This document comprises standard design drawings and specifications for pipe culverts issued by the South Carolina Department of Transportation (SCDOT) Design Standards Office. The standards apply to permanent pipe culvert installations for transportation applications statewide and are intended for use in SCDOT roadway projects. The drawings detail trench preparation, foundation installation, backfill procedures, and rigid reinforced concrete pipe (RCP) specifications, including joint sealant materials and installation requirements. The standards include multiple load case scenarios addressing maximum cover installations under roadways, minimum cover installations under roadways and construction vehicle loading, non-residential driveway installations, and installations below the groundwater table. All construction must comply with specifications outlined in SC-M-714 and OSHA guidelines, and all drawings must be sealed and signed by a professional engineer registered in South Carolina.
The fill height allowable values in Table 714-205A specify maximum installation depths for RCP ranging from 12 inches to 120 inches in diameter, with varying pipe classes (II through V) dependent on structural requirements and installation conditions. The standards prohibit flexible pipe culverts on all Interstate and SCDOT evacuation routes statewide; only rigid pipe culverts are permitted for these applications. Manufacturers may substitute higher-class pipe than specified without additional compensation, provided installation depths do not exceed those shown in plans. Special design pipes are required for site conditions outside typical installations and must be designed in accordance with PCDM-05. RCP materials and joint materials must be sourced from manufacturers listed on SCDOT Qualified Product Lists 60 and 69. The standards were effective January 2021 and are subject to updates available on the SCDOT website.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN STANDARDS OFFICE
955 PARK STREET
ROOM 405
COLUMBIA, SC 29201
SOUTH CAROLINA DEPARTMENT OF TRANSPORTATION
STANDARD DRAWING
SECTION
714-000
P
IP
E C
U L
V E
R T
S (P
E R
M A
N E
N T
3/2020 DSO REQ'D TRENCH WIDTH
3/2010 JBH DET3 OD
3/2009 HJC DET4 COMPAC. NOTES
7/2008 HJC GENERAL REVISIONS
3/2008 DSO NEW STANDARD
JANUARY 2021
714-005-00
PIPE CULVERTS
(PIPE TRENCH
TYPICAL
PREPARATIONS)
714-020-00
714-105-00
714-505-00
SC-M-714
PCDM-05
OSHA
NATIONAL DOCUMENTS
REFERENCES
SCDOT DOCUMENTS
RELATED DRAWINGS & KEYWORDS
THIS DRAWING IS ONLY VALID FOR
CONSTRUCTION WHEN SEALED
AND SIGNED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE
OF SOUTH CAROLINA.
CHECK WWW.SCDOT.ORG FOR LATEST
UPDATE.
EFFECTIVE LETTING DATE
# DATE CHK DESCRIPTION
SIGNATURE
DATE
DESIGN STANDARDS OFFICE
955 PARK STREET
ROOM 405
COLUMBIA, SC 29201
SOUTH CAROLINA DEPARTMENT OF TRANSPORTATION
STANDARD DRAWING
DETAIL
TRENCH PREPARATION
WITH NO IMPROVED
FOUNDATION WORK
HDPE, SRAP, & CAAP:
TRENCH WIDTH = 1.5 X PIPE OD + 12" OR THE WIDTH REQUIRED TO
SAFELY FIT COMPACTION EQUIPMENT AND PERSONNEL BETWEEN THE
PIPE AND THE TRENCH WALLS, WHICHEVER IS GREATER.
RCP:
TRENCH WIDTH = PIPE OD + 24" OR 1.33 X PIPE OD OR THE WIDTH
REQUIRED TO SAFELY FIT COMPACTION EQUIPMENT AND PERSONNEL
BETWEEN THE PIPE AND THE TRENCH WALLS, WHICHEVER IS GREATER.
CONSTRUCT EMBANKMENT AS REQUIRED
BEFORE EXCAVATION OF PIPE TRENCH.
EMBANKMENT BACKFILL MUST BE ABLE
TO SUPPORT PIPE STRUCTURAL BACKFILL.
EXCAVATE TRENCH
(WALLS MAY BE SLOPED)
FOLLOW OSHA GUIDELINES
TRENCH WIDTH
ADJACENT EMBANKMENT MATERIAL
MUST BE COMPACTED WITHIN 5%
OF COMPACTION LEVEL OF
STRUCTURAL BACKFILL
ALL PIPE REQUIRE GOOD FOUNDATION MATERIAL.
WHEN SITE SOILS REQUIRE THE INSTALLATION OF AN
IMPROVED PIPE FOUNDATION, FOLLOW SCDOT STANDARD
DRAWING 714-020-00.
DETAIL
FOUNDATION REQUIREMENTS
DETAIL
BEDDING AND INSTALLATION
WITH NO IMPROVED
FOUNDATION WORK
PLACE UNCOMPACTED BEDDING AS
DESCRIBED IN SC-M-714
GEOTEXTILE FOR DRAINAGE FILTRATION
(IF REQUIRED)
OD
OUTSIDE
DIA. (OD)
INSIDE
DIA. (ID)
COMPACT BEDDING BEYOND THE
MIDDLE OD/3 AFTER INSTALLING PIPE
BUT BEFORE PLACING BACKFILL.
PLACE PIPE ON UNCOMPACTED
BEDDING, ALIGN AND HOME
JOINTS AS DESCRIBED IN
SC-M-714
PIPE BEDDING THICKNESS MUST BE
THE GREATEST OF THE FOLLOWING:
= 6 IN MINIMUM
= OD/10 BEFORE BEDDING COMPACTION
DETAIL
BACKFILL INSTALLATION
WITH NO IMPROVED
FOUNDATION WORK
PLACE STRUCTURAL BACKFILL
LIFTS AS DESCRIBED IN SC-M-714
GEOTEXTILE FOR DRAINAGE FILTRATION
(IF REQUIRED)
MAXIMUM 6"
(COMPACTED) LIFTS
TAKE CARE TO FULLY COMPACT SOIL
WITHIN THE PIPE HAUNCH ZONE IN
ACCORDANCE WITH SC-M-714
NOTE: PIPE WILL SEAT ITSELF
AND BEDDING MATERIAL WILL
COMPRESS DURING
BACKFILLING AND COMPACTION
EMBANKMENT OR IN-SITU SOIL
COMPLETE STRUCTURAL BACKFILL
AS REQUIRED BY SC-M-714.
SEE COMPLETED TRENCH STANDARD
FOUNDATION DRAWINGS
(714-105-00 & 714-505-00)
COMPACTED BEDDING
THIS DRAWING IS NOT TO SCALE.
NO. 19782
SIGNATURE
DATE
NO. 19782
DESIGN STANDARDS OFFICE
955 PARK STREET
ROOM 405
COLUMBIA, SC 29201
SOUTH CAROLINA DEPARTMENT OF TRANSPORTATION
STANDARD DRAWING
NATIONAL DOCUMENTS
REFERENCES
SCDOT DOCUMENTS
RELATED DRAWINGS & KEYWORDS
THIS DRAWING IS ONLY VALID FOR
CONSTRUCTION WHEN SEALED
AND SIGNED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE
OF SOUTH CAROLINA.
CHECK WWW.SCDOT.ORG FOR LATEST
UPDATE.
EFFECTIVE LETTING DATE
# DATE CHK DESCRIPTION
3/2020 DSO STR. BACKFILL REQ'D
1/2016 DSO DET 3,4 UNDER PVMT
7/2009 DSO NOTE 2
3/2008 DSO NEW STANDARD
JANUARY 2021
714-105-00
PIPE CULVERTS
RIGID PIPE
COMPLETED TRENCH
(STANDARD FOUNDATION)
714-005-00
714-205-01
SC-M-714
PCDM-05
QPL 14
QPL 69
DETAIL
STANDARD FOUNDATION INSTALLATION
M I N
I M
U M
C
O V
E R
L
O A
D
C
A S
E
M A
X I M
U M
C
V
R
L
O A
D
C
A S
E
SPRINGLINE
HAUNCH ZONE
INVERT OF FULLY INSTALLED PIPE TO MATCH
INVERT ELEVATION SHOWN IN THE PLANS
NOTE: PIPE WILL SEAT ITSELF AND BEDDING MATERIAL
WILL COMPRESS DURING BACKFILLING AND COMPACTION
P I P
E
E
M B
E D
M E
N T
Z
N
E
TRENCH WALLS
(MAY BE SLOPED)
FOLLOW OSHA
GUIDELINES
TOP OF PIPE
P A
V E
M E
N T
S T
R U
C T
U R
E
S
N
T
E
TOP OF PAVEMENT STRUCTURE
BOTTOM OF PAVEMENT STRUCTURE
R O
A D
W A
Y
E
M B
A N
K M
E N
T
O
V E
R F
I L
L
TRENCH WIDTH
S T
R U
C T
U R
A L
B A
C K
F I L
L
EXISTING EMBANKMENT OR IN-SITU SOIL
GEOTEXTILE FOR DRAINAGE FILTRATION
(IF REQUIRED)
1. USE MATERIALS AND METHODS OF CONSTRUCTION FOR PERMANENT PIPE CULVERTS IN CONFORMANCE WITH SC-M-714.
2. SEE SHEET 714-205-01 FOR RCP FILL HEIGHT TABLES.
3. WHEN CONNECTING DISSIMILAR PIPE, USE DRAINAGE STRUCTURE OR DESIGN INTERFACE. DO NOT MIX PIPE TYPE, CLASS, OR DETAILS WITHIN A SINGLE RUN OF PIPE BETWEEN DRAINAGE STRUCTURES. SEE QUALIFIED PRODUCT LIST 14 FOR
PRECAST REINFORCED CONCRETE DRAINAGE STRUCTURES.
4. USE GROUTED CONNECTIONS TO DRAINAGE STRUCTURES AS INDICATED ON DRAINAGE STRUCTURE STANDARD DRAWINGS.
FOLLOW MANUFACTURER RECOMMENDATIONS FOR CONNECTIONS TO DRAINAGE STRUCTURES.
5. USE AT LEAST THE MINIMUM CLASS REQUIRED TO CARRY THE FILL HEIGHT AS SPECIFIED IN THE STANDARD DRAWING FILL
HEIGHT TABLES. WHEN PIPE CLASS IS SPECIFIED IN THE PLANS, CONFIRM THAT THE SPECIFIED CLASS CAN CARRY THE
INSTALLED MAXIMUM COVER BEFORE BACKFILLING THE PIPE. IF INSTALLED GRADES VARY FROM THOSE SHOWN IN THE
PLANS, CONFIRM THAT PIPE CLASS IS SUFFICIENT TO CARRY THE INSTALLED FILL HEIGHTS. DO NOT REDUCE THE PIPE
CLASS BELOW THE CLASS SHOWN IN THE PLANS UNLESS DIRECTED BY THE ENGINEER.
6. USE RIPRAP, BEVELED ENDS, REINFORCED CONCRETE SLAB, WINGWALLS, OR END TREATMENT AS DESCRIBED IN THE
PLANS, SC-M-714, SPECIAL PROVISIONS, OR SCDOT STANDARD DRAWINGS.
7. PIPE EMBEDMENT ZONE BACKFILL MUST MEET OR EXCEED THE MINIMUM MATERIAL AND COMPACTION REQUIREMENTS OF
THE ROADWAY EMBANKMENT FOR THE SPECIFIED BURIAL DEPTH WITHOUT DAMAGING THE PIPE.
8. INSTALL STRUCTURAL BACKFILL MATERIAL WITHIN THE PIPE EMBEDMENT ZONE AS SHOWN. FOR MINIMUM COVER
INSTALLATIONS (PAVEMENT ON MINIMUM COVER), THE CONTRACTOR MAY (OPTIONAL) EXTEND THE STRUCTURAL BACKFILL
MATERIAL FROM THE SPRINGLINE OF PIPE TO BOTTOM OF PAVEMENT STRUCTURE.
9. USE BORROW EXCAVATION REQUIREMENTS FOR SOIL ABOVE PIPE EMBEDMENT ZONE.
10. DEPENDING ON THE TYPE OF PAVEMENT (RIGID OR FLEXIBLE), PAVEMENT STRUCTURE MAY INCLUDE SURFACE COURSE, BINDER COURSE, BASE COURSE, SUBBASE, ETC.
THIS DRAWING IS NOT TO SCALE.
TABLE: 714-105A
RIGID PIPE CULVERT STANDARD FOUNDATION
PATTERN DESCRIPTION COMPACTION MATERIAL
ROADWAY EMBANKMENT MATERIAL
(AS PER SCDOT STANDARD SPECIFICATION)
C, D 2, 3
COMPACTED STRUCTURAL BACKFILL BELOW
SPRINGLINE
A, D
COMPACTED STRUCTURAL BACKFILL FOR
HAUNCH ZONE
A, D
UNCOMPACTED STRUCTURAL BACKFILL FOR
MIDDLE BEDDING
B, D
COMPACTED STRUCTURAL BACKFILL FOR
OUTER BEDDING
D, E
EXISTING EMBANKMENT OR IN-SITU SOIL C 2
A. PLACE & COMPACT.
B. PLACE LOOSE/UNCOMPACTED.
C. PLACE USING BORROW SPECIFICATION REQUIREMENTS.
D. USE INSTALLATION METHODS THAT DO NOT DAMAGE PIPE.
E. PLACE LOOSE/UNCOMPACTED, COMPACT AFTER PLACING PIPE IN TRENCH.
1. USE THE SAME MATERIAL FOR ALL LAYERS, ONLY COMPACTION/FUNCTION MAY VARY. SEE SC-M-714
FOR ALLOWABLE MATERIALS.
2. FOLLOW BORROW SPECIFICATION FOR MATERIALS AND COMPACTION, OR IN-SITU SOIL.
3. IF WITHIN PIPE EMBEDMENT ZONE, USE METHODS AND MATERIALS THAT DO NOT DAMAGE PIPE.
EQUALIZATION OF RUBBER GASKET MAY BE
ACCOMPLISHED BY PULLING THE GASKET AWAY
FROM THE PIPE WALL AND RELEASING IT SEVERAL
TIMES AROUND THE PERIMETER OF PIPE JOINT.
DETAIL
RUBBER PROFILE
GASKET EQUALIZATION
(ASTM C443)
SIGNATURE
DATE
NO. 19782
DESIGN STANDARDS OFFICE
955 PARK STREET
ROOM 405
COLUMBIA, SC 29201
SOUTH CAROLINA DEPARTMENT OF TRANSPORTATION
STANDARD DRAWING
3/2020 DSO GENERAL REVISIONS
8/2012 DSO SCDOT LETTER 3/12
3/2010 JBH GENERAL REVISIONS
3/2009 HJC COMPLETE TABLE
7/2008 HJC GENERAL REVISIONS
3/2008 DSO NEW STANDARD
JULY 2020
714-205-01
PIPE CULVERTS
SMOOTH WALL
(RIGID REINFORCED
CONCRETE PIPE (RCP)
DETAILS &
FILL HEIGHT)
714-005-00
714-020-00
714-105-00
714-120-00
714-990-MO
SC-M-714
PCDM-05
QPL 60
QPL 69
AASHTO M31, M170, M198, M295, M302,
M315, M336, T96, T104
ASTM C443, C990
NATIONAL DOCUMENTS
REFERENCES
SCDOT DOCUMENTS
RELATED DRAWINGS & KEYWORDS
THIS DRAWING IS ONLY VALID FOR
CONSTRUCTION WHEN SEALED
AND SIGNED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE
OF SOUTH CAROLINA.
CHECK WWW.SCDOT.ORG FOR LATEST
UPDATE.
EFFECTIVE LETTING DATE
# DATE CHK DESCRIPTION
CUT JOINT SEALANT TO BE SIDE
LAPPED AS SHOWN IN DETAIL 2.
DO NOT OVERLAP, TWIST, OR BEND
JOINT SEALANT.
DETAIL
JOINT SEALANT INSTALLATION
PROVIDE BETWEEN 1"& 3" SIDE
LAP OF JOINT MATERIAL. DO NOT
INSTALL WITH GAPS IN JOINT MATERIAL.
DO NOT TWIST ENDS OF SEALANT AROUND
EACH OTHER OR STACK ONE END ON TOP
OF THE OTHER.
SIDE LAP
DETAIL
PREFORMED FLEXIBLE JOINT MATERIAL
FOR PIPES UP TO AND INCLUDING
48" DIAMETER (ASTM C990)
ASTM C990 PREFORMED FLEXIBLE JOINT SEALANT
(INSTALL ACCORDING TO MANUFACTURER'S DIRECTIONS
AND SCDOT SUPPLEMENTAL TECHNICAL SPECIFICATION
SC-M-714.)
PIPE MAY BE
BELLED IF SUPPLIED
BY MANUFACTURER
SIDE LAP
PLACE ASTM C990 MATERIAL ON THE UPPER HALF OF THE
TONGUE END AND LOWER HALF OF THE GROOVE END. PROVIDE
BETWEEN 1" AND 3" OVERLAP ON EACH SIDE.
DETAIL
PREFORMED FLEXIBLE JOINT MATERIAL
FOR PIPES LARGER THAN 48" DIAMETER
(ASTM C990)
ASTM C443 RUBBER GASKET
(INSTALL ACCORDING TO MANUFACTURERS
DIRECTIONS AND SCDOT SPECIFICATIONS)
DETAIL
RUBBER PROFILE
GASKET (ASTM C443)
PIPE MAY BE
BELLED IF
SUPPLIED BY
MANUFACTURER
1. SEE SHEET 714-005-00, 714-020-00, 714-105-00, & 714-120-00 FOR GENERAL NOTES, AND TRENCH INSTALLATION REQUIREMENTS.
2. USE ONLY REINFORCED CONCRETE PIPE AND JOINT MATERIAL FROM MANUFACTURERS LISTED ON QUALIFIED PRODUCT LIST
69. USE ONLY PIPE CLASSES LISTED IN TABLE 714-205A.
3. FLEXIBLE PIPE CULVERTS ARE PROHIBITED FROM USE ON ALL INTERSTATE AND SCDOT EVACUATION ROUTES. USE ONLY RIGID
PIPE CULVERTS FOR ALL INTERSTATE AND SCDOT EVACUATION ROUTES STATEWIDE.
4. MANUFACTURERS MAY SUBSTITUTE A HIGHER CLASS PIPE THAN THE PIPE CLASS SPECIFIED ON THE PLANS, HOWEVER, INSTALLATION DEPTH SHALL NOT EXCEED THE DEPTH SHOWN ON THE PLANS OR VIOLATE THE FILL HEIGHTS IDENTIFIED IN
TABLE 714-205A. NO ADDITIONAL PAYMENT WILL BE MADE FOR HIGHER CLASS PIPE SUBSTITUTION.
5. SITE CONDITIONS OTHER THAN TYPICAL INSTALLATION MAY REQUIRE SPECIAL DESIGNED PIPE. SPECIAL DESIGN PIPE MAY
ALSO BE REQUIRED FOR INSTALLATIONS OUTSIDE OF SCDOT RIGHT OF WAY - SEE RIGHT OF WAY/UTILITY/MUNICIPAL
AGREEMENT FOR THESE INSTALLATIONS. WHEN REQUIRED, ALL SPECIAL DESIGN PIPES MUST BE DESIGNED IN ACCORDANCE
WITH PCDM-05.
6. THIS FILL HEIGHT TABLE IS FOR USE IN SCDOT ROADWAY APPLICATIONS ONLY AND SHOULD NOT BE USED FOR ANY OTHER
TRANSPORTATION FACILITY.
7. THE REINFORCED CONCRETE PIPE FILL HEIGHT VALUES IN TABLE 714-205A ARE BASED ON CALCULATIONS PROVIDED BY THE
AMERICAN CONCRETE PIPE ASSOCIATION. FILL HEIGHT VALUES IN TABLE 714-205A ARE APPLICABLE FOR THE FOLLOWING LOAD
CASE CRITERIA:
LOAD CASE 1 - STANDARD MAXIMUM COVER INSTALLATION UNDERNEATH ROADWAY. ANY PIPE REQUIRING INSTALLATION
DEPTHS GREATER THAN THIS VALUE WILL REQUIRE A SPECIAL DESIGNED PIPE.
LOAD CASE 2 - STANDARD MINIMUM COVER INSTALLATION UNDERNEATH ROADWAY. THIS VALUE IS SET BY AASHTO LRFD
MINIMUM COVER REQUIREMENTS, REGARDLESS OF PIPE STRUCTURAL CAPACITY. PIPE INSTALLATIONS AT DEPTHS
SHALLOWER THAN THIS VALUE ARE NOT PERMITTED FOR LOAD CASE 2.
LOAD CASE 3 - STANDARD MINIMUM COVER INSTALLATION FOR CONSTRUCTION VEHICLE LOADING. THIS VALUE
INCLUDES AASHTO BRIDGE CONSTRUCTION SPECIFICATION MINIMUM (75 KIP/AXLE) CONSTRUCTION LOAD. WHERE
POSSIBLE, AVOID DRIVING CONSTRUCTION VEHICLES OVER INSTALLED PIPE. EXTEND CONSTRUCTION FILL HEIGHT
BEYOND SIDES OF PIPE BY THE LARGER OF 3 FEET OR ONE PIPE DIAMETER. IN ORDER TO MINIMIZE LATERAL
DISPLACEMENT, PERIODICALLY CHANGE THE LOCATION OF EQUIPMENT CROSSING OVER PIPE.
LOAD CASE 4 - NON-RESIDENTIAL DRIVEWAY (LIGHT COMMERCIAL) SAME STRUCTURAL DESIGN LOADING AS LOAD CASE
2 BUT MINIMUM COVER OVER PIPE IS NOT LIMITED BY AASHTO LRFD (MOST CURRENT EDITION ADOPTED BY THE
DEPARTMENT) SECTION 12 MINIMUM COVER REQUIREMENT. FOR THIS CONDITION SCDOT WILL PERMIT PIPE TO BE
INSTALLED AT A DEPTH THAT IS SHALLOWER THAN THE AASHTO MINIMUM. THE VALUE USED FOR MINIMUM COVER WILL
ONLY BE LIMITED BY THE PIPES STRUCTURAL CAPACITY DETERMINED FROM THE STRUCTURAL DESIGN. USE LOAD CASE
2 FOR HEAVY COMMERCIAL DRIVEWAYS. SEE 714-990-MO FOR RESIDENTIAL DRIVEWAY INSTALLATION FOR
MAINTENANCE APPLICATIONS.
LOAD CASE 6 - STANDARD MAXIMUM COVER INSTALLATION BELOW GROUNDWATER TABLE. MAXIMUM DEPTH PIPE CAN
BE INSTALLED WITH GROUNDWATER TABLE ELEVATION AT 2 X O.D. ABOVE PIPE INVERT.
8. ALL VALUES NOTED AS "---" TYPICALLY INDICATE THAT PIPE SIZE IN NOT AVAILABLE OR THAT A SPECIAL DESIGN PIPE IS
REQUIRED FOR THIS SIZE. CHECK WITH PIPE MANUFACTURE FOR SPECIAL DESIGN PIPE.
PAY ITEMS:
714XXXX (SIZE) SMOOTH WALL PIPE CULVERT..........................................................................................LF
714XXXX (SIZE) RC PIPE CULVERT (RCP) - (CLASS)...................................................................................LF
714XXXX (SIZE) RC PIPE CULVERT (RCP) - (CLASS) AASHTO M198 JOINT (ASTM C990).......................LF
714XXXX (SIZE) RC PIPE CULVERT (RCP) - (CLASS) AASHTO M315 JOINT (ASTM C443).......................LF
20345XX (DIAMETER) PIPE ADDITIONAL FOUNDATION WORK.................................................................LF
TABLE 714-205A: REINFORCED CONCRETE PIPE ALLOWABLE FILL HEIGHTS
PIPE
DIAMETER
HYDRAULIC
AREA
MANNING'S
COEFFICIENT
ESTIMATED
MINIMUM
TRENCH
WIDTH
LOAD CASE 1 LOAD CASE 2 LOAD CASE 3 LOAD CASE 4 LOAD CASE 6
MAXIMUM COVER
(UNDER ROADWAY) [ FT ]
MINIMUM COVER
(UNDER ROADWAY) [ FT ]
MINIMUM COVER
(CONSTRUCTION VEHICLE) [ FT ]
MINIMUM COVER
(NON-RESIDENTIAL DRIVEWAY )
NOT FOR USE UNDER ROADWAY [ FT ]
MAXIMUM COVER
(INVERT AT 2 X OD BELOW
GROUNDWATER TABLE) [ FT ]
PIPE CLASS PIPE CLASS PIPE CLASS PIPE CLASS PIPE CLASS
[ IN ] [ FT2 ] [ n ] [ IN ] II III IV V II III IV V II III IV V II III IV V II III IV V
12 0.78 SEE MFG 42 12.00 17.00 25.00 38.00 2.75 1.25 1.00* 1.00* 5.00 4.00 3.00 1.00 2.75 1.25 0.00 0.00 12.00 17.00 25.00 38.00 15 1.22 SEE MFG 45 13.00 17.00 26.00 39.00 2.75 1.25 1.00* 1.00* 5.00 4.00 3.00 1.00 2.75 1.25 0.00 0.00 12.00 17.00 26.00 39.00 18 1.76 0.012 49 13.00 17.00 26.00 40.00 2.50 1.25 1.00* 1.00* 5.00 4.00 3.00 1.00 2.50 1.25 0.00 0.00 12.00 17.00 26.00 40.00 24 3.14 0.012 56 13.00 17.00 26.00 40.00 2.50 1.00* 1.00* 1.00* 5.00 4.00 3.00 1.00 2.50 0.00 0.00 0.00 12.00 17.00 26.00 40.00 30 4.90 0.012 63 13.00 17.00 26.00 40.00 2.50 1.00* 1.00* 1.00* 5.00 4.00 3.00 1.00 2.50 0.00 0.00 0.00 12.00 17.00 26.00 40.00 36 7.06 0.012 70 12.00 17.00 26.00 40.00 2.50 1.00* 1.00* 1.00* 5.00 3.00 3.00 1.00 2.50 0.00 0.00 0.00 12.00 17.00 26.00 39.00 42 9.62 0.012 77 12.00 17.00 26.00 40.00 2.25 1.00* 1.00* 1.00* 4.00 3.00 2.00 1.00 2.25 0.00 0.00 0.00 12.00 17.00 26.00 39.00 48 12.56 0.012 84 12.00 17.00 26.00 40.00 1.00* 1.00* 1.00* 1.00* 4.00 3.00 2.00 1.00 0.00 0.00 0.00 0.00 12.00 16.00 25.00 39.00 54 15.90 0.012 91 12.00 17.00 26.00 40.00 1.00* 1.00* 1.00* 1.00* 4.00 3.00 2.00 1.00 0.00 0.00 0.00 0.00 11.00 16.00 25.00 39.00 60 19.63 0.012 98 12.00 17.00 26.00 39.00 1.00* 1.00* 1.00* 1.00* 4.00 3.00 1.00 1.00 0.00 0.00 0.00 0.00 11.00 16.00 25.00 39.00 66 23.75 0.012 107 12.00 17.00 26.00 39.00 1.00* 1.00* 1.00* 1.00* 4.00 3.00 1.00 1.00 0.00 0.00 0.00 0.00 11.00 16.00 25.00 38.00 72 28.27 0.012 116 12.00 17.00 25.00 39.00 1.00* 1.00* 1.00* 1.00* 4.00 3.00 1.00 1.00 0.00 0.00 0.00 0.00 11.00 16.00 24.00 38.00 78 33.18 0.012 126 12.00 17.00 25.00 --- 1.00* 1.00* 1.00* --- 3.00 3.00 1.00 --- 0.00 0.00 0.00 --- 11.00 15.00 24.00 --- 84 38.48 0.012 135 12.00 16.00 25.00 --- 1.00* 1.00* 1.00* --- 3.00 3.00 1.00 --- 0.00 0.00 0.00 --- 10.00 15.00 24.00 --- 90 44.17 0.012 144 12.00 16.00 --- --- 1.00* 1.00* --- --- 3.00 3.00 --- --- 0.00 0.00 --- --- 10.00 15.00 --- --- 96 56.74 0.012 154 11.00 16.00 --- --- 1.00* 1.00* --- --- 3.00 3.00 --- --- 0.00 0.00 --- --- 10.00 15.00 --- ---
108 63.61 0.012 172 11.00 16.00 --- --- 1.00* 1.00* --- --- 3.00 3.00 --- --- 0.00 0.00 --- --- 9.00 15.00 --- --- 120 78.54 0.012 191 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
* IF PIPE IS INSTALLED UNDER RIGID PAVEMENT VALUE MAY BE REDUCED TO 0.75-FT
THIS DRAWING IS NOT TO SCALE.
NATIONAL DOCUMENTS
REFERENCES
SCDOT DOCUMENTS
RELATED DRAWINGS & KEYWORDS
THIS DRAWING IS ONLY VALID FOR
CONSTRUCTION WHEN SEALED
AND SIGNED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE
OF SOUTH CAROLINA.
CHECK WWW.SCDOT.ORG FOR LATEST
UPDATE.
EFFECTIVE LETTING DATE
# DATE CHK DESCRIPTION
JANUARY 2021
714-205-02
PIPE CULVERTS
SMOOTH WALL
(RIGID REINFORCED
CONCRETE PIPE (RCP))
FILL HEIGHT CHART
DESIGN STANDARDS OFFICE
955 PARK STREET
ROOM 405
COLUMBIA, SC 29201
SOUTH CAROLINA DEPARTMENT OF TRANSPORTATION
STANDARD DRAWING
THIS ITEM HAS BEEN
REMOVED
EFFECTIVE JANUARY
2021 LETTING.
SEE 714-205-01
| 714-000-00.pdf |
| 714-005-00.pdf |
| 714-105-00.pdf |
| 714-205-01.pdf |
| 714-205-02.pdf |
| 2020-11-09T11:09:34-0500 | |
| George Robert Bedenbaugh, Jr. |
| Date2_af_date: 11/09/20 | |
| 2020-11-09T11:45:48-0500 | |
| George Robert Bedenbaugh, Jr. |
| Date6_af_date: 11/09/20 | |
| 2020-11-09T11:46:34-0500 | |
| George Robert Bedenbaugh, Jr. |
Date4_af_date: 11/09/20
File details come from the government source that posted it. Updated .