Cooling Tower Replacement
John P. Kinneary US Courthouse Columbus, Ohio
RFP 47PF0019R0099
Pre‐Bid Walkthrough Q&A and Attendance Sheets
These answers are just clarifications. There are no changes to the specifications.
1. Contractor asked about the two new cooling towers, do they have modulating dampers in them? No dampers.
2. Contractor asked about extent of the galvanized vs. stainless steel aspects of the cooling towers, can we point him to the section that describes the make up? Spec 23 65 13 2.01 C “Water‐contacted metal components in the basin shall be constructed of Type 304 stainless steel. All other steel components shall be heavy gauge polymerized G‐210 galvanized steel.
3. They asked if you had contacted the manufacturer regarding the units, they would like to know who your contact was so they can get the pricing correct. Tony DeCrescenzo at ElitAire 614.360.1330