Appendix D-Coyote Ridge ES_CD_08222025.pdf
PDF 2 MB Posted
- Attached to
- Building Automation Upgrade Project (Phase 6)
- Solicitation number
- 26-002
- Issued by
- Adams County, Denver City, Colorado
About this file
This document is a Controls Design set of schematic and points list drawings for the Adams 12 Coyote Ridge Elementary School located at 13770 Broadlands Dr, Broomfield, CO 80023. The project involves a comprehensive controls design for multiple mechanical zones throughout the school, including spaces such as computer rooms, libraries, halls, music rooms, cafeteria, storage areas, and gymnasium. The design includes detailed schematics for eight different mechanical zones (MZ-1 through MZ-8 and SZ-5 through SZ-8), each with specific temperature, ventilation, and equipment control requirements.
The technical drawings by Iconergy provide intricate details for control systems, including relief dampers, exhaust fans, temperature sensors, humidity sensors, CO2 sensors, freeze stats, and various valves and switches. Each zone schematic includes an I/O summary table detailing digital and analog inputs and outputs, with notations to "Replace with New" for most components. The project number is 251487, with an issue date of 08-22-2023, suggesting a current infrastructure upgrade or replacement project for the school's environmental control systems. The drawings indicate a standardized approach to mechanical control across different school spaces, with specific attention to temperature regulation, air quality, and safety systems.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE OF CONTENTS / LEGEND
COVER
TOC
LEGEND
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
13770 BROADLANDS DR,
BROMMFIELD, CO 80023
Appendix D
MZ-1 SCHEMATIC AND POINTS LIST
OA
M
RA
N.C.
SF
N.O.
(N)HD TEMP
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
SHEET NOTES:
(N)RAT
T
DX
DX
COIL
SMOKE
TYP. (4) ZONES: COMPUTER ROOM, FLOOR 1
LIBRARY, FLOOR 2 WEST HALL, FLOOR 2
LIBRARY.
N.C.
RH-4
RH-4 RELIEF
DAMPER
EA
DX1-SS
HWS
HWR
M
HW
N.O.
HW-VLV
DX2-SS (N)CD TEMP
T
N.C.
N.O.
(N)ZNT.SPACE
TRELAY
CT COND-ALMCONDENSING UNIT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
F-7
ZN DMPR 1
M700
MZ-1
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
13770 BROADLANDS DR,
BROOMFIELD, CO 80023
MZ-2 SCHEMATIC AND POINTS LIST
M
RA
N.C.
SF
N.O.
(N)HD TEMP
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
SHEET NOTES:
(N)RAT
T
DX
DX
COIL
SMOKE
TYP. (11) ZONES: B217, B216, B211, B218, B215,
B123, B117, B118, B112, B124, B111
N.C.
RH-5
RH-5 RELIEF
DAMPER
EA
DX1-SS
HWS
HWR
M
HW
N.O.
HW-VLV
DX2-SS (N)CD TEMP
T
N.C.
N.O.
(N)ZNT.SPACE
TRELAY
CT COND-ALMCONDENSING UNIT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
TYP. (3) F-3, F-11, EF-16&17
ZN DMPR 2
TYP. (10) ZONES: B217, B216, B218, B215, B123,
B117, B118, B112, B124, B111
F-3,F-11 ONLY3
M701
MZ-2
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
MZ-3 SCHEMATIC AND POINTS LIST
M
RA
N.C.
SF
N.O.
(N)HD TEMP
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
SHEET NOTES:
(N)RAT
T
DX
DX
COIL
SMOKE
TYP. (14) ZONES: B219, B214, SPEC B209,
OFFICE B203, B205, K2 B106, SPEC B104, PT
B105, B222, B221, B220, B129, ART B130
EA
DX1-SS
HWS
HWR
M
HW
N.O.
HW-VLV
DX2-SS (N)CD TEMP
T
N.C.
N.O.
(N)ZNT.SPACE
TRELAY
CT COND-ALMCONDENSING UNIT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
TYP. (3) F-1, F-2, RF-14
ZN DMPR 1
OUTSIDE LIGHTSEXT LIGHTING
M702
MZ-3
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
MZ-4 SCHEMATIC AND POINTS LIST
M
RA
N.C.
SF
N.O.
(N)HD TEMP
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
(N)RA CO2
SHEET NOTES:
(N)RAT
T
DX
DX
COIL
SMOKE
TYP. (4) ZONES: A115 MUSIC, A106 CAFE, CAFE
AUX L, A100 COMMS
N.C.
RH-7
RH-7 RELIEF
DAMPER
EA
DX1-SS
HWS
HWR
M
HW
N.O.
HW-VLV
DX2-SS (N)CD TEMP
T
N.C.
N.O.
(N)ZNT.SPACE
TRELAY
CT COND-ALMCONDENSING UNIT
ZN DMPR 1
(N)OA CO2(N)OAT
T
M703
MZ-4
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
SZ-5 SCHEMATIC AND POINTS LIST
M
RA
N.C.
SF
N.O.
(N)DAT
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
(N)RA CO2
SHEET NOTES:
(N)RAT
T
SMOKE
TYP. (2) ZONES: GYM, A105 STORAGE1
N.C.
RH-8
RH-8 RELIEF
DAMPER
EA
HWS
HWR
M
HW
N.O.
HW-VLV
(N)ZNT.SPACE
TRELAY
CT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
F-8
TYP. (2)MAD 50%+
M704
SZ-5
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
SZ-6 SCHEMATIC AND POINTS LIST
M
RA
N.C.
SF
N.O.
(N)DAT
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
SHEET NOTES:
(N)RAT
T
DX
SMOKE
N.C.
RH-1,-2
RH-1,-2 RELIEF
DAMPER
EA
DX1-SS
HWS
HWR
M
HW
N.O.
HW-VLV
(N)T.A127
TRELAY
CT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
TYP. (2) F-4, F-19
N.C.
M705
SZ-6
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
SZ-7 SCHEMATIC AND POINTS LIST
M
RA
N.C.
SF
N.O.
(N)DAT
T
MAD
SF-Sts
SA
T
(N)MAT
TYP. (1)
SF-SS
FREEZE
STAT
T
SHEET NOTES:
(N)RAT
T
DX
SMOKE
EA
DX1-SS
HWS
HWR
M
HW
N.O.
HW-VLV
(N)T.LOUNGE
TRELAY
CT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
F-18
DX2-SS
M706
SZ-7
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
SZ-8 SCHEMATIC AND POINTS LIST
MN.C.
SF
SF-Sts
SA
TYP. (1)
SF-SS
SHEET NOTES:
STAINLESS STEEL PLATES.1
SZ-OVRD
HTG ENAB
(N)T.CAFE AUX RIGHT
TRELAY
CT
EA
M
RELAY
EF
EF-STSCT
EF-SS
EXHAUST FAN
TYP. (4) F-5, F-10, F-12, F-13
DMPR ENAB
(N)T.FREEZER
T
(N)T.COOLER
T
ALARMANSUL SYS
CUH-6
M
SF
CUH-SSRELAY
1 1
M707
SZ-8
SCHEMATIC & PL
ADAMS 12
COYOTE RIDGE
ELEMENTARY SCHOOL
CONTROLS DESIGN
File details come from the government source that posted it. Updated .