SODA CREEK STATION, CA
USDA FOREST SERVICE
PACIFIC SOUTHWEST REGION 5
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE:
JOHN F. MCLAUGHLIN III
REGIONAL MECHANICAL ENGINEER
REGIONAL OFFICE, REGION 5
1323 CLUB DRIVE, VALLEJO, CA 94595
PHONE: 707.562.8868 CEL: 731.589.1425
EMAIL: johnfmclaughlin@fs.fed.us
ARCHITECT AND PRIME:
MARCY WONG DONN LOGAN ARCHITECTS
800 BANCROFT WAY, SUITE 200
BERKELEY, CA 94710
ATTN: KENT ROYLE, ASSOCIATE PRINCIPAL
PHONE: 510.843.0916
EMAIL: kent@wonglogan.com
ELECTRICAL ENGINEER:
GHD INC.
2235 MERCURY WAY, SUITE 150
SANTA ROSA, CA 95407
ATTN: RICK GUGGIANA, PROJECT MANAGER
PHONE: 707.523.1010
EMAIL: rick.guggiana@ghd.com
PROJECT SCOPE:
IMPROVEMENTS TO AN EXISTING STAND-ALONE ELECTRICAL GENERATION
SYSTEM TO ACCOMMODATE THE NEW GOVERNMENT-FURNISHED 30 KW
GENERATOR, AN EXISTING 17KW STANDBY GENERATOR, AND LOADS
FROM EXISTING BUILDINGS, INCLUDING WIRING, NEW MANUAL TRANSFER
SWITCH, DISTRIBUTION PANEL, PROPANE PIPING, AND CONCRETE PAD.
OCTOBER 2014
PROJECT LOCATION
SODA CREEK STATION, CA
LATITUDE: 39.4251605
LONGITUDE: -122.977779
COUNTY: LAKE
AREA: LAKE PILLSBURY
NOT TO SCALE
N
SHEET OF
SCALE
DRAWING
CHECKED BY
DATE
CHECKED BY
A/E
DRAWN BY
DESIGNED BY
PROJECT NUMBER
N A
M E:
PR
O
JE
C
T
FO
R
ES
T:
D R
A W
IN
G
N A
M E:
PACIFIC
REGION
SOUTHWEST
R5
NO. DATE REVISIONS
SERVICE
U S D A
FOREST
SO
DA
C
RE
EK
G
EN
ER
AT
OR
W
IR
IN
G
PR
OJ
EC
T
JJVL
10/06/2014
RG
RG
RG
(MWDL #1420)
AG-91S8-D-11-0080
LOCATION MAP
2235 Mercury Way, Suite 150
Santa Rosa, California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com
GHD Inc.
1 5
G0.1
NOT TO SCALE
LAKE
PILLSBURRY
NOT TO SCALE
N
PROJECT
LOCATION
SHEET INDEX
SHEET OF
DRAWING
NUMBER
DESCRIPTION
SUBMITTAL
PRE-FINAL
GENERAL
1 5
G 0.1
COVER SHEET, VICINITY MAP, AND LOCATION MAP
X
ELECTRICAL
2 5
E 0.1
GENERAL NOTES, LEGEND AND ABBREVIATIONS
X
3 5
E 1.0 ELECTRICAL SITE LAYOUT PLAN X
4 5
E 5.0 MISCELLANEOUS DETAILS X
5 5
E 6.0 SINGLE LINE DIAGRAM AND SCHEDULE X
AREA MAP
CALIFORNIA
S
O
D
A
C
R
E
E
K
S
I M
M
O
N
S
E
L
K
M
O
U
N
T
A
I
E
L
K
M
O
U
N
T
A
I
S I M
M O
S
I M
M
O
ANNOTATION
SWITCHING
LIGHTING
CONDUIT
MAIN SWITCHBOARD
DISTRIBUTION PANEL BOARD
COMBINATION METER/MAIN SERVICE PANEL
BRANCH CIRCUIT PANEL BOARD, SURFACE OR FLUSH
MOUNTED
LIGHTING CONTROL PANEL
SIGNAL TERMINAL CABINET OR CONTROL PANEL
SURFACE OR FLUSH MOUNTED
SIGNAL TERMINAL BACKBOARD
CONCRETE UNDERGROUND HAND HOLE
(NUMBER DENOTES CHRISTY SIZE)
TRANSFORMER
EQUIPMENT
GENERAL ELECTRICAL NOTESELECTRICAL SYMBOLS LEGEND
KEYNOTE
DEMOLITION NOTE
RACEWAY, FEEDER OR CIRCUIT DESIGNATION (SEE SCHEDULE)
LIGHTING FIXTURE TYPE DESIGNATION
(SEE SCHEDULE)
DETAIL INDICATOR SECTION INDICATOR
MECHANICAL EQUIPMENT DESIGNATION
(SEE SCHEDULE)
DUPLEX RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,
MOUNTING HEIGHT: +18" AFF UON
DUPLEX RECEPTACLE - SPLIT WIRED, SWITCHED
DUPLEX RECEPTACLE - EMERGENCY POWER
DUPLEX RECEPTACLE - CEILING MOUNTED
FLOOR RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,
FLUSH TYPE UON
DOUBLE DUPLEX RECEPTACLE, 15A 125V 2P 3W, GROUNDING TYPE,
MOUNTING HEIGHT: +18" AFF UON
SINGLE RECEPTACLE, 20A 125V 2P 3W, GROUNDING TYPE,
MOUNTING HEIGHT: +18" AFF UON
SPECIAL PURPOSE RECEPTACLE AS DESIGNATED
SEE 'SPECIAL SYMBOLS' ON EACH SHEET
DUAL SERVICE RECESSED FLOOR BOX WITH DUPLEX AND DATA
RECEPTACLES
JUNCTION BOX, CODE SIZED UON
FLOOR JUNCTION BOX
DISCONNECT SWITCH - FUSED WHERE APPLICABLE
MOTOR STARTER, COMBINATION WITH DISCONNECT SWITCH
MOTOR STARTER OR CONTROLLER
MOTOR CONNECTION
CEILING EXHAUST FAN
WATER HEATER
POWER POLE: P=POWER, T=TELEPHONE,
D=DATA, C=COMBINATION
TEST PORT
GROUND ROD
GUY WIRE AND ANCHOR
THERMOSTAT (SEE MECHANICAL DRAWINGS)
COORDINATE MOUNTING HEIGHT
BYPASS TIMER OR TIME SWITCH
PUSHBUTTON
LIGHTING CONTACTOR
CONDUIT INSTALLED ABOVE GRADE
CONDUIT INSTALLED UNDERGROUND OR UNDER SLAB
CONDUIT STUB-OUT WITH CAP
FLEXIBLE CONDUIT WHIP TO LIGHT FIXTURE OR EQUIPMENT
FLUORESCENT FIXTURE, RECESSED
RECESSED DOWN LIGHT FIXTURE
RECESSED DIRECTIONAL FIXTURE (ARROW INDICATES AIMING)
FLUORESCENT FIXTURE, SURFACE MOUNTED
SURFACE, PENDANT OR OTHER FIXTURE
FLUORESCENT FIXTURE, WALL MOUNTED
WALL-MOUNTED HID, INCANDESCENT, OR COMPACT FLUORESCENT
FIXTURE
FLUORESCENT FIXTURE, PENDANT OR CABLE HUNG
LIGHT TRACK AND TRACK-MOUNTED FIXTURES
BATH FAN WITH INTEGRAL LIGHT
EXIT SIGN, SINGLE FACE WITH DIRECTIONAL ARROWS AS INDICATED
EXIT SIGN, DOUBLE FACE WITH DIRECTIONAL ARROWS AS INDICATED
EXIT SIGN, LOW LEVEL
COMBINATION EXIT/EMERGENCY LIGHT FIXTURE
MOUNTING HEIGHT: +8'-0" AFF, UON
EMERGENCY FIXTURE
MOUNTING HEIGHT: +8'-0" AFF, UON
DENOTES FIXTURE CONNECTED TO EMERGENCY CIRCUIT
ADJUSTABLE SPOT OR FLOOD (ARROW INDICATES AIMING)
OUTDOOR SITE LIGHT, POLE MOUNTED LUMINAIRE ARROW
INDICATES AIMING DIRECTION, IF APPLICABLE
BOLLARD OR POST-TOP FIXTURE
LIGHT SWITCH, SPST - MOUNTING HEIGHT: +44" AFF, UON
LIGHT SWITCH, DPST - MOUNTING HEIGHT: +44" AFF, UON
LIGHT SWITCH, 3-WAY - MOUNTING HEIGHT: +44" AFF, UON
LOW VOLTAGE SWITCH, MOMENTARY CONTACT, 3-POS.,
CENTER-OFF, MOUNTING HEIGHT: +44" AFF, UON
TIMER SWITCH - MOUNTING HEIGHT: +44" AFF, UON
CIRCUIT AND SWITCH DESIGNATION FOR LIGHTING FIXTURE
CIRCUIT AND RELAY DESIGNATION FOR LIGHTING FIXTURES
(SEE CORRESPONDING LIGHTING CONTROL PANEL RELAY
SCHEDULE)
DIMMER SWITCH - MOUNTING HEIGHT: +44" AFF, UON
OCCUPANCY SENSOR POWER PACK, 1-CIRCUIT, MOUNTED ABOVE
CEILING
OCCUPANCY SENSOR POWER PACK, 2-CIRCUIT
MOUNTED ABOVE CEILING
OCCUPANCY SENSOR, CEILING MOUNTED, LINE VOLTAGE
OCCUPANCY SENSOR, CEILING MOUNTED, LOW VOLTAGE
OCCUPANCY SENSOR, WALL MOUNTED, LINE VOLTAGE, 1-CIRCUIT
MOUNTING HEIGHT: +44" AFF, UON
OCCUPANCY SENSOR, WALL MOUNTED, LINE VOLTAGE, 2-CIRCUIT
MOUNTING HEIGHT: +44" AFF, UON
PHOTO CONTROL SWITCH - MOUNT ON BUILDING EXTERIOR
TIME CLOCK FOR LIGHTING CONTROL
POWER
CONDUIT HOME RUN TO DESIGNATED PANEL, TERMINAL, OR
CONTROL CABINET
EXAMPLES:
NOTE FOR CONDUIT: THE TIC MARKS INDICATE THE QUANTITY OF
#12 AWG WIRES OR, IF INDICATED, THE QUANTITY OF OTHER SIZE
WIRE OR CABLES.
SEE THE SINGLE LINE DIAGRAM FOR FEEDER SIZES.
EXAMPLES: = (3) #12 = (2) #10
= (1) TYPE F1 CABLE. SEE CABLE SCHEDULE.
F1
OBJECT LINES
NEW OBJECTS
(HEAVY CONTINUOUS LINES, UNDERGROUND CONDUIT
HEAVY DASHED LINES)
EXISTING OBJECTS TO REMAIN. MAY INCLUDE NEW CIRCUITING ETC.
(FINE CONTINUOUS LINES, UNDERGROUND CONDUIT
FINE DASHED LINES)
EXISTING OBJECTS TO BE DEMOLISHED
(EXTRA FINE DASHED LINES, SCREENED)
E-501
A
E-301
WH
A
ABBREVIATIONS
(D) DEMOLISH
(E) EXISTING
(F) FUTURE
(N) NEW
A AMPERES
AC ALTERNATING CURRENT
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CAPACITY
ANN ANNUNCIATOR
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BAT BATTERY
BFG BELOW FINISH GRADE
CATV CABLE TELEVISION
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CO CONDUIT ONLY
COMPT COMPARTMENT
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
EF EXHAUST FAN
EGU ENGINE GENERATOR UNIT
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRICAL NON-METALLIC TUBING
EP EXPLOSION PROOF
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FO FIBER OPTIC
FU FUSE
GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFR GROUND FAULT RELAY
HID HIGH INTENSITY DISCHARGE
HOA "HAND-OFF-AUTO" SWITCH
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HVAC HEATING, VENTILATION &
AIR-CONDITIONING
IG ISOLATED GROUND
JB JUNCTION BOX
KAIC KILO-AMPS INTERRUPTING CAPACITY
KV KILOVOLT
KVA KILOVOLT-AMP
KW KILOWATT
KWH KILOWATT-HOUR
LPS LOW PRESSURE SODIUM
LV LOW VOLTAGE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MFR MANUFACTURER
MH METAL HALIDE
MLO MAIN LUGS ONLY
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
PA PUBLIC ADDRESS
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PB PULL BOX, ELECTRICAL
RECPT RECEPTACLE, OUTLET
RGS RIGID GALVANIZED STEEL (CONDUIT)
RVSS REDUCED VOLTAGE SOFT
START
RTU REMOTE TERMINAL UNIT
TV TELEVISION MONITOR (SET)
TVSS TRANS. VOLT. SURGE SUPPRESSOR
UF UNDER FLOOR
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT-AMP
VFD VARIABLE FREQUENCY DRIVE
WP WEATHERPROOF
WPI WEATHERPROOF IN USE
XFMR TRANSFORMER
SHEET OF
SCALE
DRAWING
CHECKED BY
DATE
CHECKED BY
A/E
DRAWN BY
DESIGNED BY
PROJECT NUMBER
N A
M E:
PR
O
JE
C
T
FO
R
ES
T:
D R
A W
IN
G
N A
M E:
PACIFIC
REGION
SOUTHWEST
R5
NO. DATE REVISIONS
SERVICE
U S D A
FOREST
SO
DA
C
RE
EK
G
EN
ER
AT
OR
W
IR
IN
G
PR
OJ
EC
T
JJVL
10/06/2014
RG
RG
RG
(MWDL #1420)
AG-91S8-D-11-0080
CCTV CAMERA, CEILING MOUNT
INTERCOM CALL IN SWITCH - MOUNTING HEIGHT: +44" AFF, UON
TELEPHONE OUTLET FOR WALL MOUNTED TELEPHONE
MOUNTING HEIGHT: +44" AFF UON
DATA OUTLET - MOUNTING HEIGHT: +18" AFF UON
TELEPHONE/DATA OUTLET, FLUSH TYPE UON
MOUNTING HEIGHT: +18" AFF UON
SURFACE RACEWAY WITH POWER AND TELEPHONE/DATA
RECEPTACLES AS INDICATED
CATV OUTLET - MOUNTING HEIGHT: +96" AFF UON
AUDIO/VIDEO OUTLET - MOUNTING HEIGHT: +18" AFF UON
CLOCK WITH BUZZER - MOUNTING HEIGHT: SEE PLANS
BELL, STANDARD 6" - MOUNTING HEIGHT: SEE PLANS PA SYSTEM
SPEAKER - WALL MOUNTED
PA SYSTEM SPEAKER - CEILING MOUNTED
PA SYSTEM HORN - MOUNTING HEIGHT: SEE PLANS
COMMUNICATION
2235 Mercury Way, Suite 150
Santa Rosa, California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com
GHD Inc.
2 5
E0.1
NOT TO SCALE
1. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC, SIZE AND LOCATION OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER
POSSIBLE, CONTRACTOR SHALL MAKE USE OF MANUFACTURER'S OR OWNER'S DATA AVAILABLE AND VERIFY DATA IN
THE FIELD FOR PROVIDING AND INSTALLING CORRECT CABLE LENGTHS.
2. ALL WIRING SHALL CONFORM TO THE LATEST EDITION OF NATIONAL ELECTRICAL CODE OR APPLICABLE STATE
BUILDING CODE.
3. ALL EQUIPMENT AND MATERIALS SHALL BE UL LISTED WHERE LISTING IS AVAILABLE FOR THAT TYPE OF EQUIPMENT OR, SHALL CONFORM TO ANSI OR NEMA STANDARDS.
4. WORKMANSHIP SHALL CONFORM TO CONSTRUCTION PRACTICES RECOMMENDED BY THE AMERICAN ELECTRICIANS
HANDBOOK BY CROFT (LATEST EDITION) AND SHALL BE SUBJECT OF THE APPROVAL OF THE AGENCY WHO HAS JURISDICTION, AND THE ENGINEER.
5. METALLIC ENCLOSURES, RACEWAYS AND ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH
REQUIREMENTS OF NEC ARTICLE 250. PROVIDE GROUND WIRE IN EVERY RACEWAY. SIZE IN ACCORDANCE WITH NEC TABLE
250-122.
6. COORDINATE WITH ENGINEER FOR EQUIPMENT REQUIREMENTS, AND PROVIDE ALL WIRING AND PROTECTION EQUIPMENT
REQUIRED.
7. CONDUIT SHALL BE PVC (BELOW GRADE), OR GALVANIZED RIGID STEEL (EXPOSED INSTALLATION) UNLESS NOTED
OTHERWISE. PROVIDE PROPER FITTINGS BETWEEN DISSIMILAR MATERIALS. FLEXIBLE CONDUIT SHALL BE JACKETED TYPE
AND IN ACCORDANCE WITH NEC ARTICLE 350.
8. WIRING SHALL BE NEC TYPE RHW OR USE-2. CONDUCTORS SHALL BE STRANDED COPPER.
9. TEST: TESTING RESULTS SHALL SUBMITTED FOR APPROVAL TO ENGINEER.
A. OPERATION TEST
B. INSULATION RESISTANCE
C. GROUND RESISTANCE
10. CONTRACTOR SHALL SUBMIT ELECTRICAL PRODUCT CATALOG DATA, AND RECEIVE APPROVAL FROM ENGINEER BEFORE
ORDERING MATERIALS.
SHEET OF
SCALE
DRAWING
CHECKED BY
DATE
CHECKED BY
A/E
DRAWN BY
DESIGNED BY
PROJECT NUMBER
N A
M E:
PR
O
JE
C
T
FO
R
ES
T:
D R
A W
IN
G
N A
M E:
PACIFIC
REGION
SOUTHWEST
R5
NO. DATE REVISIONS
SERVICE
U S D A
FOREST
SO
DA
C
RE
EK
G
EN
ER
AT
OR
W
IR
IN
G
PR
OJ
EC
T
JJVL
10/06/2014
RG
RG
RG
(MWDL #1420)
AG-91S8-D-11-0080
2235 Mercury Way, Suite 150
Santa Rosa, California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com
GHD Inc.
3 5
E1.0
AS SHOWN
E5.0
TRANSFER SWITCH
AND PANELBOARD,
SEE ENLARGED PLAN
SHEET GENERAL NOTES
1. PLAN BASED ON BEST AVAILABLE RECORD INFORMATION. VERIFY ALL LOCATIONS
AND SUBSURFACE CONDITIONS PRIOR TO START OF WORK.
2. REPAIR, PATCH AND TOUCH UP MARRED SURFACES TO MATCH ADJACENT FINISHES.
3. INSTALL THE FOLLOWING GOVERNMENT FURNISHED MATERIALS:
• GENERATOR - 1 EACH
• TRANSFER SWITCH - 1 EACH
• DISTRIBUTION PANEL - 1 EACH
• CONCRETE PULLBOX WITH LID - 1 EACH
• 2" ELECTRICAL CONDUIT - 160 LINEAR FEET
• 2" GALVANIZED RIGID STEEL CONDUIT - 50 LINEAR FEET
• #3/0 AWG ELECTRICAL WIRE - 580 LINEAR FEET
4. UNDERGROUND CONDUIT SHALL BE PVC, SCHEDULE 40, PER NEMA TC-2.
5. ABOVEGROUND CONDUIT SHALL BE GALVANIZED RIGID STEEL CONDUIT, PER UL 6
AND ANSI C80.1.
6. WIRE SHALL BE INSULATED COPPER, TYPE RHH/RHW.
KEYNOTES
1. PROVIDE TRANSFER SWITCH AND PANELBOARD MOUNTED ON RGS POSTS AND
UNISTRUT SUPPORTS.
2. PROVIDE NEW CONDUIT RACEWAY BETWEEN GENERATOR, TRANSFER SWITCH,
BATTERY CHARGER AND BLOCK HEATER.
3. PROVIDE NEW POLYETHYLENE PROPANE PIPE BETWEEN GENERATOR AND (E)
PROPANE PIPE.
4. BELOW GRADE LIQUID PROPANE PIPE TO BE POLYETHYLENE PIPE RATED FOR THIS
USE AND 150 PSI PRESSURE.
5. ABOVE GRADE LIQUID PROPANE PIPE TO BE BLACK IRON STEEL, SCHEDULE 80,
PROVIDE TWO COATS OF RUST INHIBITING PAINT.
6. INSTALL PIPE SYSTEM PER REQUIREMENTS OF PROPANE SUPPLIER.
7. PROVIDE ANODELESS SERVICE RISER, ELSTER OR EQUAL WITH TRACE WIRE CLIP.
8. CONNECT 1" GAS SERVICE TO GENERATOR PER MANUFACTURER
RECOMMENDATION: INSTALL STAINLESS STEEL FLEXIBLE CONNECTION WITH
POLYMER COATING. MAXIMUM 48 INCH LENGTH.
9. PROVIDE BALL VALVE SHUT OFF RATED FOR PROPANE SERVICE.
10. LOCATION OF CONDUITS FOR GENERATOR CIRCUIT BREAKER, BATTERY CHARGER,
BLOCK HEATER, AND FUEL INLET FLEXIBLE FUEL LINE AS PER MANUFACTURER'S
RECOMMENDATION.
11. GOVERNMENT FURNISHED PULL BOX.
12. BRING GAS SUPPLY RISER UP THROUGH GENERATOR PAD IN SLEEVE. FILL ANNULAR
SPACE BETWEEN PIPE AND SLEEVE WITH SAND. ROUTE GAS PIPE UP AND IN TO
CONNECTION IN GENERATOR ENCLOSURE. LOCATE PIPE IN PAD USING
MANUFACTURER RECOMMENDED DIMENSION.
E
PULLBOX,
SEE DETAIL
E5.0
2"C, 3#3/0, 1#6
SEE DETAIL
E5.0
1" PROPANE PIPE,
SEE DETAIL
E5.0
GENERATOR
CONCRETE PAD
(BY OTHERS)
0 40'20'
1"=20'
CONNECT PROPANE PIPE TO (E)
PROPANE PIPE AND FITTINGS
ENLARGED PLAN
(E) GENERATOR
BUILDING WALL
PULBOX
TRANSFER SWITCH
AND PANELBOARD
MOUNTING SUPPORT
ELECTRICAL
CONDUIT FROM
GENERATOR
(E) GROUND ROD,
SEE DETAIL
E5.0
PROPANE
LOCATION
1"C, 4#12, 2#12
SEE DETAIL
E5.0
ELECTRICAL CONDUIT FOR
GENERATOR BATTERY
CHARGER AND BLOCK HEATER
CONDUIT
LOCATIONS
9 12
DRAWING
CHECKED BY
DATE
CHECKED BY
A/E
DRAWN BY
DESIGNED BY
PROJECT NUMBER
N A
M E:
PR
O
JE
C
T
FO
R
ES
T:
D R
A W
IN
G
N A
M E:
PACIFIC
REGION
SOUTHWEST
R5
NO. DATE REVISIONS
SERVICE
U S D A
FOREST
SO
DA
C
RE
EK
G
EN
ER
AT
OR
W
IR
IN
G
PR
OJ
EC
T
JJVL
10/06/2014
RG
RG
RG
(MWDL #1420)
AG-91S8-D-11-0080
2235 Mercury Way, Suite 150
Santa Rosa, California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com
GHD Inc.
4 5
E5.0
NOT TO SCALE
NOTE:
ALL ENCLOSURES & MTG MTRLS SHALL BE STAINLESS STEEL.
4"
(TYP)
THREADED CAP (TYP)
ELEVATION
PLAN
CONCRETE PIER, TYP
1/4" DIA U-BOLT HDG,
TYP
P1001SL HDG, TYP
3'- 10"
AS REQUIRED
2" RGS, TYP.
P1001SL HDG, TYP
PANEL
"SC"
CONCRETE PIER, TYP
" CHAMFER, TYP
2"C
2"C W/ MYERS
HUB OR EQUAL
CONDUITS
AS REQUIRED
10"
30"
17-1/4"
22-1/4"
35-1/4"
DESIGN LOAD: TRAFFIC
12"
12"
22-1/4"
35-1/4"
SIDE KNOCKOUTS. NON-SETTLING SHOULDERS
MAINTAIN GRADE AND FACILITATE BACKFILLING.
PULL AND JUNCTION BOX WITH END AND
A HIGH DENSITY REINFORCED CONCRETE
ULTRAVIOLET INHIBITOR
FACE ANCHORED IN CONCRETE
ETCHED POLYETHYLENE FACE
N36-61J
3"
BEAD WELDED
MARKING: ELECTRICAL
STEEL COVERS FIT
OVER ENTIRE BOX
NOTE:
MOUNTING SUPPORT (OFCI)
(E) GROUND ROD
TYP. PULLBOX (OFCI)
9'-6" L X 4'-6" W
#6 @ 12" EA. WAY TOP
& BOTTOM
6" BASE COURSE
COMPACTED TO 95%
MIN. DENSITY
GENERATOR CONCRETE PAD (BY OTHERS)
NOTE:
MAINTAIN A MINIMUM VERTICAL SEPARATION OF 12" WHEN CROSSING SANITARY SEWER
LINES. ROUTE CONDUIT EITHER ABOVE OR BELOW OTHER UTILITIES AS NECESSARY TO
ACHIEVE THIS SEPARATION WHILE MAINTAINING THE MINIMUM BACKFILL COVERAGE.
ROCK FREE
NATIVE BACKFILL,
95% COMPACTION
#4 MINIMUM SALT
FREE SAND ALL
AROUND
SUB-BASE AND SURFACE TO MATCH
SURROUNDING CONDITIONS
E
FINISH GRADE
M
I N
C
O V
E R
6" NOMINAL
ELECTRICAL TRENCH
GAS TRENCH
WARNING TAPE: BRIGHTLY RED
COLORED PLASTIC TAPE, 8 MIL
APPROXIMATELY 12" BELOW
FINISHED GRADE
ROCK FREE
NATIVE BACKFILL,
95% COMPACTION
#4 MINIMUM SALT
FREE SAND ALL
AROUND
SUB-BASE AND SURFACE TO MATCH
SURROUNDING CONDITIONS
G
FINISH GRADE
M
I N
C
O V
E R
6" NOMINAL
PULLBOX LOCATION
PROPANE PIPE CONNECTION LOCATION
REMOVE CONDUITS, LB FITTINGS AND PULL
BOX. REPAIR, PATCH AND TOUCH UP MARRED
SURFACES TO MATCH ADJACENT FINISHES
REMOVE (E) PIPES AND FITTINGS
INSIDE THE GENERATOR
BUILDING AND UNDERGROUND
CONNECT (N) PROPANE PIPE AND
FITTINGS TO (E) PROPANE FITTING
INTERCEPT (E) CONDUITS
WITH PULLBOX
PULLBOX (OFCI),
SEE DETAIL
MOUNTING SUPPORT (OFCI),
SEE DETAIL
E5.0
CONDUIT STUB-UP
WRAP STEEL CONDUIT WITH
INSULATING TAPE
RIGID STEEL CONDUIT
FINISH GRADE
AS NECESSARY TO
ACCOMODATE TRENCH DEPTH
COUPLING
PVC CONDUIT
COUPLING
E
6" WIDE X 4 MIL THICK BRIGHT COLOR
CONTINUOUSLY PRINTED WARNING
TAPE MANUFACTURED FOR DIRECT
BURIAL 12" BELOW FINISH GRADE
#12 TRACER WIRE
GROUND CONNECTION OF (N)
TRANSFER SWITCH AND PANEL
TO (E) GROUND ROD
(E) GROUND ROD LOCATION,
SEE DETAIL
E5.0
E5.0
DRAWING
CHECKED BY
DATE
CHECKED BY
A/E
DRAWN BY
DESIGNED BY
PROJECT NUMBER
N A
M E:
PR
O
JE
C
T
FO
R
ES
T:
D R
A W
IN
G
N A
M E:
PACIFIC
REGION
SOUTHWEST
R5
NO. DATE REVISIONS
SERVICE
U S D A
FOREST
SO
DA
C
RE
EK
G
EN
ER
AT
OR
W
IR
IN
G
PR
OJ
EC
T
JJVL
10/06/2014
RG
RG
RG
(MWDL #1420)
AG-91S8-D-11-0080
2235 Mercury Way, Suite 150
Santa Rosa, California 95407 USA
T 1 707 523 1010 F 1 707 527 8679
W www.ghd.com
GHD Inc.
5 5
E6.0
NOT TO SCALE
SCHEDULE
150A
200A DOUBLE THROW NEMA KS-1,
TYPE TC NEMA 3R ENCLOSURE (OFCI)
PRODUCT:
GE TC10324R
GENERATOR 30KW, 240V,
1-PHASE, 4-WIRE,
OWNER FURNISHED
CONTRACTOR INSTALLED (OFCI)
DISTRIBUTION PANEL 'SC' (OFCI)
PRODUCTS:
GE TYPE AL,
EATON POW-R-LINE 1a, SQUARE D TYPE NQ
PULLBOX 24"x 36" x 12" DEEP
W/ 12" EXTENSION (OFCI)
PRODUCTS:
BROOKS, CHRISTY, JENSEN, OLDCASTLE
(E) BACKUP GENERATOR
2"C, 3#3/0, 1#6G
(OFCI)
PANEL SCHEDULE
PANEL NAME:
SC
VOLTAGE: 240 NEMA RATING: 3R NOTES: PROVIDE 200A SUBFEED BREAKER FOR BARRACKS
MAINS RATING: 200A PHASE: 1 AIC RATING: 10K MOUNTING: SURFACE
BUS RATING: 225A WIRE: 3 DEMAND FACTOR: LOCATION: OUTDOOR ON MOUNTING SUPPORT
CKT NO. USE DESCRIPTION
BKR
SIZE
BKR
OPTS
BKR KVA PHASE BKR KVA
BKR
OPTS
BKR
SIZE
DESCRIPTION USE CKT NO.
1 P GAS HOUSE 100/2 1.00 A 1.50 100/2 PUMP HOUSE P 2
3 1.00 B 1.50 4
5 P OFFICE 70/2 1.00 A 0.10 20/1 BATTERY CHARGER O 6
7 1.00 B 1.00 20/1 BLOCK HEATER O 8
9 P WAREHOUSE 70/2 1.00 A 0.10 20/1 LIGHTS L 10
11 1.00 B SPACE 12
13 SPACE A SPACE 14
15 SPACE B SPACE 16
17 SPACE A 4.00 200/2
BARRACKS (SEE NOTE)
P 18
19 SPACE B 4.00 20
LOADS USE LEGEND LOAD TYPE
PHASE A: 8.7
(KVA)
H HVAC
PHASE B: 9.5
(KVA)
L LIGHTING
M MOTOR
TOTAL: 18.2
(CONNECTED KVA)
O OTHER
75.8
(CONNECTED AMPS)
R RECEPTACLE
P PANEL
SINGLE LINE DIAGRAM
PROVIDE #2 AWG 4/C TYPE SOOW CORD
(40 FOOT LENGTH), TO REPLACE (E) FLEXIBLE
CABLE AND CONNECT TO (N) TRANSFER SWITCH
REMOVE (E) GENERATOR,
SEE PHOTO #3
REMOVE (E) DISTRIBUTION
PANEL, GUTTER, CONDUITS
AND CABLES TO BE REMOVED,
SEE PHOTOS #1 AND #2
PHOTO #1 PHOTO #2
PHOTO #3
REMOVE (E) GENERATOR
REMOVE (E) DISTRIBUTION PANEL,
GUTTER, CONDUITS AND CABLES,
SEE PHOTOS #1 AND #2
REMOVE (E) FLEXIBLE CABLE
KILLARK VP1033 PLUG
KILLARK VPR1033 CONNECTOR