FC1 Elevator Modernization Scope of Work Summary

This document is a scope of work exhibit for the University of Texas at Austin's FC1 Elevator Modernization project. The project involves a selective alteration and modernization of two hydraulic elevators serving the FC1 office building. The work aims to maximize reliability and extend the usable lifespan of the existing equipment while incorporating energy-efficient design principles. The scope requires qualified vendors to address all aspects of the modernization process to ensure the elevators meet current operational and safety standards.

The document establishes the detailed technical requirements and specifications for the elevator modernization work that vendors must address in their proposals. Specific details regarding pricing terms, contract duration, performance schedules, milestone dates, and other contractual provisions are contained within the referenced RFP documentation. The project represents the University's commitment to upgrading critical building infrastructure while maintaining operational efficiency and reducing energy consumption in the FC1 facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FC1 Elevator 1 and 2 Modernization RFP 721-26063

RFP 721-26063 – EXHIBIT A

SECTION 4.5 SCOPE OF WORK

HYDRAULIC PASSENGER ELEVATOR

FC1 elevators 1 and 2

PART 1 GENERAL

1.1 SPECIAL CONSIDERATIONS

A) The resultant elevator system will maximize reliability and extend the usable lifespan of the equipment. The project will correct code violations within the hoistway, pit, machinery spaces, and control rooms. The intent is to create a system with the longest life span and make it as reliable as possible. Parts of the elevator system will be brought into compliance using a combination of the latest adopted codes and the latest published codes.

The latest technology shall be utilized to provide the most current safety features available. The building will be continually occupied during the construction period. The contractor will need to provide an accessible route for the building’s occupants and always keep one elevator in service. Temporary screening shall be installed inside the hoistway during the construction process to protect the workers inside the hoistway and to prevent interference with the car left in operation. The contractor shall provide routine monthly service and respond to calls for repair or entrapment twenty-four hours a day on the car that is in operation for the entire period of construction and warranty.

1.2 SUMMARY

A) Description of work: This will be a selective modernization of two elevators located at FC1. This project will utilize the latest adopted edition of ASME A17.1- 2016. All requirements of ASME A17.1 section 8.7.3 shall be followed. The platform, sling, jack, and cab will be retained. The power units will be changed to increase reliability. The project consists of replacing the elevator drive and control systems. A new operational and motion controller will be installed. New switches and wiring for the controls will be provided. The hall doors will be retained and will be fitted with new hangers, rollers, and interlocks. The car doors will be retained, and a new door operator will be installed. The new power units will be installed and have secondary containment.

B) Project completion Date: The Construction dates shall be scheduled at a pre-construction meeting. This meeting will be scheduled with the building’s occupants after the contract is awarded. Once the work has begun it shall be completed within the agreed schedule. Work can only be done on one elevator at a time. The other elevator must be maintained and kept in service. Maintenance service and response to callbacks need to be included to maintain continuity of service.

C) Hydraulic passenger elevator system.

1) (New) Non-proprietary operational controller (Part 13)

2) (New) Landing system

3) (New) Car station to fit in the existing dover swing panel space Refer to Supplement #004

4) (New) Power unit- Motor, pump, unitized oil control valve, silencer (shall not contain degradable parts), tank, viscosity control, and secondary containment for the full capacity of the hydraulic system.

5) (New) Hydraulic oil

a. Hydraulic elevators shall be supplied with a petroleum-based oil that includes an additive package to prevent oxidation, corrosion, and wear. The oil shall have a cleanliness rating meeting the ISO target of 17/14/11 or better. Vegetable based or blended Vegetable oils are not acceptable.

6) (Reuse/Relocate) Battery rescue units. Install new batteries.

7) (New) Steel shut off valves in machine room and the pit.

8) (New/Reuse) Piping from power unit to jack. Use threaded connections or Victaulic® zero flex™ style 07 rigid coupling with Grade “T” Nitrile Gaskets. Substitutes must be approved by the Elevator Manager.

9) (New) Inground Jack with PVC corrosion protection.

10) (New) Heavy Duty car door operators

11) (New) Firefighters’ Service Phase I and Phase II

12) (New) Hall Controls and Fixtures

13) (New) Car and Hoistway wiring

14) (New) Car top inspection stations

15) (New) Limit Switches

16) (New) Slide guide linings for omega rails

17) (New) Rail leaches to capture excess oil at the bottom of the rails

18) (Retain) The car platform, bolsters, sling, guides, and cab.

D) Pit Work: Refer to Supplement # 002

1) Paint pit floor and sump hole with a chemical resistant non-slip paint. Properly clean and prepare the surfaces using the manufacturer’s instructions for proper adhesion of the new coating. Floor coating shall be equal to or better than POX-A-Crete® Heavy-Duty Epoxy Resurfacer.

2) Paint pit walls to the height of the lowest landing sill with a suitable chemical resistant paint compatible in color and texture with the floor coating.

3) Provide (New/Reuse) Supply Piping to the jack(s) and a (New) Steel shut-off valve in the pit. The piping shall use threaded connections or Victaulic® zero flex™ style 07 rigid coupling with Grade “T” Nitrile Gaskets.

4) (New) Inground Jack with PVC corrosion protection.

5) Provide a means to collect oil from the guide rails. The rails are TK Elevator omega style (Ʊ)

6) Provide (New) NEMA 4 rated GFCI receptacle in the pit.

7) Examine the pit ladder and make modifications to provide for safe and code compliant pit entry into each pit. The existing condition has a shared pit ladder mounted above and below the spreader beam.

8) The ladder rungs shall be covered with a non-slip substance equal to or better than PIG® TuffGrit™ ladder rung cover.

E) Hoistway Work: Refer to Supplement # 003

1) Maintain the fire rating of the hoistway by sealing all penetrations

a) Use an approved UL fire stop system based on the type of penetration

2) Remove all metal or wood protrusions from walls to create a smooth surface.

3) Construct vertical walls or bevel all ledges greater than four inches to meet the requirements of A17.1 2.1.6.2

4) Provide (New) a car top standard railing where a fall hazard is present

5) Provide (New) lighting on the car top, 5-foot candles, and the entire length of the hoistway, 5-foot candles, to provide a combined10-foot candles when used together to work on parts of the doors, car gate operators, landing system, and limit switches.

6) Provide a (New) car top inspection station that is accessible while standing on the access landing. The station shall have a stop switch, light switch, inspection/run selector switch, and the run buttons requiring operation with both hands.

7) Provide “LOW OVERHEAD” Caution Signs if required by A17.1

F) Machine Room Work: Refer to Supplement # 006

1) Provide (New/Reuse) Supply Piping to the jack and a (New) Steel shut-off valve in the machine room. The piping shall use threaded connections or Victaulic® zero flex™ style 07 rigid coupling with Grade “T” Nitrile Gaskets.

2) Seal all penetrations in the machine room walls using an approved UL fire stop system for the type of penetration.

3) Clean and Paint the Machine Room Floor chemical resistant non-slip paint up. Properly clean and prepare the surfaces using the manufacturer’s instructions for proper adhesion of the new coating. Floor coating shall be equal to or better than POX-A-Crete® Heavy-Duty Epoxy Resurfacer.

4) Provide a (New) GFCI duplex receptacle in the machine room.

G) Electrical Requirements: Refer to Supplement # 005

1) (Reuse) the existing power module disconnect switches.

2) Provide (New) university standard Demarcation box in the machine room.

3) Provide (New/Reuse) car light disconnect switches if the existing switches do not meet NFPA 70 430.109(C).

4) Provide a new GFCI duplex receptacle in the machine room and a new NEMA 4 rated GFCI receptacle in the pit.

5) Provide (New) hoistway lighting as required to provide a combined 10fc at the car top, door operator, and hoistway interlocks when used in conjunction with the car top light.

6) Provide (New) lighting over the machine and controller as required to provide 19fc at the floor in front of the controllers and around the power unit where needed for maintenance.

7) Mount controllers and electrical devices to maintain proper electrical working clearances.

8) Relocate fire alarm control modules within three feet of their demarcation box.

9) Remove all unused conduit and boxes from the machine room.

10) Provide a 1 ¼ inch conduit from the demarcation box to the telecom/network closet.

11) Seal all penetrations using an approved UL fire stop system for the type of penetration.

1.3 ELEVATOR WORK

A) The Contractor shall coordinate, begin, and complete all work required by the agreed upon dates. The work shall meet all applicable codes including fire and smoke rated hoistway enclosure, pit, shaft venting, and machine room work.

B) The Contractor shall furnish all labor and material necessary for wiring from the Demarcation box mounted in the elevator machine room to the elevator controller system.

C) The Contractor shall provide a 1 ¼ inch conduit from the demarcation box to the telecom/network closet.

D) The Contractor shall Extend telephone cable from the demarcation box to each Elevator Car, to the Elevator Controller, or to any other termination point. UT’s Elevator Section shall be responsible for providing dial tone for each elevator cab and machine room telephone.

E) The Contractor shall Notify UT’s Elevator Section at least ten working days prior to the final inspection of the elevator of any repair or installation services required for telephone operation. The elevator cannot be QEI inspected without an emergency communication device.

F) Replace all hoistway, car, and machine room wiring according to Part 12 of this specification.

G) The contractor shall furnish and install a new operational hydraulic elevator controller in accordance with Part 14 of this specification. The contractor shall make all necessary connections to the building’s existing or newly installed fire control system. The elevator control system for fire recall shall be fully operational.

H) Bevel all ledges in the hoistway over 4” in width. Maintain the fire rated integrity of the hoistway for full compliance with the building code, ASME A17.1, and the design specifications provided in the project drawings.

I) The contractor shall use the latest adopted A17.1 Code, these specifications, UT Elevator Supplements #001, #002, #003, #004, #005, and #006.

J) FOR BUILDING EMERGENCY POWER (Generator) or future use: The elevator controls shall include two inputs from the emergency electrical system. One input shall be from a set of Form C contacts, which shall change state when electrical system has switched to emergency operation. A second input shall be from a set of normally open contacts, which shall close 0-50 seconds prior to any controlled change of the emergency electrical system and shall open after the change. This input shall be designated as the pre-transfer signal.

1) This building is not supplied with generator power. A battery rescue (New/Reuse) unit will be the auxiliary power source. Provide an elevator controller that will function with battery lowering and be convertible to generator supplied power at a future date.

a) If a new battery lowering units are installed, the university will want to retain possession of the old units.

K) The elevator contractor shall remove and dispose of material, hoisting material, hydraulic oil, and packing material.

L) Provide improved lighting in the elevator machine room, Cab Interior, pit, and hoistway. It shall have an efficacy greater than or equal to fifty lumens/watts and comply with requirements in Divion26. (Supplement #005)

M) Retain and modify the cab according to Part 18 of this specification.

N) Provide a (New) car-operating panel as specified in Part 19 of this specification.

O) Provide a (New) car top inspection station according to Part 20 of this specification.

P) Replace, modify, or add cab entrance components in accordance with Part 21 of this specification.

Q) Provide (New) landing fixtures according to Part 24 of this specification.

R) Any work which requires disturbing the materials of the hoistway enclosure or the machine room enclosure shall be in accordance with Part 36 of this specification.

S) Prior to commencement of any work provide a signed copy of The University of Texas’ ENVIRONMENTAL

HEALTH AND SAFETY CONSTRUCTION SITE PROCEDURES FOR CONTRACTORS.

T) All labeling required by ASME A17.1 and NFPA 70 shall be permanently engraved/embossed and permanently affixed plaques. Plaques may be either plastic or metal. Shall not use “Permanent Marker,” or “Labeling Tape.”

U) Provide Submittals for Approval, in accordance with Part 5 of this specification, to the Project Manager.

V) Provide Submittals for project close out in accordance wit Part 6 of this specification.

PART 2 REFERENCES- The latest published version of the following shall be used except where noted:

2.1 American Society of Mechanical Engineers (ASME):

A) A17.1: 2016 Safety Code for Elevators and Escalators except for door protection and emergency communication devices where the latest published edition will govern.

B) A17.2: Guide for Inspection of Elevators, Escalators, and Moving Walks.

2.2 National Fire Protection Association (NFPA):

A) NFPA 13

B) NFPA 70: National Electrical Code.

C) NFPA 72

D) NFPA 80: Fire Doors and Windows.

2.3 Americans with Disabilities Act: Accessibility Guidelines for Buildings and Facilities.

2.4 Texas Accessibility Standard (TAS)

2.5 AWS D1.1: Structural Welding Code.

2.6 IBC: International Building Code

2.7 UPC: City of Austin Uniform Plumbing Code

2.8 IMC: International Mechanical code

PART 3 SYSTEM DESCRIPTION- Existing conditions of FC1 Elevators as follows:

3.1 Car 1

A) Type: Hydraulic; cylinder in buried casing

B) Electric Power Characteristics: 480VAC three-phase 60Hz. (Contractor to verify)

C) For elevator drive equipment: 40 HP (Contractor to verify)

D) For car lighting: 120 Volt, 60 Hz.

E) Machine room dimensions 206 X 87 X 96h (Contractor to verify)

F) Machine room door 69.5 X 82.5 (Contractor to verify)

G) Pit depth 48 (Contractor to verify)

H) Car weight: 2140 lbs.

I) Rated Net Capacity: 3000 lbs.

J) Rated Speed: 160 FPM

K) Car Interior Dimensions: 81 X 53 (Contractor to verify)

L) Cab Height: 93 inches (Contractor to verify)

M) Car gate type and operation: 42-inch single speed center opening

N) Hoistway 210 w X 76 front to back (Contractor to verify)

O) Car guide rails Omega. (Contractor to verify)

P) Distance between guide rails not measured (Contractor to verify)

Q) No. of Stops: 4

R) Travel distance 503.5 inches (Contractor to verify)

S) No. of car Openings: 1

3.2 Car 2

A) Type: Hydraulic; cylinder in buried casing

B) Electric Power Characteristics: 480VAC three-phase 60Hz. (Contractor to verify)

C) For elevator drive equipment: 40 HP (Contractor to verify)

D) For car lighting: 120 Volt, 60 Hz.

E) Machine room dimensions 206 X 87 X 96h (Contractor to verify)

F) Machine room door 69.5 X 82.5 (Contractor to verify)

G) Pit depth 48 (Contractor to verify)

H) Car weight: 2140 lbs.

I) Rated Net Capacity: 3000 lbs.

J) Rated Speed: 160 FPM

K) Car Interior Dimensions: 81 X 53 (Contractor to verify)

L) Cab Height: 93 inches (Contractor to verify)

M) Car gate type and operation: 42-inch single speed center opening

N) Hoistway 210 w X 76 front to back (Contractor to verify)

O) Car guide rails Omega. (Contractor to verify)

P) Distance between guide rails not measured (Contractor to verify)

Q) No. of Stops: 3

R) Travel distance 343.125 inches (Contractor to verify)

S) No. of car Openings: 1

NOTE: All information shall be field verified prior to ordering any equipment.

PART 4 OPERATION:

4.1 Elevator #1 and #2: Duplex Selective Collective

A) DOOR OPERATION AND CONTROL FEATURES:

1) Automatic power horizontal center opening door operation with entrance protection per ASME A17.1. 2022 (3D type). Mechanical reopening devices shall not be provided.

B) Mechanical/Electrical limit switches shall be installed in the hoistway near the terminal landings and be designed to cut off the electric current and stop the car should it run beyond either terminal landing.

C) The elevator shall be provided with a self-leveling feature that will automatically bring the car even with the landing floor. This feature shall be entirely automatic and independent of the operating device and shall correct for overtravel or undertravel. The car shall be maintained within on half inch of level with the landing at any load up to full capacity.

4.2 VISCOSITY CONTROL

A) The elevator shall be provided with viscosity control for the hydraulic oil. The oil shall be monitored for over temperature conditions and circuitry to shut down the elevator in case of over temperature shall be provided.

1) Viscosity control can be omitted if a pulse width modulation type control valve and a variable frequency drive is used. (Bucher hydraulics)

4.3 FIREFIGHTERS' SERVICE

A) Provide "Firefighter's Operation" in accordance with latest ASME A17.1.

1) Keyed for FEO K1

4.4 INDEPENDENT SERVICE and INSPECTION SERVICE

A) Provide Independent Service Operation

B) Provide top of car Inspection Operation

C) Remove power from car door during inspection operation

D) Top of the car operation will not be in effect until the top of car control is initiated

E) Provide Hoistway access switches at each entrance

PART 5 SUBMITTALS FOR REVIEW

5.1 Submit to the Project Manager: PRIOR TO START OF PROJECT

A) Shop Drawings (REQUIRED): to Include following information:

1) Location of components in the machine room. Show the arrangement so that components can be removed for repairs without disturbing other components. Arrange equipment for clear passage through doors and access doors.

2) Show design drawings and specifications for Machine Room Shunt Trip Power Module with all the required interface contacts.

3) Show electrical working clearances on machine room layout drawings.

4) Show locations for the connections of the cab lights and telephone in hoistway and/or machine room.

5) Show location of access doors, entrance doors, and frames.

6) Expected heat dissipation of elevator equipment in machine room.

7) Electrical characteristics and connection requirements.

8) Manufacturer’s Specifications for Elevator Controller.

9) Manufacturer’s Specifications for Jack assembly.

10) Show building reactions and buffer strike forces.

11) Manufacturer’s Specifications for Door/Gate operators.

12) Manufacturer’s Specifications for hall and car fixtures.

13) Samples: Illustrate cab interior finishes and car and hoistway door and frame finishes.

14) Submit the shop drawings for approval by the Elevator Project Manager

15) Submit the design drawings of the Car station, Position Indicators, Hall push button stations, Inspection key switches, Traveling lanterns, and Arrival indicators for approval by the Elevator Project Manager.

PART 6 SUBMITTALS AT PROJECT CLOSEOUT

6.1 Contract Close-out Procedures and Submittals:

A) Furnish two copies of bound maintenance manuals for each elevator. Include full maintenance and operating instructions, parts list, recommended spare parts, emergency parts inventory, sources of purchases, wiring diagrams and twelve (12) months warranty in writing for all new equipment;

B) A complete Maintenance Control Program (MCP) shall be available before the final acceptance inspection;

1) Include legible schematic of all as built wiring diagrams of installed electrical equipment and changes made in the work. List symbols corresponding to identity or markings on machine room and hoistway apparatus;

2) Provide any unique testing procedures;

3) Provide all onsite documentation;

4) Provide maintenance logs;

5) Provide repair logs;

6) Provide callback logs.

C) Supply two keys for each type of key cylinder, two hoistway door un-locking keys, and two tamper proof drivers (hex-pin) per elevator;

D) Special tools for accessing controls, electrical prints (one copy laminated with heat applied clear plastic and one electronic copy), parts catalogs, keys, proprietary components, and twelve month written warranty on equipment shall be turned over to the Elevator Project Manager upon final acceptance of the elevator.

PART 7 QUALITY ASSURANCE

7.1 Perform Work in accordance with latest published edition of ASME A17.1, AWS D1.1, NFPA 70, AISC, and as supplemented in this section

7.2 Fabricate and install door and frame assemblies in accordance with NFPA 80 and UL 10B.

7.3 Installer Qualifications:

A) The Installation Contractor shall have maintained an organization in continuous operation for the past five years installing the types of elevators listed. The Installation Contractor shall have operated an Elevator and Escalator maintenance service business in Austin, TX area with an office and warehouse facilities for a minimum of five years prior to bid date of this project. Bidders shall provide proof they have maintained an office with a store front mailing address over the last five years in Austin, TX prior to contract award.

B) The Installation Contractor shall provide documentation of the qualified personnel available at Austin, TX to ensure proper installation and fulfillment of maintenance and/or repair service required for the warranty period on a 24-hour emergency call basis. Journeyworkers (installers or mechanics), and Apprentices (helpers) shall have training in the field of Elevator and Escalator Installation. The training shall follow a nationally recognized program approved by the U.S. Department of Labor Office of Apprenticeship. To ensure that work and training is performed in a safe and consistent manner the numeric ratio of Apprentices to Journeyworkers shall be one Apprentice to one Journeyworker. At no time shall the ratio of Apprentices to Journeyworkers be exceeded.

C) The Maintenance Contractor shall submit with the bid written documentation of the Apprenticeship Program as submitted to the registration agency (U.S. Department of Labor Office of Apprenticeship) required by 29 CFR parts 29 and 30.

D) The Maintenance Contractor shall submit documentation of Journey level workers having successfully completed the requirements set forth in the Apprenticeship Program.

E) The Maintenance Contractor shall submit upon request Apprenticeship Agreement and/or documentation of the competencies achieved by each Apprentice.

F) The Maintenance Contractor’s employees shall include qualified experienced supervisory personnel to guarantee satisfactory performance of the contract. The Maintenance Contractor shall furnish a statement declaring the direct employment of the necessary personnel, organization, and local facilities to fulfill the services and conditions required under these guidelines.

G) Consideration will not be given to bids submitted by a firm or corporation who has established an unsatisfactory record of performance in connection with installation, inspection, renovation, and/or repair of Elevator Equipment on former projects. The University reserves the right to determine the competency of the Installation Contractors being considered for the award of this contract.

PART 8 DEMOLITION

8.1 All demolitions or modifications to existing systems shall be coordinated through the Owner’s Project Manager.

Demolition drawings are based on casual field observation and existing record documentations. The accuracy or exactness of the drawings is not guaranteed. The Contractor shall verify that field measurements are as shown on Drawings. The Contractor shall be responsible for reporting discrepancies to the Engineer before disturbing the existing installation.

8.2 Coordinate scope of demolition for project. Factors to include in determining scope of demolition are:

A) Minimize impact on areas outside scope of work;

B) Where existing infrastructure is no longer required due to renovation, remove as much existing conduit and boxes as possible to provide a final clean installation that is both safe and identifiable to maintain;

C) All wiring that is no longer required will be removed as part of demolition; No energized and terminated wires shall remain at conclusion of construction;

D) Items/areas requiring temporary power;

E) Updated and complete panelboard directories are required at conclusion of construction;

F) Areas impacted by outages and or phases of construction;

G) Coordinate with UT EHS prior to any coring operations or demolition for testing of hazardous materials.

8.3 The contractor is responsible for the disposal of all materials removed, including the hydraulic oil, and any soil that is not returned to backfill around the new jack.

PART 9 REGULATORY REQUIREMENTS

9.1 The elevator shall conform to the most stringent standards of either the most recently published ASME A17.1 and the latest Codes as referenced by A17.1 for manufacture and installation of elevator systems.

9.2 Texas Department of Licensing and Regulation’s adopted rules and codes for elevators.

9.3 Most recently published NFPA codes (70, 101, Etc.).

9.4 Products Requiring Electrical Connection:

A) Listed and classified by Underwriters' Laboratories, Inc.

B) Conform to ASME A17.5

PART 10 WARRANTY

10.1 Contract Closeout.

10.2 Warranty: Include coverage for elevator operating equipment and devices.

10.3 Equipment Warranty: Provide the University of Texas with a manufacturer’s written twelve-month warranty on all equipment installed.

10.4 Means to provide corrosion protection: A ten-year unconditional warranty for the means of corrosion protection and for the means of monitoring and maintaining the corrosion protection shall be included. The installer’s warranty shall cover the costs of repair, removal, and replacement of the means for corrosion protection should a failure occur within the ten-year period of coverage.

PART 11 MAINTENANCE SERVICE

11.1 The contractor shall provide routine monthly service and respond to calls for repair or entrapment twenty-four hours a day on the car that is in operation for the entire period of construction and warranty.

11.2 Contractor is to provide service and maintenance as described in The University of Texas’ maintenance specifications. This service shall be for One year on all elevators included in this specification. This Preventative Maintenance as described shall begin on the first day of the month following the Final Acceptance of the last Unit. A copy of the University of Texas’ maintenance specifications will be furnished upon request.

Documentation (Maintenance Control Program) shall be provided during the included Service Period showing dates, times, and type of Maintenance that was provided.

11.3 The Elevator contractor shall schedule, with the Project Manager, a walk-through inspection to examine the workmanship and condition and create a punch list four weeks prior to the expiration of the twelve-month service contract. Punch list items shall be completed prior to the end of service period.

11.4 Examine system components monthly. Clean, adjust, and lubricate equipment.

11.5 Include systematic examination, adjustment, and lubrication of elevator equipment; maintain hydraulic fluid levels. Repair or replace parts whenever required. Use parts produced by the manufacturer of the original equipment.

A) Provide a complete Maintenance Control Program with logbooks in the machine room.

B) Include monthly fire service, battery lowering, and emergency light Inspection and test logs.

C) Include cleaning of Hoistway sills and Car sills.

D) Include repair of elevator cab handrails.

11.6 Perform work without removing cars during peak traffic periods.

11.7 Maintain in Austin, Texas area an adequate stock of parts for replacement or emergency purposes. Have personnel available to ensure the fulfillment of this maintenance service on a twenty-four-hour emergency call basis for this maintenance period.

11.8 Perform maintenance work using competent and qualified personnel under the supervision and in the direct employment of the elevator contractor.

11.9 Maintenance service shall not be assigned or transferred to any agent or subcontractor without prior written consent of the Owner.

PART 12 PRODUCTS

12.1 MANUFACTURERS

A) Equivalent products and services by the following are acceptable:

1) Tejas Elevators Elevator Company

2) ThyssenKrupp Elevator Company

3) Otis Elevator Company

4) KONE Elevator Company

5) Metro Elevator

6) Southwest Elevator

7) Mitsubishi Elevators

8) Fujitec

9) Bucher hydraulics

10) Delaware Elevator, Inc.

11) Hydraulic Elevators, LLC

12) Hyperion Solutions

13) SmartRise

14) Virginia Controls

15) Swift

16) Elevator Controls

17) G.A.L.

18) Peelle

19) Monitor Car and Hall fixtures. (Supplement #004)

20) Innovation Car and Hall fixtures. (Supplement #004)

21) Elevator Products Corp. (EPCO). (Supplement #004)

22) Owner approved equal.

B) Substitutions:

1) The University of Texas’ Elevator Manager shall approve all substitutions.

12.2 MATERIALS

A) Steel:

1) Shapes: ASTM A 36.

2) Sheet: ASTM A 446, galvanized, stretcher leveled, Commercial Grade.

B) Stainless Steel: ASTM A 167, Type 302 or 304.

C) Aluminum: Anodizing quality.

1) Extrusions: ASTM B 221.

2) Sheet: ASTM B 209, alloy 6063.

D) Plywood: APA Structural I, Grade C-D, sanded.

E) Plastic Laminate: NEMA LD-3, General Purpose Type.

F) Paints:

1) Primer for steel: Red Oxide.

2) Primer for wood: Alkyd primer/sealer.

3) Enamel: Semi-gloss alkyd.

4) Concrete: Coatings approved for floor application

12.3 ELECTRICAL SYSTEM CHARACTERISTICS

A) Electrical Characteristics:

1) 480 volts, three phase, 60 Hz. (Contractor to verify)

2) 120 volt, single phase, 60 HZ.

12.4 ELECTRICAL COMPONENTS

A) Boxes, Conduit, Wiring, and Devices: Required by NFPA 70 and ASME A17.5.

B) All wiring shall be run inside proper conduit. Flexible conduit is only allowed in lengths of three (3) feet or shorter when attaching to a device that requires periodic adjustment. Open runs of wire other than traveling cable and cables to the car door safety devices shall not be accepted. Do not use flexible metal conduit as a grounding conductor.

C) Spare Conductors: Include ten extra conductors and three extra shielded pairs (audio/video/Ethernet) in traveling cables.

D) Include wiring and connections to elevator devices remote from hoistway and between elevator machine rooms.

Provide additional components and wiring to suit machine room layout.

E) Provide (New) Demarcation box, Unity Manufacturing Type 1-UL 50 and 50E with optional back panel and standard coin latch (or equivalent if approved by Elevator Manager) measuring 24 x 24 x 8 5/8 inches equipped with:

1) Terminals for connecting fire alarm inputs

2) A separate branch circuit supplying one (1) 110VAC duplex receptacle

3) Terminals for connection to card reader security

4) Terminals for connection of car telephone

5) Terminations of data cables required for card reader security, and for remote monitoring of elevator controls

F) Locate all electrical equipment, except earthquake protective devices conforming to the requirements of ASME A17.1 Rule 8.4.10.1.2, four feet above the pit floor. If any equipment is located less than four feet, it shall be:

1) Weatherproof (NEMA 4)

2) Wiring shall be identified for use in wet locations in accordance with the requirements in NFPA 70.

G) All Car Junction boxes shall be installed on the car top in an accessible location where they don’t interfere with refuge space or space needed to stand to perform maintenance.

H) All wiring shall be installed in accordance with the current adopted NFPA 70, ASME A17.1, and A17.5.

I) Provide car top lighting to provide a minimum of ten foot-candles at the car top inspection station, hoistway interlocks, hoistway door motors, car gate operators, and car gate switches when used in conjunction with the hoistway lighting. The switch is to be accessible while standing on the access landing.

PART 13 OPERATIONAL CONTROLLER:

13.1 Non-proprietary microprocessor-based elevator controller. Controller enclosures shall be NEMA 1

A) The controller shall use circuit breakers for overcurrent protection of the various circuits that originate from the controller

B) The controller shall have a light fixture that automatically operates any time the cover is open. The illumination from this light can be added to the machine room lighting to obtain the code requirement in front of the controller.

C) The controller shall have a duplex receptacle inside the enclosure.

D) The controller shall have a graphical user interface built into the control board.

E) The controller shall have the ability to be accessed remotely over an Ethernet connection. Optional connections through WiFi or direct connection to the controls with special tools are allowed, but Ethernet is required.

13.2 Drive Control utilizing soft start technology or variable frequency drive.

13.3 Landing System shall be compatible with controller selected.

1) The elevator shall be provided with a self-leveling feature that will automatically bring the car level to the floor landings. This feature shall be entirely automatic and independent of the operating device and shall correct for over travel or under travel. The car shall be maintained within one half inch of level with the landing at all loads up to capacity.

PART 14 ADDITIONAL FEATURES:

14.1 Provide machine room monitoring system

A) The monitoring shall be capable of providing system status, car location, travel direction, operating mode, door operation indication, dispatching ETAs, and security status.

B) The monitoring system shall be capable of remotely registering calls for the car and hall. Configuration of hall and car call restrictions in support of building security (for example: car to lobby) shall be provided by the system. The monitoring system shall be capable of implementing security overrides if required.

C) The monitoring system shall be capable of setting the group to flood operation mode when indicated by a sensor in the pit.

D) The monitoring system shall be capable of initiating recall of any car in the group to a selected floor and of controlling door operation of that car at the selected floor.

E) The elevator controller shall support an interface for communication and interaction via a separate application program running on a Windows PC. This application shall communicate with the controller and allow the user to view real-time elevator status information, initiate and facilitate setup and adjustment procedures, and provide advanced troubleshooting capabilities. The PC application shall be designed specifically for elevator applications and shall graphically and dynamically display information from the controller.

1) A PC application and elevator controller shall support remote connection via intranet.

2) A mechanism shall be provided to prevent the unauthorized alteration of elevator configuration parameters.

14.2 Reporting

A) A local Ethernet client/server based report collection and generation application shall be available. Based on historical data collected by the server, the report application shall provide hall call performance, hall call analysis, traffic analysis, hall call log, car call log, event log, emergency log, maintenance log, and percent in service reports.

B) The report application shall be capable of emergency notification and report distribution through email service.

C) The controller shall maintain an event log to record events or faults. They shall be displayed in chronological order and time stamped for analysis and/or review. Data displayed shall include the type of event or fault, the date and time it occurred, and the position of the car and status of inputs and outputs at the time of the occurrence. The event log shall be able to be saved and reviewed offline via the PC application.

14.3 Communication

A) Communication between the elevator controller and the PC application shall be via a standard 100 base T TCP/IP Ethernet network connection. The elevator controller shall be compatible with standard networking equipment (cables, hubs, switches, and routers etc.).

14.4 Building Management System Interface

A) An interface to a Tridium technology client Building Management System shall be available. This interface shall allow the management system to view car location, call status, and door operation. The interface shall allow the management system to set any of three levels of demand-response operation, each of which shall specify a set of cars to continue running in response to curtailed energy availability or if the building owner is voluntarily reducing energy demand. The interface shall allow selected cars to be removed from and/or returned to service as desired through the building management system.

14.5 Basic Security

A) As an integral part of the controller, the Controls must include all necessary network hardware to allow communication between the Embedded Monitoring Interface (EMI) and the Central Monitoring Station (CMS).

The network connection in the control must be compatible with a 10Base-T connection to a computer network supporting TCP/IP protocol, which will allow a network cable to be plugged directly into the control system. The contractor will be responsible for providing all hardware equipment and devices required for communication between the elevator controller and the University’s main CMS remote monitoring computer through Ethernet connections. The connections must allow for both normal polling of Elevator status and immediate communication of an Emergency Status.

PART 15 PUMP UNIT

A) Motor, Pump, Valve, Fluid Tank, Hydraulic Fluid, Jack unit.

1) Power Unit (New) (Oil Pumping and Control Mechanism)

a) Pump and valves: Specifically designed for elevator application; the pump shall be of the positive displacement type. Pump/valve assembly shall be suspended within the oil reservoir by a rubber isolated suspension system to allow easy removal of components without draining oil from the reservoir.

b) A silencer shall be installed in the oil reservoir interior. The silencer shall not contain degradable parts.

c) Pump unit shall be mounted on isolation pads to limit the vibration and sound transmitted to the building structure. Mount motor and pump unit on vibration and acoustic isolators, equal to type ND by Mason Industries, and securely fasten to building supports to prevent lateral displacement.

d) Oil Control Valve: shall be a unitized design that contains the up and down portions, high-pressure relief valve, and check valve in a single housing. Valve shall be compatible with viscosity control.

Welded manifolds with separate valves to accomplish each function will not be permitted.

e) Viscosity control shall be provided.

i) Viscosity control can be omitted if a pulse width modulation type control valve and a variable frequency drive is used. (Bucher hydraulics)

f) The oil shall be monitored for over temperature conditions and circuitry to shut down the elevator in case of over temperature shall be provided.

g) Power unit shall be guarded to protect against accidental contact of the moving parts.

h) Fill system with new petroleum based hydraulic oil that includes an additive package to prevent oxidation, corrosion, and wear. The oil shall have a cleanliness rating meeting the ISO target of 17/14/11 or better. Vegetable based or blended oils are not acceptable.

i) The power unit shall have secondary containment for the full capacity of the hydraulic oil should the tank develop a leak.

1. Hydraulic Elevator Pump units require a secondary containment system. The system shall be capable of containing the entire contents of the hydraulic system in case of a catastrophic failure of the tank. Containment systems may use a pan, or an oil proof sealant applied to the floors and the walls. Secondary Containment systems shall be designed to hold the entire system capacity.

Systems shall not hamper the repair or maintenance of the Pump unit or require modification to perform maintenance or repair to the Pump unit.

PART 16 LUBRICATION

16.1 Grease Fittings: For lubricating bearings that require periodic lubrication.

16.2 Lubrication Points: Visible and easily accessible.

PART 17 CAR STRUCTURAL FABRICATION: (Not used)

PART 18 CAB FABRICATION:

18.1 Provide a new swing panel or modify the existing to accept a new car station. (Supplement #004)

PART 19 CAR OPERATING PANELS using LED LAMPS

19.1 Provide a vandal-resistant Car Operating Panel for each car, designed to the University of Texas’ specifications.

(Supplement #004)

19.2 Position all devices to comply with ADA, TAS, and latest published ASME A17.1 code.

19.3 All lettering on car panel shall be engraved and filled. Silk screened lettering is not acceptable.

19.4 The car operating panel shall be provided with buttons for activating the audible alarm and telephone.

19.5 Include a service cabinet at the bottom of the primary car panel containing:

A) Integral certificate window/hinged door Northeast J200 cam lock

B) Independent service switch. (Toggle)

C) Access Enable switch. (Keyed EPCO EN-2)

D) Fan or blower switch. (2 speed Toggle)

E) Light switch. (Toggle)

F) Stop switch. (Toggle or push pull)

G) Emergency light test button/switch

H) Two holes for future switches capped

I) 120 V, 15 Amp GFCI convenience receptacle

19.6 ADA Flush Telephone:

A) Integral with car operating panel.

B) Compatible with the university’s POTS lines

19.7 Integral Fire Service Operation Cabinet with Code required features

A) Operating features as required by A17.1 2.27.3.3

B) Fire service operating instructions shall be engraved and filled on the inside of Fire Service Operation Cabinet door.

19.8 Elevator identification number one half (½) inch high, and capacity one quarter (¼) inch high, engraved and filled. Locate below emergency light.

19.9 Emergency lights integral to car-operating panels.

19.10 CAR PANEL DESIGN, from top to bottom: (Supplement #004)

A) Digital Car position indicator

B) Emergency light

C) Elevator identification number

D) Capacity of Elevator

E) Firefighters’ Service Phase II Panel and Operating Instructions as required by ASME A17.1. Verify latest ASME A17.1 wording. Fire Service Instructions shall be engraved on the inside of the Firefighters’ Service Cabinet Door.

F) Telephone- speaker grille and microphone

G) Car call buttons

H) Door open and door close buttons (highest operable part to be located below 38 inches AFF)

I) Alarm button and telephone activation button (lowest operable part to be located above 34 inches AFF)

J) Provide Removable Blank for Card Reader. The future card reader shall be placed in the area indicated and meet the ADA height requirements. The area where the future card reader will be installed in the Car Panel must be self-contained and isolated from the Elevator wiring within the car panel. The card reader must be installed using a cover panel to be removed and replaced from the finish side of the car panel using tamperproof screws. The height of this reader must be incompliance with all ADA and TAS requirements. Card reader shall be bypassed anytime the Elevator is in Fire Service Mode.

K) Combination service panel door and Certificate holder (supplement #004)

L) Utilize LED lamps in all panel lights.

19.11 The car operating panel cover shall be hinged on one edge adjacent to cab wall and held in place by eight EPCO 1 keyed locks. Service panel cam lock shall be keyed for Northeast J200 key. Fire service shall be keyed for FEO K1 key.

PART 20 CAR TOP INSPECTION STATION: (New)

20.1 Provide a device to operate the elevator from the top of the car during adjustment, inspection, maintenance, and repair.

20.2 Operating means shall conform to the following:

A) Device shall be of the continuous pressure type;

B) The device shall be accessible while standing on the access landing;

C) The device shall contain the car top Stop Switch, car top Inspection Switch, car top Light Switch, and the run buttons requiring operation with both hands;

D) Operate the car at a speed not exceeding 150 ft/min;

E) Operate the car per ASME A17.1 2.26.1.4;

F) Device shall be used only for the purpose of adjustment, inspection, maintenance, and repair of the elevator or hoistway equipment;

G) Provide an audible signal when the elevator is on Firefighter’s Service Phase I operation.

20.3 Provide a GFCI duplex receptacle on the car top.

PART 21 CAB ENTRANCE:

21.1 Door Operation and Control Features: (New)

A) A (New) Door Operator shall be furnished and installed.

B) A (New) Car door contact shall be furnished and installed.

1) Door movements shall be electrically cushioned at both limits of travel. Direct drive geared operators, A.C.

controlled units with oil checks, Stationary door vane or other deviations of these are not acceptable.

2) The door operator must be fully compatible with the operational controller selected and approved.

3) The door operating mechanism shall be arranged for manual operation in the event of a power failure.

4) Doors shall automatically open when the car arrives at the landing.

5) Nudging: Shall be provided.

6) The Door operator shall not require proprietary tools for adjusting.

7) The door operator must be fully compatible with the operational controller selected and approved.

C) The limitations on the closing of the doors shall meet ASME A17.1 2022 section 2.13.4

D) A door protection system meeting shall meet ASME A17.1 2022 section 2.13.5 shall be provided. A mechanical reopening device shall not be provided.

PART 22 ACCESSIBILITY PROVISIONS

22.1 Conform to State of Texas Accessibility Standards (TAS) for provisions for the disabled:

A) The highest operational part of any button in the control panel shall be located a maximum of 48 inches above floor;

B) Emergency buttons (Door open, door close, phone, and alarm) shall be located within a reach range between thirty-five and thirty-eight inches above the finished floor

C) The telephone shall be a hands-free model;

D) Braille: All car control buttons shall be designated by Braille and raised standard alphabet characters for letters, Arabic symbols for numbers, or standard symbols as required in ASME A17.1;

E) The handrail if provided shall conform to TAS sections 505.4, 505.5, 505.7, 505.8 and 505.9;

F) The audible signaling device shall have a sound pressure rating of not less than 80 dBA nor greater than 90 dBA at 10 feet. It shall be located to be heard inside the car and outside the hoistway. For elevators with a travel greater than one hundred feet there shall be an audible device mounted on the car and a duplicate device mounted at the designated level. The device shall be capable of operating for a minimum of four hours if normal power fails;

G) Braille on hoistway doorframes: Provide (New) two-inch-high raised numerals with Braille on both sides of each landing jamb to identify landing number, Tactile characters on signs shall be located 48 inches (1220 mm) minimum and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character;

H) Elevator Identification shall be provided on the doorjambs at the designated and alternate landings directly below the floor-numbering placard and shall be located 48 inches (1220 mm) minimum and 60 inches (1525

mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

PART 23 HOISTWAY ENTRANCES:

23.1 Hoistway Doors: (Reuse)

23.2 Hoistway Door Frames: (Reuse)

23.3 Sills: (Reuse)

23.4 Install (New) SEES Enforcer door gibs on the hall doors

23.5 Install (New) SmartTork™ Inc. hoistway door closers on the hall doors

23.6 Install (New) door hanger roller assemblies with integral hoistway door safety retainers

23.7 Door tracks: (New) Provide new hall door tracks.

23.8 Interlocks: (New) interlock that has been tested as required by the appropriate code. Interlocks shall bear Underwriters’ Laboratories “B” label of approval.

23.9 Hoistway door unlocking devices (New) shall be provided on all floors and comply with ASME A17.1. These devices shall permit authorized personnel to gain access to the hoistway when the elevator car is away from the landing.

23.10 Install new floor indicator braille plates at each landing.

PART 24 LANDING CONTROLS (New)

24.1 Landing Buttons: Surface Mount Vandal-resistant stainless steel Illuminating type, with indications required by

ASME A17.1.

24.2 Hall button covers are to be engraved and filled with pictograph detailing “In Case of Fire Elevators Are Out of Service”. ASME A17.1 Fig 2.27.9

24.3 Provide Hoistway Access Switches at the top and bottom landings

A) Switches are to be mounted in separate enclosures adjacent to and within twelve inches of the doorjamb at a height between sixty-six and seventy-eight inches above the finished floor. Alternate location must be approved by the Elevator Manager.

B) Access key switch shall be operated by an EPCO EN2- Key.

24.4 All screws to be Oval Head Hex-Pin tamper proof.

24.5 The covers shall have countersunk mounting holes.

PART 25 FINISHES

25.1 Existing fascia, door frame supports, rails, brackets, spreader beams, pipe stands, or other metal surface in the hoistway that shows signs of rust or corrosion shall be cleaned of rust, oil, or grease, wiped clean with solvent and painted with a rust encapsulating paint made for direct to metal application.

25.2 Machine Room Components shall have their surfaces cleaned and degreased before applying the appropriate touch up paint from the manufacturer.

25.3 Galvanized Surfaces: Clean with neutralizing solvent; paint one coat.

25.4 Aluminum: Mill finish.

25.5 Wood Surfaces not exposed to Public View: One coat primer, one coat enamel.

25.6 Stainless Steel: #4 Satin.

PART 26 MACHINE ROOM AND PIT FLOORS.

26.1 Clean and paint the machine room and pit floors.

1) Paint the machine room floor below the grating, pit floor, sump hole with a chemical resistant non-slip paint.

Properly clean and prepare the surfaces using the manufacturer’s instructions for proper adhesion of the new coating. Floor coating shall be equal to or better than POX-A-Crete® Heavy-Duty Epoxy Resurfacer.

B) Paint pit walls to the height of the lowest landing sill with a suitable chemical resistant paint compatible in color and texture with the floor coating.

PART 27 SECONDARY, MACHINERY AREAS, AND HOISTWAY EQUIPMENT

27.1 Paint all newly installed equipment and any unpainted existing equipment with a rust encapsulating type direct to metal type paint. Including the jack, pit channels, buffer stands springs, rail brackets, etc..

PART 28 EXECUTION

28.1 SITE VISIT

A) Examine work of other Divisions that…