Davis Technical College HVAC Split Systems Upgrade - Approved Plans Summary
This document comprises approved mechanical construction plans prepared by WHW Engineering LLC for the Division of Facilities Construction and Management (DFCM) for Davis County Applied Technology College (Davis Technical College) located at 550 E 300 S, Kaysville, Utah 84037. The project, identified as DFCM #27050220, involves the removal and replacement of existing split direct expansion (DX) cooling systems in the Main Building and the Barlow Building. The scope of work includes demolition of existing split systems, condensate pumps, refrigerant piping, electrical connections, and thermostats; installation of new wall-mounted split DX units with integral condensate pumps; routing of new refrigerant piping through roof penetrations; provision of new condensate piping connected to existing drain systems; and installation of new BACnet-capable thermostats. The plans include mechanical floor and rooftop demolition plans (sheets MD101-MD104), mechanical installation plans (sheets ME101-ME104), mechanical details (sheets ME501-ME502), and mechanical schedules (sheet ME601). Code compliance is certified for the 2021 International Building Code, International Mechanical Code, and International Plumbing Code with Utah annotations. Plans were reviewed for code compliance and approved by Thomas Peterson on July 9, 2026, with design completion dated June 22, 2026.
The approved plans specify three DX systems: two 36,000 BTU/hour units (CU-1 and CU-2) serving the Main Building and Barlow Building with wall-mounted indoor units rated at 2,150 CFM, and one 36,000 BTU/hour unit (CU-3) serving the Print Room with a wall-mounted unit rated at 1,750 CFM. All equipment operates on 208/230V, single-phase, 60Hz electrical service with rooftop condensing units equipped with hail guards, 18-inch aluminum stands, and roof flashing details compliant with DFCM roofing standards. The contractor must coordinate with design-build electrical contractors for all electrical design and installation per 2020 National Electrical Code standards, coordinate with the roofing warranty holder (Perks Roofing) for all roofing work, and ensure field verification of existing conditions prior to fabrication or equipment ordering. All roofing work must be performed by the warranty holder, and state-appointed code inspectors shall provide final acceptance upon verification of compliance with drawings, specifications, and applicable codes, particularly for concrete construction, seismic requirements for water heaters, fire caulking at rated walls, and epoxy applications as required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G001
DAVIS TECHNICAL
COLLEGE HVAC
SPLIT SYSTEMS
UPGRADES
DFCM #27050220North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)______
1) One Story: ______
c) Total Allowable Area for:
1_< Allowable Area
Actual Area
b) Sum of the Ratio Calculations for Mixed Occupancies:
a) 0.25I = 100f F P 30
WstA I 100100 fIA t taA = A + +
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Hours Assembly ListingListing
Element AssemblyHours
Smoke Partitions Fire Partitions
Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers
Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
____________________________________________Tabular Area:I:
per Floor (square feet): __________________________Actual AreaH:
Number of Stories: ______ Building Height: ______G:
Required: ______ Provided: ______ Type of Sprinkler System: ____________
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guidelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: ________ ________ ________ ________ ________
CODE ANALYSIS
GENERAL:
G001 - TITLE SHEET
G002 - SPECIAL INSPECTIONS AND TESTING
MG001 - MECHANICAL LEGEND AND GENERAL NOTES
MECHANICAL:
MD101 - LAB AND OFFICE MECHANICAL DEMO PLAN
MD102 - ROOFTOP MECHANICAL DEMO PLAN
MD103 - BARLOW BUILDING MECHANICAL DEMOLITION PLAN
MD104 - ROOFTOP BARLOW BUILDING MECHANICAL DEMOLITION PLAN
ME101 - LAB AND OFFICE MECHANICAL PLAN
ME102 - ROOFTOP MECHANICAL PLAN
ME103 - BARLOW BUILDING MECHANICAL PLAN
ME104 - ROOFTOP BARLOW BUILDING MECHANICAL PLAN
ME501 - MECHANICAL DETAILS
ME502 - MECHANICAL DETAILS
ME601 - MECHANICAL SCHEDULES
DRAWING INDEX:
DAVIS COUNTY APPLIED
TECHNOLOGY COLLEGE
550 E 300 S, KAYSVILLE,
UT 84037
CODE REVIEW STAMP
DESIGN CRITERIA:
THESE DOCUMENTS - DRAWINGS AND SPECIFICATIONS COMPLY
WITH ALL THE REQUIREMENTS OF THE DFCM STANDARDS FOR
MECHANICAL UPGRADES OF EXISTING BUILDING.
CODE INSPECTION REQUIREMENTS:
1. BEFORE A FINAL ACCEPTANCE CAN BE ISSUED, THE STATE
APPOINTED CODE INSPECTOR SHALL PROVIDE A FINAL REPORT
RECOMMENDING THAT THE NEW PLUMBING WORK IS IN
COMPLIANCE WITH THE DRAWINGS, SPECIFICATIONS AND
APPLICABLE CODES ESPECIALLY FOR THE FOLLOWING ITEMS.
a.)CONCRETE CONSTRUCTION, MATERIALS, STEEL, MIX, AND FORMS.
b.)SEISMIC - WATER HEATER.
c.)EPOXY - IF REQUIRED.
d.)FIRE CAULKING AT RATED WALLS - IF REQUIRED.
2. SEE ALSO SHEET G002.
DEFERRED SUBMITTALS: NONE
SPECIAL INSPECTIONS:
1. SEE SHEET DRAWING G002.
PROJECT SCOPE:
THIS PROJECT WILL UPGRADE THE SPLIT SYSTEM IN THE LAB AND
PRINT ROOM. OLD DUCTWORK AND MECHANICAL UNITS SHALL BE
REMOVED. NEW SPLIT SYSTEM EQUIPMENT SHALL BE PROVIDED
AND CONNECTED TO NEW DUCTWORK. NEW CONDENSATE PIPING
SHALL BE PROVIDED AND CONNECTED TO EXISTING DRAIN AND
CONDENSATE PUMP. ALL ROOFING WORK MUST BE PERFORMED BY
THE WARRANTY HOLDER. CONTACT PERKS ROOFING FOR ALL
ROOFING WORK ON THE UPPER AND LOWER ROOF.
B x x
D N/A
EXISTING
NO NO
YES YES
2 30
170,826
1,708.26
WORK LOCATION
S
E
250 S
DATC DR
NA NA
NA
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
07/09/2026
SPECIAL INSPECTIONS
AND TESTING
G002
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MECHANICAL LEGEND
SYMBOL ABR. DESCRIPTION
GENERAL TERMINOLOGY
DETAIL NUMBER DESIGNATION
CORRESPONDING WITH GRID LOCATION
MECHANICAL EQUIPMENT DESIGNATION
EQUIPMENT ITEM DESIGNATION
REGISTER, GRILL OR DIFFUSER
DESIGNATION WITH BALANCING CFM LISTED
BELOW
GRILLE, OR LOUVER DESIGNATION WHERE
BALANCING NOT REQUIRE
REVISION DESIGNATOR AND NUMBER
KEY NOTE DESIGNATOR AND NUMBER
POC POINT OF CONNECTION
POR POINT OF REMOVAL
GC GENERAL CONTRACTOR
MC MECHANICAL CONTRACTOR
ATC CONTROL CONTRACTOR
EC ELECTRICAL CONTRACTOR
FPC FIRE PROTECTION CONTROL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
C COMMON
NC NORMALLY CLOSED
NO NORMALLY OPEN
A2
MA
D-1
CFM
R-1
SYMBOL ABR. DESCRIPTION
WET SIDE
PUMP
REGULATOR
UNION
BUTTERFLY VALVE
GATE VALVE
CBV CIRCUIT BALANCING VALVE
BV BALL VALVE
PRESSURE GAUGE AND GAUGE COCK -
WATER
PRESSURE GAUGE AND GAUGE COCK -
STEAM
THERMOMETER AND THERMOWELL
DIRECTION OF FLOW
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
EXISTING PIPING TO BE REMOVED
EXISTING PIPING TO REMAIN
NEW PIPING
PIPE CAP OR PLUG
FLEXIBLE CONNECTION
CW CULINARY COLD WATER
HW CULINARY HOT WATER
RECIRCULATED CULINARY HOT WATER
HEATING WATER SUPPLY
HEATING WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CN CONDENSATE LINE
R
HWS
HWR
CHWS
CHWR
SYMBOL ABR. DESCRIPTION
AIR SIDE
EXISTING AIR DUCT TO BE REMOVED
EXISTING AIR DUCT TO REMAIN
NEW AIR DUCT
NEW SPIRAL DUCT
NEW MEDIUM PRESSURE DUCT
BURIED OR UNDER FLOOR DUCT
FLEXIBLE AIR DUCT
LINED DUCT
VANED ELBOW
RADIUS ELBOW
FLEXIBLE AIR DUCT CONNECTION
VOLUME DAMPER
SUPPLY AIR DIFFUSER
RETURN AIR, FRESH AIR, AND TRANSFER AIR
CEILING MOUNTED EXHAUST FAN OR
EXHAUST GRILLE
RETURN OR OUTSIDE AIR DUCT UP
SUPPLY DUCT UP
EXHAUST AIR INTAKE UP
RETURN OR OUTSIDE AIR DUCT DOWN
SUPPLY DUCT DOWN
EXHAUST DUCT DOWN
ROUND DUCT UP
ROUND DUCT DOWN
AP ACCESS PANEL
EXISTING EQUIPMENT TO BE REMOVED
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
T-STAT WALL MOUNTED THERMOSTAT
MECHANICAL EQUIPMENT CONTROLLED
SA SUPPLY AIR
RA RETURN AIR
EA EXHAUST AIR
OA OUTSIDE AIR
MA MIXED AIR
FA FRESH AIR
RF RELIEF AIR
VDVD
T
RTU-1
T
RTU-1
GENERAL NOTES:
MECHANICAL INFORMATION IS NOT LIMITED TO THE MECHANICAL DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMATION OF THE EXISTING
BUILDING AND SITE CONDITIONS, EXISTING PIPING, EXISTING ELECTRICAL, AND
EXISTING SUPPORTS.
A - EACH DRAWING SHEET AND THE SPECIFICATIONS HAVE BEEN PREPARED TO
SUPPLEMENT EACH OTHER AND THEY SHALL BE INTERPRETED AS AN INTEGRAL
UNIT WITH ITEMS SHOWN AND NOTED ON ONE AND NOT THE OTHER BEING
FURNISHED AND INSTALLED AS THOUGH SHOWN AND CALLED OUT IN ALL PLACES.
ITEMS IN SPECIFICATIONS OR DRAWINGS LISTED WHICH ARE DIFFERING IN
EFFICIENCY OR QUALITY SHALL BE HELD TO THE GREATEST OF: EFFICIENCY,
QUALITY OR GOVERNING CODE.
B - THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE INSTALLATION OF THE
SYSTEMS ACCORDING TO THE TRUE INTENT AND MEANING OF THE CONTRACT
DOCUMENTS.
C - THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH PROPER SERVICE
ACCESS AND CLEARANCES ACCORDING TO MANUFACTURERS RECOMMENDATIONS.
THE CONTRACTOR SHALL REVIEW SUPPLIERS BID PACKAGES FOR COMPLETENESS
AND COMPLIANCE TO THE SPECIFICATIONS, SCHEDULES, AND DESIGN INTENT (ALL
EQUIPMENT AND METHODS). THE CONTRACTOR SHALL REMOVE AND REINSTALL
CORRECTLY AT HIS OWN EXPENSE ANY EQUIPMENT NOT IN COMPLIANCE.
D - THE CONTRACTOR SHALL CONSULT MANUFACTURERS INSTALLATION
INSTRUCTIONS FOR SIZES, METHODS, ACCESSORIES, AND CLEARANCES IN SPACE
AVAILABLE PRIOR TO BIDDING PROJECT.
E - ANYTHING NOT CLEAR OR IN CONFLICT WILL BE EXPLAINED BY MAKING
APPLICATION TO THE ENGINEER IN WRITING.
ANY AND ALL ALTERATIONS TO THE SYSTEM SHOWN SHALL BE SUBMITTED TO THE
ENGINEER PRIOR TO CHANGES FOR APPROVAL. CONTRACTOR SHALL NOT START
ANY CHANGES UNTIL NOTIFIED IN WRITING. IF CHANGES ARE MADE PRIOR TO
APPROVAL CONTRACTOR SHALL TAKE ALL RESPONSIBILITY FOR THE CHANGES
MADE AND ALL COSTS RELATING TO FAILURE OR REPLACEMENT OF ALTERATIONS.
CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LOCATIONS.
THE WORKING DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT SHOW EVERY
OFFSET, BEND, OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE
SPACE PROVIDED. ALL LOCATIONS FOR MECHANICAL EQUIPMENT SHALL BE FIELD
VERIFIED AND COORDINATED WITH ALL DRAWINGS. THE CONTRACTOR SHALL
PROVIDE OR COORDINATE WITH THE GENERAL CONTRACTOR PROVISIONS FOR
BLOCKOUTS OR CORE DRILLS THROUGH STRUCTURE.
THE INSTRUCTION TO "PROVIDE" ALSO INCLUDES INSTALLATION.
MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL SMOKE AND FIRE
DAMPERS AS REQUIRED BY LOCAL CODES AND AUTHORITIES.
SHEET METAL DUCT SIZES SHOWN ON DRAWINGS ARE FREE AREA DIMENSIONS.
PROVIDE AND INSTALL BALANCING DAMPERS IN ALL SUPPLY AND EXHAUST AIR
BRANCH DUCTS. BALANCE TO CFM SHOWN ON PLAN.
SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF
DIFFUSERS AND GRILLES.
PROVIDE TURNING VANES IN ALL ELBOWS OF RECTANGULAR DUCT.
THE CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY IN HANDLING AND
DISPOSING OF REFRIGERANTS, OILS, ETC. ALL SUCH MATERIALS SHALL BE
HANDLED, DISPOSED, AND USED IN ACCORDANCE WITH ALL LOCAL, STATE, AND
FEDERAL LAWS.
THE MECHANICAL CONTRACTOR SHALL VERIFY MOTOR VOLTAGES WITH THE
ELECTRICAL DRAWING BEFORE ORDERING MOTORIZED EQUIPMENT AND
CONTROLS.
C.F.M. LISTED IS ACTUAL AIR.
SUPPLIERS SHALL REVIEW ALL DRAWINGS AND THE SPECIFICATIONS PRIOR TO
SUBMITTING PRICES TO THE CONTRACTOR. ALL QUESTIONS AND DISCREPANCIES
SHALL BE BROUGHT TO THE ENGINEERS ATTENTION PRIOR TO BIDDING.
CONTRACTOR SHALL THOROUGHLY REVIEW AND SIGN SUBMITTALS FOR
COMPLETENESS AND COMPLIANCE TO THE SPECIFICATIONS PRIOR TO ENGINEERS
REVIEW. SUPPLIERS SHALL HIGHLIGHT OR MARK ALL INFORMATION REQUIRED TO
SHOW COMPLIANCE TO THE SPECIFICATIONS. ALL REQUESTED EXCEPTIONS TO
THE SPECIFICATIONS, OR SCHEDULES SHALL BE CLEARLY NOTED AND EXPLAINED.
SUBMITTAL REVIEW AND ACCEPTANCE IS FOR DESIGN CONCEPT ONLY, AND DOES
NOT AT ANY TIME RELIEVE THE CONTRACTOR OF RESPONSIBILITY TO MEET
SPECIFICATIONS, CAPACITIES, OR DESIGN INTENT.
ALL MECHANICAL SHALL BE INSTALLED AND CONFORM TO THE 2021 EDITION OF THE
IMC AND IPC WITH UTAH ANNOTATIONS AND LOCAL AUTHORITY REQUIREMENTS.
THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE DRAINING DOWN AND
RE-FILLING OF ALL SYSTEMS NECESSARY TO COMPLETE THE WORK OUTLINED BY
THIS PROJECT. THIS INCLUDES PROVIDING THE REQUIRED CHEMICAL TREATMENT
WHEN RE-FILLING THE SYSTEM.
THIS CONTRACTOR SHALL CONTRACT WITH A DESIGN BUILD ELECTRICAL
CONTRACTOR FOR THE DESIGN AND CONSTRUCTION OF THE ELECTRICAL PORTION
OF THIS PROJECT. ELECTRICAL INSTALLATION AND DESIGN SHALL BE PER 2020
NEC.
ALL PIPING, MATERIALS, ETC. SHALL BE NEW AND DOMESTIC MADE UNLESS
SPECIFICALLY AUTHORIZED IN WRITING PRIOR TO BID.
G-1
G-2
G-3
G-4
G-5
G-6
G-7
G-8
G-9
G-10
G-11
G-12
G-13
G-14
G-15
G-16
G-17
G-18
G-19
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
SPECIAL INSPECTIONS
AND TESTING
MG001
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
VEST.CONCOURSE
ELEC.
CLASSROOM CLASSROOM
OFFICE
SERVER T.R.
BREAKOUT
JAN.
OFFICE
SERVER
OFFICE
FD
DN
UP
UP
UP
DN
UP
SS
T
SHEET NOTES:
REMOVE EXISTING SLIT DX SYSTEM IN
THIS APROXIMATE LOCATOIN. REMOVE
CONDENSATE PUMP, REFRIGERANT
PIPING THROUGH ROOF TO
CONDENCSER AND ELECTRICAL BACK
TO PANEL. REMOVE THERMOSTAT. SEE
ME101 FOR NEW WORK.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE PROVISIONS
WITH A DESIGN BUILD ELECTRICIAN TO
VERIFY ELECTRICAL CONDITIONS.
DESIGN BUILD CONTRACTOR SHALL
PROVIDE ANY NEW WIRING, CIRCUIT
BREAKERS, PANELS, SWITCH GEAR AND
ALL NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS ELEMENTS
ASSOCIATED WITH EXISTING
MECHANICAL EQUIPMENT BEING
REMOVED. ALL ABANDONED PIPING AND
WIRING SHALL BE REMOVED BACK TO
PANEL UNLESS OTHERWISE APPROVED.
ELECTRICIAN SHALL FIELD VERIFY AND
CONFIRM ELECTRICAL SCOPE AND
EXISTING CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE DOCUMENTED
AND PROVIDED TO ENGINEER.
3. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
4. ROOFING WORK MUST BE COMPLETED
BY THE WARRANTY HOLDER OR DFCM
SHORTLISTED CONTRACTOR.
3/16" = 1' - 0"
0 1' 2' 4' 8' 16' 32'
MAIN BUILDING
MECHANICAL FLOOR DEMO PLAN
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
MAIN BUILDING
MECHANICAL FLOOR
DEMOLITION PLAN
MD101
MAIN BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1 1
CU
SHEET NOTES:
ROOF DEMO NOTES. REMOVE ROOF
MOUNTED CONDENSER IN THIS
APPROXIMATE LOCATION. REMOVE
STAND, ELECTRICAL.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE PROVISIONS
WITH A DESIGN BUILD ELECTRICIAN TO
VERIFY ELECTRICAL CONDITIONS.
DESIGN BUILD CONTRACTOR SHALL
PROVIDE ANY NEW WIRING, CIRCUIT
BREAKERS, PANELS, SWITCH GEAR AND
ALL NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS ELEMENTS
ASSOCIATED WITH EXISTING
MECHANICAL EQUIPMENT BEING
REMOVED. ALL ABANDONED PIPING AND
WIRING SHALL BE REMOVED BACK TO
PANEL UNLESS OTHERWISE APPROVED.
ELECTRICIAN SHALL FIELD VERIFY AND
CONFIRM ELECTRICAL SCOPE AND
EXISTING CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE DOCUMENTED
AND PROVIDED TO ENGINEER.
3. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
1/16" = 1' - 0" 0 2' 4' 8' 16' 32' 64'
MAIN BUILDING ROOFTOP
MECHANICAL FLOOR DEMO PLAN
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
MAIN BUILDING ROOFTOP
MECHANICAL FLOOR
DEMOLITION PLAN
MD102
MAIN BUILDING ROOFTOP
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
SHEET NOTES:
REMOVE EXISTING SLIT DX SYSTEM IN
THIS APROXIMATE LOCATOIN. REMOVE
CONDENSATE PUMP, REFRIGERANT
PIPING THROUGH ROOF TO
CONDENCSER AND ELECTRICAL BACK
TO PANEL. REMOVE THERMOSTAT. SEE
ME101 FOR NEW WORK.
REMOVE DRAIN PIPING TO THIS
APPROXIMATE LOCATION. FIELD
VERIFY EXACT ROUTING AND POINTS
OF REMOVAL.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE PROVISIONS
WITH A DESIGN BUILD ELECTRICIAN TO
VERIFY ELECTRICAL CONDITIONS.
DESIGN BUILD CONTRACTOR SHALL
PROVIDE ANY NEW WIRING, CIRCUIT
BREAKERS, PANELS, SWITCH GEAR AND
ALL NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS ELEMENTS
ASSOCIATED WITH EXISTING
MECHANICAL EQUIPMENT BEING
REMOVED. ALL ABANDONED PIPING AND
WIRING SHALL BE REMOVED BACK TO
PANEL UNLESS OTHERWISE APPROVED.
ELECTRICIAN SHALL FIELD VERIFY AND
CONFIRM ELECTRICAL SCOPE AND
EXISTING CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE DOCUMENTED
AND PROVIDED TO ENGINEER.
3. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
1/2" = 1' - 0" 0 1' 2' 4' 8'
BARLOW BUILDING
MECHANICAL DEMO PLAN
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
BARLOW BUILDING
MECHANICAL DEMOLITION
PLAN
MD103
BARLOW BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1/4" = 1' - 0" 0 4'1' 2' 8' 16'
ROOFTOP BARLOW BUILDING
MECHANICAL DEMO PLAN
SHEET NOTES:
REMOVE ROOF MOUNTED CONDENSER
IN THIS APPROXIMATE LOCATION.
REMOVE STAND, ELECTRICAL, AND
REFRIGERANT PIPING.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE PROVISIONS
WITH A DESIGN BUILD ELECTRICIAN TO
VERIFY ELECTRICAL CONDITIONS.
DESIGN BUILD CONTRACTOR SHALL
PROVIDE ANY NEW WIRING, CIRCUIT
BREAKERS, PANELS, SWITCH GEAR AND
ALL NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS ELEMENTS
ASSOCIATED WITH EXISTING
MECHANICAL EQUIPMENT BEING
REMOVED. ALL ABANDONED PIPING AND
WIRING SHALL BE REMOVED BACK TO
PANEL UNLESS OTHERWISE APPROVED.
ELECTRICIAN SHALL FIELD VERIFY AND
CONFIRM ELECTRICAL SCOPE AND
EXISTING CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE DOCUMENTED
AND PROVIDED TO ENGINEER.
3. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
ROOFTOP BARLOW BUILDING
MECHANICAL DEMOLITION
PLAN
MD104
ROOFTOP BARLOW BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MECH.
HALL
VEST.CONCOURSE
ELEC.
REFRESH OFFICE HUDDLE HUDDLE OFFICE
CLASSROOM CLASSROOM
STUDENT
SERVICES OPEN
OFFICE
OFFICE
SERVER T.R.
BREAKOUT
JAN.
OFFICE
TRANSACTION
WINDOW
WORK
SERVER
OFFICE
OFFICE
OFFICE
SS
T
FD
DN
UP
UP
UP
DN
UP
SS
T
SHEET NOTES:
PROVIDE SPLIT DX SYSTEM IN THIS
APPROXIMATE LOCATION. PROVIDE
CONDENSATE PUMP AND TIE INTO
EXISTING WASTE PIPING. PROVIDE
REFRIGERANT PIPING THROUGH ROOF
TO CONDENSER. PROVIDE NEW
ELECTRICAL FROM PANEL. PROVIDE
BACNET CAPABLE EQUIPMENT NEW
WIRED THERMOSTAT. RPUTE ALL PIPING
TO FOLLOW EXISTING ROUTES WHERE
POSSIBLE. PROVIDE ROOF
PENETRATIONS TO MEET DFCM
ROOFING STANDARDS IF NEEDED. SEE
ME501 FOR DETAILS, SEE ME601 FOR
SCHEDULES.
PROVIDE NEW THERMOSTAT
APPROXIMATELY 48" AFF. IN THIS
APPROXIMATE LOCATION. FIELD
VERIFY EXACT LOCATION.
0 1' 2' 4' 8' 16' 32' 1/8" = 1' - 0"
MAIN BUILDING
MECHANICAL FLOOR PLAN
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
3. FACTORY START UP OF NEW SYSTEMS
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
MAIN BUILDING
MECHANICAL FLOOR PLAN
ME101
MAIN BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1 1
CU
SHEET NOTES:
PROVIDE NEW CONDENSING UNIT AND
ALL ASSOCIATED ITEMS IN THIS
APPROXIMATE LOCATION. FIELD
VERIFY. INSTALL PER MANUFACTURES
RECOMMENDATION. PROVIDE HAIL
GUARD AND EQUIPMENT STAND. SEE
MECHANICAL DETAILS. PROVIDE WALK
PADS AT EACH PIECE OF EQUIPMENT.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE PROVISIONS
WITH A DESIGN BUILD ELECTRICIAN TO
VERIFY ELECTRICAL CONDITIONS.
DESIGN BUILD CONTRACTOR SHALL
PROVIDE ANY NEW WIRING, CIRCUIT
BREAKERS, PANELS, SWITCH GEAR AND
ALL NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS ELEMENTS
ASSOCIATED WITH EXISTING
MECHANICAL EQUIPMENT BEING
REMOVED. ALL ABANDONED PIPING AND
WIRING SHALL BE REMOVED BACK TO
PANEL UNLESS OTHERWISE APPROVED.
ELECTRICIAN SHALL FIELD VERIFY AND
CONFIRM ELECTRICAL SCOPE AND
EXISTING CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE DOCUMENTED
AND PROVIDED TO ENGINEER.
3. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
1/2" = 1' - 0" 0 1' 2' 4' 8'
ROOFTOP MAIN BUILDING
MECHANICAL PLAN
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
ROOFTOP
MECHANICAL PLAN
ME102
ROOFTOP MAIN BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
2T
SS 1
SS 1
SHEET NOTES:
PROVIDE SPLIT DX SYSTEM IN THIS
APPROXIMATE LOCATION. PROVIDE
CONDENSATE PUMP AND TIE INTO
EXISTING WASTE PIPING. PROVIDE
REFRIGERANT PIPING THROUGH ROOF
TO CONDENSER. PROVIDE NEW
ELECTRICAL FROM PANEL. PROVIDE
BACNET CAPABLE EQUIPMENT NEW
WIRED THERMOSTAT. RPUTE ALL
PIPING TO FOLLOW EXISTING ROUTES
WHERE POSSIBLE. PROVIDE ROOF
PENETRATIONS TO MEET DFCM
ROOFING STANDARDS IF NEEDED. SEE
ME501 FOR DETAILS, SEE ME601 FOR
SCHEDULES.
PROVIDE NEW THERMOSTAT
APPROXIMATELY 48" AFF. IN THIS
APPROXIMATE LOCATION. FIELD
VERIFY EXACT LOCATION.
TIE IN TO EXISTING DRAIN PIPING IN
THIS APPROXIMATE LOCATION. FIELD
VERIFY EXACT ROUTING AND POINTS
OF CONNECTION.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS. CONTRACTOR
SHALL FIELD VERIFY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE PROVISIONS
WITH A DESIGN BUILD ELECTRICIAN TO
VERIFY ELECTRICAL CONDITIONS.
DESIGN BUILD CONTRACTOR SHALL
PROVIDE ANY NEW WIRING, CIRCUIT
BREAKERS, PANELS, SWITCH GEAR AND
ALL NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS ELEMENTS
ASSOCIATED WITH EXISTING
MECHANICAL EQUIPMENT BEING
REMOVED. ALL ABANDONED PIPING AND
WIRING SHALL BE REMOVED BACK TO
PANEL UNLESS OTHERWISE APPROVED.
ELECTRICIAN SHALL FIELD VERIFY AND
CONFIRM ELECTRICAL SCOPE AND
EXISTING CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE DOCUMENTED
AND PROVIDED TO ENGINEER.
3. ALL CONTROLS WIRING AND ELECTRICAL
WIRING MUST BE PROVIDED WITH
CONDUIT.
1/2" = 1' - 0" 0 1' 2' 4' 8'
BARLOW BUILDING
MECHANICAL DEMO PLAN
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
BARLOW BUILDING
MECHANICAL PLAN
ME103
BARLOW BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1 3
CU
CU2
SHEET NOTES:
PROVIDE NEW CONDENSING UNIT AND
ALL ASSOCIATED ITEMS IN THIS
APPROXIMATE LOCATION. FIELD
VERIFY. INSTALL PER MANUFACTURES
RECOMMENDATION. PROVIDE HAIL
GUARD AND EQUIPMENT STAND. SEE
MECHANICAL DETAILS. PROVIDE WALK
PADS AT EACH PIECE OF EQUIPMENT.
PROVIDE NEW REFRIGERANT LINESET
ROOF PENETRATION IN THIS
APPROXIMATE LOCATION. PROVIDE
WITH LINESET ENCLOSURE, SEE
DETAIL A3/ME501. ROOF
PENETRATIONS SHALL BE A MINIMUM
OF 18" APART.
1/4" = 1' - 0" 0 4'1' 2' 8' 16'
ROOFTOP BARLOW BUILDING
MECHANICAL PLAN
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY
EXISTING MECHANICAL AND
ARCHITECTURAL CONDITIONS,
INCLUDING, BUT NOT LIMITED TO:
EXISTING ROUTING AND LOCATION OF
DUCTWORK, PIPING, ELECTRICAL AND
STRUCTURAL ELEMENTS.
CONTRACTOR SHALL FIELD VERIFY
POTENTIAL CONFLICTS
BETWEEN NEW MECHANICAL
ELEMENTS AND EXISTING CONDITIONS
PRIOR TO BEGINNING FABRICATION OR
ORDERING EQUIPMENT.
2. CONTRACTOR SHALL MAKE
PROVISIONS WITH A DESIGN BUILD
ELECTRICIAN TO VERIFY ELECTRICAL
CONDITIONS. DESIGN BUILD
CONTRACTOR SHALL PROVIDE ANY
NEW WIRING, CIRCUIT BREAKERS,
PANELS, SWITCH GEAR AND ALL
NECESSARY ELECTRICAL
ACCOMMODATIONS FOR ANY NEW OR
RE-LOCATED MECHANICAL EQUIPMENT.
CONTRACTOR SHALL COORDINATE THE
DEMOLITION AND REMOVAL OF ANY
ELECTRICAL AND CONTROLS
ELEMENTS ASSOCIATED WITH
EXISTING MECHANICAL EQUIPMENT
BEING REMOVED. ALL ABANDONED
PIPING AND WIRING SHALL BE
REMOVED BACK TO PANEL UNLESS
OTHERWISE APPROVED. ELECTRICIAN
SHALL FIELD VERIFY AND CONFIRM
ELECTRICAL SCOPE AND EXISTING
CONDITIONS PRIOR TO ANY
DEMOLITION WORK OR ORDERING
ANY NEW MECHANICAL EQUIPMENT.
SHOP DRAWINGS, CALCULATIONS, AND
MODIFICATIONS SHALL BE
DOCUMENTED AND PROVIDED TO
ENGINEER.
3. ALL CONTROLS WIRING AND
ELECTRICAL WIRING MUST BE
PROVIDED WITH CONDUIT.
4. PRIME CONTRACTOR SHALL PROVIDE
ALL COORDINATION BETWEEN
SUB-TIER
CONTRACTORS. THIS SHALL INCLUDE
THE COORDINATION BETWEEN
SUB-TIER
CONTRACTORS,
SUB-TIERCONTRACTORS AND
FACILITIES, SUB-TIER CONTRACTORS
AND ARCHITECT/ENGINEER, ETC.
5. ALL DEMOLISHED EQUIPMENT AND
MATERIAL SHALL BE BROKEN DOWN TO
FIT THROUGH DESIGNATED PATHWAYS.
FIELD VERIFY EXACT SCOPE OF
DEMOLITION AND REMOVAL PATH.
CONTRACTOR SHALL BE RESPONSIBLE
TO REPAIR ANY DAMAGE TO BUILDING
DURING REMOVAL OF EQUIPMENT AND
MATERIAL.
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
ROOFTOP BARLOW BUILDING
MECHANICAL PLAN
ME104
ROOFTOP BARLOW BUILDING
KEYPLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
CU
4" MIN. RADIUS
ALL BENDS
3/4" COND. DRAIN
LINE. (BEYOND) RUN
TO SERVICE SINK IN
CUST. ROOM.
PIPE THRU ROOF.
SEE EQUIPMENT
STAND DETAIL.
ROOFING
THERMOSTAT
CONTROLLER
WALL
FLOOR
NOTE:
RUN STEEL COVER CONTINUOUS FROM CONDENSING
UNIT TO RISERS OR PENETRATIONS AT BUILDING WALL
OR ROOF.
VA
R
IE
S
4"
UNISTRUT PIPE
CLAMP (TYP.)
INSULATION (TYP.)
UNISTRUT CHANNEL
1-5/8" x1-5/8"
18 GAUGE GALVANIZED
SHEET METAL PROTECTIVE
COVER. RUN FROM COND.
UNIT TO BUILDING.
ADJUSTABLE HEIGHT PIPE
SUPPORT PP10 BY PORTABLE
PIPE HANGERS OR EQUAL.
20 GAUGE GALV.
SLEEVE 6" LONG
(TYPICAL)
4" AS REQ'D.
2" AS REQ'D. 2"
2"
PLAN VIEW
NOTE: THAT PITCH POCKETS ARE NOT AN
ACCEPTABLE METHOD OF WATER-PROOFING
BASE OF PIPES
2"
AS
R
EQ
'D
2"
8" M
IN
. T
O F
AS
TE
N
ER
S
1'
8" M
IN
LINE SET ENCLOSURE
SCALE: NONEA3
LINE SET OR OTHER SIM.
PENETRATIONS THROUGH ROOF
FASTEN FLANGES OF ENCLOSURE TO
DECK WITH (12) #14 STS (OR APPROPRIATE
FASTENERS FOR DECK TYPE)
20 GA. GALVANIZED CAP -FASTEN TO
ENCLOSURE W/ (2 PER SIDE ON 3 SIDES)
HIGH-DOMED, CAPPED, GASKETED FASTENERS
- ALL SEAMS / JOINTS ARE TO BE FULLY
WELDED / WATER-PROOFED
NOTE THAT THIS EDGE OF THE CAP IS TO
EXTEND 4" BEYOND THE FACE OF THE
ENCLOSURE TO SHIELD LINE SET
PENETRATION FROM WEATHER -
PROVIDE HEMMED DRIP EDGE AS SHOWN
SEAL OR FOAM IN AND AROUND
OPENINGS TO FURTHER PROTECT
THE OPENING FROM THE ELEMENTS
AND INSECTS ETC.
NOTCH CAP WHERE
PIPES PENETRATE
WELD PARTIAL PIPE
EXTENSION TO ENCLOSURE -
SEE PHOTO ABOVE
LINE SET OR OTHER SIM.
PENETRATIONS THROUGH ROOF
PACK BASE OF ENCLOSURE
W/ BATT INSULATION
FASTEN FLANGES OF ENCLOSURE TO
DECK WITH (12) #14 STS (OR APPROPRIATE
FASTENERS FOR DECK TYPE)
ROOFING MEMBRANE -
VARIES BY PROJECT
RIGID INSULATION
-VARIES BY PROJECT
ROOF DECK VARIES BY
PROJECT
ADHERE FLASHING TO
ENCLOSURE
TERMINATION BAR AND
SEALANT
ONE PIECE 24 GA. G-90
G.I. COUNTER FLASHING
SEALANT
20 GA. GALVANIZED
ENCLOSURE WITH ALL SEAMS /
JOINTS FULLY WELDED /
WATER-PROOFED
TYPICAL
MIN.
2"
MIN.
2"
VARIES
MIN.
2"
MIN.
2"
TYPICAL
PIPE / CONDIUT FLASHING OPTIONS
" M
IN
NOTE: IF THE TOP OF THE
EXISTING VENT IS LESS THAN
12" ABOVE THE NEW
FINISHED ROOF SURFACE,
THE VENT MUST BE
EXTENDED
NOTE THAT WHERE A PIPE IS CAPABLE
OF BEING FLASHED USING A ROOFING
MANUFACTURES PRE-FABRICATED
BOOT (SUCH AS SHOWN ABOVE), THAT
OPTION IS REQUIRED AND SHOULD BE
USED OVER A FIELD FLASHED DETAIL
(SUCH AS SHOWN BELOW)
NOTE THAT PITCH
POCKETS ARE NOT AN
ACCEPTABLE METHOD
OF WATER-PROOFING
BASE OF PIPES
PIPE/CONDUIT FLASHING DETAIL
SCALE: NONEA1
HEAT WELDED
FLASHING
ROOFING MEMBRANE -
VARIES BY PROJECT
ROOFING MEMBRANE -
VARIES BY PROJECT
ROOF DECK VARIES BY
PROJECT
PLUMBING VENT /
STACK
FLASHING MEMBRANE AND
SEALANT
STAINLESS STEEL
CLAMPING RING
ADHERED FIELD
FLASHED MEMBRANE
HEAT WELDED
FLASHING
ROOFING MEMBRANE -
VARIES BY PROJECT
RIGID INSULATION
-VARIES BY PROJECT
ROOF DECK VARIES BY
PROJECT
CONTINUOUS WELD
SPM MEMBRANE
PRE-FABRICATED BOOT
WITH MINIMUM 1" TURN-UP
STAINLESS STEEL CLAMPING
RING
FLASHING MEMBRANE AND
SEALANT
PIPE / CONDUIT
TYP
UNISTRUT AND
GALVANIZED COVER
FOR VERTICAL
INSTALLATION AS WELL.
ANCHOR TO MASONRY.
THERMOPLASTIC
2"x4" DIA.
ADAPTOR
SANITARY
"Y" FITTING
2" WASTE DOWN.
RUN IN WALL TO
BELOW.
1-1/2" P-TRAP AND TAIL PIECE USE
THERMOPLASTIC PIPE AND FITTINGS.
1-1/2"
NIPPLE
2"X1-1/2"
BUSHING
TRAP GUARD
CONDENSATE LINE.
MAINTAIN AIR GAP.
CONDENSATE LINE.
2" VENT UP
THROUGH
ROOF.
SANITARY
"Y" FITTING
EXTERIOR REFRIGERANT PIPE SUPPORT
SCALE: NONEA4
WALL MOUNT AC UNIT DETAIL
SCALE: NONEB4
FUNNEL DRAIN DETAIL
SCALE: NONED4
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
MECHANICAL DETAILS
ME501
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
PIPE HANGER DETAIL
CLEVIS HANGER
A3
SINGLE HORIZONTAL RUN
WITHOUT INSULATION
CLEVIS HANGER
NOTE:
PROVIDE WITH VAPOR BARRIER
ON CHILLED WATER AND
DOMESTIC COLD WATER PIPING
HANGER
BOLT UNISTRUT TO EXISTING
WALL AND CONCRETE USING
EXPANSION ANCHOR BOLTS
MOUNT PIPING TO UNISTRUT
CALCIUM SILICATE
BLOCK
PROVIDE PIPE CLAMPS
WITH BOLTS AND NUTS
16 GA. ZINC COATED SHEET STEEL
SHIELD AT LEAST 12" LONG (TYP)
CALCIUM SILICATE
BLOCK
INSULATION WITH OR WITHOUT
VAPOR BARRIER
ATTACH TO ROOM
OVERHEAD STRUCTURE
SPRING TYPE ISOLATOR
FOR INSTALLATION NEAR
HOT WATER PUMPSATTACH TO EXISTING
CEILING
HANGER ROD
HEAVY DUTY
CLEVIS HANGER
PIPE
HANGER ROD
HEAVY DUTY
CLEVIS HANGER
SUPPORT NUT
LOCKING NUT
INSULATION
LOCKING NUT
SUPPORT NUT
PIPE
16 GAGE ZINC COATED
SHEET STEEL SHIELD
AT LEAST 12" LONG.
CALCIUM SILICATE BLOCK
TYPICAL AIR COOLED CONDENSING UNIT DETAIL
SCALE: NONEC1
F L
S ROUTE TO DF COIL
SEE DETAIL
FILTER DRIER
SIGHT GLASS
FLEXIBLE
CONNECTION
(TYP)
VIBRATION ISOLATORS
UNDERNEATH UNITS.
(ONE EACH CORNER)
MOUNT TO ROOF CURB
OR HOUSEKEEPING PAD
WITH SEISMIC CLIPS.
ROOFING MEMBRANE - VARIES
BY PROJECT
RIGID INSULATION -
VARIES BY PROJECT
STAINLESS STEEL
CLAMPING RING
CONT. BEAD OF
APPROVED SEALANT
FIELD FABRICATED
METAL HOOD
PRE-MOLDED PVC
PIPE FLASHING
2" MIN. WELDED
SPLICE
GALVANIZED C4x5.4
CHANNEL
24" TALL GALVANIZED HSS 3x.203 -
MEASURE AND FIELD CUT BOTTOM OF
POSTS AS REQ'D. TO ACHIEVE LEVEL
TOP OF PLATFORM
8" M
IN
ADJUSTABLE BASE / SUPPORT
NOTE:
4 SUCH SUPPORT LEGS ARE TO BE
PROVIDED FOR EACH PIECE OF
EQUIPMENT - INSTALL IN A 24" x 48"
RECTANGULAR CONFIGURATION - MITER
CHANNEL CORNERS AND WELD (TYP.)
12x12x1/2" GALVANIZED STEEL
PLATE - FASTEN INTO DECK
PER STRUCTURAL ENGINEERS
RECOMMENDATIONS
NOTE:
NO WELDING WILL BE ALLOWED ON
THE ROOF - WELDING SHALL BE DONE
IN THE PARKING LOT OR IN A SHOP
1/2"⌀ THROUGH BOLT WITH LOCK
WASHER - DRILL THROUGH ANGLES
AND HSS POST AS REQ'D.
ROOF DECK - VARIES
BY PROJECT
1/4
1/4
1/8
CJP (TYP @ MITERED CHANNEL
JOINTS TOP & SIDES)
3x3x1/4x 4" LONG GALVANIZED STEEL
ANGLE WELDED TO BASE PLATE -
EACH SIDE OF HSS POST
BOTH ENDS
1/4 ROOFTOP EQUIPMENT VARIES - IF
EQUIPMENT MOUNTING POINTS ALIGN WITH
THE CHANNEL FRAME, ATTACHMENT OF
EQUIPMENT CAN BE MADE DIRECTLY TO
THE FRAME - IF EQUIPMENT MOUNTING
POINTS DO NOT ALIGN WITH THE CHANNEL
FRAME, MOUNT TO A UNI-STRUT SYSTEM
THAT WOULD SPAN BETWEEN AND ATTACH
TO BOTH THE CHANNEL FRAME AS WELL AS
THE EQUIPMENT MOUNTS
FIELD CUT BOTTOM OF SUPPORT POSTS
AS REQ'D. TO ACHIEVE A LEVEL PLATFORM
NOTE THAT THIS DETAIL IS TO BE
USED WHEREVER ROOFTOP
EQUIPMENT WOULD TYPICALLY BE
INSTALLED ON WOOD, BOXED, CURB -
WOOD CURBS SHOULD NOT BE USED
COORDINATE WITH DETAIL #03 AND
DETAIL #04 FOR ELECTRICAL AND
OR LINE SET (AS OCCURS)
PENETRATION DETAILS
TYPICAL NOTE: ALL EXISTING LINE SETS AND
ELECTRICAL LINES / CONNECTIONS (AS OCCUR)
ARE TO BE REPLACED WITH NEW - WITH THE
EXCEPTION OF RIGHT AT THE EQUIPMENT
LOCATION, ELECTRICAL LINES AND JUNCTION
BOX'S THAT ARE RUN ABOVE THE ROOF, AND OR
DECK, ARE TO BE REPLACED AND RE-RUN
BENEATH THE DECK BACK TO THE NEAREST
JUNCTION OR ELECTRICAL BOX - NO FLEXIBLE
ELECTRICAL CONDUIT WILL BE ALLOWED LOWER
THAN 12" ABOVE THE FINISHED ROOF SURFACE -
ALL ELECTRICAL WORK MUST BE DONE TO NEC
STANDARDS
NOTE THAT WALK PADS ARE TO BE
PROVIDED AT ALL 4 SIDES OF
THESE ELEVATED PLATFORMS
EQUIPMENT PLATFORM 3D
ROTATE DIRECTION OF BASE
PLATES AS REQ'D TO ALIGN WITH
SLOPE OF DECK (TYP.)
ELEVATED PLATFORM DETAIL
SCALE: NONEB3
PR
OV
ID
E
" A
BO
VE
R
OO
F
DE
CK
LEGS SHALL BE ROUND, NOT
SQUARE. ALUMA STAND OR
APPROVED EQUAL
FILL ALL GALVANIZING HOLES WITH
ZINC PLUGS
PROVIDE SLIP SHEET UNDER STAND
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
MECHANICAL DETAILS
ME502
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
DX UNIT SCHEDULE - INDOOR UNIT
SYMBOL AREA SERVED EQUIPMENT
SERVED TYPE CFM ESP
COOLING
(BTU/HR)
ELECTRICAL
OPERATING
WEIGHT MANUF & MODEL SCHEDULE
NOTESVOLTAGE PHASE FREQUENCY MCA
MAIN BLDG CU-1 WALL
MOUNTED 2150 CFM .60" 36000 208/230 V 1 60Hz 1A 214 Lbs MSY-GX36NL 1,2,3,4,5,6
BARLOW
BUILDING CU-2 WALL
MOUNTED 2150 CFM .60" 36000 208/230 V 1 60Hz 1A 214 Lbs MSY-GX36NL 1,2,3,4,5,6
BARLOW
BUILDING CU-3 WALL
MOUNT 1750 CFM .10" 36,000 208/230 V 1 60Hz 1A 48 Lbs MSY-GX36NL 1,2,3,4,5,6
1. R-454B REFRIGERANT
2. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.
3. PROVIDE WITH INTEGRAL CONDENSATE PUMP. ROUTE CONDENSATE LINE TO NEAREST FLOOR DRAIN OR FUNNEL DRAIN.
4. PROVIDE WITH INDIVIDUAL ZONE THERMOSTAT.
5. EACH UNIT IS POWERED INDIVIDUALLY.
6. COORDINATE PIPING AND ELECTRICAL CONNECTIONS TO HAVE A MINIMUM OF 36"X30" CLEARANCE IN FRONT OF ELECTRICAL CONNECTIONS.
SS
SS
SS
SS
SS
DX CONDENSER SCHEDULE - OUTDOOR UNIT
SYMBOL EQUIPMENT
SERVED
COOLING
(BTU/HR)
ELECTRICAL
SEER 2 OPERATING
WEIGHT MANUF & MODEL SCHEDULE
NOTESVOLTAGE PHASE FREQUENCY MCA MOCP
MAINTENANCE
LAB 36000 40000 3 60Hz 23 A 25 A 18.5 116 Lbs MUY-GX36NL 1,2,3,4,5,6,7,8
MAINTENANCE
LAB 36000 40000 3 60Hz 23 A 25 A 18.5 116 Lbs MUY-GX36NL 1,2,3,4,5,6,7,8
PRINT ROOM 36,000 208/230 V 1 60Hz 23 A 25 A 18.5 186.3 Lbs MUY-GX36NL 1,2,3,4,5,6,7,8
1. R410A REFRIGERANT
2. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.
3. PROVIDE WITH CONTROLS SYSTEM, INCLUDING PANEL, SENSORS, PROGRAMMING, GRAPHICS, ETC. AS REQUIRED FOR A COMPLETE AND FUNCTIONING SYSTEM.SYSTEM SHALL BE WEB
ENABLED FOR MONITORING AND ADJUSTMENTS.
4. PROVIDE WITH ANY ADDITIONAL PIPING, REFRIGERANT, ETC. TO ACCOMMODATE ACTUAL PIPING LENGTHS.
5. PROVIDE WITH 18" HIGH ALUMA-STAND OR EQUAL WITH ROUND STAND.
6. ROOF FLASHING.
7. PROVIDE WITH CONDENSER HAIL GUARD.
8. OWNER FURNISHED, CONTRACTOR INSTALLED.
CU
CU
CU
CU
CU
550 E 300 S, KAYSVILLE, 84037
SHEET NO.
AE
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
SG
06/17/2026
JL
WHW JOB NO.:
26065
1 2 3
CONSULTANTS
SHEET TITLE
PROJECT NAME & ADDRESS
DTC HVAC
SPLIT SYSTEMS
DFCM #27050220
CODE REVIEW STAMP
ENGINEERING LLC.
733 WEST 9000 SOUTH
SANDY, UTAH 84070
(801)466-4021 EMAIL: excellence@whw-engineering.com
PROFESSIONAL MECHANICAL ENGINEERING
WHW
JOHN M.
LARSEN
No. 12199025
PR
OF
ESS IONAL ENGINEER
S T A T E O F U T A H
06/22/26
MECHANICAL PLAN
ME601
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
| Sheets and Views |
| M 26065 DTC HVAC UPGRADES-G001 |
| M 26065 DTC HVAC UPGRADES-G002 |
| M 26065 DTC HVAC UPGRADES-MG001 |
| M 26065 DTC HVAC UPGRADES-MD101 |
| M 26065 DTC HVAC UPGRADES-MD102 |
| M 26065 DTC HVAC UPGRADES-MD103 |
| M 26065 DTC HVAC UPGRADES-MD104 |
| M 26065 DTC HVAC UPGRADES-ME101 |
| M 26065 DTC HVAC UPGRADES-ME102 |
| M 26065 DTC HVAC UPGRADES-ME103 |
| M 26065 DTC HVAC UPGRADES-ME104 |
| M 26065 DTC HVAC UPGRADES-ME501 |
| M 26065 DTC HVAC UPGRADES-ME502 |
| M 26065 DTC HVAC UPGRADES-ME601 |
File details come from the government source that posted it. Updated .