7-25-049 HV-1 HVAC Floor Plan-Layout.pdf
PDF 2 MB Posted
- Contract number
- 26-350SOS-PHYSE-P-94430
- Issued by
- Illinois
About this file
Document Summary
This is an HVAC design and construction document prepared by Evan Lloyd Associates, Inc. for a project located at the Stratton Building, 401 S. Spring Street, Springfield, Illinois. The project is sponsored by the State of Illinois for the installation of new air handling units in the LPU Print Shop North End. The document is dated August 7, 2025, with project number 25-049 and an expiration date of November 30, 2026.
The scope of work includes the installation of two new air handling units (AHU-1 and AHU-2), each rated at 800 CFM, and one heat pump unit rated at 48,000 BTUH cooling capacity. The HVAC contractor is responsible for providing shop drawings, installing all equipment per manufacturer specifications and the 2018 International Mechanical Code, furnishing a one-year guarantee covering labor and materials from the date of substantial completion, and providing operation and maintenance manuals. All condensate piping must be Schedule 40 PVC with solvent-welded connections. The contractor must provide a minimum of three sets of shop drawings and is required to perform all work as indicated on the drawings with any field changes made at no additional cost. Work encompasses new suction and liquid refrigerant lines, condensate drain lines pitched to existing floor drains, electrical connections at 208 volts, and thermostat controls with specific wiring configurations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
HV-1
TCR
© Evan Lloyd Associates, Inc.
TC
S
E
CRADE
IO
N
AT
TIMOTHY
B. SMITH
L
SN
E
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Si xth S tre et
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
NE
W
A
IR
H
AN
DL
IN
G
UN
IT
S
FO
R
TH
E
LP
U
PR
IN
T
SH
OP
N
OR
TH
E
ND
ST
RA
TT
ON
B
UI
LD
IN
G
1 S . S
PR
IN
G
ST
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
AUG. 7, 2025
25-049
AUG. 7, 2025
NOV. 30, 2026
SCALE: 18" = 1'-0"
PARTIAL BASEMENT HVAC PLAN
NO
RT
H
EXISTINGSTORAGE
EXISTING PRINTSHOP
EXISTING STORAGE
EXISTING SECURITYOFFICE EXISTING MECHANICALROOM
EXISTINGTOILET
EXISTING LOADINGDOCK
HP
48,000 BTUH
COOLING
D
D
D
D
RISE UP ABOVE THE CEILING
AND RUN AS HIGH AS POSSIBLE.
HVAC CONTRACTOR SHALL REMOVE
PORTIONS OF THE EXISTING CEILING
TO INSTALL THE NEW CONDENSATE
DRAIN LINE ABOVE THE CEILING.
EXTEND TO NEAREST
EXISTING FLOOR DRAIN.
AHU
800 CFM
AHU
800 CFM
RUN NEW 5/8" PVC DRAIN LINE
FROM EACH UNIT HIGH ON WALL.
EXISTING STORAGE
EXISTINGCORRIDOR
EXISTING POST OFFICE
EXISTING SECURITYOFFICE
NEW 5/8" PVC DRAIN LINE
FROM EACH UNIT.D
PITCH DN.
PITCH DN.
EXISTINGCORRIDOR
RUN NEW SUCTION LINE AND LIQUID LINE
HIGH ON WALL, RUN ONE ABOVE THE OTHER.
USAGE
AREA OF
710 3/4
O/A
DUCT
HP
PHASE
AHU-1
MARK COOLING
AIR HANDLING UNIT SCHEDULE
CFM
COOLING
HIGH SPEED
.50"
( KW-BTUH)
HEATING CAPACITYE.S.P. COIL
VOLT.
CONFIG.
UNIT REMARKS
HORIZONTAL
AMPS
.63N/A
AND MODEL NUMBER
MANUFACTURER
TRANE TPKFYP024KM142B GENERAL
1, 2, 3
PROVIDE MOUNTING WALL BRACKET, MOUNT UNIT 1'-0" BELOW CEILING.
PROVIDE A CONDENSATE PUMP.
PIPE CONDENSATE DRAIN LINES PER MANUFACTURER'S REQUIREMENTS.
1.
2.
3.
REMARKS:
3/4710AHU-2 .50" GENERAL- N/A 1
HORIZONTAL
HORIZONTALHORIZONTAL 208.63
SEER
MIN.
TRANE NTXMSM48A182BA
MARK
HEAT PUMP SCHEDULE
REMARKSAND MODEL NUMBER
MANUFACTURER
28.0
COOLING CAPACITY
NOMINAL
PHASE
VOLT.
208 1HP-1 AHU-1 & 2
UNIT
INDOOR
AMPS
MOCD
50.048,000 1, 2, 3, 4
PROVIDE PRE-CHARGED REFRIGERANT LINE SETS W/
3/4" INSULATION.
PROVIDE WALL MOUNTING BRACKET.
1.
2.
REMARKS:
PROVIDE LOCKED, TAMPER RESISTANT CAPS ON THE
REFRIGERANT LINES PER THE I.M.C. M110.10
MOUNT THE TOP OF THE UNIT AT 8'-0" A.F.F.
3.
4.
AHU-1
TYPICAL HEATING AND
COOLING THERMOSTAT
NTXMSM48A182BA
TB7L1L2L3
TB3 G DIP SWITCH 3-7 OFF
(S)
J1 P1
L1L2 G
CN105 TB5 TB15
16-2 AWG (S)
L1L2 G
CN105 TB5 TB15
TPKFYP024KM142B TPKFYP024KM142B
MIFH2 MIFH2
MRCH2 MRCH2
SCALE: N.T.S.
AHU-1 & 2 REFRIGERANT & CONTROL WIRING DIAGRAM
GRD.
DIAGRAM SYMBOL LEGEND
DISPLAY DESCRIPTION
CONTROL WIRE
REF. PIPE
TRANE TPKFYP024KM142B
AHU-2
SCALE: N.T.S.
KEY PLAN
NO
RT
H
PROJECT AREA
GENERAL HVAC NOTES
HVAC CONTRACTOR SHALL NOT SCALE THE DRAWINGS FOR EQUIPMENT SIZES. HVAC CONTRACTOR SHALL OBTAIN THE LATEST SHOP DRAWINGS FROM THE MANUFACTURER FOR EACH PIECE OF EQUIPMENT AND USE IT FOR ACTUAL DIMENSIONS.
ALL WORK SHALL BE PERFORMED BY A HVAC CONTRACTOR EXPERIENCED IN THE TRADE. HVAC CONTRACTOR SHALL INSTALL SYSTEMS, EQUIPMENT AND COMPONENTS IN ACCORDANCE WITH MINIMUM REQUIREMENTS SHOWN IN THESE PLANS. ANY DEVIATION FROM THE DESIGN PLANS SHALL ONLY BE PERFORMED IF APPROVED BY THE ARCHITECT. ALL WORK SHALL MEET OR EXCEED THE MINIMUM REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. HOWEVER, ANY DEVIATION FROM THE DESIGN PLANS IMPLIED BY LOCAL CODES THAT SUGGESTS INSTALLATION OF LESS THAN THE REQUIREMENTS SPECIFIED IN THESE DESIGN PLANS SHALL NOT BE ALLOWED WITHOUT APPROVAL BY THE ARCHITECT.
ALL THE HVAC WORK SHALL BE INSTALLED PER THE 2018 INTERNATIONAL MECHANICAL CODE AND THE 2021 INTERNATIONAL
ENERGY CONSERVATION CODE.
THE HVAC SUBCONTRACTOR SHALL PROVIDE A MINIMUM OF 3 SETS OF SHOP DRAWINGS: 1 SET FOR THE USING AGENCY, 1 SET FOR THE ARCHITECT AND 1 SET FOR THEMSELVES. THE HVAC CONTRACTOR SHALL ALSO PROVIDE AN OPERATION AND
MAINTENANCE MANUAL FOR THE OWNER.
THE HVAC SUBCONTRACTOR SHALL PROVIDE THE OWNER WITH A WRITTEN ONE (1) YEAR GUARANTEE COVERING ALL LABOR AND MATERIALS FURNISHED AND INSTALLED AS PART OF THIS PROJECT. THE GUARANTEE SHALL COMMENCE FROM THE DATE
OF SUBSTANTIAL COMPLETION.
THE HVAC SUBCONTRACTOR SHALL INSTALL THE NEW EQUIPMENT PER THE MANUFACTURER REQUIREMENTS.
ALL WORK SHALL BE PERFORMED AS INDICATED ON DRAWINGS UNLESS FIELD CONDITIONS REQUIRE MINOR CHANGES SHALL
BE MADE WITH NO ADDITIONAL COST.
ALL CONDENSATE PIPING SHALL BE SCHEDULE 40 PVC PIPING AND FITTINGS WITH SOLVENT WELDED CONNECTIONS.
1.
2.
3.
4.
5.
6.
7.
8.