635-21-121 (VEG 21.19) 100PCT Stamped Drawings 04-25-2023.pdf

PDF 4 MB Posted

Attached to
Z2DA--Replace Automatic Transfer Switches 635-21-121
Solicitation number
36C25923R0065
Issued by

About this file

This statement of work outlines requirements for replacing ten automatic transfer switches at the Oklahoma City VA Medical Center. The contractor will remove the existing ATS units and install new ones according to provided drawings and specifications. The contractor must be a licensed electrical contractor and will provide all necessary labor, materials, tools and equipment. The project is expected to take no more than 90 days. The contractor must coordinate all utility outages with the VA at least two weeks in advance and is responsible for daily clean up and securing the work site.

The contractor must follow all applicable codes and standards and will inspect the ATS units prior to replacement. A one-year warranty is required. The objective is to directly replace the ATS units while minimizing disruptions to the medical center's operations. The contractor must submit documentation and provide training at the completion of the project.

View the file

Other files

File Type Posted
36C25923R0065 0003.docx DOCX document
Pre-Bid Sign in Sheet.pdf PDF
21.19 PRE BID RFI Log 07-17-2023.pdf PDF
36C25923R0065 0002.docx DOCX document
36C25923R0065 0001.docx DOCX document
36C25923R0065_1.docx DOCX document
Specifications - 635-21-121.pdf PDF
NEW - Calculation Worksheet for Self-Performed and Subcontracted Work.docx DOCX document
S02-3-10-2021 Past Performance Questionnaire_Blank_Fillable PDF.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA OF WORK SHEET INDEX

OKLAHOMA CITY HEALTH CARE SYSTEM

OKLAHOMA CITY, ST

VAMC PROJECT #: 635-21-121

REPLACE AUTOMATIC TRANSFER SWITCHES

Plan North

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

04/26/2023VEG 21.19 TM WHB

GI001

COVER SHEET

Pl an

N or th

True North

NO

RT

H

KE

LL

EY

A

VE

NE 13th STREET

PROJECT SITE

NE 13th STREET

NO

RT

H

KE

LL

EY

A

VE

NO

RT

H

PH

ILL

IP

S

AV

E.

NE 15th STREET

NE 16th STREET NE 16th STREET

NO

RT

H

PH

ILL

IP

S

AV

E.

NE 14th STREET

NE 15th STREET

SHEET NO. SHEET NAME

GI001 COVER SHEET

E-001 ELECTRICAL SYMBOLS

E-002 ELECTRICAL SYMBOLS & ABBREVIATIONS

ED111 BASEMENT PARTIAL DEMO FLOOR PLANS

EP111 SWITCHGEAR ROOM #3

EP112 BASEMENT PARTIAL FLOOR PLANS

ES101 BASEMENT TEMPORARY POWER

EP-501 DETAILS

EP-601 PRIMARY ONE LINE DIAGRAM

EP-602 ATS POWER RISER

EP-603 RISER DIAGRAM SWITCHGEAR ROOM #3

EP-604 RISER DIAGRAM ATS REMOVAL AND INSTALLATION

EP-605 RISER DIAGRAM ATS - 5 REMOVAL AND INSTALLATION

EP-606 RISER DIAGRAM ATS - 4 REMOVAL AND INSTALLATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

VEG 21.19

N

EGC

04/26/2023 TM WHB

E-001

ELECTRICAL SYMBOLS

SWITCH, NORMALLY CLOSED FLOAT

SWITCH, NORMALLY CLOSED FOOT OPERATED

SWITCH, NORMALLY CLOSED LIMIT

SWITCH, NORMALLY CLOSED TEMPERATURE

ACTIVATED

SWITCH, NORMALLY OPEN FLOAT

SWITCH, NORMALLY OPEN TEMPERATURE

ACTIVATED

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

PULL BOX

PRESSURE SWITCH-CLOSE ON

INCREASE

PRESSURE SWITCH-OPEN ON

INCREASE

MANHOLE

ELECTRICAL SYMBOLS - DIAGRAM

TIME CLOCK

VENTILATOR OR FAN COIL UNIT OUTLET

CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED

FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.

RECEPTACLE, SWITCHED

DUPLEX

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE

CORD (CENTER LINE OF OUTLET: 6'-6" AFF. (MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS

DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.

3-GANG COMPARTMENT BOX IN FLOOR FOR

TELEPHONE, DATA & RECEPTACLE.

RECEPTACLE, SPECIAL PURPOSE

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

ELECTRIC DOOR STRIKE

CARD READER

MAGNETIC DOOR POSITION SWITCH

CAMERA

JUNCTION BOX

MAGNETIC LOCK

OUTLET, COMBINATION TELEPHONE/DATA

COMMUNICATION

CABLE TELEVISION LINE

CLOSED CIRCUIT TELEVISION LINE, MINIMUM 1" CONDUIT

FIBER OPTIC LINE

FLOOR BOX: SYMBOL INDICATES TYPE

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,

PROVIDE SCHEDULE ON LEGEND

SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,

PROVIDE SCHEDULE ON LEGEND. MTD.

7'-6" AFF UNLESS OTHERWISE NOTED.

OUTLET TELEPHONE ONLY

TELEPHONE LINE

INTERCOM LINE, MINIMUM 3/4" CONDUIT

SOUND LINE

NURSE CALL LINE, MINIMUM 3/4" CONDUIT

OUTLET; LETTER INDICATES AS FOLLOWS:

A = AUDIO V = VIDEO I = INTERCOM C = 6" ABOVE COUNTER

RADIO, MINIMUM 3/4" CONDUIT

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"

AFF UNLESS OTHERWISE NOTED.

OUTLET, TELEVISION

BLANK= 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK

COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" AFF

M = MONITOR (CCTV SYSTEM).

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER

TOP UNLESS OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS

AT MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

D = DUTY STATION. MTD 5'-0" AFF UNLESS NOTED OTHERWISE.

E = MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB

LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION.

P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH

S = AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS

OTHERWISE NOTED.

U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE

NOTED.

NURSE CALL STATION.

2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF LAMP)

MTD 6" ABOVE DOOR.

D = CORRIDOR DOME LIGHT.

I = AUXILIARY INTERSECTIONAL DOME LIGHT.

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

REMOTE DICTATING OUTLET MTD 1'-6" AFF. UNLESS OTHERWISE

NOTED.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL OPERATION

OF INSTRUMENT & TYPE REQUIRED).

TELECOMMUNICATIONS MANHOLE

DATA BOX

DURESS BUTTON

CCTV SYSTEM WORKSTATION

REQUEST TO EXIT MOTION DETECTOR

REMOTE DOOR RELEASE BUTTON

CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM

NURSE CALL MASTER CONSOLE

ETHERNET NETWORK SWITCH

WIRELESS ACCESS POINT

COMMUNICATION SYMBOLS:

SWITCH

F = FUSED SWITCH

K = KEY OPERATED

L = LOCK

LM= LOW VOLTAGE MASTER

M = MANUAL MOTOR STARTING

MC= MOMENTARY CONTACT

MP= MOTOR SNAP WITH PILOT LIGHT

P = WITH PILOT LIGHT (THERMAL TYPE)

X = EXPLOSION PROOF

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE

LVD = LOW VOLTAGE DIMMER

LV= LOW VOLTAGE SWITCH

GS= GRAPHIC SCREEN CONTROL STATION

PB= PUSH BUTTON STATION

WP= WEATHER PROOF

T = TIMER OPERATED

LOS= OCCUPANCY SENSOR

ELECTRICAL SYMBOLS - LIGHTING PLAN

LIGHTING, ONE HEAD EMERGENCY BATTERY

POWER

STREET LIGHT WITH BRACKET

LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE

LIGHT POLE, TWO MAST ARMS, TWO LUMINAIRES

LIGHT POLE, POST TOP MOUNT LUMINAIRE

LIGHT POLE, ONE LUMINAIRE

LIGHTING, EXTERIOR BUILDING

LIGHTING, TWO HEAD EMERGENCY BATTERY

POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY

POWER

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

LIGHT POLE, TWO LUMINAIRES

RECESSED DOWNLIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE

INFORMATION.

JUNCTION BOX

TRANSFORMER, PLAN

WYE CONNECTION

DUCT, CELL FLOOR HEADER

DUCT, TROLLEY

DUCT, UNDERFLOOR

JUNCTION BOX

EARTH GROUND

LADDER CABLE TRAY

BRANCH CIRCUIT HOMERUN. ONE SEPARATE GREEN

GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH

HOMERUN; NOT SHOWN

WIREWAY

RIGID CONDUIT LINE

SUBSTATION

BUSWAY

FLOOR OUTLET, DATA COMMUNICATION

OUTLET, DATA COMMUNICATION

PUSH BUTTON

DISTRIBUTION PANEL

LIGHTING PANEL

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, CLOCK HANGER

RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, DUPLEX ON EMERGENCY POWER

(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, QUADRAPLEX

RECEPTACLE, SINGLE

RECEPTACLE, SINGLE WITH SWITCH

EQUIPMENT GROUND CONDUCTOR

NEUTRAL

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

SWITCH, NORMALLY OPEN TIME DELAY

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

MEDIUM-VOLTAGE OIL CIRCUIT BREAKER

MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

FUSIBLE LINK

VARIABLE FREQUENCY DRIVE

GENERATOR, POWER

BATTERY

CAPACITOR

LIGHTNING ARRESTOR

RECTIFIER, CATHODIC PROTECTION

RELAY; LETTER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE

51 = AC-TIME OVERCURRENT

67 = AC-DIRECTIONAL OVERCURRENT

86 = LOCK OUT

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED, VAV

STARTER, COMBINATION W/DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

POTHEAD

STRESS CONE

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

ELECTRICAL SYMBOLS - POWER PLAN

RECEPTACLE, DUPLEX 6" ABOVE COUNTER HEIGHT

RC

VFD

R

A

V

W

WH

T

S

HVS

LVS

P T

D

DP#__

LP

C

TC

T T

C C

W W

B B

C

S

H

S

J

F

RRB

C

C

PB

P

BLANK OUTLET BOX

RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER

(MOUNT 18" AFF. UNLESS NOTED OTHERWISE

DUAL PASSIVE INFRARED / MICROPHONIC TECHNOLOGY

(ULTRASONIC NOT ALLOWED)

M

DT

FLOOR OUTLET, RECEPTACLE

GROUNDING BAR

HEADWALL

A bx

A b x

A b x

LIGHT FIXTURE POWER CONNECTION DESIGNATIONS:

OPEN - NORMAL POWER CIRCUIT

SHADED - LIFE SAFETY EMERGENCY POWER CIRCUIT

HATCHED - CRITICAL POWER CIRCUIT

RECESSED TROFFER LIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULES FOR MORE

INFORMATION.

CEILING SURFACE MOUNTED LIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE

INFORMATION.

WALL SURFACE MOUNTED LIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE

INFORMATION.

A b x

EXTERIOR FLOOD LIGHT

LIGHT FIXTURE, BOLLARD

LIGHT FIXTURE, DIRECTIONAL

R

ENTRY MONITOR/BUZZER COMBINATION OR DOOR BELL

DOME CAMERA

MOTION DETECTORM

ML

J

ES

CR

FIX

DB

CB

NCM

WAP

NWS

S

S

NCM

NCT

N

N

RX

WS

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

04/26/2023VEG 21.19 TM WHB

E-002

ELECTRICAL SYMBOLS &

ABBREVIATIONS

NEUT OR N

NC

NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PULL BOX OR PANEL BOARD

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

REQ REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT·AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR

FIX

FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND ELECTRICAL GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT·AMPERE

MW MEGAWATT

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

SINGLE POLE

1PH SINGLE PHASE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE PHASE

4/C FOUR-CONDUCTOR

4W FOUR WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT / ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT OR ADJOINING

ADO AUTOMATIC DOOR OPENER

AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE·HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BYPASS

CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA OR CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED / CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED / OWNER

INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT

BRKR

CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR

PNL

DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

NORMALLY CLOSED

1P

AF

C

ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE

WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND

REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

B. DISCONNECT AND REMOVE ALL WIRES AND CONDUIT BACK TO THE OVERCURRENT

DEVICE AND RELABEL AS A SPARE. REUSE EXISTING CONDUIT IN COMPLIANCE WITH

NEC. DO THESE UNLESS OTHERWISE NOTED.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

D. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN

JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE.

E. REPLACE ALL EXISTING HANDLE TIE MULTI-PHASE BREAKERS IN AREA OF WORK WITH

MULTI-PHASE BREAKER TO MAKE EXISTING MANUFACTURER.

KEY NOTE.

NEW LINE TYPE

EXISTING LINE TYPE

DEMO LINE TYPE

ELECTRICAL GENERAL NOTES:

ELECTRICAL GENERAL NOTES - DEMOLITION:

KEYNOTES:

NEW - EXISTING & DEMO LINE TYPES:

A. FOR WHEEL CHAIR PATIENT USE, MOUNT TELEPHONE OUTLET 35" AFF TO BOTTOM

OF OUTLET BOX.

B. DESK PHONES - MOUNT OUTLET 1'-6" AFF

C. PAY PHONES - MOUNT OUTLET 4'-0" AFF

D. HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED ON BED WALLS OR PBPU

DETAILS.

E. SEE VA. BARRIER FREE DESIGN GUIDE PG-18-13

COMMUNICATION GENERAL NOTES:

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE

OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN, AS REQUIRED.

B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

D. ALL WIRING SHALL BE (3)#12 THWN/THHN COPPER 3/4C" UNLESS OTHERWISE NOTED.

E. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS SHALL BE 3/4".

F. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS. SEAL

REMAINING ANNULUS WITH FIRE CAULK.

G. FURNISH ACCESS DOORS FOR INSTALLATION BY GENERAL CONTRACTOR IN WALLS

AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED ELECTRICAL BOXES AND

DEVICES.

H. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN FIXTURE PIGTAILS. ARMORED CABLE

(AC) SHALL NOT BE USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED CABLE (AC)

SHALL NOT BE USED WHERE MORE THAN THREE CONDUCTORS

(PHASE/NEUTRAL/GROUND) ARE REQUIRED, WHERE EXPOSED; OR IN LENGTHS

EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.

I. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE 2020 NATIONAL

ELECTRICAL CODE AND THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING

JURISDICTION.

J. COORDINATE ALL OUTAGES WITH VHA COR PER SPECIFICATION PRIOR TO WORK BEING

DONE.

K. CONTRACTOR SHALL SET INDOOR TEMPORARY ATS AND SWITCHBOARD IN

SWITCHGEAR 3 ROOM AND OUTDOOR GENERATOR WITH JERSEY BARRIERORS IN VA

DESIGNATED AREAS ONLY. THE SWITCHBOARD WILL PROVIDE CONSTRUCTION POWER

AND TEMPORARY POWER TO THE REMOVED ATS'S LOADS WHILE REGULAR NORMAL

AND EMERGENCY POWER SOURCES ARE DISCONNECTED. THE NORMAL POWER TO THE

TEMPORARY ATS IS TAPPED FROM SECONDARY SIDE OF SUBSTATION J AND THE

EMERGENCY POWER IS FROM THE OUTDOOR GENERATOR. THE TEMPORARY SYSTEM

SHALL BE CONNECTED SO THE GENERATOR STARTS AND THE ATS TRANSFERS TO

GENERATOR POWER AUTOMATICALLY WHEN POWER IS LOST AT SUBSTATION J.

TRANSFER BACK TO NORMAL SHALL BE MANUAL SELECTION AT THE ATS. CONTRACTOR

IS RESPONSIBLE FOR MAINTAINING THE TEMPORARY POWER SYSTEM WHICH INCLUDES

FUELING OF GENERATOR.

L. CONTRACTOR SHALL SUBMIT CABLE ROUTING PLANS FOR APPROVAL BEFORE

OUTAGES.

M. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, EXISTING CONDUIT, AND

CONDUCTOR PRIOR TO PLACING ORDERS. ANY DEVIATIONS OF EXISTING CONDITIONS

FROM DESIGNED DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE VHA COR.

DEMO HATCH

1. CONTRACTOR TO VERIFY THE SWITCHED POLE NUMBER OF EACH ATS WHETHER 3 OR 4

POLES PRIOR TO PLACING ORDER. VERIFY THE LIST BELOW:

2. CONTRACTOR TO PURCHASE 4 POLE ATS FOR ALL LOCATIONS AND INSTALL AS 3 POLE

AT LOCATIONS WITH 3 POLE ATS.

3. CONTRACTOR SHALL TEST EXISTING ATS SWITCHING FROM NORMAL TO GENERATOR

AND BACK TO NORMAL PRIOR TO REMOVAL. AFTER ATS REMOVAL, TEST

ATS-GENERATOR CONTROL WIRES TO SIMULATE TRANSFER TO GENERATOR AND BACK

TO NORMAL POWER. AFTER CONNECTING NEW ATS, TEST ATS SWITCHING FROM

NORMAL TO GENERATOR AND BACK TO NORMAL.

IMPORTANT NOTES FOR CONTRACTOR:

ATS POLE CHART

ATS-# 3 POLE 4 POLE

ATS-1

ATS-2

ATS-3

ATS-4

ATS-5

ATS-6

ATS-7

ATS-8

ATS-9

ATS-10

X X X

X X

X X X

X X

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

KEY PLAN

04/26/2023

KEY PLAN

E

A

B

F

C

D

NO SCALE

Plan North

VEG 21.19

1. PROVIDE TEMPORARY CONNECTION TO EXISTING PANELS DPLS

(ATS-1) AND DPCR (ATS-2).

2. DISCONNECT AND REMOVE ATS LEAVING EXISTING CONDUCTORS AND

FEEDERS IN PLACE FOR RECONNECTION IN NEW CONSTRUCTION.

3. CONNECT TEMPORARY POWER TO EXISTING LOAD CABLES, SEE

SHEET EP111.

4. PROVIDE CEILING JUNCTION BOX AT SUBSTATION-3 TO REUSE ATS-5

NORMAL POWER CONNECTION.

5. PROVIDE JUNCTION BOX ABOVE ATS FOR RECONNECTION TO NEW ATS

IN NEW LOCATION. SEE SHEET EP111.

6. EXTEND EXISTING WIRE AND CONDUITS FROM ATS-5 LOCATION TO

NEW LOCATION SHOWN ON EP111. UTILIZE TRAPEZE WHEN POSSIBLE.

7. DISCONNECT FEEDERS FROM CIRCUIT BREAKER FEEDING ATS-5 IN

SUB-3 AND REMOVE WIRE AND CONDUIT FROM SUB-3 TO EXISTING

ATS-5 LOCATION.

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

PARTIAL DEMO BASEMENT FLOOR - EXISTING

Plan North

TM WHB

ED111

BASEMENT PARTIAL DEMO FLOOR

PLANS

MAIN TIE MAIN

SW

IT

CH

T

-J

MAIN

SWITCHGEAR 3A - SERVES

ATS-10 - 400A.

X-RAY - 400A.

6th FL. MECH. RM. - 600A.

MAIN

SWITCHGEAR

XFMR KXFMR JINACTIVE SWITCH

BOX OLD TEMP.

DPCRDPLS

BOX C/B HB2LS

BOX C/B LB2CR

MCC-4

J-BOX

XFMR SR-1

SWITCH L

SW

IT

CH

T

-K

XFMR HMECH

STR #6

ATS-11 ATS-12

PNL HB1

BF112

PNL 4A

ATS-1 250A

ATS-2 600A ATS-3 650A

ATS-9 225A

ATS-8 650A

ATS-7 400A

ATS-6 175A

ATS -10 400A

BOX C/B SR

J

J

J

J

J

J

J

ATS-5 225A

2 3

JJJJ

VAC

MAIN 1

AMP

ATS-8

H #31

H #11

ATS-9

ATS-1

AMP VAC

MAIN #2

H #43

ATS-2

H #73

TIE

H #32 ATS-5

ATS-4

ATS-3 AMP VAC

VACAMP

J-BOX

MAIN

SWITCHGEAR

A V

ATS -10

X-RAY

ATS-7

KW

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

TM WHB

EP111

SWITCHGEAR ROOM #3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

KEY PLAN

04/26/2023

KEY PLAN

E

A

B

F

C

D

NO SCALE

Plan North

VEG 21.19

1. PROVIDE TRANSFER SWITCHES PER SPECIFICATION SECTION 26 36 23.

CONNECT TO EXISTING CABLES AT JUNCTION BOXES PROVIDED DURING

DEMOLITION.

2. RE-USE EXISTING BREAKERS.

3. PROVIDE 3 - #4/0, #4/0 N, #4 GND WIRING. MATCH EXISTING CONDUIT. MATCH

EXISTING CONTROL AND ALARM WIRING.

4. PROVIDE 3 - #350, #350 N, #4 GND WIRING. MATCH EXISTING CONDUIT. MATCH

EXISTING CONTROL AND ALARM WIRING.

5. PROVIDE TWO SETS OF 3 - #3 / 0, 1 - #3 / 0 N, #3 GND WIRING. MATCH EXISTING

CONDUIT. MATCH EXISTING CONTROLS AND ALARM WIRING.

6. PROVIDE TWO SETS OF 3 - #350, 1 - #350 N, #1 GND WIRING. MATCH EXISTING

CONDUIT. MATCH EXISTING CONTROLS AND ALARM WIRING.

7. PROVIDE TWO SETS OF 3 - #400, #1 / 0 GND WIRING. MATCH EXISTING

CONDUIT. MATCH EXISTING CONTROLS AND ALARM WIRING.

8. EXTEND AND RECONNECT EXISTING CABLE THROUGH BOX FOR CONNECTION

TO ATS. (DETAIL 3 THIS DRAWING)

9. SWITCHGEAR 3A-SERVES

ATS-10-600A

X-RAY-400A

6TH FL MECH RM-600A

10. USE EXISTING UNISTRUT AND CONDUIT TRAPEZE'S WHEN POSSIBLE.

PROVIDE (WIRE AND CONDUIT SIZE) AND RECONNECT TO EXISTING BREAKER

FEEDING ATS-5.

11. APPROXIMATE LOCATION OF TEMPORARY ATS AND SWITCHBOARD.

12. ROUTE TEMPORARY CABLES VIA WALL PENETRATIONS HIGH ENOUGH TO

PREVENT FLOODING. REFER TO DRAWING ES101.

13. TAP THE 480V SIDE OF TRANSFORMER J TO POWER THE TEMPORARY ATS,

SIMILAR TO WHAT WAS DONE WITH SWITCHBOARD 3A ON THE K

TRANSFORMER SIDE.

14. THE PULL/TERMINATION BOXES ARE FOR CONTRACTOR USE TO CONNECT

THE EMERGENCY, NORMAL, AND LOAD NEW AND EXISTING CABLES.

CONTRACTOR TO SIZE THE BOXES AND BUS BARS AS NEEDED FOR THE

DIFFERENT ATS. BOXES OF ATS WITHOUT NEUTRALS DON'T REQUIRE THE

NEUTRAL BARS.

15. PROVIDE 3-#4/0, #4 GND WIRING. MATCH EXISTING CONDUIT.

16. PROVIDE TWO SETS OF 3-#3/0, #3 GRD WIRING. MATCH EXISTING CONDUIT.

MATCH EXISTING CONTROLS AND ALARM WIRING.

SPACESPACE

SPACE

SPACE

SPACE SPACE SPACE

SPACE

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

PARTIAL BASEMENT FLOOR - NEW

NTS

ENLARGED SWITCHGEAR

NTS

ENLARGED SWITCHGEAR ROOM BF112 ELEVATION - A

A

NTS

ENLARGED SWBD 3A ROOM BF112 ELEVATION - B

B

NTS

PULLBOX/TERMINATION BOXES

KEYNOTES 00

EP111

MAIN TIE MAIN

SW

IT

CH

T

-J

MAIN SWITCHGEAR

MAIN

XFMR KXFMR J

INACTIVE SWITCH

BOX OLD TEMP.

DPCR

ATS-1

DPLS

PNL 4A

BOX C/B HB2LS

BOX C/B LB2CR

MCC #4

J-BOX BOX C/B SR

XFMR SR-1

SWITCH L

SW

IT

CH

T

-K

XFMR HMECH BF112

STR #6

250A

ATS-11 ATS-12

PNL HB1

ATS-5

225A

ATS-3

650A

W

IR

EW

AY

ATS-2

600A

WIREWAY

WIREWAY

WIREWAY

WIREWAY

1 1 1

4 6 6

BF112

BF113

J

J

J

J

J

J

ATS-9

225A

ATS-8

800A

ATS-7

400A

ATS-6

200A

ATS-10

400A

J

J

J

J

A

B

W

IR

EW

AY

INSULATOR

BUSBAR

ENCLOSURE

A

B

C

N

GND

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

KEY PLAN

04/26/2023

KEY PLAN

E

A

B

F

C

D

NO SCALE

Plan North

VEG 21.19

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

PARTIAL BASEMENT FLOOR - EXISTING

Plan North

1. PROVIDE ATS-4. RE-USE EXISTING CONDUITS AND J-BOXES WHEN

POSSIBLE. INSTALL NEW J-BOXES WHEN NECESSARY. SEE DETAIL 3 ON

SHEET EP111.

2. REMOVE EXISTING ATS-4. PROVIDE TEMPORARY POWER TO PANEL HBE

FOR CONTINUED OPERATION.

3. PROVIDE ATS PER SPECIFICATION 26 36 23. EXTEND EXISTING TWO SETS OF

3 - #350, #1 GND WIRING. AND CONDUIT, FROM OLD LOCATION THROUGH

JUNCTION BOX TO NEW LOCATION SHOWN.

4. DISCONNECT AND REMOVE CONDUIT AND JUNCTION BOXES.

5. MAINTAIN EXISTING UNISTRUT TO EXTEND CONDUIT AND FEEDERS FROM

PANEL HBE TO THE NEW LOCATION FOR ATS-4.

6. INTERCEPT EXISTING CONDUIT AND CONDUCTORS ON OTHER SIDE OF

WALL AND EXTEND TO NEW PULLBOX AND THEN TO NEW ATS-4 LOCATION

FOR TERMINATION.

7. INTERCEPT POWER FEEDS AND CONDUIT FROM EXISTING PANEL HBE IN

ROOM BF114 AND EXTEND TO NEW PULLBOX AND THEN TO NEW ATS-4

LOCATION FOR TERMINATION.

8. PROVIDE A 4" HOUSEKEEPING PAD.

9. INTERCEPT NORMAL AND EMERGENCY POWER FEEDS AND CONDUIT FROM

EXISTING ROOM BF114 AND EXTEND TO NEW PULLBOX AND THEN TO NEW

ATS-4 LOCATION FOR TERMINATION.

10. PROVIDE NEW 24"X24"X12" PULLBOX MOUNTED AT A MINIMUM 12" ABOVE

THE ATS.

11. PREPARE AND SUBMIT ALL OUTAGE PLAN PER SPECIFICATIONS AS MAY

DEEM NECESSARY FOR VA APPROVAL PRIOR TO EXECUTION OF THE WORK.

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

PARTIAL BASEMENT FLOOR - NEW

Plan North

TM WHB

EP112

BASEMENT PARTIAL FLOOR PLANS

ATS-4

NTS

BF114 ELEVATION

4 NTS

BF115 ELEVATION

EXISTING ATS-4

600A

P12

PNL HBE

FIRE ALARM

P12 CNTL PNL

P12 BKR

P12 DISCO

PRIMARY, SECONDARY,

FIRE HAT, SHUNT

BF115

BF114

STAIR #7

ELEV

P-12

BA123a

ELEV

P-11

P12

PNL HBE

FIRE ALARM

P12 CNTL PNL

P12 BKR

P12 DISCO

PRIMARY, SECONDARY,

FIRE HAT, SHUNT

BF115

BF114

STAIR #7

ELEV

P-12

BA123a

ELEV

P-11

NEW ATS-4

600A

J

TM WHB

ES101

BASEMENT - TEMPORARY POWER

1. SUBMIT PLAN FOR VHA APPROVAL BEFORE SETTING TEMPORARY

GENERATOR AND BARRIERS. PROTECT GENERATOR IN ACCORDANCE

WITH THE REQUIREMENTS OF 010000 GENERAL REQUIREMENTS.

2. SUBMIT PLAN FOR VHA APPROVAL BEFORE ROUTING CABLES. PROTECT

CABLES IN ACCORDANCE WITH THE REQUIREMENTS OF 01000 GENERAL

REQUIREMENTS.

3. PROPOSED ROUTING OF TEMPORARY CABLES.

4. PROPOSED LOCATION OF TEMPORARY GENERATOR.

5. CABLES BETWEEN GENERATOR AND TEMPORARY ATS.

6. CABLES BETWEEN TEMPORARY SWITCHBOARD.

7. APPROXIMATE LOCATION OF ATS AND SWITCHBOARD. SUBMIT PLAN FOR

VA APPROVAL BEFORE SETTING THE EQUIPMENT. SEE DRAWING EP111

FOR ADDITIONAL INFORMATION. WILL REMOVE SWITCHBOARD, ATS AND

CABLES AT THE END OF PROJECT.

8. ROUTE CABLES TO OUTSIDE VIA WALL BORING HIGH ENOUGH TO

PREVENT FLOODING. REPAIR HOLES AFTER PROJECT. SUBMIT PLAN FOR

VHA APPROVAL BEFORE BORING HOLES.

9. PREPARE AND SUBMIT ALL OUTAGE PLAN PER SPECIFICATIONS AS MAY

DEEM NECESSARY FOR VA APPROVAL PRIOR TO EXECUTION OF THE

WORK.

1" = 10'

PARTIAL BASEMENT FLOOR PLAN1

Pl an

N or th Tr ue N or th

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

KEY PLAN

GENERAL NOTES

04/26/2023

KEY PLAN

E

A

B

F

C

D

NO SCALE

Plan North

VEG 21.19

TEMPORARY JERSEY BARRIERS

PROPOSED TEMPORARY GENERATOR LOCATION

BF

BF104

BF105

BF106

BF117

BF100 BF101

BF

BF112

STAIR #6

BF113

BF115

BF114

STAIR #7

BF110

BF108

BF

BF109

ELEV

P-12

BF109a

BF104b

BF104a

BA

9c

BA119g

BA120

BA121

BA

BA

BA123a

BA123b

BE100a

BA123a1

ELEV

P-11

BF126

BF127

BF128a

BF125b

BF125

BF128

BF124

BF153

BF154

BF152

BF129

BF130

BF131

BF132

BF133

BF134

BF135

BF136 BF137

BF138

BF139 BF140

BF141

BF142

BF143

BF144

BF

BF146

BF147

BF148

BF149

BF150 BF151

BF155

BF129a

BF127a

1 4

TEMP GENERATOR

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

04/26/2023VEG 21.19 TM WHB

EP501

DETAILS

NO SCALE

CONDUIT TRAPEZE MOUNTING DETAIL2

NO SCALE

CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT1

NO SCALE

CONDUIT EXPANSION JOINT CROSSING DETAIL - EXPANSION FITTING3

NO SCALE

COMMON ELECTRICAL EQUIPMENT HOUSE KEEPING PAD DETAIL5

NO SCALE

TYPICAL RACEWAY SUPPORT METHODS DETAIL4

(3/8") MIN GALVANIZED

THREADED ROD, TYP.

LOCKING SQUARE

WASHER & LOCKNUT

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

WASHER & LOCKNUT

REFER TO PLANS

FOR QUANTITY &

SIZE OF CONDUITS

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

PROVIDE (5") OF SLACK AT MIDPOINT

BETWEEN TWO END OF FLEXIBLE

GALVANIZED STEEL CONDUIT.

PROVIDE GREEN INSULATED COPPER

EQUIPMENT GROUNDING CONDUCTOR

WITH FLEXIBLE CONDUIT.

FLOOR OR ROOF STRUCTURE. FIELD

VERIFY ACTUAL CONDITIONS, TYP.

SEISMIC OR EXPANSION JOINT.

FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

STEEL

EXPANSION

ANCHORCONDUIT

TRAPEZE

CONDUIT,

TYP.

(3' - 0") MAX

SPRING NUT

BEAM

CLAMP, TYP.

GENERAL NOTE:

DETAIL IS APPLICABLE

ONLY FOR CONDUIT

SMALLER THAN (3").

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND PERIMETER.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

EXPANSION FITTING

WITH BONDING JUMPER

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

SEISMIC OR EXPANSION JOINT.

FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, SECT.),

TYP.

STEEL

EXPANSION

ANCHORCONDUIT

TRAPEZE

CONDUIT,

TYP.

SPRING NUT

BEAM

CLAMP, TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

1.

2.

GENERAL NOTES:

INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL 1 ON THIS SHEET.

INSTALLATION IS REQUIRED FOR CONDUIT 3" OR LARGER.

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND PERIMETER.

(3'-0") MAX

HEAD

INSULATING

BUSHING

STRUCTURAL UNIT

NOTE: TIE WIRE SHALL NOT BE USED

AS A COMPONENT OF ANY RACEWAY

HANGER SYSTEM.

BEAM, CLAMP OR HANGER CLAMP AS

REQUIRED BY WEIGHT SUPPORTED

STRUCTURAL UNIT

BEAM, CLAMP OR HANGER CLAMP AS

REQUIRED BY WEIGHT SUPPORTED

RACEWAY

0.5" THROUGH 1"

ALL THREAD - SIZE AS REQUIRED

RACEWAY, .5" THROUGH 6"

CONDUIT HANGER

RACEWAY, .5" THROUGH 6"

4"

HOUSE KEEPING PAD

46"

40"

APPROXIMATE. 1,400 LBS

REFER TO STRUCTURAL

DRAWINGS FOR ADDITIONAL

INFORMATION

EP601

PRIMARY ONE LINE DIAGRAM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

04/26/2023VEG 21.19

1. WORK WILL BE OCCURRING IN SWITCHGEAR 3 ROOM BF112, ELEVATOR

ROOM BF114 AND GENERATOR ROOM BF115.

G

VS VM

"EMG"

35/1

AS50 A

5175/5

GS50/5

GS

50/5

51150/5 AS A

3 50

GS50/5

75/5

50 AS A AS

50/5

75/5

1 50

GS

50 A

SPARE"XFG"-EM"XFB"-EM "XFD"-EM

SO P.T.

A.T.S.

ATS

XFG

LIFE SAFETY

MCC # 1 & 2

G200/5

10 KVA

POWER

TRANSF

1Ø,120°/240V

4160V.,3Ø, 3W, 1200A, BUS

GS50/5

"XFJ"

300/5A

AS50

A

"XFG"

50/5 1 50

GS

50 AS A

"XFE"

GS

"XFB"

GS

50 AS A

51 AS A

GS

51 AS

"XFD"

A

UNIT SUBSTATION

200A 200A

5KV

50 P.T.

GS

51 AS A

GS

50 AS AAS

GS

50 A AS

GS

50 A

RESEARCH BLDG. #19

NON-CRITICAL TIE CRITICAL

5KV

5KV

5KV

5KV

5KV

5KV

5KV

BREAKER RELAY SETTING CONDUCTOR SERVES

PRIMARY ELECTRICAL FEEDER SCHEDULE

DESIG. FRAME 50/51 50 OR 51GS

"XFF"

"XFA"

"XFH" 1 - 3 1/2"

1 - 3 1/2"

1 - 3"

2 - 4"

2 - 4"

1 - 2 1/2" XFMR "F" & "H"

XFMR "L"

5KV

2 1

5KV

5KV

125KV

NO NC

P.T.

SO

CP

1000KW

1200A. BUS, 3Ø, 3W,+ GND.

SWITCHGEAR ROOM 1

CP

NC

NO

5KV

5KV

"XFC" "XFA" "XFF" "XFK"

250 A

TIE

P.T.

N

150/5

N.O.

MAIN 1 MAIN 227

1X

2X

N AS51 WM A

S.C.

L.A.

-2

-2

800/5

35/1 P.T.

2 VS VM

5KV

800/5

L.A.

S.C.

-1

-1

35/1 P.T.

2 5KV

VSVM

51N

51WMA AS

UTILITY

TRANSFORMER 2

5000 KVA

12.5 - 4.16 KV12.5 - 4.15 KV

5000 KVA

TRANSFORMER 1

UTILITY

NONC NC

NO

WEST 12.5 KV PARK PLACE SUB. EAST 12.5 KV STONEWALL SUB.

OG&E

EQUIPMENT

PARK PLACE

CHILLER #1

ELEVATORS

BLDG 1

GS

50 AS A

SO

NO

PT

SO

250A

ATS

XFB

A.T.S.

P.T.

NC

P.T.

250A250A

SWITCHGEAR ROOM 2

SWITCHGEAR ROOM 3

150 AMP

EQUIPMENT BRANCH TIE

NCP.T. SO

PT

SO

NO

460 KW GENERATOR

BUILDING 21 & BOILER PLANT

80 AMP

80 AMP

5 KV SWITCH

PULL SECTION

3 EA. (4#350 MCM & 1#2 G.)

SW

V

VS

A 100A/3P

125A/3P

CENTRIFUGAL CHILLER

1000A/3P

MCC #1

600A/3P

EMCC #1

400A/3P

SPACE

150A

100 AMP

50 AMP

TIEJ K

BLDG. #19

ARF BLDG.

BF-118

ER - NORMAL

CHILLER 1 CHILLER 2

480V

CHILLER MDP

CHILLER PLANT MDP

RAD/ONC

TELE SWITCH: 10th FL

6-500 MCM, 5 KV 2-1/0, GND.

CCLP-INSUL. INSUL.

LEVEL-100%

6-500 MCM, 5 KV 2-1/0, GND.

CCLP-INSUL. INSUL.

LEVEL-100%

3-NO. 2 1 #2 GND.

CCLP-INSUL.

3-2/0, 5KV 1-NO. 2 GND.

CCLP-INSUL.

3-350 MCM 1-NO. 2 GND.

CCLP-INSUL.

3-350 MCM 1-NO. 2 GND.

CCLP-INSUL.

XFMR "L"

4160-480/277V

750 KVA

500 TON

4160V. 3Ø

CENTRIFUGAL

CHILLER WITH

5KV STARTER

PER MECH

TRANSFORMER

"F" 1000 KVA

4160-480/277V.

TRANSFORMER

"H2" 500 KVA

4160-480/277V.

TRANSFORMER

"H1" 4160-480

/277V 300 KVA

TRANSFORMER "B"

1000 KVA

4160-208/120V

TRANSFORMER

"A" 1000 KVA

4160-208/120V

TRNFMR "H"

4160-480 /277V 300

KVA

TRANSFORMER "C"

300 KVA

4160-208/120V

TRANSFORMER "D"

300 KVA

4160-208/120V

5KV, 600 AMP, 3PDT

3 POSITION SWITCH,

SWITCH "L"

OFF POSITION

NORMAL SETTING

ON 1 ALTERNATE

SETTING ON 2

NORMAL SETTING ON 1

ALTERNATE SETTING ON 2

TRANSFORMER "K"

300 KVA

4160-480/277V

TRANSFORMER "J"

1000 KVA

4160-480/277V

5KV, 600AMP,

3PST

5 KV-DT-3 POSTION,

600 AMP SWITCH

5KV, 600AMP,

3PST

3#4,1#8G,2 1/2"C.

5KV. EPR.

TRANSFORMER "E"

1000 KVA

4160-480V.

500 KVA

4160-480V

TRANSFORMER "G"

225 KVA

4160-208/120V

TRANSFORMER "H3"

500 KVA

4160-480/277V

5 KV CIRCUIT

3#2/0,1#4G, 5KV EPR.

IN EX. CONDUIT

G.F.

SENSOR

ENCLOSED BKR.

1600 AMP 480/277V.

3Ø, 4W SWBD. 1600 AMP

480/277V. 3Ø, 4W

SCR CONT. NO. 1 (DOM. WTR.

BOOSTER PUMPS)

SCR CONT. NO. 2 (SEC.

CHILLED WATER PUMPS)

75/5

150/5

300/5

50/5

50/5

4160V. 3Ø 3W +GND, 1200A. BUS

3Ø ISC = 7403 AMP

300/5

50/5

MAIN SERVICE

NO. 1

MAIN SERVICE

NO. 2

XFMR "K"

ALTERNATE "L"

XFMR "J"

ALTERNATE "K"12

A

MP

F

RA

ME

-3 0,0

A

MP

IN

TE

RR

UP

TI

NG

C

AP

AC

IT

Y

MAIN

NO. 1

MAIN

NO. 2

"XFJ"

NEW

CABLE

DESIG.

CONDUIT

SIZE

P.T.

A.T.S.

4160V. 3Ø 3W +GND,

1200A. BUS 3Ø ISC = 6053 AMP

TO SYNC.

CCT. OF

GEN

75/5

50/5

50/5

300/5

150/5

50/5

300/5

50/5

50/5

100/5

STONEWALL

KITCHEN 480 V.

MICROWAVE 480 V.

7B X-RAY

TELE. OFFICE

LAUNDRY

FIRE PUMP, 4

GROUP AIR

COMPRESSORS

SUB-BSMT

250A

TMueck Note

K

K

K

HG1 H11 MCC-2 HG2 H12 H32 H43H13 H73 MCC-3 ATS-3 ATS-5 MCC-4

MAIN

BKR.

(29616)

FEEDER 13

5KV FEEDER

5KV

(28316)

(26661)

AS

AM

WM

VS

VM

GF

GF

GF

GF

LIF

E

SA

FE

TY

R

IS

ER

ME

CH

. P

EN

TH

OU

SE

R

IS

ER

6th

FL

R.

M

EC

HA

NI

CA

L R

IS

ER

X-

RA

Y

RI

SE

R

CR

IT

IC

AL

P

OW

ER

R

IS

ER

(19464)(25762) (14069)(19810)(20102)

NO

RM

AL

P

OW

ER

R

IS

ER

CRITICAL RISER

X-RAY RISER

6th FLR. MECH. RISER

MECH. PENTHOUSE RISER

LIFE SAFETY RISER

(16059)

(2915)

(2915) (2915)

(2915) (2915)

(3480)

P-11

P-10

P-9

3#1,1#6G.,1 1/2"C. (TYP.)

P-8

P-7

P-12

500 KW GENERATOR

ATS-3 ATS-5

UNIT SUBSTATION #3 - RM. BF-112

LOCATED IN BF-114 ON DRAWING EP112

TM WHB

EP602

ATS POWER RISER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

04/26/2023VEG 21.19

1. REPLACE AUTOMATIC TRANSFER SWITCH.

2. DISCONNECT CABLE AND TEST. GIVE VALUES TO ENGINEERS FOR

EVALUATION. IF CABLE IS IN ADEQUATE CONDITION, MOUNT WALL OR

CEILING BOX, CUT AND COIL THE END IN BOX FOR RE-USE.

3. SEE SHEET EP111 AND ES101 FOR MORE INFORMATION.

1 1 1 1 1

1 1 1 1

480V, 3Ø, 200 AMP

FUSED @ 125 AMPS

(TYPICAL OF 4)

EX. PNL. HBE

480V, 3Ø, 600 AMP

480V, 3Ø

125 AMP

EX. HYDRAULIC

ELEVATOR

CONTROLLER

ATS-9

LIFE SAFETY

BRANCH

400AMP

ATS-4

ELEVATOR

RISER

480V, 3Ø

600 AMP

EMERGENCY

EQUIP

ATS-1

LIFE

SAFETY

RISER

ATS-2

CRITICAL

RISER

500 KW

GENERATOR

ATS-EQUIP

EMCC #1

3 #1, 1 #6 GND.,

1 1/2" C. (TYP.)

TO ELEVATOR

CONTROLLERS 8F-100A

ATS-8

EQUIPMENT

SYS.

800AMP

ATS-7

EQUIPMENT

SYS.

600AMP

ATS-6

X-RAY

POWER

400AMP

SWBD 3A

1200AMP,

1000A M.B.

480/277V, 3Ø, 4W

4160 - 480/277V

TRANSFORMER "K"

1000/1150 KVA

ATS-8

PENT.

MECH.

BREAKER

ATS-9

LIFE

SAFETY

BREAKER

ATS-1

LIFE

SAFETY

RISER

H6

BKR.

H31

4160 - 480/277V

TRANSFORMER "J"

1000/1150 KVA

ATS-2

CRITICAL

RISER

ATS-4

ELEVATOR

RISER

MAIN

BKR.

ATS-10

CRITICAL BRANCH

600AMP

600 KW

GENERATOR

TIE N.O.

1600A 1600A

1200 400

2 2 2 2

2 2 2 2 2

2 2

ATS9

EMERGENCY

EQUIP

ATS10ATS6ATS7ATS8

FB100E

FB1001

FB1000

FA601 FB801 ATS3 ATS5

FA600 FB800 FB1100 FB900

FB600E FB800E FB900E FB1100E

FEEDER SCHEDULE

ATS-# CABLE CONFIGUREATION EXTENDED FOR EACH PHASE

2[1(#400) +1(#1/0 GND)]

#4/0, #4/0 N, #4 GND

#2/0, #3 GND

#4/0, #4/0 N, #4 GND

#350, #350 N, #4 GND

2[1(#3/0, #3/0 N, #3 GND)]

2[3(#3/0, #3 GND)]

2[#350, #350 N, #1 GND]

2[#350, #350 N, #1 GND]

12'

10'

10'

10'

60'

10'

10'

10'

10'

10'

2[#350, #1 GND]

G 1150KW TEMP GENERATOR

1200A

100A

TEMPORARY 1200A SWITCHBOARD

TEMP ATS 1200A - NORMAL,

OFF, GENERATOR3

BRANCH FOR TEMPORARY POWER ATS LOADS

BRANCH FOR CONTRACTOR POWER

NORMAL SOURCE

CABLE CONFIGUREATION

2[1(#400)+1(#1/0 GND)]

#4/0, #4/0 N, #4 GND

#2/0, #3 GND

#4/0, #4/0 N, #4 GND

#350, #350 N, #4 GND

2[1(#3/0, #3/0 N, #3 GND)]

2[3(#3/0, #3 GND)]

2[#350, #350 N, #1 GND]

2[#350, #350 N, #1 GND]

2[#350, #1 GND]

EMERGENCY SOURCE

CABLE CONFIGUREATION

2[1(#400)+1(#1/0 GND)]

#4/0, #4/0 N, #4 GND

#2/0, #3 GND

#4/0, #4/0 N, #4 GND

#350, #350 N, #4 GND

2[1(#3/0, #3/0 N, #3 GND)]

2[3(#3/0, #3 GND)]

2[#350, #350 N, #1 GND]

2[#350, #350 N, #1 GND]

2[#350, #1 GND]

LOAD APPROX. LENGTH

UNIT SUBSTATION BF112

LOCATED IN SWGR. RM. 3

T-B2

GROUND

1ST FLOOR

2ND FLOOR

3RD FLOOR

4TH FLOOR

5TH FLOOR

6TH FLOOR

7TH FLOOR

8TH FLOOR

T-G2

T-12

T-32

PANEL

LG3

PANEL

L23

T-13

T-43

T-73

T-G1

T-11

T-31

2 1/2"

1 1/4", 4-#2, 1-#8 GND.

J 18" x 12" x 6"

100 AMP

4-#2 1-#8 GND.

FB622

FB610FB620

FB621

FB522

FB521

FB510FB520

SCA

FB421

FB420

FB410

FB500

ATS-4

FB1001

FB1007

ATS-5

FB1100E

FB900E

FB800E

ATS-3

FB600E

ATS-2

FB801

ATS-1

FA601

FB800

FA600

FB1100

FB900

T-K

FB1002

T-43

FB830

CR

FB812

T-J

FB1200

FB121 FB111

FA606

FB822

FB100

FB120 FB110

FB201

FB310

FB320

FB301

FB810FB820

FA603

FA100

FA121 FA120

FA110

FA200

FB901

FB1110 ATS 5

FA210

FA220

FA221

FB821

FA604

FA602

FB902

T-22

CR

FB811FB823

FA201

FA301

FA320 FA310

FA321

FB825

FB824

T-4EDP

FB1120

FB

CB-225A

FB1140

FA605FA500

BASEMENT FLOOR

TGRLS

45KVA

(1543)

(1630)

LGRLS

(2760)

DX2

BLDG 20

T45CR

FB1000E

FB1000

FLOORFLOOR

1ST FL

GROUND

2ND FL

3RD FL

4TH FL

5TH FL

6TH FL

7TH FL

ATS 8

ATS 6

ATS 10

ATS 7

ATS 9

ATS 3

HG1

H11

HG 2

H6

T3CR T3LS

8TH FL

1F-136

30KVA 15KVA

T-B2

PANEL

HB2LS

17000

SCA

PANEL

LB2CR

3321 SCA

PANEL

LB2A

PANEL

LB2

SCA

PANEL

HB2

13000

SCA

MCC-4

17215

SCA

J

BF135

T-B2

PANEL

HG2LS

15000

SCA

PANEL

LG2CR

SCA

PANEL

HG2CR

SCA

PANEL

LG21CR

PANEL

L12CR

SCA

PANEL

L12CRA

PANEL

H2X

19126

SCA

H2X1

X-RAY

SCA

PANEL

H22LS

14362

SCA

PANEL

L22CR

SCA

PANEL

H22CR

105863

SCA

PANEL

HPT1

PANEL

HPT1A

PANEL

HPT2

PANEL

LPT1

IPU-X DX1

PANEL

H71CR

PANEL

XRAY

PANEL

H6CR

PANEL

H72CR

PANEL

H62CR

PANEL

L51CR

PANEL

L72CR

PANEL

H6M2

PANEL

5NS2

PANEL

5NS1

PANEL

L5LS

PANEL

H5LS

PANEL

H6LS

PANEL

L52CR

PANEL

H52CR

PANEL

H4EDP

14000

SCA

PANEL

EDPE

22000

SCA

PANEL

H42LS

14000

SCA

PANEL

L42CRA

PANEL

L42CRB

3424 SCA

PANEL

L44CR

SCA

PANEL

H6M1

PANEL

L6M1

PANEL

L6E

PANEL

X-RAY

CYSTO

PANEL

H7LS

PANEL

L7LS

PANEL

7NS

PANEL

PANEL

LPLS

PANEL

L45CR

PANEL

H43CR

14292

SCA

PANEL

L43CR

SCA

PANEL

H33LS

11618

SCA

PANEL

DPLS

17248

SCA

PANEL

DPCR

18227

SCA

PANEL

HBE

15143

SCA

TM WHB

EP603

RISER DIAGRAM SWITCHGEAR

ROOM #3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

04/26/2023VEG 21.19

1. REPLACE AUTOMATIC TRANSFER SWITCH. REFER TO ATS POWER

RISER SHEET.

2. CONNECT TEMPORARY POWER AT EXISTING CABLES IN ELECTRIC

ROOM 3 AND ELEVATOR ROOM TO KEEP PANEL POWERED DURING

CONSTRUCTION. SCHEDULE CONNECT AND DISCONNECT OUTAGES

WITH VA.

3. SEE SHEET EP111 AND ES101 FOR MORE INFORMATION.

1 1 1 1 1

1 1 1 1 1

FEED FROM MAIN LUG OUT OF H41. TERMINATES INTO A 125 AMP BRKR. IN

PANEL H41B.

100 AMP FEED FROM L41A

CIRC. 38-40-42

FEED FROM

L21B 100

AMP. CIRC.

37-39-41

PANEL

L41C

208Y/120V 3Ø 4W

100A M.B.

42 CKT

PANEL

H41A

480Y/277V 3Ø 4W

100A M.B.

42 CKT

PANEL

H31

14925

SCA

PANEL

L31

SCA

PANEL

L21C

208Y/120V 3Ø 4W 100

AMP MAIN

LUG 42

CKT

PANEL

L21B

SCA

PANEL

L11B

SCA

PANEL

L11A

SCA

PANEL

H11 15530

SCA

PANEL

L11AA

PANEL

LG1D

208Y/120V 3Ø 4W 100A M.B.

42 CKT

PANEL

H21

15146

SCA

PANEL

L21A

MCC-3

SCA

ELEC

AREA

PANEL

H73

SCA

PANEL

L73

SCA

PANEL

L83

ELEVATORS

P-7, 8, 9, 10 ELEVATOR

P-11

PANEL

L63

SCA

PANEL

L53

SCA

PANEL

L43

SCA

PANEL

H43

SCA

FB1003

FB1004

FB1005

FB1006

T5N1

45 KVA

PANEL

H6

PANEL

H62

T6N

30 KVA

PANEL

L62

PANEL

L71

T7N1

30 KVA

PANEL

H71

PANEL

H72

T7N2

75 KVA

PANEL

L72

PANEL

L73

T7LS

45 KVA

T-XRAY

45 KVA

T5LS

45 KVA

PANEL

L42D

208Y/120V 3Ø 4W

100A M.B.

42 CKT

PANEL

L42A

SCA

PANEL

L42C

SCA

PANEL

H42

13162

SCA

PANEL

H42B

480Y/277V 3Ø 4W 100A

M.B. 42

CKT

PANEL

L42B

FEED FROM H32

225 AMP. BRKR.

4-4/0, 1-#2 GND.

TO A 225 AMP

BRKR. IN H42B.

150 AMP

3-1/0 1-#2

GND.

4-3/0 1-#2

GND.

4-3/0 1-#2

GND.

TPT-1

15 KVA

TO

X-RAY

EQUIP.

T-7CR

75 KVA

T51CR

45 KVA

T6M 75

KVA

PANEL

A2 CR

PANEL

LB2B

PANEL

A1 CR

PANEL

LB2C

PANEL

LB3 LS

PANEL

HB3 LS

PANEL

LB3 CR

PANEL

HB3 CR

PANEL

HB2A

FB101

HG2

ATS-9ATS-7ATS-10

TO EMERGENCY GENERATOR

BLDG 20, 600 KW

PANEL

LG1A

SCA

PANEL

LG1B

PANEL

HG1

15848

SCA

FA300

H31

FB802

DPCR

FB803

DPCR

100 AMP FEED

FROM H12

4-#2 1-#8 GND.

4-3/01-#2

GND.

75 KVA

T12A

PANEL

L12C

PANEL

L12B

PANEL

LG2B

208Y/120V 3Ø 4W

100A M.B.

42 CKT

PANEL

LG2C

4-3/0 1-#2

GND

ATS-8 ATS-6

PANEL

LG1C

T-G2

CR

PANEL

L12A

SCA

PANEL

H12 13467

SCA

PANEL

LG2A

SCA

PANEL

HG2

13676

SCA

PANEL

H12A

FB200

H12

FB300

H32

PANEL

H32

13242

SCA

PANEL

L32

SCA

FEED FROM

TRANSFORMER

TO 225 AMP

MAIN

PANEL

L22

1CR

PANEL

L22A

SCA

PANEL

L22B

SCA

PANEL

H22

13162

SCA

PANEL

MCC2

12295

SCA

1 1/4" CONDUIT

4-#2 1-#8 GND.

1" CONDUIT

3-#6 1-#8 GND.

50 AMP. BRKR

FROM H13

FB804

DPCR

FB610

H43

FB700

MCC3

FB600

H73

FB400

H13

PANEL

H52

T52 45

KVA

PANEL

L52

PANEL

L53

PANEL

L51

T-22

1CR

100 AMP

4-#2 1-#8

GND.

75 KVA

T-21

T52CR

75 KVA

T42 112.5

KVA

ELEVATOR

P-12

BRKRS

B1-B12

BRKRS

A1-A10

PANEL

SWBD 3A

1200 AMP

1000 A. MB.

480/277V 3Ø, 4W

PANEL

H13

SCA

PANEL

L13

SCA

45 KVA

T-23

PANEL

L33

SCA

500 kw

GEN

PANEL

H41 14000

SCA

PANEL

H41B

PANEL

L41B

PANEL

L41A

SCA

MAIN

LUG

ATS 5

EGB

EP604

RISER DIAGRAM ATS REMOVAL

AND INSTALLATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

04/26/2023VEG 21.19

1. DISCONNECT LOAD CABLES, CONNECT TEMPORARY POWER TO

LOAD PANELS VIA EXISTING CABLES FOR RE-USE.

2. DISCONNECT - NORMAL CABLES.

3. DISCONNECT EMERGENCY POWER CABLES AND CONTROL WIRES.

4. REMOVE ATS.

5. MOUNT NEW ATS AT GENERAL LOCATION OF REMOVED ATS.

6. CONNECT EXISTING NORMAL CABLES AND NEW ATS CABLES AT BOX.

7. CONNECT EXISTING AND NEW ATS EMERGENCY CABLES AND WIRES

AT BOXES.

8. DISCONNECT LOAD CABLES FROM TEMPORARY POWER, CONNECT

EXISTING AND NEW ATS LOAD AT BOXES, RESTORE POWER TO THE

ATS AND PUT ATS BACK IN SERVICE.

9. SEE DETAIL 3 ON SHEET EP111 FOR BOX INFORMATION.

ATS

LOAD

PANEL

NORMAL

SOURCE

EMERGENCY

SOURCE

ATS

LOAD

PANEL

NORMAL

SOURCE

EMERGENCY

SOURCE

NO SCALE

REMOVAL DIAGRAM TYPICAL OF ATS-1, 2, 3, 6, 7, 8, 9,101 NO SCALE

INSTALLATION DIAGRAM TYPICAL OF ATS-1, 2, 3, 6, 7, 8, 9, 102

EP605

RISER DIAGRAM ATS-5 REMOVAL

AND INSTALLATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

04/26/2023VEG 21.19

1. DISCONNECT LOAD CABLES, CONNECT TEMPORARY POWER TO

4HDPE PANEL VIA EXISTING CABLES IN ROOM 3.

2. DISCONNECT - NORMAL CABLES, INSTALL JUNCTION BOX ON

CEILING NEAR SUBSTATION 3 WITH EXISTING CABLES FOR RE-USE.

3. DISCONNECT EMERGENCY POWER CABLES AND CONTROL WIRES.

4. REMOVE ATS-5.

5. MOUNT NEW ATS-5 AT LOCATION ON NORTH WALL SHOWN ON

DRAWING EP111.

6. CONNECT EXISTING NORMAL CABLES AND NEW ATS-5 CABLES AT

BOX.

7. CONNECT EXISTING AND NEW ATS-5 EMERGENCY CABLES AND

WIRES AT BOXES.

8. DISCONNECT LOAD CABLES FROM TEMPORARY POWER, CONNECT

EXISTING AND NEW ATS-5 LOAD AT BOXES, RESTORE POWER TO

THE ATS-5 AND PUT ATS-5 BACK IN SERVICE.

9. SEE DETAIL 3 ON SHEET EP111 FOR BOX INFORMATION.

ATS-5

LOAD

PANEL

4HEDP

NORMAL

SOURCE

EMERGENCY

SOURCE

ATS-5

LOAD

PANEL

4HEDP

NORMAL

SOURCE

EMERGENCY

SOURCE

NO SCALE

REMOVAL DIAGRAM TYPICAL OF ATS-51 NO SCALE

INSTALLATION DIAGRAM TYPICAL OF ATS-52

EP606

RISER DIAGRAM ATS-4 REMOVAL

AND INSTALLATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

635-21-121

OKLAHOMA CITY, OKLAHOMA 73104

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER

SWITCHES

00KEYNOTES

04/26/2023VEG 21.19

1. DISCONNECT LOAD CABLES, CONNECT TEMPORARY POWER TO HBE

PANEL, INSTALL BOX FOR NEW CABLES BETWEEN ROOMS BF114

AND BF115.

2. DE-ENERGIZE NORMAL CABLES, PULL BACK INTO ROOM BF115 FOR

RE-USE.

3. DISCONNECT EMERGENCY POWER CABLES AND CONTROL WIRES,

INSTALL BOXES WITH EXISTING CABLE AND WIRING FOR RE-USE.

4. REMOVE ATS-4.

5. MOUNT NEW ATS-4 IN ROOM BF115.

6. RECONNECT EXISTING NORMAL CABLES TO NEW ATS-4, CONNECT

NEW CABLE IF ADDITIONAL CABLE IS REQUIRED.

7. CONNECT EXISTING AND NEW ATS-4 EMERGENCY CABLES AND

WIRES AT JUNCTION BOXES.

8. DISCONNECT PANEL HBE FROM TEMPORARY POWER, CONNECT

NEW ATS-4 CABLES TO HBE PANEL VIA BOXES, RESTORE POWER TO

THE ATS-4 AND PUT ATS-4 BACK IN SERVICE.

9. SEE DETAIL 3 ON SHEET EP111 FOR BOX INFORMATION.

ATS-4

LOAD

PANEL

HBE

NORMAL

SOURCE

EMERGENCY

SOURCE

ATS-4

LOAD

PANEL

HBE

NORMAL

SOURCE

EMERGENCY

SOURCE

NO SCALE

REMOVAL DIAGRAM TYPICAL OF ATS-41 NO SCALE

INSTALLATION DIAGRAM TYPICAL OF ATS-42

File details come from the government source that posted it. Updated .