7-2-CS26071-26079220-Approved Plans.pdf

PDF 6 MB Posted

Attached to
DFCM Construction - Prequalified Mechanical Stage II - Davis Technical College - High Bay HVAC Phase B - Project #26079220
Solicitation number
CS26071
Issued by
Davis County, Utah

About this file

This file consists of approved electrical construction plans and specifications for HVAC Phase B improvements at Davis Technical College, prepared by the State of Utah Division of Facilities Construction and Management (DFCM) in coordination with Resolut Group. The project involves the replacement of rooftop HVAC units and associated electrical infrastructure in a high bay area, with a construction cost estimate of $300,000. The electrical scope includes four roof-top units (RTUs) with capacities ranging from 21.6 to 23.2 full-load amperes at 208V three-phase, along with disconnects, overcurrent protection, conduit routing, and weatherproof receptacles. The plans contain comprehensive electrical symbol schedules, installation details, equipment schedules, and demolition plans showing existing conditions to remain and new installations. The document was reviewed for code compliance by Thomas Peterson on September 18, 2025, and reflects Phase B of a multi-phase project identified as Project #250481 and #26079220.

This is a Stage II Invitation to Bid project, restricted to contractors who have completed Stage I prequalification and remain on the DFCM Prequalified Contractors list as of the solicitation date. The electrical work must comply with local and state codes, the National Electrical Code (NEC), and includes requirements for copper THHN/THWN-2 conductors, EMT conduit with steel fittings, equipment grounding conductors, tamper-resistant receptacles, and comprehensive labeling and documentation. The electrical contractor is responsible for coordinating with mechanical, plumbing, and general contractors; providing all materials and labor for complete and operable systems; testing system functionality; managing conduit routing and support; and delivering updated panel circuit directories with unique descriptions. No specific bid submission deadline or award date is provided in the technical plans document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

THOMAS PETERSON

09/18/2025

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

EG001

ELECTRICAL

NOTES &

SYMBOLS

CURRENT/ISSUE DATE:

DRAWN BY:

CHECKED BY:

RESOLUT PROJECT #:

SHEET CONTENTS

REVISIONS

KC

250481

08/19/2025

D A

TC

PH

A

SE

B

H

IG

H B

A Y

H

VA

C

IM

PR

O

VE

M

EN

TS

KA

YS

VI

LL

E, U

TA

H

A

B

C

D

1 2 3 4 5

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

Project #:

40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com

250481

KEY PLAN

TS

ELECTRICAL SYMBOL SCHEDULE

SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING

2x4 LINEAR LIGHT FIXTURE CEILING (1) (2) (3) (16)

2x4 LINEAR EMERGENCY LIGHT FIXTURE CEILING (1) (2) (3) (16)

RECESSED LIGHT FIXTURE (1) (3) CEILING

RECESSED EMERGENCY LIGHT FIXTURE (1) (3) CEILING

RECESSED WALL WASH LIGHT FIXTURE (1) (3) CEILING

CEILING LIGHT FIXTURE (1) (2) CEILING

PENDANT/CHANDELIER LIGHT FIXTURE (1) (2) (3)SUSPENDED

WALL LIGHT FIXTURE, SURFACE (1) (2) AS NOTED

WALL LIGHT FIXTURE, RECESSED AS NOTED (1) (2)

TRACK LIGHT FIXTURE WITH TRACK (1) (2) (3)CEILING

SUSPENDEDCEILING FAN

FLOOD/LANDSCAPE/MONUMENT LIGHT FIXTURE (1) (2) (3)GROUND

AREA LIGHT FIXTURE (1) (2)POLE

EXIT SIGN, WALL, ARROW INDICATES DIRECTION (1) (2) (4) (5)7'-6"

(1) (4) (5)CEILINGEXIT SIGN, ARROW INDICATES DIRECTION

EMERGENCY LIGHT FIXTURE, WALL 7'-6" (1) (2)

PHOTO-ELECTRIC CELLP AS NOTED

POWER PACK CEILINGPP

SLAVE PACK CEILINGSP

MINI POWER PACK CEILINGMP

(7)CEILINGDUAL TECHNOLOGY VACANCY SENSOR

DUAL TECHNOLOGY VAC. SENSOR, WALL (7)AS NOTED

DUAL TECHNOLOGY VAC. SENSOR SWITCH, 1-ZONE (7)4'-0"

DUAL TECHNOLOGY VAC. SENSOR SWITCH, 2-ZONE (7)4'-0"

DAYLIGHT SENSOR CEILING

BOLLARD LIGHT GROUND

PASSIVE INFRARED SENSOR CEILING

SINGLE POLE SWITCHS 4'-0"

DOUBLE POLE, SINGLE THROW SWITCHS 4'-0"2

THREE WAY SWITCH 4'-0"S

4'-0"aS

3 THREE WAY SWITCH ATTRIBUTE SIGNIFIES FIXTURE

SWITCHING

4'-0"FOUR WAY SWITCHS

DUAL LEVEL SWITCH BANK 4'-0"SS

DIMMER SWITCH 4'-0"S

LOW VOLTAGE SWITCH 4'-0"S

(15)KEYED SWITCH, SINGLE POLE 4'-0"S

K

TIMER SWITCH, SINGLE POLE 4'-0" (15)S

T

TIME CLOCK AS NOTEDTC

LIGHTING CONTROL PANEL, SURFACE 6'-6" TO TOP

LIGHTING CONTROL PANEL, RECESSED 6'-6" TO TOP

(S) (S) SIMPLEX (D) DUPLEX (Q) QUADPLEX OR DOUBLE DUPLEX(D) (Q)

STANDARD CONVENIENCE OUTLET 18"

CONVENIENCE OUTLET, GFCI 18"

STANDARD CONVENIENCE OUTLET, HOSPITAL 18"18"

STANDARD CONVENIENCE OUTLET, SWITCHED 18"

STANDARD CONVENIENCE OUTLET, CUSTOM HEIGHT (6)

48"UNLESS

NOTED

CONVENIENCE OUTLET, GFCI, CUSTOM HEIGHT (6)

48"UNLESS

NOTED

CONVENIENCE OUTLET, ISOLATED GROUND 18"

CONVENIENCE OUTLET, FLOOR FLOOR

CONVENIENCE OUTLET, CEILING CEILING

2 CIRCUITS TO EACH DEVICE 18"

COMBINATION POWER AND COMMUNICATION FLOOR BOX FLOOR

SPECIAL PURPOSE OUTLET

DIRECT CONNECTION TO EQUIPMENT

CORD DROP OUTLET SUSPENDEDD

POWER/VOICE-DATA SERVICE POLE AS NOTED

DJU DISTRIBUTION JUNCTION UNIT

VFD VARIABLE FREQUENCY DRIVE

SURGE PROTECTION DEVICESPD

J JUNCTION BOX AS NOTED (12)

J JUNCTION BOX, WALL AS NOTED (12)

J JUNCTION BOX, FLOOR FLOOR (12)

C CLOCK OUTLET (*)

S

M MANUAL MOTOR CONTROLLER SWITCH WITHOUT

TERMINAL OVERLOAD PROTECTION

SWITCH WITH PILOT LIGHTS

P

MANUAL SWITCH WITH THERMAL OVERLOADS

TH

SINGLE POLE DOOR SWITCHS

X

PUSH BUTTON SWITCH, SINGLE AS NOTED

PUSH BUTTON SWITCH, DOUBLE AS NOTED

BUSH BUTTON SWITCH, TRIPLE AS NOTED

EMERGENCY POWER OFF (EPO) SWITCH

NON-FUSED DISCONNECT SWITCH (13) (14)

FUSED DISCONNECT SWITCH (13) (14)

MAGNETIC STARTER (13) (14)

MAGNETIC STARTER WITH FUSED DISCONNECT (13) (14)

MAGNETIC STARTER WITH BREAKER DISCONNECT (13) (14)

POWER RELAY (13) (14)

MOTOR OUTLET

MOTOR OUTLET, ROOF MOUNTED ROOF

LIGHTNING PROTECTION AIR TERMINAL ROOF

LIGHTNING PROTECTION BOND PLATE

LIGHTNING PROTECTION GROUND ROD GROUND

UTILITY POWER POLE SEE PLANS

TRANSFORMER SEE PLANS

TRANSFORMER SEE PLANS

EMERGENCY GENERATOR SEE PLANS

CABLE TRAY

MAIN DISTRIBUTION POWER PANEL

PANEL BOARD, SURFACE 6'-6" TO TOP

PANEL BOARD, RECESSED 6'-6" TO TOP

TELEPHONE OUTLET, SINGLE PORT 18"

TELEPHONE OUTLET, SINGLE OUTLET, CUSTOM HEIGHT (6)(6)

DATA OUTLET, DUAL PORT 18"

DATA OUTLET, DUAL PORT, CUSTOM HEIGHT (6)(6)

DUAL DATA AND SINGLE TELEPHONE PORT 18"

DUAL DATA AND SINGLE TELEPHONE PORT,

CUSTOM HEIGHT (6)

# DATA OUTLET, ATTRIBUTE SIGNIFIES PORT QUANTITY 18"

TELEPHONE OUTLET, SINGLE PORT, FLOOR MOUNTED FLOOR

DATA OUTLET, DUAL PORT, FLOOR MOUNTED FLOOR

TELEVISION OUTLET AS NOTED (6) (11)

NURSE CALL STATION, SINGLE BED 4'-11" (11)

NURSE CALL STATION, DOUBLE BED 4'-11" (11)

NURSE CALL STATION, EMERGENCY 4'-11" (11)

NURSE CALL STATION, CODE BLUE 4'-11" (11)

NURSE CALL STATION, MICROPHONE/SPEAKER UNIT 4'-11" (11)

NURSE CALL PULL CHAIN AS NOTED

NURSE CALL DOME LIGHT CEILING (11)

NURSE CALL DOME LIGHT, WALL WALL (11)

SPEAKER CEILING

SPEAKER, WALL AS NOTED (11)

VOLUME CONTROL, WALL 4'-0" (11)

MICROPHONE, WALL AS NOTED (11)

MICROPHONE, FLOOR FLOOR

BELL, WALL AS NOTED

CHIME, WALL AS NOTED

SECURITY CAMERA, FIXED, WALL AS NOTED (11)

SECURITY CAMERA, PTZ, WALL AS NOTED (11)

CR CARD READER 4'-0" (11)

MAIN DISTRIBUTION FRAME 6'-6" TO TOPMDF

INTERMEDIATE DISTRIBUTION FRAME 6'-6" TO TOPIDF

MAIN TELEPHONE BOARD 6'-6" TO TOP

SECURITY PANEL, SURFACE AS NOTED

SECURITY PANEL, RECESSED AS NOTED

SECURITY CAMERA, FIXED CEILING

SECURITY CAMERA, PTZ CEILING

SMOKE DETECTOR CEILING (9) (11)

SMOKE DETECTOR, LOW FREQUENCY, SOUNDER BASE CEILING (9)CEILING (9)

SMOKE DETECTOR, LOW FREQUENCY, SOUNDER BASE, WALL 7'-6" (9) (11)7'-6" (9) (11)

SMOKE DETECTOR, SOUNDER BASE, VISUAL IND. CEILING (9)

SMOKE DETECTOR, SOUNDER BASE, VISUAL IND., WALL 7'-6" (9) (11)

DUCT SMOKE DETECTOR SEE MECH. (9)

FSD FIRE/SMOKE DAMPER SEE MECH.FIRE/SMOKE DAMPER SEE MECH.

HEAT DETECTOR CEILING (9) (11)

BEAM DETECTOR, RECEIVER (9)

BEAM DETECTOR, TRANSMITTER (9)

BEAM DETECTOR, RECEIVER/TRANSMITTER (9)

BEAM DETECTOR, REFLECTOR (9)

FLAME DETECTOR (9)

FIRE FIGHTER TELEPHONE OUTLET (9) (11)

F FIRE ALARM MANUAL PULL STATION (9) (11)4'-0"

# (9) (11)FIRE ALARM STROBE, ATTRIBUTE SIGNIFIES

CANDELA RATING 7'-6"

FIRE ALARM HORN (9) (11)7'-6"

# (9) (11)7'-6"FIRE ALARM HORN STROBE, ATTRIBUTE SIGNIFIES

CANDELA RATING

FIRE ALARM SPEAKER (9) (11)7'-6"

(9) (11)7'-6"# FIRE ALARM SPEAKER STROBE, ATTRIBUTE SIGNIFIES

CANDELA RATING

F FIRE SPRINKLER FLOW BELL 7'-6" AFF (9)

F FIRE ALARM CHIME AS NOTED (9)

ELECTRO MAGNETIC DOOR HOLDER AS NOTED

RM RELAY MODULE (9)

MONITOR MODULE (9)MM

CONTROL MODULE (9)CM

PRESSURE SWITCH (9)PS

TAMPER SWITCH (9)TS

FLOW SWITCH (9)FS

LOOP ISOLATION MODULE (9)IM

FIRE EXTINGUISHER MONITOR (9)XM

FIRE RISER SEE PLANS

FIRE ALARM PANEL, SURFACE (15)AS NOTED

FIRE ALARM PANEL, RECESSED (15)AS NOTED

XX

X MECHANICAL/PLUMBING EQUIPMENT CALLOUT

KITCHEN EQUIP. CALLOUT, OR AS NOTED BY ARCH.

X KITCHEN EQUIP. CALLOUT, OR AS NOTED BY ARCH.

LUMINAIRE TYPE

X

XX.X DIAGRAM/DETAIL CALLOUT

CONDUIT RUN CONCEALED IN WALL OR CEILING

CONDUIT RUN CONCEALED IN FLOOR OR GROUND

SURFACE RACEWAY/WIREMOLD

LOW VOLTAGE CONDUIT RUN

DEMOLITION

EXISTING

HOME RUN TO PANEL

CONDUIT STUB

CONDUIT BREAK/CONTINUATION

CONDUIT STUB DOWN

CONDUIT STUB UP

FUSE

GROUND/GROUND ROD

CIRCUIT BREAKER

A AMPS

AFC AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPS INTERR. CAPACITY

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

C CONDUIT

CND CONDUIT

CO CONDUIT ONLY

CT CURRENT TRANSDUCER

CU COPPER MATERIAL

DED DEDICATED

DFA DROP FROM ABOVE

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EM EMER./EGRESS BATTERY

EMT ELEC. METALLIC TUBING

ENT ELEC. NON-METAL. TUBING

ER EXISTING TO BE RELOCATED

EX EXISTING TO REMAIN

FMC FLEXIBLE METAL CONDUIT

GC GENERAL CONTRACTOR

GEC GRND. ELEC. COND. AT SES

GFCI GRND. FLT. CURR. INTERR.

GFEP GRND. FLT. EQUIP. PROTECT.

GND GROUND

IMC INTER. METAL CONDUIT

IG ISOLATED GROUND

KCMIL 1000 CIRCULAR MILS (MCM)

LFMC LIQUID-TIGHT FLEX.

METAL. COND.

LFNC LIQUID-TIGHT FLEX.

NON-METAL. COND.

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPS

N1 NEMA 1

N3R NEMA 3R

N NEW

NL NIGHT LIGHT, BYPASS

LOCAL SWITCHING

PC PLUMBING CONTRACTOR

POC POINT OF CONNECTION

POS POINT OF SALE

R RELOCATED

RX RECEIVER

RM ROOF MOUNTED

RMC RIGID METALLIC CONDUIT

RNC RIGID NON-METALLIC COND.

SBJ SYSTEM BONDING JUMPER

SCA SHORT CIRCUIT AMPERES

TX TRANSMITTER

TC TEMP. CONTROL CONTR.

TR TAMPERPROOF

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

VA VOLT/AMPS

VIF VERIFY IN FIELD

WP WEATHERPROOF/NEMA 3R

XP EXPLOSION PROOF

XR EXISTING TO BE REMOVED

ABBREVIATIONS

(1) SEE LUMINAIRE SCHEDULE FOR FIXTURE TYPES AND DETAILS.

(2) SEE LUMINAIRE SCHEDULE FOR MOUNTING REQUIREMENTS.

(3) WIRE LIGHT FIXTURE FROM ADJACENT J-BOX

(4) CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST

(5) DIRECTIONAL ARROWS INDICATE REQUIRED CHEVRONS.

(6) COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL INTERIOR ELEVATIONS

(7) USE WITH POWER PACK.

(8) "X" IN SYMBOL IS INCHES BETWEEN RECEPTACLE ALONG WIREWAY. SEE DRAWINGS.

(9) PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.

(10) MATCH THE VOLTAGE OF THE RELAY WITH THAT OF THE CONTROLLING CIRCUIT.

(11) USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE AND INSTALLATION.

(12) PROVIDE MUD RING AND/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.

(13) USE HEAVY DUTY DEVICE FOR 480 VOLT.

(14) SIZE TO THE EQUIPMENT BEING CONTROLLED

(15) FIRE ALARM PANELS: FACP: FIRE ALARM CONTROL PANEL, NAC: NOTIFICATION APPLIANCE CIRCUIT PANEL, ANNUN: GRAPHIC ANNUNCIATOR PANEL, AND SES: SMOKE EVACUATION SYSTEM PANEL.

(16) LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.

(17) PROVIDE 5' OF SERVICE LOOP AND TERMINATE IN 2-PORT SURFACE MOUNT BOX.

NOTESNOTES

ELECTRICAL SYMBOL SCHEDULE

SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING

ELECTRICAL SYMBOL SCHEDULE

SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING

ELECTRICAL SYMBOL SCHEDULE

SYMBOL DEVICE/FIXTURE DESCRIPTION COMMENTSMOUNTING

POKETHRU

ECU EMERGENCY CONTROL UNIT CEILING

DOOR CONTACT 4'-0" (11)D

REQUEST TO EXIT 4'-0" (11)X

KEYPAD 4'-0" (11)K

ELECTRIC HINGE 4'-0" (11)H

ELECTRIC LATCH 4'-0" (11)L

ELECTRIC STRIKE 4'-0" (11)S

BIOMETRIC READER 4'-0" (11)B

2x2 LINEAR EMERGENCY LIGHT FIXTURE CEILING (1) (2) (3) (16)

CEILING2x2 LINEAR LIGHT FIXTURE (1) (2) (3) (16)

CEILING WI-FI ACCESS POINT, DUAL DATA PORT CEILING (17)CEILING WI-FI ACCESS POINT CEILING

TOUCH PANEL 4'-0"TP

CORD REEL OUTLET SUSPENDEDCR

ANNUNCIATOR PANEL (9)ANN

GAP GENERATOR ANNUNCIATOR PANEL SEE PLANS

ATS AUTOMATIC TRANSFER SWITCH SEE PLANS

POKE THRU, POWER FLOOR

POKE THRU, POWER AND DATA FLOOR

POKE THRU, POWER AND DATA W/AV FLOORJ

(9) (11)CEILING# CEILING MOUNT FIRE ALARM SPEAKER STROBE,

ATTRIBUTE SIGNIFIES CANDELA RATING

(9) (11)CEILING# CEILING MOUNT FIRE ALARM HORN STROBE,

ATTRIBUTE SIGNIFIES CANDELA RATING

(9) (11)CEILING# CEILING MOUNT FIRE ALARM STROBE,

ATTRIBUTE SIGNIFIES CANDELA RATING

DUAL TECHNOLOGY VAC. SENSOR WITH DIMMER, WALL (7)AS NOTED

(7)4'-0"DUAL TECHNOLOGY VAC. SENSOR SWITCH WITH DIMMER,

1-ZONE

(9) (11)CEILINGCEILING MOUNT FIRE ALARM HORN

SECURITY MOTION SENSOR CEILING/WALL (6) (11)SECURITY MOTION SENSOR CEILING/WALL (6) (11)M

2x4 LINEAR CRITICAL LIGHT FIXTURE CEILING (1) (2) (3) (16)

2x2 LINEAR CRITICAL LIGHT FIXTURE CEILING (1) (2) (3) (16)

EQUIPMENT CONNECTION

FIRE ALARM, LOW FREQUENCY, VISUAL AS NOTED (9)

FIRE ALARM, LOW FREQUENCY, NON-VISUAL AS NOTED (9)

NOTIFICATION APPLIANCE CONTROL PANEL (15)NAC

CARBON MONOXIDE DETECTOR CEILING (9) (11)CO

ROOM CONTROLLER CEILINGRC

BOLLARD LIGHT, POLE TOP AREA LIGHT POLE (1) (2)

DUPLEX OUTLET, POP-UP COUNTERTOP

CONVENIENCE OUTLET, GFCI, CUSTOM HEIGHT, HOSPITAL (6)

48"UNLESS

NOTED

LOW VOLTAGE DIMMER SWITCH 4'-0"S

SCENE CONTROLLER 4'-0"SC

PARTITION SENSOR CEILINGPS

EV CHARGEREV

GENERAL NOTES

1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND SPECIFICATIONS ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT DOCUMENTS AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION OR CONFLICT EXIST IN EITHER THE PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING HIS BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIER SHALL SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS AT THEIR OWN EXPENSE. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE, THE CONTRACTOR SHALL TEST AND CONFIRM IT'S PROPER OPERATION. ANY INCOMPLETE SYSTEM

SHALL BE MADE COMPLETE AND OPERABLE.

2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE

GREATER THAN SPECIFIED AND/OR DIMENSIONED ON THE PLANS.

3. NO ADDITIONS TO THE CONTRACTOR BID WILL BE ALLOWED FOR CHANGES MADE NECESSARY BY INTERFERENCE WITH OTHER WORK.

4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS AND LABOR FOR THE CONNECTIONS OF ALL EQUIPMENT

SHOWN ON THE PLANS - ARCHITECTURAL, MECHANICAL, ETC.

5. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH LOCAL AND STATE CODES AND THE NEC. IF AT ANY TIME DURING CONSTRUCTION, OR AFTER, SOMETHING IS FOUND TO BE INSTALLED IN VIOLATION OF THE CODES LISTED ABOVE, IT SHALL BE

CORRECTED AT THE CONTRACTORS EXPENSE.

6. ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE CONDITIONS AND SPACE THAT

EQUIPMENT IS BEING INSTALLED WITHIN.

7. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED FROM. VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BREAKERS AS NECESSARY FOR A

COMPLETE AND OPERABLE SYSTEM.

8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELE/DATA ROOM FROM WHICH NEW TELE/DATA OUTLETS WILL BE FED FROM. VERIFY EXISTING PATCH PANEL SPACES AND PROVIDE NEW PATCH PANELS AS NECESSARY TO

LAND ALL NEW TELE/DATA CABLING.

9. THE ELECTRICAL CONTRACTOR SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE ELECTRICAL CONTRACTOR SHALL GROUND THE ELECTRICAL

SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.

10. THE ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS, CABINETS, DISCONNECT, TRANSFORMERS, ETC. AND SHALL MOVE THE PANELS/EQUIPMENT AT HIS EXPENSE IF REJECTED BY AN INSPECTOR. IF CLEARANCE IS NOT POSSIBLE, THE DESIGNER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.

11. CONDUIT LAYOUTS SHOWN ON THE PLANS ARE DIAGRAMMATIC, NOT INDICATING THE ROUTING REQUIRED. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT, BUILDING STRUCTURE AND OTHER POTENTIAL OBSTRUCTIONS.

12. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE

OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.

13. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY STANDARD

METHODS AND PRACTICES.

14. MINIMUM SIZE CONDUIT SHALL BE 3/4". ABOVE GROUND CONDUIT SHALL BE EMT WITH STEEL SET SCREW FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH40) WITH GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN DIRECT

CONTACT WITH THE SOIL.

15. FLEXIBLE METAL CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR SEAL-TITE CONDUIT SHALL NOT EXCEED 72” INCHES. USE LFMC IN DAMP

OR WET LOCATIONS.

16. WIRING DEVICES SHALL MATCH EXISTING COLOR AND FACEPLATE TYPE. COLOR TO MATCH ADJACENT ARCHITECTURAL FINISH.

COORDINATE WITH ARCHITECT.

17. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE APPLICATION. ANY DEVICE BOXES NOT SECURED WILL BE MADE SECURE AT THE CONTRACTORS

EXPENSE.

18. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB RATED NYLON PULL CORD.

19. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS, WALLS, ETC.), THEY SHALL BE APPROVED BY THE INSPECTING OFFICER (INSPECTOR). THE UNCOVERING AND REPLACEMENT OF ELECTRICAL WORK FOR THE INSPECTION PURPOSES WILL

BE AT THE COST OF THE ELECTRICAL CONTRACTOR.

20. ALL BATTERY POWERED OR CONTINUOUS BURN LUMINAIRES SHOWN ON THE PLANS, SUCH AS EXIT LIGHTS, NIGHT LIGHTS, OR EMERGENCY LIGHTS, SHALL BE CONNECTED TO THE UN-SWITCHED LEG OF THE LIGHTING CIRCUIT FEEDING THAT AREA.

21. LUMINAIRES INSTALLED IN THE MECHANICAL ROOM SHALL BE PLACED SO THAT ALL EQUIPMENT IS ADEQUATELY ILLUMINATED AFTER

THE MECHANICAL EQUIPMENT IS IN PLACE.

22. ALL LUMINAIRES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND NOT SOLELY FROM THE CEILING GRID OR OTHER

NONSTRUCTURAL MEMBER.

23. TO MAINTAIN CONSISTENT LIGHT QUALITY, LUMINAIRES SHALL BE OF THE SAME SURFACE TEMPERATURE AND COLOR RENDERING INDEX, LUMINAIRE TYPES SHALL BE OF THE SAME MANUFACTURER AND LUMEN OUTPUT.

24. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120 OR 277VAC BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12(CU,THHN/THWN-2)+1#12(CU,THHN/THWN-2)GND IN 3/4” EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10(CU,THHN) FOR 120VAC BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 100' TO ACCOMMODATE FOR VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES AND NOTES ON DRAWINGS FOR ALL OTHER BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.

25. CONDUCTORS SHALL BE COPPER STRANDED, 600VAC RATED, TYPE THHN/THWN-2 UNLESS OTHERWISE NOTED.

26. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS, WIRES, AND OVERCURRENT PROTECTION PRIOR TO ROUGH-IN. THE ELECTRICAL CONTRACTOR SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE EQUIPMENT SUPPLIER.

27. THE ELECTRICAL CONTRACTOR SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE

ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FROM THE PREMISES.

28. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE

OF EQUIPMENT AND ADDITIONAL COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.

29. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE

MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS.

30. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED WITH THE

ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL BE MADE TO CONCEAL WIRING METHODS.

31. PROVIDE AN UPDATED, TYPED PANEL CIRCUIT DIRECTORY FOR ALL PANELS WHERE CIRCUITS HAVE BEEN MODIFIED, ADDED, OR REMOVED BY THE SCOPE OF THIS PROJECT. CIRCUIT DESCRIPTIONS ON THE DIRECTORY SHALL BE UNIQUE AND INDICATE THE ROOM AND EQUIPMENT/DEVICE IT IS FEEDING. DATE DIRECTORY WITH PROJECT COMPLETION DATE. MODIFIED CIRCUITS TO BE IN BOLD.

32. PROVIDE A CLEAR, TYPED LABEL ON THE FACEPLATE OF ALL RECEPTACLES AND LIGHT SWITCHES INDICATING THE CIRCUIT IT IS TIED TO.

USE LABELING CONVENTION XX-xx, WHERE "XX" IS THE NAME OF THE PANEL AND "xx" IS THE BRANCH CIRCUIT NUMBER. LABELS LENGTH

SHALL NOT EXCEED 1/4" ON EITHER SIDE OF TEXT.

33. FUSED DISCONNECTS TO BE HEAVY DUTY.

34. FURNISH AND INSTALL TAMPER-RESISTANT RECEPTACLES FOR 120V RECEPTACLES IN AREAS SPECIFIED 210.52 OF THE NEC AND AS

REQUIRED UNDER 403.12 OF THE NEC.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

EG501

ELECTRICAL

DETAILS

CURRENT/ISSUE DATE:

DRAWN BY:

CHECKED BY:

RESOLUT PROJECT #:

SHEET CONTENTS

REVISIONS

KC

250481

08/19/2025

D A

TC

PH

A

SE

B

H

IG

H B

A Y

H

VA

C

IM

PR

O

VE

M

EN

TS

KA

YS

VI

LL

E, U

TA

H

A

B

C

D

1 2 3 4 5

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

Project #:

40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com

250481

KEY PLAN

TS

REFER TO SECTION

FOR ATTACHMENT

OF ALL THREAD

ROD TO KINDORF

CHANNEL 1 1/2"x1 1/2"-12GA. KINDORF

CHANNEL OR APPROVED

SUBSTITUTE

3/8" ALL THREAD,

MINIMUM. INCREASE

ROD SIZE IF WEIGHT

REQUIRES PER ROD

MANUFACTURERS

RECOMMENDATIONS.

SUPPORT CONDUIT

WITH KINDORF

STRAP OR

APPROVED

SUBSTITUTE.

BEAM CLAMPS OR

HANGER CLAMPS

AS REQUIRED BY

WEIGHT

SUPPORTED

PROVIDE 25% SPACE

CAPACITY

NUT

WASHER

WASHER

NUT

EG501

8 TRAPEZE SUPPORT DETAIL

NO SCALE

EG501 NO SCALE

ROOF TOP UNIT DETAIL

NOTE:

1. COORDINATE ROOF PENETRATIONS AND MATERIALS

REQUIREMENTS WITH ROOF CONTRACTOR PRIOR TO

ROUGH-IN.

2. REMOVE ALL EXISTING FLASHING, LEAD, ETC. PIPE

SURFACE MUST BE FREE OF ALL RUST, GREASE,

INSULATION, ETC.

3. CONDUIT MUST BE ANCHORED TO STRUCTURE

BELOW TO ENSURE STABILITY.

4. PRE-MOLD PIPE FLASHING MAY BE CUT TO HEIGHT,

BUT NO LOWER THEN REINFORCING RING. NO

WRINKLES OR FOLDS UNDER CLAMPING RING.

5. APPLY LAP SEALANT BETWEEN PENETRATION AND

PRE-MOLD PIPE FLASHING PRIOR TO INSTALLATION

OF CLAMPING RING.

STAINLESS STEEL

CLAMP RING

CONDUIT

ROOF

MEMBRANE

BONDING

ADHESIVE PRE-MOLDED

PIPE FLASHING

FIELD FABRICATED

METAL HOOD BY

OTHER (OPTIONAL)

HIGH GRADE

SEALANT

EG501 NO SCALE

ROOF PENETRATION DETAIL

EQUIPMENT SCHEDULE

TYPE DESCRIPTION

ELECTRICAL OVER CURRENT PROTECTION STR

REMARKSVOLT PHASE LOAD FLA

WIRE COND OCPD/

TYPE

DISCONNECT FUSE NEMA

SETS QTY SIZE GND SIZE MOCP SIZE POLE SIZE SIZE

RTU - 1 ROOF-TOP UNIT 208 3 29.00 MCA 23.2 1 3 8 10 3/4 35 C1 60 3 35 - 9 A 14A

RTU - 2 ROOF-TOP UNIT 208 3 29.00 MCA 23.2 1 3 8 10 3/4 35 C1 60 3 35 - 9 A 14A

RTU - 3 ROOF-TOP UNIT 208 3 29.00 MCA 23.2 1 3 8 10 3/4 35 C1 60 3 35 - 9 A 14A

RTU - 4 ROOF-TOP UNIT 208 3 27.00 MCA 21.6 1 3 8 10 3/4 35 C1 60 3 35 - 9 A

ABBREVIATIONS:

KW = KILOWATTS VA = VOLT AMPERES OCPD = OVERCURRENT PROTECTIVE DEVICE

V/PH = VOLTAGE/PHASE KVA = KILOVOLT AMPERES GND = GROUND COND = CONDUIT

HP = HORSEPOWER FLA = FULL LOAD AMPERES STR = STARTER MOCP = MAXIMUM OCPD (LISTED BY THE MANUFACTURER)

W = WATTS MCA = MINIMUM CIRCUIT AMPACITY PL = POLE

REMARKS: REMARKS:

1. NEMA 1 FUSED DISCONNECT SWITCH A. FURNISHED, INSTALLED AND CONNECTED UNDER DIVISION 26.

2. NEMA 1 NON-FUSED DISCONNECT SWITCH B. FURNISHED AND INSTALLED UNDER ANOTHER DIVISION REQUIRING CONNECTION UNDER DIV 26.

3. BREAKER IN ENCLOSURE C. FURNISHED UNDER ANOTHER DIVISION BUT INSTALLED AND CONNECTED UNDER DIV 26.

4. MANUAL STARTER WITH THERMAL OVERLOAD D. FURNISHED, INSTALLED AND CONNECTED UNDER ANOTHER DIVISION.

5. MANUAL MOTOR CONTROLLER W/OUT THERMAL OVERLOAD E. FURNISHED AND INSTALLED UNDER DIV 26 REQUIRING CONNECTION UNDER ANOTHER DIVISION.

6. MAGNETIC STARTER

7. MAGNETIC STR/NON-FUSED DISCONNECT COMBINATION OCPD TYPES:

8. MAGNETIC STR/FUSED DISCONNECT COMBINATION C1 = THERMAL MAGNETIC CIRCUIT BREAKER

9. NEMA 3R FUSED DISCONNECT SWITCH C2 = MAGNETIC ONLY CIRCUIT BREAKER

10. NEMA 3R NON-FUSED DISCONNECT SWITCH

11. VARIABLE FREQUENCY DRIVE NOTES:

12. RECEPTACLE/SPECIAL PURPOSE OUTLET/ETC. - THE DIVISION 26 CONTRACTOR MAY INCREASE THE CONDUIT SIZE BY ONE INCREMENTAL SIZE TO FACILITATE

INSTALLATION OR TO HELP WITH MATERIAL AVAILABILITY/COST.13. DIRECT CONNECTION

14. DUCT DETECTOR IN RETURN AIR DUCT. PROVIDE RELAY/CONTROL MODULE AND 120V POWER AS REQUIRED TO

TIE TO FIRE ALARM FOR AUTOMATIC SHUT OFF.

15. CONTROLLED WITH LIGHTS

16. LM-EB DISCONNECT W/CNTRL WIRING TO VFD

17. SPLIT SYSTEM. INDOOR UNIT FED FROM OUTDOOR UNIT.

GENERAL NOTE: THE EC SHALL COORDINATE ALL REQUIREMENTS (IE: MOCP SIZE, UNIT THERMAL PROTECTION, ETC) WITH APPROVED MECHANICAL SHOP DRAWINGS/SUBMITTALS AND BRING UP ANY DISCREPANCIES WITH THE ELECTRICAL

ENGINEER OF RECORD IN WRITING PRIOR TO ROUGH-IN AND ORDERING OF MATERIALS.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

RTU

(E)

RTU

(E)

RTU

(E)

RTU

(E)

CURRENT/ISSUE DATE:

DRAWN BY:

CHECKED BY:

RESOLUT PROJECT #:

SHEET CONTENTS

REVISIONS

KC

250481

08/19/2025

D A

TC

PH

A

SE

B

H

IG

H B

A Y

H

VA

C

IM

PR

O

VE

M

EN

TS

KA

YS

VI

LL

E, U

TA

H

A

B

C

D

1 2 3 4 5

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

Project #:

40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com

250481

KEY PLAN

TS

SCALE:

ED103 1/8"=1'-0"

ROOF POWER DEMOLITION PLAN

ED103

ROOF

POWER

DEMOLITION

PLAN

GENERAL NOTES

A. EC SHALL COORDINATE WITH ALL OTHER TRADES

DURING DEMOLITION AND CONSTRUCTION TO

FACILITATE TIMELY WORK.

B. ALL AREAS ARE TO BE KEPT CLEAN AND CLEAR OF

DEBRIS AT ALL TIMES.

C. CONTRACTOR SHALL PATCH AND REPAIR ALL WALLS,

CEILINGS ETC. TO MATCH EXISTING CONDITIONS.

PENETRATIONS SHALL BE SEALED WITH FIRE RATED

CAULK.

D. ROUTE ALL CONDUIT IN A NEAT AND ORDERLY FASHION.

ALL CONDUIT SHALL BE CONCEALED ABOVE CEILINGS

OR IN WALLS OR FINISHED SPACES UNLESS OTHERWISE

INDICATED ON THE PLANS.

E. DEVICES SHOWN ON DEMOLITION SHEETS ARE

GATHERED FROM AS-BUILT DRAWINGS AND FIELD

INVESTIGATION. NOT ALL DEVICES ARE SHOWN. DEVICE

PLACEMENT IS SCHEMATIC AND NOT EXACT.

CONTRACTOR TO FIELD VERIFY FOR EXACT LOCATIONS

AND COORDINATE WORK WITH ALL OTHER DEVICES,

EQUIPMENT, CONDUIT, ETC. WHETHER OR NOT SHOWN

TO COMPLETE PROJECT.

F. CONTRACTOR TO COORDINATE WITH OWNER FOR ITEMS

TO BE SALVAGED PRIOR TO DEMOLITION. CONTRACTOR

RESPONSIBLE FOR DISPOSING OF ANY MATERIAL THAT

THE OWNER DOES NOT WANT TO KEEP.

G. CAP AND LABEL ALL EMPTY CONDUIT TO REMAIN.

H. DEVICES/EQUIPMENT SHOWN IN GRAY ARE EXISTING TO

REMAIN. PRESERVE AND PROTECT. MAINTAIN EXISTING

CIRCUIT INTEGRITY.

KEYED NOTES#

1. ROOF TOP UNITS TO BE REMOVED AND REPLACED BY

MECHANICAL CONTRACTOR. EC TO DISCONNECT EQUIPMENT

AND VERIFY CONDUIT AND CONDUCTORS ARE IN GOOD

WORKING CONDITION FOR NEW EQUIPMENT.

2. EC SHALL DEMOLISH EXISTING SERVICE RECEPTACLE ON

ROOF TOP UNIT. VERIFY CIRCUIT INTEGRITY AND PREPARE

CIRCUIT FOR REUSE.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

RTU

RTU

RTU

RTU

EF

(E)

EF

(E)1

TYP

WP

WP

WP

WP

E103

ROOF

POWER

PLAN

CURRENT/ISSUE DATE:

DRAWN BY:

CHECKED BY:

RESOLUT PROJECT #:

SHEET CONTENTS

REVISIONS

KC

250481

08/19/2025

D A

TC

PH

A

SE

B

H

IG

H B

A Y

H

VA

C

IM

PR

O

VE

M

EN

TS

KA

YS

VI

LL

E, U

TA

H

A

B

C

D

1 2 3 4 5

181 East 5600 South Murray, UT 84107

801.530.3148 T

801.530.3150 F

Project #:

40 W Cache Valley Blvd., Bldg 1, Suite B, Logan, UT 84341 | (435) 752-5081 info@resolutgroup.com | resolutgroup.com

250481

KEY PLAN

TS

SCALE:

E103 1/8"=1'-0"

ROOF POWER PLAN

GENERAL NOTES

A. EC SHALL COORDINATE WITH ALL OTHER TRADES

DURING DEMOLITION AND CONSTRUCTION TO

FACILITATE TIMELY WORK.

B. ALL AREAS ARE TO BE KEPT CLEAN AND CLEAR OF

DEBRIS AT ALL TIMES.

C. CONTRACTOR SHALL PATCH AND REPAIR ALL WALLS,

CEILINGS ETC. TO MATCH EXISTING CONDITIONS.

D. ROUTE ALL CONDUIT IN A NEAT AND ORDERLY FASHION.

ALL CONDUIT IN FINISHED SPACES SHALL BE

CONCEALED ABOVE CEILINGS OR IN WALLS UNLESS

OTHERWISE INDICATED ON THE PLANS.

E. BRANCH CIRCUITS SHALL NOT EXCEED 3% VOLTAGE

DROP.

F. PROVIDE UPDATED TYPED CIRCUIT DIRECTORY WITH

UNIQUE CIRCUIT DESCRIPTIONS PER NEC 408.4 FOR

PANELS AFFECTED BY THIS PROJECT.

G. PROVIDE HOUSEKEEPING PADS FOR ALL FLOOR

MOUNTED AND GRADE MOUNTED ELECTRICAL

EQUIPMENT. MINIMUM REQUIREMENTS: 4" HIGH, 4% AIR

ENTRAINED, POLYFIBER REINFORCED CONCRETE, 4"

WIDER AND 4" LONGER THAN EQUIPMENT TO BE PLACED

ON IT. REFER TO ELECTRICAL DETAIL DRAWINGS FOR

TRANSFORMER, GENERATOR, OR SWITCHGEAR PADS

THAT MAY EXCEED THESE REQUIREMENTS.

H. WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT

SHOWN. PROVIDE PROPER NUMBER OF CONDUCTORS

TO ACHIEVE CIRCUIT AND SWITCHING CONNECTIONS

SHOWN.

I. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO

BREAKERS. BRANCH CIRCUITS SHALL BE SIZED

ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS

INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT

SCHEDULE.

J. DEVICES/EQUIPMENT SHOWN IN GRAY ARE EXISTING TO

REMAIN. PRESERVE AND PROTECT. MAINTAIN EXISTING

CIRCUIT INTEGRITY.

KEYED NOTES#

1. NEW MECHANICAL EQUIPMENT CAN BE RECONNECTED TO

EXISTING CIRCUITS IF THE EXISTING CIRCUITS MEET THE

REQUIREMENTS SHOWN ON THE EQUIPMENT SCHEDULE AND

ARE IN GOOD WORKING ORDER. IF EXISTING CONDITIONS DO

NOT MEET THE EQUIPMENT SCHEDULE REQUIREMENTS, THAN

EC SHALL PROVIDE NEW BREAKER, CONDUIT AND

CONDUCTORS AS INDICATED. ALL NEW BREAKERS SHALL

MATCH AIC RATING OF EXISTING PANEL BOARDS.

2. EC SHALL PROVIDE A SERVICE RECEPTACLE WITHIN 25 FEET

EACH RTU. RECEPTACLES SHALL HAVE WEATHERPROOF IN

USE COVER.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

G001 COVER SHEET
M001 SYMB AND LEGENDS
MD101 MECH DEMO PLAN
MD102 MECH DEMO PLAN
MD103 ROOF MECH DEMO PLAN
M103 ROOF MECH PLAN
M501 MECH DETAILS
M601 MECH SCHED
20250819.1_250481_Davis Tech High Bay Phase B
EG001 ELECTRICAL NOTES & SYMBOLS
EG501 ELECTRICAL DETAILS
ED103 ROOF POWER DEMOLITION PLAN
E103 ROOF POWER PLAN

File details come from the government source that posted it. Updated .