Attachment_0002__Drawings.pdf
PDF 3 MB Posted
- Solicitation number
- 140P5123R0001
About this file
This solicitation package includes drawings and specifications for replacing a cooling tower and condenser water pumps at Tuskegee Airmen National Historic Site in Tuskegee, Alabama. The scope of work involves demolishing the existing cooling tower and two condenser water pumps, and installing a new cooling tower, two pumps, an expansion tank, air separator, and chemical shot feeder. The drawings provide demolition plans, new mechanical plans, details, and schedules for the equipment. Relevant federal agencies are the Department of the Interior National Park Service Southeast Region, who issued solicitation number 140P5123R0001 for this project. The package appears to contain the necessary information for contractors to understand requirements and prepare bids to complete the replacement work at the historic site.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT SITE
ALABAMA
REGION
RECOMMENDED:
Project Manager
APPROVED:
Superintendent
Date
Date
STATEREGION COUNTY
NAME OF PARK
TITLE OF PROJECTCROFT & ASSOCIATES - P15PC00467
PRIME / ARCH / MEP:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
STRUCTURAL:
PES STRUCTURAL ENGINEERS
ATLANTA, GEORGIA
SheetMark REVISION Date Initial
LOCATION WITHIN PARK
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
UNITED STATES
DEPARTMENT OF THE INTERIOR
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRELIMINARY DESIGN
/2
/2
:4 :1
P
M
REPLACE COOLING TOWER AND
CONDENSER WATER PUMPS
HANGAR 1
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
ALABAMA
1 9
XX
XXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
INDEX OF DRAWINGS
SHEET
SUB
SHEET TITLE OF SHEET
GENERAL
1 G001 COVER SHEET
MECHANICAL DEMOLITION
2 MD101 DEMO FLOOR PLAN - MECHANICAL
MECHANICAL
3 M001 MECHANICAL GENERAL NOTES & LEGEND
4 M101 NEW MECHANICAL FLOOR PLAN
5 M501 MECHANICAL DETAILS
6 M601 SCHEDULES
ELECTRICAL
7 E-001 ELECTRICAL LEGEND
8 E-002 ELECTRICAL NOTES
9 E-101 FLOOR PLAN - POWER
Grand total: 9
A
L
A
B A
M
A
L
I
C
E N S
E
D
E
N
G
I N E
E
R
V
I
N
C
E
T L
M
A
Z
PROFESSIONAL
09/25/2020
MD101
CCC-1
P-1B
P-1A
WSHP-5
WSHP-4
P-1B
P-1A
CCC-1
15 2
X KEYED NOTES:
1. DEMOLISH EXISTING COOLING TOWER AND ASSOCIATED PIPING (LOOP WATER SUPPLY & RETURN, MAKEUP WATER, ELECTRICAL CONNECTIONS, DRAIN LINE ABOVE FLOOR) AS REQUIRED FOR RECONNECTION OF
NEW EQUIPMENT. REMOVE EXISTING TEMPERATURE GAUGES (2 TOTAL)
2. DEMOLISH EXISTING INSULATION & HEAT TRACE OF ALL EXISTING PIPING LOCATED OUTSIDE.
3. DEMOLISH EXISTING PUMPS (2) AND ASSOCIATED PIPING AS REQUIRED FOR RECONNECTION OF NEW
EQUIPMENT. REMOVE EXISTING TEMPERATURE GAUGES AT PUMPS (4 TOTAL)
4. DEMOLISH EXISTING EXPANSION TANK AND ASSOCIATED PIPING AS REQUIRED FOR RECONNECTION OF
NEW EQUIPMENT
5. DEMOLISH EXISTING AIR SEPARATOR AND ASSOCIATED PIPING AS REQUIRED FOR RECONNECTION OF NEW
EQUIPMENT
6. DEMOLISH EXISTING CHEMICAL SHOT FEEDER AND PIPING AS REQUIRED FOR RECONNECTION OF NEW
EQUIPMENT
7. EXISTING WATER SOURCE HEAT PUMP TO REMAIN
8. EXISTING CONDENSER WATER SUPPLY TO REMAIN
9. EXISTING CONDENSER WATER RETURN TO REMAIN
10. DEMOLISH EXISTING SUCTION DIFFUSER, BLOCKING VALVE AND PIPING AS REQUIRED FOR RECONNECTION
TO NEW EQUIPMENT
11. AFTER EQUIPMENT IS REMOVED, FLUSH THE SYSTEM, CLEAN ALL STRAINERS AT EACH WATER SOURCE
HEAT PUMP AND IN THE MECHANICAL ROOM
12. EXISTING STORM CATCH BASIN TO REMAIN.
13. EXISTING HUB DRAIN TO REMAIN
14. REMOVE EXISTING CW MAKEUP STATION
15. REMOVE EXISTING CW MAKEUP OUTSIDE THE BUILDING AS SHOWN.
16. COOLING TOWNER SHALL BE DIASSEMBLED BEFORE REMOVAL THRU DOUBLE DOOR.
STAGING AREA
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/2
/2
:4 :2
P
M
DEMO FLOOR PLAN -
MECHANICALMD101
AEH
AEH
VLM
2 9
HANGAR ONE XX
XXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
09/23/2020
SCALE AMD101
1 MECHANICAL PLAN - DEMO
B L D
G
SCALE BMD101
2 MECHANICAL PLAN - DEMO PART PLAN
SCALE
8 0 8 16
SCALE OF FEET
A
SCALE
SCALE OF FEET
B
NOT TO SCALEMD101
3 Staging Area Map
A
L
A
B A
M
A
L
I
C
E N S
E
D
E
N
G
I N E
E
ITEMSYMBOLSYMBOL ITEM
DRAIN PIPING
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
UNION
REDUCER
AUTOMATIC AIR VENT
THERMOMETER
PRESSURE GAGE W/ GAGECOCK
STRAINER W/ BLOWDOWN VALVE
RELIEF VALVE
CHECK VALVE
CONTROL VALVE, 3-WAY
CONTROL VALVE, 2-WAY
PRESSURE REDUCING VALVE
BALANCING COCK
GLOBE VALVE
GATE VALVE
D
CWR
CWS
CALIBRATED BALANCING VALVE
BUTTERFLY VALVE
FLEXIBLE CONNECTION
MANUAL AIR VENT WITH CAP
GATE VALVE W/HOSE FITTING
BALL VALVE
THERMOMETER WELL
VALVED PRESSURE GAGE CONNECTION
N.T.S. NOT TO SCALE
HVAC LEGEND-SYMBOL
BOTTOM ELEVATION
ABOVE FINISHED FLOOR
ACCESS DOOR
CONDENSATE DRAIN
FLEXIBLE CONNECTION
B.E.
A.F.F.
A.D.
C.D.
F.C.
DRAIN PIPINGD
FLEXIBLE CONNECTION
N.T.S. NOT TO SCALE
CD CONDENSATE DRAIN
T
THERMOSTAT OR ZONE
SENSOR AS INDICATED IN
MECHANICAL SCHEDULE
REFRIGERANT LIQUIDRL
REFRIGERANT SUCTIONRS
TYPICALTYP.
# KEYED NOTE TAG
CATCH BASINCB
HUB DRAINHD
FLOOR DRAINFD
LIMIT OF CONSTRUCTION
GENERAL NOTES :
1. THESE DRAWINGS ARE SCHEMATIC, AND ARE
NOT REPRESENTATIVE OF ALL POTENTIAL
CONDITIONS. CONTRACTOR IS RESPONSIBLE
FOR COORDINATION WITH ALL OTHER
DISCIPLINES TO ENSURE PROPER
INSTALLATION OF ALL SYSTEMS AND
EQUIPMENT.
HVAC CONTROLS NOTES:
1. EXISTING BUILDING AUTOMATION SYSTEM SHALL BE REUSED.
GRAPHICS SHALL BE UPDATED TO INCLUDE ANY ADDITIONAL
CONTROL POINTS INDICATED ON THE CONTRACT DOCUMENTS.
2. EXISTING BUILDING AUTOMATION SYSTEM (BAS) IS
MANUFACTURED BY CIRCON AND INSTALLED IN 2017.
3. THE EXISTING SEQUENCE OF OPERATION FOR THE EXISTING
WSHP UNIT SHALL REMAIN UNCHANGED.
4. SEQUENCE OF OPERATION:
A. THE HVAC SYSTEM IS CONTROLLED ON AN OCCUPIED AND
UNOCCUPIED MODE OF OPERATION. CONTRACTING OFFICER
SHALL CONFIRM HOURS OF OPERATION AND IF REQUIRED, IT
SHALL BE RE-PROGRAMMED.
B. CIRCULATING PUMPS P-1A AND P-1B SHALL BE OPERATED AS
LEAD/LAG AND ON A TIME SCHEDULED AS INDICATED BY THE
CONTRACTING OFFICER AND PROGRAMMED BY THE
CONTRACTOR.
C. DURING THE UNOCCUPIED MODE, THE SYSTEM SHALL BE
OFF. THE UNOCCUPIED MODE SHALL BE OVERRIDDEN IF 1.
THE OUTDOOR AIR TEMPERATURE FALLS BELOW 36°F
(ADJUSTABLE), THE LEAD PUMP SHALL START TO CIRCULATE
CONDENSER WATER THRU THE LOOP AND COOLING TOWER
(CCC-1). 2. ANY WSHP UNIT CALLS FOR COOLING OR
HEATING.
D. DURING THE OCCUPIED MODE, THE LEAD PUMP SHALL BE
STARTED, THE COOLING TOWER (CCC-1) FAN, AND SPRAY
PUMP SHALL BE ENABLED.
E. THE CONDENSER RETURN WATER TEMPERATURE (CWRT)
SHALL BE MAINTAINED AT 90°F (ADJUSTABLE). ON A RISE IN
CWRT ABOVE 90°F (ADJUSTABLE), CCC-1 FAN SPEED SHALL
MODULATE FROM LOW TO HIGH. ON A FURTHER RISE IN
CWRT, THE SPRAY PUMP SHALL BE ACTIVATED.
F. ON A FALL IN CWRT BELOW 90°F (ADJUSTABLE), CCC-1 AND
SPRAY PUMP SHALL REMAIN OFF. ON A FURTHER FALL IN
CWRT, THE BY-PASS VALVE SHALL MODULATE OPEN TO
MAINTAIN 90°F (ADJUSTABLE) CWRT.
G. SUMP PUMP HEATERS SHALL BE ENERGIZED IF THE SUMP
PUMP WATER TEMPERATURE FALLS BELOW 38°F
(ADJUSTABLE)
H. THE EXISTING BAS SHALL CONTINUOUSLY MONITOR THE
FOLLOWING:
1. PUMP P-1A AND 1B STATUS.
2. CONDENSER WATER SUPPLY AND RETURN
3. COLLING TOWER FAN STATUS
4. COOLING TOWER FAN SPEED.
5. SPRAY PUMP STATUS
6. SUMP PUMP WATER TEMPERATURE
7. SUMP PUMP HEATER STATUS.
8. OUTDOOR AIR TEMPERATURE AND HUMIDITY
COORDINATION FOR EQUIPMENT SHUTDOWN :
1. CONTRACTOR SHALL SUBMIT A
CONSTRUCTION SCHEDULE INDICATING
EQUIPMENT DELIVERIES, TIME SCHEDULE FOR
DEMOLITION, TIME SCHEDULE FOR
INSTALLATION OF NEW EQUIPMENT, AND
SCHEDULE FOR EQUIPMENT START-UP.
CONSTRUCTION SCHEDULE SHALL BE
APPROVED BY THE CONTRACTING OFFICER
PRIOR TO PROCEEDING WITH WORK.
2. EQUIPMENT INDICATED TO BE REMOVED SHALL
BE REMOVED FROM THE JOBSITE AND
DISPOSED OF PER STATE AND FEDERAL
REGULATIONS.
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/2
/2
:4 :1
P
M
MECHANICAL GENERAL
NOTES & LEGENDM001
AEH
AEH
VLM
3 9
HANGAR ONE XX
XXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
09/23/2020
A
L
A
B A
M
A
L
I
C
E N S
E
D
E
N
G
I N E
E
M101
WSHP-2
WSHP-7
HD
FD FD
CB
WSHP-9
WSHP-1
WSHP-8
WSHP-6
WSHP-5
WSHP-4
WSHP-3
WSHP-10
CCC-1
P-1A
P-1B
FLOOR MTD
ABOVE CEILING
FLOOR MTD
ON MEZZ.
FLOOR MTD
ON MEZZ.
FLOOR MTD
FLOOR MTD
FLOOR MTD
FLOOR MTD
FLOOR MTD
ABOVE CEILING
KEYED NOTES:
1. NEW COOLING TOWER, CCC-1. RECONNECT ALL PIPING.
2. NEW PUMPS, P-1A AND P-1B. RECONNECT TO EXISTING PIPING. PROVIDE NEW
VALVES, SUCTION DIFFUSER, PRESSURE GAUGE AND TEMPERATURE GAUGES FOR
EACH PUMP SYSTEM. SEE 3/M501
3. NEW EXPANSION TANK (B&G D-40V) AND RECONNECT TO EXISTING PIPING
4. NEW AIR SEPARATOR AND RECONNECT TO EXISTING PIPING
5. NEW BURNHAM 5 GALLON CHEMICAL SHOT FEEDER AND RECONNECT TO EXISTING
PIPING. SEE 1/M501.
6. EXISTING WATER SOURCE HEAT PUMP.
7. EXISTING CONDENSER WATER SUPPLY. PROVIDE NEW FIBERGLASS INSULATION AND
ALUMINUM JACKET ON ALL PIPING OUTSIDE THE BUILDING. HEAT TRACE AT 5 W/LF
8. EXISTING CONDENSER WATER RETURN. PROVIDE NEW FIBERGLASS INSULATION
AND ALUMINUM JACKET ON ALL PIPING OUTSIDE THE BUILDING. HEAT TRACE AT 5
W/LF.
9. TEST AND BALANCE: PERFORM TESTING & BALANCING FOR NEW EQUIPMENT AS
WELL AS ALL WATER SOURCE HEAT PUMPS. TAB SHALL INCLUDE ALL HYDRONIC
SYSTEMS (EXCLUDE AIR SYSTEMS)
10. NEW SUCTION DIFFUSER.
11. NEW MAKE-UP WATER STATION. SEE DETAIL 5/M-501
12. NEW COOLING TOWER MAKEUP WATER. CONNECT TO NEW COOLING TOWER.
13. HUB DRAIN, HD, TO REMAIN.
14. CATCH BASIN, CB, TO REMAIN.
X
WSHP-5
WSHP-4
P-1B
P-1A
CCC-1
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/2
/2
:4 :2
P
M
NEW MECHANICAL FLOOR
PLANM101
AEH
AEH
VLM
4 9
HANGAR ONE XX
XXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
09/23/2020
SCALE AM101
1 MECHANICAL PLAN - NEW
SCALE BM101
2 MECHANICAL PLAN - NEW PART PLAN
SCALE
8 0 8 16
SCALE OF FEET
A
SCALE
SCALE OF FEET
B
B L D
G
09/25/2020
A
L
A
B A
M
A
L
I
C
E N S
E
D
E
N
G
I N E
E
FUNNEL FOR ADDING
CHEMICALS
FROM PUMP SUCTION
FROM PUMP DISCHARGE
5-GALLON CHEMICAL
POT FEEDER
SUPPORT STAND
EXISTING 4" CONCRETE PAD
TO FLOOR DRAIN
EXTERIOR
WALL
NEW COOLING
TOWER
CCC-1
NEW PUMP
(P-1A)
2" EXISTING CWS
2" EXISTING CWR
NOTES:
1. REPLACE EXISTING COOLING TOWER AND RECONNECT TO EXISTING PIPING
2. EXISTING MAKE-UP WATER FOR COOLING TOWER SHALL BE RECONNECTED.
3. REPLACE EXISTING PUMPS (P-1A AND P-1B) AND RECONNECT TO EXISTING PIPING
4. REPLACE EXISTING CONDENSER MAKE-UP WATER SHOT FEEDER AND RECONNECT.
5. REPLACE EXISTING AIR SEPARATOR AND RECONNECT TO EXISTING PIPING
6. REPLACE EXISTING EXPANSION TANK AND RECONNECT TO EXISTING PIPING.
NEW PUMP
(P-1B)
NEW AIR
SEPARATOR
NEW EXPANSION TANK
NEW CHEMICAL POT FEEDER
EXISTING
CONCRETE
PAD
EXISTING
CONCRETE
PAD
EXISTING
CONCRETE
PAD
NEW MAKE-UP
WATER
NEW STEEL
SUPPORTS
NEW MAKE-UP WATER
STATION. SEE 5/M501
NEW CHECK VALVE
NEW FLEX CONNECTION, TYP. (2)
NEW PRESSURE GAUGE
EXISTING CONCRETE
PAD
FLOOR
NEW BALL VALVE
(TYP.) NEW PUMPNEW
SUCTION
DIFFUSER
NEW BUTTERFLY VALVE (SHUT-OFF)
NEW GLOBE VALVE FOR BALANCING
T
CWR
AI - CONDENSER WATER SUPPLY
TEMP.
BI - CONDENSER WATER PUMP STATUS
BD - CONDENSER WATER PUMP START/STOP
NEW PUMPS
P-1A/P-1B
EXISTING CONTROL
VALVE (TYP.)
NEW
COOLING
TOWER
CCC-1
T
T
AI - CONDENSER WATER SUPPLY TEMP.
AI - CONDENSER WATER RETURN TEMP.
PROVIDE NEW TEMPERATURE AND
PRESSURE GAUGES WITH NEW COOLING
TOWER AND PUMPS. OTHER ITEMS ARE
EXISTING TO REMAIN.
THERMOMETER (TYP.)
PRESSURE GAUGE
(TYP.)
EXISTING BY-PASS
CONTROL VALVE (TYP.)
BI - CONDENSER WATER PUMP STATUS
BD - CONDENSER WATER PUMP START/STOP
CWS
FROM DOMESTIC COLD
WATER SYSTEM
PRESSURE REDUCING VALVE. SET VALVE
FOR 40 PSIG DOWNSTREAM PRESSURE
ASME APPROVED PRESSURE RELIEF
VALVE. SET FOR 60 PSIG
TO LOOP WATER
MAKE-UP
REDUCED PRESSURE PRINCIPAL
BACKFLOW PREVENTER
DRAIN FUNNEL, TYP.
RUN RELIEF VALVE DISCHARGE AND
DRAIN LINE TO NEAREST FLOOR DRAIN
TO COOLING
TOWER
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/2
/2
:4 :2
P
M
MECHANICAL DETAILSM501
AEH
AEH
VLM
5 9
HANGAR ONE XX
XXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
09/23/2020
NOT TO SCALEM501
1 CHEMICAL POT FEEDER DETAIL
NOT TO SCALEM501
2 PIPING SCHEMATIC
NOT TO SCALEM501
3 END SUCTION - BASE MOUNTED PUMP DETAIL
NOT TO SCALEM501
4 CONTROL DIAGRAM
NOT TO SCALEM501
5 MAKE-UP WATER STATION
A
L
A
B A
M
A
L
I
C
E N S
E
D
E
N
G
I N E
E
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/2
/2
:4 :2
P
M
SCHEDULESM601
AEH
AEH
VLM
6 9
HANGAR ONE XX
XXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
09/23/2020
AMBIENT TEMP
4) PROVIDE ELECTRIC IMMERSION HEATER TO MAINTAIN 40 DEG F PAN WATER TEMPERATURE. ELECTRIC HEATER SHALL BE 2 KW MINIMUM BASED ON 0 DEG F
3) PROVIDE VARIABLE SPEED DRIVE EITH BACNET CAR TO COMMUNICATE WITH EXISTING BAS
2) CORROSION RESISTANT STAINLESS STEEL BASIN
1) UNIT SHALL OPERATE AT BELOW FREEZING TEMPERATURES AND WILL REQUIRE 20% PROPYLENE GLYCOL SOLUTION
NOTES:
CCC-1 COOLING TOWER EVAPCO LSWE 4-2G6-Z 257 55 100 90 0.45 100 80 2 5 1 120 1-4
DESCRIPTION GPM °F IN °F OUT PD (FT WC) DB °F WB °F QNTY HP HP GPMMARK MFGR BASIS OF DESIGN
CAPACITY
(MBH)
CONDENSER WATER AMBIENT AIR FANS SPRAY PUMP
NOTES
CLOSED CIRCUIT FLUID COOLER SCHEDULE
2) STAND BY PUMP
1) BALANCE FOR FLOW AND HEAD SHOWN
NOTES:
P-1B
BELL &
GOSSETT
BASE MOUNTED END
SUCTION
B&G e-1510
CONDENSER
WATER
55 50 1.5 1,800 1,2
P-1A
BELL &
GOSSETT
BASE MOUNTED END
SUCTION
B&G e-1510
CONDENSER
WATER
55 50 1.5 1,800 1
MARK MFGR DESCRIPTION
MANUFACTURER &
MODEL NO SERVICE
FLOW
(GPM)
HD.
(FT)
MOTOR
(HP) RPM NOTES
PUMP SCHEDULE
3) 304 STAINLESS STEEL STRAINER
2) ASME TANK
1) NPT CONNECTION
NOTES:
AS-1
BELL &
GOSSETT
ROLAIRTROL AIR
SEPERATOR
RL-2N
CONDENSER
WATER
55 2" NPT 0.64 1-3
MARK MFGR DESCRIPTION MODEL SERVICE
FLOW
(GPM)
OPENING SIZE
AND TYPE
PD
(FTH2O) NOTES
AIR SEPERATOR SCHEDULE (BASE BID)
1. GPM AND PRESSURE DROP THRU COIL SHOWN FOR BALANCING PURPOSES
GENERAL NOTES:
10 1.5 WVFC1019 3.16 3.78 17.9 12.5
9 1.5 WVFC1019 3.16 3.78 17.9 12.5
8 1.5 WVFC1019 3.16 3.78 17.9 12.5
7 1.5 WVFC1019 3.16 3.78 17.9 12.5
6 4.0 WGCV048 8 4.25 43.6 34.7
5 3.5 WGCV042 7 10.08 40.0 33.4
4 5.0 WGCV060 10 9.64 57.2 47.2
3 2.5 WCCH5030 5 2.86 28.8 20.9
2 1.5 WCCH5019 3.16 1.63 18.1 13.2
1 4.0 WGCV048 8 4.25 43.6 34.7
NUMBER FT TOTAL SEN
MARK TONS
MODEL
GPM
WTR PD MBH MBH
EXISTING WATER SOURCE HEAT PUMPS (FOR REFERENCE ONLY)
A
L
A
B A
M
A
L
I
C
E N S
E
D
E
N
G
I N E
E
EQUIPMENT JUNCTION BOX, VOLTAGE AND WIRING PER
EQUIPMENT REQUIREMENTS
EQUIPMENT JUNCTION BOX, WALL MOUNTED.
J
120V DUPLEX RECEPTACLE, WALL MOUNTED, 18" AFF UNO.
120V DUPLEX RECEPTACLE, CEILING MOUNTED.
120V QUAD RECEPTACLE, WALL MOUNTED, 18" AFF UNO.
SPECIAL PURPOSE OUTLET, WALL MOUNTED, 18" AFF UNO.
120V DUPLEX RECEPTACLE, IN FLUSH FLOOR BOX.
120V QUAD RECEPTACLE, IN FLUSH FLOOR BOX.
WEATHERPROOF COVER WITH GFCI RECEPTACLE, WALL
MOUNTED AT 18" AFF UNO.
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE,
WALL MOUNTED AT 18" AFF UNO.
WP
GFCI
ELECTRICAL SYMBOL LEGEND
*NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER TO DEVICE.
J
FURNITURE POWER CONNECTION.P
LIGHTING, POWER, DISTRIBUTION PANEL.
BRANCH CIRCUIT OR FEEDER: CONCEALED IN
CONSTRUCTION IN FINISHED AREAS, EXPOSED IN
UNFINISHED AREAS.
BRANCH CIRCUIT: WIRE TICK MARKS INDICATE NUMBER
OF WIRES. NO TICK MARKS INDICATE MINIMUM (2)
CONDUCTORS. GROUND WIRES NOT INDICATED.
BRANCH CIRCUIT OR FEEDER: CONCEALED IN OR
UNDERGROUND.
PHOTOCELL (EXTERIOR, INTERIOR)PC
SINGLE POLE SWITCH, 48" UNO.
3-WAY SINGLE POLE SWITCH, 48" UNO.
4 4-WAY SINGLE POLE SWITCH,48" UNO.
M MOTOR RATED SWITCH,48" UNO.
D
DIMMER SWITCH, 0-10V, LEGRAND #CD4FBL (SINGLE
POLE), #CD4FBL3P (3-WAY), OR EQUIVALENT, 48" UNO.
OS
WALL OCCUPANCY SENSOR-SINGLE OR 3-WAY, 48" UNO.
DUAL TECHNOLOGY.
LV
MULTI-BUTTON WALL STATION, LEVITON GREENMAX
DIGITAL SWITCH OR EQUIVALENT.
CEILING/WALL MOUNTED EXIT SIGN
WALL MOUNTED EMERGENCY LIGHTING FIXTURE
RECESSED DOWNLIGHT, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
EMERGENCY RECESSED DOWNLIGHT, REFER TO
LIGHTING FIXTURE SCHEDULE FOR DETAILS.
2X4 RECESSED TROFFER, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
2X2 RECESSED TROFFER, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
LINEAR STRIP FIXTURE, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
CEILING MOUNTED OCCUPANCY SENSOR, DUAL
TECHNOLOGY. WATTSTOPPER DT-300 OR EQUIVALENT.
F FAN SWITCH, WITH PILOT LIGHT.
OS
LIGHTING SYMBOL LEGEND
*NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER TO DEVICE.
CEILING MOUNTED VACANCY SENSOR, DUAL TECHNOLOGY.
WATTSTOPPER DT-300 OR EQUIVALENT.
OS
EMERGENCY 2X4 RECESSED TROFFER, REFER TO
LIGHTING FIXTURE SCHEDULE FOR DETAILS.
EMERGENCY 2X2 RECESSED TROFFER, REFER TO
LIGHTING FIXTURE SCHEDULE FOR DETAILS.
EXTERIOR WALL FIXTURE, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
DATA OUTLET WALL MOUNTED 18" AFF UNO, WITH 3/4"
CONDUIT & PULLSTRING STUBBED TO 6" ABOVE
ACCESSIBLE CEILING, TERMINATED WITH BUSHING.
TV OUTLET, SINGLE GANG BOX, 18" AFF UNO, WITH 1"
CONDUIT IN WALL, STUBBED OUT 6" ABOVE CEILING
W/PULL STRING.
DATA OUTLET WALL MOUNTED 18" UNO, WITH 3/4"
CONDUIT & PULLSTRING STUBBED TO 6" ABOVE
ACCESSIBLE CEILING,TERMINATED WITH BUSHING.
TV
DATA OUTLET FLOOR MOUNTED, WITH 1'" CONDUIT &
PULLSTRING STUBBED TO 6" ABOVE ACCESSIBLE CEILING.
FURNITURE COMMUNICATION/DATA CONNECTION.
DOORBELL PUSH BUTTON, PROVIDE SINGLE GANG BOX
WITH 3/4"C & PULLSTRING TO PLENUM SPACE ABOVE
CEILING LEVEL
DOORBELL CHIME, MOUNT AT 80" AFFB
PAGING SYSTEM CONTROL UNITPAG
SPEAKER, CEILING/PENDANT, WALLS
S
PB
WIRELESS ACCESS POINT, CEILING MOUNTED
LOW VOLTAGE SYMBOL LEGEND
*NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER TO DEVICE.
PHONE OUTLET WALL MOUNTED 18" AFF UNO, WITH 3/4"
CONDUIT & PULLSTRING STUBBED TO 6" ABOVE
ACCESSIBLE CEILING, TERMINATED WITH BUSHING.
C
DATA OUTLET, CEILING MOUNTED
CARD READER
DOOR LOCKDL
CR
SECURITY CAMERA
DOOR CONTACTDC
DB DURESS PUSH BUTTON, PROVIDE SINGLE GANG BOX
WITH 3/4"C & PULLSTRING TO PLENUM SPACE ABOVE
CEILING LEVEL
BACKBOARD: 3/4" 4FT X 8FT FIRERATED PLYWOOD
GROUND BAR
MAGNETIC DOOR HOLDER
CEILING MOUNTED SMOKE DETECTOR
FIRE ALARM TAMPER, FLOW AND PRESSURE SWITCH
RESPECTIVELY (COORDINATE EXACT QUANTITY AND
LOCATION WITH SPRINKLER SHOP DRAWINGS)
FIRE ALARM ADA APPROVED STROBE WALL DEVICE, 84"AFF
FIRE ALARM ADA APPROVED HORN WALL DEVICE, 84"AFF
FIRE ALARM ADA PULL STATION, 48"AFF
FIRE ALARM ADA APPROVED SPEAKER WALL DEVICE,
84"AFF
P
F
F
CEILING MOUNTED CO DETECTOR
SMOKE DUCT MOUNTED DETECTOR
HEAT DETECTOR
F co
P F
T
FIRE ALARM ADA APPROVED HORN/STROBE WALL DEVICE,
84"AFF
C M
M
FIRE ALARM ADA APPROVED STROBE CEILING DEVICE
FIRE ALARM ADA APPROVED HORN/STROBE CEILING
DEVICE
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FACP
FAA
FIRE ALARM ADA APPROVED SPEAKER CEILING DEVICE
FIRE ALARM ADA APPROVED SPEAKER/STROBE WALL
DEVICE, 84"AFF
F
FIRE ALARM ADA APPROVED SPEAKER/STROBE CEILING
DEVICE
FIRE ALARM SYMBOL LEGEND
*NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER TO DEVICE.
ABORT SWITCH
CONTROL (C) MODULE, MONITOR (M) MODULE
A AMPS, AMPERES
AB AS-BUILT
AC ALTERNATING CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING
JURISDICTION
AIC AMPERE INTERRUPTING
CAPACITY
AL ALARM
AM AMMETER
AT ASTRONOMIC TIMER
ATS AUTOMATIC TRANSFER
SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT
TELEVISION
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
ELECTRICAL ABBREVIATIONS:
CLR CLEARANCE
CPVC CHLORINATED
POLYVINYL CHLORIDE
CT CURRENT
TRANSFORMER
CTR COUNTER
CU COPPER
DC DIRECT CURRENT
DIA DIAMETER
DS DISCONNECT SWITCH
EA EACH
ELEC ELECTRICAL
EMER EMERGENCY
EMT ELECTRICAL METALLIC
TUBING
ES EMERGENCY STOP
FA FIRE ALARM
FACP FIRE ALARM CONTROL
PANEL
FC FULLY CLOSED
FLA FULL LOAD AMPS
FO FULLY OPEN
FU FUSE
GC GENERAL CONTRACTOR
GFCI GROUND FAULT
CIRCUIT
INTERRUPTOR
GND GROUND
HP HORSEPOWER
HZ HERTZ
IMC INTERMEDIATE METAL
CONDUIT
JB JUNCTION BOX
KVA KILO-VOLT AMP(S)
KW KILO-WATT
KWH KILO-WATT HOUR(S)
LTG LIGHTING
LTS LIGHTS
LO LOCKOUT
MC METAL-CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL
CENTER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTR METER
MTS MANUAL TRANSFER
SWITCH
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATED
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OC OVERCURRENT
OCPD OVERCURRENT
PROTECTION DEVICE
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PUSHBUTTON
PH PHASE
PNL PANELBOARD
POE POWERED OVER
ETHERNET
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA REMOTE
ANNUNCIATOR
RCC RELAY CONTROL
CABINET
REF REFERENCE
REQD REQUIRED
RMC RIGID METAL CONDUIT
SW SWITCH
SWB SWITCHBOARD
SWGR SWITCHGEAR
UC UNDER COUNTER
UL UNDERWRITERS
LABORATORY
UNO UNLESS NOTED
OTHERWISE
V VOLT(S)
VA VOLT-AMPERE(S)
VFD VARIABLE FREQUENCY
DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S)
WP WATER PROOF
XFMR TRANSFORMER
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/1
/2
:2
:1
P
M
ELECTRICAL LEGENDE-001
RER
RER
RER
7 9
HANGAR 1 XX
XXXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
08/07/202009/25/2020
GENERAL REQUIREMENTS:
1. ALL WORK SHALL CONFORM TO THE 2017 EDITION OF THE NATIONAL
ELECTRICAL CODE (NFPA 70), ALL STATE AND LOCAL CODES, RULES, AND
REGULATIONS, AND PROJECT SPECIFICATIONS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FEES, PERMITS, AND
LICENSES FOR THE COMPLETE INSTALLATION OF THE WORK OUTLINED IN
THESE CONTRACT DOCUMENTS.
3. THE CONTRACT DOCUMENTS ARE DIAGRAMMATIC IN NATURE AND NOT EVERY
DETAIL OR EXACT LOCATION OF EQUIPMENT AND/OR CONDUIT IS SHOWN.
VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO ORDERING ANY
MATERIAL OR PERFORMING ANY WORK. NOTIFY THE ENGINEER OF RECORD
OF ANY CONDITIONS OR DIMENSIONS WHICH WOULD AFFECT PERFORMANCE
OF WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS AND/OR
SPECIFICATIONS.
4. THE ELECTRICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS WITH
CATALOG SHEETS TO THE DESIGNER OF RECORD PRIOR TO ORDERING ANY
ELECTRICAL EQUIPMENT. SHOP DRAWINGS AND CATALOG SHEETS SHALL BE
SUBMITTED AS A COMPREHENSIVE COMPLETE SET, AND PARTIAL EQUIPMENT
SUBMITTALS WILL NOT BE ACCEPTED. ELECTRICAL SUBMITTALS SHALL
INCLUDE:
4.1 LIGHTING FIXTURES AND CONTROLS
4.2 PANELBOARDS AND SAFETY SWITCHES
4.3 WIRING
4.4 CONDUIT AND FITTINGS
4.5 WIRING DEVICES
5. CONTRACTOR IS TO COORDINATE W/ GENERAL CONTRACTOR IN REGARDS
TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY BONDING OR
INSURANCE REQUIREMENTS.
6. HANDLE, STORE AND PROTECT EQUIPMENT AND MATERIALS IN ACCORDANCE
WITH THE MANUFACTURER'S RECOMMENDATIONS. REPLACE DAMAGED OR
DEFECTIVE ITEMS WITH NEW ITEMS.
COORDINATION:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATIONS AND ELECTRICAL
REQUIREMENTS OF MECHANICAL/PLUMBING EQUIPMENT WITH THE
MECHANICAL/PLUMBING CONTRACTORS PRIOR TO ORDERING ANY MATERIAL
OR PERFORMING ANY WORK ASSOCIATED WITH SUCH EQUIPMENT.
2. ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATION OF LIGHT
FIXTURES WITH MECHANICAL CONTRACTOR, PLUMBING CONTRACTOR, AND
FIRE PROTECTION CONTRACTOR PRIOR TO INSTALLATION TO AVOID
CONFLICT WITH DUCTWORK, PIPING, AND SPRINKLER SYSTEM COMPONENTS.
3. EXACT DEVICE LOCATIONS (RECEPTACLES, DATA/TELEPHONE OUTLETS, LIGHT
FIXTURES, ETC.) SHALL BE COORDINATED WITH ARCHITECTURAL PLANS.
4. TRACK LIGHTS, FLOOD LIGHTS, AND WALL WASHERS SHALL HAVE THEIR
AIMING ANGLES ADJUSTED PER OWNER/ARCHITECTURAL REQUIREMENTS
PRIOR TO FINALIZATION OF LIGHTING WORK.
MATERIALS:
1. OUTLET BOXES
1.1. GENERAL USE BOXES: GALVANIZED, PRESSED STEEL UNITS OF
PROPER DEPTH AND GAUGE REQUIRED BY THE OUTLET
LOCATION. EQUIP WITH PLASTER RING OR COVER AS NECESSARY.
1.2. SPECIAL BOXES: GALVANIZED SHEET METAL OR CAST CONSTRUCTION
AND SIZED IN ACCORDANCE WITH NFPA 70. FOR SPECIAL
SYSTEM, USE BOXES AS RECOMMENDED BY THE EQUIPMENT
MANUFACTURER.
2. CONDUIT
2.1 RIGID METALLIC CONDUIT (RMC): HOT DIPPED GALVANIZED STEEL
CONFORMING TO (FS) WW-C581E AND UL 6.
2.2 ELECTRICAL METALLIC TUBING (EMT):
GALVANIZED STEEL CONFORMING TO ASA C80.3, (FS) WW-C563 AND
ULF 797.
2.3 FLEXIBLE METAL CONDUIT (FMC): SPIRAL WOUND,SQUARE LOCKED,
HOT DIPPED GALVANIZED STEEL CONFORMING TO UL 1
2.4 METAL-CLAD CABLE (MC): INTERLOCKING METALTAPE SHEATH,
CONFORMING TO UL 1569
2.5 NON-METALLIC SHEATHED CABLE (NM): CONFORMING TO UL 719
3. CONDUIT FITTINGS
3.1 RMC: HOT DIPPED GALVANIZED OR CADMIUM PLATED. FITTINGS USED
WITH COATED RMC SHALL HAVE A SIMILAR COATING.
3.2 EMT: COMPRESSION OR SET SCREW TYPE, MADE OF CADMIUM
PLATED STEEL OR HOT DIPPED GALVANIZED MALLEABLE IRON.
3.3 MC: TWO SCREW, DOUBLE CLAMP MALLEABLE IRON, HOT DIPPED
GALVANIZED OR CADMIUM PLATED.
4. WIRING
4.1 ALL WIRING SHALL BE COPPER UNLESS NOTED OTHERWISE.
4.2 INSULATION: HEAT AND MOISTURE RESISTANT WITH A TEMPERATURE
RATING OF AT LEAST 75 DEGREES THERMAL HIGH HEAT NYLON
(THHN), THERMAL HIGH WATER RESISTANT NYLON (THWN) AND A 600
VOLT RATING UNLESS OTHERWISE INDICATED.
4.3 USE STRANDED CONDUCTOR ON ALL WIRING #8 AWG AND LARGER.
ALL OTHER WIRING MAY BE SOLID.
5. USE ANCHORS AND FASTENERS OF A TYPE DESIGNED AND INTENDED FOR
USE IN THE BASE MATERIAL TO WHICH THE MATERIAL OR SUPPORT IS TO BE
ATTACHED, AND CAPABLE OF SUPPORTING THE INTENDED LOAD AND WITH
STANDING ANY ASSOCIATED STRESSES AND VIBRATIONS. DO NOT USE
WOODEN PLUGS FOR FASTENING.
6. ALL MATERIALS USED FOR CONSTRUCTION SHALL BE INSTALLED IN A NEAT
AND WORK-LIKE MANNER.
7. ALL WIRING DEVICES SHALL BE SPECIFICATION GRADE AND MATCH BASE
BUILDING STANDARD DEVICE STYLE, COLOR, AND MOUNTING HEIGHT
UNLESS REQUIRED TO BE IN COMPLIANCE WITH ADA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPONENTS NECESSARY
TO INSTALL LIGHT FIXTURES PER MANUFACTURER'S RECOMMENDATIONS.
THIS INCLUDES, BUT IS NOT LIMITED TO, MOUNTING HARDWARE, SLOPED-
CEILING ADAPTORS, GYP BOARD TRIM KITS, ETC.
9. FOR ALL TELEPHONE/DATA OUTLETS, PROVIDE AN OUTLET BOX WITH 3/4”
CONDUIT AND A PULL STRING TO THE ACCESSIBLE CEILING SPACE.
10. ALL MATERIALS AND EQUIPMENT FURNISHED AND INSTALLED BY THE
ELECTRICAL CONTRACTOR SHALL BE NEW, UL LISTED OR LABELED, AND
CONFORM TO NEMA ANS/ANSI STANDARDS WHERE APPLICABLE.
11. FURNISH AND INSTALL PULL BOXES, JUNCTION BOXES, AND DEVICE BOXES
OF SUITABLE GAUGE AND SIZE AS NECESSARY TO PROVIDE A FULLY
FUNCTIONAL AND CODE COMPLIANT SYSTEM.
EXECUTION:
1. MAINTAIN THE INTEGRITY OF ALL EXISTING CIRCUITS IN SERVICE THAT MAY
BE AFFECTED BY THIS WORK. IDENTIFY ALL SOURCES OF POWER AND DE-
ENERGIZE REQUIRED CIRCUITS BEFORE BEGINNING WORK.
2. PERFORM ALL CUTTING AND DRILLING TO PROVIDE PENETRATIONS
THROUGH WALLS AND FLOORS FOR ELECTRICAL INSTALLATION WORK.
3. WHERE CONDUITS PASS THROUGH FIRE RATED OR SMOKE RATED
ASSEMBLIES, CONTRACTOR SHALL FOLLOW UL GUIDELINES FOR
SEALING/STOPPING PENETRATIONS TO MAINTAIN FIRE AND/OR SMOKE
RATING OF WALL ASSEMBLY.
4. ALL DEVICES AND JUNCTION BOXES SHALL BE ACCESSIBLE. PROVIDE
ACCESS PANELS AS REQUIRED TO ENSURE ACCESS TO DEVICES.
COORDINATE ACCESS PANEL LOCATIONS AND TYPES WITH ARCHITECT OF
RECORD AND GENERAL CONTRACTOR PRIOR TO ORDERING AND
INSTALLATION.
5. DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL STRUCTURAL
SUPPORTS, OR OTHERWISE DIRECTLY ON EQUIPMENT, PROVIDED NO
MODIFICATION TO EQUIPMENT IS NECESSARY. ALL STRUCTURAL SUPPORTS
FOR ELECTRICAL EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY
ELECTRICAL CONTRACTOR.
6. ALL ELECTRICAL DEVICE CONNECTIONS SHALL BE TIGHTENED TO THE
TORQUE VALUES RECOMMENDED BY THE DEVICE MANUFACTURER. IF
THESE VALUES ARE NOT LISTED, TIGHTEN TO POUND INCH OR POUND
FOOT VALUES RECOMMENDED BY UL STANDARD 486A-B.
7. GROUNDING
7.1 ALL ELECTRICAL EQUIPMENT, WIRING, CONDUITS, AND BUILDING
ELEMENTS SHALL BE GROUNDED PER THE REQUIREMENTS OF
NFPA 70.
7.2 THE BUILDING GROUNDING ELECTRODE SYSTEM SHALL BE
INSTALLED TO MAINTAIN A RESISTANCE TO EARTH OF 25 OHMS OR
LESS. IF A SINGLE GROUNDING ELECTRODE CAN NOT MEET THIS
REQUIREMENT, THE CONTRACTOR IS REQUIRED TO INSTALL
SUPPLEMENTAL ELECTRODES PER SECTION 250.53 OF NFPA 70.
7.3 PROVIDE AN EQUIPMENT CONDUCTOR IN ALL RACEWAYS SIZED IN
ACCORDANCE WITH THE REQUIREMENTS OF NFPA 70. CONDUITS
ARE NOT PERMITTED TO BE USED IN LIEU OF A GROUND WIRE.
7.4 BOND ALL BRANCH CIRCUIT DEVICES TO THE BUILDING GROUND
SYSTEM BY MEANS OF THE GROUNDING CONDUCTOR INSTALLED IN
EACH RACEWAY.
8. CABLE INSTALLED OUTSIDE OF RACEWAYS SHALL BE SUPPORTED
INDEPENDENTLY AND NOT FROM OTHER SYSTEMS. SECURING CABLES TO
OR FROM WATERLINES, ELECTRICAL RACEWAYS, OR ANY OTHER
MECHANICAL SYSTEM IS NOT ACCEPTABLE. CABLES SHALL BE SUPPORTED
FROM BAR JOISTS, CABLE TRAYS, UNI-STRUT TRAPEZE HANGERS, OR
OTHER HANGERS INSTALLED AND APPROVED FOR THIS PURPOSE.
MAXIMUM SPACING SHALL BE 10' ON CENTER WITH A MAXIMUM 8” SAG.
CABLES SHALL MAINTAIN A MINIMUM 6” CLEARANCE FROM ELECTRICAL
EQUIPMENT.
9. IDENTIFICATION
9.1 PROVIDE 1/8” SELF-STICK LABELS WITH BLOCK LETTERING
PROTECTED WITH CLEAR TAPE TO IDENTIFY PANEL AND CIRCUIT
NUMBER AT RECEPTACLES, SWITCHES, CONTROL CABINETS, ETC.
ADDITIONALLY, PROVIDE 1-1/2” HIGH ENGRAVED LAMINATED
NAMEPLATES TO IDENTIFY CABINETS, PANELBOARDS, MOTOR
STARTERS, ETC.
9.2 IDENTIFY ALL MAJOR JUNCTION BOXES USING BLACK LETTERS TO
IDENTIFY THE PANEL AND CIRCUIT NUMBER OR SYSTEM WIRING
9.3 CONTRACTOR SHALL PROVIDE IDENTIFICATION FOR WIRING
SYSTEMS AND EQUIPMENT.
9.4 POWER WIRING SHALL HAVE CONDUCTORS COLOR BANDED IN
EACH JUNCTION AND PULL BOX.
9.5 CONTROL CIRCUIT WIRING SHALL BE IDENTIFIED WITH WIRE
NUMBERS AT EACH TERMINATION.
9.6 ON PANELBOARD NAMEPLATES, LIST THE PANEL DESIGNATION,
AMPERAGE, VOLTAGE, AND PHASE.
9.7 PROVIDE TYPEWRITTEN PANELBOARD CIRCUIT DIRECTORY IN
PANELBOARD DOOR IDENTIFYING ALL ACTIVE CIRCUITS AND
SPARES. ACTIVE CIRCUITS SHALL DESIGNATE EQUIPMENT
SERVED.IRECTORY SHALL REFLECT ACTUAL CIRCUITRY, AND SHALL
NOT BE A REPRODUCTION OF DESIGN DRAWING PANEL
SCHEDULES IF DEVIATIONS WERE MADE DURING CONSTRUCTION.
10. WIRING
10.1 ALL WIRING SHALL BE INSTALLED IN APPROVED CONDUITS OR
RACEWAYS UNLESS NOTED OTHERWISE.
10.2 ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRAL
CONDUCTORS UNLESS NOTED OTHERWISE.
10.3 WIRES SHALL BE A MINIMUM #12 AWG IN SIZE.
10.4 COLOR CODE WIRING AS FOLLOWS:
10.4.1 120/240V, 1 PHASE: NEUTRAL - WHITE, PHASE A - BLACK, PHASE B - RED,
GROUND - GREEN
10.4.2 120/208V, 3 PHASE: NEUTRAL - WHITE, PHASE A - BLACK, PHASE B - RED,
PHASE C - BLUE, GROUND - GREEN
10.4.3 277/480V, 3 PHASE: NEUTRAL - GREY, PHASE A - BROWN, PHASE B -
ORANGE, PHASE C -YELLOW, GROUND - GREEN
11. CONDUIT
11.1 ALL CONDUITS SHALL BE INSTALLED IN A CONCEALED LOCATION WHERE
POSSIBLE, WITH THE EXCEPTION OF DEDICATED MECHANICAL AND
ELECTRICAL SPACES. IN THOSE AREAS OUTSIDE OF THE EXCEPTION
WHERE IT IS NOT POSSIBLE TO INSTALL CONDUITS IN A CONCEALED
MANNER, ELECTRICAL CONTRACTOR SHALL INSTALL EXPOSED CONDUITS
PARALLEL AND AT RIGHT ANGLES TO THE NEARBY SURFACES AND
STRUCTURAL MEMBERS. IN THESE AREAS, GROUP RACEWAYS IN MINIMUM
GROUPS OF THREE RACEWAYS ON A COMMON SUPPORT SYSTEM.
11.2 PROVIDE PULL ROPE IN ALL EMPTY CONDUITS.
11.3 EXTERIOR LOCATIONS: USE RMC CONDUIT.
11.4 INTERIOR LOCATIONS, WHERE SUBJECT TO DAMAGE BELOW 8' AFF: USE RMC
OR EMT CONDUIT.
11.5 INTERIOR LOCATIONS, WHERE NOT SUBJECT TO DAMAGE, ABOVE 8' AFF, OR
IN CONCEALED LOCATIONS: USE RMC OR EMT CONDUIT.
11.6 TYPE MC CABLE FOR LIGHTING CIRCUITS IS PERMITTED IN CONCEALED
LOCATION UP TO A MAXIMUM RUN OF 6'0” FEET AT THE END OF
RUN TO CONNECT LIGHT FIXTURES TO SUPPLYING BRANCH CIRCUIT.
11.7 TYPE NM CABLE IS NOT PERMITTED TO BE USED WITHOUT CONDUIT IN ANY
LOCATIONS EXCEPT BY WRITTEN APPROVAL BY THE ENGINEER OF RECORD.
11.8 FMC IS PERMITTED TO BE USED IN FOR RUNOUTS FOR EQUIPMENT SUBJECT
TO VIBRATION (MOTORS, HVAC EQUIP, ETC.). RUNOUT LENGTHS FOR FMC
MUST BE 6'0” FEET OR LESS.
11.9 CONDUIT REQUIREMENTS IN THIS SECTION ARE PROVIDED FOR GENERAL
PRICING AND INSTALLATION GUIDANCE. CONTRACTOR IS RESPONSIBLE FOR
FOLLOWING NFPA 70 REQUIREMENTS.
12. RECEPTACLES
12.1 ALL RECEPTACLES LOCATED WITHIN 6'-0” OF A SINK OR LAVATORY SHALL BE
GFCI RATED.
13. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY BALANCING ALL
BRANCH CIRCUITS AMONG THE PHASES OF THE SYSTEM ACCORDING TO NFPA 70.
14. PRIOR TO ENERGIZING OF ALL NEW FEEDERS, CHECK ALL WIRE AND CABLE FOR
CONTINUITY FOR CIRCUITRY AND FOR SHORT CIRCUITS. CORRECT ANY
DEFICIENCIES PRIOR TO ENERGIZING.
15. RECORD DRAWINGS
15.1 MAINTAIN A SET OF DRAWINGS ON SITE. THESE DRAWINGS SHALL BE
UPDATED WITH ALL FORMAL FIELD CHANGES AND OTHER PORTIONS OF THE
WORK THAT VARY SIGNIFICANTLY FROM THE CONTRACT DOCUMENTS.
INDICATE ACTUAL ROUTING OF ALL MAIN SERVICE, TRANSFORMER, AND
PANELBOARD FEEDERS.
15.2 DELIVER RECORD DRAWINGS TO OWNER PRIOR TO CLOSEOUT OF
CONSTRUCTION.
16. ALL MATERIALS AND LABOR SHALL BE UNCONDITIONALLY WARRANTED FOR A PERIOD
OF ONE (1) YEAR FROM DATE OF SUBSTANTIAL COMPLETION. SPECIFIC
MANUFACTURER'S EQUIPMENT WARRANTIES IN EXCESS OF ONE (1) YEAR SHALL
TAKE PRECEDENCE. MANUFACTURER'S WARRANTIES SHALL BE PROVIDED
WHENEVER AVAILABLE AND POSSIBLE. ALL EQUIPMENT SHALL BE NEW AND UNUSED
FROM THE FACTORY AND SHALL NOT BE MODIFIED OR REBUILT.
GENERAL ELECTRICAL NOTES:
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/1
/2
:2
:1
P
M
ELECTRICAL NOTESE-002
RER
RER
RER
8 9
HANGAR 1 XX
XXXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
08/07/202009/25/2020
NPS OFFICENPS OFFICE
ARMY OFFICE
WAITING ROOM
SOFFIR MANAGER'S
OFFICE
DISPATCHER'S OFFICE
CADET WAITING ROOM
NPS OFFICE NPS OFFICE
HEATER ROOM
MECHANICAL COOLER
ROOM
FIRE PROTECTION
ROOM
ELECTRICAL ROOM
VISITOR ORIENTATION
HVAC ROOM
RESTROOM
RESTROOM
TEAM ROOM
CHIEF MAINT. OFFICE
SUPPLY ROOM
XFMR
PP
MDPPP1
CCC-1
P-1B
P-1A
CCC-1A
CCC-1B
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
A/E FIRM LOCATION WITHIN PARK
TITLE OF SHEET
/1
/2
:2
:1
P
M
FLOOR PLAN - POWERE-101
RER
RER
RER
9 9
HANGAR 1 XX
XXXXXX
235151
TUSKEGEE AIRMEN NATIONAL HISTORIC SITE
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
08/07/2020
1. COORDINATE WITH MECHANICAL DRAWINGS BEFORE
ANY WORK IS TO BEGIN.
GENERAL NOTES:
1. EXISTING WALL MOUNTED DISCONNECTS FOR PUMPS.
DISCONNECT EXISTING PUMPS AND RECONNECT NEW
PUMPS TO DISCONNECT UTILIZING EXISTING BRANCH
CIRCUITS.
2. EXISTING WALL MOUNTED DISCONNECTS FOR
CLOSED-CIRCUIT COOLING TOWER. DISCONNECT
EXISTING COOLING TOWER, COOLING TOWER
CIRCULATION PUMP AND COOLING TOWER HEATER
AND RECONNECT TO NEW COOLING TOWER, NEW
COOLING TOWER CIRCULATION PUMP AND NEW
COOLING TOWER HEATER UTILIZING EXISTING
BRANCH CIRCUITS.
KEY NOTES:X
E-101
1 FLOOR PLAN - POWER
8 0 8 16
SCALE OF FEET
B L D
G
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT TAG DESCRIPTION VOLTAGE PHASE MCA MOCP HP PANEL DISCONNECT SWITCH REMARKS
CCC-1 CLOSED-CIRCUIT COOLING
TOWER
480V 3 PHASE/4 WIRE 8.4 20 - REUSE EXISTING
BRANCH CIRCUIT
REUSE EXISTING
DISCONNECT
REUSE EXISTING BRANCH CIRCUIT THAT WAS SERVING
EXISTING COOLING TOWER
CCC-1A CLOSED-CIRCUIT COOLING
TOWER CIRC PUMP
480V 3 PHASE/3 WIRE 1.2 20 - REUSE EXISTING
BRANCH CIRCUIT
REUSE EXISTING
DISCONNECT
REUSE EXISTING BRANCH CIRCUIT THAT WAS SERVING
EXISTING COOLING TOWER
CCC-1B CLOSED-CIRCUIT COOLING
TOWER HEATER
480V 3 PHASE/3 WIRE 3 20 - REUSE EXISTING
BRANCH CIRCUIT
REUSE EXISTING
DISCONNECT
REUSE EXISTING BRANCH CIRCUIT THAT WAS SERVING
EXISTING COOLING TOWER
P-1A CIRCULATING PUMP 208V 3 PHASE/3 WIRE - 20 1.5 REUSE EXISTING
BRANCH CIRCUIT
REUSE EXISTING
DISCONNECT
REUSE EXISTING BRANCH CIRCUIT THAT WAS SERVING
EXISTING PUMP
P-1B CIRCULATING PUMP 208V 3 PHASE/3 WIRE - 20 1.5 REUSE EXISTING
BRANCH CIRCUIT
REUSE EXISTING
DISCONNECT
REUSE EXISTING BRANCH CIRCUIT THAT WAS SERVING
EXISTING PUMP
1 1
2 2 2
| G001 - COVER SHEET |
| MD101 - DEMO FLOOR PLAN - MECHANICAL |
| M001 - MECHANICAL GENERAL NOTES & LEGEND |
| M101 - MECHANICAL PLAN - FIRST FLOOR |
| M501 - MECHANICAL DETAILS |
| M601 - SCHEDULES |