This file consists of approved electrical construction plans and specifications for HVAC Phase B improvements at Davis Technical College, prepared by the State of Utah Division of Facilities Construction and Management (DFCM) in coordination with Resolut Group. The project involves the replacement of rooftop HVAC units and associated electrical infrastructure in a high bay area, with a construction cost estimate of $300,000. The electrical scope includes four roof-top units (RTUs) with capacities ranging from 21.6 to 23.2 full-load amperes at 208V three-phase, along with disconnects, overcurrent protection, conduit routing, and weatherproof receptacles. The plans contain comprehensive electrical symbol schedules, installation details, equipment schedules, and demolition plans showing existing conditions to remain and new installations. The document was reviewed for code compliance by Thomas Peterson on September 18, 2025, and reflects Phase B of a multi-phase project identified as Project #250481 and #26079220.
This is a Stage II Invitation to Bid project, restricted to contractors who have completed Stage I prequalification and remain on the DFCM Prequalified Contractors list as of the solicitation date. The electrical work must comply with local and state codes, the National Electrical Code (NEC), and includes requirements for copper THHN/THWN-2 conductors, EMT conduit with steel fittings, equipment grounding conductors, tamper-resistant receptacles, and comprehensive labeling and documentation. The electrical contractor is responsible for coordinating with mechanical, plumbing, and general contractors; providing all materials and labor for complete and operable systems; testing system functionality; managing conduit routing and support; and delivering updated panel circuit directories with unique descriptions. No specific bid submission deadline or award date is provided in the technical plans document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
09/18/2025
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
EG001
ELECTRICAL
NOTES &
SYMBOLS
CURRENT/ISSUE DATE:
DRAWN BY:
CHECKED BY:
RESOLUT PROJECT #:
SHEET CONTENTS
REVISIONS
KC
250481
08/19/2025
D A
TC
PH
A
SE
B
H
IG
H B
A Y
H
VA
C
IM
PR
O
VE
M
EN
TS
KA
YS
VI
LL
E, U
TA
H
A
B
C
D
1 2 3 4 5
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
Project #:
40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com
250481
KEY PLAN
TS
ELECTRICAL SYMBOL SCHEDULE
SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING
2x4 LINEAR LIGHT FIXTURE CEILING (1) (2) (3) (16)
2x4 LINEAR EMERGENCY LIGHT FIXTURE CEILING (1) (2) (3) (16)
RECESSED LIGHT FIXTURE (1) (3) CEILING
RECESSED EMERGENCY LIGHT FIXTURE (1) (3) CEILING
RECESSED WALL WASH LIGHT FIXTURE (1) (3) CEILING
CEILING LIGHT FIXTURE (1) (2) CEILING
PENDANT/CHANDELIER LIGHT FIXTURE (1) (2) (3)SUSPENDED
WALL LIGHT FIXTURE, SURFACE (1) (2) AS NOTED
WALL LIGHT FIXTURE, RECESSED AS NOTED (1) (2)
TRACK LIGHT FIXTURE WITH TRACK (1) (2) (3)CEILING
SUSPENDEDCEILING FAN
FLOOD/LANDSCAPE/MONUMENT LIGHT FIXTURE (1) (2) (3)GROUND
AREA LIGHT FIXTURE (1) (2)POLE
EXIT SIGN, WALL, ARROW INDICATES DIRECTION (1) (2) (4) (5)7'-6"
(1) (4) (5)CEILINGEXIT SIGN, ARROW INDICATES DIRECTION
EMERGENCY LIGHT FIXTURE, WALL 7'-6" (1) (2)
PHOTO-ELECTRIC CELLP AS NOTED
POWER PACK CEILINGPP
SLAVE PACK CEILINGSP
MINI POWER PACK CEILINGMP
(7)CEILINGDUAL TECHNOLOGY VACANCY SENSOR
DUAL TECHNOLOGY VAC. SENSOR, WALL (7)AS NOTED
DUAL TECHNOLOGY VAC. SENSOR SWITCH, 1-ZONE (7)4'-0"
DUAL TECHNOLOGY VAC. SENSOR SWITCH, 2-ZONE (7)4'-0"
DAYLIGHT SENSOR CEILING
BOLLARD LIGHT GROUND
PASSIVE INFRARED SENSOR CEILING
SINGLE POLE SWITCHS 4'-0"
DOUBLE POLE, SINGLE THROW SWITCHS 4'-0"2
THREE WAY SWITCH 4'-0"S
4'-0"aS
3 THREE WAY SWITCH ATTRIBUTE SIGNIFIES FIXTURE
SWITCHING
4'-0"FOUR WAY SWITCHS
DUAL LEVEL SWITCH BANK 4'-0"SS
DIMMER SWITCH 4'-0"S
LOW VOLTAGE SWITCH 4'-0"S
(15)KEYED SWITCH, SINGLE POLE 4'-0"S
K
TIMER SWITCH, SINGLE POLE 4'-0" (15)S
T
TIME CLOCK AS NOTEDTC
LIGHTING CONTROL PANEL, SURFACE 6'-6" TO TOP
LIGHTING CONTROL PANEL, RECESSED 6'-6" TO TOP
(S) (S) SIMPLEX (D) DUPLEX (Q) QUADPLEX OR DOUBLE DUPLEX(D) (Q)
STANDARD CONVENIENCE OUTLET 18"
CONVENIENCE OUTLET, GFCI 18"
STANDARD CONVENIENCE OUTLET, HOSPITAL 18"18"
STANDARD CONVENIENCE OUTLET, SWITCHED 18"
STANDARD CONVENIENCE OUTLET, CUSTOM HEIGHT (6)
48"UNLESS
NOTED
CONVENIENCE OUTLET, GFCI, CUSTOM HEIGHT (6)
48"UNLESS
NOTED
CONVENIENCE OUTLET, ISOLATED GROUND 18"
CONVENIENCE OUTLET, FLOOR FLOOR
CONVENIENCE OUTLET, CEILING CEILING
2 CIRCUITS TO EACH DEVICE 18"
COMBINATION POWER AND COMMUNICATION FLOOR BOX FLOOR
SPECIAL PURPOSE OUTLET
DIRECT CONNECTION TO EQUIPMENT
CORD DROP OUTLET SUSPENDEDD
POWER/VOICE-DATA SERVICE POLE AS NOTED
DJU DISTRIBUTION JUNCTION UNIT
VFD VARIABLE FREQUENCY DRIVE
SURGE PROTECTION DEVICESPD
J JUNCTION BOX AS NOTED (12)
J JUNCTION BOX, WALL AS NOTED (12)
J JUNCTION BOX, FLOOR FLOOR (12)
C CLOCK OUTLET (*)
S
M MANUAL MOTOR CONTROLLER SWITCH WITHOUT
TERMINAL OVERLOAD PROTECTION
SWITCH WITH PILOT LIGHTS
P
MANUAL SWITCH WITH THERMAL OVERLOADS
TH
SINGLE POLE DOOR SWITCHS
X
PUSH BUTTON SWITCH, SINGLE AS NOTED
PUSH BUTTON SWITCH, DOUBLE AS NOTED
BUSH BUTTON SWITCH, TRIPLE AS NOTED
EMERGENCY POWER OFF (EPO) SWITCH
NON-FUSED DISCONNECT SWITCH (13) (14)
FUSED DISCONNECT SWITCH (13) (14)
MAGNETIC STARTER (13) (14)
MAGNETIC STARTER WITH FUSED DISCONNECT (13) (14)
MAGNETIC STARTER WITH BREAKER DISCONNECT (13) (14)
POWER RELAY (13) (14)
MOTOR OUTLET
MOTOR OUTLET, ROOF MOUNTED ROOF
LIGHTNING PROTECTION AIR TERMINAL ROOF
LIGHTNING PROTECTION BOND PLATE
LIGHTNING PROTECTION GROUND ROD GROUND
UTILITY POWER POLE SEE PLANS
TRANSFORMER SEE PLANS
TRANSFORMER SEE PLANS
EMERGENCY GENERATOR SEE PLANS
CABLE TRAY
MAIN DISTRIBUTION POWER PANEL
PANEL BOARD, SURFACE 6'-6" TO TOP
PANEL BOARD, RECESSED 6'-6" TO TOP
TELEPHONE OUTLET, SINGLE PORT 18"
TELEPHONE OUTLET, SINGLE OUTLET, CUSTOM HEIGHT (6)(6)
DATA OUTLET, DUAL PORT 18"
DATA OUTLET, DUAL PORT, CUSTOM HEIGHT (6)(6)
DUAL DATA AND SINGLE TELEPHONE PORT 18"
DUAL DATA AND SINGLE TELEPHONE PORT,
CUSTOM HEIGHT (6)
# DATA OUTLET, ATTRIBUTE SIGNIFIES PORT QUANTITY 18"
TELEPHONE OUTLET, SINGLE PORT, FLOOR MOUNTED FLOOR
DATA OUTLET, DUAL PORT, FLOOR MOUNTED FLOOR
TELEVISION OUTLET AS NOTED (6) (11)
NURSE CALL STATION, SINGLE BED 4'-11" (11)
NURSE CALL STATION, DOUBLE BED 4'-11" (11)
NURSE CALL STATION, EMERGENCY 4'-11" (11)
NURSE CALL STATION, CODE BLUE 4'-11" (11)
NURSE CALL STATION, MICROPHONE/SPEAKER UNIT 4'-11" (11)
NURSE CALL PULL CHAIN AS NOTED
NURSE CALL DOME LIGHT CEILING (11)
NURSE CALL DOME LIGHT, WALL WALL (11)
SPEAKER CEILING
SPEAKER, WALL AS NOTED (11)
VOLUME CONTROL, WALL 4'-0" (11)
MICROPHONE, WALL AS NOTED (11)
MICROPHONE, FLOOR FLOOR
BELL, WALL AS NOTED
CHIME, WALL AS NOTED
SECURITY CAMERA, FIXED, WALL AS NOTED (11)
SECURITY CAMERA, PTZ, WALL AS NOTED (11)
CR CARD READER 4'-0" (11)
MAIN DISTRIBUTION FRAME 6'-6" TO TOPMDF
INTERMEDIATE DISTRIBUTION FRAME 6'-6" TO TOPIDF
MAIN TELEPHONE BOARD 6'-6" TO TOP
SECURITY PANEL, SURFACE AS NOTED
SECURITY PANEL, RECESSED AS NOTED
SECURITY CAMERA, FIXED CEILING
SECURITY CAMERA, PTZ CEILING
SMOKE DETECTOR CEILING (9) (11)
SMOKE DETECTOR, LOW FREQUENCY, SOUNDER BASE CEILING (9)CEILING (9)
SMOKE DETECTOR, LOW FREQUENCY, SOUNDER BASE, WALL 7'-6" (9) (11)7'-6" (9) (11)
SMOKE DETECTOR, SOUNDER BASE, VISUAL IND. CEILING (9)
SMOKE DETECTOR, SOUNDER BASE, VISUAL IND., WALL 7'-6" (9) (11)
DUCT SMOKE DETECTOR SEE MECH. (9)
FSD FIRE/SMOKE DAMPER SEE MECH.FIRE/SMOKE DAMPER SEE MECH.
HEAT DETECTOR CEILING (9) (11)
BEAM DETECTOR, RECEIVER (9)
BEAM DETECTOR, TRANSMITTER (9)
BEAM DETECTOR, RECEIVER/TRANSMITTER (9)
BEAM DETECTOR, REFLECTOR (9)
FLAME DETECTOR (9)
FIRE FIGHTER TELEPHONE OUTLET (9) (11)
F FIRE ALARM MANUAL PULL STATION (9) (11)4'-0"
# (9) (11)FIRE ALARM STROBE, ATTRIBUTE SIGNIFIES
CANDELA RATING 7'-6"
FIRE ALARM HORN (9) (11)7'-6"
# (9) (11)7'-6"FIRE ALARM HORN STROBE, ATTRIBUTE SIGNIFIES
CANDELA RATING
FIRE ALARM SPEAKER (9) (11)7'-6"
(9) (11)7'-6"# FIRE ALARM SPEAKER STROBE, ATTRIBUTE SIGNIFIES
CANDELA RATING
F FIRE SPRINKLER FLOW BELL 7'-6" AFF (9)
F FIRE ALARM CHIME AS NOTED (9)
ELECTRO MAGNETIC DOOR HOLDER AS NOTED
RM RELAY MODULE (9)
MONITOR MODULE (9)MM
CONTROL MODULE (9)CM
PRESSURE SWITCH (9)PS
TAMPER SWITCH (9)TS
FLOW SWITCH (9)FS
LOOP ISOLATION MODULE (9)IM
FIRE EXTINGUISHER MONITOR (9)XM
FIRE RISER SEE PLANS
FIRE ALARM PANEL, SURFACE (15)AS NOTED
FIRE ALARM PANEL, RECESSED (15)AS NOTED
XX
X MECHANICAL/PLUMBING EQUIPMENT CALLOUT
KITCHEN EQUIP. CALLOUT, OR AS NOTED BY ARCH.
X KITCHEN EQUIP. CALLOUT, OR AS NOTED BY ARCH.
LUMINAIRE TYPE
X
XX.X DIAGRAM/DETAIL CALLOUT
CONDUIT RUN CONCEALED IN WALL OR CEILING
CONDUIT RUN CONCEALED IN FLOOR OR GROUND
SURFACE RACEWAY/WIREMOLD
LOW VOLTAGE CONDUIT RUN
DEMOLITION
EXISTING
HOME RUN TO PANEL
CONDUIT STUB
CONDUIT BREAK/CONTINUATION
CONDUIT STUB DOWN
CONDUIT STUB UP
FUSE
GROUND/GROUND ROD
CIRCUIT BREAKER
A AMPS
AFC AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPS INTERR. CAPACITY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
C CONDUIT
CND CONDUIT
CO CONDUIT ONLY
CT CURRENT TRANSDUCER
CU COPPER MATERIAL
DED DEDICATED
DFA DROP FROM ABOVE
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EM EMER./EGRESS BATTERY
EMT ELEC. METALLIC TUBING
ENT ELEC. NON-METAL. TUBING
ER EXISTING TO BE RELOCATED
EX EXISTING TO REMAIN
FMC FLEXIBLE METAL CONDUIT
GC GENERAL CONTRACTOR
GEC GRND. ELEC. COND. AT SES
GFCI GRND. FLT. CURR. INTERR.
GFEP GRND. FLT. EQUIP. PROTECT.
GND GROUND
IMC INTER. METAL CONDUIT
IG ISOLATED GROUND
KCMIL 1000 CIRCULAR MILS (MCM)
LFMC LIQUID-TIGHT FLEX.
METAL. COND.
LFNC LIQUID-TIGHT FLEX.
NON-METAL. COND.
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
N1 NEMA 1
N3R NEMA 3R
N NEW
NL NIGHT LIGHT, BYPASS
LOCAL SWITCHING
PC PLUMBING CONTRACTOR
POC POINT OF CONNECTION
POS POINT OF SALE
R RELOCATED
RX RECEIVER
RM ROOF MOUNTED
RMC RIGID METALLIC CONDUIT
RNC RIGID NON-METALLIC COND.
SBJ SYSTEM BONDING JUMPER
SCA SHORT CIRCUIT AMPERES
TX TRANSMITTER
TC TEMP. CONTROL CONTR.
TR TAMPERPROOF
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
VA VOLT/AMPS
VIF VERIFY IN FIELD
WP WEATHERPROOF/NEMA 3R
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
ABBREVIATIONS
(1) SEE LUMINAIRE SCHEDULE FOR FIXTURE TYPES AND DETAILS.
(2) SEE LUMINAIRE SCHEDULE FOR MOUNTING REQUIREMENTS.
(3) WIRE LIGHT FIXTURE FROM ADJACENT J-BOX
(4) CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST
(5) DIRECTIONAL ARROWS INDICATE REQUIRED CHEVRONS.
(6) COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL INTERIOR ELEVATIONS
(7) USE WITH POWER PACK.
(8) "X" IN SYMBOL IS INCHES BETWEEN RECEPTACLE ALONG WIREWAY. SEE DRAWINGS.
(9) PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
(10) MATCH THE VOLTAGE OF THE RELAY WITH THAT OF THE CONTROLLING CIRCUIT.
(11) USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE AND INSTALLATION.
(12) PROVIDE MUD RING AND/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
(13) USE HEAVY DUTY DEVICE FOR 480 VOLT.
(14) SIZE TO THE EQUIPMENT BEING CONTROLLED
(15) FIRE ALARM PANELS: FACP: FIRE ALARM CONTROL PANEL, NAC: NOTIFICATION APPLIANCE CIRCUIT PANEL, ANNUN: GRAPHIC ANNUNCIATOR PANEL, AND SES: SMOKE EVACUATION SYSTEM PANEL.
(16) LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
(17) PROVIDE 5' OF SERVICE LOOP AND TERMINATE IN 2-PORT SURFACE MOUNT BOX.
NOTESNOTES
ELECTRICAL SYMBOL SCHEDULE
SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING
ELECTRICAL SYMBOL SCHEDULE
SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING
ELECTRICAL SYMBOL SCHEDULE
SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING
POKETHRU
ECU EMERGENCY CONTROL UNIT CEILING
DOOR CONTACT 4'-0" (11)D
REQUEST TO EXIT 4'-0" (11)X
KEYPAD 4'-0" (11)K
ELECTRIC HINGE 4'-0" (11)H
ELECTRIC LATCH 4'-0" (11)L
ELECTRIC STRIKE 4'-0" (11)S
BIOMETRIC READER 4'-0" (11)B
2x2 LINEAR EMERGENCY LIGHT FIXTURE CEILING (1) (2) (3) (16)
CEILING2x2 LINEAR LIGHT FIXTURE (1) (2) (3) (16)
CEILING WI-FI ACCESS POINT, DUAL DATA PORT CEILING (17)CEILING WI-FI ACCESS POINT CEILING
TOUCH PANEL 4'-0"TP
CORD REEL OUTLET SUSPENDEDCR
ANNUNCIATOR PANEL (9)ANN
GAP GENERATOR ANNUNCIATOR PANEL SEE PLANS
ATS AUTOMATIC TRANSFER SWITCH SEE PLANS
POKE THRU, POWER FLOOR
POKE THRU, POWER AND DATA FLOOR
POKE THRU, POWER AND DATA W/AV FLOORJ
(9) (11)CEILING# CEILING MOUNT FIRE ALARM SPEAKER STROBE,
ATTRIBUTE SIGNIFIES CANDELA RATING
(9) (11)CEILING# CEILING MOUNT FIRE ALARM HORN STROBE,
ATTRIBUTE SIGNIFIES CANDELA RATING
(9) (11)CEILING# CEILING MOUNT FIRE ALARM STROBE,
ATTRIBUTE SIGNIFIES CANDELA RATING
DUAL TECHNOLOGY VAC. SENSOR WITH DIMMER, WALL (7)AS NOTED
(7)4'-0"DUAL TECHNOLOGY VAC. SENSOR SWITCH WITH DIMMER,
1-ZONE
(9) (11)CEILINGCEILING MOUNT FIRE ALARM HORN
SECURITY MOTION SENSOR CEILING/WALL (6) (11)SECURITY MOTION SENSOR CEILING/WALL (6) (11)M
2x4 LINEAR CRITICAL LIGHT FIXTURE CEILING (1) (2) (3) (16)
2x2 LINEAR CRITICAL LIGHT FIXTURE CEILING (1) (2) (3) (16)
EQUIPMENT CONNECTION
FIRE ALARM, LOW FREQUENCY, VISUAL AS NOTED (9)
FIRE ALARM, LOW FREQUENCY, NON-VISUAL AS NOTED (9)
NOTIFICATION APPLIANCE CONTROL PANEL (15)NAC
CARBON MONOXIDE DETECTOR CEILING (9) (11)CO
ROOM CONTROLLER CEILINGRC
BOLLARD LIGHT, POLE TOP AREA LIGHT POLE (1) (2)
DUPLEX OUTLET, POP-UP COUNTERTOP
CONVENIENCE OUTLET, GFCI, CUSTOM HEIGHT, HOSPITAL (6)
48"UNLESS
NOTED
LOW VOLTAGE DIMMER SWITCH 4'-0"S
SCENE CONTROLLER 4'-0"SC
PARTITION SENSOR CEILINGPS
EV CHARGEREV
GENERAL NOTES
1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT DOCUMENTS AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION OR CONFLICT EXIST IN EITHER THE PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING HIS BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIER SHALL SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS AT THEIR OWN EXPENSE. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE, THE CONTRACTOR SHALL TEST AND CONFIRM IT'S PROPER OPERATION. ANY INCOMPLETE SYSTEM
SHALL BE MADE COMPLETE AND OPERABLE.
2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE
GREATER THAN SPECIFIED AND/OR DIMENSIONED ON THE PLANS.
3. NO ADDITIONS TO THE CONTRACTOR BID WILL BE ALLOWED FOR CHANGES MADE NECESSARY BY INTERFERENCE WITH OTHER WORK.
4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS AND LABOR FOR THE CONNECTIONS OF ALL EQUIPMENT
SHOWN ON THE PLANS - ARCHITECTURAL, MECHANICAL, ETC.
5. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH LOCAL AND STATE CODES AND THE NEC. IF AT ANY TIME DURING CONSTRUCTION, OR AFTER, SOMETHING IS FOUND TO BE INSTALLED IN VIOLATION OF THE CODES LISTED ABOVE, IT SHALL BE
CORRECTED AT THE CONTRACTORS EXPENSE.
6. ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE CONDITIONS AND SPACE THAT
EQUIPMENT IS BEING INSTALLED WITHIN.
7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED FROM. VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BREAKERS AS NECESSARY FOR A
COMPLETE AND OPERABLE SYSTEM.
8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELE/DATA ROOM FROM WHICH NEW TELE/DATA OUTLETS WILL BE FED FROM. VERIFY EXISTING PATCH PANEL SPACES AND PROVIDE NEW PATCH PANELS AS NECESSARY TO
LAND ALL NEW TELE/DATA CABLING.
9. THE ELECTRICAL CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE ELECTRICAL CONTRACTOR SHALL GROUND THE ELECTRICAL
SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.
10. THE ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS, CABINETS, DISCONNECT, TRANSFORMERS, ETC. AND SHALL MOVE THE PANELS/EQUIPMENT AT HIS EXPENSE IF REJECTED BY AN INSPECTOR. IF CLEARANCE IS NOT POSSIBLE, THE DESIGNER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.
11. CONDUIT LAYOUTS SHOWN ON THE PLANS ARE DIAGRAMMATIC, NOT INDICATING THE ROUTING REQUIRED. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT, BUILDING STRUCTURE AND OTHER POTENTIAL OBSTRUCTIONS.
12. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE
OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.
13. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY STANDARD
METHODS AND PRACTICES.
14. MINIMUM SIZE CONDUIT SHALL BE 3/4". ABOVE GROUND CONDUIT SHALL BE EMT WITH STEEL SET SCREW FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN DIRECT
CONTACT WITH THE SOIL.
15. FLEXIBLE METAL CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR SEAL-TITE CONDUIT SHALL NOT EXCEED 72” INCHES. USE LFMC IN DAMP
OR WET LOCATIONS.
16. WIRING DEVICES SHALL MATCH EXISTING COLOR AND FACEPLATE TYPE. COLOR TO MATCH ADJACENT ARCHITECTURAL FINISH.
COORDINATE WITH ARCHITECT.
17. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE APPLICATION. ANY DEVICE BOXES NOT SECURED WILL BE MADE SECURE AT THE CONTRACTORS
EXPENSE.
18. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB RATED NYLON PULL CORD.
19. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS, WALLS, ETC.), THEY SHALL BE APPROVED BY THE INSPECTING OFFICER (INSPECTOR). THE UNCOVERING AND REPLACEMENT OF ELECTRICAL WORK FOR THE INSPECTION PURPOSES WILL
BE AT THE COST OF THE ELECTRICAL CONTRACTOR.
20. ALL BATTERY POWERED OR CONTINUOUS BURN LUMINAIRES SHOWN ON THE PLANS, SUCH AS EXIT LIGHTS, NIGHT LIGHTS, OR EMERGENCY LIGHTS, SHALL BE CONNECTED TO THE UN-SWITCHED LEG OF THE LIGHTING CIRCUIT FEEDING THAT AREA.
21. LUMINAIRES INSTALLED IN THE MECHANICAL ROOM SHALL BE PLACED SO THAT ALL EQUIPMENT IS ADEQUATELY ILLUMINATED AFTER
THE MECHANICAL EQUIPMENT IS IN PLACE.
22. ALL LUMINAIRES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND NOT SOLELY FROM THE CEILING GRID OR OTHER
NONSTRUCTURAL MEMBER.
23. TO MAINTAIN CONSISTENT LIGHT QUALITY, LUMINAIRES SHALL BE OF THE SAME SURFACE TEMPERATURE AND COLOR RENDERING INDEX, LUMINAIRE TYPES SHALL BE OF THE SAME MANUFACTURER AND LUMEN OUTPUT.
24. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120 OR 277VAC BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12(CU,THHN/THWN-2)+1#12(CU,THHN/THWN-2)GND IN 3/4” EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10(CU,THHN) FOR 120VAC BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 100' TO ACCOMMODATE FOR VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES AND NOTES ON DRAWINGS FOR ALL OTHER BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.
25. CONDUCTORS SHALL BE COPPER STRANDED, 600VAC RATED, TYPE THHN/THWN-2 UNLESS OTHERWISE NOTED.
26. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS, WIRES, AND OVERCURRENT PROTECTION PRIOR TO ROUGH-IN. THE ELECTRICAL CONTRACTOR SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE EQUIPMENT SUPPLIER.
27. THE ELECTRICAL CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE
ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FROM THE PREMISES.
28. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE
OF EQUIPMENT AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.
29. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE
MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS.
30. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED WITH THE
ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL BE MADE TO CONCEAL WIRING METHODS.
31. PROVIDE AN UPDATED, TYPED PANEL CIRCUIT DIRECTORY FOR ALL PANELS WHERE CIRCUITS HAVE BEEN MODIFIED, ADDED, OR REMOVED BY THE SCOPE OF THIS PROJECT. CIRCUIT DESCRIPTIONS ON THE DIRECTORY SHALL BE UNIQUE AND INDICATE THE ROOM AND EQUIPMENT/DEVICE IT IS FEEDING. DATE DIRECTORY WITH PROJECT COMPLETION DATE. MODIFIED CIRCUITS TO BE IN BOLD.
32. PROVIDE A CLEAR, TYPED LABEL ON THE FACEPLATE OF ALL RECEPTACLES AND LIGHT SWITCHES INDICATING THE CIRCUIT IT IS TIED TO.
USE LABELING CONVENTION XX-xx, WHERE "XX" IS THE NAME OF THE PANEL AND "xx" IS THE BRANCH CIRCUIT NUMBER. LABELS LENGTH
SHALL NOT EXCEED 1/4" ON EITHER SIDE OF TEXT.
33. FUSED DISCONNECTS TO BE HEAVY DUTY.
34. FURNISH AND INSTALL TAMPER-RESISTANT RECEPTACLES FOR 120V RECEPTACLES IN AREAS SPECIFIED 210.52 OF THE NEC AND AS
REQUIRED UNDER 403.12 OF THE NEC.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
EG501
ELECTRICAL
DETAILS
CURRENT/ISSUE DATE:
DRAWN BY:
CHECKED BY:
RESOLUT PROJECT #:
SHEET CONTENTS
REVISIONS
KC
250481
08/19/2025
D A
TC
PH
A
SE
B
H
IG
H B
A Y
H
VA
C
IM
PR
O
VE
M
EN
TS
KA
YS
VI
LL
E, U
TA
H
A
B
C
D
1 2 3 4 5
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
Project #:
40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com
250481
KEY PLAN
TS
REFER TO SECTION
FOR ATTACHMENT
OF ALL THREAD
ROD TO KINDORF
CHANNEL 1 1/2"x1 1/2"-12GA. KINDORF
CHANNEL OR APPROVED
SUBSTITUTE
3/8" ALL THREAD,
MINIMUM. INCREASE
ROD SIZE IF WEIGHT
REQUIRES PER ROD
MANUFACTURERS
RECOMMENDATIONS.
SUPPORT CONDUIT
WITH KINDORF
STRAP OR
APPROVED
SUBSTITUTE.
BEAM CLAMPS OR
HANGER CLAMPS
AS REQUIRED BY
WEIGHT
SUPPORTED
PROVIDE 25% SPACE
CAPACITY
NUT
WASHER
WASHER
NUT
EG501
8 TRAPEZE SUPPORT DETAIL
NO SCALE
EG501 NO SCALE
ROOF TOP UNIT DETAIL
NOTE:
1. COORDINATE ROOF PENETRATIONS AND MATERIALS
REQUIREMENTS WITH ROOF CONTRACTOR PRIOR TO
ROUGH-IN.
2. REMOVE ALL EXISTING FLASHING, LEAD, ETC. PIPE
SURFACE MUST BE FREE OF ALL RUST, GREASE,
INSULATION, ETC.
3. CONDUIT MUST BE ANCHORED TO STRUCTURE
BELOW TO ENSURE STABILITY.
4. PRE-MOLD PIPE FLASHING MAY BE CUT TO HEIGHT,
BUT NO LOWER THEN REINFORCING RING. NO
WRINKLES OR FOLDS UNDER CLAMPING RING.
5. APPLY LAP SEALANT BETWEEN PENETRATION AND
PRE-MOLD PIPE FLASHING PRIOR TO INSTALLATION
OF CLAMPING RING.
STAINLESS STEEL
CLAMP RING
CONDUIT
ROOF
MEMBRANE
BONDING
ADHESIVE PRE-MOLDED
PIPE FLASHING
FIELD FABRICATED
METAL HOOD BY
OTHER (OPTIONAL)
HIGH GRADE
SEALANT
EG501 NO SCALE
ROOF PENETRATION DETAIL
EQUIPMENT SCHEDULE
TYPE DESCRIPTION
ELECTRICAL OVER CURRENT PROTECTION STR
REMARKSVOLT PHASE LOAD FLA
WIRE COND OCPD/
TYPE
DISCONNECT FUSE NEMA
SETS QTY SIZE GND SIZE MOCP SIZE POLE SIZE SIZE
RTU - 1 ROOF-TOP UNIT 208 3 29.00 MCA 23.2 1 3 8 10 3/4 35 C1 60 3 35 - 9 A 14A
RTU - 2 ROOF-TOP UNIT 208 3 29.00 MCA 23.2 1 3 8 10 3/4 35 C1 60 3 35 - 9 A 14A
RTU - 3 ROOF-TOP UNIT 208 3 29.00 MCA 23.2 1 3 8 10 3/4 35 C1 60 3 35 - 9 A 14A
RTU - 4 ROOF-TOP UNIT 208 3 27.00 MCA 21.6 1 3 8 10 3/4 35 C1 60 3 35 - 9 A
ABBREVIATIONS:
KW = KILOWATTS VA = VOLT AMPERES OCPD = OVERCURRENT PROTECTIVE DEVICE
V/PH = VOLTAGE/PHASE KVA = KILOVOLT AMPERES GND = GROUND COND = CONDUIT
HP = HORSEPOWER FLA = FULL LOAD AMPERES STR = STARTER MOCP = MAXIMUM OCPD (LISTED BY THE MANUFACTURER)
W = WATTS MCA = MINIMUM CIRCUIT AMPACITY PL = POLE
REMARKS: REMARKS:
1. NEMA 1 FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED AND CONNECTED UNDER DIVISION 26.
2. NEMA 1 NON-FUSED DISCONNECT SWITCH B. FURNISHED AND INSTALLED UNDER ANOTHER DIVISION REQUIRING CONNECTION UNDER DIV 26.
3. BREAKER IN ENCLOSURE C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED AND CONNECTED UNDER DIV 26.
4. MANUAL STARTER WITH THERMAL OVERLOAD D. FURNISHED, INSTALLED AND CONNECTED UNDER ANOTHER DIVISION.
5. MANUAL MOTOR CONTROLLER W/OUT THERMAL OVERLOAD E. FURNISHED AND INSTALLED UNDER DIV 26 REQUIRING CONNECTION UNDER ANOTHER DIVISION.
6. MAGNETIC STARTER
7. MAGNETIC STR/NON-FUSED DISCONNECT COMBINATION OCPD TYPES:
8. MAGNETIC STR/FUSED DISCONNECT COMBINATION C1 = THERMAL MAGNETIC CIRCUIT BREAKER
9. NEMA 3R FUSED DISCONNECT SWITCH C2 = MAGNETIC ONLY CIRCUIT BREAKER
10. NEMA 3R NON-FUSED DISCONNECT SWITCH
11. VARIABLE FREQUENCY DRIVE NOTES:
12. RECEPTACLE/SPECIAL PURPOSE OUTLET/ETC. - THE DIVISION 26 CONTRACTOR MAY INCREASE THE CONDUIT SIZE BY ONE INCREMENTAL SIZE TO FACILITATE
INSTALLATION OR TO HELP WITH MATERIAL AVAILABILITY/COST.13. DIRECT CONNECTION
14. DUCT DETECTOR IN RETURN AIR DUCT. PROVIDE RELAY/CONTROL MODULE AND 120V POWER AS REQUIRED TO
TIE TO FIRE ALARM FOR AUTOMATIC SHUT OFF.
15. CONTROLLED WITH LIGHTS
16. LM-EB DISCONNECT W/CNTRL WIRING TO VFD
17. SPLIT SYSTEM. INDOOR UNIT FED FROM OUTDOOR UNIT.
GENERAL NOTE: THE EC SHALL COORDINATE ALL REQUIREMENTS (IE: MOCP SIZE, UNIT THERMAL PROTECTION, ETC) WITH APPROVED MECHANICAL SHOP DRAWINGS/SUBMITTALS AND BRING UP ANY DISCREPANCIES WITH THE ELECTRICAL
ENGINEER OF RECORD IN WRITING PRIOR TO ROUGH-IN AND ORDERING OF MATERIALS.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
RTU
(E)
RTU
(E)
RTU
(E)
RTU
(E)
CURRENT/ISSUE DATE:
DRAWN BY:
CHECKED BY:
RESOLUT PROJECT #:
SHEET CONTENTS
REVISIONS
KC
250481
08/19/2025
D A
TC
PH
A
SE
B
H
IG
H B
A Y
H
VA
C
IM
PR
O
VE
M
EN
TS
KA
YS
VI
LL
E, U
TA
H
A
B
C
D
1 2 3 4 5
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
Project #:
40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com
250481
KEY PLAN
TS
SCALE:
ED103 1/8"=1'-0"
ROOF POWER DEMOLITION PLAN
ED103
ROOF
POWER
DEMOLITION
PLAN
GENERAL NOTES
A. EC SHALL COORDINATE WITH ALL OTHER TRADES
DURING DEMOLITION AND CONSTRUCTION TO
FACILITATE TIMELY WORK.
B. ALL AREAS ARE TO BE KEPT CLEAN AND CLEAR OF
DEBRIS AT ALL TIMES.
C. CONTRACTOR SHALL PATCH AND REPAIR ALL WALLS,
CEILINGS ETC. TO MATCH EXISTING CONDITIONS.
PENETRATIONS SHALL BE SEALED WITH FIRE RATED
CAULK.
D. ROUTE ALL CONDUIT IN A NEAT AND ORDERLY FASHION.
ALL CONDUIT SHALL BE CONCEALED ABOVE CEILINGS
OR IN WALLS OR FINISHED SPACES UNLESS OTHERWISE
INDICATED ON THE PLANS.
E. DEVICES SHOWN ON DEMOLITION SHEETS ARE
GATHERED FROM AS-BUILT DRAWINGS AND FIELD
INVESTIGATION. NOT ALL DEVICES ARE SHOWN. DEVICE
PLACEMENT IS SCHEMATIC AND NOT EXACT.
CONTRACTOR TO FIELD VERIFY FOR EXACT LOCATIONS
AND COORDINATE WORK WITH ALL OTHER DEVICES,
EQUIPMENT, CONDUIT, ETC. WHETHER OR NOT SHOWN
TO COMPLETE PROJECT.
F. CONTRACTOR TO COORDINATE WITH OWNER FOR ITEMS
TO BE SALVAGED PRIOR TO DEMOLITION. CONTRACTOR
RESPONSIBLE FOR DISPOSING OF ANY MATERIAL THAT
THE OWNER DOES NOT WANT TO KEEP.
G. CAP AND LABEL ALL EMPTY CONDUIT TO REMAIN.
H. DEVICES/EQUIPMENT SHOWN IN GRAY ARE EXISTING TO
REMAIN. PRESERVE AND PROTECT. MAINTAIN EXISTING
CIRCUIT INTEGRITY.
KEYED NOTES#
1. ROOF TOP UNITS TO BE REMOVED AND REPLACED BY
MECHANICAL CONTRACTOR. EC TO DISCONNECT EQUIPMENT
AND VERIFY CONDUIT AND CONDUCTORS ARE IN GOOD
WORKING CONDITION FOR NEW EQUIPMENT.
2. EC SHALL DEMOLISH EXISTING SERVICE RECEPTACLE ON
ROOF TOP UNIT. VERIFY CIRCUIT INTEGRITY AND PREPARE
CIRCUIT FOR REUSE.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
RTU
RTU
RTU
RTU
EF
(E)
EF
(E)1
TYP
WP
WP
WP
WP
E103
ROOF
POWER
PLAN
CURRENT/ISSUE DATE:
DRAWN BY:
CHECKED BY:
RESOLUT PROJECT #:
SHEET CONTENTS
REVISIONS
KC
250481
08/19/2025
D A
TC
PH
A
SE
B
H
IG
H B
A Y
H
VA
C
IM
PR
O
VE
M
EN
TS
KA
YS
VI
LL
E, U
TA
H
A
B
C
D
1 2 3 4 5
181 East 5600 South Murray, UT 84107
801.530.3148 T
801.530.3150 F
Project #:
40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com
250481
KEY PLAN
TS
SCALE:
E103 1/8"=1'-0"
ROOF POWER PLAN
GENERAL NOTES
A. EC SHALL COORDINATE WITH ALL OTHER TRADES
DURING DEMOLITION AND CONSTRUCTION TO
FACILITATE TIMELY WORK.
B. ALL AREAS ARE TO BE KEPT CLEAN AND CLEAR OF
DEBRIS AT ALL TIMES.
C. CONTRACTOR SHALL PATCH AND REPAIR ALL WALLS,
CEILINGS ETC. TO MATCH EXISTING CONDITIONS.
D. ROUTE ALL CONDUIT IN A NEAT AND ORDERLY FASHION.
ALL CONDUIT IN FINISHED SPACES SHALL BE
CONCEALED ABOVE CEILINGS OR IN WALLS UNLESS
OTHERWISE INDICATED ON THE PLANS.
E. BRANCH CIRCUITS SHALL NOT EXCEED 3% VOLTAGE
DROP.
F. PROVIDE UPDATED TYPED CIRCUIT DIRECTORY WITH
UNIQUE CIRCUIT DESCRIPTIONS PER NEC 408.4 FOR
PANELS AFFECTED BY THIS PROJECT.
G. PROVIDE HOUSEKEEPING PADS FOR ALL FLOOR
MOUNTED AND GRADE MOUNTED ELECTRICAL
EQUIPMENT. MINIMUM REQUIREMENTS: 4" HIGH, 4% AIR
ENTRAINED, POLYFIBER REINFORCED CONCRETE, 4"
WIDER AND 4" LONGER THAN EQUIPMENT TO BE PLACED
ON IT. REFER TO ELECTRICAL DETAIL DRAWINGS FOR
TRANSFORMER, GENERATOR, OR SWITCHGEAR PADS
THAT MAY EXCEED THESE REQUIREMENTS.
H. WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT
SHOWN. PROVIDE PROPER NUMBER OF CONDUCTORS
TO ACHIEVE CIRCUIT AND SWITCHING CONNECTIONS
SHOWN.
I. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO
BREAKERS. BRANCH CIRCUITS SHALL BE SIZED
ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS
INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT
SCHEDULE.
J. DEVICES/EQUIPMENT SHOWN IN GRAY ARE EXISTING TO
REMAIN. PRESERVE AND PROTECT. MAINTAIN EXISTING
CIRCUIT INTEGRITY.
KEYED NOTES#
1. NEW MECHANICAL EQUIPMENT CAN BE RECONNECTED TO
EXISTING CIRCUITS IF THE EXISTING CIRCUITS MEET THE
REQUIREMENTS SHOWN ON THE EQUIPMENT SCHEDULE AND
ARE IN GOOD WORKING ORDER. IF EXISTING CONDITIONS DO
NOT MEET THE EQUIPMENT SCHEDULE REQUIREMENTS, THAN
EC SHALL PROVIDE NEW BREAKER, CONDUIT AND
CONDUCTORS AS INDICATED. ALL NEW BREAKERS SHALL
MATCH AIC RATING OF EXISTING PANEL BOARDS.
2. EC SHALL PROVIDE A SERVICE RECEPTACLE WITHIN 25 FEET
EACH RTU. RECEPTACLES SHALL HAVE WEATHERPROOF IN
USE COVER.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
| G001 COVER SHEET |
| M001 SYMB AND LEGENDS |
| MD101 MECH DEMO PLAN |
| MD102 MECH DEMO PLAN |
| MD103 ROOF MECH DEMO PLAN |
| M103 ROOF MECH PLAN |
| M501 MECH DETAILS |
| M601 MECH SCHED |
| 20250819.1_250481_Davis Tech High Bay Phase B |
| EG001 ELECTRICAL NOTES & SYMBOLS |
| EG501 ELECTRICAL DETAILS |
| ED103 ROOF POWER DEMOLITION PLAN |
| E103 ROOF POWER PLAN |