4-Exhibit 04 - Terminal 4 Concessions Utility Matrix.pdf
PDF 166 KB Posted
- Solicitation number
- 0485-2026-07-RFP-230932
- Issued by
- Los Angeles County, California
About this file
This is a Concessions Utility Matrix exhibit prepared for Los Angeles International Airport's Terminal 4 concessions agreement package. The document outlines the utility infrastructure and service requirements for concession operations in both pre-security and post-security areas of Terminal 4. The matrix details the locations, capacities, and technical specifications of available utilities including electrical service, water supply, wastewater connections, HVAC systems, and data/communications infrastructure that prospective concessionaires must understand and account for in their operational planning and bid proposals.
The utility matrix serves as a critical planning tool for bidders to assess the feasibility and costs associated with establishing concession operations at designated locations within Terminal 4. By providing comprehensive information on utility availability, connection points, capacity limitations, and service characteristics, the document enables qualified individuals and firms to develop accurate proposals for developing, managing, and operating concessions at the airport. This supporting exhibit ensures that all potential concessionaires have access to the same baseline infrastructure information necessary to prepare competitive and realistic bids for the Terminal 4 concessions agreement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Supply Air from
Building System
(Note 7)
Supply Air from
Building System
POC Size (Note
10)
Outside Air
Makeup Air
Duct Stubout to
Building Exterior
(Note 11)
Makeup Air
Duct Stubout to
Building Exterior
POC Size
Grease Exhaust
Duct Stubout to
Building Exterior
Grease Exhaust
Duct Stubout to
Building Exterior
Dishwasher
Exhaust Duct
Stubout to
Building Exterior
Dishwasher
Exhaust Duct
Stubout to
Building Exterior
POC Size
General Exhaust
Duct Stubout to
Building Exterior
Clothes Dryer
Exhaust Vent
Clothes Dryer
Exhaust Vent
POC Size
HHWS/HHWR
Stubout for
Tenant Supplied
Fan Coil Unit
HHWS/HHWR
Stubout for
Tenant Supplied
Fan Coil Unit
POC Size
CHWS/CHWR
Stubout for
Tenant Supplied
Fan Coil Unit
CHWS/CHWR
Stubout for
Tenant Supplied
Fan Coil Unit
POC Size
Flow and BTU
Meter for CHWS and HWS
Kitchen Exhaust
Fan Roof
Curbs/Pad
General Exhaust
Fan Roof
Curbs/Pad
G101 - TER04.L01TA019
CONCESSION
1,371 SF NO YES 10"x10"
.5CFM/FT²
(NOTE 8)
600 CFM 30"x18" NO - NO - NO NO - YES 3/4"
1 TON PER
200ft²
1-1/4" BY TENANT BY TENANT NO
TER04.L03CA013
TRAVEL ESSENTIALS
Existing Currency
Exchange
130 SF NO
G301 - TER04.L03CA021
RETAIL CONCESSION
1,270 SF NO YES
16" DIA. .5CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 1"
1 TON PER
200ft²
1 1/2" BY TENANT NO NO
G302 - TER04.L03CA022 COFFEE CONCESSION 937 SF NO YES 18" DIA.
.5CFM/FT²
(NOTE 8)
6,000CFM 20"x24" NO - NO - NO NO - YES 1"
1 TON PER
200ft²
1-1/4" BY TENANT BY TENANT NO
G303 - TER04.L03.CA028 BAR CONCESSION 602 SF NO YES 14" DIA.
.5CFM/FT²
(NOTE 8)
6,000CFM 20"x24" NO - NO - NO NO - YES 1"
1 TON PER
200ft²
1-1/4" BY TENANT BY TENANT NO
G305 - TER04.L03CA011 RETAIL CONCESSION 506 SF NO YES 48"x48" (VIF) - NO - NO - NO - NO NO - YES 3/4" (VIF) - - BY TENANT NO NO
G306 - TER04.L03CA006
FULL SERVICE
RESTAURANT
2,015 SF YES PARTIAL (E) VIF - 2,575 CFMF (VIF) (E) VIF YES NO NO - YES 1" (VIF) - 1-1/2" (VIF) BY TENANT VIF VIF
G307 - TER04.L03CA008 RETAIL CONCESSION 1,184 SF NO YES
10" DIA. (VIF)
8" DIA. (VIF)
- NO - NO - NO - NO NO - YES 1" (VIF) - 2" (VIF) BY TENANT NO NO
G304 -
TER04.L03CA001.01
QSR CONCESSION 1,004 SF YES YES 12" DIA.
.25CFM/FT²
(NOTE 8)
600 CFM 24"x24" YES 26"x26" NO - NO NO - YES 1"
1 TON PER
200ft²
1-1/4" BY TENANT YES NO
G308 - TER04.L03SA002 COFFEE CONCESSION 712 SF NO YES -
.25CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - NO N/A
1 TON PER
200ft²
1-1/4" BY TENANT NO NO
G310 - TER04.L03SA003 RETAIL CONCESSION 1,249 SF NO YES 16" DIA.
.25CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
200ft²
1-1/4" BY TENANT NO NO
G311 - TER04.L03SA004 RETAIL CONCESSION 1,470 SF NO YES 16" DIA.
.25CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 1"
1 TON PER
200ft²
1-1/2" BY TENANT NO NO
G313 -
TER04.L03SA0015.01
QUICK SERVICE
RESTAURANT
1,510 SF YES YES (2) 12" DIA.
.25CFM/FT²
(NOTE 8)
600 CFM 26" X 26" NO - NO -
YES
26"x26"
NO - YES 3/4"
1 TON PER
200ft²
1" BY TENANT YES YES
G312 -
TER04.L03SA0015.02
QUICK SERVICE
RESTAURANT
788 SF YES YES 14" DIA.
.25CFM/FT²
(NOTE 8)
NO
600 CFM
26" X 26" NO
NO -
YES
26"x26"
NO - YES 3/4"
1 TON PER
200ft²
1" BY TENANT YES YES
G309 - TER04.L03SA0022
& TER04.L03SA0022.01
RESTAURANT W/
SEATING
3,344 SF YES YES 24"x24"
.4CFM/FT²
(NOTE 8)
6,000 CFM 24" x 24" NO
NO -
YES
26"x26"
NO - YES 1"
1 TON PER
200ft²
1-1/2" BY TENANT YES YES
G314 - TER04.L03SA0024.01
COFFEE/ BAR
CONCESSION
700 SF NO YES 10" DIA.
.5CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
200ft²
1-1/4" BY TENANT NO NO
TER04.L03CA027 CONCESSIONS SEATING 3,911 SF NO YES -
.5CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - NO - NO - NO NO NO
TER04.L03SA015 CONCESSIONS SEATING 4,867 SF NO YES -
.5CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - NO - NO - NO NO NO
TER04.L03SA024 CONCESSIONS SEATING 2,762 SF NO YES -
.5CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - NO - NO - NO NO NO
TER04.L04SA011 GHOST KITCHEN LEVEL 4 3,144 SF YES YES (2) 14"x12"
.4CFM/FT²
(NOTE 8)
6,000 CFM (2) 26"x26" - - NO -
YES
(2) 26"x26"
NO - YES (2) 3/4"
1 TON PER
200ft²
(2) 1-1/2" BY TENANT YES YES
TER04.L02CU012 Dry Storage 447 SF NO YES -
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1" NO NO NO
TER04.L02SA029 Wet Storage 138 SF NO YES 8" DIA.
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1" NO NO NO
TER04.L02SA047 Wet Storage 472 SF NO YES 8" DIA
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1" NO NO NO
TER04.L02SA056 Wet Storage 353 SF NO YES 8" DIA
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1" NO NO NO
TER04.L02SA057 Wet Storage 364 SF NO YES 8" DIA
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1" NO NO NO
TER04.L04SA014 Dry Storage 205 SF NO YES 8" DIA.
TER04.L04SA015 Wet Storage 1,361 SF NO YES TBD
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1-1/4" NO NO NO
TER04.L04SA020 Dry Storage 2,493 SF NO YES TBD
.15CFM/FT²
(NOTE 8)
NO - NO - NO - NO NO - YES 3/4"
1 TON PER
500ft²
1-1/2" NO NO NO
HEADHOUSE LEVEL 1
HEADHOUSE LEVEL 3
CONCOURSE LEVEL 3
COMMON AREA SEATING AT LEVEL 3 CONCOURSE
STORAGE
Issued 05/12/2025Utility Provisions for AA T4/5MP Concession Spaces
ROOM NO. CONCESSION TYPE AREA COOKING
MECHANICAL
CONCOURSE LEVEL 4
EXHIBIT 4
Supply Air from
Building System
(Note 7)
Supply Air from
Building System
POC Size (Note
10)
Outside Air
Makeup Air
Duct Stubout to
Building Exterior
(Note 11)
Makeup Air
Duct Stubout to
Building Exterior
POC Size
Grease Exhaust
Duct Stubout to
Building Exterior
Grease Exhaust
Duct Stubout to
Building Exterior
Dishwasher
Exhaust Duct
Stubout to
Building Exterior
Dishwasher
Exhaust Duct
Stubout to
Building Exterior
POC Size
General Exhaust
Duct Stubout to
Building Exterior
Clothes Dryer
Exhaust Vent
Clothes Dryer
Exhaust Vent
POC Size
HHWS/HHWR
Stubout for
Tenant Supplied
Fan Coil Unit
HHWS/HHWR
Stubout for
Tenant Supplied
Fan Coil Unit
POC Size
CHWS/CHWR
Stubout for
Tenant Supplied
Fan Coil Unit
CHWS/CHWR
Stubout for
Tenant Supplied
Fan Coil Unit
POC Size
Flow and BTU
Meter for CHWS and HWS
Kitchen Exhaust
Fan Roof
Curbs/Pad
General Exhaust
Fan Roof
Curbs/Pad
HEADHOUSE LEVEL 1
Issued 05/12/2025Utility Provisions for AA T4/5MP Concession Spaces
ROOM NO. CONCESSION TYPE AREA COOKING
MECHANICAL
1 11
BTU FU
2 12
BT HWS
3 13
CHWS MP
4 14 CW MUA
5 15
CW NG
6 16
DHW ROOF STUBOUT
7 17
EA SA STUBOUT
8 18
EF SS
9 19
10 20
Maximum Capacity of 10 Fixture Units
HOT WATER SUPPLY
NOTES
Coffee & Bar concepts likely will NOT require full cooking (hoods & rated kitchen) provisions. However, until actual unit allocation & retail category mix is fully developed, LAWA reserves the right to provide cooking infrastructure.
BY TENANT
FROM ROOF TO TENANT SPACE & CAPPED FOR
FUTURE BUILT OUT
Maximum Capacity of 150 Fixture Units for Combination of SAN
& GREASE Waste Maximum Capacity of 50 Supply Fixture Units.
Maximum Capacity of 30 Fixture Units
Common Area Sealing Power (By Base Building) to be left below the deck to be connected to future furniture (By Others). Number of 20A power circuits to be determined once location(s) & size(s) of Common
Area Seating is determined.
CHILLED WATER SUPPLY
Tenant to connect to base building FLS device
(1) Emergency Lighting Circuit OPC from base building electrical system
POC Size to determined & vetted by Base Building Engineer
DOMESTIC HOT WATER
MEDIUM PRESSURE
3/4" POC Conduit by Base Building COLD WATER CONDITIONED MAKE-UP AIR
Provide Natural Gas point of connection to each Food & Beverage unit. LAWA and American Airlines to coordinate allocation of allowable CFH to each unit type and location.
COLD WATER NATURAL GAS
NOTES (Continued) LEGEND
Roof Pad/Curb for Future MUA Unit/Equipment to be provided by base building BRITISH THERMAL UNIT FIXTURE UNITS OR FIXTURE COUNT
Maximum Capacity of 75 Fixture Units for Combination of SAN
& GREASE Waste Maximum Capacity of 35 Supply Fixture Units.
GENERAL NOTE
Exhibit G Utility Matrix is a working document in DRAFT format that is SUBJECT TO CHANGE based on further coordination & design development between LAWA & American Airlines. LAWA anticipates meeting with American Airlines design team personnel to develop a solution that is agreeable to both parties, that will support phasing and the end-state concessions program
Electrical voltage and amperage to be further evaluated based on
Natural Gas coordination and design development.
EXHAUST DUCT
EXTEND SUPLY DUCT FROM MAIN TO INSIDE
TENANT SPACE
Tenants to install individual, per unit, demand meters (ex: Honeywell E-
Mon Class 6000 Pulse Meter) to support tenant metering of electric, water, & gas services, as applicable.
EXHAUST FAN STAINLESS STEEL
Provide 120V receptacles and 277V lighting fed from house power system. One receptacle per wall, minimum.
Duct size shown are for reference and actual duct size will be engineered based on ventilation air requirements (CFM).
2" IT Conduit terminating at the TWC can be utilized for tenant metering
Sanitary Sewer & Sanitary Sewer Vent can be eliminated IF Grease
Waste & Grease Waste Vent can accommodate anticipated load/capacity
Supply air is not for space conditioning (except for common seating areas) and is based on meeting minimum ventilation
(outside) air requirements only.
Outside air provide by base building system.
If Natural Gas is used, Meter will be located within tenant space
Power Metering
Conduit (From
TWC for Future
Metering BT)
(Note 19)
Power Voltage
(Note 21)
Power Voltage
POC Size
Circuit Breaker
Amp
(Note 21)
Fire Alarm BAS (Note 14)
Conduit Stubout to Kitchen
Exhaust Fan
Emergency
Power
Telecom Conduit
Stubout from
TWC
Radio Antenna
Conduit and
Path
Conduit to
LAWA IT Room for FIDS
Connection
G101 - TER04.L01TA019 CONCESSION 1,371 SF NO N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls NOTE 6 2" NO NO
TER04.L03CA013
TRAVEL ESSENTIALS
Existing Currency Exchange
G301 - TER04.L03CA021 RETAIL CONCESSION 1,270 SF NO N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
NO NOTE 6 2" NO NO
G302 - TER04.L03CA022 COFFEE CONCESSION 937 SF NO N/A 120/208V 3" 300A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
G303 - TER04.L03.CA028 BAR CONCESSION 602 SF NO N/A 120/208V 3" 300A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
G305 - TER04.L03CA011 RETAIL CONCESSION 506 SF NO N/A 120/208V (E) 4" (VIF) 100A (VIF) NOTE 5 VIF N/A NOTE 6 1-1/4" (VIF) NO NO
G306 - TER04.L03CA006 FULL SERVICE RESTAURANT 2,015 SF YES N/A 120/208V
(E) 2-1/2" (VIF)
(E) 1-1/4" (VIF)
800A (VIF) NOTE 5 VIF VIF NOTE 6 1" (VIF) NO NO
G307 - TER04.L03CA008 RETAIL CONCESSION 1,184 SF NO N/A 120/208V (E) 1-1/2" (VIF) 100A (VIF) NOTE 5 VIF N/A NOTE 6 1" (VIF) NO NO
G304 - TER04.L03CA001.01 QSR CONCESSION 1,004 SF YES N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
G308 - TER04.L03SA002 COFFEE CONCESSION 712 SF NO N/A 120/208V 3" 300A NOTE 5
(1) DATA
OUTLET
NO NOTE 6 2" NO NO
G310 - TER04.L03SA003 RETAIL CONCESSION 1,249 SF NO N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
NO NOTE 6 2" NO NO
G311 - TER04.L03SA004 RETAIL CONCESSION 1,470 SF NO N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
NO NOTE 6 2" NO NO
G313 - TER04.L03SA0015.01 QUICK SERVICE RESTAURANT 1,510 SF YES N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
G312 - TER04.L03SA0015.02 QUICK SERVICE RESTAURANT 788 SF YES N/A 120/208V 4" 400A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
G309 - TER04.L03SA0022 &
TER04.L03SA0022.01
RESTAURANT W/ SEATING 3,344 SF YES N/A 277/480V 4" 400A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
G314 - TER04.L03SA0024.01 COFFEE/ BAR CONCESSION 700 SF NO N/A 120/208V 3" 300A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
TER04.L03CA027 CONCESSIONS SEATING 3,911 SF NO N/A NOTE 13 - N/A YES NO NO NOTE 6 NO NO YES (2" MIN.)
TER04.L03SA015 CONCESSIONS SEATING 4,867 SF NO N/A NOTE 13 - N/A YES NO NO NOTE 6 NO NO YES (2" MIN.)
TER04.L03SA024 CONCESSIONS SEATING 2,762 SF NO N/A NOTE 13 - N/A YES NO NO NOTE 6 NO NO YES (2" MIN.)
TER04.L04SA011 GHOST KITCHEN LEVEL 4 3,144 SF YES N/A 277/480V 4" 400A NOTE 5
(1) DATA
OUTLET
¾” Power
¾” Controls
NOTE 6 2" NO NO
TER04.L02CU012 Dry Storage 447 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L02SA029 Wet Storage 138 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L02SA047 Wet Storage 472 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L02SA056 Wet Storage 353 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L02SA057 Wet Storage 364 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L04SA014 Dry Storage 205 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L04SA015 Wet Storage 1,361 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
TER04.L04SA020 Dry Storage 2,493 SF NO N/A NOTE 9 TBD NOTE 9 YES YES NO Per Code
Requirements
2" NO NO
CONCOURSE LEVEL 3
COMMON AREA SEATING AT LEVEL 3 CONCOURSE
STORAGE
Utility Provisions for AA T4/5MP Concession Spaces Issued 05/12/2025
ELECTRICAL/LOW VOLTAGE
CONCOURSE LEVEL 4
ROOM NO. CONCESSION TYPE AREA COOKING
HEADHOUSE LEVEL 1
HEADHOUSE LEVEL 3
Power Metering
Conduit (From
TWC for Future
Metering BT)
(Note 19)
Power Voltage
(Note 21)
Power Voltage
POC Size
Circuit Breaker
Amp
(Note 21)
Fire Alarm BAS (Note 14)
Conduit Stubout to Kitchen
Exhaust Fan
Emergency
Power
Telecom Conduit
Stubout from
TWC
Radio Antenna
Conduit and
Path
Conduit to
LAWA IT Room for FIDS
Connection
Utility Provisions for AA T4/5MP Concession Spaces Issued 05/12/2025
ELECTRICAL/LOW VOLTAGE
ROOM NO. CONCESSION TYPE AREA COOKING
HEADHOUSE LEVEL 1
1 11
BTU FU
2 12
BT HWS
3 13
CHWS MP
4 14 CW MUA
5 15
CW NG
6 16
DHW ROOF STUBOUT
7 17
EA SA STUBOUT
8 18
EF SS
9 19
10 20
NOTES
HOT WATER SUPPLY
Coffee & Bar concepts likely will NOT require full cooking (hoods & rated kitchen) provisions. However, until actual unit allocation & retail category mix is fully developed, LAWA reserves the right to provide cooking infrastructure.
BY TENANT
NOTES (Continued)
Roof Pad/Curb for Future MUA Unit/Equipment to be provided by base building BRITISH THERMAL UNIT FIXTURE UNITS OR FIXTURE COUNT
LEGEND
(1) Emergency Lighting Circuit OPC from base building electrical system
Provide Natural Gas point of connection to each Food & Beverage unit.
LAWA and American Airlines to coordinate allocation of allowable CFH to each unit type and location.
If Natural Gas is used, Meter will be located within tenant space
Maximum Capacity of 150 Fixture Units for Combination of SAN &
GREASE Waste Maximum Capacity of 50 Supply Fixture Units.
Maximum Capacity of 30 Fixture Units
Common Area Sealing Power (By Base Building) to be left below the deck to be connected to future furniture (By Others). Number of 20A power circuits to be determined once location(s) & size(s) of Common
Area Seating is determined.
POC Size to determined & vetted by Base Building Engineer
COLD WATER NATURAL GAS
Maximum Capacity of 75 Fixture Units for Combination of SAN &
GREASE Waste Maximum Capacity of 35 Supply Fixture Units.
Tenant to connect to base building FLS device
Maximum Capacity of 10 Fixture Units
DOMESTIC HOT WATER
FROM ROOF TO TENANT SPACE & CAPPED FOR
FUTURE BUILT OUT
CHILLED WATER SUPPLY MEDIUM PRESSURE
3/4" POC Conduit by Base Building COLD WATER CONDITIONED MAKE-UP AIR
EXHAUST FAN STAINLESS STEEL
2" IT Conduit terminating at the TWC can be utilized for tenant metering
Provide 120V receptacles and 277V lighting fed from house power system. One receptacle per wall, minimum.
EXHAUST DUCT
EXTEND SUPLY DUCT FROM MAIN TO INSIDE
TENANT SPACE
Supply air is not for space conditioning (except for common seating areas) and is based on meeting minimum ventilation (outside) air requirements only.
Outside air provide by base building system. Tenants to install individual, per unit, demand meters (ex: Honeywell E-
Mon Class 6000 Pulse Meter) to support tenant metering of electric, water, & gas services, as applicable.
GENERAL NOTE
Exhibit G Utility Matrix is a working document in DRAFT format that is SUBJECT TO CHANGE based on further coordination & design development between LAWA & American Airlines. LAWA anticipates meeting with American Airlines design team personnel to develop a solution that is agreeable to both parties, that will support phasing and the end-state concessions program
Electrical voltage and amperage to be further evaluated based on
Natural Gas coordination and design development.
Sanitary Sewer & Sanitary Sewer Vent can be eliminated IF Grease
Waste & Grease Waste Vent can accommodate anticipated load/capacity
Duct size shown are for reference and actual duct size will be engineered based on ventilation air requirements (CFM).
Sanitary Sewer (Note
20)
Sanitary Sewer
POC Size
Sanitary Sewer
Vent (Note 20)
Sanitary Sewer
Vent POC Size Grease Waste
Grease Waste
POC Size
Grease Waste
Vent
Grease Waste
Vent POC Size
Domestic Cold
Water
Domestic Cold
Water POC Size
Domestic Cold
Water Meter
Domestic Hot
Water
Natural Gas
(Note 15)
Natural Gas POC
Size
Natural Gas
Meter
(Note 17)
Condensate for
Tenant FCU
Condensate for
Tenant FCU POC
Size
G101 - TER04.L01TA019
CONCESSION
1,371 SF NO YES (NOTE 1) 4" YES (NOTE 1) 4" N/A N/A N/A N/A YES (NOTE 1) 2" BY TENANT BY TENANT 200CFH -
BY TENANT
(NOTE 15)
NO BY TENANT
TER04.L03CA013
TRAVEL ESSENTIALS
Existing Currency
Exchange
130 SF NO
G301 - TER04.L03CA021
RETAIL CONCESSION
1,270 SF NO NO - NO - NO - NO - NO - NO NO NO - NO YES 1"
G302 - TER04.L03CA022 COFFEE CONCESSION 937 SF NO YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 2" BY TENANT BY TENANT 200CFH -
BY TENANT
(NOTE 15)
NO BY TENANT
G303 - TER04.L03.CA028 BAR CONCESSION 602 SF NO YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 2" BY TENANT BY TENANT 200CFH -
BY TENANT
(NOTE 15)
NO BY TENANT
G305 - TER04.L03CA011 RETAIL CONCESSION 506 SF NO NO - NO - NO - NO - NO - NO NO NO - NO NO -
G306 - TER04.L03CA006
FULL SERVICE
RESTAURANT
2,015 SF YES NO - NO - YES 4" (VIF) YES 2" (VIF) YES 2" (VIF) YES 1-1/2" (VIF)
1,098 CFH
(Existing) VIF
1-1/2" (VIF)
BY TENANT
(NOTE 15)
YES 3/4" (VIF)
G307 - TER04.L03CA008 RETAIL CONCESSION 1,184 SF NO NO - NO - NO - NO - NO - NO NO NO - NO NO -
G304 -
TER04.L03CA001.01
QSR CONCESSION 1,004 SF YES YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 2" BY TENANT BY TENANT 500CFH -
BY TENANT
(NOTE 15)
NO BY TENANT
G308 - TER04.L03SA002 COFFEE CONCESSION 712 SF NO YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 3" BY TENANT BY TENANT NO - NO NO BY TENANT
G310 - TER04.L03SA003 RETAIL CONCESSION 1,249 SF NO NO - NO - NO - NO - NO - NO NO NO - NO YES 1"
G311 - TER04.L03SA004 RETAIL CONCESSION 1,470 SF NO NO - NO - NO - NO - NO - NO NO NO - NO YES 1"
G313 -
TER04.L03SA0015.01
QUICK SERVICE
RESTAURANT
1,510 SF
YES
YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 2" BY TENANT BY TENANT 600 CFH 1" NO NO BY TENANT
G312 -
TER04.L03SA0015.02
QUICK SERVICE
RESTAURANT
788 SF YES YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 4" YES (NOTE 1) 3" YES (NOTE 1) 2" BY TENANT BY TENANT 1,000 CFH 2" (NOTE 15) BY TENANT
(NOTE 15)
NO BY TENANT
G309 - TER04.L03SA0022
& TER04.L03SA0022.01
RESTAURANT W/
SEATING
3,344 SF YES YES (NOTE 3) 4" YES (NOTE 3) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 3) 2" BY TENANT BY TENANT 1,000 CFH 2" (NOTE 15) BY TENANT
(NOTE 15)
NO BY TENANT
G314 - TER04.L03SA0024.01
COFFEE/ BAR
CONCESSION
700 SF NO YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 4" YES (NOTE 1) 2" BY TENANT BY TENANT 200CFH -
BY TENANT
(NOTE 15)
NO BY TENANT
Multiple COMMON SEATING Varies NO NO - NO - NO - NO - NO - NO NO NO - NO TBD TBD
TER04.L04SA011 GHOST KITCHEN LEVEL 4 3,144 SF YES YES (NOTE 3) 4" YES (NOTE 3) 4" YES (NOTE 3) 4" YES (NOTE 3) 4" YES (NOTE 3) 3" BY TENANT BY TENANT
1,000CFH
4" (NOTE 15)
BY TENANT
(NOTE 15)
NO BY TENANT
TER04.L02CU012 Dry Storage 447 SF NO NO - NO - NO - NO - NO - NO NO NO - NO TBD TBD
TER04.L02SA029 Wet Storage 138 SF NO YES (NOTE 2) TBD (NOTE 16) YES (NOTE 2) TBD (NOTE 16) NO - NO - YES (NOTE 2) TBD (NOTE 16) NO BY TENANT NO - NO TBD TBD
TER04.L02SA047 Wet Storage 472 SF NO YES (NOTE 2) TBD (NOTE 16) YES (NOTE 2) TBD (NOTE 16) NO - NO - YES (NOTE 2) TBD (NOTE 16) NO BY TENANT NO - NO TBD TBD
TER04.L02SA056 Wet Storage 353 SF NO YES (NOTE 2) TBD (NOTE 16) YES (NOTE 2) TBD (NOTE 16) NO - NO - YES (NOTE 2) TBD (NOTE 16) NO BY TENANT NO - NO TBD TBD
TER04.L02SA057 Wet Storage 364 SF NO YES (NOTE 2) TBD (NOTE 16) YES (NOTE 2) TBD (NOTE 16) NO - NO - YES (NOTE 2) TBD (NOTE 16) NO BY TENANT NO - NO TBD TBD
TER04.L04SA014 Dry Storage 205 SF NO NO - NO - NO - NO - NO - NO NO NO - NO TBD TBD
TER04.L04SA015 Wet Storage 1,361 SF NO YES (NOTE 2) TBD (NOTE 16) YES (NOTE 2) TBD (NOTE 16) NO - NO - YES (NOTE 2) TBD (NOTE 16) NO BY TENANT NO - NO TBD TBD
TER04.L04SA020 Dry Storage 2,493 SF NO NO - NO - NO - NO - NO - NO NO NO - NO TBD TBD
Issued 05/12/2025
ROOM NO. CONCESSION TYPE AREA COOKING
PLUMBING
Utility Provisions for AA T4/5MP Concession Spaces
HEADHOUSE LEVEL 1
HEADHOUSE LEVEL 3
CONCOURSE LEVEL 3
COMMON AREA SEATING AT LEVEL 3 CONCOURSE
STORAGE
CONCOURSE LEVEL 4
Sanitary Sewer (Note
20)
Sanitary Sewer
POC Size
Sanitary Sewer
Vent (Note 20)
Sanitary Sewer
Vent POC Size Grease Waste
Grease Waste
POC Size
Grease Waste
Vent
Grease Waste
Vent POC Size
Domestic Cold
Water
Domestic Cold
Water POC Size
Domestic Cold
Water Meter
Domestic Hot
Water
Natural Gas
(Note 15)
Natural Gas POC
Size
Natural Gas
Meter
(Note 17)
Condensate for
Tenant FCU
Condensate for
Tenant FCU POC
Size
Issued 05/12/2025
ROOM NO. CONCESSION TYPE AREA COOKING
PLUMBING
Utility Provisions for AA T4/5MP Concession Spaces
HEADHOUSE LEVEL 1
SPACE SAN WASTE (DFU)
GREASE
WASTE
(DFU)
VENT (FU) CW (FU) NG (BTU)*
Coffee & Bar 25 25 50 35 725000*
Quick Service Restaurant 25 50 75 35 725000*
Full Service Restaurant 75 75 150 50 1100000*
Retail - Specialty (Spa) 30 N/A 30 15 N/A
1 11
BTU FU
2 12
BT HWS
3 13
CHWS MP
4 14 CW MUA
5 15
CW NG
6 16
DHW ROOF STUBOUT
7 17
EA SA STUBOUT
8 18
EF SS
9 19
10 20
NOTES
HOT WATER SUPPLY
NOTES (Continued)
Coffee & Bar concepts likely will NOT require full cooking (hoods & rated kitchen) provisions. However, until actual unit allocation & retail category mix is fully developed, LAWA reserves the right to provide cooking infrastructure.
Roof Pad/Curb for Future MUA Unit/Equipment to be provided by base building
Tenant to connect to base building FLS device
(1) Emergency Lighting Circuit OPC from base building electrical system
Common Area Sealing Power (By Base Building) to be left below the deck to be connected to future furniture (By Others). Number of 20A power circuits to be determined once location(s) & size(s) of Common
Area Seating is determined.
POC Size to determined & vetted by Base Building Engineer
Maximum Capacity of 75 Fixture Units for Combination of SAN &
GREASE Waste Maximum Capacity of 35 Supply Fixture Units.
Maximum Capacity of 10 Fixture Units
Maximum Capacity of 150 Fixture Units for Combination of SAN
& GREASE Waste Maximum Capacity of 50 Supply Fixture Units.
Maximum Capacity of 30 Fixture Units
DOMESTIC HOT WATER
FROM ROOF TO TENANT SPACE & CAPPED FOR
FUTURE BUILT OUT
LEGEND
BRITISH THERMAL UNIT FIXTURE UNITS OR FIXTURE COUNT
BY TENANT
3/4" POC Conduit by Base Building
Provide Natural Gas point of connection to each Food & Beverage unit.
LAWA and American Airlines to coordinate allocation of allowable CFH to each unit type and location.
CHILLED WATER SUPPLY MEDIUM PRESSURE
COLD WATER CONDITIONED MAKE-UP AIR
COLD WATER NATURAL GAS
PROPOSED MAXIMUM PLUMBING LOADS
COMMENTS
*One (1) Asian-Inspired QSR allowed up to 1,000, 000 BTU/Hr. Size all QSR piping for minimum 1,000,000 BTU/Hr since location of Asian QSR is not known. All other QSRs limited to 725,000 BTU/Hr.
maximum (IF GAS PROVISIONS PROVIDED)
*IF GAS PROVISIONS PROVIDED
GENERAL NOTE
Exhibit G Utility Matrix is a working document in DRAFT format that is SUBJECT TO CHANGE based on further coordination & design development between LAWA & American Airlines. LAWA anticipates meeting with American Airlines design team personnel to develop a solution that is agreeable to both parties, that will support phasing and the end-state concessions program
Electrical voltage and amperage to be further evaluated based on
Natural Gas coordination and design development.
EXHAUST DUCT
EXTEND SUPLY DUCT FROM MAIN TO INSIDE TENANT
SPACE
Tenants to install individual, per unit, demand meters (ex: Honeywell E-
Mon Class 6000 Pulse Meter) to support tenant metering of electric, water, & gas services, as applicable.
2" IT Conduit terminating at the TWC can be utilized for tenant metering
Sanitary Sewer & Sanitary Sewer Vent can be eliminated IF Grease
Waste & Grease Waste Vent can accommodate anticipated load/capacity
Provide 120V receptacles and 277V lighting fed from house power system. One receptacle per wall, minimum.
Duct size shown are for reference and actual duct size will be engineered based on ventilation air requirements (CFM).
If Natural Gas is used, Meter will be located within tenant space
EXHAUST FAN STAINLESS STEEL
Supply air is not for space conditioning (except for common seating areas) and is based on meeting minimum ventilation
(outside) air requirements only.
Outside air provide by base building system.