EXISTING SYSTEM'S POINTS LIST

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

; Panel type definitions panel-type 01 irc-3 master job-name 1 ~C.S.U. NCGRP 09-03~ comm-baud-rate 9600 panel-type 10 remote-annunciator class-b

; Configuration information configure 1 printer disabled configure 1 baud-rate 2400 start-action 1 6001 bell-coder 1 disabled audible-walk-test external-command-set 1 enabled

; Card type definitions card-type 01 1 zas-1b card-type 01 2 zas-1b

; Multi-Resident panel definitions

; Polling list poll-address 10

; Device type definitions device-type 0101 0102 photoelectric 3 1 3 1 device-type 0103 thermal 0 0 0 0 device-type 0104 0112 photoelectric 3 1 3 1 device-type 0113 thermal 0 0 0 0 device-type 0114 0121 photoelectric 3 1 3 1 device-type 0122 thermal 0 0 0 0 device-type 0123 photoelectric 3 1 3 1 device-type 0124 0133 thermal 0 0 0 0 device-type 0134 0136 photoelectric 3 1 3 1 device-type 0137 thermal 0 0 0 0 device-type 0138 photoelectric 3 1 3 1 device-type 0139 thermal 0 0 0 0 device-type 0140 0141 thermal 0 0 0 0 device-type 0142 0145 photoelectric 3 1 3 1 device-type 0146 0154 photoelectric 3 1 3 1 device-type 0155 thermal 0 0 0 0 device-type 0156 0161 photoelectric 3 1 3 1 device-type 0162 0164 thermal 0 0 0 0 device-type 0165 photoelectric 3 1 3 1 device-type 0166 0169 thermal 0 0 0 0 device-type 0170 photoelectric 3 1 3 1 device-type 0171 thermal 0 0 0 0 device-type 0172 0173 photoelectric 3 1 3 1 device-type 0174 0175 thermal 0 0 0 0 device-type 0176 0190 photoelectric 3 1 3 1 device-type 0201 alarm-monitor-module 0 1 0 1 device-type 0203 0221 alarm-monitor-module 0 1 0 1 device-type 0222 relay-module 0 0 0 0 device-type 0223 0233 alarm-monitor-module 0 1 0 1 device-type 0234 relay-module 0 0 0 0 device-type 0236 0237 alarm-monitor-module 0 1 0 1 device-type 0271 supervisory-monitor-module 0 0 0 0 device-type 0272 0273 alarm-monitor-module 0 1 0 1 device-type 0274 supervisory-monitor-module 0 0 0 0 device-type 0275 alarm-monitor-module 0 1 0 1 device-type 0276 supervisory-monitor-module 0 0 0 0 device-type 0277 alarm-monitor-module 0 1 0 1 device-type 0278 supervisory-monitor-module 0 0 0 0 device-type 0279 alarm-monitor-module 0 1 0 1 device-type 0280 supervisory-monitor-module 0 0 0 0 device-type 0281 alarm-monitor-module 0 1 0 1 device-type 0282 supervisory-monitor-module 0 0 0 0 device-type 0283 alarm-monitor-module 0 1 0 1 device-type 0284 supervisory-monitor-module 0 0 0 0 device-type 0330 photoelectric 3 1 3 1 device-type 0331 thermal 0 0 0 0 device-type 0332 photoelectric 3 1 3 1 device-type 0335 0345 photoelectric 3 1 3 1 device-type 0333 thermal 0 0 0 0 device-type 0346 0351 photoelectric 3 1 3 1 device-type 0412 alarm-monitor-module 0 1 0 1 device-type 0414 0425 alarm-monitor-module 0 1 0 1 device-type 0202 relay-module 0 0 0 0 device-type 0409 alarm-monitor-module 0 1 0 1 device-type 0240 0243 alarm-monitor-module 0 1 0 1 device-type 0410 alarm-monitor-module 0 1 0 1 device-type 0261 0262 supervisory-monitor-module 0 0 0 0 device-type 0252 0253 visual-module n 0 N 0 device-type 0254 0257 audible-module n 0 N 0 device-type 0250 visual-module n 0 N 0 device-type 0251 visual-module n 0 N 0 device-type 0245 0246 audible-module n 0 N 0 device-type 0247 0249 visual-module n 0 N 0 device-type 0258 relay-module 0 0 0 0 device-type 0259 0260 supervisory-monitor-module 0 0 0 0 device-type 0244 alarm-monitor-module 0 1 0 1 device-type 0464 supervisory-monitor-module 0 0 0 0 device-type 0191 photoelectric 3 1 3 1 device-type 0463 supervisory-monitor-module 0 0 0 0 device-type 0238 relay-module 0 0 0 0 device-type 0235 relay-module 0 0 0 0 device-type 0353 photoelectric 3 1 3 1 device-type 0334 photoelectric 3 1 3 1 device-type 0352 photoelectric 3 1 3 1 device-type 0263 alarm-monitor-module 0 1 0 1 device-type 0239 relay-module 0 0 0 0 device-type 0301 0307 photoelectric 3 1 3 1 device-type 0329 thermal 0 0 0 0 device-type 0402 0408 alarm-monitor-module 0 1 0 1 device-type 0471 supervisory-monitor-module 0 0 0 0 device-type 0472 alarm-monitor-module 0 1 0 1 device-type 0473 supervisory-monitor-module 0 0 0 0 device-type 0474 alarm-monitor-module 0 1 0 1 device-type 0475 relay-module 0 0 0 0 device-type 0264 audible-module y 0 y 0 device-type 0426 alarm-monitor-module 0 1 0 1 device-type 0310 0328 photoelectric 3 1 3 1 device-type 0308 0309 photoelectric 3 1 3 1 device-type 0401 alarm-monitor-module 0 1 0 1 device-type 0480 alarm-monitor-module 0 1 0 1 device-type 0265 alarm-monitor-module 0 1 0 1 device-type 0354 thermal 0 0 0 0 device-type 0355 photoelectric 3 1 3 1 device-type 0356 photoelectric 3 1 3 1 device-type 0430 relay-module 0 0 0 0 device-type 0359 thermal 0 0 0 0 device-type 0431 supervisory-monitor-module 0 0 0 0 device-type 0432 supervisory-monitor-module 0 0 0 0

; Device/Zone response definitions normal-response alarm-zone 01 01 sup-open-set 50 10 12 alarm-action 0900 alarm-action 4000 alarm-message 01 ~SMOKE DETECTOR - VAULT ELEV. MACH. ROOM~ normal-response alarm-zone 01 02 sup-open-set 50 10 12 alarm-action 0900 alarm-action 4000 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B01~ normal-response alarm-zone 01 03 sup-open-set 50 10 14 alarm-action 0902 alarm-message 01 ~THERMAL DETECTOR - VAULT ROOM B02~ normal-response alarm-zone 01 04 sup-open-set 50 10 12 alarm-action 0900 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B03~ normal-response alarm-zone 01 05 sup-open-set 50 10 12 alarm-action 0900 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B03~ normal-response alarm-zone 01 06 sup-open-set 50 10 12 alarm-action 0900 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B03~ normal-response alarm-zone 01 07 sup-open-set 50 10 12 alarm-action 0900 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B03~ normal-response alarm-zone 01 08 sup-open-set 50 10 12 alarm-action 0900 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B03~ normal-response alarm-zone 01 09 sup-open-set 50 10 12 alarm-action 0900 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM B03~ normal-response alarm-zone 01 10 sup-open-set 50 10 12 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 129~ alarm-zone 01 11 sup-open-set 50 10 12 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 127~ normal-response alarm-zone 01 12 sup-open-set 50 10 12 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 126~ normal-response alarm-zone 01 13 sup-open-set 50 10 14 alarm-action 1010 alarm-message 01 ~THERMAL DETECTOR - VAULT ROOM 147~ normal-response alarm-zone 01 14 sup-open-set 50 10 12 alarm-action 1008 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 148~ normal-response alarm-zone 01 15 sup-open-set 50 10 12 alarm-action 1008 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 148~ normal-response alarm-zone 01 16 sup-open-set 50 10 12 alarm-action 1008 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 148~ normal-response alarm-zone 01 17 sup-open-set 50 10 12 alarm-action 1008 alarm-action 4000 alarm-message 01 ~SMOKE DETECTOR - VAULT GND ELEV LOBBY~ normal-response alarm-zone 01 18 sup-open-set 50 10 12 alarm-action 1008 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 148~ alarm-zone 01 19 alarm-action 1008 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 148~ normal-response alarm-zone 01 20 sup-open-set 50 10 12 alarm-action 1008 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 148~ normal-response alarm-zone 01 21 sup-open-set 50 10 12 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 116~ normal-response alarm-zone 01 22 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 130~ normal-response alarm-zone 01 23 sup-open-set 50 10 12 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 131~ normal-response alarm-zone 01 24 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 132~ normal-response alarm-zone 01 25 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 133~ normal-response alarm-zone 01 26 alarm-action 1002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 134~ normal-response alarm-zone 01 27 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 135~ alarm-zone 01 28 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 137~ normal-response alarm-zone 01 29 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 145~ normal-response alarm-zone 01 30 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 145A~ normal-response alarm-zone 01 31 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 144~ normal-response alarm-zone 01 32 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 143~ normal-response alarm-zone 01 33 sup-open-set 50 10 14 alarm-action 1002 alarm-message 01 ~THERMAL DETECTOR - ROOM 142~ normal-response alarm-zone 01 34 alarm-action 1000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - CORRIDOR 136~ normal-response alarm-zone 01 35 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - CORRIDOR 153~ alarm-zone 01 36 alarm-action 1000 sup-open-set 10 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 149~ normal-response alarm-zone 01 37 alarm-action 1002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 151~ normal-response alarm-zone 01 38 alarm-action 1000 sup-open-set 50 10 12 alarm-message 08 ~SMOKE DETECTOR - ROOM 138~ normal-response alarm-zone 01 39 alarm-action 1002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 139~ normal-response alarm-zone 01 40 sup-open-set 50 10 14 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 140~ normal-response alarm-zone 01 41 sup-open-set 50 10 12 alarm-action 1000 alarm-message 01 ~SMOKE DETECTOR - ROOM 104~ normal-response alarm-zone 01 42 sup-open-set 50 10 12 alarm-action 1000 alarm-action 4004 alarm-message 01 ~SMOKE DETECTOR - GND S ELEV LOBBY~ normal-response alarm-zone 01 43 alarm-action 1000 sup-open-set 50 10 12 alarm-action 4004 alarm-message 01 ~SMOKE DETECTOR - S. ELEV. MACH. ROOM 101~ alarm-zone 01 44 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 215~ normal-response alarm-zone 01 45 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 214~ normal-response alarm-zone 01 46 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 215~ normal-response alarm-zone 01 47 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 216~ normal-response alarm-zone 01 48 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 221~ normal-response alarm-zone 01 49 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 220~ normal-response alarm-zone 01 50 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 219~ normal-response alarm-zone 01 51 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 218~ alarm-zone 01 52 alarm-action 2000 alarm-message 01 ~SMOKE DETECTOR - ROOM 217~ normal-response alarm-zone 01 53 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 235~ normal-response alarm-zone 01 54 sup-open-set 50 10 12 alarm-action 2006 alarm-action 4002 alarm-message 01 ~SMOKE DETECTOR - VAULT 2ND FLR ELEV LBBY~ normal-response alarm-zone 01 55 sup-open-set 50 10 14 alarm-action 2008 alarm-message 01 ~THERMAL DETECTOR - VAULT ROOM 236~ normal-response alarm-zone 01 56 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ normal-response alarm-zone 01 57 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ normal-response alarm-zone 01 58 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ normal-response alarm-zone 01 59 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ normal-response alarm-zone 01 60 alarm-message 01 ~SMOKE DETECTOR - WEST CORRIDOR 236~ normal-response alarm-zone 01 61 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - EAST CORRIDOR 236~ normal-response alarm-zone 01 62 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 225~ normal-response alarm-zone 01 63 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 223~ normal-response alarm-zone 01 64 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 224~ normal-response alarm-zone 01 65 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 228~ normal-response alarm-zone 01 66 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 229~ normal-response alarm-zone 01 67 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 231~ normal-response alarm-zone 01 68 alarm-action 2002 alarm-message 01 ~THERMAL DETECTOR - ROOM 232~ alarm-zone 01 69 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 233~ normal-response alarm-zone 01 70 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 239~ normal-response alarm-zone 01 71 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 240~ normal-response alarm-zone 01 72 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 210~ normal-response alarm-zone 01 73 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 210~ normal-response alarm-zone 01 74 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 207~ normal-response alarm-zone 01 75 alarm-action 2002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - ROOM 206~ normal-response alarm-zone 01 76 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - WEST CORRIDOR 230~ alarm-zone 01 77 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - EAST CORRIDOR 230~ normal-response alarm-zone 01 78 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 201~ normal-response alarm-zone 01 79 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 202~ normal-response alarm-zone 01 80 sup-open-set 50 10 12 alarm-action 2000 alarm-action 4004 alarm-message 01 ~SMOKE DETECTOR - 2ND FLR S ELEV LOBBY~ normal-response alarm-zone 01 81 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - 2ND FLOOR STAIR #1~ normal-response alarm-zone 01 82 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ normal-response alarm-zone 01 83 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ normal-response alarm-zone 01 84 sup-open-set 50 10 12 alarm-action 2006 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 237~ alarm-zone 01 85 alarm-message 01 ~SMOKE DETECTOR - ROOM 222~ normal-response alarm-zone 01 86 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 222~ normal-response alarm-zone 01 87 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 222~ normal-response alarm-zone 01 88 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 222~ normal-response alarm-zone 01 89 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 222~ normal-response alarm-zone 01 90 alarm-action 2000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - ROOM 222~ normal-response alarm-zone 01 91 sup-open-set 50 10 12 alarm-action 1000 alarm-action 4008 alarm-message 01 ~SMOKE DETECTOR PARKING LEVEL ELEV. LOBBY~ normal-response sup-zone 01 99 sup-message 01 ~CM1N Power supply or Internal fault~ normal-response alarm-zone 02 01 sup-open-set 50 10 18 alarm-action 0904 alarm-message 01 ~MANUAL STATION - VAULT ROOM B01~ sup-zone 02 02 sup-message 01 ~VAULT ALTERNATE ELEVATOR RECALL~ normal-response alarm-zone 02 03 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - 1ST FLOOR WEST ENTRANCE~ normal-response alarm-zone 02 04 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - CORRIDOR 136~ normal-response alarm-zone 02 05 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - CORRIDOR 106~ normal-response alarm-zone 02 06 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - -EAST CORRIDOR 136~ normal-response alarm-zone 02 07 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - 1ST FLR STAIR #1~ normal-response alarm-zone 02 08 sup-open-set 50 10 18 alarm-action 1012 alarm-message 01 ~MANUAL STATION - VAULT ROOM 148~ normal-response alarm-zone 02 09 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - ROOM 151~ normal-response alarm-zone 02 10 sup-open-set 50 10 18 alarm-action 1004 alarm-message 01 ~MANUAL STATION - CORRIDOR 152~ normal-response alarm-zone 02 11 sup-open-set 50 10 18 alarm-action 1012 alarm-message 01 ~MANUAL STATION - VAULT ROOM 146~ normal-response alarm-zone 02 12 sup-open-set 50 10 18 alarm-action 2004 alarm-message 01 ~MANUAL STATION - WEST CORRIDOR 226~ normal-response alarm-zone 02 13 sup-open-set 50 10 18 alarm-action 2010 alarm-message 01 ~MANUAL STATION - VAULT ROOM 235~ normal-response alarm-zone 02 14 sup-open-set 50 10 18 alarm-action 2004 alarm-message 01 ~MANUAL STATION - CENTRAL CORRIDOR 226~ normal-response alarm-zone 02 15 sup-open-set 50 10 18 alarm-action 2010 alarm-message 01 ~MANUAL STATION - VAULT ROOM 237~ normal-response alarm-zone 02 16 sup-open-set 50 10 18 alarm-action 2010 alarm-message 01 ~MANUAL STATION - VAULT ROOM 237~ normal-response alarm-zone 02 17 sup-open-set 50 10 18 alarm-action 2004 alarm-message 01 ~MANUAL STATION - 2ND FLR STAIR #4~ normal-response alarm-zone 02 18 sup-open-set 50 10 18 alarm-action 2004 alarm-message 01 ~MANUAL STATION - CORRIDOR 234~ alarm-zone 02 19 sup-open-set 50 10 18 alarm-action 2004 alarm-message 01 ~MANUAL STATION - EAST CORRIDOR 230~ normal-response alarm-zone 02 20 sup-open-set 50 10 18 alarm-action 2004 alarm-message 01 ~MANUAL STATION - WEST CORRIDOR 230~ normal-response alarm-zone 02 21 alarm-set 50 10 19 sup-open-set 50 10 18 alarm-action 0104 alarm-message 01 ~MANUAL STATION - ROOF STAIR #2~ normal-response sup-zone 02 22 sup-message 01 ~VAULT PRIMARY ELEVATOR RECALL~ normal-response alarm-zone 02 23 sup-open-set 50 10 24 alarm-set 50 10 09 alarm-action 6000 alarm-action 6002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM B03~ normal-response alarm-zone 02 24 sup-open-set 50 10 24 alarm-set 50 10 09 alarm-action 6000 alarm-action 6002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM B03~ normal-response alarm-zone 02 25 sup-open-set 50 10 24 alarm-set 50 10 09 alarm-action 6000 alarm-action 6002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM B03~ alarm-zone 02 26 sup-open-set 50 10 24 alarm-set 50 10 09 alarm-action 6000 alarm-action 6002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM B03~ normal-response alarm-zone 02 27 sup-open-set 50 10 24 alarm-set 50 10 09 alarm-action 6000 alarm-action 6002 alarm-action 8000 alarm-action 8002 alarm-message 01 ~OXYGEN SENSOR - VAULT STAIR #4~ normal-response alarm-zone 02 28 sup-open-set 50 10 24 alarm-set 50 10 06 alarm-action 8000 alarm-action 8002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM 148~ normal-response alarm-zone 02 29 sup-open-set 50 10 24 alarm-set 50 10 06 alarm-action 6000 alarm-action 6002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM B01~ normal-response alarm-zone 02 30 alarm-action 0906 sup-open-set 50 10 16 alarm-message 01 ~DUCT DET - AHU-6 RETURN~ normal-response alarm-zone 02 31 alarm-action 0906 sup-open-set 50 10 16 alarm-message 01 ~DUCT DET - AHU-6 SUPPLY~ normal-response alarm-zone 02 32 alarm-action 1006 sup-open-set 50 10 16 alarm-message 01 ~DUCT DET - AHU-7 SUPPLY~ alarm-zone 02 33 alarm-action 1006 sup-open-set 50 10 16 alarm-message 01 ~DUCT DET - AHU-7 RETURN~ normal-response sup-zone 02 34 sup-message 01 ~DIESEL PUMP SHUT DOWN~ normal-response sup-zone 02 35 sup-message 01 ~ALTERNATE SOUTH ELEVATOR RECALL~ normal-response alarm-zone 02 36 sup-open-set 50 10 16 alarm-action 2012 alarm-message 01 ~DUCT DET - VAULT AHU-9 SUPPLY~ normal-response alarm-zone 02 37 alarm-set 50 10 11 sup-open-set 50 10 10 alarm-action 0104 alarm-set 50 10 03 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 238 (HSSD)~ normal-response sup-zone 02 38 sup-message 01 ~PRIMARY SOUTH ELEVATOR RECALL~ normal-response sup-zone 02 39 sup-message 01 ~GENERAL OXYGEN ALARM OUTPUT~ normal-response alarm-zone 02 40 sup-open-set 50 10 24 alarm-set 50 10 06 alarm-action 8000 alarm-action 8002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM 146~ normal-response alarm-zone 02 41 sup-open-set 50 10 24 alarm-set 50 10 06 alarm-action 8000 alarm-action 8002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM 148~ alarm-zone 02 42 sup-open-set 50 10 24 alarm-set 50 10 06 alarm-action 8000 alarm-action 8002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM 148~ normal-response alarm-zone 02 43 sup-open-reset 50 10 24 alarm-set 50 10 06 alarm-action 8000 alarm-action 8002 alarm-message 01 ~OXYGEN SENSOR - VAULT ROOM 148~ normal-response alarm-zone 02 44 sup-open-set 50 10 18 alarm-action 0904 alarm-message 01 ~MANUAL STATION - VAULT ROOM B03~ normal-response sup-zone 02 45 sup-short-reset 60 02 45 sup-message 01 ~FIRE ALARM HORNS - A~ normal-response sup-zone 02 46 sup-short-reset 60 02 46 sup-message 01 ~FIRE ALARM HORNS - B~ normal-response sup-zone 02 47 sup-short-reset 60 02 47 sup-message 01 ~FIRE ALARM STROBES - A~ normal-response sup-zone 02 48 sup-short-reset 60 02 48 sup-message 01 ~FIRE ALARM STROBES - B~ normal-response sup-zone 02 49 sup-short-reset 60 02 49 sup-message 01 ~OUTSIDE HORN/LIGHT~ sup-zone 02 50 sup-short-reset 60 02 50 sup-message 01 ~OXYGEN STROBES RM. B03 & 155~ normal-response sup-zone 02 51 sup-short-reset 60 02 51 sup-message 01 ~OXYGEN STROBE RM. 237~ normal-response sup-zone 02 52 sup-short-reset 60 02 52 sup-message 01 ~OXYGEN STROBE RM. 239~ normal-response sup-zone 02 53 sup-short-reset 60 02 53 sup-message 01 ~OXYGEN STROBE RM. 148~ normal-response sup-zone 02 54 sup-short-reset 60 02 54 sup-message 01 ~OXYGEN HORN RM. BO3/155~ normal-response sup-zone 02 55 sup-short-reset 60 02 55 sup-message 01 ~OXYGEN HORN RM. 237~ normal-response sup-zone 02 56 sup-short-reset 60 02 56 sup-message 01 ~OXYGEN HORN RM. 239~ normal-response sup-zone 02 57 sup-short-reset 60 02 57 sup-message 01 ~OXYGEN HORN RM. 148~ normal-response sup-zone 02 58 sup-message 01 ~PULSE HORN START~ normal-response sup-zone 02 59 sup-message 01 ~AUX. POWER SUPPLY - GROUND FAULT~ normal-response sup-zone 02 60 sup-message 01 ~AUX. POWER SUPPLY - TROUBLE~ sup-zone 02 61 sup-message 01 ~STROBE POWER RISER~ normal-response sup-zone 02 62 sup-message 01 ~HORN POWER RISER~ normal-response alarm-zone 02 63 sup-open-set 50 10 24 alarm-set 50 02 39 alarm-action 5000 alarm-action 5002 alarm-message 01 ~OXYGEN SENSOR - RM. 239 - NORTH WALL~ normal-response sup-zone 02 64 sup-short-reset 60 02 64 sup-message 01 ~OXY STROBE FOR ROOM 155~ normal-response alarm-zone 02 65 sup-open-set 50 10 24 alarm-set 50 02 39 alarm-action 5000 alarm-action 5002 alarm-message 01 ~OXYGEN SENSOR - RM. 239 - SOUTH WALL~ normal-response sup-zone 02 71 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH - BASEMENT VAULT~ normal-response alarm-zone 02 72 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-set 50 10 09 alarm-message 01 ~ALARM SWITCH - BASEMENT VAULT~ normal-response alarm-zone 02 73 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-set 50 10 02 alarm-message 01 ~WATER FLOW SWITCH - 3RD FLOOR MECH ROOM~ sup-zone 02 74 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH - 3RD FLOOR MECH ROOM~ normal-response alarm-zone 02 75 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-set 50 10 01 alarm-set 50 10 09 alarm-set 50 10 06 alarm-set 50 10 03 alarm-message 01 ~WATER FLOW SWITCH - VAULT~ normal-response sup-zone 02 76 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH - VAULT~ normal-response alarm-zone 02 77 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-set 50 10 04 alarm-message 01 ~WATER FLOW SWITCH - NORTH 2ND FLOOR~ normal-response sup-zone 02 78 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH - NORTH 2ND FLOOR~ normal-response alarm-zone 02 79 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-set 50 10 07 alarm-message 01 ~WATER FLOW SWITCH - NORTH 1ST FLOOR~ normal-response sup-zone 02 80 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH - NORTH 1ST FLOOR~ normal-response alarm-zone 02 81 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-set 50 10 04 alarm-set 50 10 07 alarm-message 01 ~WATER FLOW SWITCH - SOUTH 1ST & 2ND FLRS~ normal-response sup-zone 02 82 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH -SOUTH 1ST & 2ND FLOORS~ normal-response alarm-zone 02 83 sup-open-set 50 10 20 alarm-action 0104 alarm-set 50 10 21 alarm-message 01 ~WATER FLOW SWITCH - MAIN~ normal-response sup-zone 02 84 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH - MAIN~ normal-response alarm-zone 03 01 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR CORRIDOR 160~ normal-response alarm-zone 03 02 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR CORRIDOR 160~ normal-response alarm-zone 03 03 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 155 ~ alarm-zone 03 04 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 155~ normal-response alarm-zone 03 05 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 157~ normal-response alarm-zone 03 06 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 158~ normal-response alarm-zone 03 07 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 159~ normal-response alarm-zone 03 08 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 175~ normal-response alarm-zone 03 09 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 175A~ normal-response alarm-zone 03 10 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR CORRIDOR 160~ normal-response alarm-zone 03 11 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR CORRIDOR 160~ normal-response alarm-zone 03 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 167~ normal-response alarm-zone 03 13 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 165~ normal-response alarm-zone 03 14 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 162~ normal-response alarm-zone 03 15 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 167~ normal-response alarm-zone 03 16 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 164~ normal-response alarm-zone 03 17 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR 2ND FLR CORRIDOR NORTH~ normal-response alarm-zone 03 18 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR 2ND FLR CORRIDOR NORTH~ normal-response alarm-zone 03 19 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 242~ normal-response alarm-zone 03 20 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 242~ alarm-zone 03 21 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 243~ normal-response alarm-zone 03 22 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 243~ normal-response alarm-zone 03 23 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 244~ normal-response alarm-zone 03 24 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 245~ normal-response alarm-zone 03 25 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 246 N.E.~ normal-response alarm-zone 03 26 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 246 S.E.~ normal-response alarm-zone 03 27 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 246 N.W.~ normal-response alarm-zone 03 28 sup-open-set 50 10 12 alarm-action 2001 alarm-message 01 ~SMOKE DETECTOR ROOM 246 S.W.~ alarm-zone 03 29 alarm-action 2003 alarm-message 01 ~THERMAL DETECTOR ROOM 247~ normal-response alarm-zone 03 30 sup-open-set 50 10 12 alarm-action 3000 alarm-action 4000 alarm-message 01 ~SMOKE DETECTOR - VAULT TOP OF ELEV SHAFT~ normal-response alarm-zone 03 31 alarm-action 3002 sup-open-set 50 10 14 alarm-message 01 ~THERMAL DETECTOR - VAULT ROOM 304~ normal-response alarm-zone 03 32 sup-open-set 50 10 12 alarm-action 3000 alarm-action 4000 alarm-message 01 ~SMOKE DETCTOR - VAULT 3RD FLR ELEV LOBBY~ normal-response alarm-zone 03 33 sup-open-set 50 10 14 alarm-action 3002 alarm-message 01 ~THERMAL DETECTOR - VAULT ROOM 303~ normal-response alarm-zone 03 34 alarm-action 3000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR RM. 305~ normal-response alarm-zone 03 35 alarm-action 3000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300~ normal-response alarm-zone 03 36 alarm-action 3000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300~ alarm-zone 03 37 alarm-action 3000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300~ normal-response alarm-zone 03 38 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 39 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 40 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 41 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 42 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 43 alarm-action 3000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300~ normal-response alarm-zone 03 44 alarm-action 3000 sup-open-set 50 10 12 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300~ normal-response alarm-zone 03 45 alarm-action 3000 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300~ normal-response alarm-zone 03 46 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 47 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 48 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 49 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 50 sup-open-set 50 10 12 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR - ROOM 301~ normal-response alarm-zone 03 51 sup-open-set 50 10 12 alarm-action 3006 alarm-action 4004 alarm-message 01 ~SMOKE DETECTOR - 3RD FLR S ELEV LOBBY~ normal-response alarm-zone 03 52 sup-open-set 50 10 12 alarm-action 3006 alarm-action 4004 alarm-message 01 ~SMOKE DETECTOR - TOP OF S ELEV SHAFT~ normal-response alarm-zone 03 53 alarm-action 3006 alarm-message 01 ~SMOKE DETECTOR THIRD FL. SOUTH~ normal-response alarm-zone 03 54 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~THERMAL DETECTOR KITCHEN/VENDING RM 168~ normal-response alarm-zone 03 55 alarm-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR BREAK ROOM 169~ normal-response alarm-zone 03 56 sup-open-set 50 10 12 alarm-action 1001 alarm-message 01 ~SMOKE DETECTOR ROOM 180~ normal-response alarm-zone 03 59 alarm-action 2001 sup-open-set 50 10 12 alarm-message 01 ~Heat Det. Rm 243A Walk-In cooler~ normal-response alarm-zone 04 01 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION VESTIBULE ROOM 175~ normal-response alarm-zone 04 02 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION CORRIDOR 160~ normal-response alarm-zone 04 03 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION CORRIDOR 160 EXIT~ normal-response alarm-zone 04 04 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION 1ST FLR STAIRWELL EXIT~ alarm-zone 04 05 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION ROOM 169~ normal-response alarm-zone 04 06 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION ROOM 163 NORTH~ normal-response alarm-zone 04 07 sup-open-set 50 10 18 alarm-action 1005 alarm-message 01 ~MANUAL STATION ROOM 163 SOUTH~ normal-response alarm-zone 04 08 sup-open-set 50 10 18 alarm-action 2005 alarm-message 01 ~MANUAL STATION 2ND FLR STAIRWELL~ normal-response alarm-zone 04 09 sup-open-set 50 10 18 alarm-action 3004 alarm-message 01 ~MANUAL STATION - VAULT ROOM 303~ normal-response alarm-zone 04 10 alarm-set 50 10 01 alarm-set 50 10 11 sup-open-set 50 10 10 alarm-action 0104 alarm-message 01 ~SMOKE DETECTOR - VAULT ROOM 300 (HSSD)~ normal-response alarm-zone 04 12 sup-open-set 50 10 18 alarm-action 3010 alarm-message 01 ~MANUAL STATION - ROOM 301~ normal-response alarm-zone 04 14 sup-open-set 50 10 18 alarm-action 3004 alarm-message 01 ~MANUAL STATION - VAULT ROOM 305~ alarm-zone 04 15 sup-open-set 50 10 18 alarm-action 3010 alarm-message 01 ~MANUAL STATION - 3RD FLR S ELEV LOBBY~ normal-response alarm-zone 04 16 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-1 SUPPLY~ normal-response alarm-zone 04 17 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-1 RETURN~ normal-response alarm-zone 04 18 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-4 SUPPLY~ normal-response alarm-zone 04 19 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-4 RETURN~ normal-response alarm-zone 04 20 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-5 SUPPLY~ normal-response alarm-zone 04 21 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-5 RETURN~ normal-response alarm-zone 04 22 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-3 SUPPLY~ alarm-zone 04 23 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-3 RETURN~ normal-response alarm-zone 04 24 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-2 SUPPLY~ normal-response alarm-zone 04 25 sup-open-set 50 10 16 alarm-action 3012 alarm-message 01 ~DUCT DETECTOR - AHU-2 RETURN~ normal-response alarm-zone 04 26 alarm-action 6500 alarm-action 6502 alarm-message 01 ~OXYGEN SENSOR ROOM 155~ normal-response sup-zone 04 30 sup-message 01 ~CONTROL RELAY FAN SHUTDOWN AHU-8 RM 180~ normal-response sup-zone 04 31 sup-short-set 50 04 30 sup-message 01 ~Duct Det AHU-8 Supply Rm 180~ normal-response sup-zone 04 32 sup-short-set 50 04 30 sup-message 01 ~Duct Det AHU-8 Retrun Rm 180~ normal-response sup-zone 04 63 sup-short-action 9005 sup-message 01 ~ANNUNCIATOR LAMP TEST BUTTON~ normal-response sup-zone 04 64 sup-message 01 ~ANNUNCIATOR 24VDC SUPERVISION~ normal-response sup-zone 04 71 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH FIRST FLOOR~ alarm-zone 04 72 sup-open-set 50 10 20 alarm-set 50 10 21 alarm-set 50 10 08 alarm-action 0104 alarm-message 01 ~WATER FLOW FIRST FLOOR~ normal-response sup-zone 04 73 sup-short-set 50 10 23 sup-open-set 50 10 22 sup-message 01 ~TAMPER SWITCH SECOND FLOOR~ normal-response alarm-zone 04 74 sup-open-set 50 10 20 alarm-set 50 10 21 alarm-set 50 10 08 alarm-action 0104 alarm-message 01 ~WATER FLOW SECOND FLOOR~ normal-response sup-zone 04 75 sup-message 01 ~BUILDING FIRE ALARM RELAY OUTPUT~ normal-response alarm-zone 04 80 alarm-action 6500 alarm-action 6502 alarm-message 01 ~ROOM 155 OXYGEN ALARM~ normal-response switch-zone 10 04 switch-message 01 ~~ normal-response switch-zone 10 08 switch-message 01 ~~ normal-response switch-zone 10 17 switch-message 01 ~~ normal-response switch-zone 10 24 switch-message 01 ~~ priority-response sup-zone 10 97 sup-short-action 9002 sup-message 01 ~Channel 1 Communications fault~ priority-response sup-zone 10 99 sup-message 01 ~SAN POWER SUPPLY OR INTERNAL FAULT~