About this file

This is a Pothole Report and Subsurface Utility Engineering (SUE) Test Hole Data Report prepared by T2 Utility Engineering for the City of Santa Monica's Moss Avenue Pump Station Rehabilitation Project (Project No. CA16200400), with Woodard & Curran serving as the client. The report documents the results of five exploratory test holes (TH-1A through TH-5A) conducted on January 21, 2026, at the Moss Pump Station located at Appian Way in Santa Monica, Los Angeles County. The investigation identified multiple electrical utilities with concrete encasement running in a southeast-northwest direction, as well as a metallic electric utility running east-west. All utilities were located and marked with reference markers, with depths ranging from 0.90 feet to 4.70 feet below the natural ground surface. The test holes revealed 24-inch electrical concrete encasements at various depths, with one instance where metal debris prevented complete documentation of utility bottom depth. The report includes detailed cross-sections, site photographs, utility descriptions, and swing tie measurements to establish precise utility locations relative to reference structures such as irrigation boxes and electric boxes.

The test hole data serves as a critical planning document for the upcoming Moss Avenue Pump Station Rehabilitation Project, for which the City of Santa Monica is accepting electronic bids through the OpenGov vendor portal with a bid deadline of 3:00 p.m. on Thursday, September 17, 2026. This subsurface utility information is essential for contractors to understand existing utility conflicts and depths during construction planning and execution. The SUE investigation was conducted prior to bid solicitation to provide prospective bidders with accurate utility location data, thereby reducing risk of utility strikes during project implementation and ensuring safe construction practices.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NO: CA16200400

CLIENT: WOODARD & CURRAN

PROJECT: PW SANTA MONICA - MOSS PUMP STATION

SUE CREW/TRUCK NO:

CITY,COUNTY: SANTA MONICA, LA, LA

LOCATION/INTERSECTION: MOSS PUMP STATION-APPIAN WAY

SURFACE TYPE REFERENCE MARKER (RM) UTILITY TYPE

ASPHALT A OTHER O CUT X X ROD & CAP RC BURIED ELECTRIC BE EXPLORATORY EXP GAS SERVICE GS STREET LIGHT SL WATER MAIN WM

CONCRETE C ASPHALT/CONCRETE AC LATHE L SLEEVE S BURIED TELECOM BT FIBER OPTIC CABLE FOC OTHER O TRAFFIC SIGNAL TS RECLAIMED WATER RW

INTERLOCK BRICK I NAIL & DISK ND WOODEN STAKE W CABLE TV CATV FORCE MAIN FM SANITARY SEWER SAN UNKNOWN UNK FUEL LINE FL

NATURAL GROUND NG OTHER O PK NAIL PK COMBINED SEWER COMB GAS MAIN/PIPELINE GM STORM SEWER STM WATER SERVICE WS PIPELINE PL

ASBESTOS AC CORRUGATED METAL PIPE CMP PLASTIC (PVC, PE, HDPE) PL CONCRETE CONC OTHER O WOOD WD

CLAY CL DIRECT BURIED CABLE DBC METALLIC (IRON,STEEL,COATED) MET COPPER CU UNKNOWN UNK FIBERGLASS FIBG

TH NO TH DATE UTILITY TYPE UTILITY

MATERIAL

UTILITY

DIRECTION

UTILITY WIDTH

(FIELD)

APPARENT

UTILITY

OWNER

SWING TIE SWING TIE FROM

STRUCTURE

SWING TIE

APPROX

DISTANCE

DEPTH RM

TO TOP OF

UTILITY

SURFACE TYPE

TH-1A 1/21/2026 ELEC - SOUTHEAST -

NORTHWEST 24.00" SANTA

MONICA

A B C

90° FOC 1

East of irrigation box East of electric box

0.6' 10.3' 20.2'

0.90' NG

TH-2A 1/21/2026 ELEC - SOUTHEAST -

NORTHWEST 24.00" SANTA

MONICA

A B C

90° FOC 2

East of irrigation box East of electric box

0.6' 11.7' 20.2'

0.90' NG

TH-3A 1/21/2026 ELEC - SOUTHEAST -

NORTHWEST 24.00" SANTA

MONICA

A B C

90° FOC 1

East of irrigation box East of electric box

10.1' 5.7'

10.11'

2.00' NG

TH-4A 1/21/2026 ELEC - SOUTHEAST -

NORTHWEST 24.00" SANTA

MONICA

A B C

90° FOC 2

East of irrigation box East of electric box

10.1' 8.6' 11.9'

2.00' NG

TH-5A 1/21/2026 ELEC MET EAST - WEST 1.00" SANTA

MONICA

A B C

90° FOC 3

West of irrigation box West of electric box

4.1' 6.7' 17.5'

0.90' NG

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 0.90 FT TOP AND 2.60 FT BOTTOM.

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 0.90 FT TOP, UNABLE TO GET BOTTOM, METAL

DEBRIS IN THE WAY.

TEST HOLE DATA SUMMARY

JDW, /JD, /, JD, RC, JDW/, RC/719, 721

5622 Research Drive Suite A Huntington Beach, California 92649

TEL:714.487.5780

www.T2ue.com

UTILITY MATERIAL

REMARKS

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 2.00 FT TOP AND 4.70 FT BOTTOM.

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 2.00 FT TOP AND 4.70 FT BOTTOM

FOUND 1 IN METAL ELECTRIC AT 0.90 FT TOP.

REMARKS: REVISION NOTES:

REVIEWED BY: XX ON

CHECKED BY: XX ON Note: This is a summary only and is to be used in conjunction with the Individual Test Hole Data Reports

REVISION DATE:

CLIENT TEST HOLE NO:

SUE CREW/TRUCK NO:

CITY,COUNTY:

LOCATION/INTERSECTION:

UTILITY DESCRIPTION REFERENCE MARKER

UTILITY TYPE ELECTRIC LOCATION NORTH EDGE

UTILITY MATERIAL BRICK MARKED BY LATHE

UTILITY DIRECTION STATION

UTILITY WIDTH (FIELD) 24.00" OFFSET -

UTILITY WIDTH (RECORD) - OFFSET FROM SWING TIES

APPARENT UTILITY OWNER SANTA MONICA SWING TIES FROM STRUCTURE APPROX DISTANCE

DEPTH FROM REFERENCE MARKER A 0.60'

TOP OF UTILITY 0.90' B 10.30'

BOTTOM OF UTILITY 2.60' C 20.20'

ELEVATION OF UTILITY

TOP OF UTILITY -

APPARENT BOTTOM OF UTILITY -

SURFACE

TYPE NATURAL GROUND

THICKNESS -

REMARKS:

REVISION NOTES:

REVIEWED DATE: CHECKED DATE: REVISION DATE:

REVIEWED BY: CHECKED BY:

TEST HOLE DATA REPORT

TEST HOLE NO: TH-1A TH-1A

TEST HOLE DATE: 1/21/2026 JDW RC/721

PROJECT NO: CA16200400

5622 Research Drive Suite A Huntington Beach, California 92649

TEL:714.487.5780

www.T2ue.com

SANTA MONICA, LA, LA

CLIENT: WOODARD & CURRAN

PROJECT: PW SANTA MONICA -

MOSS PUMP STATION SANTA MONICA PUMP STATION

MAP SITE PHOTO - FACING NW

CROSS SECTION - NOT TO SCALE TEST HOLE - UTILITY - FACING NORTH

DISCLAIMER: ADDITIONAL MATERIAL AND/OR UTILITIES MAY EXIST BELOW APPARENT BOTTOM

SOUTHEAST -

NORTHWEST

90° FOC 1

East of irrigation box East of electric box

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 0.90 FT TOP AND 2.60 FT BOTTOM.

CITY,COUNTY:

LOCATION/INTERSECTION:

UTILITY DESCRIPTION REFERENCE MARKER

UTILITY TYPE ELECTRIC LOCATION NORTH EDGE

UTILITY MATERIAL BRICK MARKED BY LATHE

UTILITY DIRECTION STATION

UTILITY WIDTH (FIELD) 24.00" OFFSET -

UTILITY WIDTH (RECORD) - OFFSET FROM SWING TIES

APPARENT UTILITY OWNER SANTA MONICA SWING TIES FROM STRUCTURE APPROX DISTANCE

DEPTH FROM REFERENCE MARKER A 0.60'

TOP OF UTILITY 0.90' B 11.70'

BOTTOM OF UTILITY - C 20.20'

ELEVATION OF UTILITY

TOP OF UTILITY -

APPARENT BOTTOM OF UTILITY -

SURFACE

TYPE NATURAL GROUND

THICKNESS -

REMARKS:

REVISION NOTES:

REVIEWED DATE: CHECKED DATE: REVISION DATE:

REVIEWED BY: CHECKED BY:

TEST HOLE DATA REPORT

TEST HOLE NO: TH-2A TH-2A

TEST HOLE DATE: 1/21/2026 /721

PROJECT NO: CA16200400

5622 Research Drive Suite A Huntington Beach, California 92649

TEL:714.487.5780

www.T2ue.com

SANTA MONICA, LA, LA

CLIENT: WOODARD & CURRAN

PROJECT: PW SANTA MONICA -

MOSS PUMP STATION SANTA MONICA PUMP STATION

MAP SITE PHOTO - FACING NORTH

CROSS SECTION - NOT TO SCALE TEST HOLE - UTILITY - FACING NW

DISCLAIMER: ADDITIONAL MATERIAL AND/OR UTILITIES MAY EXIST BELOW APPARENT BOTTOM

SOUTHEAST -

NORTHWEST

90° FOC 2

East of irrigation box East of electric box

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 0.90 FT TOP, UNABLE TO GET

BOTTOM, METAL DEBRIS IN THE WAY.

CITY,COUNTY:

LOCATION/INTERSECTION:

UTILITY DESCRIPTION REFERENCE MARKER

UTILITY TYPE ELECTRIC LOCATION SOUTH EDGE

UTILITY MATERIAL BRICK MARKED BY WOODEN STAKE

UTILITY DIRECTION STATION

UTILITY WIDTH (FIELD) 24.00" OFFSET -

UTILITY WIDTH (RECORD) - OFFSET FROM

APPARENT UTILITY OWNER SANTA MONICA SWING TIES FROM STRUCTURE APPROX DISTANCE

DEPTH FROM REFERENCE MARKER A 10.10'

TOP OF UTILITY 2.00' B 5.70'

BOTTOM OF UTILITY 4.70' C 10.11'

ELEVATION OF UTILITY

TOP OF UTILITY -

APPARENT BOTTOM OF UTILITY -

SURFACE

TYPE NATURAL GROUND

THICKNESS -

REMARKS:

REVISION NOTES:

REVIEWED DATE: CHECKED DATE: REVISION DATE:

REVIEWED BY: CHECKED BY:

TEST HOLE DATA REPORT

TEST HOLE NO: TH-3A TH-3A

TEST HOLE DATE: 1/21/2026 JDW RC/721

PROJECT NO: CA16200400

5622 Research Drive Suite A Huntington Beach, California 92649

TEL:714.487.5780

www.T2ue.com

SANTA MONICA, LA, LA

CLIENT: WOODARD & CURRAN

PROJECT: PW SANTA MONICA -

MOSS PUMP STATION SANTA MONICA PUMP STATION

MAP SITE PHOTO - FACING NW

CROSS SECTION - NOT TO SCALE TEST HOLE - UTILITY - FACING NORTH

DISCLAIMER: ADDITIONAL MATERIAL AND/OR UTILITIES MAY EXIST BELOW APPARENT BOTTOM

SOUTHEAST -

NORTHWEST

90° FOC 1

East of irrigation box

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 2.00 FT TOP AND 4.70 FT BOTTOM.

CITY,COUNTY:

LOCATION/INTERSECTION:

UTILITY DESCRIPTION REFERENCE MARKER

UTILITY TYPE ELECTRIC LOCATION NORTH EDGE

UTILITY MATERIAL BRICK MARKED BY LATHE

UTILITY DIRECTION STATION

UTILITY WIDTH (FIELD) 24.00" OFFSET -

UTILITY WIDTH (RECORD) - OFFSET FROM

APPARENT UTILITY OWNER SANTA MONICA SWING TIES FROM STRUCTURE APPROX DISTANCE

DEPTH FROM REFERENCE MARKER A 10.10'

TOP OF UTILITY 2.00' B 8.60'

BOTTOM OF UTILITY 4.70' C 11.90'

ELEVATION OF UTILITY

TOP OF UTILITY -

APPARENT BOTTOM OF UTILITY -

SURFACE

TYPE NATURAL GROUND

THICKNESS -

REMARKS:

REVISION NOTES:

REVIEWED DATE: CHECKED DATE: REVISION DATE:

REVIEWED BY: CHECKED BY:

TEST HOLE DATA REPORT

TEST HOLE NO: TH-4A TH-4A

TEST HOLE DATE: 1/21/2026 JDW RC/721

PROJECT NO: CA16200400

5622 Research Drive Suite A Huntington Beach, California 92649

TEL:714.487.5780

www.T2ue.com

SANTA MONICA, LA, LA

CLIENT: WOODARD & CURRAN

PROJECT: PW SANTA MONICA -

MOSS PUMP STATION SANTA MONICA PUMP STATION

MAP SITE PHOTO - FACING NW

CROSS SECTION - NOT TO SCALE TEST HOLE - UTILITY - FACING SW

DISCLAIMER: ADDITIONAL MATERIAL AND/OR UTILITIES MAY EXIST BELOW APPARENT BOTTOM

SOUTHEAST -

NORTHWEST

90° FOC 2

East of irrigation box

FOUND 24 IN ELECTRICAL CONCRETE ENCASEMENT AT 2.00 FT TOP AND 4.70 FT BOTTOM

CITY,COUNTY:

LOCATION/INTERSECTION:

UTILITY DESCRIPTION REFERENCE MARKER

UTILITY TYPE ELECTRIC LOCATION CENTER OF UTILITY

UTILITY MATERIAL MARKED BY LATHE

UTILITY DIRECTION EAST - WEST STATION

UTILITY WIDTH (FIELD) 1.00" OFFSET -

UTILITY WIDTH (RECORD) 1" OFFSET FROM SWING TIES

APPARENT UTILITY OWNER SANTA MONICA SWING TIES FROM STRUCTURE APPROX DISTANCE

DEPTH FROM REFERENCE MARKER A 4.10'

TOP OF UTILITY 0.90' B 6.70'

BOTTOM OF UTILITY 1.00' C 17.50'

ELEVATION OF UTILITY

TOP OF UTILITY -

APPARENT BOTTOM OF UTILITY -

SURFACE

TYPE NATURAL GROUND

THICKNESS -

REMARKS:

REVISION NOTES:

REVIEWED DATE: CHECKED DATE: REVISION DATE:

REVIEWED BY: CHECKED BY:

TEST HOLE DATA REPORT

TEST HOLE NO: TH-5A TH-5A

TEST HOLE DATE: 1/21/2026 JDW/ RC/721

PROJECT NO: CA16200400

5622 Research Drive Suite A Huntington Beach, California 92649

TEL:714.487.5780

www.T2ue.com

SANTA MONICA, LA, LA

CLIENT: WOODARD & CURRAN

PROJECT: PW SANTA MONICA -

MOSS PUMP STATION SANTA MONICA PUMP STATION

MAP SITE PHOTO - FACING NW

CROSS SECTION - NOT TO SCALE TEST HOLE - UTILITY - FACING NORTH

DISCLAIMER: ADDITIONAL MATERIAL AND/OR UTILITIES MAY EXIST BELOW APPARENT BOTTOM

METALLIC (IRON,

STEEL, COATED)

90° FOC 3

West of irrigation box West of electric box

FOUND 1 IN METAL ELECTRIC AT 0.90 FT TOP.