A04_Statement_of_Work.pdf

PDF 6 MB Posted

Attached to
Electrical Improvements, Lake Mead, NV Federal contract opportunity
Solicitation number
140P8122Q0054
Issued by
Department of the Interior National Park Service Pacific West Region

About this file

This statement of work describes electrical and physical security improvements required at a communications site within Lake Mead National Recreation Area. The project involves coordinating commercial power connection from Nevada Energy, installing electrical infrastructure including a utility demarcation point, breaker panel, and outlets, upgrading the existing solar power system, and adding a double-swing vehicle gate. Bidders must provide pricing for coordination with the utility provider, trenching and conduit installation, an H-frame and meter/disconnect, wiring between buildings, interior and exterior lighting, solar upgrades, and the vehicle gate. The related federal contract opportunity was issued by the Department of the Interior National Park Service Pacific West Region under solicitation number 140P8122Q0054 to obtain these improvements at the Consolidation Point site.

View the file

Other files for this federal contract opportunity

Other files attached to Electrical Improvements, Lake Mead, NV, newest first.
File Type Posted
B08_Contract_Price_Schedule.pdf PDF
Sol_140P8122Q0054.pdf PDF
B08_Transmittal.pdf PDF
A06_Nevada_Energy_Planning_Document.pdf PDF
B03_General_Decision_NV20220024.pdf PDF
B08_Release_of_Claims.pdf PDF
B08_Invoice_Payment_Request.docx DOCX document
A06_Nevada_Energy_Power_Availability.pdf PDF
A06_Nevada_Energy_Cost_Estimate.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Lake Mead National Recreation Area Consolidation Point

Electrical and Physical Security Improvements Statement of Work

The work involved with this project is to obtain a Commercial Power Connection in conjunction with Nevada Energy (NV Energy), installation of a Utility Demarcation, electrical upgrades to allow for Commercial Power Connection to the existing communications building and the installation of a 12ft wide double swing vehicle access gate in the existing chain link fence. The existing Consolidation Point communications site is located in the Callville Bay area of Lake Mead National Recreation area.

Detailed description of project requirements are:

1. Perform coordination with and execute the commercial power agreement for connection with NV Energy for a minimum of a 100amp single phase service.

a. NV Energy Project Number 3008671779

2. Provide required trenching and conduit from the NV Energy junction box which is located approximately 500ft from the communication sites proposed utility demarcation point depicted in the attached picture.

3. Provide and install a new Utility H Frame inside of the communications site existing chain-link fence in the approximate location shown on the attached pictures. New Utility H Frame to be tied into the existing grounding system.

4. Provide and install a utility meter and disconnect on the Utility H Frame.

5. Provide and install needed conduit and wire between the Utility H frame and the communications building.

6. Provide and install a new 100amp (minimum) breaker panel in the communications shelter.

7. Provide and install a minimum of four 2-way electrical outlets in the equipment building.

8. Provide and install an exterior AC Powered entry/security light that is controlled by an interior switch and a photo sensor on the light structure.

9. Provide and install two interior AC Powered light fixtures on the ceiling.

10. Provide needed upgrades for the existing solar power system to allow for the connection of the new commercial power service that results in the primary powering of the communications site and its equipment from commercial power with a combination of solar and back up generator providing the backup power of the sites equipment.

11. Provide and install a 12ft wide double swing vehicle gate in the existing east fence line and tie the gate into the existing grounding system.

Optional item:

1. Upgrade existing DC powered Airconditioning system to AC power.

2. Replace existing DC Powered Air Conditioner with a new AC powered unit.