Addendum_2_Drawings.pdf
PDF 7 MB Posted
- Attached to
- Solid Waste Truck Wash Replacement (Rebid)
- Solicitation number
- 23-0021-SW rebid
- Issued by
- Pinellas County, Florida
About this file
File Summary: Addendum 2 Drawings for Solid Waste Truck Wash Replacement Project
Addendum 2 Drawings is a set of technical drawings prepared by Ardurra, Inc. for the City of Clearwater, Florida, Public Works Department related to the Solid Waste Truck Wash Replacement project (Job No. 2024-0578-00). The drawings document the site plan, electrical infrastructure, power distribution, and control systems for both the manual truck wash bay and the automatic truck wash system designated as an additive alternate. The project involves installation of two truck wash facilities with associated electrical equipment, including seven pole lights with security cameras, conduit systems for power and communication, handholes, pull boxes, and comprehensive electrical connections. The electrical design includes a 30 KVA transformer upgrade, dual-channel concrete poles with separated power and CCTV conduit systems, lighting panels, receptacles, disconnects, and control equipment. The site utilizes existing fuel storage and materials recovery facilities, with temporary impact zones defined for utility construction, paving, and striping activities. Contractor accessibility is provided through Sunshine Drive or Logan Street, and the design incorporates safety provisions such as maintaining 7.5 feet minimum distance from overhead electrical lines per NESC or Duke Electric standards. The drawings were initially drawn June 15, 2026, reviewed and approved by Christopher F. Kuzler, P.E. (License #45534) and Agata A. Ristow, P.E. (License #89628), with Addendum 2 issued July 21, 2026, and final revision dated July 28, 2026.
The electrical power and control cable schedules specify extensive interconnections between the truck wash systems and support equipment, including pre-soak pumps, reverse osmosis water pumps, high-pressure water pumps, and wash management system pedestals. Cables range from #14 gauge to #4/0 gauge depending on application, with conduit sizes from 1 inch to 2.5 inches. The design notes indicate that cameras, cabling, and security systems are to be installed by others (the city contractor), while power conductors for the camera system and all truck wash equipment connections shall be provided by the electrical contractor. The contractor is responsible for sizing all site handholes and ensuring proper grounding with impedance not exceeding 5 ohms. The additive alternate design specifications include provisions for a designated duct bank to be installed last and the requirement for two spare 2-inch conduits for future camera system expansion. The design is based on NS Wash Corporation automatic truck wash systems, with a note that contractors selecting alternate vendors must provide all necessary cables, conduits, updated breaker sizes, miscellaneous equipment, and complete record drawings in CAD format.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APP. R/W LINE TYP.
AP
P.
R /W
L
IN
E
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
PROPOSED AUTOMATED
TRUCK WASH (TYP.)
EX. MONITORING
WELL (TYP.)
CONTRACTOR TO UTILIZE
SUNSHINE DR. OR LOGAN ST.
FOR CONSTRUCTION ACCESSIBILITY
PROPOSED MANUAL
TRUCK WASH
EXISTING FUEL STORAGE
FACILITY
EX. MATERIALS
RECOVERY FACILITY
PROPOSED AUTOMATED TRUCK WASH (TYP.)
(ADDITIVE ALTERNATE)
TEMPORARY IMPACT ZONE UNDER (BASE BID)
FUEL TANK ACCESS ZONE
ADDITIVE ALTERNATETEMPORARY IMPACT TO EX MANHOLE
(ADDITIVE ALTERNATE)
C S X R A I L R O A D R / W
N . H
ER
CU
LE
S
AV
E.
THIS LAY-DOWN OR OFFICE AREA MAY
ONLY BE UTILIZED IF THE ADDITIVE
ALTERNATE IS NOT ACCEPTED
BID DOCUMENTS
RECORD DRAWINGS
SURVEYED BY:
APPROVED BY:
REVIEWED BY:
PROJECT ENGINEER
DRAWN BY:
DATE
DATE
REVISION BY DATE
CALL 811
SHEET NO.:
CONTRACT NO.: DATE DRAWN:
DESIGNED BY:
SURVEYED BY:
APPROVED BY
HORIZ.
DRAWN BY:
VERT.
SCALE:DWG NAME: FIELD BOOK:
CHECKED BY:
DATE
JOB NO.:
INVESTIGATE BEFORE YOU EXCAVATE
SUNSHINE STATE
ONE CALL
OF FLORIDA
www.callsunshine.com
(800) 432-4770
MIN. 48 HOURS
BEFORE YOU EXCAVATE
05/29/261 BID DOCUMENTS
07/21/262 ADDENDUM #2
CFK
CFK
G0.05
4921 Memorial Highway One Memorial Center, Suite 300
Tampa, Florida 33634 Phone: (813) 880-8881 www.Ardurra.com License #2610
SCALE: FEET
SCALE: FEET
C-SP.DWG
06/15/2026
MJG
2024-0578-00 CSA CFK
CHRISTOPHER F. KUZLER, P.E. 45534
LEGEND
CONTRACTOR TO MAINTAIN
UNOBSTRUCTED ACCESS
MANUAL TRUCK WASH WORK ZONE
AUTOMATIC TRUCK WASH WORK ZONE
ADDITIVE ALTERNATE
FUEL TANK ACCESS ZONE
ADDITIVE ALTERNATE
TEMPORARY IMPACT ZONE
(ONLY DURING UTILITY CONSTRUCTION
AND PAVING & STRIPING)
LAY-DOWN OR OFFICE TRAILER AREA
OFFICE TRAILER AREA
Ju ly
1, C
U se rs
\M gl ad ba ch \D
C\
AC
CD
oc s\ Ar du rr a, In c\
-0
8-
\P ro je ct F ile s\
-P ro d\
-D w gs
\C -S
P.
dw g
05/29/26CITY OF CLEARWATER, FLORIDA
PUBLIC WORKS DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
C:\Users\Mgladbach\DC\ACCDocs\Ardurra, Inc\2024-0578-00\Project Files\03-Prod\03-Dwgs\C-SP.dwg
DT
W
DT
W
HW
HW
DT
W
DT
W
GA
S
DW
DT
W
DT
W
RWM RWM RWM
RW
M
RW
M
RW
M
RW
M
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
HANDHOLE-1
MANUAL TRUCK WASH BAY
SEE SHEET E1.03
P-PW01
P-PW02
P-PW03
P-LTG300A
P-LTG300B
P-REC300
P-SECCAM3
D POLE
LIGHT 1
P-SLP01B
P-SECCAM1
P-SECCAM2
P-SLP01B
P-SECCAM1
P-SECCAM2
RUN 2" CONDUIT
UNDERGROUND AND UP
CANOPY STRUCTURE TO
A GANG BOX AT EACH
CAMERA LOCATION.
UPGRADED
UTILITY XFMR
P-UTIL01
P-XFMR100
P-130
2" CNDT
MANUAL TRUCK WASH ROOM
SEE SHEETS E1.01 & 1.02
12" X 12" X 8"
NEMA 4X SS
WALL MOUNTED
PULLBOX @ 4' AG
P-LTG300A
P-LTG300B
P-REC300
P-PW01
P-PW02
P-PW03
BID DOCUMENTS
RECORD DRAWINGS
SURVEYED BY:
APPROVED BY:
REVIEWED BY:
PROJECT ENGINEER
DRAWN BY:
DATE
DATE
REVISION BY DATE
CALL 811
SHEET NO.:
CONTRACT NO.: DATE DRAWN:
DESIGNED BY:
SURVEYED BY:
APPROVED BY
HORIZ.
DRAWN BY:
VERT.
SCALE:DWG NAME: FIELD BOOK:
CHECKED BY:
DATE
JOB NO.:
INVESTIGATE BEFORE YOU EXCAVATE
SUNSHINE STATE
ONE CALL
OF FLORIDA
www.callsunshine.com
(800) 432-4770
MIN. 48 HOURS
BEFORE YOU EXCAVATE
CITY OF CLEARWATER, FLORIDA
PUBLIC WORKS DEPARTMENT
100 S. MYRTLE AVE.
07/21/261 ADDENDUM #2
AAR
E0.04
One Memorial Center, Suite 300
Tampa, Florida 33634 Phone: (813) 880-8881 www.Ardurra.com License #2610
SCALE: FEET
SCALE: FEET
E-ESP.DWG
11/08/2024 VAW
2024-0578-00 VAW AAR
Ju ly
8, C
U se rs
\c av er et t\
DC
\A
CC
Do cs
\A rd ur ra
, I nc
\2
4-
-0
0\ Pr oj ec t F ile s\
-P ro d\
-D w gs \E le c\
E-
ES
P.
dw g
POLE LIGHT 2
D
D
D
POLE LIGHT 6
D
D
D
06/15/2026AGATA A. RISTOW, P.E. 89628
POLE LIGHT 3
POLE LIGHT 7
POLE LIGHT 5
POLE LIGHT 4
CAMERA CAMERA
CAMERA
P-SLP01B
P-SECCAM2
P-SLP01B
P-SLP01B
P-SECCAM2
P-SLP01B
06/15/260 BID DOCUMENTS AAR
P-SLP01B
P-SECCAM2 P-SLP01B
P-SECCAM2
KEYED NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR SIZING ALL SITE HANDHOLES.
2. CAMERA SYSTEM AND ALL ASSOCIATED CONTROL WIRING, CONDUITS AND BOXES
INSTALLED BY THE CITY CONTRACTOR. POWER CONDUCTORS FOR CAMERA SYSTEM SHALL
BE BY ELECTRICAL CONTRACTOR, RUN IN UNDERGROUND CONDUITS INSTALLED BY CITY
CONTRACTOR.
3. SEE SHEET E8.03 DETAIL S1 "EQUIPMENT RACK."
4. TRUCK WASH CONTRACTOR TO SET LIGHT POLES AND PULL ELECTRICAL WIRES. TRUCK
WASH CONTRACTOR TO ENSURE BASE OF LIGHT POLES ARE AT LEAST 7.5' AWAY FROM
EXISTING OVERHEAD ELECTRICAL LINES PER NESC OR THE MINIMUM DISTANCE SPECIFIED
BY DUKE ELECTRIC STANDARDS, WHICHEVER IS FURTHER.
GENERAL NOTES:
1. POLES SHALL BE DUAL-CHANNEL WITH CONDUITS KEPT UNDERGROUND
TO NEARBY PULL BOXES. NO CONDUIT SHALL RUN UP THE POLES UNLESS
NOTED OTHERWISE.
2. LIGHTING POWER CONDUIT SYSTEM SHALL FEED UP CHANNEL IN DUAL
CHANNEL CONCRETE POLES IN ACCORDANCE WITH NEC.
3. CCTV CONDUIT SYSTEM SHALL BE INSTALLED IN SEPARATE CHANNEL
FROM POWER CONDUCTORS IN DUAL CHANNEL CONCRETE POLES.
4. REFER TO CABLE SCHEDULES SHEET E3.01 FOR CONNECTIONS BETWEEN
EQUIPMENT.
5. ENCASE DUCTBANK IN CONCRETE UNDER ROADWAY AREAS SUBJECT TO
VEHICULAR TRAFFIC. EXTEND CONCRETE 5' BEYOND ROADWAYS.
DUCTBANK IN NON VEHICULAR TRAFFIC AREAS CAN BE DIRECT BURIED.
6. SECURITY CAMERAS AND CABLING TO BE INSTALLED BY OTHERS.
CONTRACTOR TO REFER TO LIGHTING SCHEDULE MOUNTING HEIGHTS.
7. REFER TO LIGHTING SCHEDULE SHEET E3.02 FIXTURE D FOR SITE POLE
AND POLE LIGHT INFORMATION.
AutoCAD SHX Text M
AutoCAD SHX Text
SOLID WASTE TRUCK WASH REPLACEMENT
AutoCAD SHX Text
ELECTRICAL OVERALL SITE PLAN
S
DT
W
DT
W
HW
HW
DT
W
DT
W
GA
S
DW
DT
W
DT
W
RWM RWM RWM
RW
M
RW
M
RW
M
RW
M
S
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
S
HANDHOLE-1
MANUAL TRUCK WASH BAY
SEE SHEET E1.03
P-PW01
P-PW02
P-PW03
P-LTG300A
P-LTG300B
P-REC300
P-SECCAM3
D POLE
LIGHT 1
P-SLP01B
P-SECCAM1
P-SECCAM2
P-SLP01B
P-SECCAM1
P-SECCAM2
RUN 2" CONDUIT
UNDERGROUND AND UP
CANOPY STRUCTURE TO
A GANG BOX AT EACH
CAMERA LOCATION.
UPGRADED
UTILITY XFMR
P-UTIL01
P-XFMR100
P-130
2" CNDT
MANUAL TRUCK WASH ROOM
SEE SHEETS E1.01 & 1.02
12" X 12" X 8"
NEMA 4X SS
WALL MOUNTED
PULLBOX @ 4' AG
P-LTG300A
P-LTG300B
P-REC300
P-PW01
P-PW02
P-PW03
BID DOCUMENTS
RECORD DRAWINGS
SURVEYED BY:
APPROVED BY:
REVIEWED BY:
PROJECT ENGINEER
DRAWN BY:
DATE
DATE
REVISION BY DATE
CALL 811
SHEET NO.:
CONTRACT NO.: DATE DRAWN:
DESIGNED BY:
SURVEYED BY:
APPROVED BY
HORIZ.
DRAWN BY:
VERT.
SCALE:DWG NAME: FIELD BOOK:
CHECKED BY:
DATE
JOB NO.:
INVESTIGATE BEFORE YOU EXCAVATE
SUNSHINE STATE
ONE CALL
OF FLORIDA
www.callsunshine.com
(800) 432-4770
MIN. 48 HOURS
BEFORE YOU EXCAVATE
CITY OF CLEARWATER, FLORIDA
PUBLIC WORKS DEPARTMENT
100 S. MYRTLE AVE.
07/21/261 ADDENDUM #2
E0.04A
One Memorial Center, Suite 300
Tampa, Florida 33634 Phone: (813) 880-8881 www.Ardurra.com License #2610
SCALE: FEET
SCALE: FEET
E-ESP.DWG
11/08/2024 VAW
2024-0578-00 VAW AAR
Ju ly
8, C
U se rs
\c av er et t\
DC
\A
CC
Do cs
\A rd ur ra
, I nc
\2
4-
-0
0\ Pr oj ec t F ile s\
-P ro d\
-D w gs \E le c\
E-
ES
P.
dw g
POLE LIGHT 2
D
D
D
POLE LIGHT 6
D
D
D
KEYED NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR SIZING ALL SITE HANDHOLES.
2. CAMERA SYSTEM AND ALL ASSOCIATED CONTROLS WIRING, CONDUITS AND BOXES
INSTALLED BY THE CITY CONTRACTOR. POWER CONDUCTORS FOR CAMERA SYSTEM SHALL
BE BY ELECTRICAL CONTRACTOR, RUN IN UNDERGROUND CONDUITS INSTALLED BY CITY
CONTRACTOR.
3. SEE SHEET E8.03 DETAIL S1 "EQUIPMENT RACK."
4. TRUCK WASH CONTRACTOR TO SET LIGHT POLES AND PULL ELECTRICAL WIRES. TRUCK
WASH CONTRACTOR TO ENSURE BASE OF LIGHT POLES ARE AT LEAST 7.5' AWAY FROM
EXISTING OVERHEAD ELECTRICAL LINES PER NESC OR THE MINIMUM DISTANCE SPECIFIED
BY DUKE ELECTRIC STANDARDS, WHICHEVER IS FURTHER.
5. IN THE EVENT THAT THE ADDITIVE ALTERNATIVE DESIGN IS CHOSEN, CITY CONTRACTOR TO
INSTALL DESIGNATED DUCT BANK LAST.
6. DESIGNATED DUCT BANK ONLY TO BE INSTALLED IF THE ADDITIVE ALTERNATIVE DESIGN IS
CHOSEN.
7. CONTRACTOR TO RUN 2 SPARE 2" CONDUITS FOR CAMERA SYSTEM.
8. INSTALL HANDHOLE IN PROXIMITY TO PEDESTAL.
GENERAL NOTES:
1. POLES SHALL BE DUAL-CHANNEL WITH CONDUITS KEPT UNDERGROUND
TO NEARBY PULL BOXES. NO CONDUIT SHALL RUN UP THE POLES UNLESS
NOTED OTHERWISE.
2. LIGHTING POWER CONDUIT SYSTEM SHALL FEED UP CHANNEL IN DUAL
CHANNEL CONCRETE POLES IN ACCORDANCE WITH NEC.
3. CCTV CONDUIT SYSTEM SHALL BE INSTALLED IN SEPARATE CHANNEL
FROM POWER CONDUCTORS IN DUAL CHANNEL CONCRETE POLES.
4. REFER TO CABLE SCHEDULES SHEET E3.01 FOR CONNECTIONS BETWEEN
EQUIPMENT.
5. ENCASE DUCTBANK IN CONCRETE UNDER ROADWAY AREAS SUBJECT TO
VEHICULAR TRAFFIC. EXTEND CONCRETE 5' BEYOND ROADWAYS.
DUCTBANK IN NON VEHICULAR TRAFFIC AREAS CAN BE DIRECT BURIED.
6. SECURITY CAMERAS AND CABLING TO BE INSTALLED BY OTHERS.
CONTRACTOR TO REFER TO LIGHTING SCHEDULE MOUNTING HEIGHTS.
7. REFER TO LIGHTING SCHEDULE SHEET E3.02 FIXTURE D FOR SITE POLE
AND POLE LIGHT INFORMATION.
8. 4X-EB TYP ABBREVIATION FOR NEMA 4X ELECTRICAL BOX.
06/15/2026AGATA A. RISTOW, P.E. 89628
POLE LIGHT 3
POLE LIGHT 7
POLE LIGHT 5
POLE LIGHT 4
CAMERA
P-SLP01B
P-SECCAM2
P-SLP01B
P-SLP01B
P-SECCAM2
P-SLP01B
06/15/260 BID DOCUMENTS AAR
AUTOMATIC TRUCK WASH BAY
SEE SHEET E2.01 & E2.02
HANDHOLE-2
P-P100 P-P110 P-P120
P-LTG400A
P-REC400
P-ATCR001
P-ATWR001
P-ATAC001
P-ATBP001
P-WMSP001
P-WMSP002
IT CABLES
IT CABLES
P-P100 P-P110 P-P120
P-LTG400A
P-REC400
P-ATCR001
P-ATWR001
P-ATAC001
P-ATBP001
P-WMSP001
P-WMSP002
P-SLP01B
P-SECCAM2
P-SLP01B
P-SECCAM2
12" X 12" X 8"
NEMA 4X SS
WALL MOUNTED
PULLBOX @ 4' AG
EXISTING
HANDHOLE-3
HANDHOLE-4
HANDHOLE-5
HANDHOLE-6
IT CABLES
IT CABLES
AutoCAD SHX Text M
AutoCAD SHX Text
SOLID WASTE TRUCK WASH REPLACEMENT
ELECTRICAL OVERALL SITE PLAN ADDITIVE ALTERNATE
P-VWCP02
WTCP-01100A DISCONNECT
P-120
P-WTCP01
VWCP-02
C a
C a
C a
C a
C a
Ca C a
C a
C a
C a
C a
C a
C a
C a
C a
C a
C C aa
C a
C a a
LVP-100: CKT 12 LVP-100: CKT 14
LVP-100: CKT 18
LVP-100: CKT 16 LVP-100: CKT 7LVP-100: CKT 7
LVP-100 CKT: 8
VWCP-01
VWCP-02
P-PSAWP2A
M
M
P-PSAWP1A
VWCP-01
P-PSAWP1B
P-PSAWP2B
PRE-SOAK
PUMP NO. 1
PRE-SOAK
PUMP NO. 2
VWCP-01
P-ROWP1A
M
M
P-ROWP2A
VWCP-02
P-ROWP1B
P-ROWP2B
RO-WP
PUMP NO. 1
RO-WP
PUMP NO. 2
M
M
P-HPWP1A
VWCP-01
P-HPWP2A
VWCP-02
P-HPWP1B
P-HPWP2B
HP-WP PUMP NO. 1
HP-WP PUMP NO. 2
M
M
DAB-WP
PUMP NO. 1
DAB-WP
PUMP NO. 2
P-DABWP2A
VWCP-02
VWCP-01
P-DBAWP1A
P-DBAWP2B
P-DBAWP1B
DAAU-WP
PUMP NO. 1
DAAU-WP
PUMP NO. 2
M
M
P-DAUWP1A
VWCP-02
P-DAUWP2A
P-DAUWP2BP-DAUWP1B
WTCP-01
P-RO10KA
P-RO10KB
VWCP-01
WTCP-01
P-AC5A
P-AC5BP-110
LVP-100: CKT 7
DP-TW-001
VWCP-01
LVP-100
C-WTCP11
C-WTCP21
P-WMSP002
P-WMSP001
P-100
DP-TW-001
100A DISCONNECT
P-VWCP01
DP-TW-001
LC-2
P-LTG400A
HANDHOLE-4
HANDHOLE-6
HANDHOLE-5
12" X 12" X 8"
NEMA 4X SS
WALL MOUNTED
PULLBOX @ 4' AG
RECORD DRAWINGS
SURVEYED BY:
APPROVED BY:
REVIEWED BY:
PROJECT ENGINEER
DRAWN BY:
DATE
DATE
REVISION BY DATE
CALL 811
SHEET NO.:
CONTRACT NO.: DATE DRAWN:
DESIGNED BY:
SURVEYED BY:
APPROVED BY
HORIZ.
DRAWN BY:
VERT.
SCALE:DWG NAME: FIELD BOOK:
CHECKED BY:
DATE
JOB NO.:
INVESTIGATE BEFORE YOU EXCAVATE
SUNSHINE STATE
ONE CALL
OF FLORIDA
www.callsunshine.com
(800) 432-4770
MIN. 48 HOURS
BEFORE YOU EXCAVATE
CITY OF CLEARWATER, FLORIDA
PUBLIC WORKS DEPARTMENT
100 S. MYRTYLE AVE.
CLEARWATER, FL 33765
07/28/261 ADDENDUM 2
E2.01
One Memorial Center, Suite 300
Tampa, Florida 33634 Phone: (813) 880-8881 www.Ardurra.com License #2610
E-ESP-PWR.DWG
11/08/2024 VAW
2024-0578-00 VAW AAR
Ju ly
8, C
U se rs
\c av er et t\
DC
\A
CC
Do cs
\A rd ur ra
, I nc
\2
4-
-0
0\ Pr oj ec t F ile s\
-P ro d\
-D w gs \E le c\
E-
ES
P-
PW
R.
dw g
BID DOCUMENTSAUTOMATIC TRUCK WASH - PROPOSED POWER PLAN
ADDITIVE ALTERNATE
SCALE: 3/16" = 1' 0"
SCALE: FEET
SCALE: FEET
10.675.33
GENERAL NOTES:
1. CONTRACTOR TO REFER TO CABLE SCHEDULES AND TRUCK WASH VENDOR
DRAWINGS FOR INTERCONNECTION BETWEEN TRUCK WASH EQUIPMENT AND
FOR CONTRACTOR SUPPLIED EQUIPMENT.
2. MOTORS, METALS, STRUCTURES, TRUCK WASH EQUIPMENT, JUNCTION BOXES,
AND HANDRAILS TO BE TIED TO EXISTING SITE GROUND LOOP. IMPEDANCE TO
GROUND SHALL NOT EXCEED 5 OHMS. REFER TO SPEC 16450 "GROUNDING
AND BONDING FOR ELECTRICAL SYSTEMS."
3. SWITCHES TO BE WEATHERPROOF.
4. WASH BAY 2 CONNECTIONS TYP TO WASH BAY 1 AND ARE NOT SHOWN FOR
CLARITY.
5. DESIGN BASED ON AUTOMATIC TRUCK WASH SYSTEMS PROVIDED BY NS WASH
CORPORATION. IF THE CONTRACTOR SELECTS AN ALTERNATE VENDOR IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL NECESSARY CABLES,
CONDUITS, UPDATED BREAKER SIZES, MISCELLANEOUS EQUIPMENT, AND
PROVIDE A COMPLETE SET OF RECORD DRAWINGS IN CAD.
KEYED NOTES:
1. DEDICATED WP GFCI RECEPTACLE TO BE INSTALLED WITHIN 5 FEET OF RO 10K
SYSTEM, 4.0 WATER SOFTENER, 1 HP RO SYSTEM BOOSTER PUMP, AND 5 HP AIR
COMPRESSOR PER NS TRUCK WASH DRAWINGS.
2. WP GFCI CONVENIENCE RECEPTACLE.
06/15/2026AGATA A. RISTOW, P.E. 89628
WASH BAY 1
WASH BAY 2
06/15/260 BID DOCUMENTS AAR
GROUND TEST WELL,
TYP.
GROUND ROD, TYP.
VENDOR PROVIDED
WASH MANAGEMENT
SYSTEM PEDESTAL 1
NEMA 4X SS
WASH MANAGEMENT
SYSTEM PULL BOX
VENDOR PROVIDED
WASH MANAGEMENT
SYSTEM PEDESTAL 2
SEE CONTINUATION ON
OVERALL SITE PLAN
AutoCAD SHX Text
SOLID WASTE TRUCK WASH REPLACEMENT
ENLARGED ELECTRICAL POWER VIEW AUTOMATIC TRUCK WASH - ADDITIVE ALTERNATE - ADDITIVE ALTERNATEADDITIVE ALTERNATE
SV
SV-20FWT2
RECORD DRAWINGS
SURVEYED BY:
APPROVED BY:
REVIEWED BY:
PROJECT ENGINEER
DRAWN BY:
DATE
DATE
REVISION BY DATE
CALL 811
SHEET NO.:
CONTRACT NO.: DATE DRAWN:
DESIGNED BY:
SURVEYED BY:
APPROVED BY
HORIZ.
DRAWN BY:
VERT.
SCALE:DWG NAME: FIELD BOOK:
CHECKED BY:
DATE
JOB NO.:
INVESTIGATE BEFORE YOU EXCAVATE
SUNSHINE STATE
ONE CALL
OF FLORIDA
www.callsunshine.com
(800) 432-4770
MIN. 48 HOURS
BEFORE YOU EXCAVATE
CITY OF CLEARWATER, FLORIDA
PUBLIC WORKS DEPARTMENT
100 S. MYRTYLE AVE.
07/28/26ADDENDUM 2
E2.02
One Memorial Center, Suite 300
Tampa, Florida 33634 Phone: (813) 880-8881 www.Ardurra.com License #2610
E-OLN.DWG
11/08/2024 VAW
2024-0578-00 VAW AAR
Ju ly
8, C
U se rs
\c av er et t\
DC
\A
CC
Do cs
\A rd ur ra
, I nc
\2
4-
-0
0\ Pr oj ec t F ile s\
-P ro d\
-D w gs \E le c\
E- O
LN
.d w g
BID DOCUMENTS
AUTOMATIC TRUCK WASH PROPOSED CONTROLS PLAN
ADDITIVE ALTERNATE
SCALE: 3/16" = 1' 0"
SCALE: FEET
SCALE: FEET
10.675.33
GENERAL NOTES:
1. CONTRACTOR TO REFER TO CABLE SCHEDULES AND TRUCK WASH VENDOR
DRAWINGS FOR INTERCONNECTION BETWEEN TRUCK WASH EQUIPMENT AND
FOR CONTRACTOR SUPPLIED EQUIPMENT.
2. 4X-EB TYP ABBREVIATION FOR NEMA 4X ELECTRICAL BOX.
3. 3R-GB TYP ABBREVIATION FOR NEMA 3R GANG BOX.
4. WASH BAY 2 CONNECTIONS TYP TO WASH BAY 1 AND ARE NOT SHOWN FOR
CLARITY.
5. DESIGN BASED ON AUTOMATIC TRUCK WASH SYSTEMS PROVIDED BY NS WASH
CORPORATION. IF THE CONTRACTOR SELECTS AN ALTERNATE VENDOR IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL NECESSARY CABLES,
CONDUITS, UPDATED BREAKER SIZES, MISCELLANEOUS EQUIPMENT, AND
PROVIDE A COMPLETE SET OF RECORD DRAWINGS IN CAD.
ER-EB1
C-EREB1
ER-EB2
C-EREB2
C-WBEB11
WB-EB-1
WTCP-01
AS-1A
C-AS11BB
AS-1B
C-AS11AA
ENL-1
C-AS11A
C-AS11B
3R-GB
AS-2A
C-AS12BB
AS-2B
C-AS12AA
3R-GB
C-AS12A
C-AS12B
3R-GB
AS-3A
C-AS13BB
AS-3B
C-AS13AA
3R-GB
C-AS13A
C-AS13B
3R-GB
AS-4A
C-AS14BB
AS-4B
C-AS14AA
3R-GB
C-AS14A
C-AS14B
3R-GB
AS-5A
C-AS15BB
AS-5B
C-AS15AA
3R-GB
C-AS15A
C-AS15B3R-GB
C-ENL1
3R-GB
SV-UCW1
C-SVUCW1A
C-SVUCW1B
C-SWS11
C-SWS11
C-SWS12
C-SWS12
3R-GB
SV-UCR1
C-SVUCR1A
C-SVUCR1B
P3V-AP 1
C-P3VAP1
SV
3R-GB
C-SV20FWT1A
C-SV20FWT1B
3R-GB
C-SV20FWT2A
C-SV20FWT2B
4X-EB
SV-20FWT1
4X-EB
C-20FWT2A
C-20FWT1A
C-20FWT1B C-20FWT2B
4X-EB
3R-GB
SV
C-20ROWT1B
C-SV20ROWT1A
C-SV20ROWT1B
C-20ROWT1A
4X-EB
3R-GB
SV
C-20ROWT2B
C-SV20ROWT2A
C-SV20ROWT2BC-20ROWT2A
SV-20ROWT1
SV-20ROWT2
SV SV
SV
3R-GB
C-15FWT1A
C-15SVFWT
4X-EB
C-15FWT1A
RO-10K
SYSTEM
C-RO10KA
VWCP-02
C-WTCP11C
C-WTCP21C
4X-EB
VWCP-01
C-RO10KB
4X-EB
8660H
SMR8820
SMT8600H
C-DAA14A
C-DAA90TA
C-DAA14B
C-DAA90TB
06/15/2026AGATA A. RISTOW, P.E. 89628
VWCP-01 WTCP-01
WTCP-01
C-15SVFWT1A
WTCP-01
VWCP-01
VWCP-01 VWCP-01 VWCP-01 VWCP-01 VWCP-01
VWCP-01
VWCP-01
C-WMSP001A
C-WMSP001B
WMSP-001
WMSP-002
WASH BAY 1
C-WMSP001C
C-WMSP002C
06/15/260 BID DOCUMENTS AAR
WASH MANAGEMENT
SYSTEM PEDESTAL 1
C-SECFOCWASH MANAGEMENT
SYSTEM PULL BOX
VENDOR PROVIDED
WASH MANAGEMENT
SYSTEM PEDESTAL 2
12" X 12" X 8"
NEMA 4X SS
WALL MOUNTED
PULLBOX @ 4' AG
HANDHOLE-6
HANDHOLE-4
HANDHOLE-5
C-WMSP002A
C-WMSP002B
WASH BAY 2
SEE CONTINUATION ON
OVERALL SITE PLAN
AutoCAD SHX Text
SOLID WASTE TRUCK WASH REPLACEMENT
ENLARGED ELECTRICAL VIEW CONTROLS AUTOMATIC TRUCK WASH - ADDITIVE ALTERNATE - ADDITIVE ALTERNATEADDITIVE ALTERNATE
RECORD DRAWINGS
SURVEYED BY:
APPROVED BY:
REVIEWED BY:
PROJECT ENGINEER
DRAWN BY:
DATE
DATE
REVISION BY DATE
CALL 811
SHEET NO.:
CONTRACT NO.: DATE DRAWN:
DESIGNED BY:
SURVEYED BY:
APPROVED BY
HORIZ.
DRAWN BY:
VERT.
SCALE:DWG NAME: FIELD BOOK:
CHECKED BY:
DATE
JOB NO.:
INVESTIGATE BEFORE YOU EXCAVATE
SUNSHINE STATE
ONE CALL
OF FLORIDA
www.callsunshine.com
(800) 432-4770
MIN. 48 HOURS
BEFORE YOU EXCAVATE
CITY OF CLEARWATER, FLORIDA
PUBLIC WORKS DEPARTMENT
100 S. MYRTYLE AVE.
07/28/261 ADDENDUM 2
E3.01
One Memorial Center, Suite 300
Tampa, Florida 33634 Phone: (813) 880-8881 www.Ardurra.com License #2610
E-OLN.DWG
11/08/2024 VAW
2024-0578-00 VAW AAR
Ju ly
8, C
U se rs
\c av er et t\
DC
\A
CC
Do cs
\A rd ur ra
, I nc
\2
4-
-0
0\ Pr oj ec t F ile s\
-P ro d\
-D w gs \E le c\
E- O
LN
.d w g
BID DOCUMENTS
POWER CABLE SCHEDULE
CABLE TAG
MAX CKT
VOLTAGE (V) # OF SET
CONDUIT SIZE
(INCH) CONDUCTORS FROM TO
C-WTCP11C 24 1 1 CAT5E VWCP-01 WTCP-01
C-WBEB11 120 1 1 2#14, #14G VWCP-01 WB-EB-1 E-STOP 1-1
C-AS11A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS11AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-1 ACTIVATION SYSTEM 1A
C-AS11B 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS11BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-1 ACTIVATION SYSTEM 1B
C-ENL1 120 1 1 3#14, #14G VWCP-01 ENL-1 ENTRANCE LIGHT 1
C-SVUCW1A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-SVUCW1B 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX SV-UCW SOLENOID VALVE 1
C-AS12A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS12AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-2 ACTIVATION SYSTEM 1A
C-AS12B 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS12BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-2 ACTIVATION SYSTEM 1B
C-AS13A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS13AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-3 ACTIVATION SYSTEM 1A
C-AS13B 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS13BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-3 ACTIVATION SYSTEM 1B
C-AS14A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS14AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-4 ACTIVATION SYSTEM 1A
C-AS14B 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS14BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-4 ACTIVATION SYSTEM 1B
C-SWS11 120 1 1 6#14, #14G VWCP-01 SWS-1 SPEED WARNING SYSTEM 1-1
C-SVUCR1A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-SVUCR1B 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX SV-UCR 1.5" SOLENOID VALVE 1
C-P3VAP1 120 1 1 4#14, #14G VWCP-01 P3V-AP VALVE AIR PANEL 1
C-AS15A 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS15AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-5 ACTIVATION SYSTEM 1A
C-AS15B 120 1 1 2#14, #14G VWCP-01 NEMA 3R RATED GANG BOX
C-AS15BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-5 ACTIVATION SYSTEM 1B
C-SWS12 120 1 1 6#14, #14G VWCP-01 SWS-2 SPEED WARNING SYSTEM 1-2
C-WBEB12 120 1 1 2#14, #14G VWCP-01 WB-EB-2 E-STOP 1-2
C-WTCP21C 24 1 1 CAT5E VWCP-02 WTCP-01
C-WBEB21 120 1 1 2#14, #14G VWCP-02 WB-EB-1 E-STOP 2-1
C-AS21A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS21AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-1 ACTIVATION SYSTEM 2A
C-AS21B 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS21BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-1 ACTIVATION SYSTEM 2B
C-ENL2 120 1 1 3#14, #14G VWCP-02 ENL ENTRANCE LIGHT 2
C-SVUCW2A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-SVUCW2B 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX SV-UCW SOLENOID VALVE 2
C-AS22A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS22AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-2 ACTIVATION SYSTEM 2A
C-AS22B 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS22BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-2 ACTIVATION SYSTEM 2B
C-AS23A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS23AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-3 ACTIVATION SYSTEM 2A
C-AS23B 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS23BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-3 ACTIVATION SYSTEM 2B
C-AS24A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS24AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-4 ACTIVATION SYSTEM 2A
C-AS24B 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS24BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-4 ACTIVATION SYSTEM 2B
C-SWS21 120 1 1 6#14, #14G VWCP-02 SWS-1 SPEED WARNING SYSTEM 2-1
C-SVUCR2A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-SVUCR2B 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX SV-UCR 1.5" SOLENOID VALVE 2
C-P3VAP21 120 1 1 4#14, #14G VWCP-02 P3V-AP VALVE AIR PANEL 2-1
C-AS25A 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS25AA 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-5 ACTIVATION SYSTEM 2A
C-AS25B 120 1 1 2#14, #14G VWCP-02 NEMA 3R RATED GANG BOX
C-AS25BB 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX AS-5 ACTIVATION SYSTEM 2B
C-SWS22 120 1 1 6#14, #14G VWCP-02 SWS-2 SPEED WARNING SYSTEM 2-2
C-WBEB22 120 1 1 2#14, #14G VWCP-02 WB-EB-2 E-STOP 2-2
C-VWCP01C 24 1 1 CAT5E VWCP-01 WASH SELECTOR
C-VWCP01D 120 1 1 2#14, #14G VWCP-01 WASH SELECTOR
C-VWCP02C 24 1 1 CAT5E VWCP-02 WASH SELECTOR
C-VWCP02D 120 1 1 2#14, #14G VWCP-02 WASH SELECTOR
C-EREB1 120 1 1 2#14, #14G WTCP-01 ER-EB1 EQUIPMENT ROOM E-STOP BUTTON
C-SV20FWT1A 120 1 1 2#14, #14G WTCP-01 NEMA 3R RATED GANG BOX
C-SV20FWT1B 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX SV-20-FWT 2" SOLENOID VALVE 1
C-SV20FWT2A 120 1 1 2#14, #14G WTCP-01 NEMA 3R RATED GANG BOX
C-SV20FWT2B 120 1 1 2#14, #14G NEMA 3R RATED GANG BOX SV-20-FWT 2" SOLENOID VALVE 2
C-20FWT1A 120 1 1 4#14, #14G WTCP-01 NEMA 4X RATED ELECTRICAL BOX
C-20FWT1B 120 1 1 MFR SUPP CABLE NEMA 4X RATED ELECTRICAL BOX 20-FWT FRESH WATER TANK 1
C-20FWT2A 120 1 1 4#14, #14G WTCP-01 NEMA 4X RATED ELECTRICAL BOX
C-20FWT2B 120 1 1 MFR SUPP CABLE NEMA 4X RATED ELECTRICAL BOX 20-FWT FRESH WATER TANK 2
C-SV20ROWT1A 120 1 1 4#14, #14G WTCP-01 NEMA 3R RATED GANG BOX
C-SV20ROWT1B 120 1 1 4#14, #14G NEMA 3R RATED GANG BOX SV-20-ROWT 2" SOLENOID VALVE 1
C-SV20ROWT2A 120 1 1 4#14, #14G WTCP-01 NEMA 3R RATED GANG BOX
C-SV20ROWT2B 120 1 1 4#14, #14G NEMA 3R RATED GANG BOX SV-20-ROWT 2" SOLENOID VALVE 2
C-20ROWT1A 120 1 1 4#14, #14G WTCP-01 NEMA 4X RATED ELECTRICAL BOX
C-20ROWT1B 120 1 1 MFR SUPP CABLE NEMA 4X RATED ELECTRICAL BOX 20-ROWT RO WATER TANK 2
C-EREB2 120 1 1 2#14, #14G WTCP-01 ER-EB1 EQUIPMENT ROOM E-STOP BUTTON
C-15FWTA 120 1 1 4#14, #14G WTCP-01 NEMA 4X RATED ELECTRICAL BOX
C-15FWTB 120 1 1 MFR SUPP CABLE NEMA 4X RATED ELECTRICAL BOX 15-FWT FRESH WATER TANK 1
C-15SVFWTA 120 1 1 2#14, #14G WTCP-01 NEMA 3R RATED GANG BOX
C-15SVFWTB 120 1 1 MFR SUPP CABLE NEMA 3R RATED GANG BOX SV-15FWT 2" SOLENOID VALVE
C-RO10KA 120 1 1 2#14, #14G WTCP-01 NEMA 4X RATED ELECTRICAL BOX
C-RO10KB 120 1 1 2#14, #14G NEMA 4X RATED ELECTRICAL BOX RO-10K SYSTEM
C-DAA14A 120 1 1 2#14, #14G VWCP-01 NEMA 4X RATED ELECTRICAL BOX
C-DAA14B 120 1 1 2#14, #14G NEMA 4X RATED ELECTRICAL BOX AC EMITTER SENSOR SMT 8660H
C-DAA14AA 120 1 1 2#14, #14G VWCP-02 NEMA 4X RATED ELECTRICAL BOX
C-DAA14BB 120 1 1 2#14, #14G NEMA 4X RATED ELECTRICAL BOX AC EMITTER SENSOR SMT 8660H
C-DAA90TA 120 1 1 2#14, #14G VWCP-01 NEMA 4X RATED ELECTRICAL BOX
C-DAA90TB 120 1 1 2#14, #14G NEMA 4X RATED ELECTRICAL BOX AC RECEIVER SENSOR SMR-8820
C-DAA90TAA 120 1 1 2#14, #14G VWCP-02 NEMA 4X RATED ELECTRICAL BOX
C-DAA90TAB 120 1 1 2#14, #14G NEMA 4X RATED ELECTRICAL BOX AC RECEIVER SENSOR SMR-8820
C-WMSP001A 24 1 1 CAT 6 WASH MANAGEMENT SYSTEM PEDESTAL 1 VWCP-01
C-WMSP001B 120 1 1 20#14, #14G WASH MANAGEMENT SYSTEM PEDESTAL 1 VWCP-01
C-WMSP001C 24 1 2 CAT 6 WASH MANAGEMENT SYSTEM PEDESTAL 1 WASH MANAGEMENT SYSTEM PULL BOX
C-WMSP002A 24 1 1 CAT 6 WASH MANAGEMENT SYSTEM PEDESTAL 2 VWCP-02
C-WMSP002B 120 1 1 20#14, #14G WASH MANAGEMENT SYSTEM PEDESTAL 2 VWCP-02
C-WMSP002C 24 1 2 CAT 6 WASH MANAGEMENT SYSTEM PEDESTAL 2 WASH MANAGEMENT SYSTEM PULL BOX
CONTROL CABLE SCHEDULE
GENERAL NOTES
1. ALL NEMA 3R GANG BOXES AND NEMA 4X ELECTRICAL BOXES FOR CONNECTION TO THE INDIVIDUAL TRUCK WASH
COMPONENTS SHALL BE BY ELECTRICAL CONTRACTOR.
2. ALL DISCONNECTS WITHIN THE TRUCK WASH SYSTEM AND LISTED IN THE CABLE SCHEDULE SHALL BE PROVIDED BY
CONTRACTOR.
3. DESIGN BASED ON AUTOMATIC TRUCK WASH SYSTEMS PROVIDED BY NS WASH CORPORATION. IF THE CONTRACTOR SELECTS AN ALTERNATE VENDOR IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL NECESSARY CABLES, CONDUITS, UPDATED BREAKER SIZES, MISCELLANEOUS EQUIPMENT, AND PROVIDE A COMPLETE SET OF RECORD
DRAWINGS IN CAD.
NOTES BY SYMBOL: " "
1. CONDUITS AND CONDUCTORS ARE PART OF THE ADDITIVE ALTERNATE DESIGN.
2. CONDUITS ARE TO BE FURNISHED AND INSTALLED BY CITY CONTRACTOR. CABLES TO BE FURNISHED AND INSTALLED BY
TRUCK WASH CONTRACTOR.
06/15/2026AGATA A. RISTOW, P.E. 89628
06/15/260 BID DOCUMENTS AAR
CABLE TAG
MAX CKT
VOLTAGE (V) # OF SET
CONDUIT SIZE
(INCH) CONDUCTORS FROM TO
P-UTIL01 480 2 2.5 3#4/0, #2N UTILITY TRANSFORMER UTILITY METER
P-MCB001 480 2 2.5 3#4/0, #1G UTILITY METER MCB-001
P-DP-TW-001 480 1 2.5 3#4/0, #1G MCB-001 PANEL DP-TW-001
P-100 480 1 1.5 3#1, #8G PANEL DP-TW-001 100A DISCONNECT
P-VWCP-01 480 1 1.5 3#1, #8G 100A DISCONNECT VWCP-01
P-110 480 1 1.5 3#1, #8G PANEL DP-TW-001 100A DISCONNECT
P-VWCP-02 480 1 1.5 3#1, #8G 100A DISCONNECT VWCP-01
P-120 480 1 1 3#6, #10G PANEL DP-TW-001 30A DISCONNECT
P-WTCP01 480 1 1 3#6, #10G 30A DISCONNECT WTCP-01
P-PW01 480 1 1.5 3#4, #10G PANEL DP-TW-001 60A DISCONNECT
P-PW02 480 1 1.5 3#4, #10G PANEL DP-TW-001 60A DISCONNECT
P-PW03 480 1 1.5 3#4, #10G PANEL DP-TW-001 60A DISCONNECT
P-PW11 480 1 1 3#4, #10G 60A DISCONNECT PRESSURE WASHER 1
P-PW12 480 1 1 3#4, #10G 60A DISCONNECT PRESSURE WASHER 2
P-PW13 480 1 1 3#4, #10G 60A DISCONNECT PRESSURE WASHER 3
P-XFMR100 480 1 1.5 3#6, #10G PANEL DP-TW-001 30 KVA XFMR-100
P-LVP100 120/208 1 2 4#1, #6G 30 KVA XFMR-100 LIGHTING PANEL LVP-100
P-130 480 1 1 3#10, #10G PANEL DP-TW-001 30A DISCONNECT
P-WBPS01 480 1 1 3#10, #10G 30 A DISCONNECT WATER BOOSTER PUMP SKID
P-REC100 120 1 1 2#12, #12G LVP-100 MANUAL TRUCK WASH ROOM INTERIOR RECEPTACLES
P-REC200 120 1 1 2#12, #12G LVP-100 MANUAL TRUCK WASH ROOM EXTERIOR RECEPTACLES
P-LTG100 120 1 1 2#12, #12G LVP-100 MANUAL TRUCK WASH ROOM INTERIOR LIGHTING
P-LTG100E 120 1 1 2#12, #12G LVP-100 MANUAL TRUCK WASH ROOM INTERIOR EMERGENCYLIGHTING
P-LTG200 120 1 1 2#12, #12G LVP-100 MANUAL TRUCK WASH ROOM EXTERIOR LIGHTING
P-WHU01 120 1 1 2#12, #12G LVP-100 MANUAL TRUCK WASH ROOM WATER HEATING UNIT
P-REC300 120 1 1 2#10, #10G LVP-100 MANUAL TRUCK WASH BAY RECEPTACLES
P-REC400 120 1 1 2#6, #10G LVP-100 AUTOMATIC TRUCK WASH BAY RECEPTACLES
P-SLP01A 480 1 1 2#12, #12G PANEL DP-TW-001 LC-1
P-SLP01B 480 1 2 2#12, #12G LC-1 SITE LIGHTING
P-LTG300A 120 1 1 2#10, #10G LVP-100 MANUAL TRUCK WASH BAY LIGHTING
P-LTG300B 120 1 1 2#10, #10G LVP-100 MANUAL TRUCK WASH BAY LIGHTING
P-SLP02A 480 1 1 2#12, #12G PANEL DP-TW-001 LC-2
P-SLP02B 480 1 2 2#12, #12G LC-2 SITE LIGHTING
P-ATCR001 120 1 1 2#6, #10G LVP-100 AUTOMATIC TRUCK WASH BAY CARBON FILTER RECEPTACLE P-ATWR001 120 1 1 2#6, #10G LVP-100 AUTOMATIC TRUCK WASH BAY WATER SOFTENER RECEPTACLE P-ATAC001 120 1 1 2#6, #10G LVP-100 AUTOMATIC TRUCK WASH BAY AIR COMPRESSOR RECEPTACLE P-ATBP001 120 1 1 2#6, #10G LVP-100 AUTOMATIC TRUCK WASH BAY BOOSTER PUMP RECEPTACLE
P-LTG400A 120 1 1 2#3, #10G LVP-100 AUTOMATIC TRUCK WASH LIGHTING
P-PSAWP1A 480 1 1 3#12, #12G VWCP-01 30A DISCONNECT
P-PSAWP1B 480 1 1 3#12, #12G 30A DISCONNECT PSA-WP PRE-SOAK ARCH WATER PUMP 1
P-ROWP1A 480 1 1 3#12, #12G VWCP-01 30A DISCONNECT
P-ROWP1B 480 1 1 3#12, #12G 30A DISCONNECT RO-WP 5HP WATER PUMP 1
P-HPWP1A 480 1 1 3#8, #10G VWCP-01 60A DISCONNECT
P-HPWP1B 480 1 1 3#8, #10G 60A DISCONNECT HP-WP 30HP WATER PUMP 1
P-DABWP1A 480 1 1 3#12, #12G VWCP-01 30A DISCONNECT
P-DABWP1B 480 1 1 3#12, #12G 30A DISCONNECT DAB-WP 3HP PUMP 1
P-DAUWP1A 480 1 1 3#12, #12G VWCP-01 30A DISCONNECT
P-DAUWP1B 480 1 1 3#12, #12G 30A DISCONNECT DAAU-WP 5 HP PUMP 1
P-PSAWP2A 480 1 1 3#12, #12G VWCP-02 30A DISCONNECT
P-PSAWP2B 480 1 1 3#12, #12G 30A DISCONNECT PSA-WP PRE-SOAK ARCH WATER PUMP 2
P-ROWP2A 480 1 1 3#12, #12G VWCP-02 30A DISCONNECT
P-ROWP2B 480 1 1 3#12, #12G 30A DISCONNECT RO-WP 5HP WATER PUMP 2
P-HPWP2A 480 1 1 3#8, #10G VWCP-02 60A DISCONNECT
P-HPWP2B 480 1 1 3#8, #10G 60A DISCONNECT HP-WP 30HP WATER PUMP 2
P-DABWP2A 480 1 1 3#12, #12G VWCP-02 30A DISCONNECT
P-DABWP2B 480 1 1 3#12, #12G 30A DISCONNECT DAB-WP 3HP PUMP 2
P-DAUWP2A 480 1 1 3#12, #12G VWCP-02 30A DISCONNECT
P-DAUWP2B 480 1 1 3#12, #12G 30A DISCONNECT DAAU-WP 5 HP PUMP 2
P-RO10KA 480 1 1 3#12, #12G WTCP-01 30A DISCONNECT
P-RO10KB 480 1 1 3#12, #12G 30A DISCONNECT RO-10K SYSTEM
P-AC5A 480 1 1 3#12, #12G WTCP-01 30A DISCONNECT
P-AC5B 480 1 1 3#12, #12G 30A DISCONNECT 5HP AIR COMPRESSOR
P-WMSP001 120 1 1 2#8, #10G LVP-100 WASH MANAGEMENT SYSTEM PEDESTAL 1
P-WMSP002 120 1 1 2#8, #10G LVP-100 WASH MANAGEMENT SYSTEM PEDESTAL 2
P-SECCAM1 120 1 2 2#12, #12G LVP-100 POLE LIGHT 2 FIBER MEDIA ENCLOSURE
P-SECCAM2 120 1 2 2#12, #12G LVP-100 POLE LIGHT 5 FIBER MEDIA ENCLOSURE
P-SECCAM3 120 1 2 2#12, #12G LVP-100 MANUAL TRUCK WASH MEDIA ENCLOSURE
AutoCAD SHX Text
SOLID WASTE TRUCK WASH REPLACEMENT
PROPOSED ELECTRICAL SCHEDULES I
File details come from the government source that posted it. Updated .