This document provides details regarding a forthcoming solicitation for the construction of a parking structure at the St. Cloud VA Medical Center in Minnesota. The Department of Veterans Affairs intends to issue an Invitation for Bid for a firm-fixed-price contract to furnish all labor, materials, tools and equipment required for the project. The work includes general construction such as demolition, site utilities, and architectural, structural, mechanical, plumbing and electrical systems. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses. The estimated value is between $10-20 million and the period of performance is approximately 487 calendar days. All questions must be submitted in writing by July 2020, with award planned for late July or early August 2020.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IRRIGATION SCHEDULE
AREA IRRIGATION TYPE
19,860 SF
SPRAY IRRIGATION
8,525 SF
DRIP IRRIGATION
U G
E
F O
F O
S2
G1
G1
G1
G2
S4
S4
S1
S
S
SS
SS
SS
SS
SS
SS
S
S
S2
SS
SS
SS
S1
E2
E1
F1
S2
S2
S5
S5
S5
S3
INV: 1034.95
S3
INV: 1034.69
P
I N
E
P
IN
E
P
I
PINE 12"
P
I
W
H
E
L
M
B A
S S
W O
O D
" 16
B A
S S
W O
O D
L
O
C
U
S
T
MAPLE 12"
MAPLE 16"
M
A
P
WV
E
L
O
C
U
T
E
M
A
P
MAPLE 18"
MAPLE 22"
H
GAS
GAS
G
A S
G
A S
G
A S
G
A
S
G
A
S
E
E
E
E
E
E
E
E
E
E
F
O
F
O
F
O
F
O
F
O
F
O
F
O
F
O
F O
F O
F
O
F
O
F
O
F
O
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
E
S
P
R
U
C
S
P
R
U
S
P
R
U
P
I
P
I
E
E
M
A
P
E
SAND VOLLEYBALL
COURT
S
S
E
E
H
A
C
K
B
E
R
R
Y
M
A
P
B
U
C
K
T
H
O
R
N
H
O
N
U
C
K
L
E
E
W
A
L
N
U
T
S
P
R
U
A
H
M
A
P
H
A
C
K
B
E
R
S
P
R
U
S
P
R
U
S
P
R
U
T
W
I
N
L
N
U
T
L
N
U
T
J
U
N
I
P
H
A
C
K
B
E
R x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
OHU
OHU
O
H
U
O
H
U
O
H
U
O
H
U
S
P
R
U
S
P
R
U
S
P
R
U
S
P
R
U
P
I
S
P
R
U x x x x x x x
T
P
T P
T P
T
P
T
P
T
P
T
P
T
P
T
P
T P
T
P
T P
T
P
T
P
DN
DN
STAIR # 1
PG-G02
ELEV/LOBBY
PG-G01
STAIR #2
PG-G03
PROPOSED PARKING GARAGE
(TWO LEVELS)
FFE MAIN: 1052.33
FFE LOWER: 1039.00
PROPOSED DETENTION /
INFILTRATION BASIN
TOP OF BANK: 1043.50
EMERGENCY OVERFLOW: 1042.90
100-YR ELEV: 1042.86
BOTTOM OF POND: 1039.00
0 10 20 40
1"= 20'SCALE:
NORTH
1151 Kildaire Farm
Rd.
Suite 120
Raleigh, NC 27511 www.acg-pa.com
(919)858-7420
320-C Midland Pkwy
Summerville, SC 29485 www.cemsengineering.com
(843)875-3637
Project Mgr: Ken Noel (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
VA FORM 08-6231
CONSULTANTS:
SHEET NOTES:
ACG Project Number
# © COPYRIGHT Apogee- CEMS JV, LLC
DRAWING TITLE
APPROVED: CHIEF OF STAFF
APPROVED: HEALTH CARE SYSTEM DIRECTOR
APPROVED: CHIEF OF POLICE
APPROVED: DIRECTOR FMS DATE: APPROVED: SAFETY MANAGER DATE:
APPROVED: GEMS COORDINATOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: SERVICE LINE DIRECTOR
DATE:
DATE:
DATE: APPROVED: INFECTION CONTROL NURSE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE:
CHECKED BY
BUILDING No
LOCATION
DATE:
DATE:
DRAWING NO.
DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
APPROVED: ASSOCIATE HEALTH CARE SYSTEM DIRECTOR
DATE
DATE:
PROJECT:
CONSTRUCT PARKING
STRUCTURE FOR PATIENT
ACCESS
ST. CLOUD VA HEALTHCARE SYSTEM
ST. CLOUD, MINNESOTA
5/27/2020
BID DOCUMENTS
656-344
18-063
N/A
IRRIGATION STRATEGY PLAN
SES EVM
IR101
1. RELOCATE EXISTING IRRIGATION TIMER, LOCATED IN
BUILDING 92, DURING CONSTRUCTION ADJACENT TO THE
EXISTING IRRIGATION VALVE MANHOLE. INSTALL (2) 4X4
PRESSURE TREATED POSTS WITH A 2'X4' PRESSURE TREATED
PLYWOOD FOR MOUNTING RELOCATED IRRIGATION TIMER.
INSTALL A TEMPORARY 120V RECEPTACLE, GFCI PROTECTED
IN WEATHERPROOF BOX TO SERVICE IRRIGATION TIMER.
DocuSign Envelope ID: 1B305C6B-CD38-4A30-B951-ADD7E9D58803
5/28/2020
MISCELLANEOUS SYMBOLS
NORTH ARROW
GRIDLINES
SOIL
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION
REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
C# COLUMN NOTATION
Z# PRECAST/ BRICK SUPPORT
L# LINTEL NOTATION
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PB ## POST-TENSIONED CONCRETE
BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRANULAR FILL
Name
Elevation
WALL PIER NOTATIONWP ##
W ## WALL NOTATION
N
TS ## THICKENED SLAB NOTATION
# KEYED PLAN NOTE
CONCRETE SYMBOLS
POST-TENSION TENDON
ANCHOR DEAD END
LOCATION
POST-TENSION TENDON
ANCHOR JACKING
LOCATION
REBAR
CHANGE OF SLAB
ELEVATION
SLOPING SLAB
CHANGE OF SLAB
THICKNESS
MECHANICAL COUPLER
REBAR SPLICE
LIMIT OF MEMBER OR
SPAN MARK
DIRECTION OF SPAN
OPENING
SELF-EXPANDING
WATERSTOP
CONTROL JOINT LOCATION
IN CONCRETE WALLS
REBAR TERMINATOR
INTENTIONALLY
ROUGHENED
CONSTRUCTION JOINT
TO 1/4" AMPLITUDE
WELDED WIRE
REINFORCING
PVC WATERSTOP
COLUMN CONTINUES
COLUMN TERMINATED
FORM-SAVER
SLAB ON GRADE
MARK
SOG# WALL FOOTING OR
THICKENED SLAB
WF# / TS#
F#
ISOLATED FOOTING
CONNECTORS
HEADED STUD
CONNECTOR SECTION END/ALT VIEW
CAST-IN ANCHOR
ROD
POST-INSTALLED
MECHANICAL ANCHOR
BOLT
POST INSTALLED
ADHESIVE ANCHOR
MASONRY MEMBERS
CMU SECTION
CMU BOND BEAM SECTION
(FULLY GROUTED)
CMU LINTEL SECTION
(FULLY GROUTED)
SINGLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
DOUBLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
PLAN
PLAN
STEEL MEMBERS
W-SHAPE BEAM
SHAPE SECTION PLAN VIEWELEVATION
CHANNEL
ANGLE
DOUBLE ANGLE
HOLLOW STRUCTURAL
SECTION
-RECTANGULAR
LLV LLH
HOLLOW STRUCTURAL
SECTION
-CIRCULAR (PIPE)
OPEN WEB STEEL
JOIST
STEEL SYMBOLS
STEEL DECK
STEEL DECK MARK AND
SPAN DIRECTION
BEAM SPLICE
CONNECTION
BEAM MOMENT
CONNECTION AT COLUMN
BEAM SHEAR CONNECTION
AT COLUMN
BEAM CONTINUOUS OVER
COLUMN
SLAB ON STEEL
DECK
SLAB ON STEEL
DECK
WWR
COLUMN STARTS HERE
HANGER OR POST
HANGER OR POST
BELOW FLOOR
SLAB-ON-DECK MARK AND
SPAN DIRECTION
OR
D#
S#
C# COLUMN MARK
COLD-FORMED STEEL SYMBOLS
CF TRACK
CF STUD/JOIST/RAFTER
BEARING WALL
(BELOW)
SCREW
600 S 162 - 54
MEMBER DEPTH:
(EXAMPLE: 6" = 600 X 1/100
INCHES)
ALL MEMBER DEPTHS ARE TAKEN
IN 1/100 INCHES. FOR ALL "T"
SECTIONS MEMBER DEPTH IS
THE INSIDE TO INSIDE
DIMENSION.
STYLE:
(EXAMPLE: STUD OR JOIST SECTION = S)
THE FOUR ALPHA CHARACTERS UTILIZED
BY THE DESIGNATOR SYSTEM ARE:
S = STUD OR JOIST SECTIONS
T = TRACK SECTIONS
U = CHANNEL SECTIONS
F = FURRING CHANNEL SECTIONS
FLANGE WIDTH:
(EXAMPLE: 1 5/8" = 1.625" = 162 X 1/100
INCHES)
ALL FLANGE WIDTHS ARE TAKEN IN 1/100
INCHES.
MATERIAL THICKNESS:
(EXAMPLE: 0.054 IN = 54 MILS;
1 MIL = 1/100 IN)
MATERIAL THICKNESS IS THE
MINIMUM BASE METAL
THICKNESS IN MILS. MINIMUM
BASE METAL THICKNESS
REPRESENTS 95% OF
THE DESIGN THICKNESS.
PRODUCT IDENTIFICATION KEY:
GAUGE THICKNESS EQUIVALENTS:
33 MIL = 20 GA
43 MIL = 18 GA
54 MIL = 16 GA
68 MIL = 14 GA
97 MIL = 12 GA
118 MIL = 10 GA
NON-COATED REINFORCING BAR
DEVELOPMENT AND SPLICE LENGTHS
f 'c = 4000 PSI
BAR SIZE Ld Ldt Lt Ltt
15 20 20 26#3
19 25 25 33#4
24 32 32 41#5
29 38 38 50#6
42 55 55 71#7
48 63 63 82#8
54 71 71 92#9
60 78 78 102#10
66 86 86 112#11
EPOXY COATED REINFORCING BAR
DEVELOPMENT AND SPLICE LENGTHS
f 'c = 4000 PSI
BAR SIZE Ld Ldt Lt Ltt
22 29 38#3
29 38 50#4
36 47 61#5
43 56 73#6
63 82 107#7
72 94 122#8
81 106 137#9
89 116 151#10
98 128 166#11
NOTES:
1. db = NOMINAL BAR DIAMETER Ld = TENSION DEVELOPMENT LENGTH Ldt = DEVELOPMENT LENGTH OF TOP BARS IN TENSION Lt = TENSION LAP SPLICE LENGTH Ltt = TENSION LAP SPLICE LENGTH OF TOP BARS Lb = COMPRESSION DEVELOPMENT LENGTH Lc = TIED COLUMN LAP SPLICE IN COMPRESSION Lcs = SPIRAL COLUMN LAP SPLICE IN COMPRESSION
2. REBAR DEVELOPMENT/SPLICE LENGTHS ARE BASED
ON ACI 318. REINFORCEMENT YIELD STRENGTH, Fy = 60 KSI.
3. "TOP BARS" = HORIZONTAL BEAM, MAT, OR SLAB REINFORCING WITH
MORE THAN 12" CAST BELOW.
4. ALL SPLICES SHALL BE TENSION SPLICES, UNO.
5. LARGER DIAMETER SPLICE LENGTHS GOVERN AT BAR SIZE
TRANSITIONS.
6. FOR LIGHTWEIGHT CONCRETE, MULTIPLY TABLE VALUES BY 1.33, UNO.
TABLE VALUES SHALL BE MULTIPLIED BY 1.5 IF THE FOLLOWING
CRITERIA ARE NOT MET:
SLAB / WALL
MIN
3db d b
R
M
IN
MIN
2db
MIN
2db
COLUMN / BEAM
TOP
BAR
TYPICAL REINFORCING BAR DEVELOPMENT / SPLICE DETAILS
S
S T
A G
G E
R
S
MECHANICAL
COUPLER
MECHANICAL
SPLICE STAGGER LAP DETAIL
T A
B L E
L A
P P
E R
(L t, L tt L c L c s
Lb
Ld, Ldt
DEVELOPMENT LENGTH
f 'c = 5000 PSI
BAR SIZE Ld Ldt Lt Ltt
13 17 17 22#3
17 23 23 29#4
22 29 29 38#5
26 34 34 44#6
38 50 50 65#7
43 56 56 73#8
48 63 63 82#9
54 71 71 92#10
59 77 77 100#11 f 'c = 5000 PSI
BAR SIZE Ld Ldt Lt Ltt
20 26 34#3
26 34 44#4
32 42 55#5
39 51 66#6
56 73 95#7
64 84 109#8
72 94 122#9
80 104 136#10
88 115 149#11
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABORATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSL LAMINATED STRAND LUMBER
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MF MOMENT FRAME
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
OWJ PRE-MANUFACTURED OPEN WEB JOIST
PC PRECAST CONCRETE
PEMB PRE-ENGINEERED METAL BUILDING
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
RTU ROOFTOP MECHANICAL UNIT
S SLOPE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SOMD SLAB ON METAL DECK
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TC TOP CHORD
TEMP TEMPERATURE
THRU THROUGH
TJI PREFABRICATED WOOD I-JOIST
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WH WEEP HOLE
WP WORK POINT
WT WEIGHT, STRUCTURAL T
WWF, WWR WELDED WIRE REINFORCEMENT
XS EXTRA STRONG (PIPE)
XXS DOUBLE EXTRA STRONG (PIPE)
& AND
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BC BOTTOM CHORD
BD BOARD
BF BRACED FRAME
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
BU BUILT UP
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION
JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GL GLUED LAMINATED TIMBER (GLULAM)
GRND GROUND
GT GIRDER TRUSS
HAS HEADED ANCHOR STUD
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR
CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
STRUCTURAL DRAWINGS ABBREVIATIONS
SHEET # SHEET NAME
S001 ABBREVIATIONS AND SYMBOLS
S002 GENERAL NOTES
S003 GENERAL NOTES
S004 SPECIAL INSPECTION REQUIREMENTS
S005 LOAD MAPS
S006 LOAD MAPS
S007 PARKING LAYOUT
S008 AXONOMETRICS
S101A FOUNDATION PLAN - AREA A
S101A.SOG SLAB ON GRADE PLAN - AREA A
S101B FOUNDATION PLAN - AREA B
S101B.SOG SLAB ON GRADE PLAN - AREA B
S102A GROUND FLOOR FRAMING PLAN - AREA A
S102A.R GROUND FLOOR REINFORCING PLAN - AREA A
S102B GROUND FLOOR FRAMING PLAN - AREA B
S102B.R GROUND FLOOR REINFORCING PLAN - AREA B
S103A ROOF FRAMING PLAN - AREA A
S103B ROOF FRAMING PLAN - AREA B
S201 WALL PLAN
S211 BUILDING SECTIONS
S212 BUILDING SECTIONS
S301 FOUNDATION SCHEDULES, SECTIONS, AND DETAILS
S302 FOUNDATION SECTIONS AND DETAILS
S311 CONCRETE COLUMN SCHEDULES, SECTIONS, AND DETAILS
S321 CONCRETE WALL SECTIONS AND DETAILS
S322 CONCRETE WALL SECTIONS AND DETAILS
S323 CONCRETE WALL SECTIONS AND DETAILS
S325 CONCRETE WALL SECTIONS AND DETAILS
S331 POST-TENSIONED CONCRETE BEAM SCHEDULE
S332 MILD REINFORCED BEAM SCHEDULE
S341 TYPICAL CONCRETE FRAMING DETAILS
S342 TYPICAL CONCRETE FRAMING DETAILS
S343 TYPICAL CONCRETE FRAMING DETAILS
S401 CMU SCHEDULES, SECTIONS, AND DETAILS
S511 ROOF FRAMING DETAILS
STRUCTURAL INDEX
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
320-C Midland Pkwy Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Ken Noel (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
VA FORM 08-6231
CONSULTANTS:
ACG Project Number
© COPYRIGHT Apogee- CEMS JV, LLC
DRAWING TITLE
APPROVED: CHIEF OF STAFF
APPROVED: HEALTH CARE SYSTEM DIRECTOR
APPROVED: CHIEF OF POLICE
APPROVED: DIRECTOR FMS DATE: APPROVED: SAFETY MANAGER DATE:
APPROVED: GEMS COORDINATOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: SERVICE LINE DIRECTOR
DATE:
DATE:
DATE: APPROVED: INFECTION CONTROL NURSE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE:
CHECKED BYBUILDING No
LOCATION
DATE:
DATE: DRAWING NO.
DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
APPROVED: ASSOCIATE HEALTH CARE SYSTEM DIRECTOR
DATE
DATE:
PROJECT: 18-063
/2
/2
:1
:1
P M
S001
ABBREVIATIONS AND SYMBOLS
KMD JKB
CONSTRUCT PARKING
STRUCTURE FOR PATIENT
ACCESS
ST. CLOUD VA HEALTH CARE SYSTEM
ST. CLOUD, MINNESOTA
05/27/2020
BID DOCUMENTS
656-344
2008 3601
GENERAL
STRUCTURES INDICATED ON THESE DRAWINGS HAVE BEEN DESIGNED FOR THE IN-
SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF
CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURES
ARE DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER CONSTRUCTION IS
COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE
CONSTRUCTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
STRUCTURES AND RELATED COMPONENTS DURING CONSTRUCTION. THIS INCLUDES
THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS,
TIEDOWNS, ETC.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT CONSTRUCTION LOADS
DO NOT EXCEED THE CAPACITY OF ANY STRUCTURAL ELEMENT AT THE TIME THE
LOADS ARE APPLIED, INCLUDING BUT NOT LIMITED TO: WEIGHTS OF MATERIALS,
WEIGHTS OF EQUIPMENT AND WORKERS, AND ALL LOADS APPLIED FROM
TEMPORARY LIFTS, HOISTS AND CRANES, ETC.
THE STRUCTURAL DRAWINGS AND SPECIFICATIONS SHALL BE USED IN CONJUNCTION
WITH THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER DISCIPLINES, TRADES, AND
DELEGATED DESIGN ELEMENTS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATION OF THE STRUCTURAL WORK WITH ALL OTHER APPLICABLE TRADES.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH
THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT.
DO NOT SCALE THE DRAWINGS. REFER TO THE WRITTEN DIMENSIONS AND
INFORMATION.
IF A DISCREPANCY IS NOTED ON THE DRAWINGS, GENERAL NOTES, OR
SPECIFICATIONS, THE CONTRACTOR SHALL SUBMIT TO THE STRUCTURAL ENGINEER
A WRITTEN REQUEST FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE
AFFECTED WORK WITHOUT DOCUMENTED RESOLUTION OF THE DISCREPANCY. ALL
COSTS RESULTING FROM THE CONTRACTOR IMPROPERLY PROCEEDING WITH THE
AFFECTED WORK PRIOR TO DOCUMENTED RESOLUTION OF THE DISCREPANCY,
INCLUDING COST OF REMOVAL AND REPLACEMENT OF NON-CONFORMING WORK,
SHALL BE BORNE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER
A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL
BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE
CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE
OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING
INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION
OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION,
AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND
LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION
OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND
MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN
ACCORDANCE WITH "STANDARD DEVIATION" DETERMINATION OUTLINED IN
ACI 318.
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC
ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN
THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF PRODUCT DATA. FOR HARD
COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF PRODUCT DATA TO THE
STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT PRODUCT DATA IN
ADOBE PDF FORMAT.
1. FIBER REINFORCEMENT FOR CONCRETE
2. DIAMOND PLATE DOWELS FOR SLABS ON GRADE
3. CONCRETE CURING COMPOUND
4. CONCRETE JOINT SEALANT
5. MASONRY JOINT REINFORCEMENT
6. EXPANSION ANCHORS
7. ADHESIVE ANCHORS
8. NON-SHRINK GROUT
9. VAPOR RETARDER
10. POST-TENSIONING PRODUCTS
11. LOCKABLE DOWELS
12. COLD FORMED STEEL FRAMING
13. COLD FORMED STEEL FRAMING CONNECTOR HARDWARE
FOUNDATIONS
SEE GEOTECHNICAL REPORT NUMBER MP185137 PREPARED BY TERRACON DATED
12/13/2018 AND ALL APPLICABLE ADDENDA AND AMENDMENTS FOR INFORMATION
RELATED TO FOUNDATION EXCAVATIONS AND SOIL-RELATED WORK.
FOUNDATIONS HAVE BEEN DESIGNED BASED ON ASSUMED ALLOWABLE SOIL BEARING
PRESSURES INDICATED BELOW. CONTRACTOR SHALL ENGAGE A LICENSED
GEOTECHNICAL ENGINEER TO REVIEW THE SOIL CONDITIONS AT THE SITE AS
NECESSARY TO CONFIRM THE ALLOWABLE BEARING PRESSURES PRIOR TO
PLACEMENT OF THE FOUNDATIONS. CONFIRMATION OF THE ACCEPTABILITY OF THE
SOILS SHALL BE REPORTED IN WRITING TO THE STRUCTURAL ENGINEER.
IF ACTUAL ALLOWABLE PRESSURES ARE FOUND TO BE LESS THAN THE ASSUMED
VALUES, THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY
AND SHALL NOT PROCEED WITH FOUNDATION CONSTRUCTION WITHOUT REVIEW BY
THE STRUCTURAL ENGINEER.
GEOTECHNICAL DESIGN DATA:
GENERAL:
FROST DEPTH 5 FT
GROUNDWATER ELEVATION 1032'
SHALLOW FOUNDATIONS AND SOIL SUPPORTED SLAB ON GRADE:
ALLOWABLE BEARING (SPREAD FOOTINGS) 4000 PSF
ALLOWABLE BEARING (CONTIN. WALL FOOTINGS) 4000 PSF
MODULUS OF SUBGRADE 150 PSI/IN
LATERAL EARTH PRESSURE:
ACTIVE COEFFICIENT (DRAINED), Ka 0.33 AT-REST COEFFICIENT (DRAINED), Ko 0.47 PASSIVE COEFFICIENT (DRAINED), Kp 3.25
UNIT WEIGHT OF BACKFILL 120 PCF
COEFFICIENT OF SLIDING FRICTION 0.45
SEE GEOTECHNICAL REPORT FOR ADDITIONAL REQUIREMENTS AND INFORMATION.
DESIGN VALUES SHALL BE FIELD VERIFIED BY QUALIFIED GEOTECHNICAL ENGINEER
RETAINED BY OWNER.
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED
GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS SHALL BE FORWARDED TO THE
STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM
THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE
STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER
CONSTRUCTION IS ATTEMPTED.
THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE AND MAINTAIN APPROPRIATE
EXCAVATION PROTECTION, INCLUDING ALL NECESSARY LAYBACKS, SHORING,
SHEETING, TIE-BACKS AND OTHER MEASURES AS DETERMINED BY THE
CONTRACTOR'S ENGINEER.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS
FOOTINGS AND MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO
UNIFORM SURFACE AND SHALL BE PROTECTED AND MAINTAINED UNIFORM UNTIL
CONCRETE IS PLACED.
ALL EARTHWORK SHALL BE COMPLETED IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE GEOTECHNICAL REPORT.
UNDERSLAB STORAGE SYSTEMS SHALL BE INSTALLED PER THE RECOMMENDATIONS
OF THE GEOTECHNICAL REPORT.
BELOW-GRADE WALLS
DO NOT BACKFILL AGAINST BELOW-GRADE CONCRETE (OR MASONRY) WALLS UNTIL
THE CONCRETE (OR MASONRY ASSEMBLAGE) HAS REACHED ITS 28-DAY
COMPRESSIVE STRENGTH.
WHERE BACKFILL IS REQUIRED ON BOTH SIDES OF BELOW-GRADE WALLS, BACKFILL
EVENLY ON EACH SIDE OF EACH WALL TO PREVENT UNBALANCED SOIL LOADS
AGAINST THE WALL.
INSULATION
ANY INSULATION SHOWN ON THE STRUCTURAL DRAWINGS IS FOR GENERAL VISUAL
REFERENCE ONLY, UNLESS NOTED OTHERWISE. SEE THE ARCHITECTURAL
DRAWINGS AND SPECIFICATIONS FOR EXACT LOCATION, PLACEMENT, THICKNESS
AND MATERIAL REQUIREMENTS.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND COMMENTARY
(ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE
LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301).
READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN
CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE
CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1
PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON
THE DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL HAVE THE PROPERTIES AS INDICATED IN THE
CONCRETE MIX SCHEDULE AND SPECIFICATIONS.
DO NOT INSTALL OR EMBED ALUMINUM ITEMS, INCLUDING BUT NOT LIMITED TO
ALUMINUM CONDUIT, INTO OR IN CONTACT WITH CONCRETE.
WHERE NEW CONCRETE IS PLACED AGAINST HARDENED/EXISTING CONCRETE,
VERIFY SOUNDNESS OF EXISTING CONCRETE AND REMOVE ALL LOOSE MATERIAL,
SNOW, ICE, FROST, WATER, SOIL, DEBRIS AND OTHER DETRIMENTAL MATERIALS
PRIOR TO PLACEMENT OF NEW CONCRETE.
WELDABLE REINFORCING STEEL
REINFORCING STEEL WHICH IS TO BE WELDED SHALL CONFORM TO ASTM A706.
WELDING OF REINFORCING STEEL, WHEN APPROVED BY THE STRUCTURAL ENGINEER,
SHALL CONFORM TO THE LATEST EDITION OF AMERICAN WELDING SOCIETY
STANDARD D1.4. ELECTRODES FOR SHOP AND FIELD WELDING OF REINFORCING
STEEL SHALL CONFORM TO ASTM A233, CLASS E90XX.
EPOXY-COATED REINFORCING STEEL
EPOXY COATED REINFORCING STEEL SHALL CONFORM TO ASTM A775 AND SHALL BE
USED ONLY WHERE SHOWN OR NOTED ON THE DRAWINGS.
PROVIDE EPOXY-COATED REINFORCING FOR THE FOLLOWING:
1. COLUMNS: TIES WITHIN BEAM DEPTH AT ALL COLUMNS
2. POST-TENSIONED SLABS: TOP AND BOTTOM BARS, SUPPORT BARS AND
BACKUP BARS
3. BEAMS: TOP AND BOT REINFORCEMENT AND STIRRUPS
4. UPTURNED BEAMS: BOTTOM REINFORCEMENT AND STIRRUPS
5. CURBS: ALL REINFORCEMENT
6. CMU WALLS: ALL DOWEL BARS
WELDED WIRE REINFORCEMENT
WELDED WIRE REINFORCEMENT SHALL BE SMOOTH WIRE FABRIC CONFORMING TO
ASTM A1064. REINFORCEMENT SHALL BE SUPPLIED IN FLAT SHEETS AND LAPPED A
MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE REINFORCEMENT SHALL BE PLACED AS FOLLOWS, UNLESS NOTED
OTHERWISE:
SLABS ON GRADE: 2" DOWN FROM TOP OF SLAB
SLABS ON COMPOSITE DECK: 3/4" DOWN FROM TOP OF SLAB
SLABS ON NON-COMPOSITE DECK: MID-DEPTH OF CONCRETE ABOVE FLUTES
SUPPORT REINFORCEMENT ON NON-METALLIC CHAIRS TO MAINTAIN PROPER
POSITION THROUGHOUT CONCRETE PLACEMENT.
(NOTE: THE TERM "WELDED WIRE FABRIC," IF USED, IS THE SAME AS "WELDED WIRE
REINFORCEMENT.")
FIBER REINFORCEMENT (SYNTHETIC)
MICRO-FIBER REINFORCEMENT SHALL BE VIRGIN (NON-RECYCLED) NYLON OR
POLYPROPYLENE FIBERS COMPLYING WITH ASTM C1116, WITH LONGEST FIBERS NOT
LESS THAN 0.75 INCHES.
MACRO-FIBER REINFORCEMENT SHALL BE VIRGIN (NON-RECYCLED) POLYPROPYLENE /
POLYETHYLENE FIBER BLEND COMPLYING WITH ASTM C1116, WITH LONGEST FIBERS
NOT LESS THAN 1.75 INCHES.
FIBERS SHALL BE INTRODUCED INTO CONCRETE MIX AT THE BATCH PLANT AND MIXED
IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
DOSAGE RATES SHALL BE AS INDICATED IN THE CONTRACT DOCUMENTS. USE ONLY
THE FIBER TYPE INDICATED FOR EACH APPLICATION. SUBSTITUTION OF FIBER TYPES IS
NOT PERMITTED.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S
POUR AND FOR EACH 100 CUBIC YARDS FOR EACH TYPE OF CONCRETE PLACED. EACH
SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28
DAYS (3 SPECIMENS TESTED AT 28 DAYS IF USING 4x8 CYLINDERS) AND ONE SPECIMEN
RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL
ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS
SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES
DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN
ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE
CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE
SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL CURING BOXES ARE NOT
PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER,
READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24 HOURS AFTER TESTING.
POTENTIALLY LOW-STRENGTH CONCRETE: CONCRETE WHICH EXHIBITS STRENGTH
BASED ON 7-DAY TESTS BELOW 70% OF THE SPECIFIED 28-DAY COMPRESSIVE
STRENGTH SHALL BE CONSIDERED DEFECTIVE WORK AND SHALL BE SUBJECT TO
REPAIR OR REPLACEMENT BY THE CONTRACTOR AT THE DISCRETION OF THE OWNER
AND STRUCTURAL ENGINEER AT NO ADDITIONAL COST TO THE OWNER.
SHORING/RE-SHORING (CONCRETE FRAME SYSTEMS)
THE SHORING AND/OR RE-SHORING DESIGN FOR CONCRETE FRAME SYSTEMS IS THE
RESPONSIBILITY OF THE CONTRACTOR. TEMPORARY SHORING FOR SLABS, BEAMS,
AND GIRDERS SHALL BE ADEQUATE TO CARRY THE TOTAL WEIGHT OF THE SLAB-
BEAM-GIRDER SYSTEM AND ANY TEMPORARY CONSTRUCTION LOADS TO BE IMPOSED
ON THE STRUCTURAL SYSTEM. SHORING FOR A LEVEL SHALL NOT BE REMOVED
UNTIL THE CONCRETE AT THAT LEVEL HAS ATTAINED THE SPECIFIED COMPRESSIVE
STRENGTH (F'C). REMOVAL OF SHORING AND/OR RESHORING SHALL NOT CAUSE
OVERSTRESSING OF ANY STRUCTURAL ELEMENTS.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND
SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI, UNO.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE
LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 301, ACI 315, ACI 318, ACI
DETAILING MANUAL (SP66), AND CRSI MANUAL OF STANDARD PRACTICE.
THE CONTRACTOR SHALL PROVIDE BAR SUPPORTS AND SPACERS AS REQUIRED TO
MAINTAIN PROPER SUPPORT AND POSITIONING OF THE REINFORCING STEEL
THROUGHOUT CONCRETE PLACEMENT OPERATIONS. DESIGN OF THE SUPPORT
SYSTEM SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE
THE FOLLOWING MINIMUM CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST EARTH: 3 INCHES
FOUNDATION TOP REINFORCEMENT: 2 INCHES
FOUNDATION BOTTOM AND SIDE REINFORCEMENT: 3 INCHES
WALL REINFORCEMENT - #5 AND SMALLER: 1-1/2 INCHES
WALL REINFORCEMENT - #6 AND LARGER: 2 INCHES
ELEVATED SLAB TOP REINFORCEMENT: 2 INCHES
ELEVATED SLAB BOTTOM REINFORCEMENT: 1 INCH
BEAM TOP REINFORCEMENT: 2-1/2 INCHES
BEAM BOTTOM REINFORCEMENT: 2 INCHES
BEAM STIRRUPS AT TOP: 2 INCHES
COLUMN LONGITUDINAL REINFORCEMENT: 2 INCHES
COLUMN TIES: 1-1/2 INCHES
SLAB ON METAL DECK REINFORCEMENT: SEE DETAILS
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT
UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
LAP SPLICES SHALL BE TENSION LAPS IN ACCORDANCE WITH SPLICE/EMBEDMENT
TABLES, UNO.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE
STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT
CORNERS OF ALL WALLS AND GRADE BEAMS. LAP SPLICE CORNERS BARS WITH
STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE)
AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE
BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST
EDITION OF THE GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY
FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE
WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB
SURFACE.
PROVIDE CURING OF CONCRETE SLABS ON GRADE AS REQUIRED TO ACCOMMODATE
FLOOR FINISHES AND FINISH MATERIALS PER THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS. REVIEW ALL FLOOR FINISH REQUIREMENTS PRIOR TO PLACEMENT
OF CONCRETE SLABS AND COORDINATE SLAB MIX, PLACEMENT AND CURING TO
COMPLY WITH FINISH FLOORING MATERIAL MANUFACTURER’S REQUIREMENTS.
CURING PROCEDURES SHALL COMPLY WITH ACI 302.1R AND USE OF CURING
MATERIALS SHALL BE APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER’S
REQUIREMENTS. MOISTURE RETENTION COVERS, IF USED, SHALL BE APPLIED FLAT
AND SMOOTH TO RESULT IN A UNIFORM APPEARANCE AND MINIMIZE SURFACE
MARKINGS AND BLEMISHES.
UNLESS NOTED OTHERWISE, OR UNLESS MORE STRINGENT REQUIREMENTS APPLY,
CURE SLABS ON GRADE AS FOLLOWS:
EXPOSED WAREHOUSE SLABS: USE ASHFORD FORMULA CURING/ SEALING/
HARDENING COMPOUND.
PROVIDE SLABS ON GRADE WITH A SMOOTH TROWEL FINISH UNLESS NOTED
OTHERWISE.
CONTRACTOR SHALL REVIEW ALL REQUIRED FLOOR FINISH MATERIAL REQUIREMENTS
PRIOR TO PLACEMENT OF CONCRETE AND SHALL PROVIDE FLOOR SLAB FLATNESS
AND LEVELNESS MEETING THE FINISH MATERIAL SUPPLIER’S WRITTEN REQUIREMENTS.
FLATNESS AND LEVELNESS SHALL BE THE MORE STRINGENT OF THE FINISH MATERIAL
REQUIREMENTS AND THE FOLLOWING:
SLABS ON GRADE:
OVERALL VALUES: FF = 20, FL = 15
LOCAL VALUES: FF = 15, FL = 10
ELEVATED SLABS:
OVERALL VALUES: FF = 20, FL = 15
LOCAL VALUES: FF = 15, FL = 10 (SHORED UNTIL AFTER TESTING)
CONTRACTOR SHALL PROVIDE ALL NECESSARY REPAIR, GRINDING AND/OR LEVELING
OF THE CONCRETE SLAB TO ACCOMMODATE ALL FLOOR FINISHES PRIOR TO
INSTALLATION OF THE FINISH MATERIALS WITH NO ADDITIONAL COST TO THE PROJECT.
THE MINIMUM LOCAL AREA SHALL BE ANY BAY DEFINED BY COLUMN LINES.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION
JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB
THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO
ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR
SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL
UNLESS NOTED OTHERWISE.
FINISH SLABS WITH FIBER REINFORCEMENT IN ACCORDANCE WITH THE FIBER
MANUFACTURER'S RECOMMENDATIONS AND AS REQUIRED TO MINIMIZE FIBER
EXPOSURE AT THE SLAB SURFACE. FOR SLABS WITH APPLIED FINISHES AND/OR
MATERIALS, INCLUDING POLISHED CONCRETE FINISHES WHEN USED, REMOVE ALL
PROTRUDING FIBERS PER THE FIBER MANUFACTURER’S RECOMMENDATIONS AND AS
REQUIRED TO PROPERLY INSTALL THE FINISHES AND/OR MATERIALS. FOR SLABS
EXPOSED TO VIEW IN THE COMPLETED CONSTRUCTION, REMOVE ALL PROTRUDING
FIBERS PRIOR TO COMPLETION OF CONSTRUCTION PER THE FIBER MANUFACTURER’S
RECOMMENDATIONS.
PENETRATIONS AND EMBEDDED ITEMS
CONTRACTOR SHALL COORDINATE WITH ALL AFFECTED TRADES THE REQUIRED
SIZES, TYPES, AND LOCATIONS OF ALL EMBEDDED ITEMS IN, AND ALL PENETRATIONS
THROUGH, STRUCTURAL ELEMENTS PRIOR TO CONSTRUCTION.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN
ON THE STRUCTURAL DRAWINGS, SHALL BE MADE WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER.
NO ITEMS (INCLUDING, BUT NOT LIMITED TO, CONDUIT, PIPING, ETC.), OTHER THAN
THOSE SHOWN ON THE STRUCTURAL DRAWINGS, SHALL BE EMBEDDED IN
STRUCTURAL ELEMENTS WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
ALL EMBEDDED ITEMS IN EXPOSED EXTERIOR CONCRETE SHALL BE GALVANIZED,
PLASTIC, OR EPOXY-COATED.
CONTRACTOR SHALL ENGAGE A PROFESSIONAL ENGINEER, LICENSED IN THE STATE
WHERE THE PROJECT IS CONSTRUCTED, TO DESIGN TEMPORARY SUPPORTS AS
FOLLOWS: SHORES AND RE-SHORES, TEMPORARY SHORING, BASEMENT WALL
BRACING.
DELEGATED DESIGN
FOR ALL SUBMITTALS INDICATED AS "DELEGATED DESIGN," THE CONTRACTOR SHALL
ENGAGE A SPECIALTY STRUCTURAL ENGINEER LICENSED IN THE STATE WHERE THE
PROJECT IS LOCATED TO DESIGN AND DETAIL THE ITEMS NOTED IN THE STRUCTURAL
SUBMITTALS AND SPECIFICATIONS AS A DELEGATED DESIGN.
DELEGATED DESIGN CALCULATIONS AND RELATED DRAWINGS SHALL CONTAIN THE
FOLLOWING, AS A MINIMUM:
1. COVER PAGE SIGNED AND SEALED BY THE SPECIALTY STRUCTURAL ENGINEER
INCLUDING A STATEMENT OF CERTIFICATION THAT THE SUBMITTED
CALCULATIONS ARE IN CONFORMANCE WITH THE DESIGN CRITERIA PROVIDED
IN THE CONTRACT DOCUMENTS AND THAT THE RELATED SHOP DRAWINGS
ARE IN CONFORMANCE WITH THE SUBMITTED CALCULATIONS.
2. TABLE OF CONTENTS, PLACED ON, OR IMMEDIATELY FOLLOWING THE COVER
SHEET.
3. SUMMARY OF APPLICABLE CODE CRITERIA, LOAD DATA AND PERFORMANCE
CRITERIA AS OUTLINED IN THE CONTRACT DOCUMENTS.
4. CLEAR DEFINITION OF THE LOCATION(S) IN THE STRUCTURE WHERE EACH
CALCULATION APPLIES.
5. LOCATION, TYPE, MAGNITUDE AND DIRECTION OF ALL LOADS IMPOSED ON THE
STRUCTURE BY THE DELEGATED DESIGN SYSTEM/COMPONENTS.
SUBMITTALS THAT DO NOT CONTAIN THE INFORMATION NOTED ABOVE WILL BE
REJECTED WITHOUT COMMENT.
THE STRUCTURAL ENGINEER’S REVIEW OF DELEGATED DESIGN SUBMITTALS WILL BE
FOR GENERAL CONFORMANCE WITH THE DESIGN LOADING, DESIGN INTENT AND
LOADS IMPOSED.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE ALL PARTS
OF THE WORK TO BE FABRICATED AND CONSTRUCTED IN ACCORDANCE WITH THE
DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR
GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS
RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL
TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT CONTRACTOR'S
REVIEW WILL BE RETURNED UNCHECKED.
PROVIDE ALL SUBMITTALS IN ELECTRONIC PDF FORMAT.
WORK REQUIRING SUBMITTALS FOR STRUCTURAL ENGINEER REVIEW SHALL NOT BE
STARTED BY THE CONTRACTOR WITHOUT APPROPRIATE REVIEWED SUBMITTALS.
WORK PERFORMED BY THE CONTRACTOR PRIOR TO RECEIVING APPROPRIATE
REVIEWED SUBMITTALS SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AS
DEEMED NECESSARY BY THE STRUCTURAL ENGINEER, AT THE CONTRACTOR'S
EXPENSE, AND WITH NO COST TO THE OWNER.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. CONCRETE MASONRY REINFORCEMENT (INCLUDING PLANS AND ELEVATIONS
FOR EACH WALL INDICATING ALL CMU REINFORCING REQUIREMENTS,
INCLUDING SHEAR WALLS)
3. CONCRETE MASONRY CONTROL JOINT LOCATIONS
4. STRUCTURAL STEEL
5. CONTRACTORS METHOD FOR MARKING TENDONS PRIOR TO ANCHOR
INSTALLATION
6. POST TENSIONED SLAB COORDINATION DRAWINGS SHOWING ALL OPENINGS,
EMBEDS, PT ANCHORAGES, ETC. FULLY COORDINATED WITH ALL TRADES
PRIOR TO SUBMITTAL
7. ELEVATED MILD REINFORCED CONCRETE SLAB COORDINATION DRAWINGS
SHOWING ALL OPENINGS, EMBEDS, ANCHORAGES, ETC. FULLY COORDINATED
WITH ALL TRADES PRIOR TO SUBMITTAL
8. EACH AREA TO BE TENSIONED SHALL BE LAID OUT ON A PLAN AND SUBMITTED
TO THE STRUCTURAL ENGINEER BY THE CONTRACTOR PRIOR TO
CONSTRUCTION.
SUBMIT DELEGATED DESIGN SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. STRUCTURAL STEEL CONNECTIONS (INCLUDING DESIGN CALCULATIONS AND
SUMMARY PAGE FOR CONNECTIONS NOT SPECIFICALLY DETAILED IN THE
CONTRACT DRAWINGS)
2. STEEL PAN STAIRS (INCLUDING DESIGN CALCULATIONS, FRAMING LAYOUTS,
MEMBER SIZES, MATERIALS AND CONNECTION DETAILS)
3. POST-TENSIONING (INCLUDING DETAILED DESIGN FOR TENDONS AND END
ANCHORAGES; CALCULATION OF LOSSES DUE TO CREEP, SHRINKAGE, STRESS
RELAXATION, ANCHORAGE SLIP, AND FRICTION; POST-TENSIONING SHOP
DRAWINGS)
4. GLAZING SYSTEMS - CURTAIN WALL AND STOREFRONT (INCLUDING DESIGN
CALCULATIONS AND CONNECTION DETAILS)
5. CONCRETE FORMWORK (INCLUDING DESIGN CALCULATIONS, FORMWORK
LAYOUT, APPLICABLE RE-SHORE AND SEQUENCING INFORMATION.)
6. PREFABRICATED COLD-FORMED STEEL TRUSSES (INCLUDING DESIGN
CALCULATIONS, FRAMING LAYOUTS, MEMBER SIZES, MATERIALS AND
CONFIGURATIONS, AND REQUIRED TEMPORARY AND PERMANENT BRACING)
OMISSION OF ANY MATERIALS REQUIRED BY THE CONTRACT DOCUMENTS FROM SHOP
DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY FOR
FURNISHING THESE MATERIALS REGARDLESS OF WHETHER THE SUBMITTALS HAVE
BEEN REVIEWED.
THE USE OF ELECTRONIC FILES OR REPRODUCTIONS OF THE CONTRACT DOCUMENTS
BY THE CONTRACTOR SIGNIFIES CONTRACTOR’S ACCEPTANCE OF ALL THE
INFORMATION SHOWN “AS IS”. CONTRACTOR WILL BE RESPONSIBLE FOR VERIFYING
THE ACCURACY AND COMPLETENESS OF THE INFORMATION PROVIDED. ISSUED
DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE OVER ANY ELECTRONIC
INFORMATION PROVIDED. ADDENDA, CHANGE ORDERS, SUPPLEMENTAL
INSTRUCTIONS ARE NOT NECESSARILY INCLUDED IN THE ELECTRONIC FILES.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN ALL CONTRACT
DOCUMENTS, INCLUDING LATEST ADDENDA, AND TO DISTRIBUTE TO ALL
SUBCONTRACTORS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS.
POST-TENSIONED CONCRETE (GENERAL)
ALL POST-TENSIONED CONCRETE SHALL ATTAIN 75% OF COMPRESSIVE STRENGTH
(BUT NOT LESS THAN 3,000PSI) AT THE TIME OF INITIAL STRESSING. PROVIDE EXTRA
TEST CYLINDERS TO SUBSTANTIATE CONCRETE STRENGTH PRIOR TO POST-
TENSIONING. AT CONTRACTOR'S OPTION MATURITY METERS MAY BE ALLOWED WITH
APPROPRIATE VERIFIED TESTING. SUBMIT PRODUCT DOCUMENTATION FOR REVIEW
PRIOR TO CONSTRUCTION.
POST-TENSIONING REINFORCING SHALL BE 1/2 INCH DIAMETER, UNBONDED
MONOSTRAND SYSTEM, LOW RELAXATION, 270 KSI HIGH-TENSILE WIRE STRAND
CONFORMING TO ASTM A416. PTI GUIDELINES SHALL BE FOLLOWED IN ALL CASES.
TENDONS THAT DO NOT SPAN THE ENTIRE LENGTH OF THE SLAB MUST BE ANCHORED
AT SLAB MID-DEPTH AND SHALL NOT BE STRESSED THROUGH THE TOP OF THE SLAB.
ENCASE POST-TENSIONING TENDONS IN WATERPROOF POLYETHYLENE PLASTIC
SHEATHING OF 25 MILS MINIMUM THICKNESS. PROVIDE SUFFICIENT STRENGTH TO
PREVENT UNREPAIRABLE DAMAGE DURING FABRICATION, TRANSPORTATION,
INSTALLATION, PLACEMENT, AND TENSIONING. REPAIR ANY DAMAGED SHEATHING
SECTION PER THE POST-TENSIONING INSTITUTE (PTI) RECOMMENDATIONS.
PROVIDE ENCAPSULATED TENDONS AT LOCATIONS EXPOSED TO THE
ELEMENTS/WATER (PARKING STRUCTURES, BALCONIES, ETC.).
POST-TENSION FORCES SHOWN ON PLANS AND SCHEDULES ARE EFFECTIVE FORCES.
WHERE NUMBERS OF TENDONS ARE SHOWN THEY ARE BASED ON A FINAL EFFECTIVE
PRESTRESS FORCE OF 26.8 KIPS PER TENDON. THE POST-TENSIONING SUPPLIER
SHALL DETERMINE THE NUMBER OF TENDONS BASED ON THESE EFFECTIVE FORCES.
INSTALL TENDONS WITH A PARABOLIC DRAPE. HOLD SLAB MAIN TENDONS IN THEIR
DESIGNED POSITIONS AS SHOWN IN THE DRAWINGS WITH CHAIRS, SUPPORT BARS,
AND SLAB BOLSTERS. MAINTAIN TENDON VERTICAL POSITION WITHIN 1/8 INCH.
PLACE CONCRETE ONLY AFTER THE POST-TENSIONING TENDONS AND
REINFORCEMENT HAVE BEEN INSPECTED AND APPROVED. CONTINUOUS INSPECTION
AND RECORDING OF ELONGATION IS REQUIRED DURING ALL STRESSING OPERATIONS.
DO NOT CUT TENDON ENDS UNTIL THE ENTIRE SLAB HAS BEEN SATISFACTORILY
STRESSED AND THE ENGINEER OF RECORD HAS REVIEWED.
THE POST-TENSIONED SLABS ARE DESIGNED BASED ON TENDONS BEING CONTINUOUS
BETWEEN EDGES OF SLABS AS SHOWN ON THE DRAWINGS. SUBMIT ANY ADDITIONAL
INTERMEDIATE STRESSING JOINTS REQUIRED BY THE CONTRACTOR TO THE
STRUCTURAL ENGINEER OF RECORD BEFORE STARTING CONSTRUCTION. THESE
LOCATIONS MAY REQUIRE ADDITIONAL REINFORCING. LOCATE CONSTRUCTION JOINTS
IN POST-TENSIONED SLABS AT THE QUARTER POINTS OF THE SLAB SPAN WHERE THE
STRANDS ARE AT MID-DEPTH FOR PROPER ANCHORAGE.
POST-TENSIONED ONE-WAY SYSTEMS (PARKING STRUCTURES)
ALL POST-TENSIONED CONCRETE NOTES APPLY TO THIS SECTION.
STRESS TENDONS IN THE FOLLOWING ORDER:
ONE-WAY SYSTEM
1. STRESS 50% OF SLAB TENDONS
2. STRESS 100% OF SLAB TEMPERATURE TENDONS
3. STRESS 50% OF BEAM TENDONS
4. STRESS 50% OF GIRDER TENDONS / WHERE APPLICABLE /
5. STRESS REMAINING SLAB TENDONS
6. STRESS REMAINING BEAM TENDONS
7. STRESS REMAINING OF GIRDER TENDONS / WHERE APPLICABLE /
DO NOT USE TEMPERATURE TENDONS OR MILD REINFORCING FOR SUPPORT OF
TENDONS.
ALL INSERTS, SLEEVES, AND OPENINGS SHALL BE CAST-IN-PLACE. DRILLED AND
POWER-DRIVEN FASTENERS ARE PROHIBITED EXCEPT FOR AS SHOWN THE “ONE-WAY
PT SYSTEM POST-INSTALLED ANCHOR DETAIL.” NO REINFORCING OR POST-
TENSIONING TENDONS SHALL BE DAMAGED BY ANY ANCHOR OR FASTENER.
FLOWABLE FILL
WHERE INDICATED ON THE STRUCTURAL DRAWINGS, FLOWABLE FILL SHALL BE A
CONTROLLED LOW-STRENGTH MATERIAL (CLSM) PRODUCED AND PLACED IN
ACCORDANCE WITH RECOMMENDATIONS OF ACI 229. PROVIDE MATERIAL WITH 28-
DAY COMPRESSIVE STRENGTH OF 1,000 PSI UNLESS NOTED OTHERWISE.
BASEMENT WALLS
UNLESS NOTED OTHERWISE, DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL THE
BASEMENT AND GROUND FLOOR SLABS HAVE BEEN COMPLETELY INSTALLED AND
REACHED THEIR 28-DAY COMPRESSIVE STRENGTH AND ALL FLOOR FRAMING AND
SLAB CONNECTIONS TO THE BASEMENT WALLS HAVE BEEN COMPLETELY INSTALLED.
WHERE BASEMENT WALLS OCCUR, BACKFILL EVENLY ON ALL SIDES OF THE BUILDING
TO PREVENT UNBALANCED SOIL LOADS AGAINST THE BASEMENT STRUCTURE,
UNLESS NOTED OTHERWISE.
REFER TO ADDITIONAL NOTES ON PLANS AND DETAILS REGARDING BACKFILL
SEQUENCING.
"LOADS IMPOSED" SUBMITTALS
FOR EACH OF THE SYSTEMS INDICATED BELOW THAT REQUIRE "LOADS IMPOSED"
SUBMITTALS, THE CONTRACTOR SHALL PROVIDE A COMPLETE LOADING
INFORMATION SUBMITTAL IDENTIFYING THE LOCATION, MAGNITUDE, DIRECTION AND
TYPE (DEAD, LIVE, WIND, SEISMIC, ETC.) OF ALL SERVICE LEVEL LOADS APPLIED TO
THE STRUCTURE. THE SUBMITTAL SHALL BE SIGNED AND SEALED BY A
PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS
CONSTRUCTED.
LOADING INFORMATION SHALL BE PROVIDED IN GRAPHIC FORM, UTILIZING MARKUPS
OF FRAMING PLANS, BUILDING ELEVATIONS OR OTHER DRAWINGS AS APPROPRIATE
TO READILY CONVEY THE LOCATIONS OF THE APPLIED LOADS. IN ADDITION, EACH
LOADING LOCATION SHALL CONTAIN A DETAIL REFERENCE SHOWING THE
CONNECTION DETAIL(S) DISPLAYING PRECISELY HOW EACH LOAD IS APPLIED TO THE
STRUCTURE.
LOADS IMPOSED ON THE STRUCTURE SHALL IMPART ONLY VERTICAL AND
HORIZONTAL LOADS ON THE STRUCTURE WITHOUT INDUCING TORSIONAL LOADS ON
THE SUPPORTING STRUCTURAL ELEMENTS, UNLESS SPECIFICALLY INDICATED
OTHERWISE.
THE CONTRACTOR'S PROFESSIONAL ENGINEER SHALL REVIEW THE IMPOSED LOADS
TO CONFIRM THAT THE LOADS APPLIED BY THE SYSTEM DO NOT EXCEED THE BASIS
OF DESIGN LOAD LIMITS AS INDICATED ON THE STRUCTURAL DRAWINGS.
WHERE THE LOADS IMPOSED BY THE CONTRACTOR'S PROPOSED SYSTEM EXCEED
THE BASIS OF DESIGN LOADS INDICATED ON THE STRUCTURAL DRAWINGS, THE
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY TO
DETERMINE WHETHER MODIFICATIONS ARE NECESSARY.
SUBMIT "LOADS IMPOSED" SUBMITTALS FOR THE FOLLOWING ITEMS:
1. ELEVATOR REACTIONS
2. EXTERIOR CLADDING (CURTAIN WALL AND STOREFRONT)
3. METAL STAIRS
4. M/E/P PLATFORMS
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
320-C Midland Pkwy Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Ken Noel (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
VA FORM 08-6231
CONSULTANTS:
ACG Project Number
© COPYRIGHT Apogee- CEMS JV, LLC
DRAWING TITLE
APPROVED: CHIEF OF STAFF
APPROVED: HEALTH CARE SYSTEM DIRECTOR
APPROVED: CHIEF OF POLICE
APPROVED: DIRECTOR FMS DATE: APPROVED: SAFETY MANAGER DATE:
APPROVED: GEMS COORDINATOR
APPROVED: PROJECTS SECTION MANAGER
APPROVED: SERVICE LINE DIRECTOR
DATE:
DATE:
DATE: APPROVED: INFECTION CONTROL NURSE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE:
CHECKED BYBUILDING No
LOCATION
DATE:
DATE: DRAWING NO.
DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
APPROVED: ASSOCIATE HEALTH CARE SYSTEM DIRECTOR
DATE
DATE:
PROJECT: 18-063
/2
/2
:1
:1
P M
S002
GENERAL NOTES
KMD JKB
CONSTRUCT PARKING
STRUCTURE FOR PATIENT
ACCESS
ST. CLOUD VA HEALTH CARE SYSTEM
ST. CLOUD, MINNESOTA
05/27/2020
BID DOCUMENTS
656-344
CONCRETE UNIT MASONRY
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE LATEST
EDITION OF THE BUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY
STRUCTURES (ACI 530).
CONCRETE MASONRY SHALL CONSIST OF HOLLOW UNITS CONFORMING TO THE
REQUIREMENTS OF ASTM C90, WITH A MINIMUM NET AREA COMPRESSIVE STRENGTH
OF 2,800 PSI, UNO. CONCRETE MASONRY ASSEMBLAGES SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH (F'M) OF 2,000 PSI AT 28 DAYS, UNO.
ALL MASONRY TO BE LAID IN RUNNING BOND, UNO. ALIGN CELLS TO ALLOW PROPER
REINFORCEMENT PLACEMENT AND GROUTING.
MORTAR SHALL BE TYPE S PROPORTIONED IN ACCORDANCE WITH ASTM C270.
FULLY MORTAR FACE SHELLS ON HEAD AND BED JOINTS. PROVIDE FULL MORTAR
COVER ON ALL WEBS AT GROUTED CELLS.
GROUT FOR REINFORCED MASONRY SHALL BE PROPORTIONED IN ACCORDANCE WITH
ASTM C476 (MINIMUM 28-DAY COMPRESSIVE STRENGTH = 2,000 PSI). COARSE AND FINE
AGGREGATES SHALL CONFORM TO ASTM C404. USE COARSE GROUT FOR ALL
GROUTING EXCEPT HIGH-LIFT POURS DEFINED BY ACI 530, WHERE FINE GROUT SHALL
BE USED.
GROUT SOLID ALL CELLS WITH REINFORCEMENT.
GROUT SOLID ALL CELLS AT BELOW-GRADE CMU IN CONTACT WITH SOIL.
PROVIDE 9-GAUGE GALVANIZED STEEL WIRE JOINT REINFORCEMENT IN ALL MASONRY
CONSTRUCTION. REINFORCEMENT SHALL BE CONTINUOUS AND BE LAPPED EIGHT
INCHES AT SPLICES. CUT REINFORCEMENT AT ALL CONTROL AND EXPANSION JOINTS.
SPACE REINFORCEMENT AT 8" ON CENTER FOR PARAPETS AND BELOW GROUND
FLOOR ELEVATION. ELSEWHERE SPACE REINFORCEMENT AT 16 INCHES ON CENTER.
BEAMS AND LINTELS SHALL BEAR A MINIMUM OF 8 INCHES ONTO SUPPORTING
MASONRY, UNLESS NOTED OTHERWISE. BEARING FOR ALL BEAMS, LINTELS, JOISTS,
ETC. SHALL BE GROUTED SOLID A MINIMUM OF ONE COURSE (8 INCHES) BELOW
BEARING ELEVATION, UNLESS NOTED OTHERWISE.
PROVIDE MASONRY CONTROL JOINTS AT 25'-0" OC MAXIMUM, UNO. LOCATE JOINTS IN
ACCORDANCE WITH NCMA TEK 10-2C "CONTROL JOINTS FOR CONCRETE MASONRY
WALLS - EMPIRICAL METHOD" AT OFFSETS, SETBACKS, WALL INTERSECTIONS,
CORNERS, CHANGES IN THICKNESS, CHANGES IN HEIGHT, OR EDGE OF OPENINGS.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50
COAL TAR MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THE
STRUCTURAL ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS.
PROVIDE FULL COVERAGE OVER ITEMS INDICATED TO RECEIVE COATING.
APPLY MASTIC COATING TO ALL STEEL ITEMS THAT WILL BE IN PERMANENT CONTACT
WITH SOIL OR FILL MATERIALS IN THE COMPLETED CONSTRUCTION.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE HILTI “KWIK BOLT TZ” OR AN EQUIVALENT
SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
ANCHOR FINISH SHALL BE CARBON STEEL FOR INTERIOR EXPOSURES AND AISI 316
STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER’S
REPRESENTATIVE.
ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL IT HAS
ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
ADHESIVE ANCHORS FOR SOLID SUBSTRATES (THREADED ROD AND REBAR)
ADHESIVE ANCHORS FOR SOLID SUBSTRATES SHALL BE HILTI "HIT-HY 200" OR AN
EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
THREADED ANCHORS SHALL BE F1554 GR 55 RODS FOR INTERIOR EXPOSURES AND
AISI 316 STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
ADHESIVE ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL IT
HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
ADDITIONALLY, ADHESIVE ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR
MASONRY WITH AN AGE OF LESS THAN 21 DAYS.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN
ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED,
NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA
SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING
COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE VOLCLAY WATERSTOP-RX 101
UNLESS NOTED OTHERWISE. INSTALL IN ACCORDANCE WITH MANUFACTURER'S
WRITTEN INSTRUCTIONS.
PVC WATERSTOPS
PROVIDE FACTORY MADE WATERSTOP FABRICATIONS FOR ALL CHANGES OF
DIRECTION, INTERSECTIONS, AND TRANSITIONS LEAVING ONLY STRAIGHT BUTT JOINT
SPLICES FOR THE FIELD.
SECURE WATERSTOP IN CORRECT POSITION USING HOG RINGS OR GROMMETS
SPACED AT 12 INCHES ON CENTER ALONG THE LENGTH OF THE WATERSTOP AND WIRE
TIE TO ADJACENT REINFORCING STEEL.
PROVIDE TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING
IRONS FOR FIELD BUTT SPLICES.
FIELD BUTT SPLICES SHALL BE HEAT FUSED WELDED USING A TEFLON COATED
THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRON AT APPROXIMATELY
380 DEGREES F. FOLLOW APPROVED MANUFACTURER RECOMMENDATIONS.
LAPPING OF WATERSTOP, USE OF ADHESIVES, OR SOLVENTS SHALL NOT BE ALLOWED.
ADHESIVE ANCHORS FOR HOLLOW SUBSTRATES
ADHESIVE ANCHORS FOR HOLLOW SUBSTRATES SHALL BE HILTI "HIT-HY 270" WITH HILTI
“HIT-SC” SCREEN TUBE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE
STRUCTURAL ENGINEER, UNO.
ANCHORS SHALL BE F1554 GR 55 THREADED RODS FOR INTERIOR EXPOSURES AND AISI
316 STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
BRICK VENEER MASONRY
PROVIDE EXPANSION JOINTS IN ACCORDANCE WITH THE ARCHITECTURAL
DRAWINGS AND SPECIFICATIONS.
IF BRICK EXPANSION JOINT LOCATIONS ARE NOT INDICATED ON THE ARCHITECTURAL
DRAWINGS OR IN THE SPECIFICATIONS, SUBMIT PROPOSED EXPANSION JOINT
LOCATIONS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO
CONSTRUCTION. UNLESS INDICATED OTHERWISE, PROVIDE EXPANSION JOINTS AT
20'-0" OC MAXIMUM. LOCATE JOINTS IN ACCORDANCE WITH BIA TECHNICAL NOTE 18A
"ACCOMMODATING EXPANSION OF BRICKWORK" AT OFFSETS, SETBACKS, WALL
INTERSECTIONS, CORNERS, CHANGES IN THICKNESS, CHANGES IN HEIGHT, OR
EDGES OF OPENINGS.
ELEVATORS
CONTRACTOR SHALL COORDINATE ELEVATOR PITS, SHAFTS, SLAB OPENINGS, WALL
OPENINGS, INCLUDING ANY TEMPORARY OPENINGS NECESSARY FOR ELEVATOR
INSTALLATION, FRAMING LOCATIONS, GUIDE RAIL SUPPORTS, DIVIDER BEAMS, HOIST
BEAMS AND SUMP PITS WITH ELEVATOR SUPPLIER AND ALL OTHER AFFECTED TRADES
PRIOR TO CONSTRUCTION AS REQUIRED FOR PROPER INSTALLATION AND OPERATION.
COORDINATE ANY REQUIRED STRUCTURAL MODIFICATIONS WITH THE STRUCTURAL
ENGINEER PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY STRUCTURAL
ELEMENTS.
SEPARATION OF DISSIMILAR METALS
DISSIMILAR METALS INCLUDING STRUCTURAL SHAPES, PLATES, CONNECTORS, ETC. SHALL BE
ELECTRICALLY ISOLATED TO PREVENT GALVANIC CORROSION VIA NON-CONDUCTIVE WASHERS,
SHOULDER WASHERS, GASKETS, COATINGS, OR EQUIVALENT SUBSTITUTE APPROVED BY THE
STRUCTURAL ENGINEER, UNO.
STRUCTURAL STEEL
STRUCTURAL STEEL MEMBERS,…