Attachment 2 - VFD Asset Replacement List with Priorities.pdf

PDF 100 KB Posted

Attached to
Variable Frequency Drive (VFD) Replacement Federal contract opportunity
Solicitation number
12805B24R0034
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

About this file

This document appears to be an asset replacement list with priority levels for variable frequency drives (VFDs) related to a federal contract opportunity. The list includes details on the drive number, ID tag, drive type, horsepower, and full load amps for 42 VFD assets across three priority levels: Containment System, Containable System, and Non-Containment/Indirect Containment System.

The federal contract opportunity is for the "Variable Frequency Drive (VFD) Replacement" solicitation, with Solicitation Number 12805B24R0034, issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area. The RFP is attached, and the contract requires the replacement of the listed VFD assets with new ACH580 Ultra Low Harmonic VFD systems in varying horsepower sizes from 75HP to 150HP, including new enclosures, bypasses, and circuit breakers.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drive Number ID Tag Drive Type HP FLA Target Asset Notes

VD‐17310‐1 ACS800‐U31‐0070‐5 75 114.3 HRU‐17310‐1

VD‐17310‐2 ACS800‐U31‐0070‐5 75 114.3 HRU‐17310‐2

VD‐17310‐3 ACS800‐U31‐0070‐5 75 114.3 HRU‐17310‐3

VD‐17310‐4 ACS800‐U31‐0070‐5 75 114.3 HRU‐17310‐4

VD‐17310‐5 ACS800‐U31‐0070‐5 75 114.3 HRU‐17310‐5

VD‐17110‐1 ACS800‐U31‐0070‐5 75 114.3 PPH‐17110‐1

VD‐17110‐2 ACS800‐U31‐0070‐5 75 114.3 PPH‐17110‐2

VD‐17110‐3 ACS800‐U31‐0070‐5 75 114.3 PPH‐17110‐3

VD‐17360‐1 ACS800‐U31‐0070‐5 75 114.3 AH‐17360‐1

VD‐17265‐1 ACS800‐U31‐0070‐5 75 114.3 HRU‐17265‐1

VD‐17265‐2 ACS800‐U31‐0070‐5 75 114.3 HRU‐17265‐2

VD‐17350‐1 ACS800‐U31‐0070‐5 75 114.3 HRU‐17350‐1

VD‐17350‐2 ACS800‐U31‐0070‐5 75 114.3 HRU‐17350‐2

VD‐17331‐1 ACS800‐U31‐0100‐5 100 132.5 AH‐17331‐1

VD‐17331‐2 ACS800‐U31‐0100‐5 100 132.5 AH‐17331‐2

VD‐17250‐1 ACS800‐U31‐0100‐5 100 132.5 HRU‐17250‐1

VD‐17250‐2 ACS800‐U31‐0100‐5 100 132.5 HRU‐17250‐2

VD‐17250‐3 ACS800‐U31‐0100‐5 100 132.5 HRU‐17250‐3

VD‐17250‐4 ACS800‐U31‐0100‐5 100 132.5 HRU‐17250‐4

VD‐27102‐5 ACS800‐U31‐0100‐5 100 132.5 PCH‐27102‐5

VD‐27102‐6 ACS800‐U31‐0100‐5 100 132.5 PCH‐27102‐6

VD‐17301‐1 ACS800‐U31‐0120‐5 125 157.1 AH‐17301‐1

VD‐17301‐2 ACS800‐U31‐0120‐5 125 157.1 AH‐17301‐2

VD‐17301‐3 ACS800‐U31‐0120‐5 125 157.1 AH‐17301‐3

VD‐17301‐4 ACS800‐U31‐0120‐5 125 157.1 AH‐17301‐4

VD‐17241‐1 ACS800‐U31‐0120‐5 125 157.1 AH‐17241‐1

VD‐17241‐2 ACS800‐U31‐0120‐5 125 157.1 AH‐17241‐2

VD‐17241‐3 ACS800‐U31‐0120‐5 125 157.1 AH‐17241‐3

VD‐17241‐4 ACS800‐U31‐0120‐5 125 157.1 AH‐17241‐4

VD‐27102‐1 ACS800‐37‐0170‐5+C129‐P902 150 170 PCH‐27102‐1

VD‐27102‐2 ACS800‐37‐0170‐5+C129‐P902 150 170 PCH‐27102‐2

VD‐27102‐3 ACS800‐37‐0170‐5+C129‐P902 150 170 PCH‐27102‐3

VD‐27102‐4 ACS800‐37‐0170‐5+C129‐P902 150 170 PCH‐27102‐4

VD‐27110‐1 ACS800‐37‐0170‐5+C129‐P902 150 170 PCW‐27110‐1

VD‐27110‐2 ACS800‐37‐0170‐5+C129‐P902 150 170 PCW‐27110‐2

VD‐27110‐3 ACS800‐37‐0170‐5+C129‐P902 150 170 PCW‐27110‐3

VD‐27110‐4 ACS800‐37‐0170‐5+C129‐P902 150 170 PCW‐27110‐4

VD‐27110‐5 ACS800‐37‐0170‐5+C129‐P902 150 170 PCW‐27110‐5

Priority 1 ‐ Containment System Priority 2 ‐ Containable System

Priority 3 ‐ Non Containment System / Indirect Containment System

ACH580, 75Hp, 460V, Ultra Low Harmonic VFD Completely new ACH580 ULH systems with new enclosures to replace the existing boxes. Includes new Bypass , new Circuit breaker, new NEMA 1

Enclosure of the same size

ACH580, 100Hp, 460V, Ultra Low Harmonic VFD Completely new ACH580 ULH systems with new enclosures to replace the existing boxes. Includes new Bypass , new Circuit breaker, new NEMA 1

Enclosure of the same size

ACH580, 125Hp, 460V, Ultra Low Harmonic VFD Completely new ACH580 ULH systems with new enclosures to replace the existing boxes. Includes new Bypass , new Circuit breaker, new NEMA 1

Enclosure of the same size

ACH580, 150Hp, 460V, Ultra Low Harmonic VFD Completely new ACH580 ULH systems with new enclosures to replace the existing boxes. Includes new Bypass , new Circuit breaker, new NEMA 1

Enclosure.The 150Hp (180A) drives in the cup will not have the same size enclosure. The new enclosure for the 150's would be smaller at

84" tall x 36" wide x 21" deep.