36E77618R0063-009.pdf
PDF 5 MB Posted
- Attached to
- Parking Garage - WR (VACAA) Construction
- Solicitation number
- 36E77618R0063
About this file
36E77618R0063 S02 Attachment 8 523-400 Parking Garage WR - 100 Percent Plans - 5 of 5.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36E77619C0004-000.docx | DOCX document | |
| 36E77618R0063-0007000.docx | DOCX document | |
| 36E77618R0063-0006000.docx | DOCX document | |
| 36E77618R0063-0005001.pdf | ||
| 36E77618R0063-0005000.docx | DOCX document | |
| 36E77618R0063-0004000.docx | DOCX document | |
| 36E77618R0063-0004001.pdf | ||
| 36E77618R0063-0003000.docx | DOCX document | |
| 36E77618R0063-0002000.docx | DOCX document | |
| 36E77618R0063-0001001.docx | DOCX document | |
| 36E77618R0063-0001000.docx | DOCX document | |
| 36E77618R0063-012.docx | DOCX document | |
| 36E77618R0063-002.pdf | ||
| 36E77618R0063-006.pdf | ||
| 36E77618R0063-001.docx | DOCX document | |
| 36E77618R0063-013.docx | DOCX document | |
| 36E77618R0063-010.pdf | ||
| 36E77618R0063-004.pdf | ||
| 36E77618R0063-007.pdf | ||
| 36E77618R0063-003.pdf | ||
| 36E77618R0063-005.pdf | ||
| 36E77618R0063-011.pdf | ||
| 36E77618R0063-008.pdf | ||
| 36E77618R0063-000.docx | DOCX document |
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CL
PTE
RTE
F
F
DOOR
F
R
FS
TS
PS
DL
SK
D
MM
(PROTECTS DOWNSTREAM
"GFCI" / "GF" INDICATES GFI OUTLET
RGE
DW
DW
2 DOUBLE POLE SWITCH
"WM" INDICATES DEVICE MOUNTED IN "WIREMOLD"
LETTER IS CIRCUIT CONTROL GROUP.
RANGE OUTLET NEMA 14-50R
W/ COVER. NEMA 5-20R
ACTUAL EQUIPMENT SERVED.
MOUNT WITH GROUND TERMINAL AT TOP.
RECEPTACLES ON SAME CIRCUIT.)
"42"" INDICATES MOUNTED AT 42" A.F.F.
("D" INDICATES DRYER OUTLET NEMA 14-30R)
FLOOR SINGLE RECEPTACLE OUTLET
SPECIAL PURPOSE CONNECTION
LETTER(S) BESIDE SYMBOL INDICATES
FIRE ALARM PULL STATION MTD 48" A.F.F.
EXIT SIGN
MANUAL STARTER - SIZE AS REQUIRED
WITH NEC - "C" INDICATES MOUNTING
SIZE & CONFIGURATION AS NOTED ABOVE
JUNCTION BOX - SIZED IN ACCORDANCE
TRANSFORMER, SIZE & TYPE AS INDICATED
3 POLE FUSIBLE DISCONNECT SWITCH
30 = AMPACITY. VOLTAGE AS REQ'D.
MULTIPLE ARROWHEADS INDICATES MULTIPLE
3 POLE WEATHERPROOF DISCONNECT SWITCH
3 POLE, NON-FUSIBLE DISCONNECT SWITCH
L4N-3 (PAR)
J C
J C , T
3R
MS
30NF
ELECTRICAL FEED TO EQUIPMENT
INDICATES CIRCUIT NUMBER
INDICATES PARTIAL CIRCUIT
INDICATES PANEL
CIRCUITS
60 = CLIP SIZE, 40 = FUSE SIZE
VOLTAGE AS REQ'D
IN CEILING SPACE
RTS
135°, 200°
HD
DC
REMOTE TEST STATION
FIRE ALARM MAIN PANEL
SMOKE DETECTOR, CEILING MOUNTED.
HEAT DETECTOR - TEMP. AS INDICATED, CEILING MOUNTED:
FIRE ALARM SYSTEM
DOOR HOLDER, MATCH EXISTING, PROVIDE 120V
DOOR CLOSER
FIRE ALARM SYSTEM MAGNETIC
(75 CANDELA)
S
"E" INDICATES EXISTING
"TP" INDICATES TAMPER PROOF
2'X2' RECESSED FLUORESCENT FIXTURE
(NORMAL POWER)
(LIFE SAFETY POWER)
2'X4' RECESSED FLUORESCENT FIXTURE
(NORMAL POWER)
(LIFE SAFETY POWER)
RECESSED DOWNLIGHT FIXTURE
(NORMAL POWER)
RECESSED DOWNLIGHT FIXTURE
(LIFE SAFETY POWER)
FROM NEAREST NORMAL POWER PANEL IF REQUIRED.
ACU
AFF
AFG
AHU
AIC
C
CS
CB
CLF
CT
CTV
CU
CUH
CWP
DT
DW
DWG
EBB
EDH
EF
EUH
EWC
EX
FACP
FBO
FC
GD
GFCI
GND
GRC
H
HD
HH
HP
HPS
HRU
HV
HWP
IG
IR
KW
KWH
LIG
LTG
MB
MC
MD
MDP
MH
MI
MLO
MMC
MTD
MW
N/A
NC
NEC
NF
NIC
NL
NM
NO
NTS
NTU
OCD
PB
PM
PT
R
RCU
RECP
REF
REQ'D
RF
RGE
RGS
RH
RT
RTAC
SF
S/N
TBD
TP
TV
TYP
UC
UNO
WM
XFMR
SYMBOLS DESCRIPTIONSSYMBOLS DESCRIPTIONSDESCRIPTIONSABBREVIATIONS SYMBOLS DESCRIPTIONS
SYMBOLS DESCRIPTIONS
1. ALL GENERAL NOTES, SYMBOL LIST & DETAILS ARE TO BE CONSIDERED AS
APPLICABLE TO ALL ELECTRICAL DRAWINGS FOR THIS PROJECT. SYMBOLS AND
ABBREVIATIONS SHOWN ON THIS SHEET ARE FOR REFERENCE ONLY AND DO
NOT INDICATE THEIR INCORPORATION IN THE DESIGN.
2. ALL WORK PERFORMED ON THIS CONTRACT SHALL BE DONE IN A NEAT AND
WORKMANLIKE MANNER AND SHALL BE IN COMPLIANCE WITH NEC, NFPA,
BOCA, OSHA, AND ALL APPLICABLE STATE AND LOCAL CODES AND ORDINANCES.
3. THESE DRAWINGS ARE, IN GENERAL, MADE TO SCALE BUT ALL MEASUREMENTS
SHALL BE TAKEN FROM FIGURED DIMENSIONS, AND NOT BY SCALING.
4. THE ELECTRICAL CONTRACTOR SHALL CONFER WITH ALL OTHER TRADES
RELATIVE TO THE LOCATION OF APPARATUS AND EQUIPMENT AND SELECT
LOCATIONS SO AS NOT TO CONFLICT WITH WORK OF OTHER TRADES.
5. LIGHTING FIXTURE MANUFACTURERS NAME & MODEL NUMBER ARE USED FOR
DESCRIPTIVE PURPOSES ONLY AND ARE INTENDED TO INDICATE THE STANDARD
OF MATERIAL OR ARTICLES REQUIRED.
6. ALL EQUIPMENT SHOWN ON THESE DRAWINGS IS INTENDED TO BE GENERALLY
REPRESENTATIVE OF THE EQUIPMENT WHICH WILL BE INSTALLED UNDER THIS
CONTRACT, BUT IT SHALL NOT BE ASSUMED THAT THE DRAWINGS INDICATE
THE SPECIFIC CONFIGURATION, ARRANGEMENT OR POINTS OF CONNECTION OF
THE ACTUAL EQUIPMENT UNLESS NOTED OTHERWISE.
7. COORDINATE W/ CONTROLS CONTRACTOR TO PROVIDE POWER FOR ALL
MISCELLANEOUS CONTROL OPERATORS AND PANELS.
8. CIRCUIT BREAKERS USED FOR LIGHTING CIRCUITS SHALL BE SWITCH DUTY
RATED AND APPROVED FOR USE WITH H.I.D. FIXTURES. CIRCUIT BREAKERS
USED FOR HVAC AND REFRIGERATION EQUIPMENT SHALL BE "HACR" RATED.
9. ALL HOME RUNS FOR LIGHTING OR POWER CIRCUITS LONGER THAN 150 FEET
SHALL BE INCREASED ONE SIZE. (IE: #12 TO #10).
10. ALL BRANCH CIRCUIT AND FEEDER CONDUCTORS SHALL BE SIZED FOR THE
O.C.D. RATING FOR THAT CIRCUIT ACCORDING TO NEC ART 310 UNLESS
OTHERWISE INDICATED ON THESE DRAWINGS. IN NO CASE SHALL CONDUCTORS
SMALLER THAN NO. 12 AWG BE USED FOR POWER OR LIGHTING CIRCUITS.
11. PROVIDE 3/8" NYLON ROPE IN ALL EMPTY SERVICE RACEWAYS.
12. ALL SLEEVES AND OTHER PENETRATIONS THRU FIRE RATED ASSEMBLIES SHALL
BE SEALED AFTER CABLE INSTALLATION WITH A FIRE RETARDANT COMPOUND.
13. ALL FLUSH MOUNTED PANELBOARDS SHALL BE PROVIDED WITH (2) 1-1/4"
EMPTY CONDUITS BETWEEN PANEL & SUSPENDED CEILING.
14. THE CONTRACTOR IS RESPONSIBLE FOR FIRESTOPPING AROUND ALL CONDUITS,
CABLES AND ELECTRICAL EQUIPMENT AT ALL PARTITIONS PIERCED PER NEC
300-21 AND B.O.C.A.
15. THE CONTRACTOR IS RESPONSIBLE FOR MEETING ALL SIESMIC REQUIREMENTS
FOR THE INSTALLATION OF ELECTRICAL EQUIPMENT UNDER B.O.C.A.
16. GROUNDING SHALL BE PER N.E.C. ARTICLE 250, INSTALL GROUNDING
CONDUCTORS WITH ALL FEEDERS AND BRANCH CIRCUITS.
17. ALL WIRING SHALL BE IN CONDUIT.
18. REMOVE EQUIPMENT, FIXTURES AND DEVICES THAT ARE NOT BEING REUSED
AND DISCARD. OWNER HAS THE OPTION TO KEEP ANY MATERIAL DESIRED.
EXISTING FIXTURES SCHEDULED FOR REUSE SHALL BE CLEANED.
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
CONDUIT
CONDUIT SLEEVE
CIRCUIT BREAKER
CENTER LINE
CURRENT LIMITING FUSE
CURRENT TRANSFORMER
CABLE TELEVISION
CONDENSING UNIT
CABINET UNIT HEATER
CONDENSER WATER PUMP
DISTRIBUTION TRANSFORMER
DISHWASHER
DRAWING
ELECTRIC BASEBOARD HEATER
ELECTRIC DUCT HEATER
EXHAUST FAN
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
EXISTING EQUIPMENT (AS NOTED)
FIRE ALARM CONTROL PANEL
FURNISHED BY OWNER
FAN COIL
GARBAGE DISPOSER
GROUND FAULT CIRCUIT INTERUPTING
GROUND
GALVANIZED RIGID STEEL CONDUIT
HUMIDIFIER
HEAT DETECTOR
HAND HOLE
HORSEPOWER / HEAT PUMP
HIGH PRESSURE SODIUM
HEAT RECOVERY UNIT
HIGH VOLTAGE
HOT WATER CIRC. PUMP
ISOLATED GROUND
INFRA-RED
KILOWATT
KILOWATT HOUR
LONG/INSTANTANEOUS/GROUND FAULT
LIGHTING
MAIN BREAKER
METAL CLAD
MAIN DISCONNECT
MAIN DISTRIBUTION PANEL
MAN HOLE / METAL HALIDE
MINERAL INSULATED
MAIN LUGS ONLY
MAINE MEDICAL CENTER
MOUNTED
MICROWAVE
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE (NFPA-70)
NOT FUSED
NOT IN CONTRACT
NIGHT LIGHT
NON METALLIC
NORMALLY OPEN
NOT TO SCALE
NURSE CALL TERMINAL UNIT
OVERCURRENT DEVICE
PULL BOX
"PLUGMOLD" UTILIZED
POTENTIAL TRANSFORMER
REMOVE
REFRIGERATION CONDENSING UNIT
RECEPTACLE
REFRIGERATOR
REQUIRED
RETURN FAN
RANGE
RIGID GALVANIZED STEEL CONDUIT
RANGE HOOD
ROOF TOP MOUNTED IN A WEATHERPROOF ENCLOSURE
ROOF TOP AIR CONDITIONER
SUPPLY FAN
SOLID NEUTRAL
TO BE DETERMINED
TAMPER PROOF
TELEVISION
TYPICAL
UNDER COUNTER
UNLESS NOTED OTHERWISE
WEATHERPROOF
INSTALL WITH "WIREMOLD"
TRANSFORMER
SYMBOLS DESCRIPTIONS
SYMBOLS DESCRIPTIONSSYMBOLS DESCRIPTIONS
SYMBOLS DESCRIPTIONS
2'X4' RECESSED FLUORESCENT FIXTURE
2'X2' RECESSED FLUORESCENT FIXTURE INTERCOM SYSTEM HEAD END
SECURITY CAMERA : ARECONT VISION:
180 DEG: AV8185DN-HB
360 DEG: AV8365DN-HB
LINE VOLTAGE DOOR SWITCH. INSTALL IN HINGE SIDE OF DOOR JAMB
WIRE TO JUNCTION BOX BEHIND EQUIPMENT IN ROOM
GFCI DUPLEX RECEPTACLE OUTLET. WP INDICATES
WEATHER PROOF
ELECTRICAL GENERAL NOTES GENERAL ABBREVIATIONS PANEL & CIRCUIT SYMBOLS FIRE ALARM & LIFE SAFETY SYMBOLS RECEPTACLE OUTLET SYMBOLS
DATA SYMBOLS
MISCELLANEOUS SYMBOLS
LIGHTING SYMBOLS
DOOR PADDLE PUSHBUTTON
AUTOMATIC TRANSFER SWITCHATS
FIRE ALARM ANNUNCIATOR
JUNCTION BOXJ
4" RED SPRINKLER TROUBLE BELL MTD 80" AFF
SPRINKLER FLOW SWITCH.
CONNECT TO FIRE ALARM SYSTEM
SPRINKLER TAMPER SWITCH.
CONNECT TO FIRE ALARM SYSTEM
SPRINKLER PRESSURE SWITCH.
CONNECT TO SPRINKLER TROUBLE BELL
MOUNT 8' ABOVE GRADE
AD
INT
DUCT MOUNTED SMOKE DETECTOR
"OC" INDICATES OVER COUNTER
DUAL TELEPHONE/DATA OUTLET AT +18" OR AS NOTED. FURNISH (1) 1" CONDUIT FROM
DEVICE OUTLET BOX TO ACCESSIBLE SPACE ABOVE SUSPENDED CEILING PROVIDE
TELEPHONE AND DATA CABLE COMPLETE, TO NEW PATCH PANEL IN DATA CLOSET.
DATA OUTLET AT +18" OR AS NOTED. FURNISH (1) 3/4" CONDUIT FROM DEVICE
OUTLET BOX TO ACCESSIBLE SPACE ABOVE SUSPENDED CEILING PROVIDE DATA CABLE
COMPLETE, TO NEW PATCH PANEL IN CLOSET.
TELEPHONE OUTLET AT +18" OR AS NOTED. FURNISH (1) 3/4" CONDUIT FROM DEVICE
DEVICE OUTLET BOX TO ACCESSIBLE SPACE ABOVE SUSPENDED CEILING PROVIDE
TELEPHONE CABLE COMPLETE, TO TELEPHONE MOUNTING BOARD. WIRING TO BE CAT5.
COLOR BY OWNER. W INDICATES WALL MOUNT AT 48" W/POST TYPE PLATE.
CR
OC
FACP
FAAN
PANELBOARD - SURFACE MOUNTED AT 6'-6" TO TOP.
MOTOR CONTROLLER - FURNISHED WITH MOTOR.
SINGLE POLE SWITCH MOUNTED AT +48" OR AS NOTED.
THREE WAY SWITCH MOUNTED AT +48" OR AS NOTED.
MASTER BOX
VISUAL NOTIFICATION APPLIANCE MEETING A.D.A.
REQUIREMENTS.
MTD AT 6" BELOW CEILING OR +80" AFF, WHICHEVER IS LESS.
CARD READER
PANELBOARD - FLUSH MOUNTED AT 6'-6" TO TOP.
EMERGENCY LIGHTING FIXTURE BATTERY
OPERATED. SEE LIGHTING FIXTURE
SCHEDULE
FOR SPECIFICATION.
EMERGENCY EXIT SIGN, SEE LIGHTING
FIXTURE
SCHEDULE FOR SPECIFICATION.
BARE LAMP FLUORESCENT STRIP - AS NOTED
ON DRAWINGS.
SP
S
C
SIMPLEX CONVENIENCE RECEPTACLE MOUNTED
AT +18" OR AS NOTED.
QUADRUPLEX RECEPTACLE OUTLET
(DOUBLE DUPLEX) NEMA 5-20R, HEAVY
DUTY. MOUNTED AT +18" OR AS NOTED,
SELF-ILLUMINATING, AND BACKPLATE.
DEVICES SHALL BE RED WHEN
CONNECTED TO CRITICAL OR EQUIPMENT
PANELS.
DUPLEX RECEPTACLE OUTLET NEMA 5-20R,
HEAVY DUTY. MOUNTED AT +18" OR AS NOTED,
SELF-ILLUMINATING, AND BACKPLATE. DEVICES
SHALL BE RED WHEN CONNECTED TO CRITICAL
OR EQUIPMENT PANELS.
FLOOR DUPLEX RECEPTACLE
OUTLET W/ COVER. NEMA 5-20R
FLOOR SPECIAL PURPOSE OUTLET LETTER(S)
BESIDE SYMBOL INDICATES ACTUAL
EQUIPMENT
SERVED.
F = FIXED TEMPERATURE, 135° UNLESS OTHERWISE NOTED
R = RATE IF RISE
R/F = COMBINATION RATE OF RISE
AND FIXED TEMPERATURE
FS
COMBINATION AUDIO/VISUAL NOTIFICATION APPLIANCE
MEETING A.D.A. REQUIREMENTS. MTD AT 6" BELOW
CEILING OR +80" AFF, WHICHEVER IS LESS. 75cd
CANDELA, OR AS NOTED. WP INDICATES WEATHERPROOF
MOTOR, HP AS INDICATED COORDINATE W/ ACTUAL
EQUIPMENT FURNISHED.
MAGNETIC STARTER - NEMA SIZE AS REQUIRED (MINIMUM
SIZE 1) PROVIDE W/ H-O-A SWITCH AND GREEN RUN
LIGHT ON COVER. - FURNISHED AND INSTALLED BY
ELECTRICAL CONTRACTOR. SIZE AS NOTED.
COMBINATION MAGNETIC STARTER - NEMA SIZE AS
REQUIRED (MINIMUM SIZE 1) PROVIDE W/ H-O-A
SWITCH AND GREEN RUN LIGHT ON COVER.
SINGLE POLE SWITCH W/ PILOT LIGHT MOUNTED AT +48"
OR AS NOTED.
SLIDE CONTROL DIMMER AT +48" OR AS NOTED, PROVIDE
SWITCH FOR FIXTURES ACTUALLY SERVED.
SM
SWITCHES LOCATED IN THE SAME AREA SHALL BE GANGED UNDER COMMON PLATE
WHENEVER PRACTICAL, GROUP SWITCHES, THERMOSTATS ETC. TOGETHER. SWITCHES
SHALL
BE LOCATED ON STRIKE SIDE OF DOOR. ADJUST TO MINIMIZE CUT OF BLOCK OR TILE.
LETTER IS SWITCH CONTROL GROUP.
H.P. RATED MANUAL MOTOR STARTER (WEATHERPROOF
WHERE OUTSIDE).
OVER COUNTER OUTLET
CASEWORK RECESSED OUTLET
S
DM
MONITOR MODULES
DOOR CONTROLLER
EMERGENCY PUSH TO EXIT BUTTON
185CD
PP
REQUEST TO EXIT SENSOR
WP
S
S
S
ML MAGNETIC LOCK
M DOOR HOLD OPEN, RELEASE ON FIRE ALARM AND DAILY AT NIGHT
EXACT TIME PROVIDED BY OWNER.
SOS
OS
DEVICES SHALL BE HOSPITAL GRADE, SEE SPEC.
SPEAKER - CEILING MOUNT
OCCUPANCY SENSOR (CEILING MOUNT)
(WATTSTOPPER LMRC-210(DIMMING) OR LMRC-100(ON/OFF)
ROOM CONTROLLER WITH LMDC-100 SENSOR AND LMSW-105
SWITCH ROOM KITS OR EQUAL,
OCCUPANCY SENSORS (CEILING MOUNT) - CORRIDOR - HUBBELL
LXOMDT2000LP FOR CORRIDOR USE / OR HUBBELL ONIDT2000
WITH POWER PACK UVPP AND OVERRIDE SWITCH LOCATED IN
NURSES STATIONS, OR EQUAL.
OCCUPANCY SENSOR WALL SWITCH - HUBBELL LHMTS1W OR
WATTSTOPPER DSW-100 OR EQUAL
EMERGENCY TELEPHONE OUTLET AT +48" OR AS NOTED. FURNISH (1) 3/4" CONDUIT FROM
DEVICE DEVICE OUTLET BOX TO ACCESSIBLE SPACE ABOVE SUSPENDED CEILING PROVIDE
TELEPHONE CABLE COMPLETE, TO TELEPHONE MOUNTING BOARD. WIRING TO BE CAT5.
COLOR BY OWNER. W INDICATES WALL MOUNT AT 48" W/POST TYPE PLATE.
EP
GFGFCIWP
C
ES ELECTRIC STRIKE
CR
KEYPAD
F
S P
F
LP
BET
LIGHTNING PROTECTION
BUILDING ENTRANCE TERMINAL FOR TELEPHONE
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig ht h in ch o ne fo ot on e q ua rte r i nc on e h al f th re e e ig hs th re e q ua rte rs
6" on e i
6" on e a nd on e h a lf i nc he s f oo t 6" th re e i nc f oo t 6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
Denis McLaughlin Telephone: 857-364-5149
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
6/15/2015
ELECTRICAL - LEGEND AND GENERAL NOTES
E001
MTF/AJZBSS 63
3"
2"
4"
NOT TO SCALE
TYPICAL PANEL NAMEPLATE DETAIL
PANEL NAMING CONVENTION
DENOTES PANEL TYPE
L4N-G-GA
- LIGHTING
- POWER/DISTRIBUTION PANEL
- RECEPTACLE PANEL
'L' 'P' 'R'
NOTE:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL
NAMEPLATE REQUIREMENTS.
5/32"DIA. HOLE
LIFE SAFETY PANEL
'L4S-G-GRA'
120/208V., 3PH, 4W
FED FROM 'GARAGE
MDP'
'N' - NORMAL
'S' - LIFE SAFETY
DENOTES VOLTAGE
'4' - 480Y/277V '2' - 208Y/120V
DENOTES FLOOR
WATER
ENTRANCE
PARKING GARAGE SERVICE ENTRANCE & POWER DISTRIBUTION RISER DIAGRAM
N.T.S
(2)4" PVC CONDUITS (GALV. STEEL WHERE
EXPOSED) WITH 2 SETS OF 4-1/C #350KCMIL
AND 1/C #4/0 CU GROUND.
ALL RACEWAYS SHALL INCLUDE EQUIPMENT GROUNDING CONDUCTOR SIZED
PER NEC TABLE 250.122.
CONTRACTOR TO PROVIDE PRIMARY AND SECONDARY LUGS AND TERMINATE
ALL GROUND CONDUCTORS #6 AND SMALLER SHALL HAVE GREEN
INSULATION. "REMARKING" IS NOT ACCEPTABLE.
ALL WIRING SHALL BE IN CONDUIT
NOTES
BOND BUILDING
STEEL
1.)
2.)
3.)
4.)
#4/0 GROUND COND.NEW 300kVA PAD MOUNT
TRANSFORMER
(2)4" PVC CONDUITS WITH 3#1/0. CU,
SHIELDED 5kV & 1#2G CU.
CONDUCTORS, SPARE CONDUIT
SHALL HAVE 500# PULLCORD.
(1)3/4"x10' GROUND ROD
AND CONDUCTOR
GROUND PER NEC.
MDP
NEW MAIN DISTRIBUTION
PANELBOARD
600 AMP 480/277VAC 3PH
#4/0 CU GROUND
COND.
LEVITON MODEL 57120-M3
SURGE SUPPRESSER (WIRE
N&G TO SPARE MODULE)
CONNECT TO A 30A 3 POLE
BREAKER
3-1/C #10 & #
10 GND. IN 1"
CONDUIT
SURGE
SUPPR
ELEVATOR 1
CONTROLLER
480Y/277V
(2)-3/4"x10' GROUND
RODS AND CONDUCTOR
GROUND PER NEC.
BUILDING
STEEL
LEVEL ONE
L4N-G-GRA
36 CKT
480Y/277V
MLO
ELECTRICAL
ROOM
GRND LVL.
T-GRA
DRY-TYPE 2 XFORMER
75kVA 480VAC 3PH ->208Y/120V
R2N-G-GRA
225A
42 CKT
208Y/120V
MCB
ELECTRICAL
ROOM
GRND LVL.
L4S-G-GRA
EMERG. MAIN
DISTRIBUTION
PANELBOARD
400 AMP
480/277VAC 3PH
LEVITON MODEL 57120-M3 SURGE
SUPPRESSER (WIRE N&G TO SPARE MODULE)
CONNECT TO A 30A 3 POLE BREAKER
SURGE
SUPPR
EM DISC.
400A
EM. ELECTRICAL
ROOM
GRND LVL.
ATS-GARAGE 'OS'
480Y/277VAC 3PH
BY-PASS
TRANSFER
SWITCH
100A
EM. ELECTRICAL
ROOM
GRND LVL.
ELEVATOR 2
CONTROLLER
480Y/277V
FACP
FIRE ALARM
CONTROL PANEL
EST3
EM. ELECTRICAL
ROOM
GRND LVL.
EXISTING
5kV
SWITCHGEAR
EXISTING
480V EM.
SWITCHGEAR
S3E-B-2A
EXIST GEN.
CNTL PNL
BASEMENT FLOOR
FINISHED GRADE
BUILDING 70 MEDIUM
VOLTAGE 4160V
SWITCHGEAR
BUILDINGBUILDING 2
1#4/0G TO BUILDING
PERIMETER GROUND
LOOP (TYPICAL), SEE
SITE PLAN.
'G', '1', '2', '3', '4', & '5'
DENOTES LOCATION
E.G.'GR' - GARAGE AND
'A'. 'B', &'C' ETC DENOTES PANEL
SEQUENCE
EXISTING MANHOLE AT
EXTERIOR OF BUILDING #2
480V SERVICE RELOCATION RISER DIAGRAM
N.T.S
(1)4" PVC CONDUITS (GALV. STEEL WHERE
EXPOSED) 24#10 AWG CONDUCTORS FOR ATS
CONTROLS.
(1)4" PVC CONDUITS (GALV. STEEL
WHERE EXPOSED) 4#500KCMIL
CONDUCTORS FOR EMERGENCY POWER.
NEW MANHOLE 10
NEAR GARAGE, SEE
SITE PLAN FOR
LOCATION
TRAILERS
300kVA
480VAC 3PH ->
208Y/120V
FISHER HOUSE
150kVA
480VAC 3PH ->
208Y/120V
SIGN
75kVA
480VAC 3PH ->
208Y/120V
SUBSTATION & MISC.
SITE LIGHTING
480VAC 3PH
J
#4/0 CU GROUND
COND.
1#4/0G TO
IRM ROOM
GROUND BAR
SUBSTATIO
N LIGHTING
DISC. OFF
OF PANEL
'P3N-B-H2'
BUSS
SIGN
P4
BLD 2
MANUAL
TRANSFER
SWITCH
TRAILERS
MANUAL
TRANSFER
SWITCH
FISHER
HOUSE
TO NORMAL
AND EMERGENCY
BKRS
TO NORMAL
AND EMERGENCY
BKRS
(1)2"C WITH 24#10 AWG
CONDUCTORS FOR ATS
CONTROLS.
CONNECT
TO
EXISTING
COMM.
(1)4" PVC CONDUITS (GALV. STEEL
WHERE EXPOSED) WITH 4#
2/0AWG, 1#6G
(1)4" PVC CONDUITS (GALV. STEEL
WHERE EXPOSED) WITH 4#
2/0AWG, 1#6G
(1)4" PVC CONDUITS (GALV. STEEL
WHERE EXPOSED) WITH 4#
2/0AWG, 1#6G
(1)4" PVC CONDUITS WITH 2 SETS
OF 3#350AWG, 1#4G
(1)4" PVC CONDUITS WITH 2 SETS
OF 3#350AWG, 1#4G
(1)4" PVC CONDUITS WITH 1 SETS
OF 3#350AWG, 1#4G
(1)4" PVC CONDUITS WITH 2 SETS
OF 3#350AWG, 1#4G
(1)4" PVC CONDUITS WITH 1 SETS
OF 3#350AWG, 1#4G PROVIDE JUNCTION BOX AT CONDUIT
BUSHINGS AND ROUTE NON-METALIC FLEX IN
MANHOLE TO SEPARATE TEL/COM CABLES,
TYPICAL.
2"C WITH 25 PAIR PIC TEL AND
SMALL TEL TERMINATED AT
BUILDING ENTRANCE TERMINAL.
NEW MANHOLE #10G
AT GARAGE, SEE SITE
PLAN FOR LOCATION
UTILIZE SPARE 5kV
BREAKER.
SET TRIP SETTING TO
50 AMPS.
NEW WALL MOUNTED JUNCTION BOXES
UTILIZE EXISTING SPARE
400AF BREAKER AND
PROVIDE A 400A TRIP PLUG
(1)2" PVC CONDUIT (GALV. STEEL
WHERE EXPOSED) WITH (1) 25 Pair
PIC CABLE
GARAGE
K L
M
M
J
TGR-G-LS
MINI-POWER
TRANSFORMER WITH
(5) 1P, 20A, BREAKERS
3kVA 480VAC 1PH -> 240/120V
2. SIZE UNLESS OTHERWISE INDICATED IN PLAN OR ON THIS DRAWING.
2#12, 1#12G, 3/4"C
1#6G,3/4"C
1#2G,3/4"C3#1/0, 1#6G,2"C
ATS-GARAGE 'LS'
480Y/277VAC 3PH
BY-PASS
TRANSFER SWITCH
300A
(1)2" PVC CONDUITS
(GALV. STEEL WHERE
EXPOSED) 12#10 AWG
CONDUCTORS FOR ATS
CONTROLS.
LS BRK
300A
OS BRK
100A
F
2#12, 1#12G, 3/4"C
ELEV BRK
150A
WITH
SHUNT
TRIP
LS ELEV
BRK
150A
WITH
SHUNT
TRIP
OPTIONAL STAND-BY
SYSTEM
ESSENTIAL
SYSTEM
J
MINI-POWER TRANSFORMER WITH
(10) 1P, 20A BREAKERS.
7.5kVA 480VAC 1PH ->240/120V
LOCATE AT IRM ROOM FOR IRM
AND SECURITY ROOM EQUIPMENT.
1#6G,3/4"C
TGR-2-OS
2#12, 1#12G, 3/4"C
M
G
WIREWAY
NORMAL ELECTRICAL ROOM EMERGENCY ELECTRICAL ROOM
LEVELTWO
J
ELEV 2
CAB
LIGHTS
ELEV 1
CAB
LIGHTS
F M
(1)4" PVC CONDUITS (GALV. STEEL WHERE
EXPOSED) 24#10 AWG CONDUCTORS FOR ATS
CONTROLS.
(1)4" PVC CONDUITS (GALV. STEEL
WHERE EXPOSED) 4#500KCMIL
CONDUCTORS FOR EMERGENCY POWER.
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h a lf i nc f oo t 6" th re e i nc f oo t 6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
Denis McLaughlin Telephone: 857-364-5149
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
6/15/2015
ELECTRICAL - ONE-LINE RISER DIAGRAM
E002
MTF/AJZBSS 64
TO BUILDING
EMERGENCY LIFE SAFETY BRANCH
CIRCUIT 20A 120VAC SEE POWER
PLANS FOR CIRCUITS. ROUTE IN 4" TEL/CO CONDUIT. RISER (TYPICAL).
PROVIDE MANUFACTURERS RECOMMENDED
WIRING AND CONNECT TO CAMPUS SYSTEM
SMOKE & HEAT
DETECTORS
TO OTHER
ADDRESSABLE
INPUT DEVICES
PULL
STATIONS
SLC LOOP
FIRE ALARM
CONTROL
PANEL
"EST 3"
LOCATED IN NORMAL
ELECTRICAL ROOMS REMOTE
POWER
SUPPLY
SS
TO OTHER
OUTPUT
DEVICES
FS
SS
TO OTHER
OUTPUT
DEVICES
FS
NEW STROBES &
SPEAKER/STROBES
DUCT SMOKE DETECTORS
(TYPICAL)
ELEVATOR DETECTORS
(TYPICAL AT ELEVATOR LOBBY AREA)
CONTACT OUTPUT
MODULE
OM
ELEVATOR CONTACT
OUTPUT MODULES
OM
DH
DOOR
HOLD
OPEN
FIRE ALARM NOTES:
1. REFER TO FLOOR PLANS FOR EXACT LOCATIONS AND QUANTITIES OF DEVICES.
2. QUANTITY OF AUDIO/VISUAL SIGNALING CIRCUITS SHALL BE PER MANUFACTURER'S REQUIREMENTS. EACH CIRCUIT SHALL
HAVE 50% SPARE CAPACITY FOR FUTURE NOTIFICATION APPLIANCES PER SPECIFICATION.
3. ALL INSTALLATION WORK WILL BE DONE IN ACCORDANCE WITH FIRE ALARM MANUFACTURER’S INSTRUCTIONS, RECOMMENDATIONS, AND APPROVED WIRING SCHEMATIC.
4. CORRIDOR AUDIO/VISUAL (STROBE) NOTIFICATION DEVICES SHALL BE SYNCHRONIZED AS REQUIRED.
5. MINIMUM CONDUIT SIZE SHALL BE ¾” RIGID CONDUIT. ALL CONDUIT IS RED IN COLOR.
6. FIRE ALARM SYSTEM MUST COMPLY WITH CITY AND STATE MASSACHUSETTS REQUIREMENTS AND STANDARDS. COORDINATE
WITH LOCAL FIRE DEPARTMENT AND CITY.
7. ALL CIRCUITS SHALL BE CLASS B LOOPS. TWO RISER PER CIRCUIT LOOP SHALL BE SEPARATED BY 1-1/4” MINIMUM.
8. ELEVATOR PIT SHALL HAVE A SMOKE DETECTOR, AND A 135DEG. HEAT DETECTOR, THE HEAT DETECTOR SHALL BE LESS THAN
2’ FROM SPRINKLER HEAD.
9. ELEVATOR CONTROL PANEL, AND TOP OF HOISTWAY SHALL HAVE A SMOKE DETECTOR, AND THE HEAT DETECTOR SHALL BE
LESS THAN 2’ FROM SPRINKLER HEAD.
10. COORDINATE EXACT QUANTITY AND LOCATION OF FIRE PROTECTION DEVICES WITH FIRE PROTECTION CONTRACTOR.
11. PROVIDE SEPARATE MULTIPLEX LOOP INITIATING CIRCUIT PER FLOOR PROVIDE SEPARATE 24V POWER CIRCUIT FOR CONTROL
ADDRESSABLE MODULES PER MANUFACTURER'S REQUIREMENTS.
12. REFER TO DETAIL ELEVATOR DEVICES & WIRING DIAGRAM.
13. REFER TO SPECIFICATIONS FOR ATC CONNECTION TO SHUT DOWN HVAC EQUIPMENT.
14. CONTRACTOR TO EXTEND WIRING FROM CONTROL ADDRESSABLE MODULE TO ELEVATOR CONTROLLER. COORDINATE WITH
ELEVATOR VENDOR FOR FINAL CONNECTIONS (TYPICAL).
15. FIRE ALARM PANEL MUST BE COMPATIBLE WITH CAMPUS SYSTEM.
RISER
OM
ELEVATOR CONTROL
MODULES
FIRE ALARM SYSTEM RISER
NOT TO SCALE
FACP
TYPICAL ACCESS CONTROL RISER DIAGRAM FOR NEW DOORS
NOT TO SCALE
RECESSED 6"X4"X1-1/2" DEEP
OUTLET BOX W/ PLASTER
RING AND FLUSH, BLANK, COVER
PLATE
PROVIDE 4"x4" METAL BOX WITH SINGLE GANG
RAISED COVER AND TYPE "F" CONNECTOR
/WALLPLATE FOR HIRSCH CARD READER/
SCRAMBLE PAD LOCATED ON EXTERIOR SIDE
OF DOOR (INGRESS). MOUNT IN DOUBLE GANG
DEVICE BOX.
FINISHED
FLOOR
TYPICAL DOOR
CEILING
SEE ARCHITECTURAL
DOOR HARDWARE
SPECIFICATIONS
PROVIDE JUNCTION BOXES FOR
CONNECTIONS TO, REQUEST TO
EXIT, PUSH TO EXIT, ELECTRIC
STRIKE AND/OR MAGNETIC LOCK
AND DOOR CONDUIT ON INTERIOR
ROOM SIDE OF DOOR, TYPICAL.
STUB 1" CONDUITS, WITH
BUSHINGS TO ACCESSIBLE
LOCATION ABOVE CORRIDOR.
FIRE SEAL CONDUITS, AS REQUIRED.
CARD ACCESS SYSTEM RISER
NOT TO SCALE.
DOOR CONTROLLER SYSTEM. CONNECT TO
MAIN CAMPUS SERVER WITH IP MODULE
(HIRSCH DIGITRAC MODEL 8 ACCESS
CONTROL PANEL WITH LAN OPTION)
RS-485
CAT 6
TO CARD READER
TO DOOR LOCK
TO DOOR CONTACT
PROVIDE DOOR LOCK AND READER
POWER SUPPLY. PROVIDE REQUEST TO
EXIT FOR EACH DOOR. TO OTHER DOOR
CONTROLLERS
TYPICAL
MOUNTING HEIGHT VARIES 46" UNLESS
NOTED OTHERWISE ON PLANS
INSTALL MINIMUM 3/4" METAL CONDUIT
SLEEVE INSIDE WALL UP THROUGH
CEILING AND TERMINATE ABOVE
CORRIDOR. (ONE CONDUIT REQUIRED
FOR ALL LOW VOLTAGE CABLES)
NOTE:
1. DOES NOT REPRESENT ACTUAL NUMBER OF DEVICES CHECK PLAN VIEW FOR EXACT NUMBER.
2. SECURITY SYSTEM TO BE MODIFIED, PROVIDED AND INSTALLED BY OWNERS SECURITY SYSTEM
PROVIDER - REDHAWK
3. ALL CABLES SHALL BE IN CONDUIT OR IN CABLE TRAY. MINIMUM CONDUIT SIZE SHALL BE 3/4".
CONDUIT TO DOOR FRAME
FOR DOOR CONTACT TO
SECURITY SYSTEM
CONDUIT FOR DOOR LOCK
DOOR
NOTES:
1. CONTROL WIRING SHALL BE PER MANUFACTURER.
2. POWER WIRING SHALL BE PER MANUFACTURER.
3. CONTRACTOR SHALL COORDINATE W/ OWNER AND 3.
CONTRACTOR SHALL COORDINATE W/ OWNER AND
ARCHITECT FOR INSTALLATION/LOCATION AND
CONNECTION OF ACCESS CONTROL EQUIPMENT.
FIPS 201 CARD READER AND/OR SCRAMBLE PAD
120V FROM
NEAREST
EMERGENCY
POWER
SOURCE
TYPICAL
DOOR OR GATE WITH ACCESS
CONTROL
TRANSFER HINGE OR
SIMILAR, SEE
ARCHITECTURAL
HARDWARE SPECIFICATIONS
ELECTRIC MORTISE
LOCK, SEE
ARCHITECTURAL
HARDWARE
SPECIFICATIONS
TO LOCAL ALARM
HORN/STROBE
TO IRM ROOM LOCAL
AREA NETWORK
TO FIRE ALARM CONTACT
OUTPUT MODULE TO
RELEASE DOORS WITH A
LOCAL FIRE SIGNAL.
REQUEST TO EXIT
OCCUPANCY SENSOR
OR BUTTON
REQUEST TO EXIT SENSOR
OR BUTTON
TO ACCESS CONTROL
PANEL. LOCATE IN
NEAREST IRM CLOSET
CONDUITS W/ ACCESS
CONTROL CABLES
EXACQ Z SERIES - IPS-6000-R2 6TB
NVR WITH SERVER AND CLIENT
SOFTWARE PROVIDE NEW LICENSE
FOR EACH CAMERA PROVIDED
UNDER THIS PROJECT
CATEGORY 6 CABLE
IP CAMERA CCTV SYSTEM RISER
NOT TO SCALE
CATEGORY 6 CABLE, TYPICAL
ARECONT #AV81185DN-HB OR
AV8365DN-HB CAMERA AS
INDICATED ON THE DRAWINGS
CISCO SG-300-52MP GIGABIT SWITCH WITH POWER OVER
ETHERNET AND LAYER 3, DHCP SERVER
LOCATE IN LEVEL TWO POLICE ROOM IN DATA RACK.
PROVIDE WITH 1000 BASE SFP MODULE
CA
CAR
IP
120V FROM NEAREST EMERGENCY POWER SOURCE
FIBER OPTIC: 2 STRAND OM 4
CABLE IN 3/4" RGS
CATEGORY 6 CABLE
120V FROM NEAREST
EMERGENCY POWER
SOURCE
120V FROM NEAREST
EMERGENCY POWER
SOURCE
HOFFMAN NEMA 4 STAINLESS STEEL
LOCKABLE ENCLOSURE WITH MOUNTING
BRACKET AND DIN RAILS.
TRANSITION NETWORKS 19 SLOT CHASSIS RACK
MOUNTED MEDIA CONVERTOR: CPSMC1910-
100/CPSMM-120/CPSFM-200/CSPFP-200/CPSLD-
100/CPSRE-230 MOUNTED IN POLICE ROOM
DATA RACK.
PO
W
ER
V
TRANSITION NETWORKS MEDIA CONVERTER
MODULE: CGFEB1039-120 (SEE PLANS FOR
CAMERA QUANTITIES)
TRANSITION HARDENED PoE MEDIA
CONVERTER: SI-IES-121D-LRT WITH
(1)TN-SFP-SXD MODULE
TRANSITION DIN RAIL MOUNTED POWER
SUPPLY: 25130 48VDC OUT 39.8 WATTS
>100M
<100M
(4) OM4 TO BUILDING 2 VIA
GARAGE IRM ROOM.
100 METER MAX.
EACH ENCLOSURE CAN
SUPPORT TWO CAMERA
(TYPICAL).
ARECONT #AV1455DN-S-NL
WITH LENS MPM2.8 MICRO
DOME IP CAMERA AS SHOWN
ON THE DRAWINGS AT STAIRs
AND ELEVATOR TOWER,
DENOTED BY MI-2.8
GROUND FLOOR
FIRST FLOOR
BASEMENT FLOOR
BASEMENT BUILDING 2
PARKING
GARAGE
FLOOR MOUNTED RACK
HUBBLE RACK H2N8432Z4 WITH
PR20620 VERTICAL POWER STRIP,
TYPICAL.
POLICE
SECURITY
DATA ROOM
295' MAXIMUM LENGTH TYPICAL FOR ALL
TELECOMMUNICATIONS RISER
NOT TO SCALE
IRM DATA
ROOM
DIMENSIONS PROVIDED FOR INFORMATION ONLY.
PROVIDE CLEARANCE FOR FRONT AND BACK OF
RACK; RACK IS 15" DEEP.
2"x1/4"x24" COPPER
GROUND BUS
(TYPICAL)
1#1/0AWG - 3/4"C TO
ELECTRICAL ROOM
GROUND BUS
1#6AWG - 3/4"C GROUND
BETWEEN ALL GROUND
BUSES (TYPICAL)
PROVIDE PATCH PANELS WITH CATEGORY 6
JACKS. PROVIDE DEDICATED PATCH PANELS.
COMPUTER NETWORK
ACTIVE EQUIPMENT (BY OWNER)
TERMINATE ALL 50/125 (OM4) FIBERS & ALL SINGLE
MODE (OS2) FIBERS ON SEPARATE SHELVES WITH ST
TYPE CONNECTORS. PROVIDE 12 STRANDS OF OM4
AND 12 STRANDS OF OS2 IN LOOSE TUBE
CONFIGURATION.
BUILDING
ENTRANCE
TERMINAL 110
BLOCKS
FIRE RETARDANT PLYWOOD
BACKBOARD 8'-0"H x 3/4"D.
LOCATE ON ALL WALLS
EXCEPT AT DOOR.
FLOOR MOUNTED RACK
MULTI-MODE TERMINATION SHELVES
SINGLE-MODE TERMINATION SHELVES
TERMINATE 50-PAIR PIC RISER
RATED TELEPHONE ON BUILDING
ENTRANCE TERMINAL 110 BLOCKS
EQUAL TO CIRCA TELECOM 50 PAIR
INDOOR BET 1880ECA1-50.
50 PAIR PIC RISER RATED TELEPHONE CABLES TO
EXISTING IRM TELEPHONE SWITCH ROOM AB25 IN
BUILDING 2 TERMINATE ON BUILDING ENTRANCE
TERMINAL 110 BLOCKS.
PROVIDE4 STRANDS OF OM4 IN
TIGHT-BUFFERED CONFIGURATION
TO SECURITY RACK IN POLICE
DATA ROOM.
2-1/2" CONDUIT WITH 12 STRAND OM4
AND 12 STRAND OS2 AND 50 PAIR PIC
CABLES ROUTED FROM EXTERIOR WALL
VIA THE CORRIDOR TO THE IRM DATA
AND TELEPHONE ROOMS
IRM
COMPUTER
ROOM AB28
IRM
TELEPHONE
ROOM AB25
BUILDING
ENTRANCE
TERMINAL 110
BLOCKS
EXISTING 110 BLOCK IN
EXISTING RACK
PROVIDE 50 PAIR PIC
TELEPHONE CABLE TO
EXISTING RACK
50 PAIR PIC TELEPHONE CABLES
12 STRAND OM4 AND 12 STRAND
OS2 FIBER OPTIC CABLES
EXISTING
FIBER RACK
MULTI-MODE TERMINATION SHELF
SINGLE-MODE TERMINATION SHELF
HUBBELL FPR3SP FIBER OPTIC
INTERCONNECTION SHELVES WITH
TWO FSPSTDS3 ST ADAPTER
PANELS, EACH SHELF.
1-WHITE CATEGORY 6, (PLENUM
RATED CABLES, TYPICAL) PROVIDE ALL
TERMINATIONS
PROVIDE 4-RJ-45, CATEGORY 6
JACKS FOR DATA AND TELEPHONE
WITH WALLPLATE. QUANTITY, TYPE
AND LOCATION AS NOTED ON THE
INSTALLATION DRAWINGS, TYPICAL.
MAXIMUM OF FOUR POSITIONS PER
WALLPLATE.
2-34
LABEL ALL FACEPLATES
WITH PATCH PANEL/JACK
NUMBER. (TYPICAL FOR ALL)
1-WHITE JACK AT WALL PHONE / CALL
BOX, TYPICAL.
PROVIDE 50 PAIR 110 CONNECTOR
SERIES INDOOR BUILDING
ENTRANCE TERMINAL(BET) WITH
SPLICE CHAMBER AND COVER,
EQUAL TO CIRCA MODEL#
1180ECA1-50. MODULES SHALL BE
300V SOLID STATE WITH PTC
EQUAL TO CIRCA MODEL# 4B1S-
300.
PROVIDE 50 PAIR 110 CONNECTOR SERIES INDOOR
BUILDING ENTRANCE TERMINAL(BET) WITH SPLICE
CHAMBER AND COVER, EQUAL TO CIRCA MODEL#
1180ECA1-50. MODULES SHALL BE 300V SOLID STATE
WITH PTC EQUAL TO CIRCA MODEL# 4B1S-300.
PROVIDE 12"X12" JUNCTION BOX
HUBBELL FPR3SP FIBER OPTIC
INTERCONNECTION SHELVES WITH
TWO FSPSTDS3 ST ADAPTER PANELS,
EACH SHELF, TYPICAL.
MULTI-MODE TERMINATION SHELF
EXACQ Z SERIES - IPS-6000-R2 6TB
NVR WITH SERVER AND CLIENT
SOFTWARE.
CISCO SF-300-24P GIGABIT SWITCH WITH
POWER OVER ETHERNET AND LAYER 3,
DHCP SERVER
SEE IP CAMERA RISER FOR
CONTINUATION AND PLANS FOR
CAMERA LOCATIONS
NEW MANHOLE #10G
AT GARAGE, SEE SITE
PLAN FOR LOCATION
12 STRAND OM4 AND 12 STRAND OS2
CABLES TO EXISTING IRM COMPUTER
ROOM AB28 IN BUILDING 2 AN
TERMINATE AT NEW FIBER SHELF
PROVIDE JUNCTION BOX AT CONDUIT
BUSHINGS AND ROUTE NON-METALIC FLEX IN
MANHOLE TO SEPARATE TEL/COM CABLES,
TYPICAL.
PROVIDE 12"X12" JUNCTION BOX
1-WHITE JACK, TELEPHONE
1-YELLOW JACK, DATA
1-BLUE JACK, DATA
1-GREEN JACK, DATA
TYPICAL.
1-WHITE CATEGORY 6,
1-YELLOW CATEGORY 6,
1-BLUE CATEGORY 6,
1-GREEN CATEGORY 6,
(PLENUM RATED CABLES, TYPICAL)
PROVIDE ALL TERMINATIONS AND TERMINATE CABLES
PER WALLPLATE IN SEQUENCE ON PATCH PANEL.
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h a lf i nc f oo t 6" th re e i nc f oo t 6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
Denis McLaughlin Telephone: 857-364-5149
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
6/15/2015
ELECTRICAL - SYSTEMS ONE-LINE RISER
DIAGRAMS
E003
MTF/AJZBSS 65
PARKING LOT # 2
TOWER # 2
STAIR
TANK #1
4,000 GAL
DIESEL UST
100 GAL.
DAY TANK
5,000 KVA
ENCLOSURE
644 GAL.
HIGH VOLTAGE
5,000 KVA
ENCLOSURE
554 GAL.
HIGH VOLTAGE
GENERATOR
EMERGENCY
(350 KW)
(527 AMP)
GRASS
LAWN
C.B.
EXIT
EXIT
DOOR
EMERG.
& STAIRS
ASPHAULT
PARKING LOT
TOT SPO
CHILD
DEVELOPM
CENTER
N E W
A
LU
M
IN
U M
H P
R A M P
D O W N
W
ID
E
"C"
HAND
HOLE
2"
S.M.H.
SMH
8"
8"
8"
S
AN
IT
AR
Y S
EW
ER
SANITARY SEWER
8"
SEWER
SEWER
SEWER
SIGNAL
SIGNAL
SHUT-OFF
WATER
VALVE
S.D.
C.B.
C .B
C .B
S.D.
M.H.
150 KVA
TRANSFORMER
140 GAL.
GRASS
LAWN
PINE
TREE
PARTITION
1 HR SMOKE
GENERATOR
600 KW
EXISTING
DISCONNECT
CABINET
GENERATOR
CONTROL
P3S-B-J6
PANEL
(ELEVATOR)
A4E-2
ATS
PACK
BATTERY
GENERATOR
P3C-B-J6
PANEL
PANEL
P4E-B-J6 DISCONNECT
MICU
(VAC. & AIR)
CONTROL PANEL
DAY TANK
FEEDER #2
LINE # 443-2211
METERING
TERMINAL
STRIPS
SWITCHBOARD "B", X-RAY
VAULT #3
BLDG #1
BREAKER
TIE
BUILDINGS 1 & 3
FIRE PUMP
STRIPS
TERMINAL
METERING
LINE # 374-2215
FEEDER #1
BLDG. #3
TRAILER COMPLEX
BLDG'S 5,7,8,10,22,30 & 20
SWITCHBOARD
5 KV FEEDER OUTDOOR
BREAKER
CHILLER
SWITCHBOARD "A"
VAULT #3
BLDG #1
GENERAL SIDE
TRANSFORMER
ROOM BLDG . #2
ROOM BLDG . #2
MECHANICAL SIDE
TRANSFORMER
POWER CIRCUIT
BREAKER
DISTRIBUTION
TO PRIMARY
EDISON
TEST CABINET
HIGH VOLTAGE
CONTROLLER
JOCKEY PUMP
ATS
A4E-1
SUB STATION
50A
PANEL
(LIEBERT)
STAND
ALONE
DISCONNECT
AIR
HANDLER
A/C
CONDENSER
DISCONNECT
INVERTER
PANEL
FIRE PUMP
CONTROLLER
FIRE
PUMP
100 H.P.
PUMP
JOCKEY
PANEL
P3G-BJ-6
930 SF
F/A pull box from bldg 88
UPS-1
P4 -E
TELE RM.
A/C AIR
HANDLER
45 KVA
%Z 5.8 480-120/208V, 3�, 4W
DPB1
P3 N
BH
ATS # B2-ATS-8
ATS
ATSATSATSATS
BCU BCU
EM
ER
G
EN
CY
B O
A R
D B
EM
ER
G
EN
CY
B O
A R
D A
N O
RM
A
L B
O A
R D
S 3 N
-B -H
M
E C H
#A3S-1
B2-ATS-5
#A4E-1
B2-ATS-4
#A3C-1
B2-ATS-2
#A3C-2
B2-ATS-1
#AB-24
B2-ATS-3
#A4E-2
B2-ATS-6
SPD-1
DIS. 30A
STERILIZER
COMPRESSOR
L3
SB
E3
100A SMOKE
SHACK
DISCONNECT
NEQB1B
DISCONNECT 60A
"TRISBG5" 15 KVA 480-120/208V, %Z 4.55, 3�, 4W
R
IS
BG
R
IN
BG
SN3-B-H2
SWITCHBOARD
GENERAL SIDE
400 AMP
480V, 3PH, 4 WIRE
EXISTING
18 POLE MLO PANEL
NEW FLOOR
EVAPORATOR
1PM4E
SCHWP-1
60A
FUSED DIS.
P1
R
IE
BG
RI
CB
G
112.5
KVA %Z
5.8 120- 25V, 3�, 4W
R
IN
BE
L3 N
BE
RINBE5A
"TRIN B" 30
KVA
480-120/208V, %Z 5.8, 3�, 4W
SCHWP-2
60A
FUSED DIS.
ATS # AC3-3
ATS # A4E-07
ATS # A4E-05
P3 G
BJ
MTS # OFFICE
TRAILERS
MTS # FISHERHOUSE
DIS. FOR
MCC (MED
VAC & AIR)
"TRIN C"
45 KVA
480-120/208V, %Z 6.3, 3�, 4W
DISCONNECT 100A
"T-IE-3"
75 KVA
480-120/208V, %Z 4.25, 3�, 4W
"T-SPD-1"
30 KVA
480-120/208V, %Z 5.8, 3�, 4W
DISCONNECT 100A
"TP1" 15
KVA
480-120/208V, %Z 4.79%, 3�, 4W
ATS
FD
WASH
EYE
FD
FD
FD
ELEV.
ELEV.
ELEV.
UNEXCAVATED
SHAFT
STERILIZERS
PIPE
SPACE
A-B23
A-B26
TELEPHONE
PUBLIC
A-B1
A-B19A
ST1-B
ST2-B
A-B27
LADDER
A-B19
A-B19B
A-B21B
A-B21
A-B21A
A-B4
A-B6
A-B5A-B7
A-B3
A-B1B
A-B1A
A-B31 A-B30
A-B12
A-B11 A-B9
FAC #67
WALL
FIXED
WALL
FIXED
LADDER
FAC
#66
A-CB1
A-CB4
A-CB5
A-CB2
A-CB3
A-CB6
A-CB7
FAC
#65
FAC
#64DF
A-B15
A-B14
A-B16A
A-B17A
A-B13B
A-B13A
#63
FAC
SWITCHGEAR
IRM TELEPHONE
A-B25
ROOM
684 SF
SWITCHGEAR
1096 SF
ROOM
A-B28
IRM COMPUTER
BREAK DOWN
AREA
SPD
SWITCHGEAR
ROOM
1162 SF
A-B18
ELECTRICAL
AUTOMATIC
TRANSFER
SWITCH ROOM
A-B18A
HAC
EQUIPMENT
4,337 SF
ROOM
A-B13
AIR HANDLING
565 SF
GENERATOR
EMERGENCY
A-B16
ROOM
HIGH VOLTAGE
SWITCHGEAR
ROOM
A-B17
STORAGE
ROOM
419 SF
A-B22 A/C
CONTROL
CENTER
254 SF
A-B20 A/C
SPD
DECONTAMINATION
ROOM
RECEIVING &
ROOM
LOCKER
MALE EMPOYEE
FIRE ALARM
ROOM
414 SF
A-B24
ENGINEERING
STAIR #1
STAIR #2
SPD BREAK
ROOM
MALE
LOUNGE
EMPLOYEE
LOCKER
ROOM
MALE EMPOYEE
LOCKER
ROOM
MALE EMPOYEE
MALE
LOUNGE
EMPLOYEE
EMPLOYEE
TOILET
MALE
EQUIPMENT
STORAGE
SPD
OFFICE
SPD
OFFICE
SPD
TORAGE
PPLIES &
CLEAN
SPD
STORAGE
SPD
ROOM
82 SF
FIRE ALARM
A-B2CART WASH
SPD
STILL
MALE LOCKERS FEMALE LOCKERS
STORAGE
EMS
ROOM
1,416 SF
EQUIPMENT
A-B10
POOL
PIPE
SPACE
LOBBY
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
SOILED
LINEN
SOILED
TRASH
AREAWAY
AREAWAY
AREAWAY
FRESH
TUNNEL
AIR
RS
BREAK DOWN
AREA / STORAGE
SPD
U P
U P
SED
UTER
OR
RAMP
UP
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
DEMO EXISTING 480V MANHOLE AND
EMTPY MANHOLE. REMOVE MANHOLE,
ASSOCIATED WIRING AND GROUNDING,
RECONNECT DRAINS AS REQUIRED.
SEE NEW ELECTRICAL SITE PLAN FOR
RELOCATION OF SERVICES.
EXTENT OF SITE DEMOLITION OF
EXISTING ELECTRICAL SERVICES SHALL
BE COORDINATED WITH GARAGE
FOUNDATION EARTH WORK.
REMOVE EXISTING SITE LIGHTING,
RELOCATE TO LOCATION AS SHOWN ON
ELECTRICAL SITE PLAN NEW
REMOVE EXISTING SITE LIGHTING, RELOCATE
TO LOCATION AS SHOWN ON ELECTRICAL SITE
PLAN NEW. FIXTURES SHALL BE CLEANED AND
RELAMPED, TYPICAL.
REMOVE EXISTING SITE LIGHTING, AS
SHOWN AND TURN OVER FIXTURES NOT
REUSED TO OWNER, AND TRANSPORT
FIXTURE TO OWNER'S STORAGE LOCATION.
ELECTRICAL SITE PLAN - ALTERNATE. EXISTING
SITE LIGHTING TO REMAIN. FIXTURES SHALL BE
CLEANED AND RELAMPED, TYPICAL.
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h a lf i nc f oo t 6" th re e i nc f oo t 6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
Denis McLaughlin Telephone: 857-364-5149
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% - BID DOCUMENTS
06/15/2015
ELECTRICAL - SITE PLAN DEMO
ES100
MLCRAN 66
1" = 20'-0" Electrical - Site Plan Demo
SMH
8"
8"
8"
SEWER
SEWER
SEWER
SIGNAL
SIGNAL
SHUT-OFF
WATER
VALVE
S.D.
C.B.
C .B
C .B
S.D.
M.H.
K
150 KVA
TRANSFORMER
140 GAL.
GRASS
LAWN
PINE
TREE
6.90'
N °5 7'
L = R =
CONCRETE
ASPHAULT
D
D S
S
D D
D
D
D
D
D D
D
D D
S
8" PVC @
5.43%
P V C
.5
R C P
CONC
BLOCKS
JE
R
SE
Y
BA
R
R
IE
R S x x x x x x x x x x x x x
CONC
BLOCKS
JE
R
SE
Y
BA
R
R
IE
R S x x x x x x x x x x x x x
PARTITION
1 HR SMOKE
POOL
15 KVA XFMR
480-120/208V, %Z 5.1, 3�, 4W
GENERATOR
600 KW
EXISTING
DISCONNECT
CABINET
GENERATOR
CONTROL
P3S-B-J6
PANEL
(ELEVATOR)
A4E-2
ATS
PACK
BATTERY
GENERATOR
P3C-B-J6
PANEL
PANEL
P4E-B-J6 DISCONNECT
MICU
(VAC. & AIR)
CONTROL PANEL
DAY TANK
FEEDER #2
LINE # 443-2211
METERING
TERMINAL
STRIPS
SWITCHBOARD "B", X-RAY
VAULT #3
BLDG #1
BREAKER
TIE
BUILDINGS 1 & 3
FIRE PUMP
STRIPS
TERMINAL
METERING
LINE # 374-2215
FEEDER #1
BLDG. #3
TRAILER COMPLEX
BLDG'S 5,7,8,10,22,30 & 20
SWITCHBOARD
5 KV FEEDER OUTDOOR
BREAKER
CHILLER
SWITCHBOARD "A"
VAULT #3
BLDG #1
GENERAL SIDE
TRANSFORMER
ROOM BLDG . #2
ROOM BLDG . #2
MECHANICAL SIDE
TRANSFORMER
POWER CIRCUIT
BREAKER
DISTRIBUTION
TO PRIMARY
EDISON
TEST CABINET
HIGH VOLTAGE
CONTROLLER
JOCKEY PUMP
ATS
A4E-1
SUB STATION
50A
PANEL
(LIEBERT)
STAND
ALONE
DISCONNECT
AIR
HANDLER
A/C
CONDENSER
DISCONNECT
INVERTER
PANEL
FIRE PUMP
CONTROLLER
FIRE
PUMP
100 H.P.
PUMP
JOCKEY
PANEL
P3G-BJ-6
930 SF
F/A pull box from bldg 88
UPS-1
P4 -E
TELE RM.
A/C AIR
HANDLER
45 KVA
%Z 5.8 480-120/208V, 3�, 4W
DPB1
P3 N
BH
ATS # B2-ATS-8
ATS
ATSATSATSATS
BCU BCU
EM
ER
G
EN
CY
B O
A R
D B
EM
ER
G
EN
CY
B O
A R
D A
N O
RM
A
L B
O A
R D
S 3 N
-B -H
M
E C H
#A3S-1
B2-ATS-5
#A4E-1
B2-ATS-4
#A3C-1
B2-ATS-2
#A3C-2
B2-ATS-1
#AB-24
B2-ATS-3
#A4E-2
B2-ATS-6
SPD-1
DIS. 30A
STERILIZER
COMPRESSOR
L3
SB
E3
100A SMOKE
SHACK
DISCONNECT
NEQB1B
DISCONNECT 60A
"TRISBG5" 15 KVA 480-120/208V, %Z 4.55, 3�, 4W
R
IS
BG
R
IN
BG
SN3-B-H2
SWITCHBOARD
GENERAL SIDE
400 AMP
480V, 3PH, 4 WIRE
EXISTING
18 POLE MLO PANEL
NEW FLOOR
EVAPORATOR
1PM4E
SCHWP-1
60A
FUSED DIS.
P1
R
IE
BG
RI
CB
G
112.5
KVA %Z
5.8 120- 25V, 3�, 4W
R
IN
BE
L3 N
BE
RINBE5A
"TRIN B" 30
KVA
480-120/208V, %Z 5.8, 3�, 4W
SCHWP-2
60A
FUSED DIS.
ATS # AC3-3
ATS # A4E-07
ATS # A4E-05
P3 G
BJ
MTS # OFFICE
TRAILERS
MTS # FISHERHOUSE
DIS. FOR
MCC (MED
VAC & AIR)
"TRIN C"
45 KVA
480-120/208V, %Z 6.3, 3�, 4W
DISCONNECT 100A
"T-IE-3"
75 KVA
480-120/208V, %Z 4.25, 3�, 4W
"T-SPD-1"
30 KVA
480-120/208V, %Z 5.8, 3�, 4W
DISCONNECT 100A
"TP1" 15
KVA
480-120/208V, %Z 4.79%, 3�, 4W
ATS
FD
WASH
EYE
FD
FD
FD
ELEV.
ELEV.
ELEV.
UNEXCAVATED
SHAFT
STERILIZERS
PIPE
SPACE
A-B23
A-B26
TELEPHONE
PUBLIC
A-B1
A-B19A
ST1-B
ST2-B
A-B27
LADDER
A-B19
A-B19B
A-B21B
A-B21
A-B21A
A-B4
A-B6
A-B5
A-B3
A-B1B
A-B1A
A-B31 A-B30
A-B12
A-B11 A-B9
FAC #67
WALL
FIXED
WALL
FIXED
LADDER
FAC
#66
A-CB1
A-CB4
A-CB5
A-CB2
A-CB3
A-CB6
A-CB7
FAC
#65
FAC
#64DF
A-B15
A-B14
A-B16A
A-B17A
A-B13B
A-B13A
#63
FAC
SWITCHGEAR
IRM TELEPHONE
A-B25
ROOM
684 SF
SWITCHGEAR
1096 SF
ROOM
A-B28
RM COMPUTER
BREAK DOWN
AREA
SPD
SWITCHGEAR
ROOM
1162 SF
A-B18
ELECTRICAL
AUTOMATIC
TRANSFER
SWITCH ROOM
A-B18A
HAC
EQUIPMENT
4,337 SF
ROOM
A-B13
AIR HANDLING
565 SF
GENERATOR
EMERGENCY
A-B16
ROOM
HIGH VOLTAGE
SWITCHGEAR
ROOM
A-B17
STORAGE
ROOM
419 SF
A-B22 A/C
CONTROL
CENTER
254 SF
A-B20 A/C
SPD
DECONTAMINATION
ROOM
RECEIVING &
ROOM
LOCKER
MALE EMPOYEE
FIRE ALARM
ROOM
414 SF
A-B24
ENGINEERING
STAIR #1
STAIR #2
SPD BREAK
ROOM
MALE
LOUNGE
EMPLOYEE
LOCKER
ROOM
MALE EMPOYEE
LOCKER
ROOM
MALE EMPOYEE
MALE
LOUNGE
EMPLOYEE
EMPLOYEE
TOILET
MALE
EQUIPMENT
STORAGE
SPD
OFFICE
SPD
OFFICE
SPD
STORAGE
SPD
ROOM
82 SF
FIRE ALARM
A-B2CART WASH
SPD
STILL
MALE LOCKERS FEMALE LOCKERS
STORAGE
EMS
ROOM
1,416 SF
EQUIPMENT
A-B10
POOL
PIPE
SPACE
LOBBY
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
SOILED
LINEN
SOILED
TRASH
AREAWAY
AREAWAY
AREAWAY
FRESH
TUNNEL
AIR
BREAK DOWN
AREA / STORAGE
SPD
U P
U P
RAMP
UP
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
11.6
ELEC
ELEC
ELEC
ELEC
PROVIDE 100A, NEMA 4X
DISCONNECT FOR SWITCH GEAR
FEEDERS AND ALARMSPROVIDE 50 PAIR 110 CONNECTOR SERIES INDOOR
BUILDING ENTRANCE TERMINAL(BET) WITH SPLICE
CHAMBER AND COVER, EQUAL TO CIRCA MODEL#
1180ECA1-50. MODULES SHALL BE 300V SOLID STATE
WITH PTC EQUAL TO CIRCA MODEL# 4B1S-300.
CONNECT FROM BET
TO RACK MOUNTED
SPARE 110 BLOCKS
PROVIDE NEW FIBER
SHELVE. CONNECT #
STRANDS 50/125 OM4
FIBER OPTIC CABLE.
PROVIDE 5"x5" JUNCTION BOX AT
ACCESSABLE LOCATION ABOVE
CEILING.
PROVIDE NEW
MANHOLE #10G
PROVIDE NEW MANHOLE #10,
NEAR EXISTING DUCTBANK.
HAND DIG AS REQUIRED NEAR
EXISTING UTILITIES
CONNECT TO EXISTING
DISCONNECT AT PRIMARY
SIDE OF TRANSFORMER.
(2) 4"C FOR POWER WIRING:
• (1) 4"C AND (1) 1"C PVC SIGN AND SIGNAL
• (1) 4"C PVC SWITCH YARD LTS
SEE ONE-LINE FOR QUANTITIES/SIZES.
4"C FOR COMMUNICATION WIRING:
• (1) 50 PAIR PIC CU
• 12 STRANDS OF OM4 AND 12 STRANDS OF OS2 FIBER OPTIC CABLE
4"C WITH ATS CONTROL WIRES TO GEN
CONTROL IN BUILDING #2, SEE ONE-
LINE FOR QUANTITIES/SIZES.4"C WITH EMERGENCY FEEDER
FROM BUILDING #2, SEE ONE-
LINE FOR QUANTITIES/SIZES.
EXISTING (2) 4" CONDUITS, INTERCEPT
AND EXTEND TO MANHOLE. PROVIDE
WIRING FROM BUILDING 2 TO EXISTING
TRANSFORMER(S).
1#4/0 GROUND LOOP AROUND
BUILDING
(4) 4"C CONDUCTORS FOR FISHER
HOUSE, TRAILERS, VA SIGN, AND MISC.
LIGHTS, FEED FROM BUILDING #2, SEE
ONE-LINE FOR QUANTITIES/SIZES.
(1) 4"C PVC FISHER HOUSE
POWER, APPROXIMATE LOCATION
2 SETS OF 4"C DUCTBANK WITH NORMAL
FEEDERS, SEE ONE-LINE FOR
QUANTITIES/SIZES.
(2) 4"C DUCTBANK WITH 4160V NORMAL
FEEDERS, SEE ONE-LINE FOR
QUANTITIES/SIZES.
2-1/2"C FOR COMMUNICATION
CABLES ROUTED ABOVE CORRIDOR
CEILING.
EXISTING (1) 4"C
PVC TRAILERS
POWER
ES501
ES501
ES501
ES501
ES501
TR
ES501
MH
ES501
CP
ES501
CP1
ES501
MP
ES501
COMMUNICATION HANDHOLE WITH
TEL/DATA, FIRE ALARM, SECURITY
& PA CONDUIT TO REMAIN,
PROTECT CONDUCTORS DURING
CONSTRUCTION.
300kVA 4160V -> 480Y/277V
TRANSFORMER
PROVIDE NEMA 1 JUNCTION BOXES ON
BASEMENT WALLS AT CONDUIT ENTRANCE.
SEAL ALL CONDUIT ENTRANCES, SEE
DETAILS.
EXISTING TEL, DATA, FIRE
ALARM, SECURITY AND PA
CABLES JUNCTION BOX FOR
FISHER HOUSE/TRAILERS, TO
REMAIN, .PROTECT CONDUITS
AND CONDUCTORS DURING
CONSTRUCTION.
FIBER OPTIC CABLES ROUTED TO SECOND
LEVEL IRM AND POLICE CLOSETS, SEE
ELECTRICAL FLOOR PLANS, AND RISER FOR
CONTINUATION.
EMERGENCY FEEDER AND ATS CONTROL
WIRING TO LEVEL 1 EM. ELECTRICAL ROOM,
SEE ELECTRICAL FLOOR PLANS, AND RISER
FOR CONTINUATION.
NORMAL FEEDER TO LEVEL 1 EM. ELECTRICAL
ROOM, SEE ELECTRICAL FLOOR PLANS, AND
RISER FOR CONTINUATION.
SWITCHGEAR BUILDING 70
EXISTING 5kV
SWITCHGEAR
SPARE 5kV BREAKER NEW LOCATIONS FOR
RELOCATED SITE LIGHTING
FIXTURES
AT EXISTING EMERGENCY SWITCHBOARD 'S3E-B-2A'
UTILIZE SPARE 400AF BREAKER, PROVIDE NEW TRIP
PLUG, SEE ELECTRICAL RISER/ONE-LINE.
GENERATOR CONTROL PANEL
AT DOUBLE DOORS OF SWITCHGEAR
BUILDING, SAW CUT AND PATCH
EXISTING CONCRETE. TRENCH FOR (2)
4"C TO 5kV SWITCHGEAR.
COORDINATE LIGHT FIXTURE
INSTALLATION WITH PARKING LOT
AND ISLAND RECONFIGURATION,
SAW CUT AND PATCH PAVEMENT
REQUIRED FOR NEW CONDUITS.
ALTERNATE DEDUCT #1
RELOCATE CAMPUS PRIMARY FEEDERS AND
DUCTBANK.
NOTE: INFRASTRUCTURE UNDER THIS
DEDUCT SHALL BE UTILIZED BY THE WEST
ROXBURY ELECTRICAL UPGRADE, PHASE II,
PROJECT # 523A4-13-208 WHICH WILL PROVIDE
A NEW CAMPUS SUBSTATION.
PROVIDE TEMPORARY (2) 5" CONDUITS TO EXISTING
1200A SWITCH. WIRE 2 SETS OF 3#750kCMIL CU, 5kV, 1-750kCMIL CU, THHW, 1#4/0AWG CU, THHW
GROUND
INSIDE OF SUBSTATION FENCE RISE DUCTBANK
ABOVE GRADE TO EXISTING SWITCHGEAR. CUT
ENCLOSURE FOR CONDUITS ACCESS AND INSTALL
BUSHINGS. CONCRETE ENCASE DUCTBANK ABOVE
GRADE.
PROVIDE (4) 5"DUCTBANK WIRE DUCTBANK WITH 2
SETS OF 3#750kCMIL CU, 5kV, 1-750kCMIL CU, THHW, 1
#4/0AWG CU, THHW GROUND. PROVIDE 500#
PULLCORD IN THE 2 SPARE CONDUITS WITH CAP, SEE
ELECTRICAL SITE DETAILS.
PROVIDE (4) 2"DUCTBANK PROVIDE 500# PULLCORD IN
EACH CONDUIT, SEE ELECTRICAL
SITE DETAILS.
SUBSTATION BUS 'B'
SUBSTATION BUS 'A'
PRIMARY MANHOLE SIZES
8"Wx8"Lx7'H WITH 3' DIA
COVER & FRAME, SEE
DETAILS.
SMALL MANHOLE SIZES
3"Wx3"Lx2.5'H WITH 3' DIA
COVER & FRAME, TYPICAL
OF 3 LOCATIONS
MH-P1A
MH-P1B
HH-1
MH-P2A
MH-P2B
HH-2
MH-P3A
MH-P3B
HH-3
HS-1
HS-2
MH-P4AB
AT EXISTING CAMPUS PRIMARY DUCTBANK
EXCAVATE AROUND THE DUCTS AND HAND DIG AS
NECESSARY AND SUPPORT EXPOSED DUCTBANK,
INSTALL BOTTOM OF MANHOLE UNDER BOTH
EXISTING DUCTBANKS. ALIGN TOP MANHOLE
WINDOWS AROUND DUCTBANKS. CUT OFF THE
ONE DUCT AT A TIME AND REMOVE LOOSE
CONCRETE TO EXPOSE THE 3 EXISTING 4"C. CUT
AT OR EXTEND TO MANHOLE WALL AND PROVIDE
A REINFORCED-CONCRETE COLLAR, SEE
DUCTBANK DETAILS AND PHASING WORK NOTES.
INTERCEPT EXISTING
SITE LIGHTING CONDUIT
AND INSTALL NEW
HANHOLE
PROVIDE TEMPORARY (2) 5" CONDUITS TO
EXISTING 1200A SWITCH. WIRE 2 SETS OF 3#
750kCMIL CU, 5kV, 1-750kCMIL CU, THHW, 1#
4/0AWG CU, THHW GROUND
AT EXISTING LIGHTING HANDHOLE
INSTALL NEW CONDUIT AND
EXTEND TO NEW SITE LIGHTING
LOCATION.
AT EXISTING LIGHTING HANDHOLE
INSTALL NEW CONDUIT AND EXTEND TO
NEW SITE LIGHTING LOCATION.
PROVIDE (4) 5"DUCTBANK WIRE DUCTBANK WITH 2
SETS OF 3#750kCMIL CU, 5kV, 1#4/0AWG CU, THHW GROUND, AND PROVIDE 1-750kCMIL CU, THHW FOR
USE BY PROJECT 523A4-13-208, CAP CONDUCTORS
FOR FUTURE USE. PROVIDE 500# PULLCORD IN THE 2
SPARE CONDUITS, SEE ELECTRICAL SITE DETAILS.
PROVIDE (4) 2"DUCTBANK PROVIDE 500# PULLCORD IN
EACH CONDUIT, SEE ELECTRICAL
SITE DETAILS.
CONNECT WIRING TO EXISTING SITE LIGHTING AS
REQUIRED.
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h a lf i nc f oo t 6" th re e i nc f oo t 6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
Denis McLaughlin Telephone: 857-364-5149
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% - BID DOCUMENTS
06/15/2015
ELECTRICAL - SITE PLAN NEW
ES101
MLCRAN 67
1" = 20'-0"
Electrical Site New with Primary Ductbank
PARTITION
1 HR SMOKE
POOL
15 KVA XFMR
480-120/208V, %Z 5.1, 3�, 4W
GENERATOR
600 KW
EXISTING
DISCONNECT
CABINET
GENERATOR
CONTROL
P3S-B-J6
PANEL
(ELEVATOR)
A4E-2
ATS
PACK
BATTERY
GENERATOR
P3C-B-J6
PANEL
PANEL
P4E-B-J6 DISCONNECT
MICU
(VAC. & AIR)
CONTROL PANEL
DAY TANK
FEEDER #2
LINE # 443-2211
METERING
TERMINAL
STRIPS
SWITCHBOARD "B", X-RAY
VAULT #3
BLDG #1
BREAKER
TIE
BUILDINGS 1 & 3
FIRE PUMP
STRIPS
TERMINAL
METERING
LINE # 374-2215
FEEDER #1
BLDG. #3
TRAILER COMPLEX
BLDG'S 5,7,8,10,22,30 & 20
SWITCHBOARD
5 KV FEEDER OUTDOOR
BREAKER
CHILLER
SWITCHBOARD "A"
VAULT #3
BLDG #1
GENERAL SIDE
TRANSFORMER
ROOM BLDG . #2
ROOM BLDG . #2
MECHANICAL SIDE
TRANSFORMER
POWER CIRCUIT
BREAKER
DISTRIBUTION
TO PRIMARY
EDISON
TEST CABINET
HIGH VOLTAGE
CONTROLLER
JOCKEY PUMP
ATS
A4E-1
SUB STATION
50A
PANEL
(LIEBERT)
STAND
ALONE
DISCONNECT
AIR
HANDLER
A/C
CONDENSER
DISCONNECT
INVERTER
PANEL
FIRE PUMP
CONTROLLER
FIRE
PUMP
100 H.P.
PUMP
JOCKEY
PANEL
P3G-BJ-6
930 SF
F/A pull box from bldg 88
UPS-1
P4 -E
TELE RM.
A/C AIR
HANDLER
45 KVA
%Z 5.8 480-120/208V, 3�, 4W
DPB1
P3 N
BH
ATS # B2-ATS-8
ATS
ATSATSATSATS
BCU BCU
EM
ER
G
EN
CY
B O
A R
D B
EM
ER
G
EN
CY
B O
A R
D A
N O
RM
A
L B
O A
R D
S 3 N
-B -H
M
E C H
#A3S-1
B2-ATS-5
#A4E-1
B2-ATS-4
#A3C-1
B2-ATS-2
#A3C-2
B2-ATS-1
#AB-24
B2-ATS-3
#A4E-2
B2-ATS-6
SPD-1
DIS. 30A
STERILIZER
COMPRESSOR
L3
SB
E3
100A SMOKE
SHACK
DISCONNECT
NEQB1B
DISCONNECT 60A
"TRISBG5" 15 KVA 480-120/208V, %Z 4.55, 3�, 4W
R
IS
BG
R
IN
BG
SN3-B-H2
SWITCHBOARD
GENERAL SIDE
400 AMP
480V, 3PH, 4 WIRE
EXISTING
18 POLE MLO PANEL
NEW FLOOR
EVAPORATOR
1PM4E
SCHWP-1
60A
FUSED DIS.
P1
R
IE
BG
RI
CB
G
112.5
KVA %Z
5.8 120- 25V, 3�, 4W
R
IN
BE
L3 N
BE
RINBE5A
"TRIN B" 30
KVA
480-120/208V, %Z 5.8, 3�, 4W
SCHWP-2
60A
FUSED DIS.
ATS # AC3-3
ATS # A4E-07
ATS # A4E-05
P3 G
BJ
MTS # OFFICE
TRAILERS
MTS # FISHERHOUSE
DIS. FOR
MCC (MED
VAC & AIR)
"TRIN C"
45 KVA
480-120/208V, %Z 6.3, 3�, 4W
DISCONNECT 100A
"T-IE-3"
75 KVA
480-120/208V, %Z 4.25, 3�, 4W
"T-SPD-1"
30 KVA
480-120/208V, %Z 5.8, 3�, 4W
DISCONNECT 100A
"TP1" 15
KVA
480-120/208V, %Z 4.79%, 3�, 4W
ATS
FD
WASH
EYE
FD
FD
FD
ELEV.
ELEV.
ELEV.
UNEXCAVATED
SHAFT
STERILIZERS
PIPE
SPACE
A-B23
A-B26
TELEPHONE
PUBLIC
A-B1
A-B19A
ST1-B
ST2-B
A-B27
LADDER
A-B19
A-B19B
A-B21B
A-B21
A-B21A
A-B4
A-B6
A-B5-B7
A-B3
A-B1B
A-B1A
A-B31 A-B30
A-B12
A-B11 A-B9
FAC #67
WALL
FIXED
WALL
FIXED
LADDER
FAC
#66
A-CB1
A-CB4
A-CB5
A-CB2
A-CB3
A-CB6
A-CB7
FAC
#65
FAC
#64DF
A-B15
A-B14
A-B16A
A-B17A
A-B13B
A-B13A
#63
FAC
SWITCHGEAR
IRM TELEPHONE
A-B25
ROOM
684 SF
SWITCHGEAR
1096 SF
ROOM
A-B28
IRM COMPUTER
BREAK DOWN
AREA
SPD
SWITCHGEAR
ROOM
1162 SF
A-B18
ELECTRICAL
AUTOMATIC
TRANSFER
SWITCH ROOM
A-B18A
HAC
EQUIPMENT
4,337 SF
ROOM
A-B13
AIR HANDLING
565 SF
GENERATOR
EMERGENCY
A-B16
ROOM
HIGH VOLTAGE
SWITCHGEAR
ROOM
A-B17
STORAGE
ROOM
419 SF
A-B22 A/C
CONTROL
CENTER
254 SF
A-B20 A/C
SPD
DECONTAMINATION
ROOM
RECEIVING &
ROOM
LOCKER
MALE EMPOYEE
FIRE ALARM
ROOM
414 SF
A-B24
ENGINEERING
STAIR #1
STAIR #2
SPD BREAK
ROOM
MALE
LOUNGE
EMPLOYEE
LOCKER
ROOM
MALE EMPOYEE
LOCKER
ROOM
MALE EMPOYEE
MALE
LOUNGE
EMPLOYEE
EMPLOYEE
TOILET
MALE
EQUIPMENT
STORAGE
SPD
OFFICE
SPD
OFFICE
SPD
RAGE
LIES &
EAN
PD
STORAGE
SPD
ROOM
82 SF
FIRE ALARM
A-B2CART WASH
SPD
STILL
MALE LOCKERS FEMALE LOCKERS
STORAGE
EMS
ROOM
1,416 SF
EQUIPMENT
A-B10
POOL
PIPE
SPACE
LOBBY
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
SOILED
LINEN
SOILED
TRASH
AREAWAY
AREAWAY
AREAWAY
FRESH
TUNNEL
AIR
S
BREAK DOWN
AREA / STORAGE
SPD
U P
U P
D R
RAMP
UP
RD
PITCHPITCH
PITCH
PITCH
1,200 SF
S.M.H.
SMH
8"
8"
8"
S
AN
IT
AR
Y S
EW
ER
SANITARY SEWER
8"
TO STORM
SLOPE DOWN
DRAIN
SEWER
SEWER
SEWER
SIGNAL
SIGNAL
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
VENT
PITCH
VENT
VENT
VENT
VENT
VENT
VENTVENT
VENT
VENT VENT
VENT
RD
RD RD
RD
RD
RD
RD
RD
RD
RD RD
VENT VENTS
PITCH
PITCH
PITCH
PITCHPITCH
PITCHPITCH
PITCHPITCH
PITCH
PITCH
PITCH
PITCH
PITCH
PITCH
RD
PITCH
SHUT-OFF
WATER
VALVE
S.D.
C.B.
C .B
C .B
S.D.
M.H.
K
150 KVA
TRANSFORMER
140 GAL.
GRASS
LAWN
PINE
TREE
CONCRETE
ASPHAULT
D D
D
D
D
D
D D
D
D D
S
8" PVC @
5.43%
P V C
.5
R C P
LIM
IT O
F W
ORK
LIM
IT
OF W
ORK
LIMIT OF WORK
LIMIT OF WORK
LIMIT OF WORK
LIMIT OF WORK
LP
LP
PB
EL
EC
EL
EC
P
P x x x x x x x x x x x x x
LP
LP
PB
EL
EC
EL
EC
P
P x x x x x x x x x x x x x
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
ELEC
11.6
ELEC
ELEC
ELEC
ELEC
POOL
15 KVA XFMR
480-120/208V, %Z 5.1, 3�, 4W
CONCRETE
ASPHAULT
PROVIDE 100A, NEMA 4X
DISCONNECT FOR SWITCH GEAR
FEEDERS AND ALARMS
PROVIDE 50 PAIR 110 CONNECTOR SERIES INDOOR
BUILDING ENTRANCE TERMINAL(BET) WITH SPLICE
CHAMBER AND COVER, EQUAL TO CIRCA MODEL#
1180ECA1-50. MODULES SHALL BE 300V SOLID STATE
WITH PTC EQUAL TO CIRCA MODEL# 4B1S-300.
CONNECT FROM BET
TO RACK MOUNTED
SPARE 110 BLOCKS
PROVIDE NEW FIBER
SHELVE. CONNECT #
STRANDS 50/125 OM4
FIBER OPTIC CABLE.
PROVIDE 5"x5" JUNCTION BOX.
PROVIDE NEW
MANHOLE #10G
PROVIDE NEW MANHOLE #10,
NEAR EXISTING DUCTBANK.
HAND DIG AS REQUIRED NEAR
EXISTING UTILITIES
CONNECT TO EXISTING
DISCONNECT AT PRIMARY
SIDE OF TRANSFORMER.
(2) 4"C FOR POWER WIRING:
• (1) 4"C AND (1) 1"C PVC SIGN AND SIGNAL
• (1) 4"C PVC SWITCH YARD LTS
SEE ONE-LINE FOR QUANTITIES/SIZES.4"C FOR COMMUNICATION WIRING:
• (1) 50 PAIR PIC CU
• # STRANDS 50/125 (OM4) FIBER OPTIC
CABLE
4"C WITH ATS CONTROL WIRES TO GEN CONTROL IN
BUILDING #2, SEE ONE-LINE FOR QUANTITIES/SIZES.
4"C WITH EMERGENCY FEEDER FROM
BUILDING #2, SEE ONE-LINE FOR QUANTITIES
/SIZES.
EXISTING (2) 4" CONDUITS, INTERCEPT
AND EXTEND TO MANHOLE. PROVIDE
WIRING FROM BUILDING 2 TO EXISTING
TRANSFORMER(S).
1#4/0 GROUND LOOP AROUND
BUILDING
(4) 4"C CONDUCTORS FOR FISHER
HOUSE, TRAILERS, VA SIGN, AND MISC.
LIGHTS, FEED FROM BUILDING #2, SEE
ONE-LINE FOR QUANTITIES/SIZES.
(1) 4"C PVC FISHER HOUSE
POWER, APPROXIMATE
LOCATION
2 SETS OF 4"C DUCTBANK WITH NORMAL
FEEDERS, SEE ONE-LINE FOR
QUANTITIES/SIZES.
(2) 4"C DUCTBANK WITH 4160V NORMAL
FEEDERS, SEE ONE-LINE FOR
QUANTITIES/SIZES.
2-1/2"C FOR COMMUNICATION CABLES
EXISTING (1) 4"C
PVC TRAILERS
POWER
ES501
ES501
ES501
ES501
ES501
TR
ES501
MH
ES501
CP
ES501
CP1
ES501
MP
ES501
COMMUNICATION HANDHOLE WITH
TEL/DATA, FIRE ALARM, SECURITY
& PA CONDUIT TO REMAIN,
PROTECT CONDUCTORS DURING
CONSTRUCTION.
300kVA 4160V -> 480Y/277V
TRANSFORMER
PROVIDE NEMA 1 JUNCTION BOXES ON
BASEMENT WALLS AT CONDUIT ENTRANCE.
SEAL ALL CONDUIT ENTRANCES, SEE
DETAILS.
EXISTING TEL, DATA, FIRE
ALARM, SECURITY AND PA
CABLES JUNCTION BOX FOR
FISHER HOUSE/TRAILERS, TO
REMAIN, .PROTECT CONDUITS
AND CONDUCTORS DURING
CONSTRUCTION.
FIBER OPTIC CABLES ROUTED TO SECOND
LEVEL IRM AND POLICE CLOSETS, SEE
ELECTRICAL FLOOR PLANS, AND RISER FOR
CONTINUATION.
EMERGENCY FEEDER AND ATS CONTROL
WIRING TO LEVEL 1 EM. ELECTRICAL ROOM,
SEE ELECTRICAL FLOOR PLANS, AND RISER
FOR CONTINUATION.
NORMAL FEEDER TO LEVEL 1 EM. ELECTRICAL
ROOM, SEE ELECTRICAL FLOOR PLANS, AND
RISER FOR CONTINUATION.
SWITCHGEAR BUILDING 70
EXISTING 5kV
SWITCHGEAR
SPARE 5kV BREAKER NEW LOCATIONS FOR
RELOCATED SITE LIGHTING
FIXTURES
AT EXISTING EMERGENCY SWITCHBOARD 'S3E-B-2A'
UTILIZE SPARE 400AF BREAKER, PROVIDE NEW TRIP
PLUG, SEE ELECTRICAL RISER/ONE-LINE.
GENERATOR CONTROL PANEL
AT DOUBLE DOORS OF SWITCHGEAR
BUILDING, SAW CUT AND PATCH
EXISTING CONCRETE. TRENCH FOR (2)
4"C TO 5kV SWITCHGEAR.
COORDINATE LIGHT FIXTURE
INSTALLATION WITH PARKING LOT
AND ISLAND RECONFIGURATION,
SAW CUT AND PATCH PAVEMENT
REQUIRED FOR NEW CONDUITS.
ALTERNATE DEDUCT #1
RELOCATE CAMPUS PRIMARY FEEDERS AND
DUCTBANK.
NOTE: INFRASTRUCTURE UNDER THIS
DEDUCT SHALL BE UTILIZED BY THE WEST
ROXBURY ELECTRICAL UPGRADE, PHASE II,
PROJECT # 523A4-13-208 WHICH WILL PROVIDE
A NEW CAMPUS SUBSTATION.
PROVIDE TEMPORARY (2) 5" CONDUITS TO EXISTING
1200A SWITCH. WIRE 2 SETS OF 3#750kCMIL CU, 5kV, 1-750kCMIL CU, THHW, 1#4/0AWG CU,…