Atch 6_ Calculations_MUHJ 19 4055 Repair Dormitory_Facility 130.pdf
PDF 11 MB Posted
- Attached to
- Joint Base Langley - Eustis (JBLE), Virginia - Repair Dormitory, Facility 130 Federal contract opportunity
- Solicitation number
- FA480025B0001
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Calculations
RENOVATE DORMITORY
FOR
633 CES, FACILITY 130
JOINT BASE LANGLEY-EUSTIS (JBLE) LANGLEY AFB, VA
100% DESIGN SUBMITTAL
6 FEBRUARY 2025
TASK ORDER NUMBER: FA480024F0138 PROJECT NUMBER: MUHJ 19-4055
DA No. 24014
Design by:
Dills Architects, P.C.
1432 N. Great Neck Road, Suite 204
Virginia Beach, Virginia 23454-1342 dillsarchitects.com
MUHJ-19-4055
Repair Dorm, 633 CES Facility 130 JBLE – Langley, Virginia
STRUCTURAL CALCULATIONS
100% Submittal
Engineer (s) Peyton D. Mulé, PE
David F. Shipman, EIT
Table of Contents Page
Design Criteria DC1 – DC10
Utility Building Calculations UB1 – UB7
Enclosure Calculations E1 – E4
Brick Pier Calculations BP1 – BP13
Stairwell Roof Calculations SR1 – SR6
Cooling Tower Platform Calculations CT1 – CT18
Design Criteria
ASCE Hazards Report Address:
1592 6th St Hampton, Virginia 23665
Standard: ASCE/SEI 7-16 Latitude: 37.072249
Risk Category: II Longitude: -76.368258
Soil Class: D - Stiff Soil Elevation: 6.316621206068881 ft
(NAVD 88)
Wind
Results:
Wind Speed 118 Vmph
10-year MRI 78 Vmph
25-year MRI 85 Vmph
50-year MRI 93 Vmph
100-year MRI 99 Vmph
Data Source: ASCE/SEI 7-16, Fig. 26.5-1B and Figs. CC.2-1–CC.2-4, and Section 26.5.2
Date Accessed: Thu Sep 19 2024
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years).
Site is in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2. Glazed openings need not be protected against wind-borne debris.
Page 1 of 3https://ascehazardtool.org/ Thu Sep 19 2024
DC1
https://ascehazardtool.org/
SS : 0.094
S1 : 0.04
Fa : 1.6
Fv : 2.4
SMS : 0.15
SM1 : 0.097
SDS : 0.1
SD1 : 0.065
TL : 8
PGA : 0.046
PGA M : 0.073
FPGA : 1.6
Ie : 1
Cv : 0.7
Seismic Design Category: A Design Response Spectrum
S (g) vs T(s)a
MCE Response SpectrumR
S (g) vs T(s)a
Design Vertical Response Spectrum
S (g) vs T(s)a
MCE Vertical Response SpectrumR
S (g) vs T(s)a
Seismic
D - Stiff SoilSite Soil Class:
Results:
Data Accessed: Thu Sep 19 2024
Date Source:
USGS Seismic Design Maps based on ASCE/SEI 7-16 and ASCE/SEI 7-16 Table 1.5-2. Additional data for site-specific ground motion procedures in accordance with ASCE/SEI 7-16 Ch. 21 are available from USGS.
Page 2 of 3https://ascehazardtool.org/ Thu Sep 19 2024
DC2
Snow
Results:
Ground Snow Load, p : 10 lb/ftg
Mapped Elevation: 6.3 ft
Data Source: ASCE/SEI 7-16, Table 7.2-8
Date Accessed: Thu Sep 19 2024
Values provided are ground snow loads. In areas designated "case study required," extreme local variations in ground snow loads preclude mapping at this scale. Site-specific case studies are required to establish ground snow loads at elevations not covered.
Snow load values are mapped to a 0.5 mile resolution. This resolution can create a mismatch between the mapped elevation and the site-specific elevation in topographically complex areas. Engineers should consult the local authority having jurisdiction in locations where the reported ‘elevation’ and ‘mapped elevation’ differ significantly from each other.
The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool.
Page 3 of 3https://ascehazardtool.org/ Thu Sep 19 2024
DC3
NRW Engineering, PC JOB TITLE Repair Dorm Facility 130 748 Lord Dunmore Dirve, Suite 101
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE 9/19/24
CHECKED BY DATE
www.struware.com
Code Search
Code:
Occupancy:
Occupancy Group = R
Risk Category & Importance Factors:
Risk Category = II
Wind Factor = 1.00 Importance Factor = 1.00
Seismic Importance factor = 1.00
Type of Construction:
Fire Rating:
Roof = 0.0 hr Floor = 0.0 hr
Building Geometry:
Roof angle (θ) 0.00 / 12 0.0 deg Building length 198.0 ft Least width 59.0 ft Mean Roof Ht (h) 28.5 ft Parapet ht above grd 30.0 ft Minimum parapet ht 1.5 ft hb for Elevated bldg 0.0 ft
Live Loads:
Roof 0 to 200 sf: 20 psf 200 to 600 sf: 24 - 0.02Area, but not less than 12 psf over 600 sf: 12 psf
Roofs used for roof gardens 100 psf
Floor:
Typical Floor 50 psf
Partitions 15 psf
Corridors above first floor 80 psf
Lobbies & first floor corridors 100 psf
Stairs and exit ways 100 psf
International Building Code 2021
Residential
DC4
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE 9/19/24
CHECKED BY DATE
Wind Loads : ASCE 7- 16
Ultimate Wind Speed 118 mph Nominal Wind Speed 91.4 mph Risk Category II Exposure Category B Enclosure Classif. Enclosed Building Internal pressure +/-0.18 Bldg Directionality (Kd) 0.85 Kh MWFRS<=60 0.700 Kh all other 0.690
Type of roof Monoslope
Topographic Factor (Kzt) Topography Flat Hill Height (H) 80.0 ft Half Hill Length (Lh) 100.0 ft Actual H/Lh = 0.80 Use H/Lh = 0.50 Modified Lh = 160.0 ft From top of crest: x = 50.0 ft Bldg up/down wind? downwind
H/Lh= 0.50 K1 = 0.000 x/Lh = 0.31 K2 = 0.792 z/Lh = 0.18 K3 = 1.000
At Mean Roof Ht:
Kzt = (1+K1K2K3)^2 = 1.00
Gust Effect Factor h = 28.5 ft Flexible structure if natural frequency < 1 Hz (T > 1 second).
B = 59.0 ft If building h/B>4 then may be flexible and should be investigated.
/z (0.6h) = 30.0 ft h/B = 0.48 Rigid structure (low rise bldg)
G = 0.85 Using rigid structure default
Rigid Structure Flexible or Dynamically Sensitive Structure ē = 0.33 Natural Frequency (η1) = 0.7 Hz ℓ = 320 ft Damping ratio (β) = 0.01 zmin = 30 ft /b = 0.450 c = 0.30 /α = 0.250 gQ, gv = 3.4 Vz = 76.0
Lz = 310.0 ft N1 = 2.85 Q = 0.88 Rn = 0.072 Iz = 0.30 Rh = 0.516 η = 1.207 h = 28.5 ft
G = 0.86 use G = 0.85 RB = 0.321 η = 2.498 RL = 0.035 η = 28.068 gR = 4.104
R = 0.807 Gf = 1.111
DC5
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE 9/19/24
CHECKED BY DATE
Ground Elevation Factor (Ke)
Grd level above sea level = 0 ft Ke = 1.0000 Constant = 0.00256
0.00256Ke = 0.00256
Enclosure Classification
Test for Enclosed Building: Ao < 0.01Ag or 4 sf, whichever is smaller
Test for Open Building: All walls are at least 80% open.
Ao ≥ 0.8Ag
Test for Partially Enclosed Building: Predominately open on one side only
Input Test Ao 500.0 sf Ao ≥ 1.1Aoi NO Ag 600.0 sf Ao > 4sf or 0.01Ag YES Aoi 1000.0 sf Aoi / Agi ≤ 0.20 YES Building is NOT Agi 10000.0 sf Partially Enclosed
Conditions to qualify as Partially Enclosed Building. Must satisfy all of the following:
Ao ≥ 1.1Aoi Ao > smaller of 4sf or 0.01 Ag Aoi / Agi ≤ 0.20 Where:
Ao = the total area of openings in a wall that receives positive external pressure.
Ag = the gross area of that wall in which Ao is identified.
Aoi = the sum of the areas of openings in the building envelope (walls and roof) not including Ao.
Agi = the sum of the gross surface areas of the building envelope (walls and roof) not including Ag.
Test for Partially Open Building: A building that does not qualify as open, enclosed or partially enclosed.
(This type building will have same wind pressures as an enclosed building.)
Reduction Factor for large volume partially enclosed buildings (Ri) :
If the partially enclosed building contains a single room that is unpartitioned , the internal pressure coefficient may be multiplied by the reduction factor Ri.
Total area of all wall & roof openings (Aog): - SF Unpartitioned internal volume (Vi) : - CF
Ri = 1.00
DC6
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE 9/19/24
CHECKED BY DATE
Wind Loads - MWFRS all h (Except for Open Buildings)
Kh = 0.690 GCpi = +/-0.18 Base pressure (qh) = 20.9 psf Bldg dim parallel to ridge = 198.0 ft G = 0.85
Roof Angle (θ) = 0.0 deg Bldg dim normal to ridge = 59.0 ft qi = qh Roof tributary area: h = 28.5 ft
Wind normal to ridge =(h/2)*L: 2822 sf ridge ht = 28.5 ft Wind parallel to ridge =(h/2)*L: 841 sf
Ultimate Wind Surface Pressures (psf)
Wind Normal to Ridge Wind Parallel to Ridge
L/B = 0.30 h/L = 0.48 L/B = 3.36 h/L = 0.14
Surface Cp qhGCp w/+qiGCpi w/-qhGCpi Dist.* Cp qhGCp w/ +qiGCpi w/ -qhGCpi
Windward Wall (WW) 0.80 14.2 see table below 0.80 14.2 see table below Leeward Wall (LW) -0.50 -8.9 -12.7 -5.1 -0.23 -4.1 -7.9 -0.4
Side Wall (SW) -0.70 -12.4 -16.2 -8.7 -0.70 -12.4 -16.2 -8.7
Leeward Roof (LR) ** Included in windward roof Neg Windward Roof: 0 to h/2* -0.90 -16.0 -19.8 -12.2 0 to h/2* -0.90 -16.0 -19.8 -12.2 h/2 to h* -0.90 -16.0 -19.8 -12.2 h/2 to h* -0.90 -16.0 -19.8 -12.2 h to 2h* -0.50 -8.9 -12.7 -5.1 h to 2h* -0.50 -8.9 -12.7 -5.1
> 2h* -0.30 -5.3 -9.1 -1.6 > 2h* -0.30 -5.3 -9.1 -1.6 Pos/min windward roof press. -0.18 -3.2 -7.0 0.6 Min press. -0.18 -3.2 -7.0 0.6
*Horizontal distance from windward edge **Roof angle < 10 degrees. Therefore, leeward roof is included in windward roof pressure zones. For monoslope roofs, NOTE: The code requires the MWFRS be designed for minimum ultimate force of 16 psf entire roof surface is either multiplied by the wall area plus an 8 psf force applied to the vertical projection of the roof. windward or leeward surface.
Windward roof overhangs : 14.2 psf (upward : add to qhGCp windward roof pressure)
Parapet z Kz Kzt qp (psf)
30.0 ft 0.701 1.00 21.2
Windward parapet: 31.8 psf (GCpn = +1.5) Leeward parapet: -21.2 psf (GCpn = -1.0)
Windward Wall Pressures at "z" (psf) Combined WW + LW Windward Wall Wind Normal Wind Parallel z Kz Kzt qzGCp w/+qiGCpi w/-qhGCpi to Ridge to Ridge
0 to 15' 0.57 1.00 11.8 8.1 15.6 20.7 16.0
20.0 ft 0.62 1.00 12.9 9.1 16.6 21.7 17.0
25.0 ft 0.67 1.00 13.7 9.9 17.5 22.6 17.8 h= 28.5 ft 0.69 1.00 14.2 10.5 18.0 23.1 18.4
DC7
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE
CHECKED BY DATE
Ultimate Wind Pressures
Wind Loads - Components & Cladding : h ≤ 60' Kh = 0.690 100.0 ft 30.0 ft
Base pressure (qh) = 20.9 psf h = 28.5 ft 0.2h = 5.7 ft 100.0 ft
Minimum parapet ht = 1.5 ft 0.6h = 17.1 ft 100.0 ft
Roof Angle (θ) = 0.0 deg GCpi = +/-0.18 Type of roof = Monoslope qi = qh = 20.9 psf
Roof Surface Pressure (psf) User input
Area 10 sf 20 sf 50 sf 100 sf 200 sf 350 sf 500 sf 1000 sf 50 sf 200 sf
Negative Zone 1 -39.30 -36.70 -33.30 -30.70 -28.1 -26.0 -24.7 -24.7 -33.3 -28.1 Negative Zone 1' -22.60 -22.60 -22.60 -22.60 -19.4 -16.9 -16.0 -16.0 -22.6 -19.4 Negative Zone 2 -51.90 -48.50 -44.10 -40.80 -37.5 -34.8 -33.1 -33.1 -44.1 -37.5 Negative Zone 3 -70.70 -64.00 -55.20 -48.50 -41.9 -36.5 -33.1 -33.1 -55.2 -41.9
Positive All Zones 16.00 16.00 16.00 16.00 16.0 16.0 16.0 16.0 16.0 16.0
Overhang Zone 1&1' -35.60 -34.90 -34.10 -33.50 -28.1 -23.7 -20.9 -20.9 -34.1 -28.1 Overhang Zone 2 -48.10 -43.70 -37.80 -33.30 -28.9 -25.3 -23.0 -23.0 -37.8 -28.9 Overhang Zone 3 -66.90 -59.20 -48.90 -41.10 -33.3 -27.0 -23.0 -23.0 -48.9 -33.3
Overhang pressures in the table above assume an internal pressure coefficient (Gcpi) of 0.0 Overhang soffit pressure equals adj wall pressure (which includes internal pressure of 3.8 psf)
Parapet qp = 21.2 psf Surface Pressure (psf) User input
Solid Parapet Pressure 10 sf 20 sf 50 sf 100 sf 200 sf 500 sf 50 sf CASE A: Zone 2 : 67.9 63.5 57.7 53.3 48.9 43.1 57.7
Zone 3 : 87.0 79.2 69.0 61.2 53.4 43.1 69.0
CASE B: Interior zone : -40.1 -38.1 -35.4 -33.4 -31.3 -28.7 -35.4 Corner zone : -45.9 -42.8 -38.8 -35.7 -32.7 -28.7 -38.8 wall a = 5.9 ft
Walls GCp +/- GCpi Surface Pressure at h Area 10 sf 100 sf 200 sf 500 sf 10 sf 100 sf 200 sf 500 sf 70 sf 200 sf
Negative Zone 4 -1.17 -1.01 -0.96 -0.90 -24.5 -21.1 -20.1 -18.8 -21.7 -20.1 Negative Zone 5 -1.44 -1.12 -1.03 -0.90 -30.1 -23.5 -21.5 -18.8 -24.5 -21.5
Positive Zone 4 & 5 1.08 0.92 0.87 0.81 22.6 19.3 18.3 16.9 19.8 18.3 Note: GCp reduced by 10% due to roof angle <= 10 deg.
User input
9/19/24
DC8
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE
CHECKED BY DATE
Snow Loads : ASCE 7- 16 Nominal Snow Forces
Roof slope = 0.0 deg Horiz. eave to ridge dist (W) = 59.0 ft
Roof length parallel to ridge (L) = 198.0 ft
Type of Roof Monoslope Ground Snow Load Pg = 10.0 psf Risk Category = II Importance Factor I = 1.0 Roof R value Rroof = 30 Thermal Factor Ct = 1.000 Exposure Factor Ce = 1.00
Pf = 0.7*Ce*Ct*I*Pg = 7.0 psf Unobstructed Slippery Surface no
Sloped-roof Factor Cs = 1.00 Balanced Snow Load = 7.0 psf Near ground level surface balanced snow load = 10.0 psf
Rain on Snow Surcharge Angle 1.18 deg Code Maximum Rain Surcharge 5.0 psf Rain on Snow Surcharge = 5.0 psf Ps plus rain surcharge = 12.0 psf Minimum Snow Load Pm = 10.0 psf
Uniform Roof Design Snow Load = 12.0 psf
0.55
Snow Drift 1 - Against roof projections, parapets, etc
Up or downwind fetch lu = 220.0 ft Projection height h = 5.2 ft Projection width/length lp = 20.0 ft Snow density γ = 15.3 pcf Balanced snow height hb = 0.46 ft hd = 2.99 ft hc = 4.74 ft hc/hb >0.2 = 10.4 Therefore, design for drift
Drift height (hd) = 2.99 ft Drift width w = 11.97 ft Surcharge load: pd = γ*hd = 45.8 psf
Balanced Snow load: = 7.0 psf
52.8 psf Snow Drift 2- Against roof projections, parapets, etc
Up or downwind fetch lu = 50.0 ft Projection height h = 4.0 ft Projection width/length lp = 20.0 ft Snow density γ = 15.3 pcf Balanced snow height hb = 0.46 ft hd = 1.39 ft hc = 3.54 ft hc/hb >0.2 = 7.7 Therefore, design for drift
Drift height (hd) = 1.39 ft Drift width w = 5.55 ft Surcharge load: pd = γ*hd = 21.2 psf
Balanced Snow load: = 7.0 psf
28.2 psf
9/19/24
Note: If bottom of projection is at least 2 feet above hb then snow drift is not required.
NOTE: Alternate spans of continuous beams shall be loaded with half the design roof snow load so as to produce the greatest possible effect - see code for loading diagrams and exceptions for gable roofs
DC9
Virginia Beach, VA 23464 JOB NO. 24.061 SHEET NO.
757-474-0612 CALCULATED BY DFS DATE 9/19/24
CHECKED BY DATE
Seismic Loads: IBC 2021 Strength Level Forces
Risk Category : II Importance Factor (Ie) : 1.00
Site Class : D
Ss (0.2 sec) = 0.09 g Fa = 1.600 S1 (1.0 sec) = 0.04 g Fv = 2.400
Site specific ground motion analysis performed:
Sms = 0.150 SDS = 0.100 Design Category = A
Sm1 = 0.096 SD1 = 0.064 Design Category = A
Seismic Design Category = A
Redundancy Coefficient ρ = 1.00 Number of Stories: 3
Structure Type: Moment-resisting frame systems of reinforced concrete
Horizontal Struct Irregularities: No plan Irregularity
Vertical Structural Irregularities: No vertical Irregularity
Flexible Diaphragms: No
Building System: Shear wall-frame interactive system w/ordinary RC moment frames & shearwalls
Seismic resisting system: Shear wall-frame interactive system w/ ordinary RC moment frames & shear walls
System Structural Height Limit: Height not limited
Actual Structural Height (hn) = 28.5 ft
DESIGN COEFFICIENTS AND FACTORS
Response Modification Coefficient (R) = 4.5 To = 0.2(Sd1/Sds) = 0.128 Over-Strength Factor (Ωo) = 2.5 Ts = Sd1/Sds = 0.638
Deflection Amplification Factor (Cd) = 4 Long Period Transition Period (TL) = error, you need to enter TL (see link above right)
SDS = 0.100
SD1 = 0.064
Seismic Load Effect (E) = Eh +/-Ev = ρ QE +/- 0.2SDS D = Qe +/- 0.000D QE = horizontal seismic force
Special Seismic Load Effect (Em) = Emh +/- Ev = Ωo QE +/- 0.2SDS D = &G40&"Qe +/-0.020D D = dead load
ALLOWABLE STORY DRIFT
Structure Type: All other structures
Allowable story drift Δa = 0.020hsx where hsx is the story height below level x
PERMITTED ANALYTICAL PROCEDURES
Index Force Analysis - Minimum lateral force Fx = 0.01Wx at each floor level
Model & Seismic Response Analysis - Permitted (see code for procedure)
Equivalent Lateral-Force (ELF) Analysis - Permitted
Building period coef. (CT) = 0.016 Cu = 1.70
Approx fundamental period (Ta) = CThn x = 0.326 Tmax = CuTa = 0.555 sec
User calculated fundamental period = T = 0.326 sec
Seismic response coef. (Cs) = SdsI/R = 0.022 need not exceed Cs = Sd1 I TL/RT^2 = 0.000 but not less than Cs = 0.044Sds*I = 0.010
USE Cs = 0.010 Design Base Shear V = 0.010W sec x= 0.90
DC10
Utility Building Calculations
JOB:
PAGE:
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Utility Roof Trusses
Top Chord Live Load 20 PSF
Top Chord Dead Load 10PSF
Bottom Chord Live Load 10 PSF
Bottom Chord Dead Load 5 PSF
Sep-24
24.061 JBLE Repair Dorm 130
UB1
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Design CMU Bearing Walls for Utility Bldg.
Known
8" CMU Wall Out-of-Plane Wind Load (from Struware) = 24.5 PSF (w)
Depth to reinforcing = 3.81 in. (d)
Running Bond Seismic Category A Roof Load acting on top of wall = 244 PLF (P)
Self weight of wall LW CMU with #5 rebar grouted at 40 in. O.C. (S) = 46 PSF (W)
Cross sectional area of #5 rebar = 0.31 in.²(As ) Effective area in compression = 42 in.² (Aₑ) f'ₘ = 1900 PSI Eₘ = 1900000 PSI Fₘ = 1/3*f'ₘ = 633 PSI Fₛ = 24000 PSI
Es = 29,000,000 PSI Wall Height = 14 ft. 5 1/2 in. (h) Wall Length = 12 ft. 4 in.
Calculations w*h
Es As
Em Sd np = k = [(np) + 2np]
1/2 -np = 0.220 j = 0.927
FsAsjd
Mrs < Mrm, therefore steel governs
Fa = 0.2*f'm[1-(12h/40tn)
] = 319 PSI
319 PSI >> 13.73 PSI, Wall is sufficient in axial strength.
fa Mmax
Fa 1.33Mr
24.061 JBLE Repair Dorm 130
Sep-24
Ra = = 177 PLF
Mmax = Swh
12*8 = 2134 ft-lb/S n = = =
1-k/3 =
15.26 p= 0.0020
0.031
Mrs = = 2189 ft-lbMrm = FmkjSd
2(12) = 3125 ft-lb
Therefore wall will work as designed+ <= 1 0.77 <= 1 fa = P + W*h/2
Ae
= 13.73 PSI
UB2
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Design of wall footing for utility bldg.
Known
1215 PLF (W) Height of Wall = 14 ft. 5 1/2 in.
Wall width = 12 in. (a) qnet = 1500 PSF Roof Wind Load = 120 PLF (w) Dead Load = 94 PLF + W = 1309 PLF (D)
Live Roof Load = 125 PLF (Lr)
Max Load Combination = LC 6. = 241 PLF Footing Depth = 1 ft., d = 9 in., b = 12 in.
Calculations b' = (W+LC)/qnet = 1 ft, however minimum design requires 2 ft.
W+LC
b' qu(b'-a)
Mu φbd
As = ρbd = Amin= 0.0018*bd = 0.1944 in /ft0.054 in
/ft
Since Amin governs, #4 bars at 12 in. O.C. are required for minimum reinforcing of a 2 ft.
wide 1 ft. deep wall footing.
= 876 PSF Mu= = 1315 in-lb/ft
Vu = qu [(b' - a)/2 - d] = 0, therefore Mu governs R = = 1.50, therefore ρ =
0.0005
24.061 JBLE Repair Dorm 130
Sep-24 qa = = 728 PSF 728 PSF << 1500 PSF qu = 1.2D+w+0.5Lr b'
Weight of wall = Length of wall = 12 ft. 4 in.
UB3
CALC. BY: DFS DATE:
CHECKED BY: DATE:
16 8 14 5 1/2 12 4 6 4 85 115 1900 633
1900000 60000 15.26 10 109 475 h (in.) b (in.) w' (psf) Ig (in
4) Yt (in.) Icr (in
) Ie (in
) W (lb.)
15.625 7.625 88 2424 3.81 614.91 2528.2 1960
5667 0.0038 0.0042 0.298 0.901 8616.5 5774
0.0181 0.3 1000 32.787 61
24000 29000000 d (in.) w (psf)
Therefore use 8 in. x 16 in. Lintel with 2 - #4 bars.
0.2 9096
0.366 0.4
12.625
Fm
(psi)
Em
(psi) fy
(psi)
Fs
(psi)
Es
(psi)
L
(ft.)
fr
(psi) fbrg(allow)
(psi) fbrg(max)
(psi)
Abrg
(in n
24.061 JBLE Repair Dorm 130
Sep-24
Lintel
Depth
(in.)
Wall
Thickness
(in.)
Wall
Height
(ft. in.)
Wall
Length
(ft. in.)
Door
Width
(ft. in.)
k As
(in j Mrm
(in-lb)
Mcr
(in-lb) f'm
(psi)
P
Dead
Load
(plf)
Live
Load
(plf)
Δmt
(in.)
Δmax
(in.)
Δallow
(in.)
Mrs
(in-lb)
V
(lb)
Mmax
(in-lb) Pe
Asb
(in
UB4
UB5
REFER TO NEXT PAGES FOR HURRICANE TIE
UB5
UB6UB6
UB7UB7
Enclosure Calculations
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Design CMU Screen Wall for Mechanical Yard.
Known
8" CMU Wall Out-of-Plane Wind Load (from Struware) = 20.9 PSF (w)
Depth to reinforcing = 3.81 in. (d)
Running Bond Seismic Category A
Self weight of wall LW CMU w/ #6 rebar grouted at 16 in. O.C. (S) = 59 PSF (W)
Cross sectional area of #6 rebar = 0.44 in^2 (As) Effective area in compression = 59 in^2 (Ae) f'm = 1900 PSI Em = 1900000 PSI Fm = 1/3*f'm = 633 PSI Fs = 24000 PSI
Es = 29,000,000 PSI Wall Height = 12 ft. 4 9/16 in. (h) Wall Length = 16 ft. 1 in.
(From top of footing)
Calculations
Ra = w*h = 259 PLF
Es As
Em Sd np = 0.110 k = [(np) + 2np]
1/2 -np = 0.372 j = 0.876
FsAsjd
Masonry resisting moment is < Steel resisting moment, therefore masonry governs
Fa = 0.2*f'm[1-(12h/40tn)
] = 341 PSI
341 PSI >> 12.39 PSI, Wall is sufficient in axial strength.
fa Mmax
Fa 1.33Mr
24.061 JBLE Repair Dorm 130
Sep-24
Mmax = Swh
= 2139 ft-lbs/S 12*2 n = = 15.26 p= = 0.0072
1-k/3 =
Mrm = FmkjSd
= 1997 ft-lbs Mrs = = 2937 ft-lbs 2(12)
Therefore wall will work as designed with #6 rebar at 16 in. O.C.
15.26*0.0017 = fa = P + W*h/2
= 12.39 PSI
Ae
+ <= 1 , 0.84 <= 1, E1
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Design Screen Wall Footing for Mechanical Yard.
Known
8" CMU Wall With 4" brick veneer. 12 ft. 4.56 in.
16 ft. 1 in.
20.9 PSF (w) 1500 PSF
40 PSF Weight of 8" CMU grout @ 48" O.C. = 59 PSF
Weight of Wall and Footing (P) = 2125.62 lbs MOVT
(1ft section) W
Calculations
Assume a 6 ft. wide footing. b
W MOVT
A S
W MOVT
A S
WL
Reinforcing
1.4W Mu = 1/8*qu(b-a) 2 = 1550 lb-ft b-a b 2
M > V, Therefore M governs reinforcing (d) = Footing depth - 3 in.
Mu φbd
As = 0.259 in^2, Therefore use #5 @ 12 in. O.C. for Transverse reinforcement.
As = 1.555 in^2, Therefore use (6) #5 spaced evenly for Longitudinal Reinforcement.
24.061 JBLE Repair Dorm 130
Sep-24
Wall Height =
Wall Length =
Out-of-Plane Wind Load (from Struware) = qnet =
Weight of 4" Clay Brick = e = = 0.84 ft.
k = = 1 ft.
Footing will work with assumed width because kern length (k) is > eccentricity (e) qmax = + = 621 PSF ρmin = 0.0018 qmin = - = 87.33 PSF
Mr = = 6377 lb-ft > 1.5*MOVT =
The wall footing will work as designed with a width of 6 ft.
qu = = 496 PSF Vu = qu*( -d)= 868 lb/ft
R = = 1.77 = ρfy(1-0.588ρfy/f'c), ρreq = 0.0000295, 2403 lb-ft
E2
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Design CMU Screen Wall for Trash Enclosure.
Known
8" CMU Wall Out-of-Plane Wind Load (from Struware) = 21.1 PSF (w)
Depth to reinforcing = 3.81 in. (d)
Running Bond Seismic Category A
Self weight of wall LW CMU w/ #6 rebar grouted at 48 in. O.C. (S) = 44 PSF (W)
Cross sectional area of #6 rebar = 0.44 in^2 (As) Effective area in compression = 40 in^2 (Ae) f'm = 1900 PSI Em = 1900000 PSI Fm = 1/3*f'm = 633 PSI Fs = 24000 PSI
Es = 29,000,000 PSI Wall Height = 8 ft. 9 in. (h) Wall Length = 12 ft. 8 in.
Calculations
Ra = w*h = 184.625 PLF
Es As
Em Sd np = 0.037 k = [(np) + 2np]
1/2 -np = 0.237 j = 0.921
FsAsjd
Steel resisting moment is < Masonry resisting moment, therefore steel governs
Fa = 0.2*f'm[1-(12h/40tn)
] = 366 PSI
366 PSI < 9.63 PSI, Wall is insufficient in axial strength.
fa Mmax
Fa 1.33Mr
24.061 JBLE Repair Dorm 130
Sep-24
Mmax = Swh
= 3231 ft-lbs/S 12*2 n = = 15.26 p= = 0.0024
15.26*0.0017 =
1-k/3 =
Mrm = FmkjSd
= 4010 ft-lbs Mrs = = 3088 ft-lbs
+ <= 1 , 0.811 <= 1, Therefore wall will work as designed with #6 rebar at 48 in. O.C.
2(12) fa = P + W*h/2
= 9.63 PSI
Ae
E3
CALC. BY: DFS DATE:
CHECKED BY: DATE:
Design Screen Wall Footing for Trash Enclosure.
Known
8" CMU Wall With 4" brick veneer interior and exterior. 8 ft. 9 in.
12 ft. 8 in.
21.1 PSF (w) 1500 PSF
40 PSF Weight of 8" CMU grout @ 48" O.C. = 44 PSF
Weight of Wall and Footing (P) = 1685 lbs MOVT
(1ft section) W
Calculations
Assume a 4 ft. wide footing. b
W MOVT
A S
W MOVT
A S
WL
Reinforcing
1.4W Mu = 1/8*qu(b-a) 2 = 524 lb-ft b-a b 2
M > V, Therefore M governs reinforcing (d) = Footing depth - 3 in.
Mu φbd
As = 0.259 in^2, Therefore use #5 @ 12 in. O.C. for Transverse reinforcement.
As = 1.037 in^2, Therefore use (5) #5 spaced evenly for Longitudinal Reinforcement.
24.061 JBLE Repair Dorm 130
Sep-24
Wall Height =
Wall Length =
Out-of-Plane Wind Load (from Struware) = qnet =
Weight of 4" Clay Brick = e = = 0.53 ft.
k = = 0.67 ft.
Footing will work with assumed width because kern length (k) is > eccentricity (e) qmax = + = 724 PSF qmin = - = 118.35 PSF
Mr = = 3370 lb-ft > 1.5*MOVT = 1212 lb-ft
The wall footing will work as designed with a width of 4 ft.
qu = = 590 PSF Vu = qu*( -d)= 344 lb/ft ρmin = 0.0018R = = 0.60 = ρfy(1-0.588ρfy/f'c), ρreq = 0.00001, E4
Brick Pier Calculations
BP1
DESIGN OF BRICK PIER
BACKING STRUCTURE
BP1
BP2
THEREFORE USE COLD FORMED STEEL SECTION 800S16254
OR (2) 600S137-33 BOXED STUD
DESIGN OF BRICK PIER
BACKING STRUCTURE
BP2
BP3BP3
BP4BP4
CALC. BY: PDM DATE:
CHECKED BY: DATE:
Design Typical P-2 Pile Cap at Brick Piers
Pier Height = 27.8 ft
Brick Weight = 40 psf (4-Sides)
Total Weight of Brick Pier = 4453.28 lbs
Pile Cap and Pile are loaded in compression only. Tie beam resolves lateral reaction at the base.
24.061 JBLE Repair Dorm 130
Sep-24
Therefore, refer to next pages for calculations.
Use 2'-6" wide x 5'-6" long x 2'-6"deep, reinforce in accordance with the typical detail shown on sheet S-504. Refer to next pages for pile cap design.
BP5
NRW Engineering, P.C.
Project
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by Date Chk'd by Date App'd by Date
PILE CAP ANALYSIS & DESIGN (ACI318-14)
In accordance with ACI318-14
Tedds calculation version 2.0.12
Design summary - PASS (0.844)
Pile analysis summary
Unit Applied Allowable Utilization Result
Pile axial compression, pile 2 kips 6 20 0.291 PASS
Pile cap design summary
Unit Required Provided Utilization Result
Flexural reinforcement in2 3 (min) 3.5 0.844 PASS
Two way col. mod. shear psi 2.1 374.7 0.006 PASS
Two way pile shear psi 9.1 164.3 0.055 PASS
5' 6" y x
1 2 z
BP6BP6
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by Date Chk'd by Date App'd by Date
Pile cap details
Pile cap width, along x axis; Lx = 5.5 ft
Pile cap width, along y axis; Ly = 2.5 ft
Total cap depth; Dcap = 25 in
Density of concrete; γconc = 150 lb/ft3
Height of soil above pile cap; hsoil = 16 in
Density of soil above pile cap; γsoil = 110 lb/ft3
Pile cap area; Acap = Lx × Ly = 1980.00 in2
Column details
Column width, along x axis; lx,col = 40 in
Column width, along y axis; ly,col = 20 in
Column location, x axis; xc = 2.75 ft
Column location, y axis; yc = 1.25 ft
Pile details
Pile material; Concrete
Concrete pile section; Circular
Pile diameter; hpile = 3 in
Allowable axial compression load; PpC,allow = 20 kips
Allowable axial tension load; PpT,allow = 0 kips
Allowable lateral load; Vp,allow = 0 kips
Number of piles; Np = 2
Pile embedment; dembed = 4 in
Pile spacing; sp = 36 in
Edge distance; E = 15 in
Surcharge loads
Surcharge dead load; pD,sur = 100 psf
Surcharge live loads; pL,sur = 100 psf
Column axial loads
Axial dead load; PD = 4.5 kips
Total area axial dead load; PD,area = γconc × Lx × Ly × Dcap + pD,sur × (Lx × Ly - lx,col × ly,col) + hsoil × γsoil × (Lx
× Ly - lx,col × ly,col) = 6.318 kips
Total area axial live load; PL,area = pL,sur × (Lx × Ly - lx,col × ly,col) = 0.819 kips
Pile group centroid
Centroid location, x direction; xpg,c = (xp1 + xp2) / Np = 2.75 ft
Centroid location, y direction; ypg,c = (yp1 + yp2) / Np = 1.25 ft
Pile distance from centroid
Pile 1 centroid distance, x direction; xp1,c = xp1 - xpg,c = -1.5 ft
Pile 1 centroid distance, y direction; yp1,c = yp1 - ypg,c = 0 ft
Pile 2 centroid distance, x direction; xp2,c = xp2 - xpg,c = 1.5 ft
Pile 2 centroid distance, y direction; yp2,c = yp2 - ypg,c = 0 ft
Moment of inertia of pile group
Moment of inertia about x-x axis; Ixx = yp1,c 2 + yp2,c
2 = 0 ft2
BP7BP7
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by Date Chk'd by Date App'd by Date
Moment of inertia about y-y axis; Iyy = xp1,c 2 + xp2,c
2 = 4.5 ft2
Loading eccentricity
Eccentricity of column load, x direction; ex,c = xc - xpg,c = 0 ft
Eccentricity of column load, y direction; ey,c = yc - ypg,c = 0 ft
Dead load pile forces
Dead axial load on pile 1; Pp1,D = (PD + PD,area) / Np = 5.41 kips
Dead axial load on pile 2; Pp2,D = (PD + PD,area) / Np = 5.41 kips
Live load pile forces
Live axial load on pile 1; Pp1,L = (PL + PL,area) / Np = 0.41 kips
Live axial load on pile 2; Pp2,L = (PL + PL,area) / Np = 0.41 kips
ASCE 7-16 load combinations (ASD)
1.0D (0.270)
1.0D + 1.0L (0.291)
1.0D + 0.6W (0.270)
0.6D + 0.6W (0.162)
Combination 2 results: 1.0D + 1.0L
Pile 2 axial load; Pp2 = 1.0 × Pp2,D + 1.0 × Pp2,L = 5.82 kips max(Pp2 / PpC,allow,0) = 0.291
PASS - Pile allowable compression load exceeds axial force
Pile cap design
Material details
Compressive strength of concrete; f'c = 3000 psi
Concrete type; Normal weight
Concrete modification factor; λ = 1
Yield strength of reinforcement; fy = 60000 psi
Compression-controlled strain limit (21.2.2.1) εty = 0.002
Nominal cover to top reinforcement; cnom,top = 3 in
Nominal cover to bottom reinforcement; cnom,bot = 3 in
ASCE 7-16 load combinations (LRFD)
1.4D (0.844)
1.2D + 1.6L + 0.5Lr (0.844)
Reinforcement in y direction
Reinforcement provided; 8 No.6 top bars (8 in c/c)
Area of reinforcement provided; As.prov = 3.52 in2
Minimum area of reinforcement (24.4.3.2); As.min = 0.0018 × Lx × Dcap = 2.97 in2
PASS - Area of reinforcement provided exceeds minimum
Maximum spacing of reinforcement (24.4.3.3); smax = min(5 × Dcap, 18 in) = 18 in
PASS - Maximum permissible reinforcement spacing exceeds actual spacing
Combination 2 results: 1.2D + 1.6L + 0.5Lr
Column modified two way shear design
Depth to reinforcement; dv2 = 16.875 in
Distance to closest pile, x direction; N.A.
BP8BP8
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by Date Chk'd by Date App'd by Date
Distance to closest pile, y direction; N.A.
Shear perimeter length; lx,perim = 53 in
Shear perimeter width; ly,perim = 25 in
Shear perimeter, modified (CRSI 5.3); bs = lx,perim + ly,perim = 78.000 in
Area inside shear perimeter; AInsidePerim = lx,perim × ly,perim = 1325.000 in2
Ultimate shear load; Vu = abs(Sum(0.833 × Pp2,LRFD2) - 1.2 × (γconc × Dcap + pD,sur + γsoil × hsoil) ×
(Acap - AInsidePerim) - 1.6 × pL,sur × (Acap - AInsidePerim)) = 2.173 kips
Ultimate shear stress from vertical load; vumod = max(Vu / (bs × dv2),0 psi) = 1.651 psi
Equivalent shear perimeter, traditional; bo = bs + dv2 = 94.875 in
Column geometry factor (Table 22.6.5.2); β = lx,col / ly,col = 2.00
Column location factor (22.6.5.3); αs =20
Concrete shear strength, traditional (22.6.5.2); vcpa = (2 + 4 / β) × λ × √(f'c × 1 psi) = 219.089 psi vcpb = (αs × dv2 / bo + 2) × λ × √(f'c × 1 psi) = 304.387 psi vcpc = 4 × λ × √(f'c × 1 psi) = 219.089 psi vcp = min(vcpa,vcpb,vcpc) = 219.089 psi
Concrete shear strength, modified (CRSI 5.3); vcp.mod = min((dv2 / (2 × (etolerance + dp / 2))) × (bo / bs) × vcp, 32 × √(f'c × 1 psi))
= 499.665 psi
Shear strength reduction factor; φv = 0.75
Nominal shear stress capacity (Eq. 22.6.1.2); vn = vcp.mod = 499.665 psi
Design shear stress capacity (8.5.1.1(d)); φvn = φv × vn = 374.749 psi vumod / φvn = 0.004
PASS - Design shear capacity exceeds ultimate shear load
Pile two way shear design, pile 2
Depth to reinforcement; dv2 = 16.875 in
Shear perimeter length; lx,perim = 24.767 in
Shear perimeter width; ly,perim = 24.767 in
Shear perimeter (22.6.4); bo = lx,perim + ly,perim = 49.534 in
Ultimate shear load; Vu = abs(Pp2,LRFD2) = 7.146 kips
Ultimate shear stress from vertical load; vug = max(Vu / (bo × dv2),0 psi) = 8.550 psi
Pile geometry factor (Table 22.6.5.2); β = ly,pile / lx,pile = 1.00
Pile location factor (22.6.5.3); αs =20
Pile shear strength (22.6.5.2); vcpa = (2 + 4 / β) × λ × √(f'c × 1 psi) = 328.634 psi vcpb = (αs × dv2 / bo + 2) × λ × √(f'c × 1 psi) = 482.738 psi vcpc = 4 × λ × √(f'c × 1 psi) = 219.089 psi vcp = min(vcpa,vcpb,vcpc) = 219.089 psi
Shear strength reduction factor; φv = 0.75
Nominal shear stress capacity (Eq. 22.6.1.2); vn = min(vcpa,vcpb,vcpc) = 219.089 psi
Design shear stress capacity (8.5.1.1(d)); φvn = φv × vn = 164.317 psi vug / φvn = 0.052
PASS - Design shear capacity exceeds ultimate shear load
BP9BP9
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by Date Chk'd by Date App'd by Date
5' 6" y x
4 No.6 bot bars (7 in c/c)
4 No.6 top bars (7 in c/c)
N o .6 b o t b a rs i n c /c
N o .6 t o p b a rs i n c /c
BP10BP10
CALC. BY: PDM DATE:
CHECKED BY: DATE:
Design Tie Beams at Brick Piers
From Brick Pier Calculations, page BP1
Uniform WL to Brick Pier = 59.9 #/ft
From previous pile calc:
Pile Cap and Pile are loaded in compression only. Tie beam resolves lateral reaction at the base.
Max Rxn transmitted to Tie Beam:
Rmax = (59.9#/ft)*(27.75ft)
Rmax = 1662 lbs
24.061 JBLE Repair Dorm 130
Sep-24
Therefore, refer to next pages for calculations. Use 1'-0" wide x 1'-0" deep, reinforce in accordance with the typical detail shown on sheet S-504. Refer to next pages for pile cap design.
BP11
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by
PDM
Date
5/23/2023
Chk'd by Date App'd by Date
RC COLUMN DESIGN
In accordance with ACI318-14
Tedds calculation version 2.2.07
Design summary
Description Unit Capacity Applied Utilization Result
Axial kips 199.4 1.7 0.009 -x x y y 1'
4 × No. 5 longitudinal bars
No. 3 ties @ 10 in c/c
Applied loads
Ultimate axial force acting on column; Pu_act = 1.7 kips
Geometry of column
Depth of column (larger dimension of column); h = 12.0 in
Width of column (smaller dimension of column); b = 12.0 in
Clear cover to reinforcement (both sides); cc = 1.5 in
Unsupported height of column about x axis; lux = 4.5 ft
Effective height factor about x axis; kx = 1.00
Column state about the x axis; Unbraced
Unsupported height of column about y axis; luy = 4.5 ft
Effective height factor about y axis; ky = 1.00
Column state about the y axis; Unbraced
Check on overall column dimensions
Column dimensions are OK - h < 4b
Reinforcement of column
Numbers of bars of longitudinal steel; N = 4
Longitudinal steel bar diameter number; Dbar_num = 5
Diameter of longitudinal bar; Dlong = 0.625 in
Stirrup bar diameter number; Dstir_num = 3
Diameter of stirrup bar; Dstir = 0.375 in
Specified yield strength of reinforcement; fy = 60000 psi
BP12BP12
MUHJ-19-4057 Repair Dorm Facility 131
Job Ref.
22.066
Section
Brick Pier Foundation Design
Sheet no./rev.
Calc. by
PDM
Date
5/23/2023
Chk'd by Date App'd by Date
Specified compressive strength of concrete; f’c = 3000 psi
Modulus of elasticity of bar reinforcement; Es = 29 × 106 psi
Modulus of elasticity of concrete; Ec = 57000 × f’c1/2 × (1psi)1/2 = 3122019 psi
Yield strain; εy = fy / Es = 0.00207
Ultimate design strain; εc = 0.003 in/in
Check for minimum area of steel - 10.6.1.1
Gross area of column; Ag = h ×b = 144.000 in2
Area of steel; Ast = N × ( π × Dlong
2) / 4 = 1.227 in2
Minimum area of steel required; Ast_min = 0.01× Ag = 1.440 in2
Area of reinforcement provided (Ast) is less than the minimum required (Ast_min) therefore apply ACI 318 clause 10.3.1.2
Reduced column area to satisfy min reinft; Ag_red = Ast / 0.01 = 122.718 in2
PASS- Reduced effective area is not less than half gross area
Check for maximum area of steel - 10.6.1.1
Permissible maximum area of steel; Ast_max = 0.08× Ag = 11.520 in2
Ast< Ast_max, PASS - Maximum steel check
Design of column ties - 25.7.2
Spacing of lateral ties; sv_ties = 10.000 in
16 times longitudinal bar diameter; sv1 = 16 × Dlong = 10.000 in
48 times tie bar diameter; sv2 = 48 × Dstir = 18.000 in
Least column dimension; sv3 = min (h,b) = 12.000 in
Required tie spacing ; s = min(sv1,sv2,sv3) = 10.000 in sv_ties < s PASS
Slenderness check about x axis
Radius of gyration; rx = 0.3 × h = 3.6 in
Actual slenderness ratio; srx_act = kx × lux / rx = 15
Slenderness ratio is less than 22, slenderness effects may be neglected
Slenderness check about y axis
Radius of gyration; ry = 0.3 × b = 3.6 in
Actual slenderness ratio; sry_act = ky × luy / ry = 15
Slenderness ratio is less than 22, slenderness effects may be neglected
Axial load capacity of axially loaded column
Strength reduction factor; φ = 0.65
Area of steel on compression face; A’s = Ast / 2 = 0.614 in2
Area of steel on tension face; As = Ast / 2 = 0.614 in2
Net axial load capacity of column; Pn =0.8 × (0.85 × f’c × (Ag_red - Ast ) + fy × Ast ) = 306.747 kips
Ultimate axial load capacity of column; Pu =φ × Pn = 199.386 kips
PASS : Column is safe in axial loading
BP13BP13
Stairwell Roof Calculations
SR1SR1
SR2SR2
www.SSMA.com34 Copyright © 2022 by the SSMA
20 psf Lateral Load
Wall Height
(ft) Spacing
(in) oc
400S137 400S162 400S200 550S162
33 ksi 50 ksi 33 ksi 50 ksi 33 ksi 50 ksi 33 ksi 50 ksi
33 43 54 68 33 43 54 68 33 43 54 68 33 43 54 68
12 1.06 1.74 3.14 4.41 1.42 2.25 4.04 5.57 1.76 2.88 5.10 6.97 1.93 2.95 5.22 7.06 16 0.83 1.50 2.92 4.18 1.17 1.99 3.79 5.31 1.48 2.60 4.82 6.69 1.74 2.77 5.05 6.89 24 0.40 4 1.04 2.50 3.72 0.70 1.50 3.32 4.81 0.97 2.06 4.28 6.14 1.35 2.41 4.70 6.55
12 0.84 1.49 2.83 4.07 1.17 1.95 3.64 5.08 1.47 2.53 4.59 6.36 1.75 2.77 5.03 6.90 16 0.57 4 1.20 2.56 3.77 0.87 1.64 3.34 4.76 1.15 2.19 4.25 6.01 1.50 2.54 4.80 6.67 24 - 0.67 3 2.06 3.21 0.33 3 1.07 4 2.78 4.16 0.55 4 1.56 3.61 5.35 1.03 2.09 4.36 6.23
12 0.62 4 1.22 2.49 3.62 0.90 1.64 3.21 4.54 1.18 2.17 4.05 5.69 1.54 2.56 4.76 6.69 16 0.31 3 0.89 4 2.18 3.28 0.57 3 1.29 2.87 4.17 0.81 4 1.78 3.66 5.29 1.24 2.28 4.48 6.40 24 - 0.30 3 1.61 3 2.65 4 - 0.64 3 2.24 4 3.48 0.15 3 1.07 3 2.94 4.54 0.69 1.74 3.94 5.85
12 0.19 3 0.70 3 1.78 4 2.67 0.41 3 1.03 3 2.33 4 3.38 0.61 3 1.44 4 2.96 4.31 1.08 2.07 4.10 5.91 16 - 0.32 3 1.42 3 2.27 3 - 0.62 3 1.94 3 2.96 4 0.20 3 0.99 3 2.52 4 3.84 0.70 4 1.69 3.72 5.51 24 - - 0.79 2 1.58 3 - - 1.25 2 2.20 3 - 0.20 2 1.73 3 3.00 3 - 0.99 4 3.01 4.76
12 - 0.25 2 1.15 3 1.82 3 - 0.50 3 1.56 3 2.35 3 0.14 2 0.81 3 2.01 3 3.05 4 0.61 3 1.53 3.34 4.97 16 - - 0.79 2 1.42 2 - - 1.16 2 1.92 3 - 0.35 2 1.57 3 2.58 3 0.17 3 1.08 3 2.88 4 4.48 24 - - 0.16 1 0.73 1 - - 0.48 1 1.18 2 - - 0.79 2 1.76 2 - 0.26 3 2.05 3 3.59 3
12 - - 0.67 2 1.17 2 - - 0.98 2 1.58 3 - 0.32 2 1.30 2 2.10 3 0.18 3 1.00 3 2.57 4 3.97 16 - - 0.32 1 0.80 2 - - 0.60 1 1.17 2 - - 0.87 2 1.65 2 - 0.51 3 2.07 3 3.43 3
24 - - - 0.15 1 - - - 0.48 1 - - 0.14 1 0.89 1 - - 1.19 2 2.48 3
20 psf Lateral Load
Wall Height
(ft) Spacing
(in) oc
350S162 362S137 362S162 362S200
33 ksi 50 ksi 33 ksi 50 ksi 33 ksi 50 ksi 33 ksi 50 ksi
33 43 54 68 33 43 54 68 33 43 54 68 33 43 54 68
12 1.16 1.89 3.36 4.46 0.91 1.53 2.77 3.80 1.23 1.99 3.55 4.76 1.55 2.56 4.49 6.01 16 0.90 1.62 3.11 4.21 0.67 1.28 2.54 3.56 0.98 1.72 3.30 4.50 1.27 2.27 4.20 5.72 24 0.43 3 1.11 4 2.64 3.72 0.24 3 0.81 4 2.11 3.10 0.50 4 1.21 2.82 4.01 0.74 4 1.71 3.65 5.18
12 0.90 1.57 2.91 3.92 0.68 1.26 2.43 3.37 0.97 1.68 3.12 4.23 1.25 2.19 3.94 5.34 16 0.60 3 1.26 2.62 3.62 0.41 3 0.97 4 2.16 3.08 0.67 4 1.36 2.82 3.92 0.92 1.85 3.60 5.00 24 - 0.69 3 2.08 4 3.06 - 0.44 3 1.66 3 2.55 4 0.13 3 0.78 3 2.27 4 3.34 0.32 3 1.21 4 2.97 4.37
12 0.64 3 1.25 2.45 3.37 0.46 3 0.99 4 2.07 2.91 0.71 4 1.36 2.67 3.66 0.95 1.82 3.38 4.65 16 0.32 3 0.91 3 2.14 4 3.03 0.16 3 0.66 3 1.77 4 2.59 0.38 3 1.01 3 2.34 3.32 0.59 3 1.43 4 3.00 4.27 24 - 0.29 3 1.56 3 2.43 3 - - 1.22 3 2.01 3 - 0.38 3 1.74 3 2.69 4 - 0.74 3 2.32 3 3.58 4
12 0.18 2 0.67 3 1.62 3 2.33 4 - 0.48 3 1.36 3 2.02 4 0.24 2 0.76 3 1.81 3 2.58 4 0.41 3 1.11 3 2.32 4 3.32 16 - 0.30 2 1.29 3 1.97 3 - 0.13 2 1.04 3 1.67 3 - 0.38 2 1.45 3 2.20 3 - 0.69 3 1.92 3 2.91 4
24 - - 0.70 2 1.35 2 - - 0.48 2 1.06 2 - - 0.84 2 1.55 2 - 1.21 2 2.19 3
12 - 0.22 2 1.00 2 1.54 3 - - 0.82 2 1.31 3 - 0.29 2 1.14 2 1.73 3 - 0.54 2 1.49 3 2.28 3
16 - - 0.68 2 1.20 2 - - 0.50 1 0.97 2 - - 0.79 2 1.36 2 - 0.12 2 1.10 2 1.88 3
24 - - 0.13 1 0.60 1 - - 0.39 1 - - 0.21 1 0.73 1 - 0.43 1 1.18 2
12 - - 0.57 1 0.98 2 - - 0.42 1 0.80 2 - - 0.66 1 1.12 2 - 0.12 1 0.91 2 1.53 2
16 - - 0.26 1 0.66 1 - - 0.13 1 0.49 1 - - 0.34 1 0.77 1 - - 0.54 1 1.15 2
24 - - - 0.11 1 - - - - - - - 0.19 1 - - - 0.50 1
20 psf Lateral Load
Wall Height
(ft) Spacing
(in) oc
600S137 600S162 600S200
33 ksi 50 ksi 33 ksi 50 ksi 33 ksi 50 ksi
33 43 54 68 97 33 43 54 68 97 33 43 54 68 97
12 1.42 2.17 3.53 4.77 7.30 2.00 3.02 5.25 7.10 11.06 2.43 3.86 7.01 9.55 15.23 16 1.27 2.02 3.40 4.65 7.20 1.82 2.85 5.10 6.95 10.91 2.25 3.66 6.81 9.36 15.04 24 0.97 1.73 3.15 4.40 6.99 1.47 2.53 4.79 6.65 10.61 1.88 3.27 6.42 9.00 14.67
12 1.29 2.04 3.41 4.66 7.21 1.85 2.87 5.11 6.96 10.91 2.26 3.65 6.73 9.25 14.84 16 1.10 1.85 3.25 4.50 7.07 1.62 2.66 4.91 6.76 10.72 2.02 3.40 6.48 9.01 14.60 24 0.73 1.48 2.93 4.18 6.80 1.18 2.25 4.51 6.38 10.34 1.56 2.91 5.98 8.54 14.12
12 1.15 1.90 3.28 4.53 7.09 1.67 2.71 4.94 6.79 10.74 2.06 3.41 6.41 8.89 14.37 16 0.92 1.67 3.08 4.33 6.92 1.40 2.45 4.69 6.55 10.50 1.77 3.11 6.10 8.59 14.06 24 0.47 1.22 2.69 3.94 6.58 0.86 1.94 4.20 6.06 10.01 1.22 2.51 5.49 8.01 13.47
12 0.82 1.56 2.97 4.21 6.80 1.25 2.28 4.48 6.37 10.29 1.60 2.86 5.63 8.00 13.16 16 0.50 1.24 2.68 3.92 6.54 0.88 1.92 4.11 6.00 9.91 1.22 2.44 5.19 7.58 12.72 24 - 0.63 4 2.13 3.36 6.03 0.19 3 1.24 3.43 5.30 9.18 0.50 4 1.66 4.37 6.77 11.86
12 0.46 4 1.17 2.59 3.81 6.42 0.79 1.78 3.79 5.58 9.63 1.11 2.24 4.71 6.92 11.64 16 - 0.76 4 2.21 3.42 6.05 0.35 3 1.33 4 3.33 5.10 9.09 0.64 4 1.73 4.18 6.38 11.06 24 - 0.01 3 1.50 3 2.68 4 5.35 - 0.52 3 2.49 3 4.21 8.09 - 0.79 3 3.19 4 5.39 9.97
12 - 0.76 3 2.15 4 3.33 5.92 0.35 3 1.26 4 3.03 4.64 8.21 0.62 3 1.62 3.76 5.75 9.94 16 - 0.28 3 1.69 3 2.84 4 5.44 - 0.75 3 2.52 3 4.08 7.58 0.10 3 1.04 3 3.16 4 5.13 9.25 24 - - 0.85 2 1.95 3 4.56 3 - - 1.60 3 3.09 3 6.44 4 - - 2.09 3 4.03 3 8.00
If no note, deflection meets L/720 1Deflection meets L/120 2Deflection meets L/240 3Deflection meets L/360 4Deflection meets L/600 See Table Notes on page 31.
Combined Axial and Lateral Loads
SR3SR3
SR4SR4
SR5SR5
SR6SR6
Cooling Tower Platform Calculations
CT1
CT2
JBLE Repair Dorm Facility 131
Job Ref.
22.066
Section
Cooling Tower Platform
Sheet no./rev.
Calc. by
DFS
Date
1/27/2025
Chk'd by Date App'd by Date
COLUMN BASE PLATE DESIGN
In accordance with AISC Steel Design Guide 1 and AISC 360-16
Tedds calculation version 2.1.12
Design summary
Overall design status; PASS
Description Unit Required Provided Utilization Result
Plate thickness (in) 0.201 0.750 0.268 PASS
Bearing strength (kips) 6.80 331.50 0.021 PASS
Bolt combined shear bending (ksi) 2.92 32.63 0.090 PASS
Anchor shear strength (kips) 0.94 12.10 0.078 PASS
Shear breakout (front) (kips) 0.94 11.71 0.080 PASS
Side shear breakout (front) (kips) 0.94 23.42 0.040 PASS
Anchor pryout (kips) 0.94 52.05 0.018 PASS
2" 6" 2"
.0
.0
.0
Plan on baseplate Elevation on baseplate
0.07 ksi
6.8 kips
0.9 kips
HSS 4x4x1/4
Bolt diameter - 0.8"
Bolt embedment - 8.0"
Flange/base weld - 0.3"
Web/base weld - 0.3"
Design forces and moments
Axial force; Pu = 6.8 kips; (Compression)
Bending moment; Mu = 0.0 kip_in
Shear force; Fv = 0.9 kips
Eccentricity; e = ABS(Mu / Pu) = 0.000 in
Anchor bolt to center of plate; f = 0in = 0.000 in
Column details
Column section; HSS 4x4x1/4
Depth; d = 4.000 in
Breadth; bf = 4.000 in
Thickness; t = 0.233 in
Baseplate details
Depth; N = 10.000 in
Breadth; B = 10.000 in
Thickness; tp = 0.750 in
Design strength; Fy = 36.0 ksi
Foundation geometry
Member thickness; ha = 12.000 in
CT3
JBLE Repair Dorm Facility 131
Job Ref.
22.066
Section
Cooling Tower Platform
Sheet no./rev.
Calc. by
DFS
Date
1/27/2025
Chk'd by Date App'd by Date
Dist center of baseplate to left edge foundation; xce1 = 18.000 in
Dist center of baseplate to right edge foundation; xce2 = 18.000 in
Dist center of baseplate to bot edge foundation; yce1 = 18.000 in
Dist center of baseplate to top edge foundation; yce2 = 18.000 in
Minimum tensile strength, base plate; Fy = 36 ksi
Minimum tensile strength, column; FyCol = 42 ksi
Compressive strength of concrete; f’c = 3 ksi
Strength reduction factors
Compression; φc = 0.65
Flexure; φb = 0.90
Weld shear; φv = 0.75
Plate cantilever dimensions
Minimum distance to edge of concrete; lmin = min(min(xce1, xce2) - N / 2 , min(yce1, yce2) - B / 2) = 13.000 in
Area of base plate; A1 = B × N = 100.000 in2
Maximum area of supporting surface; A2 = (N + 2 × lmin)2 × (B / N) = 1296.000 in2
Nominal strength of concrete under base plate; Pp = 0.85 × f'c × A1 × min(√(A2 / A1), 2) = 510.0 kips
Bending line cantilever distance m; m = (N - 0.95 × d) / 2 = 3.100 in
Bending line cantilever distance n; n = (B - 0.95 × bf) / 2 = 3.100 in
Maximum bending line cantilever; l = max(m, n) = 3.100 in
Plate thickness
Required plate thickness; tp,req = l × √((2 × Pu) / (φb × Fy × B × N)) = 0.201 in
Specified plate thickness; tp = 0.750 in
PASS - Thickness of plate exceeds required thickness
Design bearing strength (AISC 360-05-J8)
Design bearing strength; Pp = 510.00 kips
Factored bearing strength; φcPp = 331.50 kips
PASS - Allowable bearing stress exceeds applied bearing stress
Combined shear and tension in anchor bolts
Gross cross sectional area of anchor; Abolt = π × da 2 / 4 = 0.442 in2
Thickness of washer; twash = 0.250 in
Shear stress in anchor; fv = Fv / (NboltV × Abolt) = 1.06 ksi
Lever arm; z = (tp + twash / 2) / 2 = 0.438 in
Bending in anchor; Ml = Fv × z / NboltV = 0.02 kips_ft
Plastic modulus of anchor; Zbolt = da 3 / 6 = 0.070 in3
Stress in anchor due to bending; ftb = Ml / Zbolt = 2.9 ksi
Axial stress in anchor; fta = 0 ksi = 0.0 ksi
Tensile stress in anchor; ft = ftb + fta = 2.9 ksi
Nominal tensile stress of anchor (Table J3.2); Fnt = 0.75 × futa = 43.5 ksi
Nominal shear stress of anchor (Table J3.2); Fnv = 0.45 × futa = 26.1 ksi
Tensile stress of anchor; φFnt = φ × Fnt = 32.6 ksi
Modified tensile stress (Eqn J3-3a); φF'nt = min(φ × (1.3 × Fnt - (Fnt / (φ × Fnv)) × fv), φFnt) = 32.6 ksi
PASS - Combined shear and bending resistance of rods exceed tensile stress in rods
CT4
JBLE Repair Dorm Facility 131
Job Ref.
22.066
Section
Cooling Tower Platform
Sheet no./rev.
Calc. by
DFS
Date
1/27/2025
Chk'd by Date App'd by Date
ANCHOR BOLT DESIGN
In accordance with ACI318-19 (22)
Tedds calculation version 2.1.11
Anchor bolt geometry
Type of anchor bolt; Cast-in headed end bolt anchor
Diameter of anchor bolt; da = 0.75 in
Number of bolts in x direction; Nboltx = 2
Number of bolts in y direction; Nbolty = 2
Total number of bolts; ntotal = (Nboltx × 2) + (Nbolty - 2) × 2 = 4
Total number of bolts in tension; ntens = (NboltN × 2) + (Nbolty - 2) = 2
Spacing of bolts in x direction; sboltx = 6 in
Spacing of bolts in y direction; sbolty = 6 in
Number of threads per inch; nt = 10
Effective cross-sectional area of anchor; Ase = π / 4 × (da - 0.9743 in / nt)2 = 0.334 in2
Embedded depth of each anchor bolt; hef = 8 in
Material details
Minimum yield strength of steel; fya = 36 ksi
Nominal tensile strength of steel; futa = 58 ksi
Compressive strength of concrete; f’c = 3 ksi
Concrete modification factor; λ = 1.00
Modification factor for cast-in anchor concrete failure λa = 1.0 × λ= 1.00
Strength reduction factors
Tension of steel element; φt,s = 0.75
Shear of steel element; φv,s = 0.65
Concrete tension; φt,c = 0.65
Concrete shear; φv,c = 0.70
Concrete tension for pullout; φt,cB = 0.70
Concrete shear for pryout; φv,cB = 0.70
Shear force applied to bolt group; V = 0.94 kips
Steel strength of anchor in shear (17.7.1)
Built-up grout pads are used so nominal strength will be multiplied by 0.8 (17.7.1.2.1)
Effective number of anchors in shear; NboltV = 2
Nom strength of anchor in shear; Vsa = 0.8 × NboltV × 0.6 × Ase × futa = 18.62 kips
Steel strength of anchor in shear; φVsa = φv,s × Vsa = 12.10 kips
PASS - Steel strength of anchor exceeds shear in bolts
CT5
JBLE Repair Dorm Facility 131
Job Ref.
22.066
Section
Cooling Tower Platform
Sheet no./rev.
Calc. by
DFS
Date
1/27/2025
Chk'd by Date App'd by Date
Concrete breakout strength in shear perpendicular to edge - Case 2. All shear resisted by rear bolts (17.7.2)
.0
.0
' 3
.0
1' 3.0" 6.0" 1' 3.0"
Plan on foundation
AA
Concrete breakout - shear
0.94 kips
3'
' 8
Section A-A
The anchors are influenced by three or more edges where any edge distance is less than 1.5ca1 so value of ca1 is limited to c'a1 (17.7.2.1.2).
Bolt offset for limiting shear; xV,r = 11.00 in
Limiting edge distance; c’a1 = 10 in
Applied shear; Vapp = V = 0.94 kips
Edge distance x for shear near corner; ca1 = 21 in
Edge distance y for shear near corner; ca2 = min(yce1, yce2) - (((Nbolty - 1)/2) × sbolty) = 15 in
Load bearing length of anchor; le = min(hef, 8 × da) = 6 in
Basic concrete breakout strength; Vb1 = 7 × (le / da)0.2 × √(da) × λa × √(f'c × 1psi) × (c'a1)1.5 = 15.92 kips
Vb2 = 9 × λa × √(f'c × 1psi × 1 in) × (c'a1)1.5 = 15.59 kips
Basic concrete breakout strength; Vb = Min(Vb1, Vb2) = 15.59 kips
Projected area of a single anchor; AVco = 4.5 × c'a1 2 = 450 in2
Projected area of a group of anchors; AVc = 432 in2
Mod factor for edge effect; ψed.V = 1.000 = 1.000
Eccentricity of loading; e’V = 0 in
Modification factor of eccentric loading; ψec,V = min(1, 1 / (1 + ((2 × e'V) / (3 × c'a1)))) = 1.000
Modification factor for cracking; ψc,V = 1.000
Modification factor for edge distance; ψh,V = max(√(1.5 × c'a1 / ha), 1) = 1.118
Nominal concrete break out strength in shear; Vcbg = AVc / AVco × ψec,V × ψed,V × ψc,V × ψh,V × Vb = 16.73 kips
Concrete break out strength in shear; φVcbg = φv,c ×Vcbg = 11.71 kips
PASS - Shear breakout perpendicular to edge strength exceeds shear in bolts
CT6
JBLE Repair Dorm Facility 131
Job Ref.
22.066
Section
Cooling Tower Platform
Sheet no./rev.
Calc. by
DFS
Date
1/27/2025
Chk'd by Date App'd by Date
Concrete breakout strength in shear perpendicular to edge - Case 3. All shear resisted by front bolts (17.7.2)
.0
.0
' 3
.0
1' 3.0" 6.0" 1' 3.0"
Plan on foundation
AA
Concrete breakout - shear
0.94 kips
3'
' 8
The anchors are influenced by three or more edges where any edge distance is less than 1.5ca1 so value of ca1 is limited to c'a1 (17.7.2.1.2).
Bolt offset for limiting shear; xV,f = 5.00 in
Limiting edge distance; c’a1 = 10 in
Applied shear; Vapp = V = 0.94 kips
Edge distance x for shear near corner; ca1 = 15 in
Edge distance y for shear near…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .