Attachment 2 Bldg 90145 Drawings 5.2.23.pdf

PDF 13 MB Posted

Attached to
ADD/Alter Space Deficiencies, 8 SOS, Bldg 90145
Solicitation number
FA441723R0002
Issued by

About this file

This document provides details on a federal solicitation from the Department of the Air Force Special Operations Command to add and alter space deficiencies at Building 90145. The solicitation number is FA441723R0002 and seeks contractors to perform work including construction and renovations at the specified building. The solicitation includes attachment of technical drawings related to the building plans in a 13MB PDF file. Interested parties should review the drawings and specifications in preparation to bid on the opportunity. The response due date and anticipated award date are not stated but follow standard FAR part 52.214-3 timeframes.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PO

OL

P OOL

PO

OL

PO

OL

PO

OL

MARY ESTHER, FLORIDA

91065

90527

9915799156

31022

31022

90639

91006

91158

9113191129

99901 99902

90395 90080

90050

90050

91362

99147

9053590535

90535

90523

90209

90108

99108

90580

90581

91404

99326

90727

90800

90536

90534

91157

91107

91168

90306

90905

90917

99958

91059

91058

90086

90311

90508

90500

90611

90730

30041

90083

90356

99103

90524

99121

90626

90749

90757

90813

91041

91263

91264

92478 92479

90351

90363

90360

90513

29077 29077

91043

91038

90005

90734

90581

90534

29073

29073

90396 90396

29075

29075

29075

29075

91124

91149

93605

90379

90380

91101

90506

92547

90628

99154

99077

90021

90503

91537

92557

90414

90209

92540

90038

90427

90412

99009

93576

90710

91141

93318

99005

92418

91625

90221

90433

90228

99049

90612

90065

90365

90349

92536

93357

90425

92509

92485

90059

90067

91262

91259

92500

93405

90408

92031

92078

92075

90020

90028

90421

90206

90630

91113

91258

93701

90332

91042

91136

90060

92077

90010

91126

90708

90812

91302

92564

93621

90113

93333

93332

92439

90700

90758

92531

93346

90428

92276

92108

90002

92552

91153

92542

91041

90353

90640

90501

93530

92049

93565

90718

92066

92507

90322

91250

90603

90231

92408

92465

90829

91049

90135

92096

92442

91013

93454

90712

92463

92101

90420

99065

93626

90519

92073

92003 92002

92020

90029

91257

92018

90055

92467

93464

92402

90323

90407

90367

90050

90551

92086

90220

90310

90755

90034

91144

92468

90816

99141

92440

92525

91021

90423 91028

90057

90061

90066

90638

90553

91260

93437

90625

92517

90624

91036

92508

92459

93413

91268

92074

92106

92104 92041

92053

92056

92070

92524

92535

92506 92543

92097

92067

90404

90720

90632

92045

90203

91114

91119

91538

93640

90431

90838

99098

91033

92401

91000

90079

92444

90331

92511

90517

90705

92092

90117

92530

92445

91147

90343

90373

93549

93301

92545

93461

92523

91515

91024

91027

92433

92518

91361

92473

99031

92521

90140

90402

93476

92544

93429

92063

92088

91370

90518

90036

90417

91020

92062

99126

91351

90535

99019

92562

99158

91365

91603

91025

90926

93432

91601

91120

92466

90505

91035

93421

90074

90073

90039

93637

93389

92539

92036

92012

90213

92044

91500

99117

91266

92428

92460

93566

91310

91135

91106

90329

92503

90109

90763 90418

90714

93541

99010

90361

92047

90810

90627

90823

92514

93325

92555

92083

90742

93349

91164

91052

90368

92095

99137

92533

92038

93398

90833

90081

91325

91360

91007

90743

90811

91156

90916

92079

92425 92400

92015

92407

91099

92527

90601

93510

93309

90355

92054

90070

90111

90357

90023

92471

92441

90102

93304

93317

93354

90911

91145

90076

92556

91152

91030

91132

91034

92033

92450

92502

99146

99018

99094

90729

91057 92103

90387

90381

91161

92515

92446

92025

92464

90951

91162

90052

92529

93501

92014

90134

90613

92537

93493

93629

90362

99004

90141

93517

90037

92064

90392

90629

93397

90069 90068

99041

91510

99057

90388

92424

91112

90523

91133

92094

90409

90430

90711

92048

93368

93485

90577

90075

99107 99106

99016

99014

99020

99048

99090

99104

90607

92541

92516

99150

99535

92501

92463

92419 92426

90330

91154

92089

90747

90509

90522

93538

92505

99058

92023

91032

92034

99067

91546

90210

92005

99024

99025

99051 99127

99719 99718 99717

99716

99023

90609

90085

92461

92009

92434

93445

93608

91122

90724

92051

92008

92001

92549

90626

92435

93453

90327

93645

92548

90701

92553

93365

91330

90809

90432

92437

91105

93596

90580

93650

93444

91103

93586

91104

90413

92087

92522

90207

99115

92100

92004

90827

93500

90320

93556

90333

91053

90058

92058

92068

92071

92076

92072

92010

92055 90056

93486

93373

90817

90230

91146

93522

92026 92027

92040

90436

90377

90054

90642

90223

90001

93581

91012

92022

90378

92451

93573

92452

90606

91155

92436

91054

90145

90717

92030 92032

90372

90731

90328

92069

92024

90084

90005

93509

92455

92528

90703

92000

92013

91252

91055

99043

90802

91037

92011

91140

91023

91151

92430

90759

92420

92275

90610

90801

91031

90121

92039

92432

90015

91009

91039

90635

99068

90928

90616

90105

92406

93477

90615

92035

92052

90707

90229

93613

90375

90760

90049

92082 92061

92538

90337

91130

91363

90410

91350

91050

92050

92090

93381 93341

90950

99162

99001

90131

99060

90552

91016

99105 99007

99083

99055

99056

90390

99044

99126 99145

99022

90825

90358

92098

90347

91163

92102

90008

91300

92105

90621

99059

92099

99116

90048

92084

92546

90374

90300

91142

92107

92016 92017

90419

92551

92037

9204392042

92057

92513

91137

92059

90617

93653

92080

90215

90382

92404

90232

93386

90302

93414

99142

90510

92091

90521

93557

91520

91255

90702

90033

92438

93597

90935

92065

93422

90369

90532

90619

90035

90208

90618

90128

90822

90748

92472

90137

93469

90371

93618

9102990352

92060

90138

90063

90806

90525

91047

92021 92019

92028

90326

90438

93589

90713

92403

90064

90370

90115

92519

92449

90426

90062

90636

91045

99030

90531

90051

91254

90304

99500

91056

90366

91364

92429

99042

91303

91148

92093

90880

91301

90815

99118

99029

99061

90225

90416

92046

90439

90053

91265

92085

90030

91400

92550

90716

92427

93542

91159

90359

92469

90032

90106

90637

90325

91307

99045

91048

90761

90101

92081

92431

90600

93660

90434

9200792006

90308

90043

92470

90918

Tully Street

Kissam Street

M

AY

S

TR

EE

T

Downs R oad

W alkup W ay

Martin Luther K ing

Downs Road

Kanuha Drive

Blessinger D rive

Bartley Street

Mitchell Road

Independence Road

Te rry

A ve nu e

McClean Street

Hartson Street

US98

Tully Street

M ai nt en an ce

H au l R oa

US98

Howie Walters Way

Lielmanis Avenue

US98

Ke rw oo d

R oa d

Cod y A ve nu e

Lukasik Avenue

Tully Street

Red H ors e R oa d

Hamby Place

Westfall Circle

Bedel Street

Tu lly

S tre e t

Tully Street

Bennett A venue

C ru z Av en ue

Red Horse Road

C ru z Av en ue

Frazier Street

Be nn et t A ve nu e

Bedel Street

Independence Road

W alkup W ay

Corlew Road

McMillan Street

US98

W ea ve r A ve nu e

Schmauss Lane

Hume Drive

Clark Road

Gelshlager Street

Whitbeck Street

C am pa ig ne S tre et Purcell Drive

C ody Ave nue

US98

Independence Road

O 'N ei l A ve nu e

US98

McIntosh Court

Hume Drive

Harrison Drive

Acha Drive

H um e D riv e

Walters Drive

Hodges Street

Lewis Drive

Hume Drive

Galvan Street

Bland Street

Hume Drive

Grimm Lane unk unk

Tully Street

Red Horse Road

Bakke Street

M ay o St re et

Bakke Street

Tupelo Circle

Red Horse Road

Sim pson Avenue

Tully Street

Le to ur ne au C irc le

Let ourneau Cir cle

90140

90225

MARTIN LUTHER KING JR. BLVD

INTERSECTION ENTRANCE

COMMERCIAL VEHICLE INSPECTION

ENTRANCE PASS & ID OFFICE

HURLBURT EAST GATE, NO

COMMERCIAL ENTRANCE

FIRE DEPARTMENT BLDG 90734

CONTRACTOR HAUL ROUTE

NEW ADDITION

EXISTING

BLDG.

90145

IA

R

E

OF

RC

SP

EC

IA

AN

N P

ER

L O

AT

IO

M M

SC

O

D

SHEET REFERENCE:

DA

TE

SHEET NUMBER:

OF

DE

SC

RI

PT

IO

N

RE

V

AI

R

FO

RC

E

SP

EC

IA

L

OP

ER

AT

IO

NS

C

OM

M

AN

D

SP

EC

IA

L

OP

ER

AT

IO

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

ON

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

G-001

05-02-2023

TI

TL

E

SH

EE

T

JGH

JGH

CP1033732

BU

IL

D

IN

G

A D

D

IT

IO

N

SOF ADD/ALTER SPACE DEFICIENCIES

8 SOS, BLDG. 90145

HURLBURT FIELD, FLORIDA

CP1033732

INDEX OF DRAWINGS

SHEET

NUMBER SHEET NAME

GENERAL

G-001 TITLE SHEET

G-002 LIFE SAFETY PLAN

CIVIL

C-101 EXISTING CONDITIONS / DEMOLITION PLAN

C-201 SITE GEOMETRY PLAN

C-301 SITE GRADING PLAN

C-401 SITE UTILITY PLAN

C-501 SECTIONS & DETAILS

STRUCTURAL

S-001 GENERAL NOTES

S-002 GENERAL NOTES & WIND INFORMATION

S-101 FOUNDATION & SLAB-ON-GRADE PLAN

S-102 ROOF FRAMING PLAN

S-301 WALL SECTIONS

S-302 WALL SECTIONS

S-303 WALL SECTIONS

S-401 FOUNDATION DETAILS

S-501 CMU DETAILS

ARCHITECTURAL

A-001 LEGEND AND ABBREVIATIONS

AD101 FLOOR PLAN - DEMOLITION

A-110 FLOOR PLAN - NEW WORK

A-140 ROOF PLAN - DEMOLITION AND NEW WORK

A-150 CEILING PLAN - DEMOLITION AND NEW WORK

A-201 EXTERIOR ELEVATIONS

A-301 BUILDING SECTIONS

A-310 WALL SECTIONS

A-311 WALL SECTIONS

A-501 DETAILS

A-502 DETAILS

A-601 DOOR SCHEDULE AND DETAILS

A-602 DETAILS

INTERIOR

I-120 FINISH SCHEDULE

FIRE PROTECTION

FA-001 FIRE ALARM NOTES, LEGEND, & MOUNTING DETAIL

FA-101 FIRE ALARM PLAN

FA-601 FIRE ALARM RISER DIAGRAM

FX-001 GENERAL FIRE PROTECTION INFORMATION

FX-002 GENERAL FIRE PROTECTION INFORMATION

FX-101 OVERALL PLAN - NEW WORK - FIRE PROTECTION

MECHANICAL

M-001 GENERAL MECHANICAL INFORMATION

MH101 FLOOR PLAN - NEW WORK - HVAC

MP101 OVERALL PLAN - NEW WORK - PIPING

M-501 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULES

M-701 MECHANICAL CONTROLS AND SCHEMATICS

ELECTRICAL

E001 ELECTRICAL GENERAL NOTES AND LEGEND

EP101 OVERALL POWER PLAN

EP102 NEW WORK POWER PLAN

EL101 NEW WORK LIGHTING PLAN

E601 LIGHTING DETAILS & LIGHTING FIXTURE SCHEDULE

E602 ELECTRICAL RISER DIAGRAM & PANEL SCHEDULE

TELECOMMUNICATIONS

T-001 TELECOMMUNICATIONS GENERAL NOTES AND LEGEND

T-111 TELECOM FIRST FLOOR PLAN

T-601 TELECOM DETAILS AND SINGLE LINE DIAGRAMS

BASE MAP

NORTH

PROJECT SITE

NORTH

E-1

E-2

E-3

E-E E-G E-H E-I E-J

A B C D E

STORAGE / WORK

ROOM

HVAC / ELEC

TRAVEL DISTANCE: 56'

TRAVEL DISTANCE: 58'

TR

AV

EL

D

IS

TA

NC

E:

TRAVEL DISTANCE: 51'

LIFE SAFETY LEGEND

EXIT PATH WITH TOTAL TRAVEL

DISTANCE AND DIRECTION OF TRAVEL.

TRAVEL

DISTANCE: XX'

EXIT SIGN (SHADED REGION

INDICATES LIGHTED SIDE)

ROOM NAME / NUMBER DESIGNATION

ROOM NAME

LIFE SAFETY DATA -

NATIONAL FIRE PROTECTION

ASSOCIATION (NFPA) LIFE SAFETY

CODE 101, 2018 EDITION

OCCUPANCY CLASSIFICATION: NFPA 2018 - S1 ORDINARY HAZZARD STORAGE

CONSTRUCTION TYPE: NFPA 2018 - TYPE II(000) SPRINKLERED

FIRE RESISTANCE: NFPA 2018 TABLE A.8.2.1.2 - NONE REQUIRED FOR FRAME,

EXTERIOR WALLS OR PARTITIONS

MEANS OF EGRESS:

OCCUPANT LOAD:

TOTAL: 8 OCCUPANTS

STORAGE (1:500) = 3925 SF / 500 GSF = 8 OCCUPANTS

EGRESS WIDTH: 0.2 IN./PERSON = .2 IN. X 8 = 1.6" REQUIRED

MINIMUM PROVIDED 36" WIDE, 34" CLEAR DOORS

NUMBER OF EXITS: (NFPA 42.2.5) OCCUPANT LOAD < 49 = 2 EXITS REQUIRED

4 PROVIDED

TRAVEL DISTANCE:

COMMON PATH OF TRAVEL: 100' MAX. (NFPA 42.2.5)

12' MAX - COMPLIES

MAXIMUM TRAVEL DISTANCE TO EXIT: 400' MAX. (NFPA 42.2.6)

58' - COMPLIES

DEAD END: 100' MAX. (NFPA 42.2.5)

NO DEAD END CORRIDORS - COMPLIES

IA

R

E

OF

RC

SP

EC

IA

AN

N P

ER

L O

AT

IO

M M

SC

O

D

SHEET REFERENCE:

DA

TE

SHEET NUMBER:

OF

DE

SC

RI

PT

IO

N

RE

V

AI

R

FO

RC

E

SP

EC

IA

L

OP

ER

AT

IO

NS

C

OM

M

AN

D

SP

EC

IA

L

OP

ER

AT

IO

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

ON

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

G-002

05-02-2023

LIF

E

SA

FE

TY

P

LA

N

JGH

JGH

CP1033732

BU

IL

D

IN

G

A D

D

IT

IO

N

1/8" = 1'-0"G-002

1 FLOOR PLAN - LIFE SAFETY

PLAN

NORTH

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

KEY PLAN

EXISTING

B90145

NEW

ADDITION

2.04 A QUALIFIED GEOTECHNICAL ENGINEER SHALL VERIFY CONDITION AND/OR ADEQUACY OF ALL SUBGRADES, FILLS AND BACKFILLS BEFORE PLACEMENT OF FOUNDATIONS, FOOTINGS, SLABS, WALLS, FILLS, BACKFILLS, ETC. SHOULD THE CONTRACTOR FIND UNDESIRABLE SOILS, HE SHALL STOP WORK AND IMMEDIATELY CONTACT THE CONTRACTING OFFICER. ALL FOOTINGS SHALL REST EITHER ON UNDISTURBED SOIL OR A MANUALLY OPERATED VIBRATORY SLED OR TAMPER SHOULD BE USED TO DENSIFY ANY SOILS IN THE BOTTOM OF THE FOOTING TRENCHES LOOSENED DURING THE EXCAVATION OPERATION.

2.05 SIDES OF FOUNDATIONS SHALL BE FORMED UNLESS CONDITIONS PERMIT EARTH FORMING. FOUNDATIONS POURED AGAINST THE EARTH REQUIRE THE FOLLOWING PRECAUTIONS: SLOPE SIDES OF EXCAVATIONS AS APPROVED BY GEOTECHNICAL ENGINEER AND

CLEAN UP SLOUGHING BEFORE AND DURING CONCRETE PLACEMENT.

2.06 CONTRACTOR IS RESPONSIBLE FOR ADEQUATELY PROTECTING ALL EXCAVATION SLOPES.

2.07 DEWATER TO AT LEAST TWO FEET BELOW BOTTOM OF LOWEST FOUNDATION IF GROUNDWATER IS ENCOUNTERED.

2.08 SLAB-ON-GRADE REQUIREMENTS:

A. UNLESS NOTED OTHERWISE, THE SLAB-ON-GRADE SHALL BE A MINIMUM OF 6 INCHES THICK, PLACED ON COMPACTED SUBGRADE, AND REINFORCED WITH #3 AT 12"O.C. EACH WAY WITH 2 1/2" CLEAR COVER TO EARTH. FOR SLAB REINFORCING, PROVIDE "CLASS B" LAPS AT SPLICE LOCATIONS AND STAGGERED SPLICE LOCATIONS.

B. PLACE CONTRACTION OR CONSTRUCTION JOINTS AT LOCATIONS INDICATED BY “S.C.J.” SAWCUT CONTRACTION JOINTS AS SOON AFTER POURING AS POSSIBLE, WHEN CONCRETE WILL NOT RAVEL; 12 HRS. MAX. CURE CONCRETE IN ACCORDANCE WITH ACI 301. BEGIN CURING IMMEDIATELY AFTER POURING TO LIMIT CRACKING PRIOR TO SAWCUTTING CONTRACTION

JOINTS.

C. SUBGRADE SHALL BE PREPARED AS RECOMMENDED IN THE SPECIFICATIONS FOR PROOF ROLLING AND FILL PLACEMENT

FOR STRUCTURAL EXCAVATION.

D. VAPOR BARRIER SHALL BE MINIMUM 15 MIL. THICK AND CONFORM TO ASTM E1745, CLASS A, B, OR C. VAPOR BARRIER SHOULD BE PLACED ON COMPACTED SUBGRADE. VAPOR BARRIER SHOULD BE OVERLAPPED 6 IN. AND TAPED AT THE

JOINTS AND CAREFULLY FITTED AROUND SERVICE OPENINGS.

3.00 REINFORCED CONCRETE

3.01 ALL CONCRETE WORK SHALL CONFORM TO ACI 301-10, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS. DESIGN IS BASED ON ACI 318-14, BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE. DETAIL CONCRETE REINFORCEMENT AND ACCESSORIES IN ACCORDANCE WITH ACI 315, DETAILING MANUAL. DETAIL ALL CONCRETE WALLS AND BEAMS ON THE SHOP DRAWINGS IN ELEVATION UNLESS SPECIFICALLY APPROVED OTHERWISE. SUBMIT SHOP DRAWINGS FOR APPROVAL, SHOWING ALL FABRICATION DIMENSIONS AND LOCATIONS FOR PLACING REINFORCING STEEL AND ACCESSORIES. DO NOT BEGIN FABRICATION

UNTIL SHOP DRAWINGS ARE COMPLETED AND REVIEWED.

3.02 UNLESS NOTED OTHERWISE, ALL CONCRETE SHALL BE NORMAL WEIGHT AND HAVE THE FOLLOWING MINIMUM 28 DAY

COMPRESSIVE STRENGTHS:

A. FOUNDATIONS 3500 PSI

B. SLAB-ON-GRADE 3500 PSI

CONCRETE MAY CONTAIN A PROPERLY DESIGNED SUPERPLASTICIZER FOR WORKABILITY.

MINIMUM CONCRETE FLEXURAL STRENGTH (MODULUS OF RUPTURE) SHALL BE:

A. SLAB-ON-GRADE 440 PSI

3.03 REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 UNLESS NOTED OTHERWISE.

3.04 THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND REVIEWED BY THE CONTRACTING OFFICER.

RESPONSIBILITY FOR OBTAINING THE REQUIRED DESIGN STRENGTH IS THE CONTRACTOR'S.

3.05 USE OF CALCIUM CHLORIDE, CHLORIDE IONS, OR OTHER SALTS IN CONCRETE IS NOT PERMITTED.

3.06 CHAMFER OR ROUND ALL EXPOSED CORNERS A MINIMUM OF 3/4".

3.07 TIE ALL REINFORCING STEEL AND EMBEDMENTS SECURELY IN PLACE PRIOR TO PLACING CONCRETE. PROVIDE SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF REINFORCEMENT WITHIN SPECIFIED TOLERANCE DURING ALL CONSTRUCTION

ACTIVITIES. "STICKING” DOWELS INTO WET CONCRETE IS NOT PERMITTED.

3.08 PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE; SPLICE ONLY AS SHOWN OR APPROVED; STAGGER SPLICE WHERE POSSIBLE; USE FULL TENSION SPLICE (CLASS "B") UNLESS NOTED OTHERWISE. DOWELS SHALL MATCH THE SIZE AND SPACING OF THE SPECIFIED REINFORCEMENT AND SHALL BE LAPPED WITH FULL TENSION SPLICES (CLASS "B") UNLESS NOTED OTHERWISE.

TERMINATE BARS WITH STANDARD HOOKS. PROVIDE CLASS "B" LAP SPLICE CORNER BARS FOR ALL CONTINUOUS REINFORCING AT

CORNER LOCATIONS, INCLUDING BUT NOT LIMITED TO FOOTINGS AND WALLS.

3.09 REINFORCING STEEL SHALL HAVE THE FOLLOWING CONCRETE COVER UNLESS NOTED OTHERWISE (PER ACI 318-05 PAR.7.7.1):

A. CONCRETE AGAINST EARTH (NOT FORMED): 3"

B. FORMED CONCRETE EXPOSED TO THE EARTH OR WEATHER:

1. #6 THROUGH #18 BARS: 2"

2. #5 BARS AND SMALLER: 1-1/2"

C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER:

1. SLABS AND WALLS: 1"

2. BEAMS (STIRRUPS) AND COLUMNS (TIES): 1-1/2"

3.10 DO NOT PLACE DUCTS EXCEEDING ONE-THIRD THE SLAB OR WALL THICKNESS WITHIN THE SLAB OR WALL UNLESS SPECIFICALLY

SHOWN AND DETAILED ON STRUCTURAL DRAWINGS.

3.11 DO NOT WELD OR TACK WELD REINFORCING STEEL UNLESS APPROVED OR DIRECTED BY THE STRUCTURAL ENGINEER.

3.12 SHORING SHALL REMAIN IN PLACE UNTIL CONCRETE HAS ATTAINED 75% OF ITS 28-DAY STRENGTH.

3.13 ALL REINFORCING STEEL PLACEMENTS SHALL BE REVIEWED BY THE CONTRACTING OFFICER, OR BY A REPRESENTATIVE

RESPONSIBLE TO HIM. (RE: ACI 318 PAR. 1.3.1)

3.14 FOR CONCRETE PADS SEE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS.

1.00 GENERAL NOTES

1.01 THESE STRUCTURAL NOTES SHALL BE APPLIED WITH THE TECHNICAL SPECIFICATIONS IN THE SPECIFICATIONS MANUAL. ANY CONFLICTING REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER-OF-RECORD FOR RESOLUTION BEFORE PROCEEDING WITH FABRICATION OR

CONSTRUCTION.

1.02 ALL CONSTRUCTION SHALL CONFORM TO THE INTERNATIONAL BUILDING CODE, 2018.

1.03 THE STRUCTURE HAS BEEN DESIGNED UTILIZING THE FOLLOWING REFERENCES:

A. UFC 1-200-01, GENERAL BUILDING REQUIREMENTS, CHANGE 1, 24 FEBRUARY 2023

B. UFC 3-301-01, STRUCTURAL ENGINEERING, CHANGE 1, 4 FEBRUARY 2022

C. UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARD FOR BUILDINGS, CHANGE 2,

30 JULY 2022

D. INTERNATIONAL BUILDING CODE, 2018

E. ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

F. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

G. ACI 360 R-10, DESIGN OF SLAB ON GRADES

H. AISC 360-10, SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION

I. TMS 402/602-16, BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES J. ANSI/SDI, AMERICAN NATIONAL STANDARDS INSTITUTE / STEEL DECK INSTITUTE, RD-2010

STANDARD STEEL ROOF DECK

1.04 WIND LOADS - STRUCTURE HAS BEEN DESIGNED TO CONFORM TO THE WIND PROVISIONS OF ASCE 7-10.

SEE WIND PRESSURE DIAGRAM & CHART FOR THE FOLLOWING:

A. ULTIMATE BASIC WIND SPEED

B. BUILDING RISK CATEGORY

C. WIND EXPOSURE CATEGORY

D. INTERNAL PRESSURE COEFFICIENT

E. COMPONENT & CLADDING WIND PRESSURES

1.05 EARTHQUAKE LOADS - THE IBC REQUIRES THAT EARTHQUAKE DESIGN DATA BE PROVIDED REGARDLESS OF WHETHER OR NOT SEISMIC LOADS GOVERN THE LATERAL FORCE RESISTING SYSTEM DESIGN. THE

DESIGN DATA IS AS FOLLOWS:

A. SEISMIC DESIGN CATEGORY: B

B. SPECTRAL RESPONSE COEFFICIENTS

1. Ss = 0.08g Sds = 0.09g

2. S1 = 0.05g Sd1 = 0.08g

C. SITE CLASSIFICATION: D

D. BASIC SEISMIC-FORCE-RESISTING SYSTEM: STEEL ORDINARY MOMENT FRAMES

E. SEISMIC BASE SHEAR (V): 10 KIPS

F. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE

1.06 DESIGN GRAVITY LOADS ARE AS FOLLOWS:

A. SUPERIMPOSED DEAD LOADS:

1. ROOFING AND INSULATION: 3 PSF

2. MECHANICAL, ELECTRICAL, PLUMBING: 6 PSF

3. CEILINGS: 8 PSF

B. LIVE LOADS: (MAY BE REDUCED PER CODE)

1. ROOFS: 20 PSF

2. SLAB-ON-GRADE: 100 PSF

3. MECHANICAL/ ELECTRICAL/STORAGE ROOMS: 150 PSF

1.07 DRAWINGS SHOW TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. FOR DETAILS NOT SPECIFICALLY

SHOWN, PROVIDE DETAILS SIMILAR TO THOSE SHOWN.

1.08 THE DESIGN, ADEQUACY, AND SAFETY OF ERECTION BRACING, SHORING, TEMPORARY SUPPORTS, ETC., ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

1.09 CONTRACTOR SHALL MAKE NO DEVIATION FROM DESIGN DRAWINGS WITHOUT WRITTEN APPROVAL OF THE CONTRACTING OFFICER. FOR ADDITIONAL OPENINGS NOT SHOWN ON THE STRUCTURAL DRAWINGS, SEE ARCHITECTURAL, MECHANICAL, AND PLUMBING DRAWINGS. NOTIFY CONTRACTING OFFICER OF ANY

CONFLICT AND/OR OMISSION.

1.10 REVIEW OF SUBMITTALS AND/OR SHOP DRAWINGS BY THE CONTRACTING OFFICER OR OTHERS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO REVIEW AND CHECK SHOP DRAWINGS BEFORE SUBMITTAL TO THE CONTRACTING OFFICER. THE CONTRACTOR REMAINS SOLELY RESPONSIBLE FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS, AND DIMENSIONS SPECIFIED IN THE CONTRACT DOCUMENTS.

CONTRACTOR IS ALSO RESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, AND

PROCEDURES OF CONSTRUCTION.

2.00 FOUNDATIONS AND SLAB-ON-GRADE

2.01 THE DESIGN OF FOUNDATIONS, RETAINING WALLS AND SLAB ON GRADE IS BASED ON THE CRITERIA ESTABLISHED IN THE GEOTECHNICAL REPORT BY UNIVERSAL ENGINEERING SCIENCES, PENSACOLA, FLORIDA; UES PROJECT NO. 1730.2000003.0000; UES REPORT NO. 1750983, DATED FEBRUARY 28, 2020. THE RECOMMENDATIONS OF THAT REPORT SHALL BE CONSIDERED AN INTEGRAL PART OF THE CONTRACT

DOCUMENTS.

2.02 A QUALIFIED GEOTECHNICAL ENGINEER SHALL CHECK COMPACTION OF THE FOOTINGS. THE SOILS IMMEDIATELY BENEATH ALL FOOTINGS SHOULD BE COMPACTED FOR A MINIMUM DEPTH OF 12 INCHES TO A MINIMUM OF 95% OF THE SOIL’S MAXIMUM DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST

(ASTM D1557) USING A LARGE TAMPER.

2.03 SHALLOW FOUNDATIONS HAVE BEEN DESIGNED BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF

1,500 PSF.

4.00 STRUCTURAL STEEL, STEEL JOISTS, STEEL DECK AND ENGINEERED STAIRS AND RAILINGS

4.01 STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED ACCORDING TO AISC "SPECIFICATION FOR STRUCTURAL

STEEL BUILDINGS, LATEST EDITION.

4.02 SUBMIT SHOP DRAWINGS PREPARED IN ACCORDANCE WITH AISC MANUAL "DETAILING FOR STEEL CONSTRUCTION", LATEST EDITION. STEEL FABRICATOR SHALL SUPPLY ANCHOR BOLT LOCATION DRAWINGS. DO NOT BEGIN FABRICATION UNTIL SHOP

DRAWINGS ARE COMPLETED AND REVIEWED.

4.03 STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. STRUCTURAL STEEL SHAPES, PLATES, ANGLES, AND CHANNELS SHALL CONFORM TO ASTM A36 UNLESS NOTED OTHERWISE. STRUCTURAL TUBING SHALL CONFORM TO ASTM A500, GRADE B, FY = 46 KSI, UNLESS NOTED OTHERWISE. STEEL PIPE SHALL CONFORM TO ASTM A501 OR ASTM A53, TYPE E OR S, GRADE B. ANCHOR BOLTS SHALL CONFORM TO ASTM F1554 GR. 36 UNLESS NOTED OTHERWISE.

4.04 BOLTS SHALL CONFORM TO ASTM A325, 3/4-INCH DIAMETER MINIMUM, UNLESS NOTED OTHERWISE. COMPRESSIVE-WASHER- TYPE DIRECT TENSION INDICATORS OR TWIST-OFF-TYPE TENSION-CONTROL BOLTS CONFORMING TO RCSC SHALL BE PROVIDED AT ALL

BOLTED CONNECTIONS PER UFC 3-301-01.

4.05 ALL COLUMNS, UNLESS NOTED OTHERWISE, SHALL BEAR ON 1 1/2" GROUT BED. GROUT SHALL BE NON-SHRINK, NON-METALLIC

AND SHALL BE PLAED PRIOR TO POURING OF UPPER FLOOR LEVELS.

4.06 HEADED STUD SHEAR CONNECTORS: ASTM A 108, GRADES 1010 THROUGH 1020, HEADED-STUD TYPE, COLD-FINISHED CARBON STEEL; AWS D1.1, TYPE B. USE AUTOMATIC END WELDING OF HEADED-STUD SHEAR CONNECTORS ACCORDING TO AWS D1.1 AND

MANUFACTURER’S WRITTEN INSTRUCTIONS.

4.07 DEFORMED BAR ANCHORS (INDICATED AS “DBA” ON PLANS): DEFORMED STEEL REINFORCING BARS IN ACCORDANCE WITH ASTM A-496 SPECIFICATIONS, YIELD STRENGTH 70 KSI. USE AUTOMATIC END WELDING OF HEADED-STUD SHEAR CONNECTORS

ACCORDING TO AWS D1.1 AND MANUFACTURER’S WRITTEN INSTRUCTIONS.

4.08 USE PRE-QUALIFIED WELDED JOINTS AS PER AISC, AND AWS D1.1 "STRUCTURAL WELDING CODE." USE ONLY CERTIFIED WELDERS; ALL ELECTRODES SHALL CONFORM TO AWS A5 GRADE E70XX. BARE ELECTRODE AND GRANULAR FLUX SHALL CONFORM TO AWS A5, F70 AWS FLUX CLASSIFICATION. MINIMUM WELD SIZE TO BE 3/16" FILLET WELD, U.N.O.

4.09 CUTS, BOLTS, COPING, ETC. REQUIRED FOR WORK OR OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS AND MADE IN THE SHOP. CUTS OR BURNING HOLES IN STRUCTURAL STEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED.

4.10 SHOP CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS MAY BE WELDED OR BOLTED. FIELD CONNECTIONS NOT

SPECIFICALLY DETAILED ON THE DRAWINGS SHALL BE BOLTED, WHERE POSSIBLE.

4.11 WHEN SPECIFICALLY NOT DETAILED ON THE DESIGN DRAWINGS PROVIDE THE FOLLOWING BEAM CONNECTIONS:

A. PROVIDE CONNECTIONS SIMILAR TO THOSE SHOWN IN TYPICAL DETAILS IN THESE DRAWINGS.

B. WHERE BEAM REACTIONS ARE SHOWN, CONNECTIONS SHALL DEVELOP THE REACTION GIVEN.

C. WHEN BEAM REACTIONS ARE NOT SHOWN, CONNECTIONS SHALL FOLLOW TYPICAL CONNECTION DETAILS PROVIDED IN

THIS SET AND SHALL BE DESIGNED TO SUPPORT ONE-HALF THE TOTAL UNIFORM LOAD CAPACITIES SHOWN IN THE ALLOWABLE UNIFORM LOAD TABLES, PART 2 OF THE AISC MANUAL, FOR THE GIVEN BEAM, SPAN AND GRADE OF STEEL

SPECIFIED.

D. WHERE REACTIONS ARE SUBJECT TO ECCENTRICITY, SUCH ECCENTRICITY SHALL BE TAKEN INTO ACCOUNT.

E. SIGNED AND SEALED CONNECTION CALCULATIONS SHALL BE PROVIDED WITH THE STRUCTURAL STEEL SHOP

DRAWINGS.

F. SERVICE CONNECTION DESIGN CAPACITIES SHALL BE LISTED ON THE STRUCTURAL STEEL ERECTION SHOP DRAWINGS.

4.12 FIELD SPLICES SHALL BE DESIGNED TO DEVELOP THE FULL CAPACITY OF MEMBER AT THE POINT OF SPLICE IN BENDING, SHEAR AND AXIAL LOAD (COMPRESSION AND TENSION).

4.13 ALTERNATE CONNECTION DETAILS MAY BE USED IF SUCH DETAILS ARE SUBMITTED TO THE CONTRACTING OFFICER ENGINEER FOR REVIEW AND ACCEPTANCE IS GRANTED. HOWEVER, THE CONTRACTING OFFICER SHALL BE THE SOLE JUDGE OF ACCEPTABILITY AND THE CONTRACTOR'S BID SHALL ANTICIPATE THE USE OF THE SPECIFIC DETAILS SHOWN ON THE DRAWINGS.

IN ANY EVENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN OF SUCH ALTERNATE DETAILS, WHICH HE PROPOSES.

4.14 PROVIDE STIFFENER PLATES ON EACH SIDE OF WEB OF BEAM OR GIRDER AT POINTS OF CONCENTRATED LOADS. MINIMUM STIFFENER PLATE THICKNESS SHALL BE 3/8" OR FLANGE THICKNESS OF COLUMNS ABOVE OR BELOW, WHICHEVER IS THICKER.

4.15 FILLER BEAMS OR JOISTS SHOULD BE SPACED EQUALLY BETWEEN THE COLUMNS IF NOT SHOWN OTHERWISE ON THE

DRAWINGS.

4.16 PROVIDE TEMPORARY BRACING OF STRUCTURAL FRAMING TO PROVIDE LATERAL SUPPORT UNTIL ALL PERMANENT BRACING MOMENT CONNECTIONS AND FLOOR AND ROOF DECKS (DIAPHRAGMS) ARE COMPLETELY INSTALLED.

4.17 STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL AND MECHANICAL DRAWINGS AND DRAWINGS RELATED TO OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE TO CHECK AND COORDINATE DIMENSIONS, CLEARANCES, ETC. WITH THE WORK OF OTHER TRADES. THE STRUCTURAL STEEL CONTRACTOR SHALL PROVIDE FRAMING AROUND OPENINGS IN

FLOOR AND ROOF SLAB AS INDICATED IN THE MECHANICAL AND ARCHITECTURAL DRAWINGS.

4.18 UNLESS SPECIFICALLY NOTED AND DETAILED IN THESE DRAWINGS, HOLES IN BEAMS ARE NOT PERMITTED.

4.19 STRUCTURAL STEEL CONTRACTOR SHALL COORDINATE THE BOTTOM OF BASE PLATE ELEVATION WITH THE TOP OF CONCRETE ELEVATION. IN CASE OF CONFLICT, THE CONTRACTOR SHALL MAKE ALLOWANCE

IN HIS BID FOR MORE STRINGENT REQUIREMENTS.

4.20 PAINT STRUCTURAL STEEL IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. DO NOT PAINT STEEL SURFACES TO BE ENCASED IN CONCRETE OR RECEIVE SPRAYED ON FIREPROOFING, CONNECTIONS DESIGNATED AS SLIP CRITICAL, OR TO BE WELDED. STEEL SURFACES RECEIVING AUTOMATICALLY

WELDED SHEAR CONNECTORS STUDS IN THE FIELD SHALL NOT BE PAINTED.

NOTE: REFER TO SPECIAL INSPECTION

SPECIFICATION SECTION 01 45 35 FOR

SPECIAL INSPECTION REQUIREMENTS.

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-001

100% SUBMITTAL

02 MAY 2023

G E

N E

R A

L N

O T

E S

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

GENERAL NOTES CONT.

STEEL DECKING

4.21 FABRICATION AND ERECTION OF STEEL DECKING SHALL CONFORM TO THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S (SDI) "SPECIFICATION AND COMMENTARY FOR COMPOSITE STEEL FLOOR DECK, NON-

COMPOSITE STEEL DECK, AND STEEL ROOF DECK" AS APPLICABLE TO THIS PROJECT.

STEEL DECKING:

4.22 MATERIAL FOR STEEL DECKING SHALL CONFORM TO ASTM A1008 GRADES 33 AND 40, OR FROM A653. SEE

DRAWINGS FOR STEEL DECK TYPE, GAUGE, YIELD STRENGTH AND SECTION PROPERTIES.

4.23 ROOF DECK SHALL BE TYPE B, WIDE RIB.

4.24 UNLESS NOTED OTHERWISE ALL STEEL DECKING SHALL HAVE A GALVANIZED COATING CONFORMING TO

ASTM A525, G60.

4.25 STEEL ROOF DECK ANCHORAGE: SEE ROOF DECK LEGEND ON SHEET S-003

4.26 PROVIDE DECKING CONTINUOUS OVER 3 SPANS MINIMUM WHERE SUPPORTING STRUCTURE PERMITS.

4.27 STEEL DECKING SHALL BE ERECTED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS

5.00 MASONRY

5.01 CONCRETE MASONRY DESIGN AND CONSTRUCTION SHALL CONFORM TO ACI 530, BUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY STRUCTURES AND ACI 530.1, SPECIFICATIONS FOR CONCRETE

MASONRY CONSTRUCTION.

5.02 PROVIDE MASONRY WALL REINFORCEMENT & BOND BEAM SHOP DRAWINGS WITH FULLY DETAILED PLANS, SECTIONS AND ELEVATIONS OF EACH WALL.

5.03 PROVIDE LIGHTWEIGHT, HOLLOW, CONCRETE MASONRY UNITS (CMU) CONFORMING TO ASTM C90, UNLESS

NOTED OTHERWISE.

5.04 PROVIDE MASONRY CONSTRUCTION WITH MINIMUM COMPRESSIVE STRENGTH, f'm = 1700 PSI.

5.05 PROVIDE TYPE "M" OR "S" MORTAR IN ACCORDANCE WITH ASTM C270, UNLESS NOTED OTHERWISE.

5.06 VERTICAL CELLS SHALL BE REINFORCED AS NOTED IN LEGEND ON S-101, UNLESS NOTED OTHERWISE (U.N.O.) IN THE CONTRACT DRAWINGS. VERTICAL REINFORCING SHALL BE CONTINUOUS (LAPPED 48 BAR DIAMETERS MINIMUM AT SPLICES, U.N.O.) AND HELD IN POSITION AT THE TOP AND BOTTOM OF THE GROUT

POUR. U.N.O., POSITION VERTICAL REINFORCING IN THE CENTER OF THE CELL.

5.07 PROVIDE GROUT FOR REINFORCED MASONRY IN ACCORDANCE WITH ASTM C476. GROUT SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3,000 PSI UNLESS NOTED OTHERWISE. GROUT SHALL BE FLUID CONSISTENCY. FLUID CONSISTENCY SHALL MEAN THAT CONSISTENCY AS FLUID AS POSSIBLE FOR POURING WITHOUT SEGREGATION OF THE CONSTITUENT PARTS. FILL ALL CELLS BELOW GRADE WITH GROUT. ALL GROUT SHALL BE CONSOLIDATED AT THE TIME OF POURING BY VIBRATING AND THEN RECONSOLIDATED BY AGAIN PUDDLING LATER, BEFORE PLASTICITY IS LOST. WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, CONSTRUCTION JOINTS SHALL BE FORMED BY STOPPING THE POUR OF THE

GROUT 1-1/2 INCHES BELOW THE TOP OF THE UPPERMOST UNIT.

5.08 PROVIDE HORIZONTAL JOINT REINFORCEMENT COMPLYING WITH ASTM A82, NO. 9 GAUGE OR HEAVIER, ZINC

COATED, PLACED 16 INCHES ON CENTER IN CMU WALLS, UNLESS NOTED OTHERWISE.

5.09 PROVIDE RUNNING BONDS WITH VERTICAL JOINTS LOCATED AT CENTER OF MASONRY UNITS IN THE

ALTERNATE COURSE BELOW, UNLESS NOTED OTHERWISE.

5.10 ALL MASONRY UNITS SHALL BE FREE OF EXCESSIVE DUST AND DIRT AT THE TIME THEY ARE LAYED BY THE

MASON.

5.11 ALL REINFORCED HOLLOW UNIT MASONRY SHALL BE BUILT TO PRESERVE THE UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO BE FILLED. WALLS AND CROSS WEBS IN ALL REINFORCED MASONRY WALLS SHALL BE FULLY BEDDED IN MORTAR. ALL HEAD (OR END) JOINTS SHALL BE SOLIDLY FILLED WITH MORTAR FOR A DISTANCE IN FROM EACH FACE OF THE UNIT NOT LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS, BOND SHALL BE PROVIDED BY LAPPING UNITS IN SUCCESSIVE VERTICAL COURSES.

5.12 PROVIDE VERTICAL CONTROL JOINTS BETWEEN REINFORCED MASONRY WALLS AND MASONRY PARTITION

WALLS AND AS INDICATED IN THE STRUCTURAL CONTRACT DRAWINGS.

5.13 SAMPLE AND TEST MASONRY MATERIAL IN ACCORDANCE WITH TMS 602-16, TABLE 3, QUALITY

ASSURANCE LEVEL 2.

5.14 INSPECT MASONRY CONSTRUCTION IN ACCORDANCE WITH TMS 602-16, TABLE 4, QUALITY ASSURANCE

LEVEL 2.

6.00 COLD FORMED METAL FRAMING

6.01 COLD FORMED METAL STUDS: GALVANIZED STEEL PER ASTM A525, G60 COATING MEETING THE

REQUIREMENTS OF ASTM A446 GRADE A, WITH A MINIMUM YIELD STRENGTH OF 33,000 PSI.

6.02 ALL STUDS INDICATED SHALL BE 18 GAGE MINIMUM AND HAVE 1-5/8” WIDE FLANGES MINIMUM

WITH A ½” MINIMUM LIP AND SHALL BE SPACED AT 1’-4” O.C MAXIMUM, UNLESS NOTED

OTHERWISE. ALL TRACK INDICATED SHALL BE 18 GAGE MINIMUM AND HAVE 1-1/4” WIDE MINIMUM

FLANGES.

6.03 CONNECTION REQUIREMENTS (MINIMUMS):

A. TRACK TO STEEL OPTIONS

1. 0.145” DIA. P.A.F.s @ 8” O.C. STAGGERED.

2. #12 HWH SELF TAPPING TEK SCREWS @ 8” O.C.

B. TRACK TO BLOCK – (2) 3/16” TAPCON SCREW ANCHORS AT EACH JOIST/STUD

LOCATION EMBED 1¼” MINIMUM INTO BLOCK/GROUT.

C. TRACK TO CONCRETE OPTIONS:

1. 0.145” DIA. P.A.F.s @ 8” O.C. STAGGERED EMBED 1¼” MIN.

2. 3/16” TAPCON SCREW ANCHORS @ 8” O.C. EMBED 1¼” MIN.

D. STUD TO STUD OR JOIST TO JOIST: (4) #10 HWH SELF TAPPING TEK SCREWS, MIN.

E. STUD TO TRACK – (2) #10 HWH SELF TAPPING TEK SCREWS.

F. STUD TO STEEL OPTIONS

1. (2) 0.145" DIA. P.A.F.'s

2. (2) #12 HWH SELF TAPPING TEK SCREWS.

7.00 PRE-ENGINEERED METAL BUILDINGS (PEMB)

7.01 BUILDING SHALL BE CONSTRUCTED IN ACCORDANCE WITH METAL BUILDING MANUFACTURER’S

ASSOCIATION (MBMA) CRITERIA.

7.02 BUILDING SHALL BE DESIGNED FOR THE WIND AND SUPERIMPOSED GRAVITY LOADS AS SHOWN

IN SECTION 1.00 OF THESE GENERAL NOTES AS WELL AS THE ADDITIONAL LOADS:

A. BUILDING SELF-WEIGHT

B. COLLATERAL LOAD = 10 PSF

C. REDUCIBLE ROOF LIVE LOAD…PER CODE

7.03 THE FOUNDATIONS HAVE BEEN DESIGNED BASED ON THE ASSUMPTION THAT THE RIGID

FRAMES ARE PINNED AT THE BASE. THE FINAL RIGID FRAME COLUMN REACTIONS SHALL BE SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW PRIOR TO FABRICATION OF THE PEMB. THE PURPOSE OF THIS REVIEW IS TO GIVE THE CONTRACTING OFFICER OPPORTUNITY TO VERIFY THE FINAL RIGID FRAME COLUMN REACTIONS DO NOT EXCEED THE FOUNDATION CAPCITIES GIVEN ON S-101. REVISIONS

TO THE FOUNDATION DESIGN MAY BE NECESSARY PENDING THE REVIEW OF THIS SUBMITTAL.

7.04 DRIFT CRITERIA: H/180

7.05 WALL GIRT HORIZONTAL DEFLECTION CRITERIA FOR THE FOLLOWING VENEER:

A. METAL PANELS: L/120

B. SHEETROCK INTERIOR WALLS: L/240

C. MASONRY: L/600

7.05 ROOF PURLIN VERTICAL DEFLECTION CRITERIA:

A. METAL PANELS: L/180

7.06 PEMB MANUFACTURER TO PROVIDE SUPPORT AT TOP OF CMU WALLS AND TO DESIGN RIGID

FRAMES AND OTHER LATERAL SYSTEMS FOR WIND LOAD FROM CMU WALLS.

8.00 POST INSTALLED ANCHORS

8.01 ANCHOR BASIS OF DESIGN, FOR ALL POST INSTALLED ANCHORS ARE HILTI, INC PRODUCTS OR

APPROVED EQUAL. CONTACT HILTI AT (800) 879-8000.

8.02 WHERE CALLED FOR IN THE CONSTRUCTION DRAWINGS, EPOXY (ADHESIVE) SHALL BE HILTI HIT- HY 200 OR EQUIVALENT SYSTEM. PROVIDE GALVANIZED A-307 OR EQUIV. ALL-THREAD ROD AND

GALV. WASHERS AND NUTS, TYPICAL.

8.03 WHERE CALLED FOR IN THE CONSTRUCTION DRAWINGS, EXPANSION (EXP.) ANCHORS SHALL BE GALVANIZED HILTI KWIK BOLT 3, INCLUDING NUT AND WASHER, WITH 3 1/4" EMBEDMENT INTO

GROUT FILLED CMU OR CONCRETE OR APPROVED EQUAL. ANCHOR EDGE DISTANCE SHALL BE

4" MINIMUM AT ALL LOCATIONS.

8.04 INSTALL ALL ANCHORS PER THE MANUFACTURER'S WRITTEN INSTRUCTIONS, AS INCLUDED IN

THE ANCHOR PACKAGING.

8.05 THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO

PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS

SPECIFIED. THE CONTRACTING OFFICER MUST RECEIVE DOCUMENTED CONFIRMATION THAT

ALL OF THE CONTRACTOR'S PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE

COMMENCEMENT OF INSTALLING ANCHORS.

8.06 ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ANCHORS, ANCHOR EMBEDMENT, AND PROXIMITY OF ANCHORS TO EDGES OF CONCRETE AND/OR MASONRY. INSTALL ANCHORS

IN ACCORDANCE WITH THE SPACING AND EDGE CLEARANCES INDICATED IN THESE DRAWINGS.

WIND LOAD DETERMINATION ASSUMPTIONS - INTERNATIONAL BUILDING CODE 2018

ROOF SLOPE

145 C 24.0 3 ON 12 II ENCLOSED

NOTES:

1. FOR EFFECTIVE AREAS BETWEEN THOSE GIVEN ABOVE THE LOAD MAY BE INTERPOLATED,

OTHERWISE USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA.

2. THE EDGE STRIP, a = 4.3 FT.

3. PRESSURES SHALL BE APPLIED IN ACCORDANCE WITH THE FIGURE SHOWN ON THIS SHEET.

WIND VELOCITY

(MPH)

EXPOSURE

CATEGORY

MEAN ROOF

HEIGHT (FT.)

RISK

CATEGORY

ENCLOSURE

CATEGORY

REPRESENTATIVE DIAGRAMS

4. PRESSURES GIVEN ARE ULTIMATE LOADS TO BE USED WITH STRENGTH DESIGN. FOR

SERVICE LOADS TO BE USED WITH ALLOWABLE STRESS DESIGN, MULTIPLY THE PRESSURES

BY 0.60. SEE TABLES 2.3 AND 2.4 IN ASCE 7-16 FOR MORE INFORMATION ON LOAD

COMBINATIONS.

ROOF

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-002

100% SUBMITTAL

02 MAY 2023

G E

N E

R A

L N

O T

E S

W

IN

D

IN

F

O R

M A

T

IO

N

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

A B C D E

E-E E-F E-G E-H E-I E-J

E-1

E-1

E-2E-2

E-3E-3

2'-0" 21'-0" 22'-0" 24'-0" 21'-0" 2'-0"

88'-0"

2' -0

'-4

2' -0

4' -2

'-6

'-1

0"

'-4

S-301

S-301

S-302 3

B.8 C.3 D.4 D.7

F 3.0 F 3.0

F 3.0 F 3.0

F 3.0

F 3.0 F 3.0

F 3.0

HSS4X4X1/4

RCP16 HSS4X

4X 1/

RCP16

HSS4X4X1/4

RCP16

HSS4X

4X

1/

RCP16

HSS4X4X1/4

RCP16 HSS4X

4X 1/

RCP16

HSS4X

4X

1/

RCP16

HSS4X4X1/4

RCP16

4' -2

'-6

2' -1

1" 8'

-5

/2

1' -5

/2

'-4

TD3X2.25 TD3X2.25

TD3X2.25 TD3X2.25

T D

3X 2.

S.C.J. S.C.J.

S.C.J. S.C.J.

S .C

.J

S .C

.J

S .C

.J

S .C

.J

S .C

.J

S .C

.J

S .C

.J

S .C

.J

(TOF:-2'-8")

(TOF:-2'-0")

(TOF:-2'-8")

(TOF:-2'-0") 8"

'-4

8"

1' -4

40'-11 1/2" 8'-1" 26'-11" 8'-1" 3'-11 1/2"

2'-3 5/8"

8" 8"

8"

HAIRPIN (TYP.);

SEE DETAIL

6" SLAB6" SLAB

S-302

S-301

T D

3X 2.

T D

3X 2.

T

D 3X

2.

PORTAL FRAME

PORTAL FRAME

FOUNDATION AND SLAB-ON-GRADE LEGEND

= SAWN CONTRACTION JOINT OR CONSTRUCTION JOINT; CONTRACTOR'S OPTION U.N.O. PLACE

WHERE SHOWN ON PLAN

S.C.J.

= VERTICAL MASONRY CONTROL JOINT LOCATION; SEE TYPICAL DETAILS

= 8" NOMINAL CMU WALL. UNLESS NOTED OTHERWISE (U.N.O.), WALL SHALL BE REINFORCED WITH #5 VERTICAL REINFORCING AT 24" ON CENTER IN CENTER OF GROUT FILLED CELLS. PROVIDE HORIZONTAL JOINT REINFORCING AND ADDITIONAL VERTICAL REINFORCING AS OUTLINED IN THE GENERAL NOTES, TYPICAL DETAILS AND SECTIONS IN THESE DRAWINGS. ALL CMU WALLS BELOW

GRADE SHALL BE FULLY GROUT FILLED.

6" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH #3 AT 12"O.C. EACH WAY WITH 2 1/2" CLR. POSITIVE SUPPORT FROM BOTTOM OF SLAB. SLAB SHALL BE PLACED OVER A VAPOR BARRIER

AS INDICATED IN THE GENERAL NOTES SECTION 2.08 ON SHEET S-001.

6" SLAB =

RCP16 16"x16" REINFORCED CONCRETE PIER WITH (8) #5 VERTICALS AND #3 TIES AT 8"O.C.=

(TOF: X'-X") TOP OF FOOTING REFERENCE ELEVATION=

= 12" NOMINAL CMU WALL. UNLESS NOTED OTHERWISE (U.N.O.), WALL SHALL BE REINFORCED WITH #5 VERTICAL REINFORCING AT 24" ON CENTER IN CENTER OF GROUT FILLED CELLS. PROVIDE HORIZONTAL JOINT REINFORCING AND ADDITIONAL VERTICAL REINFORCING AS OUTLINED IN THE GENERAL NOTES, TYPICAL DETAILS AND SECTIONS IN THESE DRAWINGS. ALL CMU WALLS BELOW

GRADE SHALL BE FULLY GROUT FILLED.

TD3X2.25 3'-0" WIDE x 2'-3" DEEP TURNDOWN SLAB EDGE; SEE SECTION 1/S-301 FOR REINF.; PROVIDE

CORNER BARS FOR CONT. REINF.

F3.0 3'-0" SQ. x 1'-0" THICK FOOTING; REINF. WITH #5 AT 12"O.C. E.W. BOTTOM=

ALLOWABLE FOUNDATION CAPACITIES

NOTES:

1. PEMB RIGID FRAME COLUMN REACTIONS SHALL NOT EXCEED THE ABOVE FOUNDATION CAPACITIES.

TD3X2.25 UPLIFT LOAD CAPACITY: 20 KIPS

TD3X2.25 GRAVITY LOAD CAPACITY: 35 KIPS

HORIZONTAL THRUST CAPACITY: 15 KIPS

8' -0

30.00°

TURNDOWN BELOW;

SEE SECTIONS FOR

SIZE & REINFORCING

SLAB EDGE

#5 HAIRPINSEE PLAN FOR SLAB

REINFORCING

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-101

100% SUBMITTAL

02 MAY 2023

F O

U N

D A

T

IO

N

S

LA

B -O

N -G

R A

D E

P

LA

N

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

1/8" = 1'-0"S-101

1 FOUNDATION & SLAB-ON-GRADE PLAN

T.O.SLAB REF. ELEV: 0'-0" U.N.O.; REF. EL: 0'-0" = ELEV: (SEE CIVIL)

KEY PLAN

0 4' 8' 16'

SCALE 1/8":1'-0"

2'

1/4" = 1'-0"S-101

2 PEMB - TYPICAL HAIRPIN DETAIL

0 2' 4' 8'

SCALE 1/4":1'-0"

1'

PLAN

A B C D E

E-E E-F E-G E-H E-I E-J

E-1

E-1

E-2E-2

E-3E-3

S-301

S-301

S-302

B.8 C.3 D.4 D.7

PEMB ROOF FRAMING

BY PEMB MANUF.

EXISTING

BUILDING

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E )1

6K

(E)W10X30 (E)W10X30

(E)W8X24(E)W18X50(E)W18X35

(E )2

4K

(E )2

4K

(E )2

4K

(E )2

4K

(E )2

4K

(E )2

4K

(E )2

4K

(E )2

4K

(E )2

4K

S-303

HSS8X4

H S

S 8X

HSS8X4

H S

S 8X

4CRIP

CRIP

CRIP

CRIP

21'-0" 22'-0" 24'-0" 21'-0"

4' -2

'-6

'-1

0"

'-4

40'-11 1/2" 8'-1" 26'-11" 8'-1" 3'-11 1/2"

2' -1

1" 8'

-5

/2

1' -5

/2

'-4

CRIP CRIP

S-302

HSS4

HSS4

HSS4

HSS4

S-303

H S

S 8X

H S

S 8X

H

S S

H S

S

H S

S

H S

S

(L O

(L O

(L O

(L O

PORTAL FRAME

(BOTTOM BEAM MINIMUM

ELEVATION: 18'-0")

PORTAL FRAME

(BOTTOM BEAM MINIMUM

ELEVATION: 18'-0")

PRE-ENGINEERED

CANOPY; SEE ARCH

1.5" TYPE B 16 GA VULCRAFT OR EQUIVALENT

( TH= 0.0598 in, I= 0.373 in^4/ft) ROOF DECK.

INSTALLATION/ATTACHMENT:

SUPPORT FASTENERS: SIMPSON XLQ114T1224 OR EQUIVALENT

SIDELAP FASTENERS: SIMPSON XU34S1016 OR EQUIVALENT

FASTENER LAYOUT:

ZONES 1, 2 & 3: XLQ114T1224 OR EQUIVALENT @ 36/7

PATTERN

NO OF SIDELAP FASTENER PER SPAN: 6

* ANCHOR DECKING TO ALL EDGE PLATES, RIDGE PLATES AND

TOP PLATES @ 6" O.C.

ROOF FRAMING NOTES AND LEGEND

(E) EXISTING STRUCTURAL MEMBER=

(TOS: X'-X") TOP OF STEEL REFERENCE ELEVATION=

(BOD) BOTTOM OF DECK (REFERENCE ELEVATION)=

HSS8X4 HSS8X4X1/4=

HSS4 HSS4X4X1/4=

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-102

100% SUBMITTAL

02 MAY 2023

R O

O F

F R

A M

IN

G

P

LA

N

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

1/8" = 1'-0"S-102

1 ROOF FRAMING PLAN

0 4' 8' 16'

SCALE 1/8":1'-0"

2'

PLAN

NORTH

KEY PLAN

SLAB ON GRADE

0"

PEMB EAVE

17' - 4"

(5) #8 CONT. BOTTOM

VAPOR RETARDER;

TYP.1

#3 CLOSED

STIRRUPS @ 2'-0"

O.C. MAX SPACING

EXTERIOR GRADING/PAVING;

SEE CIVIL

PEMB RIGID FRAME;

BY PEMB MRF.

(4) ASTM F1554, GRADE 36 3/4" DIA.

HEADED ANCHOR BOLTS. BOLTS TO BE

HOT-DIPPED GALVANIZED. PROVIDE MIN.

12" EMBEDMENT INTO CONCRETE, (U.N.O.)

COLUMN BASE PLATE BY

PEMB. MFR./DESIGNER

(4) #7 CONT. TOP

HAIRPIN, SEE PLAN

FOR LOCATIONS

PEMB WALL GIRT;

BY PEMB MRF.

3'-4"

TOP/CMU

REF. ELEV.:

(2) #5 CONT. MIDDLE

#4 STIRRUPS @ 2'-0"

O.C. MAX SPACING

8" CMU WALL; SEE PLAN

8" BOND BEAM

WITH (1) #5 CONT.

PEMB WALL GIRT;

BY PEMB MRF.

8" 1'

-7 "2'

-3

8" 2'-4"

3'-0"

PEMB ROOF PURLIN;

BY PEMB MRF.

PEMB EAVE STRUT;

BY PEMB MRF.

PEMB WALL PANEL;

BY PEMB MRF.

PEMB ROOF PANEL;

BY PEMB MRF.

RANGE: 12" TO 18"

PEMB COLUMN DEPTH

8" MIN.

4"

T Y

P

3" C

LR

8" BOND BEAM

WITH (1) #5 CONT.

SLAB ON GRADE

0"

E

SEE SECTION 1/S-301

FOR TURNDOWN REINF.

VAPOR RETARDER;

TYP.

EXTERIOR

GRADING/PAVING;

SEE CIVIL

12" CMU WALL;

SEE PLAN

24" BOND BEAM WITH (2) #5

CONT. TOP & BOTTOM

1' -7

8"

2' -3

CMU VENEER;

SEE ARCH.

8" 2'-4"

3'-0"

1/2" P.J.F.

Z-PURLIN; BY

PEMB MANUF.

C-BENT; BY

PEMB MANUF.

RIGID FRAME; BY

PEMB MANUF.

3/4"x6" EXPANSION ANCHOR

AT 24"O.C. INTO GROUT

FILLED CMU; PROVIDE

2"x2"x1/4" PLATE WASHERS

3"

WALL CAP; SEE

ARCH.

3' -4

LA

P 1'-4"8"

FORM AND POUR TOP

8" (MINIMUM) PER TOP

OF WALL SLOPE

SERVICE REACTION (0.6W) FOR

PEMB TO RESIST: 450 LBS/FT

8" BOND BEAM WITH

(2) #5 CONT.

10'-0"

BOTTOM OF BOND BEAM

REF. ELEV.:

TOP/STEEL

18'-0 3/8"VARIES W/ SLOPE

A

1'-4" 3 5/8"

8" 11 5/8" 8"

8" 8"

8"

1' -4

2'-3 5/8"

4" CMU VENEER;

SEE ARCH

12" CMU WALL;

SEE PLAN

8" CMU WALL;

SEE PLAN

PEMB FRAME

COLUMN

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-301

100% SUBMITTAL

02 MAY 2023

W A

LL

S

E C

T

IO

N S

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

3/4" = 1'-0"S-301

1 TYPICAL EAVE WALL SECTION

3/4" = 1'-0"S-301

2 TYPICAL ENDWALL SECTION

0 6" 1' 2'

SCALE 3/4":1'-0"

4'

3/4" = 1'-0"S-301

3 WALL CORNER DETAIL

SLAB ON GRADE

0"

B.8 C.3

T/STL CANOPY

12' - 9"

SOFFIT

10' - 0"

EQ EQ

3'-0"

-8"

-2'-0"

TOP OF PIER

TOP OF FOOTING

SEE SCHEDULE FOR

FOUNDATION REINF.

SEE DETAIL FOR ANCHOR

BOLTS AND BASE PLATE

COLUMN; SEE PLAN

4" 8'-1" 4"

EQ EQ

3'-0"

C

LR

3"

S-302

S-303

3/16" RIDGE

PLATE CONT.

6" 6"

HSS CRIPPPLE BEAM;

SEE PLAN

ROOF DECK;

SEE PLAN

3/16" 3"

TYP. EA.

JOIST

1/4" BENT PLATE

PROVIDE A DOUBLE COAT OF

COAL TAR EPOXY FOR ALL

STEEL ELEMENTS BELOW

GRADE. EXTEND 2" ABOVE

FINISHED FLOOR ELEVATION.

HSS BEAM;

SEE PLAN

400S162-43

AT 16"O.C.

400T125-43

CONT.

1/

8" 2'

/4

1/ 4"

1/

2"

4"

NOTE:

EXPOSED STEEL COLUMNS TO

BE GALVANIZED AND RECEIVE

EXTERIOR PAINT (SEE ARCH.)

COLUMN; SEE PLAN

SLAB ON GRADE

0"

PEMB EAVE

17' - 4"

2 E-1

S-302

3 4

T/STL CANOPY

12' - 9"

T/(E)CMU

12' - 0"

S-303

SOFFIT

10' - 0"

SEE SCHEDULE FOR

FOUNDATION REINF.

SEE DETAIL FOR

ANCHOR BOLTS

AND BASE PLATE

SEE DETAIL FOR ANCHOR

BOLTS AND BASE PLATE

SEE SCHEDULE FOR

FOUNDATION REINF.

DRILL AND EPOXY

CONT. REINF. 8" INTO

EXISTING FOOTING

EXISTING FOOTING

-2'-8"

T/ (E) FOOTING

EXTERIOR

GRADING/PAVING;

SEE CIVIL

TOP/CMU

REF. ELEV.:

EXISTING CMU WALL

TURNDOWN

SLABEDGE; SEE

SECTION 1/S-301

3'-4"

COLUMN;

SEE PLAN

PEMB WALL GIRT;

BY PEMB MRF.

8" CMU WALL;

SEE PLAN

8" BOND BEAM

WITH (1) #5 CONT.

PEMB WALL GIRT;

BY PEMB MRF.

PEMB WALL PANEL;

BY PEMB MRF.

HSS BEAM;

SEE PLAN

HSS BEAM;

SEE PLAN

COLUMN;

SEE PLAN

ROOF DECK;

SEE PLAN

CONT. 14 GA.x8"x8" VALLEY

PLATE W/ (2) #12 SCREWS AT

8"O.C. (EA. SIDE OF VALLEY)

EXISITNG ROOF DECK

PROVIDE A DOUBLE COAT OF

COAL TAR EPOXY FOR ALL

STEEL ELEMENTS BELOW

GRADE. EXTEND 2" ABOVE

FINISHED FLOOR ELEVATION.

NOTE:

COORDINATE LOCATION OF COLUMN

FOOTINGS WITH UNDERGROUND

UTILITES PRIOR TO CONSTRUCTION

JOINT

2" EXPANSION

1/4

FLARE BEVEL

WHERE REQ'D

1'-5 1/2" 8'-5 1/2" 2'-11" (F.V.)

NOTE:

EXPOSED STEEL COLUMNS TO

BE GALVANIZED AND RECEIVE

EXTERIOR PAINT (SEE ARCH.)

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-302

100% SUBMITTAL

02 MAY 2023

W A

LL

S

E C

T

IO

N S

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

3/4" = 1'-0"S-302

1 CANOPY SECTION 1

0 6" 1' 2'

SCALE 3/4":1'-0"

4'

3/4" = 1'-0"S-302

3 CANOPY SECTION 2

B.8 C.3

T/STL CANOPY

12' - 9"

SOFFIT

10' - 0"

S-302

S-303

(2) L4x3x1/4", LLV

CAP HSS; TYPICAL

3/16"

TYP; EACH

ANGLE

3/16"

TYP.

HSS BEAM; SEE PLAN

400S162-43 AT 16"O.C.

3/16" 3"

TYP. EA.

JOIST

4" 8'-1" 4"

1/4" BENT PLATE

400T125-43 CONT.

400T125-43 CONT.

400S162-43 AT 16"O.C.

400T125-43 CONT.

1/

8" 2'

/4

1/ 4"

3/16" RIDGE

PLATE CONT.

1/

2"

4"

6" 6"

HSS BEAM; SEE PLAN

HSS CRIPPPLE BEAM;

SEE PLAN

ROOF DECK;

SEE PLAN

PEMB EAVE

17' - 4"

2 E-1

S-302

3 4

T/STL CANOPY

12' - 9"

T/(E)CMU

12' - 0"

S-303

SOFFIT

10' - 0"

JOINT

2" EXPANSION

CONT. 14 GA.x8"x8"

VALLEY PLATE W/ (2) #12

SCREWS AT 8"O.C. (EA.

SIDE OF VALLEY)

EXISITNG ROOF DECK

ROOF DECK;

SEE PLAN

HSS BEAM;

SEE PLAN

400S162-43

AT 16"O.C.PEMB WALL GIRT;

BY PEMB MRF.

PEMB WALL PANEL;

BY PEMB MRF.

1'-5 1/2" 8'-5 1/2" 2'-11" (F.V.)

EXISTING FASCIA,

GUTTER AND SOFFIT

FRAMING

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-303

100% SUBMITTAL

02 MAY 2023

W A

LL

S

E C

T

IO

N S

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

3/4" = 1'-0"S-303

1 CANOPY ROOF SECTION 1

3/4" = 1'-0"S-303

2 CANOPY ROOF SECTION 2

0 6" 1' 2'

SCALE 3/4":1'-0"

4'

CUT WWF AT JOINT

3/4"

S E

E P

LA

N

2"

CONSTRUCTION JOINTCONTROL JOINT

1/8"x(d/4) SAWN

CONTROL JOINT

d/

CONTROL JOINT OR CONSTRUCTION

JOINT AT CONTRACTOR'S OPTION

PROVIDE CONT.

WWF AT STEP

TYPICAL SLAB STEP DETAIL

4"6"

S E

E P

LA

N

S

LA

B D

E P

T H d)

SLAB EDGE

SLAB EDGE

TYPICAL SLAB REINF.;

SEE PLAN AND

DETAILS

CORNER BAR DETAIL AT TYPICAL CORNER

CORNER BAR

TO MATCH

TOP & BOTT

SLAB REINF.

2' - 0" TYP.

CRITICAL: DO NOT CUT SLAB REINF.

#5 U-BAR

SEE TYPICAL

SECTION AT

WALL OPENING

#5 BAR

2' - 0"

WITH ARCH DWGS

SEE PLAN, COORDINATE 2' - 0"

2" CLR, TYPICAL

1/2" PJF

HSS BEAM TO HSS COLUMN, U.N.O.

HSS BEAM,

CAP ENDS; TYP.

HSS COLUMN

BEYOND

1/4" MIN. END

CAP; TYP.

HSS BEAM

HSS COLUMN

HSS BEAM TO HSS BEAM, U.N.O.

HSS BEAM,

CAP ENDS; TYP.

L3x3x1/4" x FULL

HEIGHT EACH SIDE;

TYPICAL

1/4

SHOP OR

FIELD;

TYP.

1/4

FLARE BEVEL

WHERE REQ'D

L6x4x3/8" LLV x BEAM WIDTH"

ERECTION SEAT

1/4

FLARE BEVEL

WHERE REQ'D

BASE PLATE 3/4"x10"x10" W/

(4)-3/4" DIA. ANCHOR BOLTS

1-1/2" MINIMUM GROUT BED

FOR LEVELING NUTS

9"

1/

2" 7"

1/

2"

1 1/2" 7" 1 1/2"

10"

HSS4x4 COLUMNS

NOTES:

1. ALL ANCHOR BOLTS ARE 3/4-INCH DIAMETER

2. ALL ANCHORS ARE TO BE HOT-DIP ZIC GALVANIZED

3. ALL ANCHORS ARE ASTM F1554 GRADE 36

4. ALL EMBEDMENTS ARE 9 INCHES, U.N.O.

5. SEE SPECIFICATIONS AND GENERAL NOTES

FOR ADDITIONAL INFORMATION.

TYPICAL ANCHOR BOLT DETAIL, U.N.O.

P R

O

JE

C T

IO

N

4" 8"

O.S. WASHER SHOP TACK

WELDED TO NUT.

(2) NUT AND 2"X2"X3/16"

WASHERS, GALV.; TYP.

3/4" DIA. HOT DIP GALV. A307 OR

EQUIV. ANCHOR BOLT

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-401

100% SUBMITTAL

02 MAY 2023

T Y

P

IC

A L

D E

T A

IL

S

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

1" = 1'-0"S-401

1 TYPICAL SLAB-ON-GRADE DETAILS

3/4" = 1'-0"S-401

2 TYPICAL ADD. REINFORCEMENT AT WALL OPENING

0 6" 1' 2'

SCALE 3/4":1'-0"

4'

0 6" 1' 2'

SCALE 1":1'-0"

3"

1" = 1'-0"S-401

4 STEEL - CONNECTION DETAILS

3/4" = 1'-0"S-401

3 STEEL - BASE PLATE DETAILS

(2) #5 CONT.

CONC. FILL

3"

1/

4"

WHERE CMU VENEER OCCURS,

BENT PLATE 5/16"xAS REQ'Dx6"

LLH (GALV.) W/ 5/8" x 6" EXP.

BOLTS AT 16" O.C.

PROVIDE 8" DEEP OPEN

BOTTOM SILL REINF. W/

(2) #5 CONT.

S E

E A

R C

H

M A

S O

N R

Y O

P E

N

IN

G

CMU LINTEL REINFORCING SHALL EXTEND 24"

PAST FACE OF OPENING AND SHALL BEAR, EACH

SIDE, ON (2) REINFORCED GROUT FILLED CELLS.

BEARING OF STEEL LINTEL NOT REQ'D

FOR OPENINGS UP TO 4'-0"

(2) #5 CONT.

TOP & BOT.

CONC. BEAM

12" CMU

1/

4"

PROVIDE 16" DEEP OPEN

BOTTOM SILL REINF. W/

(2) #5 TOP AND BOT. CONT.

FOR OPENINGS GREATER THAN 4'-0"

8" 8"

1' -4

S E

E A

R C

H

M A

S O

N R

Y O

P E

N

IN

G 1'

-4

CMU LINTEL REINFORCING SHALL EXTEND 24"

PAST FACE OF OPENING AND SHALL BEAR, EACH

SIDE, ON (3) REINFORCED GROUT FILLED CELLS.

BEARING OF STEEL LINTEL NOT REQ'D

1/2"

WHERE CMU VENEER OCCURS,

BENT PLATE 5/16"xAS REQ'Dx6"

LLH (GALV.) W/ 5/8" x 6" EXP.

BOLTS AT 16" O.C.

ADDITIONAL GROUT FILLED

AND REINFORCED CELLS, SEE

LINTEL SCHEDULE ABOVE

PAST FACE OF OPENING; TYP.

EXTEND CMU LINTEL AND SILL REINF. 2'-0"

S E

E A

R C

H

SEE ARCH.

LINTEL REINF; SEE

SCHED. ABOVE

SILL REINF (AT WINDOWS); SEE

SCHED. ABOVE

TYPICAL GROUT FILLED AND

REINF. CELL; SEE PLAN FOR REQ'MENTS.

ELEVATION AT OPENINGS WITH 2'-0" MIN. WALL EXTENSION PAST FACE OF OPENING

VENEER;

SEE ARCH.

VENEER;

SEE ARCH.

12" CMU

ARCH

SEE

1/2"

ARCH

SEE

#3 TIES AT 6"O.C.

9 GA. STD. LADUR TYPE

JOINT REINF. AT 16" O.C.

VERTICALLY

(CUT AT CONTROL JOINT)

TYPICAL WALL

REINF.

PROVIDE (3) ADD'L GROUT FILLED

AND REINF. CELLS IN ALL

CORNERS; TYP.

TYPICAL CMU WALL CORNER DETAIL, U.N.O.

SEE PLAN

S E

E P

L A

N

PROVIDE FACTORY FABRICATED

CORNER SECTION OF HORIZ. JOINT

REINF, LAP AS REQ'D BY MFR.

SPECIFICATIONS; TYP.

CMU WALL;

SEE PLANS

TYPICAL CMU WALL END DETAIL, U.N.O.

9 GA. STD. LADUR TYPE

JOINT REINF. AT 16" O.C.

VERTICALLY

(CUT AT CONTROL JOINT)

TYPICAL WALL

REINF.

PROVIDE (2) ADD'L GROUT FILLED

AND REINF. CELLS AT ALL WALL

ENDS; TYP.

S E

E P

L A

N

CMU WALL;

SEE PLANS

SASH BLOCK UNIT

PREFORMED GASKET

CAULK JOINT

CONTROL JOINTS SHALL STOP ABOVE AND

BELOW BOND BEAMS. BOND BEAM

REINFORCING SHALL BE CONTINUOUS

THROUGH JOINT.

SEE GENERAL NOTES FOR

HORIZONTAL JOINT REINF.

S E

E P

L A

N

TYPICAL VERTICAL

WALL REINFORCEMENT

PROVIDE ADDITIONAL GROUT FILLED

AND REINF. CELL ON EACH SIDE OF

ALL CONTROL JOINTS; TYP.

CMU WALL; SEE PLAN

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

IA

R

E

OF

RC

SP

EC

IA

AN

N

P

ER

L O

AT

IO

M M

S

CO

D

SHEET REFERENCE:

D A

T E

SHEET NUMBER:

OF

D E

S C

R

IP

T

IO

N R

E V

A

IR

F O

R C

E

SP

EC

IA

L O

PE

R

A

TI

O N

S C

O M

M A

N D

SP

EC

IA

L O

PE

R

A

TI

O N

S C

IV

IL

E N

G

IN

EE

R

S Q

U A

D R

O N

H U

R

LB

U R

T

FI

E

LD

, F

LO

R

ID

A

PROJECT NUMBER:

BUILDING NUMBER:

DRAWN BY:

DESIGNED BY:

DATE:

90145

S-501

100% SUBMITTAL

02 MAY 2023

C M

U D

E T

A

IL

S

JTG

JTG

CP1033732

A d d /A lt e r

S p a c e D e fi c ie n c ie s

S O

S B ld g

5−2−2023

H U

R L B

U R

T F

IE

L D

F

L

3/4" = 1'-0"S-501

1 CMU - LINTEL (WITH VENEER)

1 1/2" = 1'-0"S-501

2 CMU - TYPICAL REINFORCING

1 1/2" = 1'-0"S-501

3 CMU - VMCJ DETAIL

0 6" 1' 2'

SCALE 3/4":1'-0"

4'

0 3" 6" 1'

SCALE 1-1/2":1'-0"

2'

SYMBOLS LEGEND

ROOM NAME / NUMBER

DESIGNATION

DOOR NUMBER

WINDOW / LOUVER

TYPE

WALL TYPE

ELEVATION

TARGET

ELEVATION NUMBER

INTERIOR ELEVATION

SYMBOL

SHEET ON WHICH

ELEVATION IS DRAWN

ELEVATION NUMBER

EXTERIOR ELEVATION

SYMBOL

SHEET ON WHICH

ELEVATION IS DRAWN

NORTH ARROW

SECTION NUMBER

SECTION SYMBOL

SHEET ON WHICH

SECTION IS DRAWN

DETAIL NUMBER

DETAIL SYMBOL

SHEET ON WHICH

DETAIL IS DRAWN

PLAN

NORTH

A101

SIM

A

A

4 A-200

ROOM NAME

PLAN NORTH

TRUE NORTH

ABBREVIATIONS

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLYWD PLYWOOD

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED

PVC POLYVINYL CHOLORIDE

R RADIUS, RANGE, RISER

RCP REFLECTED CEILING PLAN

RD REINFORCING STEEL BARS REBAR

REF REFERENCE, REFRIGERATOR

REG REGISTER

REINF REINFORCE

RET RETURN

REV REVISION

RH RIGHT HAND

RM ROOM

ROW RIGHT OF WAY

SC SOLID CORE

SCHED SCHEDULE

SD STORM DRAIN

SECT SECTION

SF SQUARE FOOT(FEET)

SHT SHEET

SIM SIMILAR

SPEC SPECIFICATION

SPKR SPEAKER

SQ SQUARE

SS SERVICE SINK

SST STAINLESS STEEL

STC SOUND TRANSMISSION…