36E77618R0063-005.pdf
PDF 4 MB Posted
- Attached to
- Parking Garage - WR (VACAA) Construction
- Solicitation number
- 36E77618R0063
About this file
36E77618R0063 S02 Attachment 4 523-400 Parking Garage WR - 100 Percent Plans - 1 of 5.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36E77619C0004-000.docx | DOCX document | |
| 36E77618R0063-0007000.docx | DOCX document | |
| 36E77618R0063-0006000.docx | DOCX document | |
| 36E77618R0063-0005001.pdf | ||
| 36E77618R0063-0005000.docx | DOCX document | |
| 36E77618R0063-0004000.docx | DOCX document | |
| 36E77618R0063-0004001.pdf | ||
| 36E77618R0063-0003000.docx | DOCX document | |
| 36E77618R0063-0002000.docx | DOCX document | |
| 36E77618R0063-0001001.docx | DOCX document | |
| 36E77618R0063-0001000.docx | DOCX document | |
| 36E77618R0063-010.pdf | ||
| 36E77618R0063-004.pdf | ||
| 36E77618R0063-007.pdf | ||
| 36E77618R0063-012.docx | DOCX document | |
| 36E77618R0063-002.pdf | ||
| 36E77618R0063-006.pdf | ||
| 36E77618R0063-009.pdf | ||
| 36E77618R0063-001.docx | DOCX document | |
| 36E77618R0063-013.docx | DOCX document | |
| 36E77618R0063-003.pdf | ||
| 36E77618R0063-011.pdf | ||
| 36E77618R0063-008.pdf | ||
| 36E77618R0063-000.docx | DOCX document |
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D N
.5
PARKING LOT # 1
TR
UE
N
OR
TH
MAGNETIC
NORTH
SCI
BUILDING
BUILDING
OREA
PARKING LOT # 2
PARKING LOT # 3
PARKING LOT # 7
ASSIGNED PARKING
MAIN
BUILDING
BUILDING
#1
MRI
ADDITION
PARKING LOT # 8
TOT SPOT
CHILD
DEVELOPMENT
CENTER
NEW RESEARCH
BLDG.
9,411 SQ FT
OUTPATIENT
PARKING
LOT #3
C
B
A
123456
M W
.3
W M
H
R .1
S T O R Y
S T O R Y
M E T A L
M E
T R
A M
P
S W
IT
C H G
EA
R B U
IL
D
IN
G
BUILDING 88
Sheet Number Sheet Name General
G000 COVER SHEET
G001 GENERAL NOTES AND MATERIAL LEGEND
G002 CODE PLAN
G003 PHASING PLAN DIAGRAM
Civil
CD101 CIVIL - PLAN - DEMO
CS101 CIVIL - PLAN - SITE
CS101-DA CIVIL - PLAN - SITE - DEDUCT ALTERNATE
CG101 CIVIL - PLAN - GRADING
CU101 CIVIL - PLAN - UTILITIES
CS501 CIVIL - DETAILS - SITE
CS502 CIVIL - DETAILS - SITE
CS503 CIVIL - DETAILS - SITE
Landscape
LP101 LANDSCAPE - PLAN - PLANTING
Architectural
AS101 PARKING LAYOUT - LEVEL 1
AS102 PARKING LAYOUT - LEVEL 2-4
AS103 PARKING LAYOUT - LEVEL 5
AS106 PLANS - RCPS - ROOFS
AS110 PLANS - ENLARGED
AS200 ELEVATIONS EXTERIOR
AS201 ELEVATIONS EXTERIOR
AS202 ELEVATIONS EXTERIOR - ENLARGED
AS210 ELEVATIONS INTERIOR
AS300 BUILDING SECTIONS
AS310 WALL SECTIONS
AS320 DETAILS ENVELOPE
AS321 DETAILS - ENVELOPE
AS330 DETAILS - CURTAINWALL
AS331 DETAILS - CURTAINWALL
AS400 ENLARGED PLANS - STAIR AND ELEVATOR
AS401 SECTIONS - STAIR AND ELEVATOR
AS402 PLANS AND SECTIONS - RAMP
AS501 DETAILS STAIR AND RAILING
AS502 DETAILS GATES AND FENCING
AS600 SCHEDULES - ROOMS AND SIGNAGE
AS601 SCHEDULE - DOORS, FRAMES AND TYPES
AS602 SCHEDULES - WINDOW AND CURTAINWALL
Structural
SS001 STRUCTURAL - GENERAL NOTES
SF101 STRUCTURAL - PLAN LEVEL 1/FOUNDATION
SF102 STRUCTURAL - TYPICAL CONCRETE SECTIONS AND DETAILS
SF103 STRUCTURAL - FOUNDATIONS SECTIONS
SF104 STRUCTURAL - FOUNDATIONS SECTIONS
SF105 STRUCTURAL - FOUNDATIONS SECTIONS
SS102 STRUCTURAL - PLAN - LEVEL 2
SS103 STRUCTURAL - PLAN - LEVEL 3
SS104 STRUCTURAL - PLAN - LEVEL 4
SS105 STRUCTURAL - PLAN - LEVEL 5
SS501 STRUCTURAL - TYPICAL PRECAST SECTIONS AND DETAILS
SS502 STRUCTURAL - FRAMING SECTIONS
SS503 STRUCTURAL - FRAMING SECTIONS
Plumbing
PL001 PLUMBING - LEGEND AND GENERAL NOTES
PL100 PLUMBING - PLAN - UNDERSLAB
PL101 PLUMBING - PLAN - LEVEL 1
PL102 PLUMBING - PLAN - LEVEL 2 - 4
PL103 PLUMBING - PLAN - LEVEL 5
PL301 PLUMBING - ENLARGED PLANS AND SECTIONS
PL501 PLUMBING - DETAILS AND SCHEDULES
Mechanical
MH001 MECHANICAL - LEGEND AND GENERAL NOTES
MH101 MECHANICAL - PLAN - LEVEL 1
MH102 MECHANICAL - PLAN - LEVEL 2
MH103 MECHANICAL - PLAN - LEVEL 3
MH501 MECHANICAL - DETAILS
MH601 MECHANICAL - SCHEDULES
Electrical
E001 ELECTRICAL - LEGEND AND GENERAL NOTES
E002 ELECTRICAL - ONE-LINE RISER DIAGRAM
E003 ELECTRICAL - SYSTEMS - ONE-LINE RISER DIAGRAMS
ES100 ELECTRICAL - SITE PLAN DEMO
ES101 ELECTRICAL - SITE PLAN NEW
ES101A ELECTRICAL - NEW SITE PLAN - ALTERNATE PARKING
ES501 ELECTRICAL - SITE DETAILS
EL101 ELECTRICAL - LIGHTING PLAN - LEVEL 1
EL102 ELECTRICAL - LIGHTING PLAN - LEVEL 2
EL103 ELECTRICAL - LIGHTING PLAN - LEVEL 3
EL104 ELECTRICAL - LIGHTING PLAN - LEVEL 4
EL105 ELECTRICAL - LIGHTING PLAN - LEVEL 5
EP101 ELECTRICAL - POWER PLAN - LEVEL 1
EP102 ELECTRICAL - POWER PLAN - LEVEL 2
EP103 ELECTRICAL - POWER PLAN - LEVEL 3
EP104 ELECTRICAL - POWER PLAN - LEVEL 4
EP105 ELECTRICAL - POWER PLAN - LEVEL 5
EJ101 ELECTRICAL - SYSTEMS PLANS LEVEL 1
EJ102 ELECTRICAL - SYSTEMS PLANS LEVEL 2
EJ103 ELECTRICAL - SYSTEMS PLANS LEVEL 3
EJ104 ELECTRICAL - SYSTEMS PLANS LEVEL 4
EJ105 ELECTRICAL - SYSTEMS PLANS LEVEL 5
E401 ELECTRICAL -LARGE SCALE PLANS
E402 ELECTRICAL -LARGE SCALE PLANS
E403 ELECTRICAL - LARGE SCALE PLANS
E404 ELECTRICAL - LARGE SCALE PLANS
E501 ELECTRICAL - DETAILS
E502 ELECTRICAL - DETAILS
E503 ELECTRICAL - DETAILS
E601 ELECTRICAL - SCHEDULES AND DIAGRAMS
E602 ELECTRICAL - SCHEDULES AND DIAGRAMS
Fire Protection
FP-001 FIRE PROTECTION - TITLE SHEET
FP-101 FIRE PROTECTION - PLAN - LEVEL 1/FOUNDATION
FP-102 FIRE PROTECTION - PLAN - LEVEL 2
FP-103 FIRE PROTECTION - PLAN - LEVEL 3
FP-104 FIRE PROTECTION - PLAN - LEVEL 4
FP-105 FIRE PROTECTION - PLAN - LEVEL 5
E
M E
PA
R
N U
D
DE
S TAT E
TI
T
E NT OF V
A I R
S
MA
OS F
I R
E C
A
FFA
N
ET RA
S
E
M E
PA
R
N U
D
DE
S TAT E
TI
T
E NT OF V
A I R
S
MA
OS F
I R
E C
A
FFA
N
ET RA
S
DEPARTMENT OF VETERANS AFFAIRS
1400 VFW Parkway
West Roxbury, MA 02132
PROJECT NO. 523-400
ARCHITECTS - ENGINEERS - CONSULTANTS PROJECT ENGINEER
WEST ROXBURY GARAGE
VA MEDICAL CENTER
WEST ROXBURY HEALTHCARE SYSTEM
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376
SPECIFICATIONS &
ESTIMATING:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
DENIS MCLAUGHLIN
VA -JAMAICA PLAIN, MA
(857) - 364-5419
FACILITY KEY PLAN PROJECT AREA MAP
Project Number
Building Number
Dwg: of 99
Drawing Number
523-400
G000
100% BID DOCUMENTS
PROJECT GENERAL NOTES
1. These notes are intended for general reference and information and to augment the Contract and Specification information provided under separate cover. Refer to those Specifications for detailed information and requirements.
2. All Work included in this Contract shall conform to all national, state, and local Codes, Ordinances and Agency requirements including, but not limited to: hazardous material removal, solid waste disposal, seismic design, and life-safety.
3. Definitions:
• New: May be used to indicate items which shall be furnished and installed by this Contract.
Typically used to ensure clarity between various components of the drawings. Not all items are labeled as "new" when it is obvious by other indication.
• Existing: Existing building or site components which are in place at the start of Construction.
Not all items are labeled as "existing" when it is obvious by other indication. Consult the Architect for clarification.
• Repair: Restore to proper operating and aesthetic condition.
• Restore: Bring back to former condition, by repairing or patching as required.
• Patch: Restore to condition matching existing adjacent construction, surface texture and finish.
• N.I.C. (Not In Contract): Work which is not included in this Contract, but which may require
Contractor coordination.
• Remove: Dismantle and/or extract from the premises entirely. Dispose of off site unless noted otherwise.
• Replace: Dismantle and/or extract from the premises entirely. Dispose of off site unless noted otherwise. Provide new material as indicated.
• Damages: Existing building or site components, not scheduled for work, which are damaged.
Such elements and components shall be replaced or restored to original condition by methods approved by the Architect.
• Demolish: Dismantle and/or extract from the premises entirely. Dispose of off site unless noted otherwise.
• Salvage: Remove and reinstall or remove and deliver to the Owner, as indicated. Salvaged components may be for limited reuse, to match existing conditions or to patch and repair as indicated
4. It is the intent of the drawings and specifications to have the Contractor provide a complete, fully operational building. Provide all labor, materials and incidentals necessary to achieve this intent. Failure of the Drawings or Specifications to indicate each incidental shall not relieve the Contractor from providing the necessary items as part of this Contract. The Drawings show the design and layout, describe the quality level and construction techniques in a general sense only. All details are typical. What is shown in one condition applies to all other similar conditions, unless noted otherwise.
5. Verify the following items and report any discrepancies to the Architect prior to proceeding with Work, and proceed with the Work only after such discrepancies are resolved by the Architect:
• Existing conditions
• The size and location of all existing utilities.
• Discrepancies between or within the Contract Documents.
• Unsuitable soils: report the location of all unsuitable soil materials below anticipated levels of footings or slabs prior to setting forms.
• Mechanical, electrical and plumbing coordination having potential impact on ceiling heights or building appearance
• Dimensional discrepancies.
6. Provide bond-outs, blocking, sleeves and pipes as required for all wall, floor, roof, and ceiling penetrations through structure. Coordinate installation of all structural, mechanical, plumbing and electrical components. Seal all penetrations in fire rated assemblies and smoke assemblies to conform to U.L. rated assemblies and all NFPA and BOCA building Code requirements. All penetrations shall also comply with the acoustical assembly rating required for each wall or floor assembly. Refer to the Code Plans for specific Code references.
7. Mechanical, electrical and plumbing coordination: ceiling heights and duct sizes are given. Coordinate the Work to achieve the given visual and performance requirements, and the requirement of including mechanical, electrical and plumbing systems within the indicated space.
8. Do not penetrate structural beams, columns, or shear walls unless specifically detailed otherwise.
9. Coordinate the Work of all Subcontractors.
10. Provide work holes and access holes to install new systems in concealed spaces, as required or indicated.
PLAN GENERAL NOTES
1. The Drawings use a system of keyed notes on plans, elevations and details. Instructions for specific components of the Work are keyed to the Drawings. Building systems (partitions, roof & foundation) are keyed to floor plans, wall sections, roof plan and other details as appropriate.
2. Work from given dimensions. In general, large-scale details take precedence over smaller scale plans, elevations and building sections. Notify the Architect of any dimensional discrepancies prior to commencing the Work, and do not begin work until such discrepancies are resolved by the Architect. Do not scale drawings. Dimensions indicated as "clear" shall be maintained in cases of discrepancy.
3. Dimensional Control:
• Exterior dimensions are from:
• Centerline of column to outside face of masonry
• Face of masonry to face of masonry
• Face of concrete to face of concrete
• Centerline of column to centerline of window opening
• Masonry opening to masonry opening
• Center line of column to face of masonry
• Interior dimensions are from:
• Face of finish to face finish
• Face of masonry to face of masonry
• Face of finish to face of masonry
• Centerline column to face of stud or masonry
4. Verify all existing conditions and dimensions and report any discrepancies to the Architect. Proceed with the work only after discrepancy has been resolved with the Architect.
5. Masonry Opening or Rough Opening dimensions indicated are nominal dimensions only.
Coordinate all Masonry Openings or Rough Openings with actual window unit, doorframe, or curtain wall/storefront sizes and requirements.
6. All new openings into existing CMU walls for mechanical or electrical penetrations shall receive a lintel. Refer to the structural plans for lintel type. Refer to Mechanical plans for number, location, and size of all penetrations.
7. Flooring and floor finishes shall be installed to a maximum differential of 1/16" between dissimilar materials. Provide transition strips or thresholds (1/2" maximum) of same material as flooring and/or as noted on the drawings.
8. Typical Details:
The following details are typical throughout this project and apply in all cases unless specifically noted otherwise. Please note that these details may not be directly referenced from the plans or other details:
• Unless noted otherwise, the location of doorframes shall be:
• 8" from adjacent wall to the hinge side in CMU partitions.
• 4" from adjacent wall to the hinge side in metal stud partitions.
• Maintain a clear dimension of 1’-6” from all adjacent construction to the latch (pull) side of the door.
• Maintain other clear dimensions in accordance with the latest version of the ADA Accessibility
Guidelines (ADAAG).
CEILING GENERAL NOTES
1. Ceiling plans do not show every fixture or component. Refer to electrical, plumbing, mechanical and structural drawings for extent of all ceiling penetrations and installations and coordinate prior to installation.
WALL GENERAL NOTES
1. Fill all CMU voids with mortar or grout at all door jambs and masonry ties. Refer to Structural Drawings for notes on masonry reinforcement.
2. All partitions shall extend from sub-floor or slab to underside of floor or roof deck above, unless noted otherwise.
3. Install one bead of acoustical sealant under each layer of GWB at intersection with floor at each side of wall. Cover with wall base.
4. Verify all metal cold-formed metal framing and connection requirements with engineer of exterior framing system.
5. All CMU is 7-5/8" (8" Nominal), unless noted otherwise.
INTERIOR GENERAL NOTES
1. All mounting heights and clearances at Toilet rooms and elsewhere shall comply with the latest version of the ADA Accessibility Guidelines (ADAAG).
• Barrier-Free clearances are given. These clear dimensions shall be maintained in cases of discrepancy.
• All dimensions given for fixture and accessory locations are clear dimensions from finished surfaces, unless noted otherwise. Coordinate actual dimensions with wall construction and finishes.
• Locate all controls, flush valves, shutoffs and similar items in accordance with the latest version of the ADA Accessibility Guidelines (ADAAG).
• A range of mounting heights may be given for some items. Maintain a consistent mounting height, within the given range, throughout the Project, unless noted otherwise.
DOOR AND WINDOW GENERAL NOTES
1. Fill all interior hollow metal frames adjacent to CMU with mortar. Fill all new exterior metal doorframes with grout. Coat inside of all hollow metal frames with asphalt emulsion.
2. Unless noted otherwise, the location of doorframes shall be:
• 8" from adjacent wall to the hinge side in CMU partitions.
• 4" from adjacent wall to the hinge side in metal stud partitions.
• Maintain a clear dimension of 1’-6” from all adjacent construction to the latch (pull) side of the door.
• Maintain other clear dimensions in accordance with the latest version of the ADA Accessibility
Guidelines (ADAAG).
3. Refer to Specifications for locations of Tempered, Wired, or Insulating Glass, unless noted otherwise.
4. All windows with contiguous metal panel infills shall have the indicated fixed or operable frame in the translucent panel. The metal panel portion shall have a fixed framing member of the same framing manufacturer of similar style that can be combined with similar units.
ROOF GENERAL NOTES
1. Provide flashing at all roof penetrations, whether shown on the roof plan or not, unless noted otherwise. Refer to Structural, Mechanical and electrical plans for number, location, and size of penetrations.
VERTICAL CIRCULATION GENERAL NOTES
1. All handrail and guardrail components shall be able to withstand a horizontal load of 250 pounds at any point.
2. Guardrails shall not allow the passage of a 4-inch sphere between members.
3. All ramp, stair, ladder, alternating tread device, handrail and guardrail components shall comply with the applicable provisions of the latest version(s) IBC, NFPA 101, and the ADA.
MATERIALS LEGEND
GRAVEL
CONCRETE MASONRY UNIT
BRICK
CONCRETE
SOIL
STEEL
WOOD FRAMING
WOOD BLOCKING
GYPSUM BOARD
PLYWOOD
BATT INSULATION
RIGID INSULATION
ABBREIATIONS
AB ANCHOR BOLT
AB AIR BARRIER
AC AIR CONDITIONING
ADDL ADDITIONAL
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AH AIR HANDLER
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
AOR AREA OF REFUGE
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ARND AROUND
AWP ACOUSTICAL WALL PANEL
BD BOARD
BF BARRIER FREE
BIT BITUMINOUS
BLDG BUILDING
BLKG BLOCKING
BM BENCHMARK
BOT BOTTOM
BO BOTTOM OF
BRK BRICK
BRG BEARING
B/S BRICK SHELF
BSMT BASEMENT
C, CRS COURSE
CAB CABINET
CB CATCH BASIN
CC CENTER TO CENTER
CF CUBIC FOOT
CFMF COLD FORMED METAL FRAMING
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONC/CCOLORED CONCRETE
CONT CONTINUOUS OR CONTINUE
CONTR CONTRACTOR
CPT CARPET
CS COUNTERSINK
CSMT CASEMENT
CT CERAMIC TILE
CWT CERAMIC WALL TILE
CUH CABINET UNIT HEATER
CY CUBIC YARD
CW CURTAIN WALL
DBL DOUBLE
DC DISPLAY CASE
DEMO DEMOLISH, DEMOLITION
DF DRINKING FOUNTAIN
DIA, DIAM DIAMETER
DIM DIMENSION
DIV DIVISION
DMP DEMOUNTABLE PARTITION
DN DOWN
DR DOOR
DTL DETAIL
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EF EXHAUST FAN
EMHO ELECTRO MAGNETIC HOLD OPEN
EIFS EXTERIOR INSULATION FINISH
SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
EP EPOXY PAINT
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSED/ENCLOSURE
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
EXT EXTERIOR
EW EYEWASH
EWC ELECTRIC WATER COOLER
FB FIRE BLANKET
FBO FURNISHED BY OWNER
FCS FLOOR COATING SYSTEM
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER AND CABINET
FFE FINISHED FLOOR ELEVATION
FG FIBERGLASS
FHVC FIRE HOSE AND VALVE CABINET
FIN FINISH(ED)
FIN GR FINISH GRADE
FLR FLOOR(ING)
FNDN FOUNDATION
FP FIREPROOFING
FO FACE OF
FRMG FRAME(ING)
FRP FIBER REINFORCED PLASTIC
FRT FIRE RETARDANT TREATED
FSR FLEXIBLE SHEET ROOFING
FT FOOT(FEET)
FTG FOOTING
FTR FIN TUBE RADIATION
FUR FURRED(ING)
FV FIELD VERIFY
FWC FABRIC WALL COVERING
GA GAUGE
GALV GALVINIZED
GB GRAB BAR
GFB GROUND FACE CMU
GL GLASS, GLAZING
GWB GYPSUM WALLBOARD
HARD HARDENER
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDO HIGH DENSITY OVERLAY
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HAND RAIL
HS HIGH SCHOOL
HT HEIGHT
HTG HEATING
HVAC HEATING/VENTILATION/AIR
CONDITIONING
IBC INSTALLED BY
CONTRACTOR
ID INSIDE DIAMETER
IN INCH (ES)
INCL INCLUDE (D), (ING)
INFO INFORMATION
INSUL INSULATED
INT INTERIOR
INV INVERT
JT JOINT
KIT KITCHEN
LAB LABORATORY
LAM LAMINATE (D)
LAV LAVATORY
LB POUND (S)
LCC LEAD COATED COPPER
LF LINEAR FOOT
LH LEFT HAND
LOC’N LOCATION
LW LIGHTWEIGHT (CMU)
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MC MEDICINE CABINET
MCWF MULTI COLOR WALL FINISH
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MED MEDIUM
MF MEMBRANE FLASHING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLDG MOULDING, MOULDING
MO MASONRY OPENING
MR MOISTURE RESISTANT
MRGB MOISTURE RESISTANT GYPSUM BOARD
MS MOP SINK
MSF METAL STUD FRAMING
MTL METAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
O/ OVER
OC ON CENTER
OD OUTSIDE DIAMETER
OFS OVERFLOW SCUPPER
OP OPAQUE
OH OVERHEAD
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPS OPERABLE PANEL SYSTEM
P, PTD PAINT
PC PRECAST CONC.
PERF PERFORATED
PERIM PERIMETER
PRKG PARKING
PL PLATE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
QR QUARTER ROUND
QT QUARRY TILE
RE: REFERENCE
REF REFRIGERATOR
REQ’D REQUIRED
REV REVISION (S), REVISED
RL RAIN LEADER
RF RUBBER FLOOR
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
S SOUTH
SAT SUSPENDED ACOUSTICAL TILE
SC SOLID CORE
SCHED SCHEDULE
SD STORM DRAIN, SOAP DISPENSER
SECT SECTION
SF SQUARE FOOT
SGL SAFETY GLASS
SH SHOWER
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SLNT SEALANT
SNR SANITARY NAPKIN RECEPTOR
SP SPECIAL PAINT
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRL STRUCTURAL
STRUCTSTRUCTURE/STRUCTURAL
SUPT SUPPORT
SUSP SUSPENDED
SV SHEET VINYL
T TOILET
TB TOWEL BAR
TB TACKBOARD
T&G TONGUE AND GROOVE
TGL TEMPERED GLASS
THK THICK(NESS)
TO TOP OF
TP TOILET PARTITION
TPD TOILET PAPER DISPENSER
TV TELEVISION
TYP TYPICAL
UCR UNDER COUNTER REFRIGERATOR
UNO UNLESS NOTED OTHERWISE
VB VAPOR BARRIER/VINY BASE
VC VALVE CABINET
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VPW VENEER PLYWOOD
VWC VINYL WALL COVERING
W WEST
W/ WITH
WC WATER CLOSET
WD WOOD
WGL WIRE GLASS
WH WATER HEATER
W/O WITHOUT
WS WATERSTOP
WP WATERPROOF
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
YD YARD
ZCC ZINC-COATED COPPER
SYMBOLS
ROOM TAG
DOOR TAG
1t WINDOW\CURTAINWALL TAG
0.0
S4
A41.1
WALL TAG
A101
SIM
BUILDING SECTION
WALL SECTION
PLAN OR SECTION DETAIL
INTERIOR ELEVATION
EXTERIOR ELEVATION
A101
SIM
FLOOR LEVEL\VERTICAL ELEVATION
COLUMN CENTERLINE
Room name
150 SF
SPECIALTY EQUIPMENT\
TOILET ACCESSORY TAG
CASEWORK TAG
1i
1i
A101
SIM
A101
CMU PARTITION
FULL HEIGHT
M4A
PARTITION TOP ANCHOR
DECK
1" DEFLECTION SPACE
W/ FULL THICK
COMPRESSED FG INSUL
FILL VOIDS AT DECK
4" CMU @ M4A
6" CMU @ M6A
8" CMU @ M8A
12" CMU @ M12A
MASONRY JOINT
REINFORCEMENT
FOR SMOKE PARTITIONS AS
INDICATED ON PLANS:
FIRESTOP SYSTEM AT
CORRIDOR SIDE; FILL VOIDS
AT DECK WITH MINERAL
WOOL.
NOTES:
1. AT SMOKE PARTITIONS, SEAL ALL PENETRATIONS TO
RESIST THE PASSAGE OF SMOKE PER NFPA 101
M8A M12A
M6A CMU PARTITION
FULL HEIGHT
M6A-3F
PARTITION TOP ANCHOR
DECK
1" DEFLECTION SPACE W/
FULL THICK COMPRESSED
FG INSUL FILL VOIDS AT
DECK
6" CMU
MASONRY JOINT
REINFORCEMENT
FOR SMOKE PARTITIONS AS
INDICATED ON PLANS:
FIRESTOP SYSTEM AT
CORRIDOR SIDE; FILL VOIDS
AT DECK WITH MINERAL
WOOL.
2" SPRAY APPLIED
CELLULOSE INSULATION
AIR BARRIER
VINYL "J" CHANNEL AT BASE
OF GWB - HOLD OFF CONC.
1/4"
BACKER ROD AND SEALANT
4" X 4" CMU CURB AT
BASE OF MTL STUD
GWB
EXTERIOR PARTITION CMU
INFILL WALL
PARTITION TOP ANCHOR
DECK OR SPANDREL
1" DEFLECTION SPACE
W/ FULL THICK
COMPRESSED FG INSUL
FILL VOIDS AT DECK
6" CMU
MASONRY JOINT
REINFORCEMENT
2" SPRAY APPLIED
CELLULOSE INSULATION
AIR BARRIER
DAMPROOFING
10 1/4"
EM6A
VINYL "J" CHANNEL AT BASE
OF GWB - HOLD OFF CONC.
1/4"
BACKER ROD AND SEALANT
4"X4" CMU CURB AT BASE
OF MTL STUD
4" CMU VENEER
GWB
METAL STUD FURRING
- PROVIDE 2" CONC.
CURB @ BASE
S1F
S2F
S4F
7/8" HAT
1- 5/8" LGMF
3-5/8" LGMF
U .N
.O
2"
U .N
.O
4"
S3F 2-5/8" LGMF
U .N
.O
3"
NOTE:
TOP OF WALL CONDITION
VARIES AT FIRE WALLS -
SEE WALL SECTIONS
1" DEFLECTION
SPACE W/ UL LISTED
FIRE STOP SYSTEM
AND PARTITION TOP
ANCHOR.
8" CMU @ M8A-2
12" CMU @ M12A-2
MASONRY JOINT
REINFORCEMENT
UL # U905
CMU PARTITION
FULL HEIGHT
2-HOUR FIRE-RATED
M8A-2
M12A-2
CMU PARTITION
FULL HEIGHT
1-HOUR FIRE-RATED
M8A-1
DECK
1" DEFLECTION SPACE
W/ UL LISTED FIRESTOP
SYSTEM & PARTITION
TOP ANCHOR
8" CMU @ M8A-1
12" CMU @ M12A-1
MASONRY JOINT
REINFORCEMENT
UL # U905 SIM
M12A-1
CMU PARTITION
FULL HEIGHT
PARTITION TOP ANCHOR
8" CMU
MASONRY JOINT
REINFORCEMENT
2" SPRAY APPLIED
CELLULOSe INSULATION
AIR BARRIER
VINYL "J" CHANNEL AT BASE
OF GWB - HOLD OFF CONC.
1/4"
BACKER ROD AND SEALANT
4" X 4" CMU CURB AT
BASE OF MTL STUD
M6A-2-3F
UL # U906
DECK
1" DEFLECTION SPACE
W/ UL LISTED FIRESTOP
SYSTEM & PARTITION
TOP ANCHOR
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
o n e ig h th in c o f o t 16 o q u a rt e r in e f o o t o a lf in o t th re e e ig h s o t th re e q u a rt e rs in o t
6" o o t
6" o d lf in c h e f o o t
6" th re h o t
6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
DENIS MCLAUGHLIN
VA -JAMAICA PLAIN, MA
(857) - 364-5419
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
GENERAL NOTES AND MATERIAL LEGEND
G001
ADHDW 2
CMU Partition CMU Partition W/ MTL Furring and Insulation
EXTERIOR - CMU Partition W/ CMU Veneer, MTL Furring and InsulationMetal Stud Furring
CMU Partition 2 HR CMU Partition 1 HR CMU Partition 2 HR W/ MTL Furring and Insulation
DN
UP
NOTES:
1. NFPA 101 primarily addresses life safety and fire protection features while the IBC addresses a wide range of considerations, including, but not limited to, structural strength, seismic stability, sanitation, adequate light and ventilation, and energy conservation. VA buildings must meet the requirements of NFPA 101 and documents referenced by NFPA 101 in order to comply with the accreditation requirements of The Joint Commission. Therefore, designs shall comply with the requirements of the latest edition of NFPA 101 and documents referenced therein. Design features not addressed by NFPA 101 or documents referenced therein shall comply with the requirements of the latest edition of the IBC or as otherwise addressed above in this Program Guide. For design features that are addressed by both the IBC as well as NFPA 101 or a document referenced by NFPA 101, the requirements of NFPA 101 or the document referenced by NFPA 101 shall be used exclusively (this applies even if the IBC requirements are different).
Applicable Codes : The VA has adopted the most recent edition of the following codes:
2012 IBC
NFPA 101 2012 Life Safety Code NFPA National Fire Codes with the exception of NFPA 5000 and NFPA 900 Occupational, Safety and Health Administration (OSHA) Standards VA Seismic Design Requirements, H-18-8 National Electrical Code (NEC) International Plumbing Code (IPC) Safety Code for Elevators and Escalators, American Society of Mechanical Engineers (ASME) A 17.1 ASME Boiler and Pressure Vessel Code ASME Code for Pressure Piping Architectural Barriers Act Accessibility Standards (ADAAS) including VA supplement, Barrier Free Design Guide (PG-18-13) Building Code Requirements for Reinforced Concrete, American Concrete Institute and Commentary (ACI 318) Manual of Steel Construction and Safety Signs. Stated in the General Requirements Section 01010 of the VA Master Construction Specification Energy Policy Act of 2005 (EPAct) DOE Interim Final Rule; Energy Conservation Standards for New Federal, Commercial and Multifamily High-Rise Residential Buildings and New Low-Rise Residential Buildings, 10 CFR Parts 443, 434, and 435 Federal Leadership in High Performance and Sustainable Buildings; Memorandum of Understand (MOU) Executive Order13423; Strengthening Federal Environmental, Energy, and Transportation Management.
The Provisions for Construction and Safety Signs. Stated in the General Requirements Section 01010 of the VA Master Construction Specification.
Ventilation for Acceptable Indoor Air Quality - ASHRAE Standard 62.1 -2004.
Safety Standard for Refrigeration Systems - ASHRAE Standard 15 - 2007
Storage Occupancies:
42.8.1.3 Open Parking Structures. Open parking Structures shall comply with 42.8.1.3.1 through 42.8.1.3.3.
42.8.1.3.1. Each parking level shall have wall openings open to the atmosphere for an area of not less than 1.4 s.f. for each linear foot of its exterior perimeter. [88A:5.5.1]
42.8.1.3.2. The openings addressed in 42.8.1.3.1 shall be distributed over 40 percent of the buildings perimeter or uniformly over two opposing sides. [ 88A:5.5.2]
42.8.1.3.3 Interior wall lines and column lines shall be at least 20% open, with openings distributed to provide ventilation [88A:5.5.3]
Construction: Type II (000)
5.1.1 Parking structures shall be building using one of the types of construction defined in NFPA 220, except as otherwise amended in this standard.
5.1.2 Open parking structures shall be of Type I or Type II construction as defined in NFPA 220.
5.1.3 Heights and Floor areas of open parking structures of Type I, Type II (222) or Type II (111) construction shall be permitted to be unlimited.
5.1.4 Open parking structures of Type II(000) shall be permitted to be of unlimited area where both of the following conditions are met:
(1) The height does not exceed 75 ft.
(2) The horizontal distance from any point on any parking level to an exterior wall opening on a street, an alley, a courtyard, or other similar permanent open space does not exceed 200 ft.
Floors:
5.3.1 Floor surfaces shall be of noncombustible materials.
5.3.1.2 Asphalt shall be permitted on grade.
Fire Sprinkler Systems:
6.4.1 Automatic sprinkler systems shall conform to NFPA 13.
6.4.4 Automatic sprinkler systems shall not be required in open parking structures.
Standpipes:
6.5.1 Parking structures exceeding a height of 50 ft or having parking levels below grade shall be provided with a Class I standpipe system in accordance with NFPA 14.
6.5.2 Class I standpipe systems of the manual dry pipe shall be permitted in open parking structures.
Detection Alarm and Communications Systems:
6.6.3 Fire alarm systems shall not be required in open parking structures.
Extinguishment Requirements.
42.8.3.5 Extinguishment Requirements (No Requirements)
Doors:
42.8.2.2.2.3 An opening for the passage of automobiles shall be permitted to serve as an exit from a street floor, provided that no door or shutter is installed therein.
Stairs:
42.8.2.2.3.2 In open parking structures, stairs complying with 7.2.2.5.1 (enclosures) shall not be required.
Ramps:
42.8.2.2.6.1 Ramps shall be permitted in accordance with any of the following condition:
(2) In a ramp-type open parking structure with open vehicle ramps not subject to closure, the ramps shall be permitted to serve in lieu of the second means of egress from floors above the level of exit discharge, provided that the ramp discharges directly outside at the street level. [88A:4.1.3]
(3) For parking structures extending only one floor level below the level of exit discharge, a vehicle ramp leading directly to the outside shall be permitted to serve in lieu of the second means of egress, provided that no door or shutter is installed therein. [88A:4.1.4]
88A 4.1.2 The Ramp requirement of NFPA 101, 7.2.5 (Ramps), and NFPA 5000, 11.2.5, shall not apply to those parts of sloped floors utilized for both parking and vehicular circulation.
Area of Refuge:
42.8.2.2.9.2 In open-air parking structures, the area of refuge requirements of 7.2.12.1.2(2) shall not apply.
Arrangement of Means of Egress:
42.8.2.5.1 Dead Ends shall not exceed 50ft.
Maximum Travel Distance to Exits:
Table 42.8.2.6.1 - Open Parking Structure - Not Protected throughout - 300 ft.
42.8.2.6.2 In open parking structures, travel distance shall comply with one of the following:
(2) The travel distance to a stair that does not meet the provisions for an exit enclosure shall not exceed the travel distance specified in Table 42.8.2.6.1, and travel along the stair shall not be limited.
EXIT
EXIT
FEC
FIRE EXTIGUISHER CABINET
2 HOUR WALL
FIRE RATINGS
SMOKE
1 HOUR FIRE RATED PARTITION
VAN
F E
C
F E
C
EXIT
E X
IT
EXIT
E X
IT
242' - 0"
3'
EXIT
F E
C
F E
C
F E
C
E X
IT
3'
EXIT
E X
IT
E X
IT
DN
DN
242' - 0"
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
o o t 16 o a rt e r in e f o o t o lf in o t th re e e ig h o t th re e q u a rt e rs in o t
6" o o t
6" o lf in c h e f o o t
6" th h o t
6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
DENIS MCLAUGHLIN
VA -JAMAICA PLAIN, MA
(857) - 364-5419
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CODE PLAN
G002
ADHDW 3
1/16" = 1'-0"
GROUND LEVEL CODE PLAN
1/16" = 1'-0"
LEVEL 2-4 CODE PLAN
DN
C
A
1 6
DN
UP
UP
C
A
1 6
UP
UP
C
A
1 6
UP
UP
CLOSE HANDRAIL IF REQ'D
- NOTE 3
C
A
1 6
UP
UP
PHASE 2
PHASE 3
STAIRS AND RAILS -
NOTE 4
ELEVATOR - NOTE 6
SPANDREL NOTE 5
SPANDREL NOTE 5
FULL HEIGHT SECURITY
GATE - NOTE 4
ANTICLIMB NOTE 2
C
A
1 6
UP
UP
PHASE 4
PHASE 3
SPANDREL - NOTE 5
ELEVATOR - NOTE 6
STAIR 2 ENCLOSURE - NOTE 3
STAIRS AND RAILS -
NOTE 4
FULL HEIGHT SECURITY
GATE - NOTE 4
ANTICLIMB NOTE 2
ISOMETRIC KEY
LEVEL 2
LEVEL 1
LEVEL 3
LEVEL 4
LEVEL 5
A
C
1 6
NOTES:
1) FULL HEIGHT ENTRY TOWER, ELEVATORS AND STAIRS TO
BE COMPLETED AS PART OF PHASE 1.
2) ANTI CLIMB FENCE TO BE MOUNTED AT THE HIGHEST PHASE
COMPLETED - TO BE MOVED TO LATER PHASES AS ADDED.
3)STAIR 2 AND RAILINGS TO BE BUILT TO THE HIGHEST PHASE
COMPLETED - STAIR 2 ENCLOSURE TO BE COMPLETED IN
PHASE 4.
4) STAIR 1 AND RAILS TO BE COMPLETED AS PART OF PHASE 1
- PROVIDE FULL HEIGHT CHAIN LINK SECURITY FENCE AND
GATE AT HIGHEST PHASE COMPLETED - MOVE IF REQUIRED IF
LATER PHASES ARE ADDED. OMIT OR REMOVE IF PROJECT IS
FULLY EXECUTED.
5)SPANDREL CLOSURE TO BE PROVIDED AT END OF HIGHEST
LEVEL OF COMPLETION TO BE MOVED IF LATER PHASES ARE
ADDED.
6)ELEVATORS TO BE COMPLETED FULL HEIGHT OF TOWER,
PROGRAM STOP TO HIGHEST LEVEL OF COMPLETION, WILL
REQUIRE ADDITIONAL STOPS TO BE PROGRAMMED IF LATER
PHASES ARE ADDED.
PHASE 1
PHASE 2
PHASE 3
PHASE 4
PHASE 1
PHASE 2
PHASE 3
PHASE 4
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
o o t 16 o a rt e r in e f o o t o lf in o t th re e e ig h o t th re e q u a rt e rs in o t
6" o o t
6" o lf in c h e f o o t
6" th h o t
6"
SPECIFICATIONS:
Lowell Specifications 34 Marc Avenue Topsham, ME 04802 Tel: (207) 406-4001 Email: keith@lowellspecs.com
482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of 99
DENIS MCLAUGHLIN
VA -JAMAICA PLAIN, MA
(857) - 364-5419
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
PHASING PLAN DIAGRAM
G003
ADHDW 4
1/32" = 1'-0"
LEVEL 1 PHASING PLAN
1/32" = 1'-0"
LEVEL 2 PHASING PLAN
1/32" = 1'-0"
LEVEL 3 PHASING PLAN
1/32" = 1'-0"
LEVEL 4 PHASING PLAN
1/32" = 1'-0"
LEVEL 5 PHASING PLAN
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig ht ch ne fo ot on e q ua rte r i nc on e h al f th re e e ig hs th re e q ua rte rs
6" on e i
6" on e nd on h al f in es
6" th re e i nc he f oo t
6"
SPECIFICATIONS:
Lowell Specifications
50 Fernald Road
Freeport, ME 04032
Tel: (207)865-4518
Fax: (207) 865-1136
Stantec 482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of ###
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CD101
JMTM
CIVIL - PLAN - DEMO
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h al f in
6" th re e i nc f oo t
6"
SPECIFICATIONS:
Lowell Specifications
50 Fernald Road
Freeport, ME 04032
Tel: (207)865-4518
Fax: (207) 865-1136
Stantec 482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of ###
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CIVIL - PLAN - SITE
CS101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h al f in
6" th re e i nc f oo t
6"
SPECIFICATIONS:
Lowell Specifications
50 Fernald Road
Freeport, ME 04032
Tel: (207)865-4518
Fax: (207) 865-1136
Stantec 482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of ###
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CIVIL - PLAN - SITE
DEDUCT ALTERNATE
CS101-DA
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h al f in
6" th re e i nc f oo t
6"
SPECIFICATIONS:
Lowell Specifications
50 Fernald Road
Freeport, ME 04032
Tel: (207)865-4518
Fax: (207) 865-1136
Stantec 482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of ###
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CIVIL - PLAN - GRADING
CG101
SBTM
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E
E E
E
EEEEEEE
E
E
E
E
E
E
E
E
E
E
E
E
E
EEEEEEEE
E
E
E
E
E
E
E
EEEEE
E
EEEEEEEEE
E
E
E
E E E E E E E E E E
E
EEEEEEEEE
E
E
E E
E
E E
E
E
EEEEEEE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
W
W
W
W W
W
W
W W
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h al f in
6" th re e i nc f oo t
6"
SPECIFICATIONS:
Lowell Specifications
50 Fernald Road
Freeport, ME 04032
Tel: (207)865-4518
Fax: (207) 865-1136
Stantec 482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of ###
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CIVIL - PLAN - UTILITIES
CU101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing Number
Location
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8 9
A
1 2 3 4 5 6 7 8 9
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua
6" on e i
6" on e h al f in
6" th re e i nc f oo t
6"
SPECIFICATIONS:
Lowell Specifications
50 Fernald Road
Freeport, ME 04032
Tel: (207)865-4518
Fax: (207) 865-1136
Stantec 482 Payne Road Scarborough, ME 04074 Tel: (207) 883-3355 Fax: (207) 883-3376 of ###
VAMC - West Roxbury, MA 02132
WEST ROXBURY GARAGE 523-400
100% BID DOCUMENTS
06/15/2015
CIVIL - DETAILS - SITE
CS501