8-25-049 E-1 Electrical Floor Plan-Layout.pdf

PDF 2 MB Posted

Attached to
Open Market Small Purchase IL|26-350SOS-PHYSE-P-94430
Contract number
26-350SOS-PHYSE-P-94430
Issued by
Illinois

About this file

Summary

This is an architectural electrical plan prepared by Evan Lloyd Associates, Inc. for the State of Illinois, specifically for the Stratton Building located at 401 S. Spring Street in Springfield, Illinois. The document pertains to the installation of new air handling units for the LPU Print Shop in the building's north end. The project is identified as No. 25-049, with a date signed of August 7, 2025, and an expiration date of November 30, 2026. The plan is drawn to a scale of 18" = 1'-0" and presents a partial basement electrical layout.

The scope of work involves electrical installation and modifications to support the new air handling units, including a new 60/50A-208V-1PH fused disconnect, extension of power wiring from the existing Federal Pacific panel on the first floor, installation of low voltage control wiring, and modifications to existing breakers and feeders. The electrical subcontractor must perform all work in accordance with the National Electrical Code and International Energy Code, utilize copper wiring with THWN, THHW, or THHN insulation, coordinate with mechanical drawings to avoid conflicts, provide a one-year written guarantee covering labor and materials from the date of substantial completion, and assume responsibility for cutting, patching, and sealing all electrical penetrations to maintain an air and water-tight seal.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E-1

BRH

© Evan Lloyd Associates, Inc.

TC

S

E

CRADE

IO

N

AT

TIMOTHY

B. SMITH

L

SN

E

IC

S

TIH

F

TE

O ILIL

001-017445

Date:

Drawn By:

Revised:

Revised:

Project No.

SHEET

OF SHEETS.

Date Signed:

Expiration Date:

S ou th Si xth S tre et

Sp rin gfi eld

, Il lin ois

Ph on e

7.7

.70

NE

W

A

IR

H

AN

DL

IN

G

UN

IT

S

FO

R

TH

E

LP

U

PR

IN

T

SH

OP

N

OR

TH

E

ND

ST

RA

TT

ON

B

UI

LD

IN

G

1 S . S

PR

IN

G

ST

SP

RI

NG

FI

EL

D, IL

LIN

OI

S

AUG. 7, 2025

25-049

AUG. 7, 2025

NOV. 30, 2026

SCALE: 18" = 1'-0"

PARTIAL BASEMENT ELECTRICAL PLAN

NO

RT

H

EXISTINGSTORAGE

EXISTING PRINTSHOP

EXISTING STORAGE

EXISTING SECURITYOFFICE EXISTING MECHANICALROOM

EXISTING LOADING/UNLOADING

EXISTING DOCKAREA

EXISTINGLOBBY

EXISTINGTOILET

EXISTING LOADINGDOCK

EXISTING ELEC.SHOP

EXISTING STORAGE

EXISTINGCORRIDOR

EXISTING POST OFFICE

EXISTING SECURITYOFFICE

EXISTINGCORRIDOR

NEW 50A-208V-1PH

HEAT PUMP (HP-1)

NEW 60/50A-208V-1PH

FUSED DISCONNECT.

EXTEND (4) #3 & (1) #8 GRD. IN 1 1/4" C.

UP TO THE EXISTING FEDERAL PACIFIC PANEL

LOCATED ON THE FIRST FLOOR ABOVE

AND CONNECT TO THE EXISTING 3P-100A

BREAKER IN PANEL.

EXISTING PANEL.

NEW .68A-208V-1PH AIR

HANDLING UNIT (AHU-1)

NEW .68A-208V-1PH AIR

HANDLING UNIT (AHU-2)

NEW LOW VOLTAGE CONTROL

WIRING RUN ALONG WALL.

(2) #4 & (1) #10

GRD. IN 1" C.

(2) #16 & (1) #10

GRD. IN 3/4" C.

AT CEILING

EXISTING ELECTRICAL

SHOP PANEL

SCALE: N.T.S.

KEY PLAN

NO

RT

H

PROJECT AREA

ALL WORK SHALL BE PERFORMED BY AN CERTIFIED ELECTRICIAN. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, THE INTERNATIONAL ENERGY CODE AND ALL REGULATIONS, LAWS AND ORDINANCES WHICH MAY BE APPLICABLE. SEE COVER SHEET G-1 FOR LATEST

ADOPTED EDITIONS.

THE ELECTRICAL SUBCONTRACTOR SHALL REFER TO ARCHITECTURAL AMD MECHANICAL DRAWINGS DURING

BIDDING AND CONSTRUCTION TO AVOID ANY AND ALL CONFLICTS.

ALL POWER WIRE IS TO BE COPPER WITH "THWN", THHW" OR "THHN" INSULATION. TYPE "AC", "BX", "NM" CABLES WILL NOT BE PERMITTED ON THIS PROJECT. ALL EXPOSED CONDUIT SHALL BE "EMT" TYPE CONDUIT WITH SET SCREW OR COMPRESSION FITTINGS FOR ALL PANEL FEEDERS AND HOME RUNS BACK TO PANELS. ALL FLEXIBLE CONDUIT CAN BE "MC" OR NON-METALLIC FLEXIBLE CONDUIT WITH APPROVED FITTINGS AND BOXES.

THE ELECTRICAL SUBCONTRACTOR IS RESPONSIBLE FOR ALL HANGERS, CLIPS, MOUNTING HARDWARE, ETC.

THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL POWER WIRING. COORDINATE WITH RESPECTIVE

CONTRACTOR FOR EQUIPMENT WIRING AND CONTROLS.

THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL SAFETY SWITCHES NOT FACTORY INSTALLED WITH

EQUIPMENT, AND MAKE FINAL CONNECTIONS TO EQUIPMENT.

ELECTRICAL SUBCONTRACTOR SHALL COORDINATE BREAKER AND WIRING SIZING WITH EQUIPMENT PRIOR TO INSTALLING, AND IF ANY DISCREPANCIES ARE FOUND, THE CONTRACTOR SHALL CORRECT AT NO COST TO THE

TENANT.

THE ELECTRICAL SUBCONTRACTOR SHALL VERIFY VOLTAGE AND PHASE OF EQUIPMENT PRIOR TO ROUGH-INS.

THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE A REVISED TYPED PANEL INDEX FOR THE EXISTING

PANELS.

THE ELECTRICAL SUBCONTRACTOR SHALL SEAL ALL ELECTRICAL PENETRATIONS THRU EXTERIOR WALL TO

MAINTAIN AN AIR AND WATER TIGHT SEAL.

THE ELECTRICAL SUBCONTRACTOR SHALL BE RESPONSIBLE FOR HIS OWN CUTTING AND PATCHING.

COORDINATE WITH THE GENERAL CONTRACTOR.

THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL THE ELECTRICAL CONDUITS A MINIMUM OF 6" ABOVE CEILING

GRID.

PER THE NEC 408.4 ALL BRANCH CIRCUITRY SHALL BE IDENTIFIED WITH A TAG TO INDICATE THE CIRCUIT AND PANEL TO WHICH IT IS SERVED FROM, TYPICAL FOR ALL SWITCHES, JUNCTION BOXES, CONVENIENCE OUTLETS, ETC.

THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE THE USING AGENCY A WRITTEN ONE (1) YEAR GUARANTEE COVERING ALL LABOR AND MATERIALS FURNISHED AND INSTALLED AS PART OF THIS PROJECT. GUARANTEE

SHALL COMMENCE FROM THE DATE OF SUBSTANTIAL COMPLETION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

GENERAL ELECTRICAL NOTES

REMOVE THE EXISTING UNUSED

BREAKER AND REPALCE WITH

A NEW 2P-50A BREAKER.

J

REMOVE PORTIONS OF THE

EXISTING FEEDERS FROM THE

EXISTING SHOP PANEL.

PROVIDE A NEW JUNCTION BOX

AND CONNECT TO THE EXISTING

LPU PANEL FEEDERS WITH NEW.

THE EXISTING LPU

PANEL FEEDER

SHALL REMAIN.

THE EXISTING SHOP PANEL

FEEDER SHALL REMAIN.

EXISTING OPENING

IN CEILING.