635-21-121 (VEG 21.19) 100PCT Stamped Drawings 04-25-2023.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25923R0065
About this file
This statement of work outlines requirements for replacing ten automatic transfer switches at the Oklahoma City VA Medical Center. The contractor will remove the existing ATS units and install new ones according to provided drawings and specifications. The contractor must be a licensed electrical contractor and will provide all necessary labor, materials, tools and equipment. The project is expected to take no more than 90 days. The contractor must coordinate all utility outages with the VA at least two weeks in advance and is responsible for daily clean up and securing the work site.
The contractor must follow all applicable codes and standards and will inspect the ATS units prior to replacement. A one-year warranty is required. The objective is to directly replace the ATS units while minimizing disruptions to the medical center's operations. The contractor must submit documentation and provide training at the completion of the project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25923R0065 0003.docx | DOCX document | |
| Pre-Bid Sign in Sheet.pdf | ||
| 21.19 PRE BID RFI Log 07-17-2023.pdf | ||
| 36C25923R0065 0002.docx | DOCX document | |
| 36C25923R0065 0001.docx | DOCX document | |
| 36C25923R0065_1.docx | DOCX document | |
| Specifications - 635-21-121.pdf | ||
| NEW - Calculation Worksheet for Self-Performed and Subcontracted Work.docx | DOCX document | |
| S02-3-10-2021 Past Performance Questionnaire_Blank_Fillable PDF.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AREA OF WORK SHEET INDEX
OKLAHOMA CITY HEALTH CARE SYSTEM
OKLAHOMA CITY, ST
VAMC PROJECT #: 635-21-121
REPLACE AUTOMATIC TRANSFER SWITCHES
Plan North
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
04/26/2023VEG 21.19 TM WHB
GI001
COVER SHEET
Pl an
N or th
True North
NO
RT
H
KE
LL
EY
A
VE
NE 13th STREET
PROJECT SITE
NE 13th STREET
NO
RT
H
KE
LL
EY
A
VE
NO
RT
H
PH
ILL
IP
S
AV
E.
NE 15th STREET
NE 16th STREET NE 16th STREET
NO
RT
H
PH
ILL
IP
S
AV
E.
NE 14th STREET
NE 15th STREET
SHEET NO. SHEET NAME
GI001 COVER SHEET
E-001 ELECTRICAL SYMBOLS
E-002 ELECTRICAL SYMBOLS & ABBREVIATIONS
ED111 BASEMENT PARTIAL DEMO FLOOR PLANS
EP111 SWITCHGEAR ROOM #3
EP112 BASEMENT PARTIAL FLOOR PLANS
ES101 BASEMENT TEMPORARY POWER
EP-501 DETAILS
EP-601 PRIMARY ONE LINE DIAGRAM
EP-602 ATS POWER RISER
EP-603 RISER DIAGRAM SWITCHGEAR ROOM #3
EP-604 RISER DIAGRAM ATS REMOVAL AND INSTALLATION
EP-605 RISER DIAGRAM ATS - 5 REMOVAL AND INSTALLATION
EP-606 RISER DIAGRAM ATS - 4 REMOVAL AND INSTALLATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
VEG 21.19
N
EGC
04/26/2023 TM WHB
E-001
ELECTRICAL SYMBOLS
SWITCH, NORMALLY CLOSED FLOAT
SWITCH, NORMALLY CLOSED FOOT OPERATED
SWITCH, NORMALLY CLOSED LIMIT
SWITCH, NORMALLY CLOSED TEMPERATURE
ACTIVATED
SWITCH, NORMALLY OPEN FLOAT
SWITCH, NORMALLY OPEN TEMPERATURE
ACTIVATED
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
PULL BOX
PRESSURE SWITCH-CLOSE ON
INCREASE
PRESSURE SWITCH-OPEN ON
INCREASE
MANHOLE
ELECTRICAL SYMBOLS - DIAGRAM
TIME CLOCK
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED
FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.
RECEPTACLE, SWITCHED
DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE
CORD (CENTER LINE OF OUTLET: 6'-6" AFF. (MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS
DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR
TELEPHONE, DATA & RECEPTACLE.
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
ELECTRIC DOOR STRIKE
CARD READER
MAGNETIC DOOR POSITION SWITCH
CAMERA
JUNCTION BOX
MAGNETIC LOCK
OUTLET, COMBINATION TELEPHONE/DATA
COMMUNICATION
CABLE TELEVISION LINE
CLOSED CIRCUIT TELEVISION LINE, MINIMUM 1" CONDUIT
FIBER OPTIC LINE
FLOOR BOX: SYMBOL INDICATES TYPE
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND. MTD.
7'-6" AFF UNLESS OTHERWISE NOTED.
OUTLET TELEPHONE ONLY
TELEPHONE LINE
INTERCOM LINE, MINIMUM 3/4" CONDUIT
SOUND LINE
NURSE CALL LINE, MINIMUM 3/4" CONDUIT
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM C = 6" ABOVE COUNTER
RADIO, MINIMUM 3/4" CONDUIT
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"
AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK= 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" AFF
M = MONITOR (CCTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER
TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS
AT MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" AFF UNLESS NOTED OTHERWISE.
E = MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB
LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE
NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF LAMP)
MTD 6" ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
REMOTE DICTATING OUTLET MTD 1'-6" AFF. UNLESS OTHERWISE
NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL OPERATION
OF INSTRUMENT & TYPE REQUIRED).
TELECOMMUNICATIONS MANHOLE
DATA BOX
DURESS BUTTON
CCTV SYSTEM WORKSTATION
REQUEST TO EXIT MOTION DETECTOR
REMOTE DOOR RELEASE BUTTON
CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM
NURSE CALL MASTER CONSOLE
ETHERNET NETWORK SWITCH
WIRELESS ACCESS POINT
COMMUNICATION SYMBOLS:
SWITCH
F = FUSED SWITCH
K = KEY OPERATED
L = LOCK
LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING
MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT
P = WITH PILOT LIGHT (THERMAL TYPE)
X = EXPLOSION PROOF
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE
LVD = LOW VOLTAGE DIMMER
LV= LOW VOLTAGE SWITCH
GS= GRAPHIC SCREEN CONTROL STATION
PB= PUSH BUTTON STATION
WP= WEATHER PROOF
T = TIMER OPERATED
LOS= OCCUPANCY SENSOR
ELECTRICAL SYMBOLS - LIGHTING PLAN
LIGHTING, ONE HEAD EMERGENCY BATTERY
POWER
STREET LIGHT WITH BRACKET
LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE
LIGHT POLE, TWO MAST ARMS, TWO LUMINAIRES
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHT POLE, ONE LUMINAIRE
LIGHTING, EXTERIOR BUILDING
LIGHTING, TWO HEAD EMERGENCY BATTERY
POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY
POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
LIGHT POLE, TWO LUMINAIRES
RECESSED DOWNLIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
JUNCTION BOX
TRANSFORMER, PLAN
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR
JUNCTION BOX
EARTH GROUND
LADDER CABLE TRAY
BRANCH CIRCUIT HOMERUN. ONE SEPARATE GREEN
GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH
HOMERUN; NOT SHOWN
WIREWAY
RIGID CONDUIT LINE
SUBSTATION
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
EQUIPMENT GROUND CONDUCTOR
NEUTRAL
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
SWITCH, NORMALLY OPEN TIME DELAY
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
MEDIUM-VOLTAGE OIL CIRCUIT BREAKER
MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
FUSIBLE LINK
VARIABLE FREQUENCY DRIVE
GENERATOR, POWER
BATTERY
CAPACITOR
LIGHTNING ARRESTOR
RECTIFIER, CATHODIC PROTECTION
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED, VAV
STARTER, COMBINATION W/DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
ELECTRICAL SYMBOLS - POWER PLAN
RECEPTACLE, DUPLEX 6" ABOVE COUNTER HEIGHT
RC
VFD
R
A
V
W
WH
T
S
HVS
LVS
P T
D
DP#__
LP
C
TC
T T
C C
W W
B B
C
S
H
S
J
F
RRB
C
C
PB
P
BLANK OUTLET BOX
RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE
DUAL PASSIVE INFRARED / MICROPHONIC TECHNOLOGY
(ULTRASONIC NOT ALLOWED)
M
DT
FLOOR OUTLET, RECEPTACLE
GROUNDING BAR
HEADWALL
A bx
A b x
A b x
LIGHT FIXTURE POWER CONNECTION DESIGNATIONS:
OPEN - NORMAL POWER CIRCUIT
SHADED - LIFE SAFETY EMERGENCY POWER CIRCUIT
HATCHED - CRITICAL POWER CIRCUIT
RECESSED TROFFER LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULES FOR MORE
INFORMATION.
CEILING SURFACE MOUNTED LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
WALL SURFACE MOUNTED LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
A b x
EXTERIOR FLOOD LIGHT
LIGHT FIXTURE, BOLLARD
LIGHT FIXTURE, DIRECTIONAL
R
ENTRY MONITOR/BUZZER COMBINATION OR DOOR BELL
DOME CAMERA
MOTION DETECTORM
ML
J
ES
CR
FIX
DB
CB
NCM
WAP
NWS
S
S
NCM
NCT
N
N
RX
WS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
04/26/2023VEG 21.19 TM WHB
E-002
ELECTRICAL SYMBOLS &
ABBREVIATIONS
NEUT OR N
NC
NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PULL BOX OR PANEL BOARD
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
REQ REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT·AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR
FIX
FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT·AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
SINGLE POLE
1PH SINGLE PHASE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE PHASE
4/C FOUR-CONDUCTOR
4W FOUR WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT / ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT OR ADJOINING
ADO AUTOMATIC DOOR OPENER
AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE·HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA OR CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED / CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED / OWNER
INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT
BRKR
CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR
PNL
DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
NORMALLY CLOSED
1P
AF
C
ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,
CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP
CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE
WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
B. DISCONNECT AND REMOVE ALL WIRES AND CONDUIT BACK TO THE OVERCURRENT
DEVICE AND RELABEL AS A SPARE. REUSE EXISTING CONDUIT IN COMPLIANCE WITH
NEC. DO THESE UNLESS OTHERWISE NOTED.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
D. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN
JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE.
E. REPLACE ALL EXISTING HANDLE TIE MULTI-PHASE BREAKERS IN AREA OF WORK WITH
MULTI-PHASE BREAKER TO MAKE EXISTING MANUFACTURER.
KEY NOTE.
NEW LINE TYPE
EXISTING LINE TYPE
DEMO LINE TYPE
ELECTRICAL GENERAL NOTES:
ELECTRICAL GENERAL NOTES - DEMOLITION:
KEYNOTES:
NEW - EXISTING & DEMO LINE TYPES:
A. FOR WHEEL CHAIR PATIENT USE, MOUNT TELEPHONE OUTLET 35" AFF TO BOTTOM
OF OUTLET BOX.
B. DESK PHONES - MOUNT OUTLET 1'-6" AFF
C. PAY PHONES - MOUNT OUTLET 4'-0" AFF
D. HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED ON BED WALLS OR PBPU
DETAILS.
E. SEE VA. BARRIER FREE DESIGN GUIDE PG-18-13
COMMUNICATION GENERAL NOTES:
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE
OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN, AS REQUIRED.
B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
D. ALL WIRING SHALL BE (3)#12 THWN/THHN COPPER 3/4C" UNLESS OTHERWISE NOTED.
E. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS SHALL BE 3/4".
F. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS. SEAL
REMAINING ANNULUS WITH FIRE CAULK.
G. FURNISH ACCESS DOORS FOR INSTALLATION BY GENERAL CONTRACTOR IN WALLS
AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED ELECTRICAL BOXES AND
DEVICES.
H. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN FIXTURE PIGTAILS. ARMORED CABLE
(AC) SHALL NOT BE USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED CABLE (AC)
SHALL NOT BE USED WHERE MORE THAN THREE CONDUCTORS
(PHASE/NEUTRAL/GROUND) ARE REQUIRED, WHERE EXPOSED; OR IN LENGTHS
EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.
I. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE 2020 NATIONAL
ELECTRICAL CODE AND THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING
JURISDICTION.
J. COORDINATE ALL OUTAGES WITH VHA COR PER SPECIFICATION PRIOR TO WORK BEING
DONE.
K. CONTRACTOR SHALL SET INDOOR TEMPORARY ATS AND SWITCHBOARD IN
SWITCHGEAR 3 ROOM AND OUTDOOR GENERATOR WITH JERSEY BARRIERORS IN VA
DESIGNATED AREAS ONLY. THE SWITCHBOARD WILL PROVIDE CONSTRUCTION POWER
AND TEMPORARY POWER TO THE REMOVED ATS'S LOADS WHILE REGULAR NORMAL
AND EMERGENCY POWER SOURCES ARE DISCONNECTED. THE NORMAL POWER TO THE
TEMPORARY ATS IS TAPPED FROM SECONDARY SIDE OF SUBSTATION J AND THE
EMERGENCY POWER IS FROM THE OUTDOOR GENERATOR. THE TEMPORARY SYSTEM
SHALL BE CONNECTED SO THE GENERATOR STARTS AND THE ATS TRANSFERS TO
GENERATOR POWER AUTOMATICALLY WHEN POWER IS LOST AT SUBSTATION J.
TRANSFER BACK TO NORMAL SHALL BE MANUAL SELECTION AT THE ATS. CONTRACTOR
IS RESPONSIBLE FOR MAINTAINING THE TEMPORARY POWER SYSTEM WHICH INCLUDES
FUELING OF GENERATOR.
L. CONTRACTOR SHALL SUBMIT CABLE ROUTING PLANS FOR APPROVAL BEFORE
OUTAGES.
M. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, EXISTING CONDUIT, AND
CONDUCTOR PRIOR TO PLACING ORDERS. ANY DEVIATIONS OF EXISTING CONDITIONS
FROM DESIGNED DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE VHA COR.
DEMO HATCH
1. CONTRACTOR TO VERIFY THE SWITCHED POLE NUMBER OF EACH ATS WHETHER 3 OR 4
POLES PRIOR TO PLACING ORDER. VERIFY THE LIST BELOW:
2. CONTRACTOR TO PURCHASE 4 POLE ATS FOR ALL LOCATIONS AND INSTALL AS 3 POLE
AT LOCATIONS WITH 3 POLE ATS.
3. CONTRACTOR SHALL TEST EXISTING ATS SWITCHING FROM NORMAL TO GENERATOR
AND BACK TO NORMAL PRIOR TO REMOVAL. AFTER ATS REMOVAL, TEST
ATS-GENERATOR CONTROL WIRES TO SIMULATE TRANSFER TO GENERATOR AND BACK
TO NORMAL POWER. AFTER CONNECTING NEW ATS, TEST ATS SWITCHING FROM
NORMAL TO GENERATOR AND BACK TO NORMAL.
IMPORTANT NOTES FOR CONTRACTOR:
ATS POLE CHART
ATS-# 3 POLE 4 POLE
ATS-1
ATS-2
ATS-3
ATS-4
ATS-5
ATS-6
ATS-7
ATS-8
ATS-9
ATS-10
X X X
X X
X X X
X X
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
KEY PLAN
04/26/2023
KEY PLAN
E
A
B
F
C
D
NO SCALE
Plan North
VEG 21.19
1. PROVIDE TEMPORARY CONNECTION TO EXISTING PANELS DPLS
(ATS-1) AND DPCR (ATS-2).
2. DISCONNECT AND REMOVE ATS LEAVING EXISTING CONDUCTORS AND
FEEDERS IN PLACE FOR RECONNECTION IN NEW CONSTRUCTION.
3. CONNECT TEMPORARY POWER TO EXISTING LOAD CABLES, SEE
SHEET EP111.
4. PROVIDE CEILING JUNCTION BOX AT SUBSTATION-3 TO REUSE ATS-5
NORMAL POWER CONNECTION.
5. PROVIDE JUNCTION BOX ABOVE ATS FOR RECONNECTION TO NEW ATS
IN NEW LOCATION. SEE SHEET EP111.
6. EXTEND EXISTING WIRE AND CONDUITS FROM ATS-5 LOCATION TO
NEW LOCATION SHOWN ON EP111. UTILIZE TRAPEZE WHEN POSSIBLE.
7. DISCONNECT FEEDERS FROM CIRCUIT BREAKER FEEDING ATS-5 IN
SUB-3 AND REMOVE WIRE AND CONDUIT FROM SUB-3 TO EXISTING
ATS-5 LOCATION.
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
PARTIAL DEMO BASEMENT FLOOR - EXISTING
Plan North
TM WHB
ED111
BASEMENT PARTIAL DEMO FLOOR
PLANS
MAIN TIE MAIN
SW
IT
CH
T
-J
MAIN
SWITCHGEAR 3A - SERVES
ATS-10 - 400A.
X-RAY - 400A.
6th FL. MECH. RM. - 600A.
MAIN
SWITCHGEAR
XFMR KXFMR JINACTIVE SWITCH
BOX OLD TEMP.
DPCRDPLS
BOX C/B HB2LS
BOX C/B LB2CR
MCC-4
J-BOX
XFMR SR-1
SWITCH L
SW
IT
CH
T
-K
XFMR HMECH
STR #6
ATS-11 ATS-12
PNL HB1
BF112
PNL 4A
ATS-1 250A
ATS-2 600A ATS-3 650A
ATS-9 225A
ATS-8 650A
ATS-7 400A
ATS-6 175A
ATS -10 400A
BOX C/B SR
J
J
J
J
J
J
J
ATS-5 225A
2 3
JJJJ
VAC
MAIN 1
AMP
ATS-8
H #31
H #11
ATS-9
ATS-1
AMP VAC
MAIN #2
H #43
ATS-2
H #73
TIE
H #32 ATS-5
ATS-4
ATS-3 AMP VAC
VACAMP
J-BOX
MAIN
SWITCHGEAR
A V
ATS -10
X-RAY
ATS-7
KW
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
TM WHB
EP111
SWITCHGEAR ROOM #3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
KEY PLAN
04/26/2023
KEY PLAN
E
A
B
F
C
D
NO SCALE
Plan North
VEG 21.19
1. PROVIDE TRANSFER SWITCHES PER SPECIFICATION SECTION 26 36 23.
CONNECT TO EXISTING CABLES AT JUNCTION BOXES PROVIDED DURING
DEMOLITION.
2. RE-USE EXISTING BREAKERS.
3. PROVIDE 3 - #4/0, #4/0 N, #4 GND WIRING. MATCH EXISTING CONDUIT. MATCH
EXISTING CONTROL AND ALARM WIRING.
4. PROVIDE 3 - #350, #350 N, #4 GND WIRING. MATCH EXISTING CONDUIT. MATCH
EXISTING CONTROL AND ALARM WIRING.
5. PROVIDE TWO SETS OF 3 - #3 / 0, 1 - #3 / 0 N, #3 GND WIRING. MATCH EXISTING
CONDUIT. MATCH EXISTING CONTROLS AND ALARM WIRING.
6. PROVIDE TWO SETS OF 3 - #350, 1 - #350 N, #1 GND WIRING. MATCH EXISTING
CONDUIT. MATCH EXISTING CONTROLS AND ALARM WIRING.
7. PROVIDE TWO SETS OF 3 - #400, #1 / 0 GND WIRING. MATCH EXISTING
CONDUIT. MATCH EXISTING CONTROLS AND ALARM WIRING.
8. EXTEND AND RECONNECT EXISTING CABLE THROUGH BOX FOR CONNECTION
TO ATS. (DETAIL 3 THIS DRAWING)
9. SWITCHGEAR 3A-SERVES
ATS-10-600A
X-RAY-400A
6TH FL MECH RM-600A
10. USE EXISTING UNISTRUT AND CONDUIT TRAPEZE'S WHEN POSSIBLE.
PROVIDE (WIRE AND CONDUIT SIZE) AND RECONNECT TO EXISTING BREAKER
FEEDING ATS-5.
11. APPROXIMATE LOCATION OF TEMPORARY ATS AND SWITCHBOARD.
12. ROUTE TEMPORARY CABLES VIA WALL PENETRATIONS HIGH ENOUGH TO
PREVENT FLOODING. REFER TO DRAWING ES101.
13. TAP THE 480V SIDE OF TRANSFORMER J TO POWER THE TEMPORARY ATS,
SIMILAR TO WHAT WAS DONE WITH SWITCHBOARD 3A ON THE K
TRANSFORMER SIDE.
14. THE PULL/TERMINATION BOXES ARE FOR CONTRACTOR USE TO CONNECT
THE EMERGENCY, NORMAL, AND LOAD NEW AND EXISTING CABLES.
CONTRACTOR TO SIZE THE BOXES AND BUS BARS AS NEEDED FOR THE
DIFFERENT ATS. BOXES OF ATS WITHOUT NEUTRALS DON'T REQUIRE THE
NEUTRAL BARS.
15. PROVIDE 3-#4/0, #4 GND WIRING. MATCH EXISTING CONDUIT.
16. PROVIDE TWO SETS OF 3-#3/0, #3 GRD WIRING. MATCH EXISTING CONDUIT.
MATCH EXISTING CONTROLS AND ALARM WIRING.
SPACESPACE
SPACE
SPACE
SPACE SPACE SPACE
SPACE
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
PARTIAL BASEMENT FLOOR - NEW
NTS
ENLARGED SWITCHGEAR
NTS
ENLARGED SWITCHGEAR ROOM BF112 ELEVATION - A
A
NTS
ENLARGED SWBD 3A ROOM BF112 ELEVATION - B
B
NTS
PULLBOX/TERMINATION BOXES
KEYNOTES 00
EP111
MAIN TIE MAIN
SW
IT
CH
T
-J
MAIN SWITCHGEAR
MAIN
XFMR KXFMR J
INACTIVE SWITCH
BOX OLD TEMP.
DPCR
ATS-1
DPLS
PNL 4A
BOX C/B HB2LS
BOX C/B LB2CR
MCC #4
J-BOX BOX C/B SR
XFMR SR-1
SWITCH L
SW
IT
CH
T
-K
XFMR HMECH BF112
STR #6
250A
ATS-11 ATS-12
PNL HB1
ATS-5
225A
ATS-3
650A
W
IR
EW
AY
ATS-2
600A
WIREWAY
WIREWAY
WIREWAY
WIREWAY
1 1 1
4 6 6
BF112
BF113
J
J
J
J
J
J
ATS-9
225A
ATS-8
800A
ATS-7
400A
ATS-6
200A
ATS-10
400A
J
J
J
J
A
B
W
IR
EW
AY
INSULATOR
BUSBAR
ENCLOSURE
A
B
C
N
GND
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
KEY PLAN
04/26/2023
KEY PLAN
E
A
B
F
C
D
NO SCALE
Plan North
VEG 21.19
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
PARTIAL BASEMENT FLOOR - EXISTING
Plan North
1. PROVIDE ATS-4. RE-USE EXISTING CONDUITS AND J-BOXES WHEN
POSSIBLE. INSTALL NEW J-BOXES WHEN NECESSARY. SEE DETAIL 3 ON
SHEET EP111.
2. REMOVE EXISTING ATS-4. PROVIDE TEMPORARY POWER TO PANEL HBE
FOR CONTINUED OPERATION.
3. PROVIDE ATS PER SPECIFICATION 26 36 23. EXTEND EXISTING TWO SETS OF
3 - #350, #1 GND WIRING. AND CONDUIT, FROM OLD LOCATION THROUGH
JUNCTION BOX TO NEW LOCATION SHOWN.
4. DISCONNECT AND REMOVE CONDUIT AND JUNCTION BOXES.
5. MAINTAIN EXISTING UNISTRUT TO EXTEND CONDUIT AND FEEDERS FROM
PANEL HBE TO THE NEW LOCATION FOR ATS-4.
6. INTERCEPT EXISTING CONDUIT AND CONDUCTORS ON OTHER SIDE OF
WALL AND EXTEND TO NEW PULLBOX AND THEN TO NEW ATS-4 LOCATION
FOR TERMINATION.
7. INTERCEPT POWER FEEDS AND CONDUIT FROM EXISTING PANEL HBE IN
ROOM BF114 AND EXTEND TO NEW PULLBOX AND THEN TO NEW ATS-4
LOCATION FOR TERMINATION.
8. PROVIDE A 4" HOUSEKEEPING PAD.
9. INTERCEPT NORMAL AND EMERGENCY POWER FEEDS AND CONDUIT FROM
EXISTING ROOM BF114 AND EXTEND TO NEW PULLBOX AND THEN TO NEW
ATS-4 LOCATION FOR TERMINATION.
10. PROVIDE NEW 24"X24"X12" PULLBOX MOUNTED AT A MINIMUM 12" ABOVE
THE ATS.
11. PREPARE AND SUBMIT ALL OUTAGE PLAN PER SPECIFICATIONS AS MAY
DEEM NECESSARY FOR VA APPROVAL PRIOR TO EXECUTION OF THE WORK.
SCALE: 1/4" = 1'-0"
1' 2' 4' 8' 16'0
PARTIAL BASEMENT FLOOR - NEW
Plan North
TM WHB
EP112
BASEMENT PARTIAL FLOOR PLANS
ATS-4
NTS
BF114 ELEVATION
4 NTS
BF115 ELEVATION
EXISTING ATS-4
600A
P12
PNL HBE
FIRE ALARM
P12 CNTL PNL
P12 BKR
P12 DISCO
PRIMARY, SECONDARY,
FIRE HAT, SHUNT
BF115
BF114
STAIR #7
ELEV
P-12
BA123a
ELEV
P-11
P12
PNL HBE
FIRE ALARM
P12 CNTL PNL
P12 BKR
P12 DISCO
PRIMARY, SECONDARY,
FIRE HAT, SHUNT
BF115
BF114
STAIR #7
ELEV
P-12
BA123a
ELEV
P-11
NEW ATS-4
600A
J
TM WHB
ES101
BASEMENT - TEMPORARY POWER
1. SUBMIT PLAN FOR VHA APPROVAL BEFORE SETTING TEMPORARY
GENERATOR AND BARRIERS. PROTECT GENERATOR IN ACCORDANCE
WITH THE REQUIREMENTS OF 010000 GENERAL REQUIREMENTS.
2. SUBMIT PLAN FOR VHA APPROVAL BEFORE ROUTING CABLES. PROTECT
CABLES IN ACCORDANCE WITH THE REQUIREMENTS OF 01000 GENERAL
REQUIREMENTS.
3. PROPOSED ROUTING OF TEMPORARY CABLES.
4. PROPOSED LOCATION OF TEMPORARY GENERATOR.
5. CABLES BETWEEN GENERATOR AND TEMPORARY ATS.
6. CABLES BETWEEN TEMPORARY SWITCHBOARD.
7. APPROXIMATE LOCATION OF ATS AND SWITCHBOARD. SUBMIT PLAN FOR
VA APPROVAL BEFORE SETTING THE EQUIPMENT. SEE DRAWING EP111
FOR ADDITIONAL INFORMATION. WILL REMOVE SWITCHBOARD, ATS AND
CABLES AT THE END OF PROJECT.
8. ROUTE CABLES TO OUTSIDE VIA WALL BORING HIGH ENOUGH TO
PREVENT FLOODING. REPAIR HOLES AFTER PROJECT. SUBMIT PLAN FOR
VHA APPROVAL BEFORE BORING HOLES.
9. PREPARE AND SUBMIT ALL OUTAGE PLAN PER SPECIFICATIONS AS MAY
DEEM NECESSARY FOR VA APPROVAL PRIOR TO EXECUTION OF THE
WORK.
1" = 10'
PARTIAL BASEMENT FLOOR PLAN1
Pl an
N or th Tr ue N or th
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
KEY PLAN
GENERAL NOTES
04/26/2023
KEY PLAN
E
A
B
F
C
D
NO SCALE
Plan North
VEG 21.19
TEMPORARY JERSEY BARRIERS
PROPOSED TEMPORARY GENERATOR LOCATION
BF
BF104
BF105
BF106
BF117
BF100 BF101
BF
BF112
STAIR #6
BF113
BF115
BF114
STAIR #7
BF110
BF108
BF
BF109
ELEV
P-12
BF109a
BF104b
BF104a
BA
9c
BA119g
BA120
BA121
BA
BA
BA123a
BA123b
BE100a
BA123a1
ELEV
P-11
BF126
BF127
BF128a
BF125b
BF125
BF128
BF124
BF153
BF154
BF152
BF129
BF130
BF131
BF132
BF133
BF134
BF135
BF136 BF137
BF138
BF139 BF140
BF141
BF142
BF143
BF144
BF
BF146
BF147
BF148
BF149
BF150 BF151
BF155
BF129a
BF127a
1 4
TEMP GENERATOR
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
04/26/2023VEG 21.19 TM WHB
EP501
DETAILS
NO SCALE
CONDUIT TRAPEZE MOUNTING DETAIL2
NO SCALE
CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT1
NO SCALE
CONDUIT EXPANSION JOINT CROSSING DETAIL - EXPANSION FITTING3
NO SCALE
COMMON ELECTRICAL EQUIPMENT HOUSE KEEPING PAD DETAIL5
NO SCALE
TYPICAL RACEWAY SUPPORT METHODS DETAIL4
(3/8") MIN GALVANIZED
THREADED ROD, TYP.
LOCKING SQUARE
WASHER & LOCKNUT
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
WASHER & LOCKNUT
REFER TO PLANS
FOR QUANTITY &
SIZE OF CONDUITS
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
PROVIDE (5") OF SLACK AT MIDPOINT
BETWEEN TWO END OF FLEXIBLE
GALVANIZED STEEL CONDUIT.
PROVIDE GREEN INSULATED COPPER
EQUIPMENT GROUNDING CONDUCTOR
WITH FLEXIBLE CONDUIT.
FLOOR OR ROOF STRUCTURE. FIELD
VERIFY ACTUAL CONDITIONS, TYP.
SEISMIC OR EXPANSION JOINT.
FIELD VERIFY ACTUAL
CONDITIONS & LOCATIONS.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
STEEL
EXPANSION
ANCHORCONDUIT
TRAPEZE
CONDUIT,
TYP.
(3' - 0") MAX
SPRING NUT
BEAM
CLAMP, TYP.
GENERAL NOTE:
DETAIL IS APPLICABLE
ONLY FOR CONDUIT
SMALLER THAN (3").
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND PERIMETER.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
EXPANSION FITTING
WITH BONDING JUMPER
FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
SEISMIC OR EXPANSION JOINT.
FIELD VERIFY ACTUAL
CONDITIONS & LOCATIONS.
STRUCTURAL MEMBER
(BEAM, JOIST, SECT.),
TYP.
STEEL
EXPANSION
ANCHORCONDUIT
TRAPEZE
CONDUIT,
TYP.
SPRING NUT
BEAM
CLAMP, TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
1.
2.
GENERAL NOTES:
INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL 1 ON THIS SHEET.
INSTALLATION IS REQUIRED FOR CONDUIT 3" OR LARGER.
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND PERIMETER.
(3'-0") MAX
HEAD
INSULATING
BUSHING
STRUCTURAL UNIT
NOTE: TIE WIRE SHALL NOT BE USED
AS A COMPONENT OF ANY RACEWAY
HANGER SYSTEM.
BEAM, CLAMP OR HANGER CLAMP AS
REQUIRED BY WEIGHT SUPPORTED
STRUCTURAL UNIT
BEAM, CLAMP OR HANGER CLAMP AS
REQUIRED BY WEIGHT SUPPORTED
RACEWAY
0.5" THROUGH 1"
ALL THREAD - SIZE AS REQUIRED
RACEWAY, .5" THROUGH 6"
CONDUIT HANGER
RACEWAY, .5" THROUGH 6"
4"
HOUSE KEEPING PAD
46"
40"
APPROXIMATE. 1,400 LBS
REFER TO STRUCTURAL
DRAWINGS FOR ADDITIONAL
INFORMATION
EP601
PRIMARY ONE LINE DIAGRAM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
04/26/2023VEG 21.19
1. WORK WILL BE OCCURRING IN SWITCHGEAR 3 ROOM BF112, ELEVATOR
ROOM BF114 AND GENERATOR ROOM BF115.
G
VS VM
"EMG"
35/1
AS50 A
5175/5
GS50/5
GS
50/5
51150/5 AS A
3 50
GS50/5
75/5
50 AS A AS
50/5
75/5
1 50
GS
50 A
SPARE"XFG"-EM"XFB"-EM "XFD"-EM
SO P.T.
A.T.S.
ATS
XFG
LIFE SAFETY
MCC # 1 & 2
G200/5
10 KVA
POWER
TRANSF
1Ø,120°/240V
4160V.,3Ø, 3W, 1200A, BUS
GS50/5
"XFJ"
300/5A
AS50
A
"XFG"
50/5 1 50
GS
50 AS A
"XFE"
GS
"XFB"
GS
50 AS A
51 AS A
GS
51 AS
"XFD"
A
UNIT SUBSTATION
200A 200A
5KV
50 P.T.
GS
51 AS A
GS
50 AS AAS
GS
50 A AS
GS
50 A
RESEARCH BLDG. #19
NON-CRITICAL TIE CRITICAL
5KV
5KV
5KV
5KV
5KV
5KV
5KV
BREAKER RELAY SETTING CONDUCTOR SERVES
PRIMARY ELECTRICAL FEEDER SCHEDULE
DESIG. FRAME 50/51 50 OR 51GS
"XFF"
"XFA"
"XFH" 1 - 3 1/2"
1 - 3 1/2"
1 - 3"
2 - 4"
2 - 4"
1 - 2 1/2" XFMR "F" & "H"
XFMR "L"
5KV
2 1
5KV
5KV
125KV
NO NC
P.T.
SO
CP
1000KW
1200A. BUS, 3Ø, 3W,+ GND.
SWITCHGEAR ROOM 1
CP
NC
NO
5KV
5KV
"XFC" "XFA" "XFF" "XFK"
250 A
TIE
P.T.
N
150/5
N.O.
MAIN 1 MAIN 227
1X
2X
N AS51 WM A
S.C.
L.A.
-2
-2
800/5
35/1 P.T.
2 VS VM
5KV
800/5
L.A.
S.C.
-1
-1
35/1 P.T.
2 5KV
VSVM
51N
51WMA AS
UTILITY
TRANSFORMER 2
5000 KVA
12.5 - 4.16 KV12.5 - 4.15 KV
5000 KVA
TRANSFORMER 1
UTILITY
NONC NC
NO
WEST 12.5 KV PARK PLACE SUB. EAST 12.5 KV STONEWALL SUB.
OG&E
EQUIPMENT
PARK PLACE
CHILLER #1
ELEVATORS
BLDG 1
GS
50 AS A
SO
NO
PT
SO
250A
ATS
XFB
A.T.S.
P.T.
NC
P.T.
250A250A
SWITCHGEAR ROOM 2
SWITCHGEAR ROOM 3
150 AMP
EQUIPMENT BRANCH TIE
NCP.T. SO
PT
SO
NO
460 KW GENERATOR
BUILDING 21 & BOILER PLANT
80 AMP
80 AMP
5 KV SWITCH
PULL SECTION
3 EA. (4#350 MCM & 1#2 G.)
SW
V
VS
A 100A/3P
125A/3P
CENTRIFUGAL CHILLER
1000A/3P
MCC #1
600A/3P
EMCC #1
400A/3P
SPACE
150A
100 AMP
50 AMP
TIEJ K
BLDG. #19
ARF BLDG.
BF-118
ER - NORMAL
CHILLER 1 CHILLER 2
480V
CHILLER MDP
CHILLER PLANT MDP
RAD/ONC
TELE SWITCH: 10th FL
6-500 MCM, 5 KV 2-1/0, GND.
CCLP-INSUL. INSUL.
LEVEL-100%
6-500 MCM, 5 KV 2-1/0, GND.
CCLP-INSUL. INSUL.
LEVEL-100%
3-NO. 2 1 #2 GND.
CCLP-INSUL.
3-2/0, 5KV 1-NO. 2 GND.
CCLP-INSUL.
3-350 MCM 1-NO. 2 GND.
CCLP-INSUL.
3-350 MCM 1-NO. 2 GND.
CCLP-INSUL.
XFMR "L"
4160-480/277V
750 KVA
500 TON
4160V. 3Ø
CENTRIFUGAL
CHILLER WITH
5KV STARTER
PER MECH
TRANSFORMER
"F" 1000 KVA
4160-480/277V.
TRANSFORMER
"H2" 500 KVA
4160-480/277V.
TRANSFORMER
"H1" 4160-480
/277V 300 KVA
TRANSFORMER "B"
1000 KVA
4160-208/120V
TRANSFORMER
"A" 1000 KVA
4160-208/120V
TRNFMR "H"
4160-480 /277V 300
KVA
TRANSFORMER "C"
300 KVA
4160-208/120V
TRANSFORMER "D"
300 KVA
4160-208/120V
5KV, 600 AMP, 3PDT
3 POSITION SWITCH,
SWITCH "L"
OFF POSITION
NORMAL SETTING
ON 1 ALTERNATE
SETTING ON 2
NORMAL SETTING ON 1
ALTERNATE SETTING ON 2
TRANSFORMER "K"
300 KVA
4160-480/277V
TRANSFORMER "J"
1000 KVA
4160-480/277V
5KV, 600AMP,
3PST
5 KV-DT-3 POSTION,
600 AMP SWITCH
5KV, 600AMP,
3PST
3#4,1#8G,2 1/2"C.
5KV. EPR.
TRANSFORMER "E"
1000 KVA
4160-480V.
500 KVA
4160-480V
TRANSFORMER "G"
225 KVA
4160-208/120V
TRANSFORMER "H3"
500 KVA
4160-480/277V
5 KV CIRCUIT
3#2/0,1#4G, 5KV EPR.
IN EX. CONDUIT
G.F.
SENSOR
ENCLOSED BKR.
1600 AMP 480/277V.
3Ø, 4W SWBD. 1600 AMP
480/277V. 3Ø, 4W
SCR CONT. NO. 1 (DOM. WTR.
BOOSTER PUMPS)
SCR CONT. NO. 2 (SEC.
CHILLED WATER PUMPS)
75/5
150/5
300/5
50/5
50/5
4160V. 3Ø 3W +GND, 1200A. BUS
3Ø ISC = 7403 AMP
300/5
50/5
MAIN SERVICE
NO. 1
MAIN SERVICE
NO. 2
XFMR "K"
ALTERNATE "L"
XFMR "J"
ALTERNATE "K"12
A
MP
F
RA
ME
-3 0,0
A
MP
IN
TE
RR
UP
TI
NG
C
AP
AC
IT
Y
MAIN
NO. 1
MAIN
NO. 2
"XFJ"
NEW
CABLE
DESIG.
CONDUIT
SIZE
P.T.
A.T.S.
4160V. 3Ø 3W +GND,
1200A. BUS 3Ø ISC = 6053 AMP
TO SYNC.
CCT. OF
GEN
75/5
50/5
50/5
300/5
150/5
50/5
300/5
50/5
50/5
100/5
STONEWALL
KITCHEN 480 V.
MICROWAVE 480 V.
7B X-RAY
TELE. OFFICE
LAUNDRY
FIRE PUMP, 4
GROUP AIR
COMPRESSORS
SUB-BSMT
250A
TMueck Note
K
K
K
HG1 H11 MCC-2 HG2 H12 H32 H43H13 H73 MCC-3 ATS-3 ATS-5 MCC-4
MAIN
BKR.
(29616)
FEEDER 13
5KV FEEDER
5KV
(28316)
(26661)
AS
AM
WM
VS
VM
GF
GF
GF
GF
LIF
E
SA
FE
TY
R
IS
ER
ME
CH
. P
EN
TH
OU
SE
R
IS
ER
6th
FL
R.
M
EC
HA
NI
CA
L R
IS
ER
X-
RA
Y
RI
SE
R
CR
IT
IC
AL
P
OW
ER
R
IS
ER
(19464)(25762) (14069)(19810)(20102)
NO
RM
AL
P
OW
ER
R
IS
ER
CRITICAL RISER
X-RAY RISER
6th FLR. MECH. RISER
MECH. PENTHOUSE RISER
LIFE SAFETY RISER
(16059)
(2915)
(2915) (2915)
(2915) (2915)
(3480)
P-11
P-10
P-9
3#1,1#6G.,1 1/2"C. (TYP.)
P-8
P-7
P-12
500 KW GENERATOR
ATS-3 ATS-5
UNIT SUBSTATION #3 - RM. BF-112
LOCATED IN BF-114 ON DRAWING EP112
TM WHB
EP602
ATS POWER RISER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
04/26/2023VEG 21.19
1. REPLACE AUTOMATIC TRANSFER SWITCH.
2. DISCONNECT CABLE AND TEST. GIVE VALUES TO ENGINEERS FOR
EVALUATION. IF CABLE IS IN ADEQUATE CONDITION, MOUNT WALL OR
CEILING BOX, CUT AND COIL THE END IN BOX FOR RE-USE.
3. SEE SHEET EP111 AND ES101 FOR MORE INFORMATION.
1 1 1 1 1
1 1 1 1
480V, 3Ø, 200 AMP
FUSED @ 125 AMPS
(TYPICAL OF 4)
EX. PNL. HBE
480V, 3Ø, 600 AMP
480V, 3Ø
125 AMP
EX. HYDRAULIC
ELEVATOR
CONTROLLER
ATS-9
LIFE SAFETY
BRANCH
400AMP
ATS-4
ELEVATOR
RISER
480V, 3Ø
600 AMP
EMERGENCY
EQUIP
ATS-1
LIFE
SAFETY
RISER
ATS-2
CRITICAL
RISER
500 KW
GENERATOR
ATS-EQUIP
EMCC #1
3 #1, 1 #6 GND.,
1 1/2" C. (TYP.)
TO ELEVATOR
CONTROLLERS 8F-100A
ATS-8
EQUIPMENT
SYS.
800AMP
ATS-7
EQUIPMENT
SYS.
600AMP
ATS-6
X-RAY
POWER
400AMP
SWBD 3A
1200AMP,
1000A M.B.
480/277V, 3Ø, 4W
4160 - 480/277V
TRANSFORMER "K"
1000/1150 KVA
ATS-8
PENT.
MECH.
BREAKER
ATS-9
LIFE
SAFETY
BREAKER
ATS-1
LIFE
SAFETY
RISER
H6
BKR.
H31
4160 - 480/277V
TRANSFORMER "J"
1000/1150 KVA
ATS-2
CRITICAL
RISER
ATS-4
ELEVATOR
RISER
MAIN
BKR.
ATS-10
CRITICAL BRANCH
600AMP
600 KW
GENERATOR
TIE N.O.
1600A 1600A
1200 400
2 2 2 2
2 2 2 2 2
2 2
ATS9
EMERGENCY
EQUIP
ATS10ATS6ATS7ATS8
FB100E
FB1001
FB1000
FA601 FB801 ATS3 ATS5
FA600 FB800 FB1100 FB900
FB600E FB800E FB900E FB1100E
FEEDER SCHEDULE
ATS-# CABLE CONFIGUREATION EXTENDED FOR EACH PHASE
2[1(#400) +1(#1/0 GND)]
#4/0, #4/0 N, #4 GND
#2/0, #3 GND
#4/0, #4/0 N, #4 GND
#350, #350 N, #4 GND
2[1(#3/0, #3/0 N, #3 GND)]
2[3(#3/0, #3 GND)]
2[#350, #350 N, #1 GND]
2[#350, #350 N, #1 GND]
12'
10'
10'
10'
60'
10'
10'
10'
10'
10'
2[#350, #1 GND]
G 1150KW TEMP GENERATOR
1200A
100A
TEMPORARY 1200A SWITCHBOARD
TEMP ATS 1200A - NORMAL,
OFF, GENERATOR3
BRANCH FOR TEMPORARY POWER ATS LOADS
BRANCH FOR CONTRACTOR POWER
NORMAL SOURCE
CABLE CONFIGUREATION
2[1(#400)+1(#1/0 GND)]
#4/0, #4/0 N, #4 GND
#2/0, #3 GND
#4/0, #4/0 N, #4 GND
#350, #350 N, #4 GND
2[1(#3/0, #3/0 N, #3 GND)]
2[3(#3/0, #3 GND)]
2[#350, #350 N, #1 GND]
2[#350, #350 N, #1 GND]
2[#350, #1 GND]
EMERGENCY SOURCE
CABLE CONFIGUREATION
2[1(#400)+1(#1/0 GND)]
#4/0, #4/0 N, #4 GND
#2/0, #3 GND
#4/0, #4/0 N, #4 GND
#350, #350 N, #4 GND
2[1(#3/0, #3/0 N, #3 GND)]
2[3(#3/0, #3 GND)]
2[#350, #350 N, #1 GND]
2[#350, #350 N, #1 GND]
2[#350, #1 GND]
LOAD APPROX. LENGTH
UNIT SUBSTATION BF112
LOCATED IN SWGR. RM. 3
T-B2
GROUND
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
7TH FLOOR
8TH FLOOR
T-G2
T-12
T-32
PANEL
LG3
PANEL
L23
T-13
T-43
T-73
T-G1
T-11
T-31
2 1/2"
1 1/4", 4-#2, 1-#8 GND.
J 18" x 12" x 6"
100 AMP
4-#2 1-#8 GND.
FB622
FB610FB620
FB621
FB522
FB521
FB510FB520
SCA
FB421
FB420
FB410
FB500
ATS-4
FB1001
FB1007
ATS-5
FB1100E
FB900E
FB800E
ATS-3
FB600E
ATS-2
FB801
ATS-1
FA601
FB800
FA600
FB1100
FB900
T-K
FB1002
T-43
FB830
CR
FB812
T-J
FB1200
FB121 FB111
FA606
FB822
FB100
FB120 FB110
FB201
FB310
FB320
FB301
FB810FB820
FA603
FA100
FA121 FA120
FA110
FA200
FB901
FB1110 ATS 5
FA210
FA220
FA221
FB821
FA604
FA602
FB902
T-22
CR
FB811FB823
FA201
FA301
FA320 FA310
FA321
FB825
FB824
T-4EDP
FB1120
FB
CB-225A
FB1140
FA605FA500
BASEMENT FLOOR
TGRLS
45KVA
(1543)
(1630)
LGRLS
(2760)
DX2
BLDG 20
T45CR
FB1000E
FB1000
FLOORFLOOR
1ST FL
GROUND
2ND FL
3RD FL
4TH FL
5TH FL
6TH FL
7TH FL
ATS 8
ATS 6
ATS 10
ATS 7
ATS 9
ATS 3
HG1
H11
HG 2
H6
T3CR T3LS
8TH FL
1F-136
30KVA 15KVA
T-B2
PANEL
HB2LS
17000
SCA
PANEL
LB2CR
3321 SCA
PANEL
LB2A
PANEL
LB2
SCA
PANEL
HB2
13000
SCA
MCC-4
17215
SCA
J
BF135
T-B2
PANEL
HG2LS
15000
SCA
PANEL
LG2CR
SCA
PANEL
HG2CR
SCA
PANEL
LG21CR
PANEL
L12CR
SCA
PANEL
L12CRA
PANEL
H2X
19126
SCA
H2X1
X-RAY
SCA
PANEL
H22LS
14362
SCA
PANEL
L22CR
SCA
PANEL
H22CR
105863
SCA
PANEL
HPT1
PANEL
HPT1A
PANEL
HPT2
PANEL
LPT1
IPU-X DX1
PANEL
H71CR
PANEL
XRAY
PANEL
H6CR
PANEL
H72CR
PANEL
H62CR
PANEL
L51CR
PANEL
L72CR
PANEL
H6M2
PANEL
5NS2
PANEL
5NS1
PANEL
L5LS
PANEL
H5LS
PANEL
H6LS
PANEL
L52CR
PANEL
H52CR
PANEL
H4EDP
14000
SCA
PANEL
EDPE
22000
SCA
PANEL
H42LS
14000
SCA
PANEL
L42CRA
PANEL
L42CRB
3424 SCA
PANEL
L44CR
SCA
PANEL
H6M1
PANEL
L6M1
PANEL
L6E
PANEL
X-RAY
CYSTO
PANEL
H7LS
PANEL
L7LS
PANEL
7NS
PANEL
PANEL
LPLS
PANEL
L45CR
PANEL
H43CR
14292
SCA
PANEL
L43CR
SCA
PANEL
H33LS
11618
SCA
PANEL
DPLS
17248
SCA
PANEL
DPCR
18227
SCA
PANEL
HBE
15143
SCA
TM WHB
EP603
RISER DIAGRAM SWITCHGEAR
ROOM #3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
04/26/2023VEG 21.19
1. REPLACE AUTOMATIC TRANSFER SWITCH. REFER TO ATS POWER
RISER SHEET.
2. CONNECT TEMPORARY POWER AT EXISTING CABLES IN ELECTRIC
ROOM 3 AND ELEVATOR ROOM TO KEEP PANEL POWERED DURING
CONSTRUCTION. SCHEDULE CONNECT AND DISCONNECT OUTAGES
WITH VA.
3. SEE SHEET EP111 AND ES101 FOR MORE INFORMATION.
1 1 1 1 1
1 1 1 1 1
FEED FROM MAIN LUG OUT OF H41. TERMINATES INTO A 125 AMP BRKR. IN
PANEL H41B.
100 AMP FEED FROM L41A
CIRC. 38-40-42
FEED FROM
L21B 100
AMP. CIRC.
37-39-41
PANEL
L41C
208Y/120V 3Ø 4W
100A M.B.
42 CKT
PANEL
H41A
480Y/277V 3Ø 4W
100A M.B.
42 CKT
PANEL
H31
14925
SCA
PANEL
L31
SCA
PANEL
L21C
208Y/120V 3Ø 4W 100
AMP MAIN
LUG 42
CKT
PANEL
L21B
SCA
PANEL
L11B
SCA
PANEL
L11A
SCA
PANEL
H11 15530
SCA
PANEL
L11AA
PANEL
LG1D
208Y/120V 3Ø 4W 100A M.B.
42 CKT
PANEL
H21
15146
SCA
PANEL
L21A
MCC-3
SCA
ELEC
AREA
PANEL
H73
SCA
PANEL
L73
SCA
PANEL
L83
ELEVATORS
P-7, 8, 9, 10 ELEVATOR
P-11
PANEL
L63
SCA
PANEL
L53
SCA
PANEL
L43
SCA
PANEL
H43
SCA
FB1003
FB1004
FB1005
FB1006
T5N1
45 KVA
PANEL
H6
PANEL
H62
T6N
30 KVA
PANEL
L62
PANEL
L71
T7N1
30 KVA
PANEL
H71
PANEL
H72
T7N2
75 KVA
PANEL
L72
PANEL
L73
T7LS
45 KVA
T-XRAY
45 KVA
T5LS
45 KVA
PANEL
L42D
208Y/120V 3Ø 4W
100A M.B.
42 CKT
PANEL
L42A
SCA
PANEL
L42C
SCA
PANEL
H42
13162
SCA
PANEL
H42B
480Y/277V 3Ø 4W 100A
M.B. 42
CKT
PANEL
L42B
FEED FROM H32
225 AMP. BRKR.
4-4/0, 1-#2 GND.
TO A 225 AMP
BRKR. IN H42B.
150 AMP
3-1/0 1-#2
GND.
4-3/0 1-#2
GND.
4-3/0 1-#2
GND.
TPT-1
15 KVA
TO
X-RAY
EQUIP.
T-7CR
75 KVA
T51CR
45 KVA
T6M 75
KVA
PANEL
A2 CR
PANEL
LB2B
PANEL
A1 CR
PANEL
LB2C
PANEL
LB3 LS
PANEL
HB3 LS
PANEL
LB3 CR
PANEL
HB3 CR
PANEL
HB2A
FB101
HG2
ATS-9ATS-7ATS-10
TO EMERGENCY GENERATOR
BLDG 20, 600 KW
PANEL
LG1A
SCA
PANEL
LG1B
PANEL
HG1
15848
SCA
FA300
H31
FB802
DPCR
FB803
DPCR
100 AMP FEED
FROM H12
4-#2 1-#8 GND.
4-3/01-#2
GND.
75 KVA
T12A
PANEL
L12C
PANEL
L12B
PANEL
LG2B
208Y/120V 3Ø 4W
100A M.B.
42 CKT
PANEL
LG2C
4-3/0 1-#2
GND
ATS-8 ATS-6
PANEL
LG1C
T-G2
CR
PANEL
L12A
SCA
PANEL
H12 13467
SCA
PANEL
LG2A
SCA
PANEL
HG2
13676
SCA
PANEL
H12A
FB200
H12
FB300
H32
PANEL
H32
13242
SCA
PANEL
L32
SCA
FEED FROM
TRANSFORMER
TO 225 AMP
MAIN
PANEL
L22
1CR
PANEL
L22A
SCA
PANEL
L22B
SCA
PANEL
H22
13162
SCA
PANEL
MCC2
12295
SCA
1 1/4" CONDUIT
4-#2 1-#8 GND.
1" CONDUIT
3-#6 1-#8 GND.
50 AMP. BRKR
FROM H13
FB804
DPCR
FB610
H43
FB700
MCC3
FB600
H73
FB400
H13
PANEL
H52
T52 45
KVA
PANEL
L52
PANEL
L53
PANEL
L51
T-22
1CR
100 AMP
4-#2 1-#8
GND.
75 KVA
T-21
T52CR
75 KVA
T42 112.5
KVA
ELEVATOR
P-12
BRKRS
B1-B12
BRKRS
A1-A10
PANEL
SWBD 3A
1200 AMP
1000 A. MB.
480/277V 3Ø, 4W
PANEL
H13
SCA
PANEL
L13
SCA
45 KVA
T-23
PANEL
L33
SCA
500 kw
GEN
PANEL
H41 14000
SCA
PANEL
H41B
PANEL
L41B
PANEL
L41A
SCA
MAIN
LUG
ATS 5
EGB
EP604
RISER DIAGRAM ATS REMOVAL
AND INSTALLATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
04/26/2023VEG 21.19
1. DISCONNECT LOAD CABLES, CONNECT TEMPORARY POWER TO
LOAD PANELS VIA EXISTING CABLES FOR RE-USE.
2. DISCONNECT - NORMAL CABLES.
3. DISCONNECT EMERGENCY POWER CABLES AND CONTROL WIRES.
4. REMOVE ATS.
5. MOUNT NEW ATS AT GENERAL LOCATION OF REMOVED ATS.
6. CONNECT EXISTING NORMAL CABLES AND NEW ATS CABLES AT BOX.
7. CONNECT EXISTING AND NEW ATS EMERGENCY CABLES AND WIRES
AT BOXES.
8. DISCONNECT LOAD CABLES FROM TEMPORARY POWER, CONNECT
EXISTING AND NEW ATS LOAD AT BOXES, RESTORE POWER TO THE
ATS AND PUT ATS BACK IN SERVICE.
9. SEE DETAIL 3 ON SHEET EP111 FOR BOX INFORMATION.
ATS
LOAD
PANEL
NORMAL
SOURCE
EMERGENCY
SOURCE
ATS
LOAD
PANEL
NORMAL
SOURCE
EMERGENCY
SOURCE
NO SCALE
REMOVAL DIAGRAM TYPICAL OF ATS-1, 2, 3, 6, 7, 8, 9,101 NO SCALE
INSTALLATION DIAGRAM TYPICAL OF ATS-1, 2, 3, 6, 7, 8, 9, 102
EP605
RISER DIAGRAM ATS-5 REMOVAL
AND INSTALLATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
04/26/2023VEG 21.19
1. DISCONNECT LOAD CABLES, CONNECT TEMPORARY POWER TO
4HDPE PANEL VIA EXISTING CABLES IN ROOM 3.
2. DISCONNECT - NORMAL CABLES, INSTALL JUNCTION BOX ON
CEILING NEAR SUBSTATION 3 WITH EXISTING CABLES FOR RE-USE.
3. DISCONNECT EMERGENCY POWER CABLES AND CONTROL WIRES.
4. REMOVE ATS-5.
5. MOUNT NEW ATS-5 AT LOCATION ON NORTH WALL SHOWN ON
DRAWING EP111.
6. CONNECT EXISTING NORMAL CABLES AND NEW ATS-5 CABLES AT
BOX.
7. CONNECT EXISTING AND NEW ATS-5 EMERGENCY CABLES AND
WIRES AT BOXES.
8. DISCONNECT LOAD CABLES FROM TEMPORARY POWER, CONNECT
EXISTING AND NEW ATS-5 LOAD AT BOXES, RESTORE POWER TO
THE ATS-5 AND PUT ATS-5 BACK IN SERVICE.
9. SEE DETAIL 3 ON SHEET EP111 FOR BOX INFORMATION.
ATS-5
LOAD
PANEL
4HEDP
NORMAL
SOURCE
EMERGENCY
SOURCE
ATS-5
LOAD
PANEL
4HEDP
NORMAL
SOURCE
EMERGENCY
SOURCE
NO SCALE
REMOVAL DIAGRAM TYPICAL OF ATS-51 NO SCALE
INSTALLATION DIAGRAM TYPICAL OF ATS-52
EP606
RISER DIAGRAM ATS-4 REMOVAL
AND INSTALLATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
635-21-121
OKLAHOMA CITY, OKLAHOMA 73104
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% BID DOCUMENTS REPLACE AUTOMATIC TRANSFER
SWITCHES
00KEYNOTES
04/26/2023VEG 21.19
1. DISCONNECT LOAD CABLES, CONNECT TEMPORARY POWER TO HBE
PANEL, INSTALL BOX FOR NEW CABLES BETWEEN ROOMS BF114
AND BF115.
2. DE-ENERGIZE NORMAL CABLES, PULL BACK INTO ROOM BF115 FOR
RE-USE.
3. DISCONNECT EMERGENCY POWER CABLES AND CONTROL WIRES,
INSTALL BOXES WITH EXISTING CABLE AND WIRING FOR RE-USE.
4. REMOVE ATS-4.
5. MOUNT NEW ATS-4 IN ROOM BF115.
6. RECONNECT EXISTING NORMAL CABLES TO NEW ATS-4, CONNECT
NEW CABLE IF ADDITIONAL CABLE IS REQUIRED.
7. CONNECT EXISTING AND NEW ATS-4 EMERGENCY CABLES AND
WIRES AT JUNCTION BOXES.
8. DISCONNECT PANEL HBE FROM TEMPORARY POWER, CONNECT
NEW ATS-4 CABLES TO HBE PANEL VIA BOXES, RESTORE POWER TO
THE ATS-4 AND PUT ATS-4 BACK IN SERVICE.
9. SEE DETAIL 3 ON SHEET EP111 FOR BOX INFORMATION.
ATS-4
LOAD
PANEL
HBE
NORMAL
SOURCE
EMERGENCY
SOURCE
ATS-4
LOAD
PANEL
HBE
NORMAL
SOURCE
EMERGENCY
SOURCE
NO SCALE
REMOVAL DIAGRAM TYPICAL OF ATS-41 NO SCALE
INSTALLATION DIAGRAM TYPICAL OF ATS-42