The document is a set of detailed project calculations for a fire protection system installation at the Andrew Johnson National Historic Site in Greeneville, Tennessee. The calculations include hydraulic analysis for two areas: the Early Home Second Floor and the Early Home Attic, both classified as light hazard environments. The project involves installing sprinkler systems with specific flow rates, pressures, and coverage requirements, with a total of 4 sprinklers on the second floor and 6 sprinklers in the attic.

The hydraulic calculations provide comprehensive technical details including water supply analysis, pipe information, and sprinkler performance data. Each area requires different water flow rates, with the second floor needing 162.93 GPM at 43.24 psi and the attic requiring 242.06 GPM at 74.19 psi. The calculations were prepared by Hunter Simpson from the National Park Service Denver Service Center on April 26, 2023, and are part of the project with PMIS Number 311420. The analysis ensures that the fire suppression system will meet the specific water pressure and distribution requirements for protecting the historic site.

View the file

Other files for this federal contract opportunity

Other files attached to INSTALL FIRE SUPPRESSION SYSTEM, ANJO, newest first.
File Type Posted
QUESTIONS_AND_ANSWERS_0002.pdf PDF
Sol_140P5325R0008_Amd_0002.pdf PDF
Sol_140P5325R0008_Amd_0001.pdf PDF
ATTACHMENT_7_Construction_Contract_Administration.docx DOCX document
ATTACHMENT_8_-__Limitation_on_Subcontracting_Report.xlsx XLSX spreadsheet
A05_ATTACHMENT_1_Specifications_(311420).pdf PDF
ATTACHMENT_6_Past_Performance_Questionnaire.docx DOCX document
B03_ATTACHMENT_5_Wage_Rate_Determination.pdf PDF
ATTACHMENT_4_Contract_Price_Schedule_-_EH_(311420).xlsx XLSX spreadsheet
Sol_140P5325R0008.pdf PDF
A06_ATTACHMENT_2_Drawings_-_Sealed_(311420).pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ANDREW JOHNSON NATIONAL HISTORICAL

SITE

GREENEVILLE, TENNESSEE

EARLY HOME

FIRE PROTECTION SYSTEM

ANJO

PMIS Number 311420

PROJECT CALCULATIONS

NATIONAL PARK SERVICE (NPS)

DENVER SERVICE CENTER (DSC)

APRIL 26, 2023

Location:

Project Name:

Drawing Name: 22187 ANJO EH F Calculation Date:4/26/2023

Hydraulic Calculations Summary for

Design

Light Hazard

1500 SF

100 SF (typical)

Early Home Second Floor

0.10 GPM/SF

Remote Area Name:

Occupancy Classification:

Density

Area of Application:

Coverage per Sprinkler:

Type of Sprinklers Calculated:

No. of Sprinklers Calculated:

at Node:

Fire Protection Wet

N/AN/A

1100.00 GPM

0.0 galType of System:

In-rack Demand:

Hose Streams:

Volume of Dry or PreAction System:

at Node:

Type Allowance at Source

Total Water Required (including Hose Streams where applicable)

43.24 psi@162.93 GPMFROM: Water Supply at Node 1:

66.01 psiSafety Margin:

Contact Name

Address:

Phone Number:

Authority Having Jurisdiction:

Name of Designer:

Automatic Peaking Results

Notes:

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:09:27PMEarly Home Second Floor@ M.E.P.CAD, Inc.

Hunter Simpson

Andrew Johnson Historic Site - Fire Suppression Early Home

Hydraulic Graph

Water Supply

Node: 1

Job Name: Project Name

Remote Area Name: Early Home Second Floor Date: 4/26/2023 N 1.85

Summary Sheet

No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).

A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:09:28PM@ M.E.P.CAD, Inc.

(GPM) (GPM) (K) (psi)

Outflowing Devices Report Description: Light Hazard

Job Number: Project Number

Device

Actual Flow Minimum Flow K-Factor Pressure

Sprinkler 103 16.80 GPM 14.82 GPM 5.6 9.00 psi

Sprinkler 101 15.40 GPM 14.82 GPM 5.6 7.56 psi

Sprinkler 102 15.91 GPM 14.82 GPM 5.6 8.07 psi

Sprinkler 100 14.82 GPM 14.82 GPM 5.6 7.00 psi

Most Demanding Sprinkler Data

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:09:28PM@ M.E.P.CAD, Inc.

Job Name: Project Name

Remote Area Name: Early Home Second Floor Date: 4/26/2023

(psi) (psi)(GPM)(psi)(GPM)(psi)

Supply Analysis

Node Name Static Residual Flow Available Total Demand Required Pressure

80.00 psi1 43.24 psi162.93 GPM1200.00 GPM 109.25 psi110.00 psiWater Supply

Node Analysis

Discharge at

Node

(GPM)

Pressure at

Node

(psi)

Elevation (ft)Node Number Node Type Notes

31' - 6" 16.80 GPM9.00 psi Sprinklers

31' - 6" 15.40 GPM7.56 psi Sprinklers

31' - 6" 15.91 GPM8.07 psi Sprinklers

31' - 6" 14.82 GPM7.00 psi Sprinklers

-1' - 3" 62.93 GPM43.24 psi1

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:09:29PM@ M.E.P.CAD, Inc.

Date: 4/26/2023

Remote Area Name: Early Home Second Floor

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

7' - 6"

32' - 2" 21' - 8"

-0.29 psi

1.62 psi

31' - 6" 14' - 2"

1"

• • • • • Route 1 • • • • •

(See

Notes)

1"

7.00 psi

14.82 GPM

0.07 psi

Sprinkler,

14.82 GPM

5.6

3E(2' - 6")

6 FPS

8' - 8"

32' - 2" 16' - 7" 4.64 psi

32' - 2" 7' - 11"

1" (See

Notes)

1"

8.33 psi

15.40 GPM

0.28 psi

Flow (q) from Route 2

30.22 GPM E(2' - 6"), T(6' - 3")

11 FPS

9' - 11"

32' - 2" 14' - 2" 1.91 psi

32' - 2" 4' - 3"

1 1/2" (See

Notes)

1 5/8"

12.97 psi

32.71 GPM

0.13 psi

Flow (q) from Route 3

62.93 GPM T(9' - 11")

10 FPS

6' - 2"

32' - 2" 6' - 7" 0.26 psi

32' - 2" 0' - 5"

2" (See

Notes)

2 1/8"

14.87 psi

0.04 psi

62.93 GPM E(6' - 2")

6 FPS

6' - 2"

21' - 3" 17' - 1"

4.72 psi

0.68 psi

32' - 2" 10' - 11"

2" (See

Notes)

2 1/8"

15.14 psi

0.04 psi

62.93 GPM E(6' - 2")

6 FPS

24' - 7"

20' - 6" 30' - 2"

0.33 psi

1.20 psi

21' - 3" 5' - 7"

2" (See

Notes)

2 1/8"

20.54 psi

0.04 psi

62.93 GPM 2E(6' - 2"), T(12' - 4")

6 FPS

6' - 2"

10' - 6" 16' - 2"

4.34 psi

0.64 psi

20' - 6" 10' - 0"

2" (See

Notes)

2 1/8"

22.08 psi

0.04 psi

62.93 GPM E(6' - 2")

6 FPS

30' - 9"

10' - 6" 48' - 10" 1.95 psi

10' - 6" 18' - 0"

2" (See

Notes)

2 1/8"

27.06 psi

0.04 psi

62.93 GPM 3E(6' - 2"), T(12' - 4")

6 FPS

13' - 6"

7' - 0" 17' - 1"

1.52 psi

0.68 psi

10' - 6" 3' - 6"

2" (See

Notes)

2 1/8"

29.01 psi

0.04 psi

62.93 GPM CV(13' - 6")

6 FPS

7' - 5"

4' - 0" 8' - 3"

1.31 psi

8.33 psi

7' - 0" 0' - 10"

2" (See

Notes)

2 1/8"

31.21 psi

0.04 psi

62.93 GPM DelV, BV(7' - 5"), BFP(-8.00

psi)

6 FPS

-1' - 3" 3' - 9"

2.25 psi

0.15 psi

4' - 0" 3' - 9"

2 1/2" (See

Notes)

2 1/2"

40.84 psi

0.02 psi

62.93 GPM 2red, S

4 FPS

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:09:30PMEarly Home Second Floor@ M.E.P.CAD, Inc.

Remote Area Name: Early Home Second Floor

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

100.00 GPM

Hose Allowance At Source

162.93 GPM

Route 1

43.24 psi

Total(Pt)

11' - 2"

32' - 2" 13' - 1"

-0.29 psi

1.05 psi

31' - 6" 1' - 11"

1"

• • • • • Route 2 • • • • •

(See

Notes)

1"

7.56 psi

15.40 GPM

0.08 psi

Sprinkler,

15.40 GPM

5.6

2E(2' - 6"), T(6' - 3")

6 FPS

8.33 psi Route 2Total(Pt)

11' - 2"

32' - 2" 25' - 2"

-0.29 psi

2.15 psi

31' - 6" 14' - 0"

1"

• • • • • Route 3 • • • • •

(See

Notes)

1"

8.07 psi

15.91 GPM

0.09 psi

Sprinkler,

15.91 GPM

5.6

2E(2' - 6"), T(6' - 3")

6 FPS

8' - 8"

32' - 2" 9' - 5" 3.04 psi

32' - 2" 0' - 8"

1" (See

Notes)

1"

9.93 psi

16.80 GPM

0.32 psi

Flow (q) from Route 4

32.71 GPM E(2' - 6"), T(6' - 3")

12 FPS

12.97 psi Route 3Total(Pt)

11' - 2"

32' - 2" 12' - 11"

-0.29 psi

1.22 psi

31' - 6" 1' - 9"

1"

• • • • • Route 4 • • • • •

(See

Notes)

1"

9.00 psi

16.80 GPM

0.09 psi

Sprinkler,

16.80 GPM

5.6

2E(2' - 6"), T(6' - 3")

6 FPS

9.93 psi Route 4Total(Pt)

4/26/2023 Page 2AutoSPRINK RVT v2.2.25.0 2:09:30PMEarly Home Second Floor@ M.E.P.CAD, Inc.

Remote Area Name: Early Home Second Floor

1.51

Fittings Legend

BFP Backflow Preventer BV Butterfly Valve CV Check Valve

DelV Deluge Valve E 90° Elbow red Reducer/Adapter

S Supply Spr Sprinkler T Tee Flow Turn 90°

4.87

1.33

1.16

0.713

Equivalent Pipe Lengths of Valves and Fittings (C=120 only)

Actual Inside Diameter

Schedule 40 Steel Pipe Inside Diameter = Factor

C Value Multiplier

Value Of C

Multiplying Factor

4/26/2023 Page 3AutoSPRINK RVT v2.2.25.0 2:09:30PMEarly Home Second Floor@ M.E.P.CAD, Inc.

Location:

Project Name:

Drawing Name: 22187 ANJO EH F Calculation Date:4/26/2023

Hydraulic Calculations Summary for

Design

Light Hazard

1500 SF

100 SF (typical)

Early Home Attic

0.10 GPM/SF

Remote Area Name:

Occupancy Classification:

Density

Area of Application:

Coverage per Sprinkler:

Type of Sprinklers Calculated:

No. of Sprinklers Calculated:

at Node:

Fire Protection Wet

N/AN/A

1100.00 GPM

0.0 galType of System:

In-rack Demand:

Hose Streams:

Volume of Dry or PreAction System:

at Node:

Type Allowance at Source

Total Water Required (including Hose Streams where applicable)

74.19 psi@242.06 GPMFROM: Water Supply at Node 1:

34.26 psiSafety Margin:

Contact Name

Address:

Phone Number:

Authority Having Jurisdiction:

Name of Designer:

Automatic Peaking Results

Notes:

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:12:40PMEarly Home Attic@ M.E.P.CAD, Inc.

Hunter Simpson

Andrew Johnson Historic Site - Fire Suppression Early Home

Hydraulic Graph

Water Supply

Node: 1

Job Name: Project Name

Remote Area Name: Early Home Attic Date: 4/26/2023 N 1.85

Summary Sheet

No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).

A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:12:41PM@ M.E.P.CAD, Inc.

(GPM) (GPM) (K) (psi)

Outflowing Devices Report Description: Light Hazard

Job Number: Project Number

Device

Actual Flow Minimum Flow K-Factor Pressure

Sprinkler 104 24.48 GPM 21.17 GPM 8 9.36 psi

Sprinkler 105 27.15 GPM 21.17 GPM 8 11.51 psi

Sprinkler 101 22.33 GPM 21.17 GPM 8 7.79 psi

Sprinkler 103 24.09 GPM 21.17 GPM 8 9.07 psi

Sprinkler 100 21.17 GPM 21.17 GPM 8 7.00 psi

Sprinkler 102 22.85 GPM 21.17 GPM 8 8.16 psi

Most Demanding Sprinkler Data

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:12:41PM@ M.E.P.CAD, Inc.

Remote Area Name: Early Home Attic Date: 4/26/2023

(psi) (psi)(GPM)(psi)(GPM)(psi)

Supply Analysis

Node Name Static Residual Flow Available Total Demand Required Pressure

80.00 psi1 74.19 psi242.06 GPM1200.00 GPM 108.45 psi110.00 psiWater Supply

Node Analysis

Discharge at

Node

(GPM)

Pressure at

Node

(psi)

Elevation (ft)Node Number Node Type Notes

36' - 8" 24.48 GPM9.36 psi Sprinklers

36' - 8" 27.15 GPM11.51 psi Sprinklers

36' - 8" 22.33 GPM7.79 psi Sprinklers

36' - 8" 24.09 GPM9.07 psi Sprinklers

38' - 2" 21.17 GPM7.00 psi Sprinklers

38' - 2" 22.85 GPM8.16 psi Sprinklers

-1' - 3" 142.06 GPM74.19 psi1

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:12:42PM@ M.E.P.CAD, Inc.

Remote Area Name: Early Home Attic

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

2' - 6"

37' - 11" 15' - 6"

0.11 psi

2.24 psi

38' - 2" 13' - 0"

1"

• • • • • Route 1 • • • • •

(See

Notes)

1"

7.00 psi

21.17 GPM

0.14 psi

Sprinkler,

21.17 GPM

E(2' - 6")

8 FPS

8' - 8"

36' - 5" 14' - 2"

0.65 psi

7.94 psi

37' - 11" 5' - 6"

1" (See

Notes)

1"

9.35 psi

22.85 GPM

0.56 psi

Flow (q) from Route 3

44.02 GPM E(2' - 6"), T(6' - 3")

16 FPS

12' - 4"

36' - 5" 16' - 0" 1.94 psi

36' - 5" 3' - 8"

1 1/2" (See

Notes)

1 5/8"

17.93 psi

46.42 GPM

0.26 psi

Flow (q) from Route 2

90.44 GPM red, T(12' - 4")

14 FPS

18' - 6"

32' - 2" 25' - 7"

1.84 psi

4.60 psi

36' - 5" 7' - 1"

2" (See

Notes)

2 1/8"

19.87 psi

51.62 GPM

0.18 psi

Flow (q) from Route 5

142.06 GPM 3E(6' - 2")

14 FPS

6' - 2"

21' - 3" 17' - 1"

4.72 psi

3.07 psi

32' - 2" 10' - 11"

2" (See

Notes)

2 1/8"

26.31 psi

0.18 psi

142.06 GPM E(6' - 2")

14 FPS

24' - 7"

20' - 6" 30' - 2"

0.33 psi

5.43 psi

21' - 3" 5' - 7"

2" (See

Notes)

2 1/8"

34.10 psi

0.18 psi

142.06 GPM 2E(6' - 2"), T(12' - 4")

14 FPS

6' - 2"

10' - 6" 16' - 2"

4.34 psi

2.91 psi

20' - 6" 10' - 0"

2" (See

Notes)

2 1/8"

39.87 psi

0.18 psi

142.06 GPM E(6' - 2")

14 FPS

30' - 9"

10' - 6" 48' - 10" 8.78 psi

10' - 6" 18' - 0"

2" (See

Notes)

2 1/8"

47.11 psi

0.18 psi

142.06 GPM 3E(6' - 2"), T(12' - 4")

14 FPS

13' - 6"

7' - 0" 17' - 1"

1.52 psi

3.07 psi

10' - 6" 3' - 6"

2" (See

Notes)

2 1/8"

55.89 psi

0.18 psi

142.06 GPM CV(13' - 6")

14 FPS

7' - 5"

4' - 0" 8' - 3"

1.31 psi

9.48 psi

7' - 0" 0' - 10"

2" (See

Notes)

2 1/8"

60.48 psi

0.18 psi

142.06 GPM DelV, BV(7' - 5"), BFP(-8.00

psi)

14 FPS

-1' - 3" 3' - 9"

2.25 psi

0.67 psi

4' - 0" 3' - 9"

2 1/2" (See

Notes)

2 1/2"

71.27 psi

0.08 psi

142.06 GPM 2red, S

10 FPS

4/26/2023 Page 1AutoSPRINK RVT v2.2.25.0 2:12:42PMEarly Home Attic@ M.E.P.CAD, Inc.

Remote Area Name: Early Home Attic

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

100.00 GPM

Hose Allowance At Source

242.06 GPM

Route 1

74.19 psi

Total(Pt)

2' - 6"

36' - 5" 15' - 6"

0.11 psi

2.47 psi

36' - 8" 13' - 0"

1"

• • • • • Route 2 • • • • •

(See

Notes)

1"

7.79 psi

22.33 GPM

0.16 psi

Sprinkler,

22.33 GPM

E(2' - 6")

8 FPS

2' - 6"

36' - 5" 12' - 3" 7.55 psi

36' - 5" 9' - 9"

1" (See

Notes)

1"

10.37 psi

24.09 GPM

0.62 psi

Flow (q) from Route 4

46.42 GPM E(2' - 6"), red

17 FPS

36' - 5" 0' - 3" 0.02 psi

36' - 5" 0' - 3"

1 1/2"

1 5/8"

17.91 psi

0.08 psi

46.42 GPM

7 FPS

17.93 psi Route 2Total(Pt)

6' - 3"

37' - 11" 6' - 6"

0.11 psi

1.08 psi

38' - 2" 0' - 3"

1"

• • • • • Route 3 • • • • •

(See

Notes)

1"

8.16 psi

22.85 GPM

0.17 psi

Sprinkler,

22.85 GPM

T(6' - 3")

8 FPS

9.35 psi Route 3Total(Pt)

6' - 3"

36' - 5" 6' - 6"

0.11 psi

1.19 psi

36' - 8" 0' - 3"

1"

• • • • • Route 4 • • • • •

(See

Notes)

1"

9.07 psi

24.09 GPM

0.18 psi

Sprinkler,

24.09 GPM

T(6' - 3")

9 FPS

10.37 psi Route 4Total(Pt)

6' - 3"

36' - 5" 19' - 3"

0.11 psi

3.63 psi

36' - 8" 13' - 0"

1"

• • • • • Route 5 • • • • •

(See

Notes)

1"

9.36 psi

24.48 GPM

0.19 psi

Sprinkler,

24.48 GPM

T(6' - 3")

9 FPS

14' - 10"

36' - 5" 20' - 10" 6.76 psi

36' - 5" 6' - 1"

1" (See

Notes)

1"

13.10 psi

27.15 GPM

0.75 psi

Flow (q) from Route 6

51.62 GPM E(2' - 6"), red, T(12' - 4")

19 FPS

19.87 psi Route 5Total(Pt)

6' - 3"

36' - 5" 6' - 6"

0.11 psi

1.48 psi

36' - 8" 0' - 3"

1"

• • • • • Route 6 • • • • •

(See

Notes)

1"

11.51 psi

27.15 GPM

0.23 psi

Sprinkler,

27.15 GPM

T(6' - 3")

10 FPS

13.10 psi Route 6Total(Pt)

4/26/2023 Page 2AutoSPRINK RVT v2.2.25.0 2:12:42PMEarly Home Attic@ M.E.P.CAD, Inc.

Remote Area Name: Early Home Attic

1.51

Fittings Legend

BFP Backflow Preventer BV Butterfly Valve CV Check Valve

DelV Deluge Valve E 90° Elbow red Reducer/Adapter

S Supply Spr Sprinkler T Tee Flow Turn 90°

4.87

1.33

1.16

0.713

Equivalent Pipe Lengths of Valves and Fittings (C=120 only)

Actual Inside Diameter

Schedule 40 Steel Pipe Inside Diameter = Factor

C Value Multiplier

Value Of C

Multiplying Factor

4/26/2023 Page 3AutoSPRINK RVT v2.2.25.0 2:12:42PMEarly Home Attic@ M.E.P.CAD, Inc.

ANJO Home Fire Supply

ANJO Fire Supply

Site Map - Time: 0.00 hours

Page 1 of 427 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-1666

11/22/2022

WaterCAD [10.03.01.08]Bentley Systems, Inc. Haestad Methods Solution CenterANJO Fire Supply.wtg

Pipe Table - Time: 0.00 hours

Flow (gpm)

Has Check Valve?

Hazen-Williams C

MaterialDiameter (in)

Stop NodeStart NodeLength (Scaled)

(ft)

LabelID

-345False130.0Ductile Iron6.0Supply ConnANJO Home61P-135

345False130.0Ductile Iron6.0Supply ConnFlow Test Data132P-278

345False150.0PVC48.0PMP-1R-120P-581

345False150.0PVC48.0Flow Test DataPMP-120P-682

Pressure Loss (psi)

Minor Loss Coefficient (Derived)

Length (User Defined)

(ft)

Has User Defined Length?

Headloss Gradient

(ft/ft)

Velocity (ft/s)

0.52.41050True0.0223.91

1.02.950150True0.0153.91

0.00.0001True0.0000.06

0.00.0001True0.0000.06

Page 2 of 427 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-1666

11/22/2022

Junction Table - Time: 0.00 hours

Pressure (psi)

Hydraulic Grade (ft)

Demand (gpm)

Demand Collection

ZoneElevation (ft)

LabelID

108250.520 <Collection: 0 items>

<None>0.00Supply Conn30

108249.43345 <Collection: 1 item>

<None>0.00ANJO Home33

109252.770 <Collection: 0 items>

<None>0.00Flow Test Data77

Page 3 of 427 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-1666

11/22/2022

Pump Table - Time: 0.00 hours

Pump Head (ft)

Flow (Total) (gpm)

Hydraulic Grade

(Discharge) (ft)

Hydraulic Grade

(Suction) (ft)

Status (Initial)Pump Definition

Elevation (ft)

LabelID

252.77345252.770.00On Pump Definition - 1

0.00PMP-180

Page 4 of 427 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-1666