CT1
CT2
8" EQUALIZER
VFD-CT1
VFD-CT2
(E)1-1/4"
10"CS
8"CS
(E)MAKEUP
10"CR
8"CR
3" OVERFLOW
2" DRAIN
WITH VALVE
BELOW
OVERFLOW
8" CS
2" DRAIN
WITH
VALVE
EXISTING
DRAIN
(R)CT
(R)CT
(R)8" CWS
(R)8"
EQUALIZER
PIPE
(E)1-1/4"
(R)10"CWS
(R)8"CWS
(E)MAKEUP
ASSEMBLY
(R)10"CWR 3
(R)8"CWR 1
EXISTING VENT PIPING
FROM BOILER ROOM
(R)3" OVERFLOW
(R)2" DRAIN
BELOW
OVERFLOW
(R)2" DRAIN
EXISTING
DRAIN
S E
N S
I T
I V
E
B
U T
N C
L A
S S
I F
I E
D
S
B U
P
R O
P E
R T
Y
O
F
T
H E
I T
D
S
A
T E
S
G
O V
E R
N M
E N
T
F
O R
F F
I C
I A
L
U
L Y
O
N
M
O V
E
T
H I
T
I C
E
P
R O
P E
R L
S
T R
C
U M
E N
W
H E
N
N
O
L O
N G
E
D E
D
General Services Administration
Public Buildings Service
Great Lakes Region
Design and Construction Division
John C. Kluczynski Federal Building
230 South Dearborn Street
Chicago , IL 60604
Columbus, OH, 43215
Kinneary U.S. Courthouse
100% Construction Documents
04-17-2019
ROH00760OH0046ZZ
COOLING TOWERS
GS-05P-17-SC-D-0010
47PF00-18-F-0076
A
M
Cooling Tower Replacement
ROH00760
KORDA
KORDA
85 Marconi Boulevard
MARK DATE DESCRIPTION
PROJECT NUMBER:
CHECKED BY:
DESIGNED BY:
1650 WATERMARK DRIVE
COLUMBUS, OHIO 43215
SUITE 200
DRAWN BY:
2017-0210
Eric Stephens
Dave Balch
Dan Edwartoski
H202
Floor Plan
Mechanical
1/4" = 1'-0"
0 1 2 4
Demolition
1/4" = 1'-0"
0 1 2 4
New Work
NEW EQUIPMENT DATA:
CT1 COOLING TOWER (COUNTER FLOW)
CAPACITY: 780 GPM AT 96.2°F EWT. 86°F LWT. 78°F WB.
CENTRIFUGAL FAN (FORCED DRAFT): 40 HP AT 480 VOLT 3 PHASE.
PONY MOTOR: 10 HP AT 480 VOLT 3 PHASE.
BASIN HEATER: 10KW, 480 VOLT 3 PHASE, PROTECTION TO -20°F.
PROVIDE STAINLESS STEEL WATER BASIN.
UNIT DIMENSIONS: LENGTH:17'-8". HEIGHT:11'-3". WIDTH:7'-10".
CT2 COOLING TOWER (COUNTER FLOW)
CAPACITY: 780 GPM AT 96.2°F EWT. 86°F LWT. 78°F WB.
CENTRIFUGAL FAN (FORCED DRAFT): 40 HP AT 480 VOLT 3 PHASE.
PONY MOTOR: 10 HP AT 480 VOLT 3 PHASE.
BASIN HEATER: 10KW, 480 VOLT 3 PHASE, PROTECTION TO -20°F.
PROVIDE STAINLESS STEEL WATER BASIN.
UNIT DIMENSIONS: LENGTH:17'-8". HEIGHT:11'-3". WIDTH:7'-10".
NEW WORK CODED NOTES:
1. PROVIDE NEW 8" EQUALIZER LINE BETWEEN CT1 AND CT2.
2. PROVIDE NEW SELF REGULATING HEAT TRACE (8 W/FT, 120V/1PH) ON
ALL CS PIPING AND ON CR PIPING.
3. INSULATE ALL CS AND CR PIPING BETWEEN COOLING TOWERS AND PIT
FLOOR. PROVIDE EMBOSSED ALUMINUM COVER.
4. PROVIDE VFD FOR 40 HP MOTOR. INSTALL IN BASEMENT BOILER ROOM.
COORDINATE VOLTAGE AND PHASE WITH NEW ELECTRICAL
DISCONNECTS AND SWITCHES.
5. NEW ISOLATION VALVE IN VERTICAL PORTION OF CR PIPE.
6. PROVIDE NEW HEAT TRACE CONTROLLERS IN THIS LOCATION.
CONNECT TO (2) EXISTING ELECTRICAL CIRCUITS. MAKE CONNECTION
TO BUILDING AUTOMATION SYSTEM TO PROVIDE ALARM IN THE EVENT
OF CABLE FAILURE.
7. PROVIDE NEW COOLING TOWER WATER LEVEL CONTROLLER IN THIS
LOCATION. MAKE CONNECTION TO NEW LEVEL INDICATOR IN TOWER
AND TO EXISTING MAKE UP WATER VALVE.
8. NEW ISOLATION VALVE IN HORIZONTAL PORTION OF CS PIPE.
DEMOLITION CODED NOTES:
1. REMOVE CS LINES AND CR LINES BACK TO POINT WHERE THEY
PENETRATE PIT FLOOR. LEAVE ENOUGH EXISTING PIPE EXPOSED FOR
CONNECTION TO REPLACEMENT PIPES.
2. REMOVE COOLING TOWER DRAIN AND OVERFLOW PIPES.
3. DISCONNECT MAKEUP WATER LINE FROM COOLING TOWER. EXISTING
MAKEUP VALVE ASSEMBLY TO REMAIN FOR REUSE. REMOVE WATER
LEVEL INDICATOR AND CONTROLS.
4. REMOVE ALL INSULATION FROM EXISTING CS AND CR PIPING
(APPROXIMATELY 120 LINEAR FEET). REMOVE HEAT TRACE.
5. REMOVE COOLING TOWERS.
6. REMOVE CR VALVE IN VERTICAL PORTION OF PIPE.
7. REMOVE TWO HEAT TRACE CONTACTORS AND ASSOCIATED CABLE.
8. REMOVE COOLING TOWER WATER LEVEL CONTROLLER.
NOTE: ALL SYMBOLS NOT NECESSARILY USED
HVAC SYMBOLS LIST
EXISTING TO REMAIN
EXISTING TO BE REMOVED
EXISTING TO BE ABANDONED
SPECIALTIES
GENERAL
MISCELLANEOUS
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CS
CR
(E)
(R)
(AB)
SOLENOID VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
PLUG VALVE
GLOBE VALVE
ISOLATION VALVE - SEE PROJECT
EXPANSION VALVE
CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
BALANCE/SHUT-OFF VALVE
3-WAY CONTROL VALVE
2-WAY CONTROL VALVE
VALVES
RISE
DROP
CAP
VALVE IN RISER/DROP
CONNECT TO EXISTING
OC
FOR COORDINATION OR REFERENCE
DENOTES ITEM PROVIDED BY
ANOTHER CONTRACTOR, SHOWN
SPECIFICATIONS FOR REQUIREMENTS
GATE VALVE
PIPING
GENERAL NOTES:
1. PRIOR TO BID, THE CONTRACTOR SHALL MAKE A SITE VISIT TO VERIFY
EXISTING CONDITIONS AND SCOPE OF DEMOLITION.
2. COORDINATE DEMOLITION OF HVAC EQUIPMENT WITH ELECTRICAL
CONTRACTOR AND TEMPERATURE CONTROLS CONTRACTOR.
3. PROJECT SHALL TAKE PLACE IN COOLING OFF SEASON.
CT1
NEW
HEAT TRACE
CT2
T
AI
SUMP
TEMP
T
AI
V
F
D
BI
AO
BO
V
F
D
BI
AO
BO
EQUALIZING LINE
SHUT-OFF VALVE
TYP. 2
TOWER FAN
T
AI
HEAT TRACE AND HEAT TRACE CONTROLS ARE NEW.
SYSTEM IS SELF REGULATING BASED ON INTEGRAL AMBIENT
AIR TEMP. SENSOR. CONTROLLERS SHALL PROVIDE AN
ALARM TO THE BAS IN THE EVENT OF HEAT TRACE FAILURE.
T
AI
TO MECH ROOM
TOWER FAN
IN MECH CORRIDOR IN MECH CORRIDOR
N.T.S.
BINARY INPUT TO DDC SYSTEM
ANALOG INPUT TO DDC SYSTEM
BINARY OUTPUT FROM DDC SYSTEM
ANALOG OUTPUT FROM DDC SYSTEM
BACNET INTERFACE FROM EQUIPMENT
BO
BI
AO
AI
BAC
TEMPERATURE CONTROL
T
AMBIENT TEMP SENSOR
AI
M
C
C
IN MECH ROOM
M
C
C
IN MECH ROOM
BOBO
AO
AutoCAD SHX Text A
AutoCAD SHX Text Cooling Tower Area Floor Plan
AutoCAD SHX Text B
AutoCAD SHX Text Cooling Tower Area Floor Plan
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text Cooling Tower Temp. Control