPE WALL

(INTERIOR OR

EXTERIOR)

CLEAN AGENT

NON-TREATMENT SIDE

CLEAN AGENT

TREATMENT SIDE

NOTE:

DETAIL DIAGRAMS TYPICAL AIR LEAKAGE SOURCES / SOLUTIONS

OCCURING AT THE CLEAN AGENT TREATMENT ENVELOPE.

A1.1

FIRE TAPE AND

SEALANT

SCALE:EXTERIOR THRESHOLD

6" = 1'-0"

A1.0 A2.0

(ETR) HOLLOW METAL FRAME

(ETR) HOLLOW METAL DOOR

(ETR) CONCRETE SLAB

(ETR) DOOR THRESHOLD

AUTOMATIC DOOR BOTTOM -

BASIS OF DESIGN - PEMKO

4131_PKL OR APPROVED

EQUAL

(ETR) HOLLOW

METAL FRAME

(ETR) WOOD DOOR

SCALE:

6" = 1'-0"

A1.0 A2.0

(ETR) WALL ASSEMBLY

PERIMETER DOOR GASKETING

- BASIS OF DESIGN - PEMKO

297_V STANDARD OR

APPROVED EQUAL

FIRE/ SMOKE GASKETING -

BASIS OF DESIGN - PEMKO

S88 OR APPROVED EQUAL

(ETR) WOOD DOOR

SCALE:

6" = 1'-0"

A1.0 A2.0INTERIOR DOOR HEAD

SCALE:

6" = 1'-0"

A1.0 A2.0

(ETR) WOOD DOOR

(ETR) WALL ASSEMBLY

(ETR) HOLLOW METAL

DOOR FRAME

PERIMETER DOOR

GASKETING - BASIS OF

DESIGN - PEMKO 297_V

STANDARD OR APPROVED

EQUAL

INTERIOR THRESHOLD

INTERIOR DOOR JAMB

(ETR) HARDSCAPE

(ETR) DOOR

THRESHOLD

AUTOMATIC DOOR

BOTTOM - BASIS OF

DESIGN - PEMKO

4131_PKL OR

APPROVED EQUAL

(ETR) CONCRETE SLAB

DOOR CLOSER - BASIS OF

DESIGN - YALE 3000 SERIES

OR APPROVED EQUAL

FIRE/ SMOKE GASKETING -

BASIS OF DESIGN - PEMKO

S88 OR APPROVED EQUAL

CONTINUOUS SEALANT A

DOOR FRAME AND WALL, TYP.

(ETR) HOLLOW METAL FRAME

CONTINUOUS SEALANT

A DOOR FRAME AND

WALL, TYP.

Architecture | Project Management

A2.0

DETAILS

6AS NOTED

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

PROJECT NUMBER

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DRAWING NUMBER

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text APPROVED (Commander)

AutoCAD SHX Text RECOMMENDED (Base Engineer)

AutoCAD SHX Text SUBMITTED (Chief Engineer)

AutoCAD SHX Text

AIR MOBILITY COMMAND

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text

TRAVIS AIR FORCE BASE

AutoCAD SHX Text

SEQ NO.

AutoCAD SHX Text

SHEET NUMBER:%%U

AutoCAD SHX Text

IF SHEET IS LESS THAN 22" X 34" IT IS A REDUCED PRINT - SCALE ACCORDINGLY

AutoCAD SHX Text

BUILDING - B54 SERVER ROOM

AutoCAD SHX Text

2020 E. FIRST STREET, SUITE 525 SANTA ANA, CALIFORNIA 92705

AutoCAD SHX Text

(714) 689-0298 www.developmentone.net

AutoCAD SHX Text

2016 COPYRIGHT DEVELOPMENT ONE, INC.

AutoCAD SHX Text THIS DRAWING AND ITS CONTENTS ARE INSTRUMENTS OF SERVICE AND ARE THE COPYRIGHTED PROPERTY OF DEVELOPMENT ONE, INC. THE USE IS EXPRESSLY INTENDED FOR THE PROJECT NOTED BELOW AND MAY NOT BE REUSED OR REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN PERMISSION OF ITS PRINCIPALS.

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

65%%% DESIGN SUBMITTAL

AutoCAD SHX Text 02/15/19

AutoCAD SHX Text A

AutoCAD SHX Text

35%%% PRELIMINARY DESIGN SUBMITTAL

AutoCAD SHX Text 06/06/19

AutoCAD SHX Text C

AutoCAD SHX Text

FINAL DESIGN DOCUMENTS

AutoCAD SHX Text 09/30/19

AutoCAD SHX Text

DM

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text 01-23-2019

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

BV

AutoCAD SHX Text

XDAT 15-1124

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text J

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text Renewal Date

AutoCAD SHX Text C23740

AutoCAD SHX Text Signature

PHOTO 1

N/A

PHOTO SHEET

A3.0

Architecture | Project Management

PHOTO 2

PHOTO 3

PHOTO 13

PHOTO 4

PHOTO 5

PHOTO 6

PHOTO 7

PHOTO 8

PHOTO 9

PHOTO 10

PHOTO 11

PHOTO 12

(ETR) EPO -

EMERGENCY POWER

OFF

INSTALL SMOKE/ FIRE

DAMPER

INSTALL SMOKE/ FIRE

DAMPER

PROVIDE SEALANT AT

(E) DUCT

PENETRATION PER

DETAIL 5/A2.0

(ETR) CABLE TRAY

SEAL PENETRATION

PER DETAIL 5/A2.0

PROVIDE SMOKE /FIRE

DAMPER

PROVIDE OPENING

WITHIN CONCRETE

WALL FOR THE

INSTALLATION OF

NEW EXHAUST FAN

WITH SMOKE/ FIRE

DAMPER

A1.0 A3.0

A1.0 A3.0

(ETR) DOOR - PROVIDE

DROP BOTTOM SEAL

(ETR) DOOR - PROVIDE

DROP BOTTOM SEAL

(ETR) DOOR - PROVIDE

DOOR CLOSER,

PERIMETER GASKETS,

AND THRESHOLD

SEAL

A1.0 A3.0

A1.0A3.0

A1.0A3.0

A1.0A3.0

A1.1A3.0

A1.1A3.0

A1.1A3.0

A1.1A3.0

A1.1A3.0

A1.1A3.0

PROVIDE SMOKE /FIRE

DAMPER

PROVIDE SMOKE /FIRE

DAMPER

PROVIDE SMOKE /FIRE

DAMPER

A1.1A3.0

PROVIDE SEALANT AT

(E) DUCT

PENETRATION PER

DETAIL 5/A2.0

INSTALL NEW FIRE

SUPPRESSION

CONTROL PANEL -

CONFIRM LOCATIONS

WITH CONTRACTING

OFFICER

INSTALL NEW MANUAL

RELEASE AND

SHUTOFF FOR CLEAN

AGENT - CONFIRM

LOCATIONS WITH

CONTRACTING

OFFICER

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

A…

This is the start of the file's text. The full file is on GovTribe.