Attchmnt 1 WTP Amndmnt 5.doc

DOC document 31 KB Posted

Attached to
Construct Water Treatment Plant
Solicitation number
AG-32KW-S-09-0231
Issued by

About this file

Attachment 1 Q A

View the file

Other files

File Type Posted
CvrPg Amendment5 WaterTrmtPlnt.pdf PDF
CvrPg Amendment4 WaterTrmtPlnt.pdf PDF
Attch1WageRateHidalgoTX.doc DOC document
CvrPg Amendment3 WaterTrmtPlnt.pdf PDF
Plan Holders List —
Attachment 3.pdf PDF
Attachment 1.pdf PDF
Attachment 2 .doc DOC document
Solicitation Cover Pages1-3S-09-02314Water Trmt.pdf PDF
Attch1WageRateHidalgoTX.doc DOC document
Atch2-BidBondMAB-WTP.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation No.: AG-32KW-S-09-0231

Amendment #05 Attachment #1

QUESTIONS AND ANSWERS

PROJECT: USDA, MOORE AIR BASE WATER TREATMENT PLANT

Moore Air Base, Edinburg, TX

General

This is a tax exempt project. Contractors will not be required to pay sales tax on this project.

The Government will make a determination of the successful Bidder based on Best Value. Proposers may submit suggestions on cost effective alternatives to the bid documents.

Sheet 23 of the Drawings shows Alternate No. 1 for a larger (Minimum 44,000 gallon) Storage Tank. Proposers shall submit additional cost information for this Alternate.

Specifications Page 17100-2 1.4 Requires Project wide loop drawing submittal. Since the equipment specified is Siemens, the standard Siemens submittal acceptable.

Page 17520-5 Item 3.3 C. implies a factory witnessed test. A factory witnessed test is not required; however, a certificate of testing is required.

Plans Sheet 7: the scale should be 1”= 20’ not 1” = 40’

Sheet 7: the high service discharge line should read 6” not 4”

Sheet 14: the drainwell with cover is 21” not 20”

Sheet 15: the 6” PVC sanitary sewer line should read 4”

Sheet 17: in Mech. Room 106, “A/C” should be “W/H”

Sheet 17: Acoustical ceiling is to be place in the office as shown. All other ceiling areas are to be 5/8” CDX plywood.

Sheet 22: the transfer line feeding the ground storage tank should be 4” not 6”