36E77618R0053-00002002.pdf

PDF 754 KB Posted

Attached to
Sioux Falls- Renovate 5th Floor Surgery Federal contract opportunity
Solicitation number
36E77618R0053
Issued by
Department of Veterans Affairs Headquarters

About this file

36E77618R0053 00002 Renovation 5th Floor Surgery - Addendum No 2.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Sioux Falls- Renovate 5th Floor Surgery, newest first.
File Type Posted
36E77618R0053-00004001.docx DOCX document
36E77618R0053-00004000.docx DOCX document
36E77618R0053-00003001.docx DOCX document
36E77618R0053-00003000.docx DOCX document
36E77618R0053-00002000.docx DOCX document
36E77618R0053-00002001.pdf PDF
36E77618R0053-00001001.pdf PDF
36E77618R0053-00001000.docx DOCX document
36E77618R0053-001.docx DOCX document
36E77618R0053-007.pdf PDF
36E77618R0053-005.pdf PDF
36E77618R0053-003.pdf PDF
36E77618R0053-004.pdf PDF
36E77618R0053-008.pdf PDF
36E77618R0053-009.docx DOCX document
36E77618R0053-010.docx DOCX document
36E77618R0053-006.pdf PDF
36E77618R0053-002.pdf PDF
36E77618R0053-000.docx DOCX document
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Renovate 5th Floor Surgery Project No.: 438-15-201 Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

01 33 24– Electronic Submittal Procedures Page 1

SECTION 01 33 24

ELECTRONIC SUBMITTAL PROCEDURES

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies requirements for provision and use of an electronic, web-based service for submittal and tracking of construction submittals for the Project.

1.2 REFERENCED DOCUMENTS

A. Additional submittal requirements: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES.

1.3 SUMMARY:

A. The intent of electronic submittals is to expedite the construction process by reducing paperwork, improving information flow, and decreasing turnaround time.

B. Shop drawing and product data submittals shall be transmitted to Architect in electronic (PDF) format using a web-based service designed specifically for transmitting and tracking submittals between construction team members.

C. The electronic submittal process is not intended for color samples, color charts, or physical material samples.

1.4 GENERAL DESCRIPTION OF PROCEDURES:

A. Submittal Preparation - Contractor may use any or all of the following options:

1. Subcontractors and Suppliers provide electronic (PDF) submittals to Contractor via the submittal exchange website.

2. Subcontractors and Suppliers provide paper submittals to General Contractor who electronically scans and converts to PDF format.

3. Subcontractors and Suppliers provide paper submittals to Scanning Service which electronically scans and converts to PDF format.

B. Contractor shall review, comment, and apply electronic stamp certifying that the submittal (as noted) complies with the requirements of the Contract Documents including verification of manufacturer / product, dimensions and coordination of information with other parts of the work.

C. Contractor shall transmit each submittal to Architect and Owner (simultaneously) using the web-based submittal exchange service.

D. Architect / Engineer review comments will be made available on web-based submittal exchange service. Contractor shall receive email notice of completed review.

E. Distribution of reviewed submittals to subcontractors and suppliers is the responsibility of the

Contractor.

Department of Veterans Affairs

01 33 24– Electronic Submittal Procedures Page 2

1.5 REQUIREMENTS AND RESPONSIBILITIES

A. Submittal Exchange Service will be provided by the VA:

1. The following submittal exchange services will be arranged and paid for by the VA for this project:

a. Submittal Exchange: 1-800-714-0024; www.submittalexchange.com.

2. Web-based tracking and approval system.

3. Automated email notice for new submittals and reminders for submittals approaching the review deadline.

4. Tracking and exchange of ITC/RFI/CO’s and other similar document as well as product and equipment submittals.

5. Means for tracking of the status such documents including whether they have been approved and released by the Owner.

6. Organized storage of submittals that is accessible for review by the designated construction team members at any time.

7. Submit a complete set of submittal on CD to the Owner at the end of the Project. Include all submittals including product submittals, shop drawings, ITC/RFI/CO’s and other similar submittals.

B. Contractor responsibilities: (All costs associated with these additional items shall be incurred by the contractor)

1. Training in the use of the service by the contractors’ team members shall be at the option of the Contractor and, if chosen, shall be paid by the Contractor

2. Contractor shall have or obtain required hardware and software: Internet Service and

Equipment Requirements:

a. Email address and Internet access at Contractor’s main office.

b. Adobe Acrobat (www.adobe.com), Bluebeam PDF Revu (www.bluebeam.com), or other similar PDF review software for applying electronic stamps and comments.

3. Contractor shall prepare or have prepared all required submittals in the PDF format required.

a. PDF files must be readable. As a general rule, a resolution of 300 dpi should be used.

b. If the Architect can download more readable product data directly from the manufacturer’s website than was submitted by the Contractor, the Architect shall reserve the right to reject the submittal.

4. Other responsibilities for submittals shall be as described in Section 01 33 23, SHOP

DRAWINGS, PRODUCT DATA, AND SAMPLES.

a. Color samples, color charts, or physical material samples shall be submitted as described in Section 01 33 23.

Department of Veterans Affairs

01 33 24– Electronic Submittal Procedures Page 3

- - - END - - -

Renovate 5th Floor Surgery 02-01-15

Department of Veterans Affairs

08 71 00- Door Hardware Page 1

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

A. Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

A. Caulking: Section 07 92 00 JOINT SEALANTS.

B. Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11 13, HOLLOW METAL

DOORS AND FRAMES;

C. Painting: Section 09 91 00, PAINTING.

D. Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS.

E. Electrical: Division 26, ELECTRICAL.

F. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

A. All hardware shall comply with UFAS, (Uniform Federal Accessible Standards) unless specified otherwise.

B. Provide rated door hardware assemblies where required by most current version of the

International Building Code (IBC).

C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified.

Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.

D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

E. The following items shall be of the same manufacturer, except as otherwise specified:

1. Cylindrical Locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

4. Exit devices.

5. Floor closers.

1.4 WARRANTY

A. Automatic door operators shall be subject to the terms of FAR Clause 52.246-21, except that the

Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latch sets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

Department of Veterans Affairs

08 71 00- Door Hardware Page 2

1.5 MAINTENANCE MANUALS

A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled

"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA

AND SAMPLES. Submit 6 copies of the schedule per Section 01 33 23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).

B. Hardware Schedule: Prepare and submit hardware schedule in the following form:

Hardware Item

Quantity Size Reference Publication Type No.

Finish Mfr.

Name and Catalog No.

Key Control Symbols

UL Mark (if fire rated and listed)

ANSI/BHMA

Finish Designation

C. Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers Association shall be submitted for approval.

Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

1.7 DELIVERY AND MARKING

A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to Contracting Officers Representative (COR) for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.

Department of Veterans Affairs

08 71 00- Door Hardware Page 3

1.8 PREINSTALLATION MEETING

A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including

Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

B. Keying: All cylinders shall be keyed into existing Falcon D-keyway Great Grand Master Key

System. Provide removable core cylinders that are removable only with a special key without disassembly of knob or lockset. Cylinders shall be 6 pin “D” keyway uncombinated standard cores. Keying information shall be furnished at a later date by the COR.

1.10 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

B. American Society for Testing and Materials (ASTM):

E2180-07................Standard Test Method for Determining the Activity of Incorporated

Antimicrobial Agent(s) In Polymeric or Hydrophobic Materials

C. American National Standards Institute/Builders Hardware Manufacturers Association

(ANSI/BHMA):

A156.1-06 ................................... Butts and Hinges

A156.2-03 ................................... Bored and Pre-assembled Locks and Latches

Department of Veterans Affairs

08 71 00- Door Hardware Page 4

A156.3-08 ................................... Exit Devices, Coordinators, and Auto Flush Bolts

A156.4-08 ................................... Door Controls (Closers)

A156.5-14 ................................... Cylinders and Input Devices for Locks.

A156.6-05 ................................... Architectural Door Trim

A156.8-05 ................................... Door Controls-Overhead Stops and Holders

A156.11-14 ................................. Cabinet Locks

A156.12-05 ............. ................... Interconnected Locks and Latches

A156.14-07 ............. ................... Sliding and Folding Door Hardware

A156.15-06 ................................. Release Devices-Closer Holder, Electromagnetic and

Electromechanical

A156.16-08 ................................. Auxiliary Hardware

A156.17-04 ............. ................... Self-Closing Hinges and Pivots

A156.18-06 ................................. Materials and Finishes

A156.20-06 ............. ................... Strap and Tee Hinges, and Hasps

A156.21-09 ................................. Thresholds

A156.22-05 ................................. Door Gasketing and Edge Seal Systems

A156.23-04 ................................. Electromagnetic Locks

A156.24-03 ................................. Delayed Egress Locking Systems

A156.25-07 ............. ................... Electrified Locking Devices

A156.26-06 ................................. Continuous Hinges

A156.28-07 ............. ................... Master Keying Systems

A156.29-07 ............. ................... Exit Locks and Alarms

A156.30-03 ............. ................... High Security Cylinders

A156.31-07 ................................ Electric Strikes and Frame Mounted Actuators

A156.36-10 ................................. Auxiliary Locks

A250.8-03 ................................... Standard Steel Doors and Frames

D. National Fire Protection Association (NFPA):

80-10 .......................................... Fire Doors and Other Opening Protectives

101-09 ........................................ Life Safety Code

E. Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

PART 2 - PRODUCTS

2.1 BUTT HINGES

A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The

Department of Veterans Affairs

08 71 00- Door Hardware Page 5 following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type

A8111/A5111 for doors over 900 mm (3 feet) wide. Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.

B. Provide quantity and size of hinges per door leaf as follows:

1. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

2. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

3. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm (4-1/2 inches x 4-1/2 inches) hinges.

4. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x

114 mm (5 inches x 4-1/2 inches).

5. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm

(5 inches x 4-1/2 inches).

6. Provide heavy-weight hinges where specified.

7. At doors weighing 330 kg (150 lbs.) or more, furnish 127 mm (5 inch) high hinges.

C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 CONTINUOUS HINGES

A. ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Product Directory."

B. General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete

C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a Teflon-coated 6.35mm

(0.25-inch) minimum diameter pin that extends entire length of hinge.

1. Base Metal for Exterior Hinges: Stainless steel.

2. Base Metal for Interior Hinges: Stainless steel.

3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.

4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.

5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.

6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.

Department of Veterans Affairs

08 71 00- Door Hardware Page 6

7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.

8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.

2.3 DOOR CLOSING DEVICES

A. Closing devices shall be products of one manufacturer for each type specified.

B. All closers shall be adjusted such that the opening force shall not exceed 5 pounds and closing time is not less than 5 seconds from 90 degree open position.

2.4 OVERHEAD CLOSERS

A. Conform to ANSI A156.4, Grade 1.

B. Closers shall conform to the following:

1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

2. Where specified, closer shall have hold-open feature.

3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.

4. Material of closer body shall be forged or cast.

5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.

6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.

7. Closers shall have full size metal cover; plastic covers will not be accepted.

8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.

9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.

10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.

11. Provide parallel arm closers with heavy duty rigid arm.

12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.

Department of Veterans Affairs

08 71 00- Door Hardware Page 7

13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.

14. All closers shall have a 1 ½” (38mm) minimum piston diameter.

2.5 DOOR STOPS

A. Conform to ANSI A156.16.

B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops.

C. Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251

(rubber pads having concave face) to receive turn piece or button.

D. Provide floor stops (Type L02141 or L02161 in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.

E. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type

L02121 elsewhere.

F. Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

G. Omit stops where floor mounted door holders are required and where automatic operated doors occur.

H. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.

I. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.

J. Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

K. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.

L. Where the specified wall or floor stop cannot be used, provide concealed overhead stops

(surface-mounted where concealed cannot be used).

2.6 OVERHEAD DOOR STOPS AND HOLDERS

A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only

Department of Veterans Affairs

08 71 00- Door Hardware Page 8 at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.

2.7 FLOOR DOOR HOLDERS

A. Conform to ANSI Standard A156.16. Provide extension strikes for Types L01301 and L01311 holders where necessary.

2.8 LOCKS AND LATCHES

A. Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have six pins. Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with construction removable cores and construction master keys. Cylinder shall be removable by special key. Construct all cores so that they will be interchangeable into the core housings of all rim locks, cylindrical locks, and any other type lock included in the Falcon Type D Great Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. The COR will provide a construction core to allow opening and closing during construction and prior to the installation of final cores.

B. In addition to above requirements, locks and latches shall comply with following requirements:

1. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension.

Provide lever design to match design selected by Architect or to match existing lever design.

Where two turn pieces are specified for privacy lock ANSI F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)

3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.

4. Privacy locks in non-mental-health patient rooms shall have an inside thumbturn for privacy and an outside thumbturn for emergency entrance. Single occupancy patient privacy doors shall typically swing out; where such doors cannot swing out, provide center-pivoted doors with rescue hardware.

2.9 PUSH-BUTTON COMBINATION LOCKS

A. ANSI/BHMA A156.5, Grade 1. Self-Powering pushbutton entry with No-Pump technology.

B. Construction: Heavy duty cylindrical lock housing conforming to ANSI/BHMA A156.25, Grade 1.

Lever handles and operating components in compliance with the UFAS and the ADA Accessibility

Guidelines. Match lever handles of locks and latchsets on adjacent doors.

Department of Veterans Affairs

08 71 00- Door Hardware Page 9

C. Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.

D. Basis of Design Push-Button Combination Lock: KABA PowerPlex 2000 Series with “No-Pump” technology: Part # P2031LLB626.

2.9 CARD READERS

Provide and install card readers where indicated. Integrate card readers with other specified systems and systems that are in place. Refer to Section 28 13 00, Physical Access Control Systems, for card reader requirements.

2.10 ELECTRIC STRIKES

A. ANSI/ BHMA A156.31 Grade 1.

B. General: Use fail-secure electric strikes at fire-rated doors.

2.11 KEYS

A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks 100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.12 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

A. Conform to ANSI Standard A156.6.

B. Provide protective plates and door edging as specified below:

1. Kick plates, mop plates and armor plates of metal, Type J100 series.

2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates and/or mop plates are not required on following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

d. Both sides of aluminum entrance doors.

Department of Veterans Affairs

08 71 00- Door Hardware Page 10

4. Armor plates for doors are listed under Article "Hardware Sets". Armor plates shall be thickness as noted in the hardware set, 875 mm (35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all

4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard.

Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.

2.13 EXIT DEVICES

A. Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.

B. Surface vertical rod panics shall only be provided less bottom rod; provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.

C. Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.

D. Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.

E. At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.

F. Exit devices for fire doors shall comply with Underwriters Laboratories, Inc., requirements for Fire

Exit Hardware. Submit proof of compliance.

Department of Veterans Affairs

08 71 00- Door Hardware Page 11

2.14 FLUSH BOLTS (AUTOMATIC)

A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm

(1-1/2 by 3-1/2 inches).

2.15 DOOR PULLS WITH PLATES

A. Conform to ANSI A156.6. Pull Type J401, 152 mm (6 inches) high by 19 mm (3/4 inches) diameter with plate Type J302, 90 mm by 350 mm (3-1/2 inches by 14 inches), unless otherwise specified. Provide pull with projection of 70 mm (2 3/4 inches) and a clearance of 51 mm (2 inches). Cut plates of door pull plate for cylinders, or turn pieces where required.

2.16 PUSH PLATES

A. Conform to ANSI A156.6. Metal, Type J302, 200 mm (8 inches) wide by 350 mm (14 inches) high. Provide metal Type J302 plates 100 mm (4 inches wide by 350 mm (14 inches) high) where push plates are specified for doors with stiles less than 200 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.

2.17 COMBINATION PUSH AND PULL PLATES

A. Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.

2.18 COORDINATORS

A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with

Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.

2.19 THRESHOLDS

A. Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.

B. For thresholds at elevators entrances see other sections of specifications.

Department of Veterans Affairs

08 71 00- Door Hardware Page 12

C. At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.

D. Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.

2.20 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR

SOUND CONTROL DOORS

A. Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).

2.21 MISCELLANEOUS HARDWARE

A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types): Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

B. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors. Provide 4 mutes or silencers for frames for each Dutch type door. Provide 2 mutes for each edge of sliding door which would contact door frame.

2.22 FINISHES

A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous

Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.

B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

C. Miscellaneous Finishes:

1. Hinges --exterior doors: 626 or 630.

2. Hinges --interior doors: 652 or 630.

3. Pivots: Match door trim.

4. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

5. Thresholds: Mill finish aluminum.

6. Cover plates for floor hinges and pivots: 630.

7. Other primed steel hardware: 600.

D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces // except where otherwise specified. //

E. Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has

Department of Veterans Affairs

08 71 00- Door Hardware Page 13 passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.

2.23 BASE METALS

A. Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

A. For existing buildings locate hardware on doors at heights to match existing hardware. The

Contractor shall visit the site, verify location of existing hardware and submit locations to VA

Contracting Officers Representative (COR) for approval.

B. Typical Hardware Heights from Finished Floor:

1. Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches).

2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).

3. Deadlocks centerline of strike 1219 mm (48 inches).

4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.

5. Centerline of door pulls to be 1016 mm (40 inches).

6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.

7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.

8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.

3.2 INSTALLATION

A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. Where closers are mounted on doors they shall be mounted with sex nuts and bolts; foot shall be fastened to frame with machine screws.

B. Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

35 mm (1-3/8 inch) (hollow core wood doors)

Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)

Department of Veterans Affairs

08 71 00- Door Hardware Page 14

C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

D. Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by COR. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.

E. Hinges Required Per Door:

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm (7 ft 6 in) high 3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Dutch type doors 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less 2 butts

Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts

F. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish.

Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or raw plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.

G. After locks have been installed; coordinate with the Contracting Officers Representative (COR) for installation of final cores.

3.3 FINAL INSPECTION

A. Installer to provide letter to VA Contracting Officers Representative (COR) that upon completion, installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Contracting Officers

Representative (COR) and VA Locksmith.

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

A.

B.

QTY DESCRIPTION CATALOG NUMBER

1 EA CONT. HINGE

1 EA PUSH PLATE J302

1 EA PULL PLATE J401 X J302

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA MOP PLATE J103

1 EA FLOOR STOP L02121 X 3 FASTENERS

3 EA SILENCER L03011

QTY DESCRIPTION CATALOG NUMBER

1 EA CONT. HINGE

1 EA PUSH BUTTON LOCK KABA - P2031LLB626

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA MOP PLATE J103

1 EA FLOOR STOP L02121 X 3 FASTENERS

3 EA SILENCER L03011

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA KEY PRIVACY INDICATOR LOCK F76 X OCCUPANCY INDICATOR

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

J103

AT INSWING DOORS

1 EA FLOOR STOP L02121 X 3 FASTENERS

1 SET SEALS R0Y154

1 EA THRESHOLD BY OTHERS

DOOR NUMBER: 507

HARDWARE GROUP NO. 02

DOOR NUMBER: 510B 510D

1 EA MOP PLATE

Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.

Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.

ELECTRIC HARDWARE ABBREVIATIONS LEGEND:

ADO = Automatic Door Operator EMCH = Electro-Mechanical Closer-Holder MHO = Magnetic Hold-Open (wall- or floor-mounted)

HARDWARE GROUP NO. 01B

HARDWARE GROUP NO. 01

DOOR NUMBER: 510A 510C

3.5 HARDWARE SETS

08 71 00- Door Hardware Page 15

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA KEY PRIVACY INDICATOR LOCK F76 X OCCUPANCY INDICATOR

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA MOP PLATE J103

1 EA FLOOR STOP L02121 X 3 FASTENERS

2 SET SEALS R0Y154

1 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

1 EA THRESHOLD BY OTHERS

QTY DESCRIPTION CATALOG NUMBER

QUANTITY AND TYPE AS REQUIRED

X 4-THRUWIRE TRANSFER

1 EA ELECTRIFIED LOCK F109 (E01-REX, E06) 24VDC

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA FLOOR STOP L02121 X 3 FASTENERS

1 SET SEALS R0Y154

1 EA CARD READER BY OTHERS (LEADING FROM CORRIDOR

500C INTO COMPUTER 536)

1 EA POWER SUPPLY REGULATED, FILTERED, 24VDC,

AMPERAGE AS REQUIRED

QTY DESCRIPTION CATALOG NUMBER

X INTERGRAL HINGE GUARD CHANNEL

X ADJUSTA-SCREWS

1 EA PUSH BUTTON LOCK KABA - P2031LLB626

1 EA SURFACE CLOSER C02011/C02021

1 EA ARMOR PLATE J101 X 1.275 MM THICKNESS

1 EA DOOR EDGE GUARD J208M/J211 (VERIFY), CUT: HARDWARE

L02101 CONVEX

AT INSWING DOORS

L02121 X 3 FASTENERS

AT OUTSWING DOORS

1 SET SEALS R0Y154

HINGEEA

1 EA WALL STOP

1 EA FLOOR STOP

HARDWARE GROUP NO. 05

DOOR NUMBER: 522

1 EA CONT. HINGE

DOOR NUMBER: 503 544 545

HARDWARE GROUP NO. 04

DOOR NUMBER: 536

HARDWARE GROUP NO. 03

08 71 00- Door Hardware Page 16

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA ENTRANCE LOCK F109

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA FIRE/LIFE WALL MAG C00011 TRI-VOLTAGE

1 SET SEALS R0Y154

QTY DESCRIPTION CATALOG NUMBER

QUANTITY AND TYPE AS REQUIRED

X 4-THRUWIRE TRANSFER

1 EA ELECTRIFIED LOCK F109 (E01-REX, E06) 24VDC

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA FLOOR STOP L02121 X 3 FASTENERS

2 SET SEALS R0Y154

1 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

1 EA THRESHOLD J32300 X 57MM WIDTH

1 EA CARD READER BY OTHERS (LEADING FROM CORRIDOR

501A INTO CONFERENCE 508)

1 EA POWER SUPPLY REGULATED, FILTERED, 24VDC,

AMPERAGE AS REQUIRED

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA STOREROOM LOCK F86

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA DOOR EDGE GUARD J208M/J211 (VERIFY), CUT: HARDWARE

L02101 CONVEX

AT OUTSWING DOORS

L02121 X 3 FASTENERS

AT INSWING DOORS

1 SET SEALS R0Y154

1 EA FLOOR STOP

HARDWARE GROUP NO. 08

DOOR NUMBER: 524 543

1 EA WALL STOP

HARDWARE GROUP NO. 06

DOOR NUMBER: 501

HARDWARE GROUP NO. 07

DOOR NUMBER: 508

EA HINGE

08 71 00- Door Hardware Page 17

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

X INTEGRAL HINGE GUARD CHANNEL

X ADJUSTA-SCREWS

1 EA STOREROOM LOCK F86

1 EA SURFACE CLOSER C02011/C02021

1 EA ARMOR PLATE J101 X 3.175 MM THICKNESS

1 EA DOOR EDGE GUARD J208M/J211 (VERIFY), CUT: HARDWARE

1 EA FLOOR STOP L02121 X 3 FASTENERS

1 SET SEALS R0Y154

QTY DESCRIPTION CATALOG NUMBER

X INTEGRAL HINGE GUARD CHANNEL

X ADJUSTA-SCREWS

2 SET AUTO FLUSH BOLT TYPE 25 LESS BOTTOM BOLT

1 EA OFFICE LOCK F82

1 EA COORDINATOR TYPE 21A

2 EA SURFACE CLOSER C02011/C02021

2 EA ARMOR PLATE J101 X 3.175 MM THICKNESS

J208M/J211 (VERIFY), CUT: HARDWARE

AT WOOD DOORS

2 EA FLOOR STOP L02121 X 3 FASTENERS

2 SET SEALS R0Y154

1 EA ASTRAGAL R0Y634 X ROY154 X THRU-BOLTS

2 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

1 EA THRESHOLD J32300 X 57MM WIDTH

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 SET AUTO FLUSH BOLT TYPE 25 LESS BOTTOM BOLT

1 EA STOREROOM LOCK F86

1 EA COORDINATOR TYPE 21A

2 EA SURFACE CLOSER C02011/C02021

2 EA ARMOR PLATE J101 X 3.175 MM THICKNESS

2 EA FLOOR STOP L02121 X 3 FASTENERS

1 SET SEALS R0Y154

1 EA ASTRAGAL R0Y634 X ROY154 X THRU-BOLTS

NOTE: INSTALL LOCK TRIM PROTECTOR BAR ON PUSH SIDE OF ACTIVE LEAF TO

PROTECT LEVER TRIM.

HARDWARE GROUP NO. 11

DOOR NUMBER: 534

2 EA CONT. HINGE

2 EA DOOR EDGE GUARD

1 EA CONT. HINGE

HARDWARE GROUP NO. 10

DOOR NUMBER: 523

HARDWARE GROUP NO. 09

DOOR NUMBER: 515

08 71 00- Door Hardware Page 18

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

X INTEGRAL HINGE GUARD CHANNEL

X ADJUSTA-SCREWS X 8-THRUWIRE

TRANSFER

X IN-HINGE ACCESS PANEL

1 EA CYLINDER TYPE AS REQUIRED

1 EA FIRE EXIT HARDWARE TYPE 7 OR 8 F75 (E04)

1 EA FIRE EXIT HARDWARE TYPE 7 OR 8 F109 LEVER (E04)

2 EA KICK PLATE J102

J208M/J211 (VERIFY), CUT: HARDWARE

AT WOOD DOORS

2 EA FLOOR STOP L02121 X 3 FASTENERS

1 EA MEETING STILE SEAL R0Y834

2 SET SEALS R0Y154

2 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

2 EA CARD READER BY OTHERS (ONE IN EACH DIRECTION OF

TRAVEL)

2 EA AUTO DOOR OPERATOR 6010

2 EA TOUCHLESS ACTUATOR SWITCH 697

2 EA DOOR POSITION SWITCH DPS SERIES

1 EA EXIT MOTION SENSOR XMS

1 EA EMERGANCY EXIT BUTTON EEB2

1 EA 24/7 TIMER BY ACCESS CONTROL SYSTEM

1 EA POWER SUPPLY BY EXIT DEVICE MANUFACTURER FOR

E04 FUNCTION

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA PASSAGE SET F75

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA WALL STOP L02101 CONVEX

1 SET SEALS R0Y154

HARDWARE GROUP NO. 13

DOOR NUMBER: 510F

2 EA DOOR EDGE GUARD

NOTE: POWER TRANSFERS SHARED BY ELECTRIC PANIC AND RE-ACTIVATION SENSOR

WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).

AUTO DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13.

DOOR NUMBER: 510

2 EA CONT. HINGE

HARDWARE GROUP NO. 12

08 71 00- Door Hardware Page 19

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA STOREROOM LOCK F86

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA WALL STOP L02101 CONVEX

1 SET SEALS R0Y154

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA STOREROOM LOCK F86

C02011/C02021

WITH STOP ARM

1 EA KICK PLATE J102

1 SET SEALS R0Y154

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA PASSAGE F75

C02011/C02021

WITH STOP ARM

1 EA KICK PLATE J102

1 SET SEALS R0Y154

QTY DESCRIPTION CATALOG NUMBER

QUANTITY AND TYPE AS REQUIRED

X 4-THRUWIRE TRANSFER

1 EA ELECTRIFIED LOCK F109 (E01-REX, E06) 24VDC

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA WALL STOP L02101 CONVEX

1 SET SEALS R0Y154

1 EA CARD READER BY OTHERS (LEADING FROM ENTRY

LOBBY INTO CORRIDOR 510)

1 EA POWER SUPPLY REGULATED, FILTERED, 24VDC,

AMPERAGE AS REQUIRED

HARDWARE GROUP NO. 16

DOOR NUMBER: 510E

EA HINGE

HARDWARE GROUP NO. 15B

DOOR NUMBER: 500E

1 EA SURFACE CLOSER

HARDWARE GROUP NO. 15

DOOR NUMBER: 500F

1 EA SURFACE CLOSER

HARDWARE GROUP NO. 14

DOOR NUMBER: 527 521

08 71 00- Door Hardware Page 20

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA FIRE EXIT HARDWARE TYPE 1 F86

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA WALL STOP L02101 CONVEX

1 SET SEALS R0Y154

QTY DESCRIPTION CATALOG NUMBER

2 EA CONT. HINGE

2 EA FIRE EXIT HARDWARE TYPE 7 OR 8 F75 (E04)

2 EA SURFACE CLOSER C02011/C02021

2 EA KICK PLATE J102

2 EA FIRE/LIFE WALL MAG C00011 TRI-VOLTAGE

1 EA MEETING STILE SEAL R0Y834

1 SET SEALS R0Y154

EA N/C F/A CONTACT BY F/A CONTRACTOR

QTY DESCRIPTION CATALOG NUMBER

1 EA CONT. HINGE

1 EA PASSAGE F75

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA WALL STOP L02101 CONVEX

2 SET SEALS R0Y154

1 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

1 EA THRESHOLD J32300 X 57MM WIDTH

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA OFFICE LOCK F082

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA FLOOR STOP L02121 X 3 FASTENERS

1 SET SEALS R0Y154

HARDWARE GROUP NO. 19

DOOR NUMBER: 518 519

HARDWARE GROUP NO. 20

DOOR NUMBER: 502 505 506 525 528 529 530 531 532 533

535 537 538 539 540 541 542

HARDWARE GROUP NO. 17

DOOR NUMBER: 534B

HARDWARE GROUP NO. 18

DOOR NUMBER: 500C

08 71 00- Door Hardware Page 21

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

EA HINGE QUANTITY AND TYPE AS REQUIRED

1 EA OFFICE LOCK F82

1 EA SURFACE CLOSER C02011/C02021

1 EA KICK PLATE J102

1 EA FLOOR STOP L02121 X 3 FASTENERS

2 SET SEALS R0Y154

1 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

1 EA THRESHOLD J32300 X 57MM WIDTH

1 EA DOOR VIEWER

LO3221 - 190 DEG. (VIEW INTO CORRIDOR

OR ENTRY LOBBY)

QTY DESCRIPTION CATALOG NUMBER

X INTEGRAL HINGE GUARD CHANNEL

X ADJUSTA-SCREWS X 4-THRUWIRE

TRANSFER

X IN-HINGE ACCESS PANEL

1 EA PUSH/PULL LATCH F09 X PADDLES POINTING DOWN

1 EA ELECTRIC STRIKE E09321

1 EA SURFACE CLOSER C02011/C02021

1 EA ARMOR PLATE J101 X 1.275 MM THICKNESS

1 EA DOOR EDGE GUARD J208M/J211 (VERIFY), CUT: HARDWARE

1 EA FLOOR STOP L02121 X 3 FASTENERS

1 SET SEALS R0Y154

2 EA AUTO DOOR OPERATOR 6010

2 EA TOUCHLESS ACTUATOR SWITCH 697

2 EA DOOR POSITION SWITCH DPS SERIES

1 EA EXIT MOTION SENSOR XMS

1 EA EMERGANCY EXIT BUTTON EEB2

1 EA 24/7 TIMER BY ACCESS CONTROL SYSTEM

1 EA POWER SUPPLY REGULATED, FILTERED, 24VDC,

AMPERAGE AS REQUIRED

1 EA CONT. HINGE

NOTE: POWER TRANSFER PIVOT IS FOR RE-ACTIVATION SENSOR WIRING (RE-

ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13)

AUTOMATIC DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR

OPERATORS.

HARDWARE GROUP NO. 21

DOOR NUMBER: 504 509 526

HARDWARE GROUP NO. 22

DOOR NUMBER: 511 512

08 71 00- Door Hardware Page 22

Department of Veterans Affairs VA Healthcare System Sioux Falls, South Dakota

02‐01‐15

QTY DESCRIPTION CATALOG NUMBER

X INTEGRAL HINGE GUARD CHANNEL

X ADJUSTA-SCREWS X 4-THRUWIRE

TRANSFER

X IN-HINGE ACCESS PANEL

1 EA PUSH BUTTON LOCK KABA - P2031LLB626

1 EA SURFACE CLOSER C02011/C02021

1 EA ARMOR PLATE J101 X 1.275 MM THICKNESS

1 EA DOOR EDGE GUARD J208M/J211 (VERIFY), CUT: HARDWARE

SET SEALS R0Y154

1 EA AUTO DOOR BOTTOM R0Y346 - HEAVY DUTY

1 EA THRESHOLD…