A06_ATTACHMENT_2_Drawings_-_Sealed_(311420).pdf
PDF 3 MB Posted
- Attached to
- INSTALL FIRE SUPPRESSION SYSTEM, ANJO Federal contract opportunity
- Solicitation number
- 140P5325R0008
About this file
These are construction and engineering design drawings for a fire suppression system installation at the Andrew Johnson Early Home, a National Historic Site located in Greeneville, Tennessee. The nine-page technical drawing set includes detailed plans for fire protection, fire alarm, and civil infrastructure work, specifically covering floor plans, riser details, system layouts, and technical specifications for each system across the building's basement, first floor, second floor, and attic. Key technical elements include a double interlock preaction sprinkler system, hydraulically designed fire protection network, fire alarm components, new underground water supply, and careful consideration for preserving the historic structure's integrity during installation. The drawings are dated 04/26/2023 and prepared by Fisher Engineering with civil engineering support from Nelson Engineering, indicating a comprehensive multi-disciplinary approach to the fire protection system design.
The drawings specify technical requirements such as using dry pendent sprinklers due to potential temperatures below 40 degrees Fahrenheit, installing a nitrogen generator, implementing weatherproof heat detectors, and ensuring minimal disruption to the historic building's structure. The fire protection system is designed as a light hazard system with specific hydraulic calculations for water flow and pressure, and the fire alarm system will integrate with an existing Honeywell Vista-128FBP fire alarm control panel. The project involves careful coordination to maintain the architectural and historical characteristics of the Andrew Johnson Early Home while implementing modern fire safety infrastructure.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P5325R0008_Amd_0002.pdf | ||
| QUESTIONS_AND_ANSWERS_0002.pdf | ||
| Sol_140P5325R0008_Amd_0001.pdf | ||
| ATTACHMENT_4_Contract_Price_Schedule_-_EH_(311420).xlsx | XLSX spreadsheet | |
| ATTACHMENT_7_Construction_Contract_Administration.docx | DOCX document | |
| A06_ATTACHMENT_3_Project_Calculations_(311420).pdf | ||
| ATTACHMENT_8_-__Limitation_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| A05_ATTACHMENT_1_Specifications_(311420).pdf | ||
| ATTACHMENT_6_Past_Performance_Questionnaire.docx | DOCX document | |
| Sol_140P5325R0008.pdf | ||
| B03_ATTACHMENT_5_Wage_Rate_Determination.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THIS PROJECT
W
TENNESSEE
KENTUCKY
TENNESSEE
NORTH
CAROLIN
A
TENNESSEE
VIRGINIA
KENTUCKY
VIR
GIN
IA
KNOXVILLE
GREAT SMOKY
MOUNTAINS N.P.
ASHEVILLE
LA FOLLETTE
WILLIAMSBURG
CORBIN
LONDON
MORRISTOWN
JEFFERSON
CITY
KINGSPORT
HAZARD
GREENEVILLE
TENNESSEE
GREENEVILLE
NOT TO SCALE
Project Manager Date
QUALITY DESIGN CERTIFICATION
OR
OR
Development (Title I)
Prepared in Accordance with Design by Design Development (Title I)
Construction Drawing Not Preceded
Approved by Superintendent on
Variance from Design Development (Title I)
Drawing No.
Date
STATEREGION COUNTY
NAME OF PARK
TITLE OF PROJECTSheetMark REVISION Date Initial
LOCATION WITHIN PARK
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
UNITED STATES
DEPARTMENT OF THE INTERIOR
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
CONSTRUCTION DOCUMENTS
/2
/2
:3 :2
P
M
FIRE SUPPRESSION - EARLY HOME
EARLY HOME
ANDREW JOHNSON NATIONAL HISTORIC SITE
UPPER SOUTH GREENE TENNESSEE
1 9
182686
311420
ANDREW JOHNSON EARLY HOME
ANDREW JOHNSON NATIONAL HISTORIC SITE
NOT TO SCALE
GREENVILLE
ANDREW JOHNSON
NATIONAL CEMETERY
INDEX OF DRAWINGS
CS COVER SHEET
FX101 EARLY HOME FLOOR PLANS - FIRE PROTECTION
FX501 DETAILS - FIRE PROTECTION - EARLY H.
FA101 EARLY HOME FLOOR PLANS - FIRE ALARM
FA501 DETAILS - FIRE ALARM - EARLY HOME
C-001 CIVIL NOTES EARLY HOME
C-101 FIRE WATER SUPPLY EARLY HOME
C-501 CIVIL DETAILS EARLY HOME
C-502 CIVIL DETAILS EARLY HOME
LIGHT HAZARD
0.10 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
FIRE PROTECTION LEGEND
UPRIGHT SPRINKLER, K-5.6
DRY PENDENT SPRINKLER, K-5.6
SIDEWALL SPRINKLER, K-5.6
SOUTH
CRAWL SPACE
NORTH
CRAWL SPACE
ELL
BASEMENT
LOWER
NORTH
PORCH
LOWER
SOUTH
PORCH
FX501
PROVIDE TANKLESS
WALL-MOUNTED
NITROGEN GENERATOR
MOUNTED ON FIREPLACE
UP TO
PARLOR
ROOMS
UP TO
KITCHEN
1"
NO SPRINKLER
COVERAGE REQUIRED IN
CRAWL SPACE AREAS
UP TO NORTH PARLOR THROUGH EXISTING
HOLE IN FOUNDATION
1"
9' - 10"
FX501
KITCHEN /
DINING ROOM
UPPER
SOUTH
PORCH
SOUTH
PARLOR
NORTH
PARLOR
UPPER
NORTH
PORCH
RAMP
FX501
SUPPLY
FROM
BASEMENT
UP TO
KITCHEN
ATTIC
UP TO
BEDROOMS
FROM SOUTH
CRAWL SPACE
1 1/4"
/4
1 1/4"
/4
DROP DOWN FROM
KITCHEN ATTIC
RUN PIPE EXPOSED TIGHT TO
WALL AND TIGHT TO CEILING.
PAINT TO MATCH ADJACENT
SURFACES. COORDINATE
WITH NATIONAL PARK
SERVICE FOR COLOR
MOUNT SPRINLKER PIPE TO BRICK
EXTERIOR. PAINT ALL EXTERIOR
SPRINKLER PIPING WITH EXPONY
BASED PAINT. COORDINATE WITH
NATIONAL PARK SERVICE FOR
COLOR
ATTACH PIPE HANGARS TO
BUILDING STRUCTURE ABOVE
CEILING. SECTIONS OF WOOD
PLANK CEILING WILL NEED TO BE
REMOVED AND REPLACED TO
MATCH EXISTING CEILING STYLE
AND COLOR1
FROM NORTH
CRAWL SPACE
FX501
NORTH
BEDROOM
SOUTH
BEDROOM
SPRINKLER
SUPPLY UP
TO SECOND
FLOOR
ATTIC
FROM KITCHEN
SPRINKLERS IN ATTIC
SPACES MUT BE
INTERMEDIATE
TEMPERATURE (TYPICAL)
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Total Water Required
Total Pressure Required
Base of Riser
Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Light Hazard
0.10 GPM
100.00 GPM
4 @ 14.82 GPM
5.6
162.93 GPM
43.24 psi
162.93 GPM
43.24 psi
+66.01 (60.42%)
Early Home Second Floor
0' - 11"
1"
1 1/2"
4' - 11"
RUN PIPE IN ATTIC ON TOP
OF JOISTS. DROP DOWN
TO KITCHEN. PENDENT TO
BE ON RETURN BEND. DRY
PENDENT NOT PERMITTED.
DROP DOWN TO UPPER
NORTH PORCH SPRINKLERS
DROP DOWN TO UPPER
SOUTH PORCH SPRINKLERS
1"
8' - 2"
SECOND
FLOOR
ATTIC
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Total Water Required
Total Pressure Required
Base of Riser
Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Light Hazard
0.10 GPM
100.00 GPM
6 @ 21.17 GPM
242.06 GPM
74.19 psi
242.06 GPM
74.19 psi
+34.26 (31.59%)
Early Home Attic
SPRINKLERS IN ATTIC
SPACES MUST BE
INTERMEDIATE
TEMPERATURE (TYPICAL)
1"
12' - 9"
1"
12' - 9"
1"
12' - 9"
1"
4' - 0"
1"
4' - 0"
1"
4' - 0"
1"
0' - 4"
1"
12' - 3"
1"
12' - 3"
/2
RUN PIPE IN ATTIC ON TOP
OF JOISTS. DROP DOWN
TO KITCHEN. DRY PENDENTS MUST BE
INSTALLED. PENDENTS ON RETURN BEND
ARE NOT PERMITTED FOR THIS BUILDING
DUE TO TEMPERATURES BELOW 40
DEGREES FAHRENHEIT.
INSPECTORS TEST
CONNECTION. MOUNT PIPE
TIGHT TO WALL. LOCATE
VALVE INSIDE ATTIC. SPOUT
TO DISCHARGE AT ATTIC
LEVEL FIELD LOCATE.
1"
6' - 5"
FIRE PROTECTION NOTES
1. SEE SHEET FX501 FOR FIRE PROTECTION SYSTEM NOTES
AND DETAILS
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
FISHER
ENGINEERING,
JOHNS CREEK,
GA
/2
/2
:3 :2
P
M
EARLY HOME FLOOR
PLANS - FIRE PROTECTIONFX101
04/26/2023
D. BROWN
H.SIMPSON
D. BROWN
2 9
182686
311420
ANDREW JOHNSON NATIONAL HISTORIC SITE
FIRE SUPPRESSION - EARLY HOME
B L D
G
SCALE AFX101
1 EARLY HOME BASEMENT FLOOR PLAN - FIRE PROTECTION
SCALE AFX101
2 EARLY HOME FIRST FLOOR PLAN - FIRE PROTECTION
SCALE AFX101
3 EARLY HOME SECOND FLOOR PLAN - FIRE PROTECTION
SCALE
4 0 4 128
SCALE OF FEET
A
SCALE AFX101
4 EARLY HOME ATTIC FLOOR PLAN - FIRE PROTECTION
FIRE PROTECTION NOTES
1. THE CONTRACTOR SHALL DEVELOP SHOP DRAWINGS FOR A
HYDRAULLICALLY DESIGNED SYSTEM BASED ON THESE DRAWINGS. THE
SYSTEM SHALL BE A DOUBLE INTERLOCK PREACTION SYSTEM IN
ACCORDANCE WITH NFPA 13, THE SPECIFICATIONS, AND THE SCOPE OF
WORK DOCUMENTS FOR THE AREAS ON THESE DRAWINGS. SPRINKLER
PIPE ROUTING, PIPE SIZE, AND SPRINKLER LOCATIONS HAVE BEEN
APPROVED BY NPS AND SHALL BE FOLLOWED. ANY DEVIATIONS SHALL BE
APPROVED BY NPS PRIOR TO SHOP DRAWING APPROVAL. PROVIDE A
SELF-CONTAINED DRY PIPE VALVE AND NITROGEN GENERATOR SYSTEM
IN A SINGLE MANUFACTURER SUPPLIED CABINET.
2. CONTRACTOR SHALL PROVIDE ALL NECESSARY AUXILIARY DRAINS AND
INSPECTORS' TEST CONNECTIONS AS REQUIRED BY NFPA 13.
INSPECTORS' TEST CONNECTIONS SHALL BE LOCATED AT THE MOST
REMOTE BRANCH LINE. INSPECTORS' TEST CONNECTIONS DRAINS SHALL
DISCHARGE TO A SAFE LOCATION OUTSIDE THE BUILDING.
3. CONTRACTOR SHALL PROVIDE ALL NECESSARY PIPE HANGERS AND
SUPPORTS AS REQUIRED BY NFPA 13.
4. CONTRACTOR MUST PROVIDE LIMITED SEISMIC BRACING PER APPROVAL
FROM THE REGIONAL STRUCTURAL FIRE MANAGER AS THE BUILDING IS
NOT SEISMICALLY RESTRAINED. CLEARANCE MUST BE PROVIDED
AROUND ALL FLOOR AND WALL PENETRATIONS BASED ON SEISMIC
REQUIREMENTS OF NFPA 13. 4-WAY BRACING MUST BE PROVIDED AT THE
TOP OF RISERS PER NFPA 13. LATERAL AND LONGITUDINAL BRACING IS
NOT REQUIRED TO BE PROVIDED.
5. ALL WATERFLOW AND HIGH/LOW NITROGEN SWITCHES SHALL BE
CONNECTED TO THE FIRE ALARM SYSTEM BY THE FIRE ALARM
CONTRACTOR.
6. ALL VALVES CONTROLLING WATERFLOW TO THE SPRINKLER SYSTEM
SHALL BE PROVIDED WITH TAMPER SWITCHES TO BE CONNECTED TO THE
FIRE ALARM SYSTEM BY THE FIRE ALARM CONTRACTOR.
7. ALL PENETRATIONS THROUGH FIRE-RESISTANT ASSEMBLIES SHALL BE
PROTECTED BY A UL-LISTED THROUGH-PENETRATION FIRESTOP SYSTEM.
ALL PENETRATIONS THROUGH SMOKE PARTITIONS SHALL BE SEALED
WITH NON-COMBUSTIBLE MATERIAL.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL CONFLICTS
WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, CABLE TRAYS,
CABLE BUNDLES, CONDUIT, UTILITY PIPING AND ALL OTHER
OBSTRUCTIONS ENCOUNTERED.
9. CONTRACTOR SHALL VERIFY ELEVATIONS AND LOCATIONS OF NEW
SPRINKLER PIPING AND EQUIPMENT PRIOR TO INSTALLATION.
10. CONTRACTOR SHALL TAKE ALL NECESSARY MEASURES TO KEEP THE
PREMISES DRY AT ALL TIMES AND TO PREVENT WATER DAMAGE.
CONTRACTOR SHALL REPAIR WATER DAMAGE RESULTING FROM THE
WORK, WHETHER INTENTIONAL OR NOT, AT NO COST TO, AND TO THE
SATISFACTION OF THE CONTRACTING OFFICER.
11. NEITHER THE CONTRACTING OFFICER NOR THE ENGINEER SHALL BE
RESPONSIBLE FOR PROVIDING A SAFE WORKING PLACE FOR THE
CONTRACTOR, SUBCONTRACTORS, OR THEIR EMPLOYEES, OR ANY
OTHER INDIVIDUAL RESPONSIBLE TO THEM FOR THE WORK. THIS
RESPONSIBILITY RESTS SOLELY ON THE CONTRACTOR'S PROJECT
SUPERINTENDENT.
12. ALL PIPING IN AREAS WITH SUSPENDED CEILINGS SHALL BE CONCEALED
ABOVE CEILINGS.
13. PAINT ALL EXPOSED FIRE SUPPRESSION SYSTEM PIPES A COLOR
DETERMINED BY THE CONTRACTING OFFICER. FIRE SUPPRESSION
SYSTEM PIPING SHALL BE PAINTED WITH AN EPOXY ENAMEL PAINT.
14. PREACTION SYSTEM BRANCHLINE PIPING MUST BE PITCHED 1/2" PER 10'
AND MAIN PIPING PITCHED 1/4" PER 10' IN ACCORDANCE WITH NFPA 13,
PARAGRAPH 16.10.3.1.
15. CONTROL VALVES MUST BE PLACED IN LOCATIONS ACCESSIBLE WITHOUT
THE USE OF A STEP LADDER WHEN POSSIBLE.
16. THE CONTRACTOR SHALL VERIFY PIPING AND SPRINKLER LOCATIONS IN
THE FIELD PRIOR TO INSTALLATION.
17. PENDENTS ON RETURN BEND ARE NOT PERMITTED FOR THIS BUILDING
DUE TO TEMPERATURES POSSIBLE BELOW 40 DEGREES FAHRENHEIT IN
ACCORDANCE WITH NFPA 13 SECTION 8.2.2.2. ALL PENDENT SPRINKLERS
MUST BE DRY PENDENTS.
18. FLOW TEST RESULTS: 110 PSI STATIC, 102 PSI AT 1405 GPM
2" DOUBLE INTERLOCK
PREACTION VALVE
UP TO FIRST FLOOR
TO BASEMENT
2" BACKFLOW PREVENTOR
2" UNDERGROUND SUPPLY
FX501
FX501
2" DOUBLE INTERLOCK
PREACTION VALVE
2" BACKFLOW PREVENTOR
2" UNDERGROUND SUPPLY
UP TO FIRST FLOOR
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
FISHER
ENGINEERING,
JOHNS CREEK,
GA
/2
/2
:3 :2
P
M
DETAILS - FIRE
PROTECTION - EARLY H.FX501
04/26/2023
D. BROWN
H.SIMPSON
W.HIGGINS
3 9
182686
311420
ANDREW JOHNSON NATIONAL HISTORIC SITE
FIRE PROTECTION - EARLY HOME
FX501
1 EARLY HOME RISER DETAIL
SCALE: 1" = 1'-0"
0 6" 1' 2'
FX501
2 EARLY HOME RISER DETAIL
SCALE: 1" = 1'-0"
0 6" 1' 2'
SOUTH
CRAWL SPACENORTH
CRAWL SPACE
ELL
BASEMENT
LOWER
NORTH
PORCH
LOWER
SOUTH
PORCH
E
WP
WP
WP WP
MM
MM
MM
MM
P
RSFACU EXISTING ELECTRICAL PANEL.
SEE NOTES 8, 9, AND 12 ON
FA501
NEW UNIT HEATER D/S
SEE NOTE 14 ON FA501
UH-1
NEW UNIT HEATER,
PROVIDED BY OTHERS
SEE NOTE 13 ON FA501
NEW NITROGEN GENERATOR D/S
SEE NOTE 11 ON FA501
MONITOR MODULES TO BE
PROVIDED FOR NON-
ADDRESSABLE
WEATHERPROOF HEAT
DETECTORS.
MONITOR MODULES TO BE
PROVIDED FOR NON-
ADDRESSABLE
WEATHERPROOF HEAT
DETECTORS.
PROVIDE PREACTION
RELEASING PANEL IN
AN ENVIRONMENTAL
ENCLOSURE
MM
MM
MM PR
MONITOR PREACTION PIPE
SYSTEM RISER CONTROL
VALVE, WATERFLOW,
NITROGEN SUPERVISORY,
AND HIGH/LOW NITROGEN
WITH RELEASING SYSTEM
CONTROL UNIT
MMR
PROVIDE RELAY FOR SMOKE/HEAT
DETECTOR ACTIVATION.
MM
R S
PROVIDE DELUGE
VALVE SOLENOID
AND RELAY
MM
MM
MM
MONITOR RSFACU FOR ALARM,
SUPERVISORY, AND TROUBLE
NEW PREACTION D/S SEE
NOTES 10 ON FA501
FX501
KITCHEN /
DINING ROOM
UPPER
SOUTH
PORCH
SOUTH
PARLOR
NORTH
PARLOR
UPPER
SOUTH
PORCH
RAMP
E
EE
P
E
EP
E
E
E
FSA
E
WP WP
WP
MM
MM
MM
MONITOR MODULES TO BE
PROVIDED FOR NON-ADDRESSABLE
WEATHERPROOF HEAT DETECTORS.
FX501
NORTH
BEDROOM
SOUTH
BEDROOM
F A
C U
E
E
E
E
INSTALL NEW SMOKE
DETECTOR IN CLOSET
ABOVE FIRE ALARM
CONTROL UNIT
DINING ROOM
ATTIC
SECOND
FLOOR
ATTIC
E
MANUAL PULL STATION
FIRE ALARM CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE SENSOR
INDICATES WEATHERPROOFWP
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
MM
R
FIRE ALARM LEGEND
P
XMIT WIRELESS COMMUNICATOR
XX
FIRE ALARM HORN / STROBE
(WALL-MOUNTED)
FACU
SUPERVISORY NITROGEN SWITCHPR
INDICATES EXISTING TO REMAINE
RELEASING SYSTEM FIRE ALARM
CONTROL UNIT
RSFACU
HEAT DETECTOR
SPD SURGE PROTECTIVE DEVICE
FSA FIRE ALARM REMOTE ANNUNCIATION PANEL
HIGH/LOW NITROGEN PRESSURE SWITCH
S RELEASING SOLENOID
DISCONNECT SWITCH
ELECTRICAL LEGEND
ELECTRICAL PANEL
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
NOTES AND DETAILS
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
FISHER
ENGINEERING,
JOHNS CREEK,
GA
/2
/2
:3 :2
P
M
EARLY HOME FLOOR
PLANS - FIRE ALARMFA101
04/26/2023
D. BROWN
H.SIMPSON
W.HIGGINS
4 9
182686
311420
ANDREW JOHNSON NATIONAL HISTORIC SITE
FIRE SUPPRESSION - EARLY HOME
B L D
G
SCALE AFA101
1 EARLY HOME BASEMENT FLOOR PLAN - FIRE ALARM
SCALE AFA101
2 EARLY HOME FIRST FLOOR PLAN - FIRE ALARM
SCALE AFA101
3 EARLY HOME SECOND FLOOR PLAN - FIRE ALARM
SCALE AFA101
4 EARLY HOME ATTIC FLOOR PLAN - FIRE ALARM
SCALE
4 0 4 128
SCALE OF FEET
A
FIRE ALARM SYSTEM SEQUENCE OF OPERATION MATRIX
MANUAL PULL STATION
ALARM AT
FACP
SUPERVISORY
AT FACP
TROUBLE AT
FACP
ALARM AT
RECEIVING
STATION
TROUBLE
AT
RECEIVING
STATION
SUPERVISORY
AT RECEIVING
STATION
ACTIVATE
HORNS &
FA
STROBES
SILENCE
HORNS &
STROBES
REMAIN
ACTIVE
ACTIVATE
RSFACU
RELAY
HEAT DETECTOR
FIRE ALARM TROUBLE
CONDITION (OPENS,
SHORTS OR GROUNDS)
ALARM SILENCE AT
FACP OR FSA
*SEE SPECIFICATION SECTION 28 31 76, PARAGRAPH 2.19.2 FOR SPECIFIC SIGNALS REQUIRED TO BE TRANSMITTED TO THE RECEIVING STATION
SMOKE DETECTOR
ALARM FROM RSFACU
SUPERVISORY FROM
RSFACU
TROUBLE FROM RSFACU
FIRE ALARM RELEASING SYSTEM SEQUENCE OF OPERATION MATRIX
ALARM AT
CONTROL
UNIT
RELEASE
PREACTION
SOLENOID
TROUBLE CONDITION
(OPENS, SHORTS OR
GROUNDS)
FIRE ALARM RELAY
ACTIVATION FROM FACU
PREACTION SYSTEM
RISER CONTROL VALVE
PREACTION SYSTEM
WATERFLOW
NITROGEN GENERATOR
SUPERVISORY
HIGH/LOW NITROGEN
SUPERVISORY
AT CONTROL
UNIT
TROUBLE AT
CONTROL
UNIT
ALARM TO
FACU AND
RECIEVING
STATION
SUPERVISORY
TO FACU AND
RECIEVING
STATION
TROUBLE TO
FACU AND
RECIEVING
STATION
N/A
FIRE ALARM NOTES
1. THE FIRE ALARM SYSTEM WILL BE EXISTING TO REMAIN WITH THE ADDITION
OF THE DEVICES NOTED ON THE DRAWING SET. DEVICES WILL BE ADDED TO
MAKE A CODE COMPLIANT FIRE ALARM SYSTEM AND PROVIDE COMPLETE
SMOKE/HEAT DETECTION FOR PREACTION SPRINKLER SYSTEM RELEASING.
THE NEW DEVICES WILL BE EXTENSIONS OF THE EXISTING HONEYWELL
VISTA-128FBP FIRE ALARM CONTROL PANEL INSTALLED IN THE EARLY HOME
BUILDING. ALARM, TROUBLE AND SUPERVISORY SIGNALS WILL BE
TRANSMITTED TO A SUPERVISING STATION VIA WIRELESS COMMUNICATORS.
2. NEW FIRE ALARM HORNS, STROBES AND HORN/STROBES TO
BE PROVIDED AND SPACED IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 72.
3. THE EXISTING FIRE ALARM SYSTEMS SHALL MONITOR THE NEW PREACTION
RELEASING FIRE ALARM CONTROL PANEL ALARM, SUPERVISORY AND
TROUBLE CONDITIONS.
4. ANY NEW AIR HANDLING UNITS OVER 2000 CFM, SHALL HAVE DUCT SMOKE
SENSORS INSTALLED ON THE SUPPLY DUCTS.
5. THE FIRE ALARM LAYOUT IS DIAGRAMMATICAL ONLY. THE ACTUAL BUILDING
LAYOUT MAY VARY FROM THE DRAWINGS. DEVICE LOCATION IS
DIAGRAMMATIC ONLY. CONTRACTOR MUST BE RESPONSIBLE FOR AVOIDING
ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS,
CABLES, CONDUITS, UTILITY PIPING AND ALL OTHER OBSTRUCTIONS
ENCOUNTERED. THE CONTRACTOR SHALL VERIFY CEILING HEIGHTS, WALL
AND PARTITION LOCATIONS AND DOOR LOCATIONS PRIOR TO INSTALLATION.
6. ALL FIRE ALARM CONDUCTORS SHALL BE SOLID OR STRANDED COPPER,
SHALL BE INSTALLED IN CONDUIT, AND WIRED CLASS B. ALL CONDUIT SHALL
BE FACTORY PAINTED RED.
7. IF ANY ADDITIONAL AMPLIFIERS OR POWER SUPPLIES ARE INSTALLED OUT IN
THE FIELD, A SMOKE DETECTOR SHALL BE INSTALLED ABOVE EACH.
8. EXISTING ELECTRICAL PANEL IS SQUARE TYPE QOC LOAD CENTER.
CONTRACTOR IS RESPONSIBLE FOR ENSURING COMPATIBILITY OF ALL
INSTALLED CIRCUIT BREAKERS AND PROVIDING ALL REQUIRED PANEL
ACCESSORIES AND HARDWARE TO MAKE THE IDENTIFIED PANEL
MODIFICATIONS.
9. INSTALL TWO NEW 15A, 1P, 120VAC, 10 KAIC CIRCUIT BREAKERS IN EXISTING
PANEL POSITIONS 27 AND 29 TO FEED NEW PREACTION RELEASING PANEL
AND NITROGEN GENERATOR.
10. INSTALL NEW 1P, 120VAC, 30A, GENERAL-DUTY RATED, NON-FUSED,
DISCONNECT SWITCH IN NEMA 1 ENCLOSURE WITH RED FINISH AS
DISCONNECTING MEANS FOR NEW PREACTION RELEASING PANEL. INSTALL
NEW 3/4-INCH CONDUIT CONTAINING THREE (3) #12 AWG CONDUCTORS
(PHASE/NEUTRAL/GROUND) FROM NEW CIRCUIT 27 IN EXISTING PANEL TO
FEED PREACTION RELEASING PANEL.
11. INSTALL NEW 1P, 120VAC, 30A, GENERAL-DUTY RATED NON-FUSED,
DISCONNECT SWITCH IN NEMA 3R ENCLOSURE AS DISCONNECTING MEANS
FOR NEW NITROGEN GENERATOR. INSTALL NEW 3/4-INCH CONDUIT
CONTAINING THREE (3) #12 AWG CONDUCTORS FROM NEW CIRCUIT 29 IN
EXISTING PANEL TO FEED NITROGEN GENERATOR.
12. INSTALL NEW 30A, 2P, 240VAC, 10 KAIC CIRCUIT BREAKER IN EXISTING PANEL
POSITIONS 28, 30 TO FEED NEW UNIT HEATER.
13. INSTALL NEW REZNOR MODEL EGW OR APPROVED EQUAL, 5KW, 240, 1PH UNIT
HEATER PER MANUFACTURER INSTRUCTIONS. SET THERMOSTAT
TEMPERATURE AT MINIMUM 41 DEGREES FAHRENHEIT. REFER TO UNIT
HEATER SCHEDULE IN THIS DRAWING SET FOR EQUIPMENT INFORMATION.
14. INSTALL NEW MINIMUM 2P, 240VAC, 30A, GENERAL-DUTY RATED, NON-FUSED,
DISCONNECT SWITCH IN NEMA 3R ENCLOSURE AS DISCONNECTING MEANS
FOR NEW UNIT HEATER. INSTALL NEW 3/4-INCH CONDUIT CONTAINING FOUR
(4) #10 AWG CONDUCTORS (PHASE/PHASE/NEUTRAL/GROUND) FROM NEW
CIRCUIT 28,30 IN EXISTING PANEL TO FEED NEW UNIT HEATER.
15. PAINT ALL NEW/EXPOSED FIRE ALARM CONDUIT A COLOR DETERMINED BY
THE CONTRACTING OFFICER.
MANUAL PULL
STATION
FACU OR
RELEASING
PANEL
WALL-MOUNTED HORN,
STROBE, OR HORN-STROBE
EXISTING
FACU
LOCATED IN
SECOND
FLOOR
CLOSET OF
EARLY HOME
MANUAL PULL
STATIONS
MM
SPRINKLER
WATERFLOW
MM
CONTROL
VALVE
SMOKE
DETECTORS
P P
HORN/
STROBE
NOTE: EXISTING INNITIATING DEVICES AND NOTIFICATION DEVICES ARE NOT SHOWN
MM
NITROGEN
SUPERVISORY
PR
HEAT
DETECTORS
NEW RELEASING
SYSTEM FIRE
ALARM
CONTROL UNIT
TO
VAC
XMITSPD
EXISTING
PROVIDE NEW SURGE
PROTECTIVE DEVICE
ON EXISTING CIRCUIT
MM
NITROGEN
SUPERVISORY
R
SOLENOID
RELAY
S
MM
MM
MM
MM R
TO
VAC
SPD
MANUAL PULL STATION
FIRE ALARM CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE SENSOR
INDICATES WEATHERPROOFWP
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
MM
R
FIRE ALARM LEGEND
P
XMIT WIRELESS COMMUNICATOR
XX
FIRE ALARM HORN / STROBE
(WALL-MOUNTED)
FACU
SUPERVISORY NITROGEN SWITCHPR
INDICATES EXISTING TO REMAINE
RELEASING SYSTEM FIRE ALARM
CONTROL UNIT
RSFACU
HEAT DETECTOR
SPD SURGE PROTECTIVE DEVICE
FSA FIRE ALARM REMOTE ANNUNCIATION PANEL
HIGH/LOW NITROGEN PRESSURE SWITCH
S RELEASING SOLENOID
ELECTRICAL NOTES
1. ENSURE ALL NEW UNDERGROUND CONDUIT IS SCHEUDLE 40 PVC AND
ALL EXTERIOR AND BASEMENT CONDUITS ARE RIGID GALVANIZED
STEEL. ALL RIGID STEEL CONDUIT PENETRATING FINISHED GRADE,
WITHIN 6-INCHES OF FINISHED GRADE, OR BURIED MUST BE PVC
COATED OR PROTECTED FROM CORROSION USING BITUMINOUS TAPE
OR OTHER APPROVED METHOD.
2. INTERIOR CONDUIT MAY BE ELECTRICAL METALLIC TUBING BUT
ELECTRICAL METALLIC TUBING MAY NOT PENETRATE WALLS.
3. ALL WALL PENETRATIONS CREATED AS PART OF THIS PROJECT MUST
BE SEALED WITH A MINIMUM 2-HOUR, UL LISTED FIRE SEALANT
SYSTEM.
DISCONNECT SWITCH
ELECTRICAL LEGEND
ELECTRICAL PANEL
NOT TO SCALEFA501
1 SEQUENCE OF OPERATION MATRICES
NOT TO SCALEFA501
2 FIRE ALARM ELEVATION (TYPICAL)
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
FISHER
ENGINEERING,
JOHNS CREEK,
GA
/2
/2
:3 :2
P
M
DETAILS - FIRE ALARM -
EARLY HOMEFA501
04/26/2023
D. BROWN
H.SIMPSON
W.HIGGINS
5 9
182686
311420
ANDREW JOHNSON NATIONAL HISTORIC SITE
FIRE PROTECTION - EARLY HOME
FA501
3 RISER DIAGRAM EARLY HOME
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
C001
RFH
MH
RFH
6 9
TITLE OF SHEET
182686
ANDREW JOHNSON NATIONAL HISTORIC SITE
A/E FIRM:
PRIME:
FISHER
ENGINEERING
CIVIL SUB:
NELSON
ENGINEERING
GENERAL NOTES:
1. PERFORM ALL WORK AND RECEIVE ALL PERMITTING IN ADVANCE OF CONSTRUCTION IN ACCORDANCE
WITH TENNESSEE DIVISION OF WATER RESOURCES - COMMUNITY PUBLIC WATER SYSTEMS DESIGN CRITERIA. THE PROJECT IS BEING PERFORMED IN GREENEVILLE, TENNESSEE ON THE PUBLIC WATER SYSTEM OWNED BY THE GREENEVILLE WATER COMMISSION. COORDINATE ALL WORK, CONNECTIONS, OUTAGES AND PERMITTING THROUGH THE UTILITY.
2. THE PROJECT CONSTRUCTION SPECIFICATIONS ARE PART OF AND APPLY TO THE WORK SHOWN ON
THESE DRAWINGS.
3. COMPLETE ALL WORK IN ACCORDANCE WITH OSHA, INDUSTRY STANDARD AND NATIONAL PARK SERVICE
(NPS) SAFETY PRACTICES. THE MOST STRINGENT REQUIREMENT APPLIES.
4. LOCATIONS, ELEVATIONS AND DIMENSIONS OF EXISTING UTILITIES, STRUCTURES, AND OTHER FEATURES SHOWN ARE THE BEST INFORMATION AVAILABLE AT THE TIME OF PREPARATION OF THESE PLANS, BUT DO NOT PURPORT TO BE ABSOLUTELY CORRECT. VERIFY, PRIOR TO CONSTRUCTION, THE LOCATIONS, ELEVATIONS, AND DIMENSIONS OF ALL EXISTING UTILITIES, STRUCTURES AND OTHER FEATURES
(WHETHER OR NOT SHOWN ON THE PLANS) AFFECTING THE WORK.
5. FIELD LOCATE ALL EXISTING UTILITIES AS TO SIZE, LOCATION, AND ELEVATION. NOTIFY THE
CONTRACTING OFFICER OF ALL CONFLICTS PRIOR TO BEGINNING CONSTRUCTION.
6. FIELD CONDITIONS MAY REQUIRE ADJUSTMENTS TO ALIGNMENTS, ELEVATIONS AND LOCATIONS. FIELD
ADJUSTMENT IS ACCEPTABLE SUCH THAT CONFIGURATION MEETS ARE APPLICABLE CODES AND
STANDARDS AND DESIGN INTENT.
7. SUBMIT PRODUCT DATA, AND AS NECESSARY SAFETY DATA SHEETS, FOR CONTRACTING OFFICER APPROVAL AND INFORMATION FOR ALL PRODUCTS SPECIFIED HEREIN. WHERE CONTRACTOR DELEGATED DESIGN IS REQUIRED, SUBMIT ALL NECESSARY BACKUP DATA AND CALCULATIONS TO VALIDATE THE
PROPOSED SOLUTION.
8. PROTECT MATERIALS FROM CONTAMINATION, CORROSION, DEFORMATION AND OTHER TYPES OF DAMAGE. STORE ITEMS IN AN ENCLOSED AREA FREE FROM CONTACT WITH SOIL AND WEATHER. REMOVE
AND REPLACE DAMAGED ITEMS WITH NEW ITEMS.
9. GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCE, RULES, REGULATIONS, AND PERMIT CONDITIONS BEARING ON THE CONDUCT OF THE WORK AS DRAWN AND SPECIFIED. IF THE CONTRACTOR OBSERVES THAT THE DRAWINGS AND SPECIFICATIONS ARE AT VARIANCE, NOTIFY THE CONTRACTING
OFFICER IN WRITING, AND ANY NECESSARY CHANGES TO BE ADJUSTED, AS PROVIDED IN THE
AGREEMENT FOR CHANGES IN THE WORK.
10. IF THE CONTRACTOR DISCOVERS ANY ERRORS OR OMISSIONS IN THE PLANS, IMMEDIATELY NOTIFY THE
COR FOR DISPOSITION.
11. CONDUCT WORK TO MINIMIZE IMPACTS TO VEHICULAR AND PEDESTRIAN TRAFFIC. WHERE UNAVOIDABLE, PROVIDE FLAGGERS AND DIVERSION DEVICES IN ACCORDANCE WITH THE MANUAL ON UNIFORM TRAFFIC
CONTROL (MUTC).
12. CONSTRUCT AND MAKE CONNECTIONS IN A MANNER TO MINIMIZE THE NUMBER AND DURATION OF OUTAGES. DO NOT OPERATE WATER SYSTEM VALVES UNLESS EXPRESSLY DIRECTED TO DO SO BY THE UTILITY OPERATOR OR CONTRACTING OFFICER. SUBMIT REQUESTS FOR OUTAGES WELL IN ADVANCE OF NEED TO MINIMIZE DELAYS TO CONSTRUCTION. PERFORM ALL CONNECTIONS IN THE PRESENCE OF THE
UTILITY OPERATOR.
13. PRESERVE AND PROTECT ALL PERMANENT REFERENCE MONUMENTS, PERMANENT CONTROL POINTS, PERMANENT BENCH MARKS, AND PROPERTY CORNERS. IF THE MONUMENTS, POINTS, OR MARKERS ARE
DISTURBED, EMPLOY A TENNESSEE REGISTERED LAND SURVEYOR TO RESET OR REPLACE THEM.
14. MAKE ALL NECESSARY ARRANGEMENTS WITH PUBLIC UTILITIES, SERVICE COMPANIES, AND OTHER AGENCIES HAVING JURISDICTION, OWNING OR CONTROLLING ROADWAYS, UTILITIES, AND INCIDENTAL
STRUCTURES ENCOUNTERED IN THE WORK SUCH THAT ITEMS MAY BE PROPERLY SUPPORTED,
PROTECTED, OR LOCATED.
15. ADHERE TO ALL NORMALLY ACCEPTED AND REASONABLY EXPECTED SAFETY PRACTICES THROUGHOUT THE PROJECT DURATION. COMPLY WITH ALL FEDERAL, STATE, AND LOCAL REGULATIONS, ORDINANCES, AND GUIDELINES PERTAINING TO SAFE USE OF EQUIPMENT AND MATERIALS AS PUBLISHED BY THE
MANUFACTURER.
16. ERECT AND MAINTAIN, AS REQUIRED BY EXISTING CONDITIONS AND PROGRESS OF THE WORK, ALL
REASONABLE SAFEGUARDS FOR SAFETY AND ENVIRONMENTAL PROTECTION, INCLUDING POSTING
DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS, PROMULGATING SAFETY REGULATIONS AND NOTIFYING OWNERS AND USERS OF ADJACENT UTILITIES OF THE EXISTENCE OF HAZARDS AND OF THE
SAFETY OR ENVIRONMENTAL REGULATIONS.
17. PROVIDE ADEQUATE PROTECTION FOR PARTS IN WORKPLACE AND ADJACENT AREAS THAT ARE SUBJECT TO DAMAGE DUE TO CONSTRUCTION. PROTECTION OF PARTS IS AT THE COST OF THE CONTRACTOR.
18. USE, HANDLE, TRANSPORT, AND DISPOSE OF ALL HAZARDOUS MATERIALS IN COMPLIANCE WITH ALL
FEDERAL, STATE AND LOCAL ENVIRONMENTAL, HEALTH OR SAFETY LAWS, AND REQUIREMENTS.
19. TAKE ALL THE PRECAUTIONS TO PREVENT THE DISCHARGE, RELEASE OR DISPOSAL OF ANY HAZARDOUS MATERIAL CREATED BY WORK ON OR ABOUT THE JOB SITE. IN THE EVENT OF ANY SPILL, RELEASE OR
ANY OTHER REPORTABLE OCCURRENCE, NOTIFY THE APPROPRIATE GOVERNMENTAL AGENCY IN
ACCORDANCE WITH THE CONTRACTING OFFICER, AND TAKE SUCH ACTION AS MAY BE NECESSARY TO MINIMIZE THE DELETERIOUS EFFECT OF SUCH SPILL ON PERSONS OR PROPERTY. THE CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ANY HAZARDOUS WASTE MATERIALS IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL REGULATIONS.
20. UPON COMPLETION OF PERFORMANCE OF ALL DUTIES UNDER THIS CONTRACT, REMOVE ALL SUPPLIES, MATERIALS, AND WASTE CONTAINING ANY HAZARDOUS MATERIAL FROM THE JOB SITE. BEAR FULL FINANCIAL RESPONSIBILITY, AS BETWEEN THE PARTIES OF THIS CONTRACT, FOR THE COMPLIANCE OF
CONTRACTOR AND ITS SUBCONTRACTORS.
21. IN THE EVENT CONTRACTOR OR SUBCONTRACTORS ENCOUNTER ON THE PREMISES ANY PIPELINE, UNDERGROUND STORAGE TANK OR OTHER CONTAINER, OF ANY KIND, THAT MAY CONTAIN A HAZARDOUS
MATERIAL, OR ENCOUNTER MATERIAL REASONABLY BELIEVED TO BE A HAZARDOUS MATERIAL,
IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO CONTRACTING
OFFICER IN WRITING.
POTABLE WATER NOTES:
1. INSTALL POTABLE WATER PIPING TO THE LINES AND GRADES INDICATED. AVOID THE CREATION OF DIPS AND HIGH POINTS, EXCEPT AS DESIGNED. PROVIDE A MINIMUM OF 30 INCHES OF COVER OVER ALL POTABLE WATER PIPING. INSTALL WATER PIPE IN ACCORDANCE WITH AWWA STANDARDS AS SPECIFIED.
2. MAINTAIN HORIZONTAL AND VERTICAL SEPARATIONS OF WATER MAINS FROM OTHER UTILITIES AS PROVIDED IN RULES OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION, CHAPTER 0400-45-01. DO NOT INSTALL THE WATER LINE CLOSER THAN TWELVE (12) INCHES IN ANY DIRECTION
FROM ANOTHER UTILITY, UNLESS WRITTEN PERMISSION IS RECEIVED.
3. TRANSPORT, HANDLE, AND STORE PIPE AND APPURTENANCES IN ACCORDANCE WITH THE APPLICABLE
AWWA STANDARDS.
4. PROVIDE ALL MATERIALS COMPLYING WITH AND BEARING THE SEAL OF THE NATIONAL SANITATION
FOUNDATION STANDARDS FOR HEALTH FOR PRODUCTS IN CONTACT WITH POTABLE WATER.
SPECIFICALLY NSF 14 (PLASTIC PIPING), NSF 61 (HEALTH EFFECTS) AND NSF 372 (LEAD CONTENT).
PROVIDE ALL PRODUCTS WITH LEAD CONTENTS MEETING THE REQUIREMENTS OF "LEAD FREE" AS
DEFINED BY THE US SAFE DRINKING WATER ACT.
5. PERFORM HYDROSTATIC AND LEAK TESTING IN ACCORDANCE WITH THE REQUIREMENTS OF AWWA C605.
LEAKAGE MAY NOT EXCEED THE AMOUNTS GIVEN IN AWWA C605.
6. PERFORM DISINFECTION OF WATER LINES IN ACCORDANCE WITH AWWA C651. DOCUMENT ALL DISINFECTION PROCEDURES AND RESULTS. COLLECT AND SUBMIT SAMPLES IN ACCORDANCE WITH TDEC. INSTALL SAMPLE POINTS AS REQUIRED TO PROVIDE NECESSARY SAMPLING POINTS. PRIOR TO DISCHARGE OF DISINFECTION WATER, REDUCE CHLORIDE CONTENT IN ACCORDANCE WITH AWWA C655.
7. MAKE CONNECTIONS TO EXISTING LINES AFTER DISINFECTION HAS BEEN COMPLETED AND APPROVED.
WHERE REQUIRED, MAKE CONNECTIONS UNDER PRESSURE (HOT TAP) IN ACCORDANCE WITH THE
RECOMMENDED PROCEDURES OF THE MANUFACTURER OF THE TAPPING EQUIPMENT AND PIPE BEING
TAPPED.
EARTHWORK NOTES:
1. PRIOR TO EXCAVATION, COMPLY WITH ALL LOCAL, STATE, AND FEDERAL REQUIREMENTS FOR
PERMITTING OF EARTH DISTURBING ACTIVITIES.
2. IT IS THE CONSTRUCTION CONTRACTOR'S RESPONSIBILITY TO IMPLEMENT BEST MANAGEMENT PRACTICES (BMPs) FOR THE PREVENTION OF STORMWATER POLLUTION. IT IS ALSO THE CONSTRUCTION CONTRACTOR'S RESPONSIBILITY TO ENSURE THESE BMPs ARE PROPERLY INSTALLED, MAINTAINED AND FUNCTIONING PROPERLY TO PREVENT TURBID OR POLLUTED WATER FROM LEAVING THE PROJECT SITE.
ADD ADDITIONAL CONTROL MEASURES, AS REQUIRED TO ENSURE THE SITE MEETS ALL FEDERAL, STATE
AND LOCAL EROSION AND TURBIDITY CONTROL REQUIREMENTS.
3. ENSURE ALL BURIED ITEMS BEAR ON FIRM, UNDISTURBED SOIL OR COMPACTED FILL.
4. IF IN PLACE MATERIALS ARE FOUND TO BE UNSUITABLE, OVER-EXCAVATE AND BACKFILL WITH WITH CRUSHED STONE STRUCTURAL FILL, COMPACTED TO 95% OF THE MAXIMUM MODIFIED PROCTOR DRY
DENSITY IAW ASTM D-1557.
5. DEWATER, AS REQUIRED, SUCH THAT THE EXCAVATIONS ARE FREE OF STANDING WATER AT THE TIME OF
CONSTRUCTION.
6. COMPACT PAVEMENT SUBGRADES TO A MINIMUM OF 95% OF THE MAXIMUM MODIFIED PROCTOR DRY DENSITY IAW ASTM D-1557. IN UNPAVED AREAS, COMPACT SUBGRADE SOILS TO A MINIMUM OF 85% OF
THE MAXIMUM MODIFIED PROCTOR DRY DENSITY IAW ASTM D-1557.
7. COORDINATE ALL NEW EXCAVATION WITH EXISTING CONDITIONS AND VERIFY PROPOSED ELEVATIONS.
REPORT CONFLICTS TO CONTRACTING OFFICER.
ACRONYMS:
ACI AMERICAN CONCRETE INSTITUTE
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY OF TESTING AND MATERIALS
AWWA AMERICAN WATERWORKS ASSOCIATION
CIP CAST-IN-PLACE
COR CONTRACTING OFFICER'S REPRESENTATIVE
EOC EDGE OF CONCRETE
EX. EXISTING
IAW IN ACCORDANCE WITH
LBS POUNDS
MIN MINIMUM
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NPS NATIONAL PARK SERVICE
OC ON CENTER
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
TDEC TENNESSEE DEPARTMENT OF ENVIRONMENT & CONSERVATION
TYP TYPICAL
NelsonEngineeringCo.
5455 North Courtenay Pkwy
Merritt Island, FL 32953
(321) 449-1128 Fax (321) 449-1195 www.NelsonEngrCo.com
CIVIL NOTES
EARLY HOME
PW
FW
LEGEND:
EXISTING POTABLE WATER
NEW FIRE SUPPRESSION SUPPLY
311420
04/26/2023
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY ROBERT F. HOYT, P.E. ON THE DATE LISTED IN THE SIGNATURE.
THE ABOVE NAMED PROFESSIONAL ENGINEER IS RESPONSIBLE FOR THE CONTENT CONTAINED ON THESE DRAWINGS
ACCORDANCE WITH RULE 61G15-23.044, F.A.C.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED. THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
NELSON ENGINEERING
5455 NORTH COURTENAY PARKWAY
MERRITT ISLAND, FL 32953
CERTIFICATE OF AUTHORIZATION #6822
E.O.R.: ROBERT F. HOYT, P.E., #89917
R O B E R T F . H O Y TL I C E N S E
F L O R I D A
STATE OF
P R O F E S S I O N A L E N G I N E E
R
NO. 89917
L I C E N S E
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
PW
FW
FW
FW
FW
FW
FW
FW
FW
FW
X
X
X
X
PW
PW
PW
PW
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
FIRE WATER SUPPLY
EARLY HOMEC101
RFH
MH
RFH
TITLE OF SHEET
ANDREW JOHNSON NATIONAL HISTORIC SITE
A/E FIRM:
PRIME:
FISHER
ENGINEERING
6" PW (E)
6" PW (E)
SPECIFIC NOTES
CITY TO TAP EXISTING WATER MAIN AND PROVIDE SIX (6) INCH LATERAL WITH SERVICE
VALVE FOR NPS CONNECTION. CONNECT TO CITY VALVE IN ACCORDANCE WITH LOCAL
REQUIREMENTS.
INSTALL SIX (6) INCH DIAMETER DUCTILE IRON FIRE WATER SUPPLY.
HAND EXCAVATE BENEATH FOUNDATION AND STUB UP THROUGH SLAB FOR CONNECTION TO
NEW FIRE SUPPRESSION RISER (REFER TO SHEET FX102). PRESERVE ALL FOUNDATIONS AND
WALLS. BACKFILL TO PROVIDE 95% COMPACTION PER ASTM D1557. WHERE COMPACTION
CANNOT BE ACHIEVED, BACKFILL WITH LOW STRENGTH, EXCAVATABLE, FLOWABLE FILL.
SELECTIVELY DEMOLISH EXISTING BRICK SIDEWALK TO FACILITATE WATER LINE
INSTALLATION. REPAIR BRICK SURFACES TO MATCH EXISTING.
PRESERVE / RESTORE EXISTING WOOD PICKET FENCE.
6" Ø DI 90° EL
ACADEMY STREET
ANJO
EARLY HOME
CIVIL SUB:
NELSON
ENGINEERING
NelsonEngineeringCo.
5455 North Courtenay Pkwy
Merritt Island, FL 32953
(321) 449-1128 Fax (321) 449-1195 www.NelsonEngrCo.com
N
15' +/-
GENERAL NOTES
1. ALL EXISTING UTILITY DATA IS BASED ON RECORD DRAWINGS AND HAVE NOT BEEN FIELD
VERIFIED. VERIFY LINE SIZES AND DETERMINE MATERIALS PRIOR TO MATERIAL
PURCHASE.
2. LIMITS OF PAVEMENT DEMOLITION SHOWN ARE APPROXIMATE. COMPLETE PAVEMENT
DEMOLITION AND REPAIR AS REQUIRED TO FACILITATE WORK. RESTORE ALL SURFACES
TO MATCH EXISTING GRADES, MATERIALS, AND CONSTRUCTION TO THE SATISFACTION
OF THE LOCAL MUNICIPALITY AND NPS.
3. BACKFLOW PREVENTION WILL BE MANAGED AS PART OF THE FIRE PIPING INSIDE THE
BUILDING AND WILL BE HANDLED SEPARATELY FROM THE CIVIL PIPING INSTALLATION.
4. REFER TO SHEETS C-501 AND C-502 FOR TYPICAL DETAILS AS THEY PERTAIN TO THE
WORK.
5. COORDINATE FINAL PIPE ROUTING WITH INTERIOR FIRE SUPPRESSION CONNECTION
AND EXISTING UTILITIES.
EXISTING POTABLE WATER
SYSTEM (TYP)
FIRE SERVICE PLAN - EARLY HOME
SCALE: 1-1/2" = 1'-0"
SCALE IN FEET
0 0.5 1
1-1/2"=1' 7 9
311420
15' +/-
182686
04/26/2023
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY ROBERT F. HOYT, P.E. ON THE DATE LISTED IN THE SIGNATURE.
THE ABOVE NAMED PROFESSIONAL ENGINEER IS RESPONSIBLE FOR THE CONTENT CONTAINED ON THESE DRAWINGS
ACCORDANCE WITH RULE 61G15-23.044, F.A.C.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED. THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
NELSON ENGINEERING
5455 NORTH COURTENAY PARKWAY
MERRITT ISLAND, FL 32953
CERTIFICATE OF AUTHORIZATION #6822
E.O.R.: ROBERT F. HOYT, P.E., #89917
R O B E R T F . H O Y TL I C E N S E
F L O R I D A
STATE OF
P R O F E S S I O N A L E N G I N E E
R
AWWA C515 NRS
GATE VALVE
4-#5 E.W. HORIZONTAL
DUCTILE IRON MECHANICAL
JOINT ADAPTER
MECHANICAL JOINT
STAINLESS STEEL
NUTS AND BOLTS
CAST IRON VALVE BOX AND
COVER, AASHTO H20 RATED,
ADJUSTABLE TYPE
4000 PSI CONCRETE
INSTALL EXPANSION JOINT
AROUND PERIMETER WHEN
LOCATED IN PAVEMENT
CAST "WATER" IN VALVE
BOX LID
SUPPORT VALVE ON
PRECAST CONCRETE BLOCK(S)
3'-0"
6"
2' MIN.
2' MIN.
WIDTH OF TRENCH + 4' MIN.
2' MIN.
CL
12" STABILIZED SUBGRADE
LBR-100
MILL AND REPAVE 3/4" MIN.
TO 1" THICKNESS WITH
ASPHALT
SAW-CUT ASPHALT (TYP)
BITUMINOUS
PRIMER COAT
PRIME @ 0.10
GAL/S.Y.
EXISTING SUBGRADE
TACK AND SEAL EDGES AT
0.3 GAL/SY (TYP)
SUBGRADE COMPACTED TO 98%
MODIFIED PROCTOR MAXIMUM
DENSITY
EXISTING ASPHALT
EXISTING BASE
EXISTING SUBGRADE
PIPE BEDDING PIPE, CONDUIT OR DUCTBANK
2" ASPHALT (SEE NOTE 4)
W
PIPE
EMBEDMENT
FINAL BACKFILL
SLOPE
WIDEN TRENCH
AS REQUIRED
BURIED WARNING AND
IDENTIFICATION TAPE
12" MIN COVER
30" MIN12"
6"
NATIVE SOIL
SEWER CROSSING ABOVE WATER PARALLEL INSTALLATION
WATER CROSSING ABOVE SEWER
(PREFERRED METHOD)
WATER LINE
SEWER LINE
18" MIN
10'
MIN
10'
MIN
10'
MIN
10'
MIN
SEWER LINE
(WRITTEN APPROVAL REQ'D)
WATER LINE
5' MIN
WATER LINE
SEWER LINEOR > 10'
18" MIN
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
CIVIL DETAILS
EARLY HOMEC501
RFH
MH
RFH
TITLE OF SHEET
ANDREW JOHNSON NATIONAL HISTORIC SITE
A/E FIRM:
PRIME:
FISHER
ENGINEERING
CIVIL SUB:
NELSON
ENGINEERING
NelsonEngineeringCo.
5455 North Courtenay Pkwy
Merritt Island, FL 32953
(321) 449-1128 Fax (321) 449-1195 www.NelsonEngrCo.com
GATE VALVE DETAIL
SCALE: 1-1/2" = 1'-0"
FIBER REINFORCED CONCRETE
HAND HOLE
30" MIN COVER
1" CURB STOP
1" SCH 40
PVC SERVICE1" CURB STOP
DOUBLE STRAP S.S.
SERVICE SADDLE
WATER MAIN
#57 STONE
TYPICAL SAMPLE TAP ASSEMBLY
SCALE: NTS
NOTES:
1. MECHANICALLY SAWCUT ALL EDGES TO REMAIN.
2. REPLACE ASPHALT, BASE AND SUBGRADE WITH THE SAME TYPE AND THICKNESS OF MATERIALS
REMOVED IN ACCORDANCE WITH LOCAL DOT STANDARDS, OR AS APPROVED BY THE COR.
3. REPLACE EXISTING CURB AND GUTTER IN AREAS DISTURBED OR DAMAGED BY CONSTRUCTION
ACTIVITIES. MATCH ORIGINAL CURB/GUTTER PROFILE AND GRADES.
4. PROVIDE ASPHALT MATERIALS IN ACCORDANCE WITH SPECIFICATION SECTION 32 12 16. MATCH THE THICKNESS OF ADJACENT ROADWAY, BUT IN ALL CASES, PROVIDE A MINIMUM THICKNESS OF TWO (2)
INCHES.
5. LAP AND FEATHER ASPHALT PAVING JOINTS PERPENDICULAR TO ROADWAY TRAFFIC.
OVER TRENCH ASPHALT REPAIR DETAIL
SCALE: NTS
TYPICAL TRENCH DETAIL
SCALE: NTS
WATER SEWER CROSSING
SCALE: NTS
8 9
311420
NOTES:
1. TYPICAL DETAIL SHOWN FOR REFERENCE. SAMPLE TAPS ARE TO BE INSTALLED ONLY AS
REQUIRED FOR CONSTRUCTION. LOCATIONS ARE TO BE SELECTED BY THE CONTRACTOR
TO SUPPORT THEIR MEANS AND METHODS. UPON COMPLETION OF SAMPLING
ACTIVITIES AND LINE INSTALLATION, REMOVE SAMPLE TAP TO THE TAP STOP AND BURY.
2. HAND HOLE IS FOR REFERENCE IF LINE IS REQUIRED TO BE BACKFILLED PRIOR TO
ACCEPTANCE TESTING.
182686
04/26/2023
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY ROBERT F. HOYT, P.E. ON THE DATE LISTED IN THE SIGNATURE.
THE ABOVE NAMED PROFESSIONAL ENGINEER IS RESPONSIBLE FOR THE CONTENT CONTAINED ON THESE DRAWINGS
ACCORDANCE WITH RULE 61G15-23.044, F.A.C.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED. THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
NELSON ENGINEERING
5455 NORTH COURTENAY PARKWAY
MERRITT ISLAND, FL 32953
CERTIFICATE OF AUTHORIZATION #6822
E.O.R.: ROBERT F. HOYT, P.E., #89917
R O B E R T F . H O Y TL I C E N S E
F L O R I D A
STATE OF
P R O F E S S I O N A L E N G I N E E
R
TEE
REDUCER
RUN
RUN
HORIZONTAL BEND
BELL
RING
SECTION
PLAIN END
P.V.C. BELL JOINT
P.V.C.
CLAMPING
RING PLAIN END
P.V.C. M.J. D.I.
FITTINGS
UPPER BEND VERTICAL OFFSET PROFILE
LOWER BEND
BRANCH
VALVE DEAD END
F
EE
T
(M
IN
R
ES
TR
AI
N
ED
L
EN
G
TH
RESTRAINED BELL JOINT
RESTRAINED MECHANICAL JOINT
3' MIN
TEE BOLT TEE BOLT
NOTES:
1. ARROW INDICATES DIRECTION OF THRUST FORCE.
2. PROVIDE TWO (2) FEET MIN TOTAL LENGTH BETWEEN FIRST JOINTS
OR RESTRAINED LENGTH ON EITHER SIDE OF TEE (RUN).
LL L
L
L
L
L
L
L
L
PIPE SIZE &
MATERIAL
HORIZONTAL BEND VERTICAL VALVE OR
DEADEND REDUCER TEE
90 45 22.5 11.25 45
VALUES CORRESPOND TO "L" DIMENSION INDICATED IN DETAILS TO LEFT
4" DI 23 10 5 3 4 40 - - x 4" 35 4" PVC 28 12 6 3 7 62 - - x 4" 55
6" DI 31 13 7 4 6 56
x 4" 29 x 4" 33
- - x 6" 51
6" PVC 39 17 8 4 9 87
x 4" 45 x 4" 51
- - x 6" 80
8" DI 41 17 8 4 8 73
x 4" 52 x 4" 31 x 6" 31 x 6" 50
- - x 8" 68
8" PVC 51 21 11 5 12 114
x 4" 82 x 4" 48 x 6" 48 x 6" 78
- - x 8" 107
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
C502 04/26/2023
RFH
MH
RFH
TITLE OF SHEET
ANDREW JOHNSON NATIONAL HISTORIC SITE
A/E FIRM:
PRIME:
FISHER
ENGINEERING
CIVIL SUB:
NELSON
ENGINEERING
NelsonEngineeringCo.
5455 North Courtenay Pkwy
Merritt Island, FL 32953
(321) 449-1128 Fax (321) 449-1195 www.NelsonEngrCo.com
JOINT RESTRAINT
SCALE: NTS
JOINT RESTRAINT SCHEDULE
SCALE: NTS
NOTES:
VALUES ARE APPLICABLE FOR 200 PSI PRESSURE (TEST), SOIL TYPE SM, AND TRENCH TYPE 3.
ALL DIMENSIONS ARE REPORTED IN INCHES UNLESS OTHERWISE REPORTED.
THRUST BLOCKING MAY BE ELIMINATED BY PROVIDING THE PRESCRIBED RESTRAINED JOINT LENGTH IS PROVIDED
IN ALL PIPE RUNS.
A
B B
A
A
C
B
B
B
B
C
B
THE FIGURES IN THIS TABLE REPRESENT AREA OF CONCRETE BLOCKING
AGAINST THE VERTICAL TRENCH WALL OF UNDISTURBED EARTH IN SQUARE
FEET AT 2000 P.S.F. SOIL BEARING CAPACITY.
1. WRAP ALL FITTINGS WITH A MINIMUM 12 MIL POLYETHYLENE
FILM BEFORE POURING THRUST BLOCK, MAKING CERTAIN TO
KEEP CONCRETE AWAY FROM ALL BOLTS, GLANDS, AND
FLANGES.
2. THRUST BLOCKS TO BE POURED AGAINST UNDISTURBED
EARTH.
3. REQUIRED VOLUMES OF BEARING AREAS TO BE AS SHOWN IN
CHART. ADJUSTMENTS, IF NEEDED, WILL BE ALLOWED TO
CONFORM TO TEST PRESSURE AND ALLOWABLE SOIL BEARING
STRESS AS SHOWN IN
SPECIFICATIONS.
4. BEARING AREA FOR THRUST BLOCK ON HORIZONTAL BENDS IS
BASED ON A TEST PRESSURE OF 200 P.S.I. AND SOIL BEARING
STRESS OF 2,000 P.S.F. THE DEPTH TO THE THRUST BLOCK
BASE TO BE EQUAL TO OR GREATER THAN TWICE THE HEIGHT.
(EXAMPLE: IF BLOCK IS TWO (2) FEET DEEP, THE BASE IS TO BE
NO GREATER THAN FOUR (4) FEET BELOW GRADE.)
5. VERTICAL BEND THRUST BLOCKS TO BE THE SAME AS
HORIZONTAL BENDS.
6. BEARING AREA OF THRUST BLOCK TO BE NOT LESS THAN ONE
SQUARE FOOT.
THRUST BLOCK MIN BEARING AREA (SQ FT)
LETTER
PIPE SIZE (IN)
3" 4" 6" 8" 10" 12"
A 1.5 2.0 4.3 7.6 11.9 17.1
B (22.5°) 0.8 1.0 1.7 3.0 4.7 6.8
B (45°) 1.0 1.4 3.2 5.8 9.1 13.0
C 2.0 2.7 6.1 10.8 16.9 24.3
THRUST BLOCK DETAIL
SCALE: NTS
CIVIL DETAILS
EARLY HOME
9 9
311420
182686
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY ROBERT F. HOYT, P.E. ON THE DATE LISTED IN THE SIGNATURE.
THE ABOVE NAMED PROFESSIONAL ENGINEER IS RESPONSIBLE FOR THE CONTENT CONTAINED ON THESE DRAWINGS
ACCORDANCE WITH RULE 61G15-23.044, F.A.C.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED. THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
NELSON ENGINEERING
5455 NORTH COURTENAY PARKWAY
MERRITT ISLAND, FL 32953
CERTIFICATE OF AUTHORIZATION #6822
E.O.R.: ROBERT F. HOYT, P.E., #89917
R O B E R T F . H O Y TL I C E N S E
F L O R I D A
STATE OF
P R O F E S S I O N A L E N G I N E E
R
| Sheets |
| CS - COVER SHEET |
| FX101 - EARLY HOME FLOOR PLANS - FIRE PROTECTION |
| FX501 - DETAILS - FIRE PROTECTION - EARLY H. |
| FA101 - EARLY HOME FLOOR PLANS - FIRE ALARM |
| FA501 - DETAILS - FIRE ALARM - EARLY HOME |
| 2023-04-26T15:16:29-0500 | |
| Robert Hoyt |
| 2023-04-26T15:16:53-0500 | |
| Robert Hoyt |
| 2023-04-26T15:17:04-0500 | |
| Robert Hoyt |
| 2023-04-26T15:17:15-0500 | |
| Robert Hoyt |
File details come from the government source that posted it. Updated .