This document is a Q&A file for the James River Reserve Fleet Fire Detection System Upgrade solicitation. The questions and answers provide specific technical details about the fire detection system upgrade for Buildings 2606 and 2612 on a base facility. Key details include building sizes (Building 2606 is approximately 6,700 sq. ft., Building 2612 is around 2,000 sq. ft.), confirmation that Unified Facilities Criteria (UFCs) do not apply, and requirements for the fire alarm system. The responses indicate that no proprietary fire alarm brand is required, the current Mass Notification System connected to a Monaco notification unit must be maintained, and the buildings are office/working spaces with no need for a VESDA (Very Early Smoke Detection Apparatus) system. The contractor will need to coordinate with the base fire department's Authority Having Jurisdiction (AHJ) during the system upgrade.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
• How big are each of these buildings? Not, exact, just order of magnitude.
o Building 2606 is ~6700 sq. ft.; 2612 ~2000 sq. ft.
• Since this is on a base, will the Unified Facilities Criteria (UFCs) apply? If so, for which branch of the military?
o No UFCs do not apply, but liaison needs to be made with base fire department Authority Having Jurisdiction (AHJ)
• Will a proprietary fire alarm brand be required, or will the component choice be up to the fire protection engineer and designer?
o No proprietary alarm required or desired.
• Will a Mass Notification System (MNS) be required?
o Current system is connected to Monaco notification unit to communicate with base dispatch and will need to be maintained/connected to newly installed system.
• How are these buildings used? Are there any sensitive electronics areas that will required a VESDA system?
o Office/working spaces. No VESDA needed.