SODA CREEK STATION, CA

USDA FOREST SERVICE

PACIFIC SOUTHWEST REGION 5

CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE:

JOHN F. MCLAUGHLIN III

REGIONAL MECHANICAL ENGINEER

REGIONAL OFFICE, REGION 5

1323 CLUB DRIVE, VALLEJO, CA 94595

PHONE: 707.562.8868 CEL: 731.589.1425

EMAIL: johnfmclaughlin@fs.fed.us

ARCHITECT AND PRIME:

MARCY WONG DONN LOGAN ARCHITECTS

800 BANCROFT WAY, SUITE 200

BERKELEY, CA 94710

ATTN: KENT ROYLE, ASSOCIATE PRINCIPAL

PHONE: 510.843.0916

EMAIL: kent@wonglogan.com

ELECTRICAL ENGINEER:

GHD INC.

2235 MERCURY WAY, SUITE 150

SANTA ROSA, CA 95407

ATTN: RICK GUGGIANA, PROJECT MANAGER

PHONE: 707.523.1010

EMAIL: rick.guggiana@ghd.com

PROJECT SCOPE:

IMPROVEMENTS TO AN EXISTING STAND-ALONE ELECTRICAL GENERATION

SYSTEM TO ACCOMMODATE THE NEW GOVERNMENT-FURNISHED 30 KW

GENERATOR, AN EXISTING 17KW STANDBY GENERATOR, AND LOADS

FROM EXISTING BUILDINGS, INCLUDING WIRING, NEW MANUAL TRANSFER

SWITCH, DISTRIBUTION PANEL, PROPANE PIPING, AND CONCRETE PAD.

OCTOBER 2014

PROJECT LOCATION

SODA CREEK STATION, CA

LATITUDE: 39.4251605

LONGITUDE: -122.977779

COUNTY: LAKE

AREA: LAKE PILLSBURY

NOT TO SCALE

N

SHEET OF

SCALE

DRAWING

CHECKED BY

DATE

CHECKED BY

A/E

DRAWN BY

DESIGNED BY

PROJECT NUMBER

N A

M E:

PR

O

JE

C

T

FO

R

ES

T:

D R

A W

IN

G

N A

M E:

PACIFIC

REGION

SOUTHWEST

R5

NO. DATE REVISIONS

SERVICE

U S D A

FOREST

SO

DA

C

RE

EK

G

EN

ER

AT

OR

W

IR

IN

G

PR

OJ

EC

T

JJVL

10/06/2014

RG

RG

RG

(MWDL #1420)

AG-91S8-D-11-0080

LOCATION MAP

2235 Mercury Way, Suite 150

Santa Rosa, California 95407 USA

T 1 707 523 1010 F 1 707 527 8679

W www.ghd.com

GHD Inc.

1 5

G0.1

NOT TO SCALE

LAKE

PILLSBURRY

NOT TO SCALE

N

PROJECT

LOCATION

SHEET INDEX

SHEET OF

DRAWING

NUMBER

DESCRIPTION

SUBMITTAL

PRE-FINAL

GENERAL

1 5

G 0.1

COVER SHEET, VICINITY MAP, AND LOCATION MAP

X

ELECTRICAL

2 5

E 0.1

GENERAL NOTES, LEGEND AND ABBREVIATIONS

X

3 5

E 1.0 ELECTRICAL SITE LAYOUT PLAN X

4 5

E 5.0 MISCELLANEOUS DETAILS X

5 5

E 6.0 SINGLE LINE DIAGRAM AND SCHEDULE X

AREA MAP

CALIFORNIA

S

O

D

A

C

R

E

E

K

S

I M

M

O

N

S

E

L

K

M

O

U

N

T

A

I

E

L

K

M

O

U

N

T

A

I

S I M

M O

S

I M

M

O

ANNOTATION

SWITCHING

LIGHTING

CONDUIT

MAIN SWITCHBOARD

DISTRIBUTION PANEL BOARD

COMBINATION METER/MAIN SERVICE PANEL

BRANCH CIRCUIT PANEL BOARD, SURFACE OR FLUSH

MOUNTED

LIGHTING CONTROL PANEL

SIGNAL TERMINAL CABINET OR CONTROL PANEL

SURFACE OR FLUSH MOUNTED

SIGNAL TERMINAL BACKBOARD

CONCRETE UNDERGROUND HAND HOLE

(NUMBER DENOTES CHRISTY SIZE)

TRANSFORMER

EQUIPMENT

GENERAL ELECTRICAL NOTESELECTRICAL SYMBOLS LEGEND

KEYNOTE

DEMOLITION NOTE

RACEWAY, FEEDER OR CIRCUIT DESIGNATION (SEE SCHEDULE)

LIGHTING FIXTURE TYPE DESIGNATION

(SEE SCHEDULE)

DETAIL INDICATOR SECTION INDICATOR

MECHANICAL EQUIPMENT DESIGNATION

(SEE SCHEDULE)

DUPLEX RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,

MOUNTING HEIGHT: +18" AFF UON

DUPLEX RECEPTACLE - SPLIT WIRED, SWITCHED

DUPLEX RECEPTACLE - EMERGENCY POWER

DUPLEX RECEPTACLE - CEILING MOUNTED

FLOOR RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,

FLUSH TYPE UON

DOUBLE DUPLEX RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,

MOUNTING HEIGHT: +18" AFF UON

SINGLE RECEPTACLE, 20A 125V 2P 3W, GROUNDING TYPE,

MOUNTING HEIGHT: +18" AFF UON

SPECIAL PURPOSE RECEPTACLE AS DESIGNATED

SEE 'SPECIAL SYMBOLS' ON EACH SHEET

DUAL SERVICE RECESSED FLOOR BOX WITH DUPLEX AND DATA

RECEPTACLES

JUNCTION BOX, CODE SIZED UON

FLOOR JUNCTION BOX

DISCONNECT SWITCH - FUSED WHERE APPLICABLE

MOTOR STARTER, COMBINATION WITH DISCONNECT SWITCH

MOTOR STARTER OR CONTROLLER

MOTOR CONNECTION

CEILING EXHAUST FAN

WATER HEATER

POWER POLE: P=POWER, T=TELEPHONE,

D=DATA, C=COMBINATION

TEST PORT

GROUND ROD

GUY WIRE AND ANCHOR

THERMOSTAT (SEE MECHANICAL DRAWINGS)

COORDINATE MOUNTING HEIGHT

BYPASS TIMER OR TIME SWITCH

PUSHBUTTON

LIGHTING CONTACTOR

CONDUIT INSTALLED ABOVE GRADE

CONDUIT INSTALLED UNDERGROUND OR UNDER SLAB

CONDUIT STUB-OUT WITH CAP

FLEXIBLE CONDUIT WHIP TO LIGHT FIXTURE OR EQUIPMENT

FLUORESCENT FIXTURE, RECESSED

RECESSED DOWN LIGHT FIXTURE

RECESSED DIRECTIONAL FIXTURE (ARROW INDICATES AIMING)

FLUORESCENT FIXTURE, SURFACE MOUNTED

SURFACE, PENDANT OR OTHER FIXTURE

FLUORESCENT FIXTURE, WALL MOUNTED

WALL-MOUNTED HID, INCANDESCENT, OR COMPACT FLUORESCENT

FIXTURE

FLUORESCENT FIXTURE, PENDANT OR CABLE HUNG

LIGHT TRACK AND TRACK-MOUNTED FIXTURES

BATH FAN WITH INTEGRAL LIGHT

EXIT SIGN, SINGLE FACE WITH DIRECTIONAL ARROWS AS INDICATED

EXIT SIGN, DOUBLE FACE WITH DIRECTIONAL ARROWS AS INDICATED

EXIT SIGN, LOW LEVEL

COMBINATION EXIT/EMERGENCY LIGHT FIXTURE

MOUNTING HEIGHT: +8'-0" AFF, UON

EMERGENCY FIXTURE

MOUNTING HEIGHT: +8'-0" AFF, UON

DENOTES FIXTURE CONNECTED TO EMERGENCY CIRCUIT

ADJUSTABLE SPOT OR FLOOD (ARROW INDICATES AIMING)

OUTDOOR SITE LIGHT, POLE MOUNTED LUMINAIRE ARROW

INDICATES AIMING DIRECTION, IF APPLICABLE

BOLLARD OR POST-TOP FIXTURE

LIGHT SWITCH, SPST - MOUNTING HEIGHT: +44" AFF, UON

LIGHT SWITCH, DPST - MOUNTING HEIGHT: +44" AFF, UON

LIGHT SWITCH, 3-WAY - MOUNTING HEIGHT: +44" AFF, UON

LOW VOLTAGE SWITCH, MOMENTARY CONTACT, 3-POS.,

CENTER-OFF, MOUNTING HEIGHT: +44" AFF, UON

TIMER SWITCH - MOUNTING HEIGHT: +44" AFF, UON

CIRCUIT AND SWITCH DESIGNATION FOR LIGHTING FIXTURE

CIRCUIT AND RELAY DESIGNATION FOR LIGHTING FIXTURES

(SEE CORRESPONDING LIGHTING CONTROL PANEL RELAY

SCHEDULE)

DIMMER SWITCH - MOUNTING HEIGHT: +44" AFF, UON

OCCUPANCY SENSOR POWER PACK, 1-CIRCUIT, MOUNTED ABOVE

CEILING

OCCUPANCY SENSOR POWER PACK, 2-CIRCUIT

MOUNTED ABOVE CEILING

OCCUPANCY SENSOR, CEILING MOUNTED, LINE VOLTAGE

OCCUPANCY SENSOR, CEILING MOUNTED, LOW VOLTAGE

OCCUPANCY SENSOR, WALL MOUNTED, LINE VOLTAGE, 1-CIRCUIT

MOUNTING HEIGHT: +44" AFF, UON

OCCUPANCY SENSOR, WALL MOUNTED, LINE VOLTAGE, 2-CIRCUIT

MOUNTING HEIGHT: +44" AFF, UON

PHOTO CONTROL SWITCH - MOUNT ON BUILDING EXTERIOR

TIME CLOCK FOR LIGHTING CONTROL

POWER

CONDUIT HOME RUN TO DESIGNATED PANEL, TERMINAL, OR

CONTROL CABINET

EXAMPLES:

NOTE FOR CONDUIT: THE TIC MARKS INDICATE THE QUANTITY OF

#12 AWG WIRES OR, IF INDICATED, THE QUANTITY OF OTHER SIZE

WIRE OR CABLES.

SEE THE SINGLE LINE DIAGRAM FOR FEEDER SIZES.

EXAMPLES: = (3) #12 = (2) #10

= (1) TYPE F1 CABLE. SEE CABLE SCHEDULE.

F1

OBJECT LINES

NEW OBJECTS

(HEAVY CONTINUOUS LINES, UNDERGROUND CONDUIT

HEAVY DASHED LINES)

EXISTING OBJECTS TO REMAIN. MAY INCLUDE NEW CIRCUITING ETC.

(FINE CONTINUOUS LINES, UNDERGROUND CONDUIT

FINE DASHED LINES)

EXISTING OBJECTS TO BE DEMOLISHED

(EXTRA FINE DASHED LINES, SCREENED)

E-501

A

E-301

WH

A

ABBREVIATIONS

(D) DEMOLISH

(E) EXISTING

(F) FUTURE

(N) NEW

A AMPERES

AC ALTERNATING CURRENT

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPS INTERRUPTING CAPACITY

ANN ANNUNCIATOR

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BAT BATTERY

BFG BELOW FINISH GRADE

CATV CABLE TELEVISION

C CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CO CONDUIT ONLY

COMPT COMPARTMENT

CPT CONTROL POWER TRANSFORMER

CT CURRENT TRANSFORMER

CU COPPER

DC DIRECT CURRENT

EF EXHAUST FAN

EGU ENGINE GENERATOR UNIT

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENT ELECTRICAL NON-METALLIC TUBING

EP EXPLOSION PROOF

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FC FOOT CANDLE

FO FIBER OPTIC

FU FUSE

GND GROUND

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFR GROUND FAULT RELAY

HID HIGH INTENSITY DISCHARGE

HOA "HAND-OFF-AUTO" SWITCH

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HVAC HEATING, VENTILATION &

AIR-CONDITIONING

IG ISOLATED GROUND

JB JUNCTION BOX

KAIC KILO-AMPS INTERRUPTING CAPACITY

KV KILOVOLT

KVA KILOVOLT-AMP

KW KILOWATT

KWH KILOWATT-HOUR

LPS LOW PRESSURE SODIUM

LV LOW VOLTAGE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MFR MANUFACTURER

MH METAL HALIDE

MLO MAIN LUGS ONLY

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR

INSTALLED

PA PUBLIC ADDRESS

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

PB PULL BOX, ELECTRICAL

RECPT RECEPTACLE, OUTLET

RGS RIGID GALVANIZED STEEL (CONDUIT)

RVSS REDUCED VOLTAGE SOFT

START

RTU REMOTE TERMINAL UNIT

TV TELEVISION MONITOR (SET)

TVSS TRANS. VOLT. SURGE SUPPRESSOR

UF UNDER FLOOR

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT-AMP

VFD VARIABLE FREQUENCY DRIVE

WP WEATHERPROOF

WPI WEATHERPROOF IN USE

XFMR TRANSFORMER

SHEET OF

SCALE

DRAWING

CHECKED BY

DATE

CHECKED BY

A/E

DRAWN BY

DESIGNED BY

PROJECT NUMBER

N A

M E:

PR

O

JE

C

T

FO

R

ES

T:

D R

A W

IN

G

N A

M E:

PACIFIC

REGION

SOUTHWEST

R5

NO. DATE REVISIONS

SERVICE

U S D A

FOREST

SO

DA

C

RE

EK

G

EN

ER

AT

OR

W

IR

IN

G

PR

OJ

EC

T

JJVL

10/06/2014

RG

RG

RG

(MWDL #1420)

AG-91S8-D-11-0080

CCTV CAMERA, CEILING MOUNT

INTERCOM CALL IN SWITCH - MOUNTING HEIGHT: +44" AFF, UON

TELEPHONE OUTLET FOR WALL MOUNTED TELEPHONE

MOUNTING HEIGHT: +44" AFF UON

DATA OUTLET - MOUNTING HEIGHT: +18" AFF UON

TELEPHONE/DATA OUTLET, FLUSH TYPE UON

MOUNTING HEIGHT: +18" AFF UON

SURFACE RACEWAY WITH POWER AND TELEPHONE/DATA

RECEPTACLES AS INDICATED

CATV OUTLET - MOUNTING HEIGHT: +96" AFF UON

AUDIO/VIDEO OUTLET - MOUNTING HEIGHT: +18" AFF UON

CLOCK WITH BUZZER - MOUNTING HEIGHT: SEE PLANS

BELL, STANDARD 6" - MOUNTING HEIGHT: SEE PLANS PA SYSTEM

SPEAKER - WALL MOUNTED

PA SYSTEM SPEAKER - CEILING MOUNTED

PA SYSTEM HORN - MOUNTING HEIGHT: SEE PLANS

COMMUNICATION

2235 Mercury Way, Suite 150

Santa Rosa, California 95407 USA

T 1 707 523 1010 F 1 707 527 8679

W www.ghd.com

GHD Inc.

2 5

E0.1

NOT TO SCALE

1. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SIZE AND LOCATION OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER

POSSIBLE, CONTRACTOR SHALL MAKE USE OF MANUFACTURER'S OR OWNER'S DATA AVAILABLE AND VERIFY DATA IN

THE FIELD FOR PROVIDING AND INSTALLING CORRECT CABLE LENGTHS.

2. ALL WIRING SHALL CONFORM TO THE LATEST EDITION OF NATIONAL ELECTRICAL CODE OR APPLICABLE STATE

BUILDING CODE.

3. ALL EQUIPMENT AND MATERIALS SHALL BE UL LISTED WHERE LISTING IS AVAILABLE FOR THAT TYPE OF EQUIPMENT OR, SHALL CONFORM TO ANSI OR NEMA STANDARDS.

4. WORKMANSHIP SHALL CONFORM TO CONSTRUCTION PRACTICES RECOMMENDED BY THE AMERICAN ELECTRICIANS

HANDBOOK BY CROFT (LATEST EDITION) AND SHALL BE SUBJECT OF THE APPROVAL OF THE AGENCY WHO HAS JURISDICTION, AND THE ENGINEER.

5. METALLIC ENCLOSURES, RACEWAYS AND ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH

REQUIREMENTS OF NEC ARTICLE 250. PROVIDE GROUND WIRE IN EVERY RACEWAY. SIZE IN ACCORDANCE WITH NEC TABLE

250-122.

6. COORDINATE WITH ENGINEER FOR EQUIPMENT REQUIREMENTS, AND PROVIDE ALL WIRING AND PROTECTION EQUIPMENT

REQUIRED.

7. CONDUIT SHALL BE PVC (BELOW GRADE), OR GALVANIZED RIGID STEEL (EXPOSED INSTALLATION) UNLESS NOTED

OTHERWISE. PROVIDE PROPER FITTINGS BETWEEN DISSIMILAR MATERIALS. FLEXIBLE CONDUIT SHALL BE JACKETED TYPE

AND IN ACCORDANCE WITH NEC ARTICLE 350.

8. WIRING SHALL BE NEC TYPE RHW OR USE-2. CONDUCTORS SHALL BE STRANDED COPPER.

9. TEST: TESTING RESULTS SHALL SUBMITTED FOR APPROVAL TO ENGINEER.

A. OPERATION TEST

B. INSULATION RESISTANCE

C. GROUND RESISTANCE

10. CONTRACTOR SHALL SUBMIT ELECTRICAL PRODUCT CATALOG DATA, AND RECEIVE APPROVAL FROM ENGINEER BEFORE

ORDERING MATERIALS.

SHEET OF

SCALE

DRAWING

CHECKED BY

DATE

CHECKED BY

A/E

DRAWN BY

DESIGNED BY

PROJECT NUMBER

N A

M E:

PR

O

JE

C

T

FO

R

ES

T:

D R

A W

IN

G

N A

M E:

PACIFIC

REGION

SOUTHWEST

R5

NO. DATE REVISIONS

SERVICE

U S D A

FOREST

SO

DA

C

RE

EK

G

EN

ER

AT

OR

W

IR

IN

G

PR

OJ

EC

T

JJVL

10/06/2014

RG

RG

RG

(MWDL #1420)

AG-91S8-D-11-0080

2235 Mercury Way, Suite 150

Santa Rosa, California 95407 USA

T 1 707 523 1010 F 1 707 527 8679

W www.ghd.com

GHD Inc.

3 5

E1.0

AS SHOWN

E5.0

TRANSFER SWITCH

AND PANELBOARD,

SEE ENLARGED PLAN

SHEET GENERAL NOTES

1. PLAN BASED ON BEST AVAILABLE RECORD INFORMATION. VERIFY ALL LOCATIONS

AND SUBSURFACE CONDITIONS PRIOR TO START OF WORK.

2. REPAIR, PATCH AND TOUCH UP MARRED SURFACES TO MATCH ADJACENT FINISHES.

3. INSTALL THE FOLLOWING GOVERNMENT FURNISHED MATERIALS:

• GENERATOR - 1 EACH

• TRANSFER SWITCH - 1 EACH

• DISTRIBUTION PANEL - 1 EACH

• CONCRETE PULLBOX WITH LID - 1 EACH

• 2" ELECTRICAL CONDUIT - 160 LINEAR FEET

• 2" GALVANIZED RIGID STEEL CONDUIT - 50 LINEAR FEET

• #3/0 AWG ELECTRICAL WIRE - 580 LINEAR FEET

4. UNDERGROUND CONDUIT SHALL BE PVC, SCHEDULE 40, PER NEMA TC-2.

5. ABOVEGROUND CONDUIT SHALL BE GALVANIZED RIGID STEEL CONDUIT, PER UL 6

AND ANSI C80.1.

6. WIRE SHALL BE INSULATED COPPER, TYPE RHH/RHW.

KEYNOTES

1. PROVIDE TRANSFER SWITCH AND PANELBOARD MOUNTED ON RGS POSTS AND

UNISTRUT SUPPORTS.

2. PROVIDE NEW CONDUIT RACEWAY BETWEEN GENERATOR, TRANSFER SWITCH,

BATTERY CHARGER AND BLOCK HEATER.

3. PROVIDE NEW POLYETHYLENE PROPANE PIPE BETWEEN GENERATOR AND (E)

PROPANE PIPE.

4. BELOW GRADE LIQUID PROPANE PIPE TO BE POLYETHYLENE PIPE RATED FOR THIS

USE AND 150 PSI PRESSURE.

5. ABOVE GRADE LIQUID PROPANE PIPE TO BE BLACK IRON STEEL, SCHEDULE 80,

PROVIDE TWO COATS OF RUST INHIBITING PAINT.

6. INSTALL PIPE SYSTEM PER REQUIREMENTS OF PROPANE SUPPLIER.

7. PROVIDE ANODELESS SERVICE RISER, ELSTER OR EQUAL WITH TRACE WIRE CLIP.

8. CONNECT 1" GAS SERVICE TO GENERATOR PER MANUFACTURER

RECOMMENDATION: INSTALL STAINLESS STEEL FLEXIBLE CONNECTION WITH

POLYMER COATING. MAXIMUM 48 INCH LENGTH.

9. PROVIDE BALL VALVE SHUT OFF RATED FOR PROPANE SERVICE.

10. LOCATION OF CONDUITS FOR GENERATOR CIRCUIT BREAKER, BATTERY CHARGER,

BLOCK HEATER, AND FUEL INLET FLEXIBLE FUEL LINE AS PER MANUFACTURER'S

RECOMMENDATION.

11. GOVERNMENT FURNISHED PULL BOX.

12. BRING GAS SUPPLY RISER UP THROUGH GENERATOR PAD IN SLEEVE. FILL ANNULAR

SPACE BETWEEN PIPE AND SLEEVE WITH SAND. ROUTE GAS PIPE UP AND IN TO

CONNECTION IN GENERATOR ENCLOSURE. LOCATE PIPE IN PAD USING

MANUFACTURER RECOMMENDED DIMENSION.

E

PULLBOX,

SEE DETAIL

E5.0

2"C, 3#3/0, 1#6

SEE DETAIL

E5.0

1" PROPANE PIPE,

SEE DETAIL

E5.0

GENERATOR

CONCRETE PAD

(BY OTHERS)

0 40'20'

1"=20'

CONNECT PROPANE PIPE TO (E)

PROPANE PIPE AND FITTINGS

ENLARGED PLAN

(E) GENERATOR

BUILDING WALL

PULBOX

TRANSFER SWITCH

AND PANELBOARD

MOUNTING SUPPORT

ELECTRICAL

CONDUIT FROM

GENERATOR

(E) GROUND ROD,

SEE DETAIL

E5.0

PROPANE

LOCATION

1"C, 4#12, 2#12

SEE DETAIL

E5.0

ELECTRICAL CONDUIT FOR

GENERATOR BATTERY

CHARGER AND BLOCK HEATER

CONDUIT

LOCATIONS

9 12

DRAWING

CHECKED BY

DATE

CHECKED BY

A/E

DRAWN BY

DESIGNED BY

PROJECT NUMBER

N A

M E:

PR

O

JE

C

T

FO

R

ES

T:

D R

A W

IN

G

N A

M E:

PACIFIC

REGION

SOUTHWEST

R5

NO. DATE REVISIONS

SERVICE

U S D A

FOREST

SO

DA

C

RE

EK

G

EN

ER

AT

OR

W

IR

IN

G

PR

OJ

EC

T

JJVL

10/06/2014

RG

RG

RG

(MWDL #1420)

AG-91S8-D-11-0080

2235 Mercury Way, Suite 150

Santa Rosa, California 95407 USA

T 1 707 523 1010 F 1 707 527 8679

W www.ghd.com

GHD Inc.

4 5

E5.0

NOT TO SCALE

NOTE:

ALL ENCLOSURES & MTG MTRLS SHALL BE STAINLESS STEEL.

4"

(TYP)

THREADED CAP (TYP)

ELEVATION

PLAN

CONCRETE PIER, TYP

1/4" DIA U-BOLT HDG,

TYP

P1001SL HDG, TYP

3'- 10"

AS REQUIRED

2" RGS, TYP.

P1001SL HDG, TYP

PANEL

"SC"

CONCRETE PIER, TYP

" CHAMFER, TYP

2"C

2"C W/ MYERS

HUB OR EQUAL

CONDUITS

AS REQUIRED

10"

30"

17-1/4"

22-1/4"

35-1/4"

DESIGN LOAD: TRAFFIC

12"

12"

22-1/4"

35-1/4"

SIDE KNOCKOUTS. NON-SETTLING SHOULDERS

MAINTAIN GRADE AND FACILITATE BACKFILLING.

PULL AND JUNCTION BOX WITH END AND

A HIGH DENSITY REINFORCED CONCRETE

ULTRAVIOLET INHIBITOR

FACE ANCHORED IN CONCRETE

ETCHED POLYETHYLENE FACE

N36-61J

3"

BEAD WELDED

MARKING: ELECTRICAL

STEEL COVERS FIT

OVER ENTIRE BOX

NOTE:

MOUNTING SUPPORT (OFCI)

(E) GROUND ROD

TYP. PULLBOX (OFCI)

9'-6" L X 4'-6" W

#6 @ 12" EA. WAY TOP

& BOTTOM

6" BASE COURSE

COMPACTED TO 95%

MIN. DENSITY

GENERATOR CONCRETE PAD (BY OTHERS)

NOTE:

MAINTAIN A MINIMUM VERTICAL SEPARATION OF 12" WHEN CROSSING SANITARY SEWER

LINES. ROUTE CONDUIT EITHER ABOVE OR BELOW OTHER UTILITIES AS NECESSARY TO

ACHIEVE THIS SEPARATION WHILE MAINTAINING THE MINIMUM BACKFILL COVERAGE.

ROCK FREE

NATIVE BACKFILL,

95% COMPACTION

#4 MINIMUM SALT

FREE SAND ALL

AROUND

SUB-BASE AND SURFACE TO MATCH

SURROUNDING CONDITIONS

E

FINISH GRADE

M

I N

C

O V

E R

6" NOMINAL

ELECTRICAL TRENCH

GAS TRENCH

WARNING TAPE: BRIGHTLY RED

COLORED PLASTIC TAPE, 8 MIL

APPROXIMATELY 12" BELOW

FINISHED GRADE

ROCK FREE

NATIVE BACKFILL,

95% COMPACTION

#4 MINIMUM SALT

FREE SAND ALL

AROUND

SUB-BASE AND SURFACE TO MATCH

SURROUNDING CONDITIONS

G

FINISH GRADE

M

I N

C

O V

E R

6" NOMINAL

PULLBOX LOCATION

PROPANE PIPE CONNECTION LOCATION

REMOVE CONDUITS, LB FITTINGS AND PULL

BOX. REPAIR, PATCH AND TOUCH UP MARRED

SURFACES TO MATCH ADJACENT FINISHES

REMOVE (E) PIPES AND FITTINGS

INSIDE THE GENERATOR

BUILDING AND UNDERGROUND

CONNECT (N) PROPANE PIPE AND

FITTINGS TO (E) PROPANE FITTING

INTERCEPT (E) CONDUITS

WITH PULLBOX

PULLBOX (OFCI),

SEE DETAIL

MOUNTING SUPPORT (OFCI),

SEE DETAIL

E5.0

CONDUIT STUB-UP

WRAP STEEL CONDUIT WITH

INSULATING TAPE

RIGID STEEL CONDUIT

FINISH GRADE

AS NECESSARY TO

ACCOMODATE TRENCH DEPTH

COUPLING

PVC CONDUIT

COUPLING

E

6" WIDE X 4 MIL THICK BRIGHT COLOR

CONTINUOUSLY PRINTED WARNING

TAPE MANUFACTURED FOR DIRECT

BURIAL 12" BELOW FINISH GRADE

#12 TRACER WIRE

GROUND CONNECTION OF (N)

TRANSFER SWITCH AND PANEL

TO (E) GROUND ROD

(E) GROUND ROD LOCATION,

SEE DETAIL

E5.0

E5.0

DRAWING

CHECKED BY

DATE

CHECKED BY

A/E

DRAWN BY

DESIGNED BY

PROJECT NUMBER

N A

M E:

PR

O

JE

C

T

FO

R

ES

T:

D R

A W

IN

G

N A

M E:

PACIFIC

REGION

SOUTHWEST

R5

NO. DATE REVISIONS

SERVICE

U S D A

FOREST

SO

DA

C

RE

EK

G

EN

ER

AT

OR

W

IR

IN

G

PR

OJ

EC

T

JJVL

10/06/2014

RG

RG

RG

(MWDL #1420)

AG-91S8-D-11-0080

2235 Mercury Way, Suite 150

Santa Rosa, California 95407 USA

T 1 707 523 1010 F 1 707 527 8679

W www.ghd.com

GHD Inc.

5 5

E6.0

NOT TO SCALE

SCHEDULE

150A

200A DOUBLE THROW NEMA KS-1,

TYPE TC NEMA 3R ENCLOSURE (OFCI)

PRODUCT:

GE TC10324R

GENERATOR 30KW, 240V,

1-PHASE, 4-WIRE,

OWNER FURNISHED

CONTRACTOR INSTALLED (OFCI)

DISTRIBUTION PANEL 'SC' (OFCI)

PRODUCTS:

GE TYPE AL,

EATON POW-R-LINE 1a, SQUARE D TYPE NQ

PULLBOX 24"x 36" x 12" DEEP

W/ 12" EXTENSION (OFCI)

PRODUCTS:

BROOKS, CHRISTY, JENSEN, OLDCASTLE

(E) BACKUP GENERATOR

2"C, 3#3/0, 1#6G

(OFCI)

PANEL SCHEDULE

PANEL NAME:

SC

VOLTAGE: 240 NEMA RATING: 3R NOTES: PROVIDE 200A SUBFEED BREAKER FOR BARRACKS

MAINS RATING: 200A PHASE: 1 AIC RATING: 10K MOUNTING: SURFACE

BUS RATING: 225A WIRE: 3 DEMAND FACTOR: LOCATION: OUTDOOR ON MOUNTING SUPPORT

CKT NO. USE DESCRIPTION

BKR

SIZE

BKR

OPTS

BKR KVA PHASE BKR KVA

BKR

OPTS

BKR

SIZE

DESCRIPTION USE CKT NO.

1 P GAS HOUSE 100/2 1.00 A 1.50 100/2 PUMP HOUSE P 2

3 1.00 B 1.50 4

5 P OFFICE 70/2 1.00 A 0.10 20/1 BATTERY CHARGER O 6

7 1.00 B 1.00 20/1 BLOCK HEATER O 8

9 P WAREHOUSE 70/2 1.00 A 0.10 20/1 LIGHTS L 10

11 1.00 B SPACE 12

13 SPACE A SPACE 14

15 SPACE B SPACE 16

17 SPACE A 4.00 200/2

BARRACKS (SEE NOTE)

P 18

19 SPACE B 4.00 20

LOADS USE LEGEND LOAD TYPE

PHASE A: 8.7

(KVA)

H HVAC

PHASE B: 9.5

(KVA)

L LIGHTING

M MOTOR

TOTAL: 18.2

(CONNECTED KVA)

O OTHER

75.8

(CONNECTED AMPS)

R RECEPTACLE

P PANEL

SINGLE LINE DIAGRAM

PROVIDE #2 AWG 4/C TYPE SOOW CORD

(40 FOOT LENGTH), TO REPLACE (E) FLEXIBLE

CABLE AND CONNECT TO (N) TRANSFER SWITCH

REMOVE (E) GENERATOR,

SEE PHOTO #3

REMOVE (E) DISTRIBUTION

PANEL, GUTTER, CONDUITS

AND CABLES TO BE REMOVED,

SEE PHOTOS #1 AND #2

PHOTO #1 PHOTO #2

PHOTO #3

REMOVE (E) GENERATOR

REMOVE (E) DISTRIBUTION PANEL,

GUTTER, CONDUITS AND CABLES,

SEE PHOTOS #1 AND #2

REMOVE (E) FLEXIBLE CABLE

KILLARK VP1033 PLUG

KILLARK VPR1033 CONNECTOR