06_ENC_JCI_Comm Horizontal Cabling_As-Builts-pdf.pdf
PDF 2 MB Posted
- Attached to
- Z1DA--554-21-704 EHRM NextGen WiFi Federal contract opportunity
- Solicitation number
- 36C25924Q0007
About this file
This document package includes horizontal cabling drawings and specifications for a federal contract opportunity with the Department of Veterans Affairs. The solicitation seeks proposals for an EHRM NextGen WiFi project at Veterans Integrated Service Network 19 to provide wireless infrastructure and cabling throughout multiple levels and areas of a medical facility. Drawings depict proposed locations and mounting details of wireless access points, switches, patch panels, fiber runs and device outlets. Specifications address technical requirements for hardware, cabling standards and labeling conventions. Response date and anticipated award date are not provided.
View the file
Other files for this federal contract opportunity
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C
C
D
D
B
B
A
A
RA
RA
WAP
1 0
MECH
2 0
+18"
SC
1 0 0
DOMESTIC WATER BOOSTER PUMP
PANEL ETHERNET DROP
1 0 +96"
06-BT-A4-M1
LB-101
MECH
06-BT-A3-M1
LB-102
FIRE PUMP RM
06-BT-SE16
LE-S01
ELEV
06-BT-ST1
LB-ST1
STAIR
UP
UP
ENC-TR-1 BOUNDARY
ENC-TR-1 BOUNDARY
L1-142-D1-02 L1-142-D1-03
L1-142-D1-01
L1-142-S1-01
L1-142-D1-05
L1-142-D1-06
WAP
1 0
11 12 08 09 13
03040506
Scale
Release Date
These Drawings are based on details from the following Contract Documents.
Telecom / AV Drawings
Security Drawings:
Electrical Drawings:
Mechanical Drawings:
Fire Protection Drawings:
SEE PLAN
Field Signoff
BIM Manager Signoff
BIM Team Signoff
Key Plan
N
JCI / IME Project Office 3250 Quentin St., Unit 112
Aurora, CO 80011 www.imelect.com
14900 Grand River Rd, Ste 100 Ft. Worth, TX 76155
Phone: 817-355-5385 www.dmitechinc.com
3/
/2
8:
:1
A
M
ENCLV041
BASEMENT HORIZONTAL
CABLING DEVICES
DENVER VA
03/27/15
TH
MB
TC
REV DESCRIPTION DATE
1 JCI Shop Drawing Update 05/30/2014
2 KT RFI #5490 12/16/2014
3 KT RFI #5220 12/16/2014
1/8" = 1'-0"1 BASEMENT LEVEL HORIZONTAL CABLING DEVICES NORTH
06.TA.300_CD12
06.QY.100_CD12-MAY-22-14
06.VM.300-A
06.VM.800
SYSTEM AND COLOR CODE
DT DATA TELECOM MAGENTA GRAY WITH WHITE BANDING
BIM COLOR CONDUIT COLOR
MA MASS NOTIFICATION ORANGE GRAY
NC NURSE CALL GREEN GREEN BANDING
FA FIRE ALARM RED OSHA RED
SC SECURITY CYAN WHITE
DDC DDC SYSTEM, AUMS AND MED GAS BLUE BLUE
CT CABLE TRAY BLACK
AV AUDIO-VISUAL COMMUNICATION YELLOW GREEN GRAY WITH WHITE BANDING
IBW IN-BUILDING WIRELESS BLACK
GENERAL NOTES
1. INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM CONTRACT
FURNISHED DRAWINGS AND/OR VENDOR SHOP DRAWINGS. INTERMOUNTAIN
ELECTRIC INC. IS NOT RESPOSIBLE FOR THE ACCURACY OF ANY INFORMATION
OR THE ADEQUACY AND CONFORMANCE TO CURRENT PREVAILING CODES OF
ANY WORK SHOWN ON THE DRAWINGS.
2. INFORMATION SHOWN ON THE DRAWINGS IS ONLY CURRENT UP TO THE DATE
OF ISSUANCE. CHANGES OCCURING AFTER THE ISSUE DATE SHALL BE THE SOLE
RESPONSIBILITY OF OTHERS.
HORIZONTAL CABLING CALLOUT SCHEDULE
1. CABLE LABELING SHOWN HEREIN HAS BEEN VERIFIED AND APPROVED BY THE VA RESIDENT
ENGINEER, VAMC IT, KT, AND JCI PER RFI #06428.
WHERE X= QTY. OF DATA PORTS
Y= QTY. OF COAXIAL DROPS (RG-6)
Z= QTY. OF FIBER STRANDS
{BUILDING & FLOOR} - {CLOSET ROOM} - {SYSTEM PANEL} - {PORT}
WHERE SYSTEM PANEL IS DEFINED AS:
D# - DATA PATCH PANEL (HORIZONTAL RACK)
PM# - PHYSIOLOGICAL MONITOR PATCH PANEL (FMS/BIOMED RACK)
S# - SECURITY PATCH PANEL (UPS/SECURITY RACK)
HC# - HEALTHCARE CAMERA PANEL (FMS/BIOMED RACK)
EX: H1-217-D1-01 IBS BUILDING (H) FLOOR 1, CLOSET ROOM 217, DATA PATCH PANEL, PORT #1
X,Y,Z
DEVICE TAG
DEVICE TYPE
CAT 6 / COAX / FIBER (F)
HEIGHT AFF TO CENTER OF BOX
AS-BUILT
4 AS-BUILT 12/22/2016
Risers to cable tray
CR
CR
UP
UP
UP
UP
DN
Tectonic Copyright 2007
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
M
M
B
B
A
A
RA
RA
WAP
1 0
+96"
IC
1 0 0
+48" T.O.D
2 0 +18"
2 0 +18"
2 0 +18"2 0
+18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
AC
2 0
+36"
2 0 +18"
2 0 +18"
ELEC
2 0
+18"
2 1 +18"
2 0 +18"
2 1
06-SV-B3-02
LS-101
MALE LOCKERS
06-SV-C3-02
LS-103
FEMALE LOCKERS
06-SV-C3-01
LS-101
STAFF TLT
06-SV-B1-02
LS-102
WORK
06-SV-D1-02
LS-102
PLUMBING WORK 06-SV-E1-03
LS-102A
PLUMBING STOR
06-SV-E1-02
LS-106
ELEC SHOP WORK
06-SV-G1-02
LS-114
REFR SHOP
06-SV-F1-01
LS-108
OFFICE
06-SV-J1-01
LS-120
LOCKSMITH STOR
06-SV-F1-02
LS-110
OFFICE 06-SV-G1-01
LS-114
AIR COND. EQUIP
06-SV-J1-05
LS-122
PAINT SHOP EQUIP
06-SV-G1-03
LS-114
AIR COND. WORK
06-SV-G1-04
LS-114
AIR COND. STOR
06-SV-F1-04
LS-C03
HALL
06-SV-F1-03
TAG-OUT/COPY
06-SV-E1-05
LS-106A
ELEC SHOP STOR
06-SV-D1-01
LS-102
PLUMBING EQUIP
06-SV-C1-01
LS-102
MACH SHOP EQUIP
06-SV-B1-01
LS-102
EQUIP STOR
06-SV-C1-02
LS-102
MACH SHOP WORK
06-SV-D3-02
LOCKER VEST
06-SV-D2-01
LS-C02
CORRIDOR
06-SV-H1-01
LS-116
STAFF LOUNGE
06-SV-H1-02
LS-118
WORK
06-SV-J1-04
LS-122
PAINT SHOP WORK
SC
1 0 0 +108"
SC
1 0 0 +108"
SC
1 0 0 +108"
SC
1 0 0 +108"
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
2 0
SC
1 0 0 +108"
06-SV-C3-04
LS-103
STAFF TLT
06-SV-D3-01
LS-105
HAC
06-SV-J1-02
LS-120
LOCKSMITH WORK
06-SV-E1-01
LS-106
ELEC SHOP EQUIP
ELEC
2 0
+18"
06-SV-ST1
LS-ST1
STAIR
06-SV-SE16
LE-S01
ELEV
5 4
IC
1 0 0
+48" T.O.D
6"
ENC-TR-1 BOUNDARY
ENC-TR-1 BOUNDARY
EN
C
-TR
-1 BO
U N
D
AR
Y
EN
C
-T R
-1 B
O U
N D
AR
Y
C O
N -T
R -0
A
BO
U N
D
AR
Y
L1-142-D1-07
L1-142-S1-21
L1-142-S1-03
L1-142-S1-04
L1-142-S1-05
L1-142-S1-06
L1-142-S1-07
L1-142-S1-20
L1-142-D1-08
L1-142-D1-09
L1-142-D1-10
L1-142-D1-12 L1-142-D1-13
L1-142-D1-14 L1-142-D1-15
L1-142-D1-16 L1-142-D1-17
L1-142-D1-18
L1-142-D1-19 L1-142-D1-20
L1-142-D1-21 L1-142-D1-22
L1-142-D1-23 L1-142-D1-24
L1-142-D1-25 L1-142-D1-26
L1-142-D1-27
L1-142-D1-30 L1-142-D1-31
L1-142-D1-34 L1-142-D1-35
L1-142-D1-36 L1-142-D1-37
L1-142-D1-32 L1-142-D1-33
2 0 +18"
L1-142-D1-28 L1-142-D1-29
L1-142-D1-38 L1-142-D1-39
L1-142-D1-40 L1-142-D1-41
L1-142-D1-42
L1-142-D1-43 L1-142-D1-44
L1-142-D1-45 L1-142-D1-46
L1-142-D1-47 L1-142-D1-48
L1-142-D2-01 L1-142-D2-02
L1-142-D2-03 L1-142-D2-04
L1-142-D2-05 L1-142-D2-06
L1-142-D2-07 L1-142-D2-08
L1-142-D2-09
L1-142-D2-10 L1-142-D2-11 L1-142-C-01
L1-142-D2-12 L1-142-D2-13 L1-142-C-02
L1-142-D2-14 L1-142-D2-15
L1-142-D2-16 L1-142-D2-17
L1-142-D2-18 L1-142-D2-19
L1-142-D2-20 L1-142-D2-21
L1-142-D2-22
L1-142-D2-23 L1-142-D2-24
L1-142-D2-25 L1-142-D2-26
L1-142-D2-27
1 0 0
L1-142-S1-08
SPARE
1 0 0
L1-142-S1-02
SPARE
11 12 08 09 13
03040506
Scale
Release Date
These Drawings are based on details from the following Contract Documents.
Telecom / AV Drawings
Security Drawings:
Electrical Drawings:
Mechanical Drawings:
Fire Protection Drawings:
SEE PLAN
Field Signoff
BIM Manager Signoff
BIM Team Signoff
Key Plan
N
JCI / IME Project Office 3250 Quentin St., Unit 112
Aurora, CO 80011 www.imelect.com
14900 Grand River Rd, Ste 100 Ft. Worth, TX 76155
Phone: 817-355-5385 www.dmitechinc.com
3/
/2
8:
:3
A
M
ENCLV065
SERVICE LEVEL - HORIZONTAL
CABLING DEVICES
DENVER VA
03/27/15
TH/GS
MB
TC
REV DESCRIPTION DATE
1 KT RFI #4632 06/09/2014
2 KT RFI #2800 05/22/2014
3 JCI Shop Drawing Update 05/30/2014
4 KT RFI #5272 09/01/2014
5 RFP #0246 10/06/2014
6 KT RFI #5490 12/16/2014
7 PER KT RFI 5898 (VA RFI 5191)
RELOCATED
3/27/2015
1/8" = 1'-0"1 SERVICE LEVEL - HORIZONTAL CABLING DEVICES
NORTH
06.TA.300_CD12
06.QY.100_CD12-MAY-22-14
06_QY_100_CD12
06.VM.300-B
06.VM.802
06.VM.801
06.SI.800
06.SI.100
06.SI.300
SYSTEM AND COLOR CODE
DT DATA TELECOM MAGENTA GRAY WITH WHITE BANDING
BIM COLOR CONDUIT COLOR
MA MASS NOTIFICATION ORANGE GRAY
NC NURSE CALL GREEN GREEN BANDING
FA FIRE ALARM RED OSHA RED
SC SECURITY CYAN WHITE
DDC DDC SYSTEM, AUMS AND MED GAS BLUE BLUE
CT CABLE TRAY BLACK
AV AUDIO-VISUAL COMMUNICATION YELLOW GREEN GRAY WITH WHITE BANDING
IBW IN-BUILDING WIRELESS BLACK
GENERAL NOTES
1. INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM CONTRACT
FURNISHED DRAWINGS AND/OR VENDOR SHOP DRAWINGS. INTERMOUNTAIN
ELECTRIC INC. IS NOT RESPOSIBLE FOR THE ACCURACY OF ANY INFORMATION
OR THE ADEQUACY AND CONFORMANCE TO CURRENT PREVAILING CODES OF
ANY WORK SHOWN ON THE DRAWINGS.
2. INFORMATION SHOWN ON THE DRAWINGS IS ONLY CURRENT UP TO THE DATE
OF ISSUANCE. CHANGES OCCURING AFTER THE ISSUE DATE SHALL BE THE SOLE
RESPONSIBILITY OF OTHERS.
HORIZONTAL CABLING CALLOUT SCHEDULE
1. CABLE LABELING SHOWN HEREIN HAS BEEN VERIFIED AND APPROVED BY THE VA RESIDENT
ENGINEER, VAMC IT, KT, AND JCI PER RFI #06428.
WHERE X= QTY. OF DATA PORTS
Y= QTY. OF COAXIAL DROPS (RG-6)
Z= QTY. OF FIBER STRANDS
{BUILDING & FLOOR} - {CLOSET ROOM} - {SYSTEM PANEL} - {PORT}
WHERE SYSTEM PANEL IS DEFINED AS:
D# - DATA PATCH PANEL (HORIZONTAL RACK)
PM# - PHYSIOLOGICAL MONITOR PATCH PANEL (FMS/BIOMED RACK)
S# - SECURITY PATCH PANEL (UPS/SECURITY RACK)
HC# - HEALTHCARE CAMERA PANEL (FMS/BIOMED RACK)
EX: H1-217-D1-01 IBS BUILDING (H) FLOOR 1, CLOSET ROOM 217, DATA PATCH PANEL, PORT #1
X,Y,Z
DEVICE TAG
DEVICE TYPE
CAT 6 / COAX / FIBER (F)
HEIGHT AFF TO CENTER OF BOX
AS-BUILT
8 AS-BUILT 12/22/2016
UP
DN
UP
DN
UP
UP
UP
UP
Tectonic Copyright 2007
Tectonic Copyright 2007
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
L
L
M
M
B
B
A
A
RA
RA
WAP
1 0
+96"
SC
1 0 0 +96"
MECH
2 0 +18"
MECH
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
TV
1 1
+72" ELEC
2 0
+18"
SC
1 0 0 (F)
+108"
WAP
1 0
+108"
WAP
1 0
+96"
2 0 +18"
CP-001
36"x48"x9" +72" T.O.P.
CP-005
36"x48"x10" +72" T.O.P.
CP-004
36"x60"x10" +72" T.O.P.
06-FO-2G
8"x10"x4"
+72" T.O.P.
06-FO-1G
8"x10"x4"
+72" T.O.P.
06-STM-1G
8"x10"x4"
06-CWFM-1G
8"x10"x4"
SC
1 0 0 (F)
FIELD VERIFY
SC
1 0 0 (F)
APPROXIMATELY
+180" AFF
PSH500A
12"x12"x6" +86" T.O.P.
06-SV-E3-01
LS-201
STAFF TLT
ELEC
2 0
+18"
ELEC
2 0 +18"
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
MY SWITCHING
06-SV1-F2-E4
06-CWFM-NCAMP-G
8"x10"x4"
06-WCCHM-2G
8"x10"x4"
06-WCCHM-3G
8"x10"x4"
06-CHWM-2G
8"x10"x4"
06-WCCHM-4G
8"x10"x4"
06-COND-1G
8"x10"x4"
+72" T.O.P.06-COND-2G
8"x10"x4"
+72" T.O.P.
06-COND-3G
8"x10"x4"
+72" T.O.P.
06-STM-2G
8"x10"x4"
06-STM-3G
8"x10"x4"
06-STM-4G
8"x10"x4"
06-SV-F3-01
LS-203
CONTROL CENTER
ETHERNET DROP
1 0
+72"
ETHERNET DROP
1 0
+72"
ETHERNET DROP
1 0
+72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0
+72"
ETHERNET DROP
1 0
+72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
06-WCCHM-1G
8"x10"x4"
06-LLHXM-1G
8"x10"x4"
06-LLHXM-2G
8"x10"x4"
ETHERNET DROP
1 0 +72"
BOILER MASTER INTEGRATION PANEL
ETHERNET DROP
1 0 +96"
MEDICAL AIR ETHERNET DROP
1 0
+96"
DDC WORK STATION - 1 DROP
AUMS WORK STATION - 1 DROP
JCI SERVICE PORTS - 4 DROP
LIGHTING INTEGRATION - 1 DROP
STEAM TRAP MONITORING INTEGRATION - 1 DROP
REFRIGERATOR MONITORING INTEGRATION - 1 DROP
SCADA INTEGRATION - 1 DROP
06-DCW-8"
1 0 +72"
06-DCW-4"
1 0
+72"
06-SV1-ST1
LS-ST1
STAIR
06-SV1-SE16
LE-S01
ELEV
06-SV1-V1
LS-207
VEST
06-DCW-BOILER
8"x10"x4"
06-DCW-BOILER
1 0
+72"
06-DCW-SL
8"x10"x4"
06-DCW-SL
1 0
+72"
06-DCW-1.25"
1 0
+96"
CE
1 0 0 (F)
SC
1 0 0
ENC-TR-1 BOUNDARY
ENC-TR-1 BOUNDARY
EN
C
-TR
-1 BO
U N
D
AR
Y
EN
C
-T R
-1 B
O U
N D
AR
Y
C O
N -T
R -0
A
BO
U N
D
AR
Y
L1-142-S1-10
L1-142-S1-11
L1-142-S1-12
L1-142-S1-09
COILED SPARE
L1-142-D2-28
L1-142-D2-29
L1-142-D2-30
L1-142-D2-31
L1-142-D2-32
L1-142-D2-33
L1-142-D2-34
L1-142-D2-35
L1-142-D2-36
L1-142-D2-37
L1-142-D2-38
L1-142-D2-39
L1-142-D2-40
L1-142-D2-41
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
ETHERNET DROP
1 0 +72"
L1-142-D2-42 L1-142-D2-43
L1-142-D2-44
L1-142-D2-45
L1-142-D2-46 L1-142-D2-47
L1-142-D3-01
L1-142-D3-02
L1-142-D3-03
L1-142-D3-04 L1-142-D3-05
L1-142-D3-06 L1-142-D3-07
L1-142-D3-08 L1-142-D3-09
L1-142-D3-10
L1-142-D3-12 L1-142-C-03
L1-142-D3-13 L1-142-D3-14
L1-142-D3-15 L1-142-D3-16
L1-142-D3-17
L1-142-D3-18
L1-142-D3-19 L1-142-D3-20 L1-142-D3-21 L1-142-D3-22
L1-142-D3-23
L1-142-D3-24
L1-142-D3-25
L1-142-D3-26
L1-142-D3-27 L1-142-D3-28
2 0 +18"
L1-142-D3-29 L1-142-D3-30
L1-142-D3-31 L1-142-D3-32L1-142-D3-33
L1-142-D3-34
L1-142-D3-35
L1-142-D7-01
L1-142-D3-37 L1-142-D3-38
L1-142-D3-44
L1-142-D3-47
L1-142-D3-46
L1-142-D3-48
L1-142-D4-02
L1-142-D4-03
L1-142-D4-04
L1-142-D4-05
L1-142-D4-06 L1-142-D4-07
L1-142-D7-02
L1-142-D7-03
L1-142-D7-04
L1-142-D7-05
L1-142-D7-06
L1-142-D7-07
L1-142-D2-48
ETHERNET DROP
1 0
ETHERNET DROP
1 0L1-142-D7-12
L1-142-D7-11
ETHERNET DROP
1 0L1-142-D6-46
06-DHW-6"
1 0
+72" L1-142-D3-45
ETHERNET DROP
1 0
L1-142-D7-10
ETHERNET DROP
1 0L1-142-D7-08
ETHERNET DROP
1 0L1-142-D7-09
L1-142-S2-01
11 12 08 09 13
03040506
Scale
Release Date
These Drawings are based on details from the following Contract Documents.
Telecom / AV Drawings
Security Drawings:
Electrical Drawings:
Mechanical Drawings:
Fire Protection Drawings:
SEE PLAN
Field Signoff
BIM Manager Signoff
BIM Team Signoff
Key Plan
N
JCI / IME Project Office 3250 Quentin St., Unit 112
Aurora, CO 80011 www.imelect.com
14900 Grand River Rd, Ste 100 Ft. Worth, TX 76155
Phone: 817-355-5385 www.dmitechinc.com
4/ 3/
:4
8:
A M
ENCLV084
SERVICE (BOILER/CHILLER)
LEVEL - HORIZONTAL CABLING
DEVICES
DENVER VA
03/27/15
TH/GS
MB
TC
REV DESCRIPTION DATE
1 KT RFI #4632 06/09/2014
2 KT RFI #2800 05/22/2014
3 JCI Shop Drawing Update 05/30/2014 4 Per Robert K 08/26/2014
5 KT RFI #5529 11/17/2014
6 KT RFI #5220 12/16/2014
7 PER CM-847/MOD P-237 DELETED 3/27/2015
NORTH
1/8" = 1'-0"1 SERVICE (BOILER/CHILLER) - HORIZONTAL CABLING DEVICES
06.TA.300_CD12
06_QY_100_1_CD12
06.QY.100.1_CD12-MAY-22-14
06.VM.300-B
06.VM.800
06VM.801
06.PP.101.1
SYSTEM AND COLOR CODE
DT DATA TELECOM MAGENTA GRAY WITH WHITE BANDING
BIM COLOR CONDUIT COLOR
MA MASS NOTIFICATION ORANGE GRAY
NC NURSE CALL GREEN GREEN BANDING
FA FIRE ALARM RED OSHA RED
SC SECURITY CYAN WHITE
DDC DDC SYSTEM, AUMS AND MED GAS BLUE BLUE
CT CABLE TRAY BLACK
AV AUDIO-VISUAL COMMUNICATION YELLOW GREEN GRAY WITH WHITE BANDING
IBW IN-BUILDING WIRELESS BLACK
GENERAL NOTES
1. INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM CONTRACT
FURNISHED DRAWINGS AND/OR VENDOR SHOP DRAWINGS. INTERMOUNTAIN
ELECTRIC INC. IS NOT RESPOSIBLE FOR THE ACCURACY OF ANY INFORMATION
OR THE ADEQUACY AND CONFORMANCE TO CURRENT PREVAILING CODES OF
ANY WORK SHOWN ON THE DRAWINGS.
2. INFORMATION SHOWN ON THE DRAWINGS IS ONLY CURRENT UP TO THE DATE
OF ISSUANCE. CHANGES OCCURING AFTER THE ISSUE DATE SHALL BE THE SOLE
RESPONSIBILITY OF OTHERS.
HORIZONTAL CABLING CALLOUT SCHEDULE
1. CABLE LABELING SHOWN HEREIN HAS BEEN VERIFIED AND APPROVED BY THE VA RESIDENT
ENGINEER, VAMC IT, KT, AND JCI PER RFI #06428.
WHERE X= QTY. OF DATA PORTS
Y= QTY. OF COAXIAL DROPS (RG-6)
Z= QTY. OF FIBER STRANDS
{BUILDING & FLOOR} - {CLOSET ROOM} - {SYSTEM PANEL} - {PORT}
WHERE SYSTEM PANEL IS DEFINED AS:
D# - DATA PATCH PANEL (HORIZONTAL RACK)
PM# - PHYSIOLOGICAL MONITOR PATCH PANEL (FMS/BIOMED RACK)
S# - SECURITY PATCH PANEL (UPS/SECURITY RACK)
HC# - HEALTHCARE CAMERA PANEL (FMS/BIOMED RACK)
EX: H1-217-D1-01 IBS BUILDING (H) FLOOR 1, CLOSET ROOM 217, DATA PATCH PANEL, PORT #1
X,Y,Z
DEVICE TAG
DEVICE TYPE
CAT 6 / COAX / FIBER (F)
HEIGHT AFF TO CENTER OF BOX
AS-BUILT
8 AS-BUILT 01/04/2017
Risers to Cable Tray
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
L
L
M
M
B
B
A
A
RA
RA
PT8,
8" SLEEVE
06-01-B1-05 L1-100
WAIT
06-01-B1-07 L1-C03
CORRIDOR
06-01-B1-04 L1-102
OFFICE
06-01-B1-02 L1-104
OFFICE
06-01-B1-01 L1-106
OFFICE
06-01-C1-01
L1-108
OFFICE
06-01-C1-02
L1-110
OFFICE
06-01-D1-01
L1-112
OFFICE
06-01-D1-02
L1-114
OFFICE
06-01-E1-01
L1-116
OFFICE
06-01-E1-02 L1-118
STOR 06-01-F1-01
L1-120
OFFICE
06-01-F1-02
L1-122
OFFICE
06-01-G1-04 L1-144
STAFF TLT
06-01-J1-03 L1-136
CONF
06-01-J1-01 L1-132
OFFICE
06-01-H1-02 L1-130
OFFICE
06-01-H1-01 L1-128
OFFICE
06-01-G1-02 L1-126
OFFICE
06-01-G1-01 L1-124
OFFICE 5
06-01-H1-05 L1-148
HAC
06-01-H1-04 L1-146
STAFF TLT
06-01-H1-03 L1-127
WAIT
06-01-F2-01 L1-C02
CORRIDOR
06-01-C1-05 L1-101
DRIVER DISPATCH
06-01-B1-03 L1-102
OFFICE
06-01-C1-03 L1-103
OFFICE
06-01-C1-04 L1-109
OFFICE
06-01-D1-03
L1-111
OFFICE
06-01-D1-04
L1-113
OFFICE
06-01-E1-03 L1-115
OFFICE 06-01-E1-04
L1-117
OFFICE
06-01-E1-05
L1-119
COPY/FAX
06-01-F1-03 L1-121
MAIL/PRINT
06-01-J1-02 L1-134
STOR
06-01-G1-03 L1-125
PLAN/DRAFTING
SC
1 0 0
(2)
(18)
SC
0 0 1 (F)
S 1 0 0 +72"
S 1 0 0 +72"
4 4
CE
0 0 1 (F)
DN
UP
UP
DN
UP
DN
DN
Tectonic Copyright 2007
ENC-TR-1 BOUNDARY
ENC-TR-1 BOUNDARY
EN
C
-TR
-1 BO
U N
D
AR
Y
EN
C
-T R
-1 B
O U
N D
AR
Y
06-01-E1-T1 L1-142
DATA/
TELECOMM
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
1 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
AC
2 0
+44"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
MECH
2 0
+18"
2 0 +18"
2 0 +18"
2 0 +18"
2 0 +18"
WAP
1 0
+46"
2 0 +18"
1 1
2 1 +18"
2 0
CP-AHU-1
36"x48"x9"
06-RHWM-1G
8"x10"x4"
+72" T.O.P.
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
06-NAE-1
24"x36"x9"
WAP
1 0
WAP
1 0
ETHERNET DROP
1 0
+96"
TMGB
24"x4"x2.75"
DAS
20.25"x13.25"x5"
W 1 0
+46"
ETHERNET DROP
1 0
+96"
PSH500A
12"x12"x6" +86" T.O.P.
ETHERNET DROP
1 0
+96"
BEP
14.75"x11"x6.25"
10.75"x3.75"x3.25"
L1-142-S2-04
L1-142-S1-14
L1-142-S1-15
L1-142-S1-17
L1-142-D4-08
L1-142-D4-09
L1-142-D4-10
L1-142-D4-11 L1-142-D4-12
2 0 +18" L1-142-D4-13 L1-142-D4-14
2 0 +18" L1-142-D4-15 L1-142-D4-16
2 0 +18" L1-142-D4-17 L1-142-D4-18
L1-142-D4-19 L1-142-D4-20
L1-142-D4-21 L1-142-D4-22
2 0 +18" L1-142-D4-23
L1-142-D4-24
L1-142-D4-25 L1-142-D4-26
L1-142-D4-27 L1-142-D4-28
L1-142-D4-29 L1-142-D4-30
L1-142-D4-31 L1-142-D4-32
L1-142-D4-33 L1-142-D4-34
L1-142-D4-35 L1-142-D4-36
L1-142-D4-37 L1-142-D4-38
L1-142-D4-39 L1-142-D4-40
L1-142-D4-41 L1-142-D4-42
L1-142-D4-43 L1-142-D4-44
L1-142-D4-45 L1-142-D4-46
L1-142-D4-47 L1-142-D4-48
L1-142-D5-01 L1-142-D5-02
L1-142-D5-03
L1-142-D5-04
L1-142-D5-05 L1-142-D5-06
L1-142-D5-07 L1-142-C-04
L1-142-D5-08 L1-142-D5-09 L1-142-C-05
L1-142-D5-10 L1-142-D5-11
L1-142-D5-12
L1-142-D5-13 L1-142-D5-14
L1-142-D5-15 L1-142-D5-16
L1-142-D5-17 L1-142-D5-18
L1-142-D5-19 L1-142-D5-20L1-142-D5-21
L1-142-D5-22
L1-142-D5-23 L1-142-D5-28
L1-142-D5-24 L1-142-D5-25
L1-142-D5-26 L1-142-D5-27
L1-142-D5-29 L1-142-D5-30L1-142-D5-31
L1-142-D5-32
L1-142-D5-33 L1-142-D5-34
L1-142-D5-37
L1-142-D5-35 L1-142-D5-36L1-142-D5-38
L1-142-D5-39
L1-142-D5-42
L1-142-D5-40 L1-142-D5-41
L1-142-D5-43 L1-142-D5-44
L1-142-D5-45 L1-142-D5-46
L1-142-D5-47 L1-142-D5-48L1-142-D6-01
L1-142-D6-02
L1-142-D6-04 L1-142-D6-05
L1-142-D6-03
L1-142-D6-06
L1-142-D6-07
L1-142-D6-08
CE
0 0 1 (F)
L1-142-S2-03
L1-142-S2-02
11 12 08 09 13
03040506
Scale
Release Date
These Drawings are based on details from the following Contract Documents.
Telecom / AV Drawings
Security Drawings:
Electrical Drawings:
Mechanical Drawings:
Fire Protection Drawings:
SEE PLAN
Field Signoff
BIM Manager Signoff
BIM Team Signoff
Key Plan
N
JCI / IME Project Office 3250 Quentin St., Unit 112
Aurora, CO 80011 www.imelect.com
14900 Grand River Rd, Ste 100 Ft. Worth, TX 76155
Phone: 817-355-5385 www.dmitechinc.com
/9
/2
8:
:4
A
M
ENCLV104
LEVEL 01 - HORIZONTAL
CABLING DEVICES
DENVER VA
03/27/15
TH/GS
MB
TC
REV DESCRIPTION DATE
1 MOD 00237 04/10/2014
2 KT RFI #4632 06/09/2014
3 KT RFI #2800 05/22/2014
4 JCI Shop Drawing Update 05/30/2014
5 RFP #0246 10/06/2014
6 PER JCI VMS DRAWING UPDATED 03/27/2015
1/8" = 1'-0"1 LEVEL 1 - HORIZONTAL CABLING DEVICES
NORTH
06.TA.301_CD12
06.QY.101_CD12-MAY-22-14
06_QY_101_CD12
06.VM.101
06.VM.803
SYSTEM AND COLOR CODE
DT DATA TELECOM MAGENTA GRAY WITH WHITE BANDING
BIM COLOR CONDUIT COLOR
MA MASS NOTIFICATION ORANGE GRAY
NC NURSE CALL GREEN GREEN BANDING
FA FIRE ALARM RED OSHA RED
SC SECURITY CYAN WHITE
DDC DDC SYSTEM, AUMS AND MED GAS BLUE BLUE
CT CABLE TRAY BLACK
AV AUDIO-VISUAL COMMUNICATION YELLOW GREEN GRAY WITH WHITE BANDING
IBW IN-BUILDING WIRELESS BLACK
GENERAL NOTES
1. INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM CONTRACT
FURNISHED DRAWINGS AND/OR VENDOR SHOP DRAWINGS. INTERMOUNTAIN
ELECTRIC INC. IS NOT RESPOSIBLE FOR THE ACCURACY OF ANY INFORMATION
OR THE ADEQUACY AND CONFORMANCE TO CURRENT PREVAILING CODES OF
ANY WORK SHOWN ON THE DRAWINGS.
2. INFORMATION SHOWN ON THE DRAWINGS IS ONLY CURRENT UP TO THE DATE
OF ISSUANCE. CHANGES OCCURING AFTER THE ISSUE DATE SHALL BE THE SOLE
RESPONSIBILITY OF OTHERS.
HORIZONTAL CABLING CALLOUT SCHEDULE
1. CABLE LABELING SHOWN HEREIN HAS BEEN VERIFIED AND APPROVED BY THE VA RESIDENT
ENGINEER, VAMC IT, KT, AND JCI PER RFI #06428.
WHERE X= QTY. OF DATA PORTS
Y= QTY. OF COAXIAL DROPS (RG-6)
Z= QTY. OF FIBER STRANDS
{BUILDING & FLOOR} - {CLOSET ROOM} - {SYSTEM PANEL} - {PORT}
WHERE SYSTEM PANEL IS DEFINED AS:
D# - DATA PATCH PANEL (HORIZONTAL RACK)
PM# - PHYSIOLOGICAL MONITOR PATCH PANEL (FMS/BIOMED RACK)
S# - SECURITY PATCH PANEL (UPS/SECURITY RACK)
HC# - HEALTHCARE CAMERA PANEL (FMS/BIOMED RACK)
EX: H1-217-D1-01 IBS BUILDING (H) FLOOR 1, CLOSET ROOM 217, DATA PATCH PANEL, PORT #1
X,Y,Z
DEVICE TAG
DEVICE TYPE
CAT 6 / COAX / FIBER (F)
HEIGHT AFF TO CENTER OF BOX
AS-BUILT
7 AS-BUILT 01/04/2017
All data drops to cable tray
DN
UP
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
L
L
M
B
B
A
A
RA
RA
WAP
1 0
WAP
1 0
+96"
TYP
2 0
+46"
ELEC
2 0
+46"
ELEC
2 0
+46"
ELEC
2 0
+46"
ELEC
2 0
+46"
ELEC
2 0
+46"
ELEC
2 0
+46"
CP-AHU-3
30"x42"x9" +72" T.O.P.
CP-AHU-2
36"x48"x9" +72" T.O.P.
06-ELEC-2G
16"x20"x6.5" +72" T.O.P.
06-ELEC-1G
16"x20"x6.5" +72" T.O.P.
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
WAP
1 0
8"x8"x30"
PSH500A
12"x12"x6" +86" T.O.P.
ELEC
2 0
+46"
ETHERNET DROP
1 0 +96"
ETHERNET DROP
1 0
+96"
ETHERNET DROP
1 0
+96"
ETHERNET DROP
1 0
+96"
SC
1 0 0
+96" BELOW LOWEST
OBSTRUCTION
SC
0 0 1 (F)
+96" BELOW LOWEST
OBSTRUCTION
CE
0 0 2 (F)
CE
0 0 1 (F)
ENC-TR-1 BOUNDARY
ENC-TR-1 BOUNDARY
EN
C
-TR
-1 BO
U N
D
AR
Y
EN
C
-T R
-1 B
O U
N D
AR
Y
L1-142-S1-18
L1-142-D6-45
L1-142-D6-09
L1-142-D6-11 L1-142-D6-12
L1-142-D6-13
L1-142-D6-14
L1-142-D6-15
L1-142-D6-16
L1-142-D6-17
L1-142-D6-18
L1-142-D6-19
L1-142-D6-24
L1-142-D6-20 L1-142-D3-01
L1-142-D6-22 L1-142-D6-23
L1-142-D6-25
L1-142-D6-31 L1-142-D6-32
L1-142-D6-33
L1-142-D6-26
L1-142-D6-27 L1-142-D6-28
L1-142-D6-29
L1-142-D6-30
L1-142-D6-34
L1-142-D6-35 L1-142-D6-36
L1-142-D6-37
L1-142-D6-38 L1-142-D6-39
L1-142-D6-40
L1-142-D6-41
L1-142-D6-42 L1-142-D6-43
L1-142-D6-44
DDC
1 0
L1-142-D7-18
L1-142-D7-19
L1-142-D7-21
CE
1 0 0
L1-142-S1-13
L1-142-S2-04
COILED SPARE
L1-142-S2-06
L1-142-S2-05A L1-142-S2-05B
DDC
1 0
DDC
1 0
L1-142-D7-20
DDC
1 0
PSH500A
12"x12"x6" +86" T.O.P.
11 12 08 09 13
03040506
Scale
Release Date
These Drawings are based on details from the following Contract Documents.
Telecom / AV Drawings
Security Drawings:
Electrical Drawings:
Mechanical Drawings:
Fire Protection Drawings:
SEE PLAN
Field Signoff
BIM Manager Signoff
BIM Team Signoff
Key Plan
N
JCI / IME Project Office 3250 Quentin St., Unit 112
Aurora, CO 80011 www.imelect.com
14900 Grand River Rd, Ste 100 Ft. Worth, TX 76155
Phone: 817-355-5385 www.dmitechinc.com
/9
/2
8:
:3
A
M
ENCLV153
LEVEL 01 (ELECT) - HORIZONTAL
CABLING DEVICES
DENVER VA
03/27/15
TH/GS
MB
TC
REV DESCRIPTION DATE
1 KT RFI #4632 06/09/2014
2 JCI Shop Drawing Update 05/30/2014
3 KT RFI #5490 12/16/2014
4 KT RFI #5478 01/16/2015
5 PER CM-847/MOD P-237 DELETED 03/27/2015
6 PER JCI VMS DRAWING UPDATED 03/27/2015
1/8" = 1'-0"1 LEVEL 1 (ELECT) - HORIZONTAL CABLING DEVICES
NORTH
06.TA.301.1_CD12
06_QY_101_1_CD12
06.QY.101.1_CD12-MAY-22-14
06.VM.101
06.VM.301
06.VM.802
06.VM.803
SYSTEM AND COLOR CODE
DT DATA TELECOM MAGENTA GRAY WITH WHITE BANDING
BIM COLOR CONDUIT COLOR
MA MASS NOTIFICATION ORANGE GRAY
NC NURSE CALL GREEN GREEN BANDING
FA FIRE ALARM RED OSHA RED
SC SECURITY CYAN WHITE
DDC DDC SYSTEM, AUMS AND MED GAS BLUE BLUE
CT CABLE TRAY BLACK
AV AUDIO-VISUAL COMMUNICATION YELLOW GREEN GRAY WITH WHITE BANDING
IBW IN-BUILDING WIRELESS BLACK
GENERAL NOTES
1. INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM CONTRACT
FURNISHED DRAWINGS AND/OR VENDOR SHOP DRAWINGS. INTERMOUNTAIN
ELECTRIC INC. IS NOT RESPOSIBLE FOR THE ACCURACY OF ANY INFORMATION
OR THE ADEQUACY AND CONFORMANCE TO CURRENT PREVAILING CODES OF
ANY WORK SHOWN ON THE DRAWINGS.
2. INFORMATION SHOWN ON THE DRAWINGS IS ONLY CURRENT UP TO THE DATE
OF ISSUANCE. CHANGES OCCURING AFTER THE ISSUE DATE SHALL BE THE SOLE
RESPONSIBILITY OF OTHERS.
HORIZONTAL CABLING CALLOUT SCHEDULE
1. CABLE LABELING SHOWN HEREIN HAS BEEN VERIFIED AND APPROVED BY THE VA RESIDENT
ENGINEER, VAMC IT, KT, AND JCI PER RFI #06428.
WHERE X= QTY. OF DATA PORTS
Y= QTY. OF COAXIAL DROPS (RG-6)
Z= QTY. OF FIBER STRANDS
{BUILDING & FLOOR} - {CLOSET ROOM} - {SYSTEM PANEL} - {PORT}
WHERE SYSTEM PANEL IS DEFINED AS:
D# - DATA PATCH PANEL (HORIZONTAL RACK)
PM# - PHYSIOLOGICAL MONITOR PATCH PANEL (FMS/BIOMED RACK)
S# - SECURITY PATCH PANEL (UPS/SECURITY RACK)
HC# - HEALTHCARE CAMERA PANEL (FMS/BIOMED RACK)
EX: H1-217-D1-01 IBS BUILDING (H) FLOOR 1, CLOSET ROOM 217, DATA PATCH PANEL, PORT #1
X,Y,Z
DEVICE TAG
DEVICE TYPE
CAT 6 / COAX / FIBER (F)
HEIGHT AFF TO CENTER OF BOX
AS-BUILT
7 AS-BUILT 01/04/2017
Riser to cable tray
Riser to cable tray
Riser to cable tray
REX
REX
REX
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
L
L
M
B
B
A
A
RA
RA
SC
1 0 0
+96" BELOW LOWEST
OBSTRUCTION
WAP
1 0
+105"
WAP
1 0
+46"
ELEV
2 0
+46"
SC
1 0 0
+96" BELOW LOWEST
OBSTRUCTION
STAIR
06-PH1-ST1
LR-ST1
ELEV
06-PH1-SE16
LE-S01
VEST
06-PH1-B3-V1
ELEV MACH RM
06-PH1-B3-E1
LR-100
SC
1 0 0 (F)
FIELD VERIFY
SC
1 0 0 (F)
FIELD VERIFY
3 4
SC
0 0 0 (F)
FIELD VERIFY
SC
0 0 0 (F)
FIELD VERIFY
ENC-TR-1 BOUNDARY
ENC-TR-1 BOUNDARY
EN
C
-TR
-1 BO
U N
D
AR
Y
EN
C
-T R
-1 B
O U
N D
AR
Y
L1-142-D7-17
L1-142-S1-19
L1-142-S1-16 L1-142-D7-15
L1-142-D7-13 L1-142-D7-14
L1-142-S1-20
L1-142-D7-22
WAP
1 0
L1-142-D7-16
11 12 08 09 13
03040506
Scale
Release Date
These Drawings are based on details from the following Contract Documents.
Telecom / AV Drawings
Security Drawings:
Electrical Drawings:
Mechanical Drawings:
Fire Protection Drawings:
SEE PLAN
Field Signoff
BIM Manager Signoff
BIM Team Signoff
Key Plan
N
JCI / IME Project Office 3250 Quentin St., Unit 112
Aurora, CO 80011 www.imelect.com
14900 Grand River Rd, Ste 100 Ft. Worth, TX 76155
Phone: 817-355-5385 www.dmitechinc.com
/9
/2
8:
:0
A
M
ENCLV253
ROOF (MECH) - HORIZONTAL
CABLING DEVICES
DENVER VA
03/27/15
TH/GS
MB
TC
REV DESCRIPTION DATE
1 MOD 00237 04/10/2014
2 KT RFI #3957 04/15/2014
3 KT RFI #4632 06/09/2014
4 JCI Shop Drawing Update 05/30/2014
5 KT RFI #3926 12/16/2014
1/8" = 1'-0"1 ROOF (MECH) - HORIZONTAL CABLING DEVICES NORTH
06.TA.302_CD12
06.QY.102_CD12-MAY-22-14
06.QY.102.1_CD12-MAY-22-14
06_QY_202_CD12
06_QY_202_1_CD12
06.VM.102
06.VM.803
06.VM.804
SYSTEM AND COLOR CODE
DT DATA TELECOM MAGENTA GRAY WITH WHITE BANDING
BIM COLOR CONDUIT COLOR
MA MASS NOTIFICATION ORANGE GRAY
NC NURSE CALL GREEN GREEN BANDING
FA FIRE ALARM RED OSHA RED
SC SECURITY CYAN WHITE
DDC DDC SYSTEM, AUMS AND MED GAS BLUE BLUE
CT CABLE TRAY BLACK
AV AUDIO-VISUAL COMMUNICATION YELLOW GREEN GRAY WITH WHITE BANDING
IBW IN-BUILDING WIRELESS BLACK
GENERAL NOTES
1. INFORMATION SHOWN ON THE DRAWINGS HAS BEEN TAKEN FROM CONTRACT
FURNISHED DRAWINGS AND/OR VENDOR SHOP DRAWINGS. INTERMOUNTAIN
ELECTRIC INC. IS NOT RESPOSIBLE FOR THE ACCURACY OF ANY INFORMATION
OR THE ADEQUACY AND CONFORMANCE TO CURRENT PREVAILING CODES OF
ANY WORK SHOWN ON THE DRAWINGS.
2. INFORMATION SHOWN ON THE DRAWINGS IS ONLY CURRENT UP TO THE DATE
OF ISSUANCE. CHANGES OCCURING AFTER THE ISSUE DATE SHALL BE THE SOLE
RESPONSIBILITY OF OTHERS.
HORIZONTAL CABLING CALLOUT SCHEDULE
1. CABLE LABELING SHOWN HEREIN HAS BEEN VERIFIED AND APPROVED BY THE VA RESIDENT
ENGINEER, VAMC IT, KT, AND JCI PER RFI #06428.
WHERE X= QTY. OF DATA PORTS
Y= QTY. OF COAXIAL DROPS (RG-6)
Z= QTY. OF FIBER STRANDS
{BUILDING & FLOOR} - {CLOSET ROOM} - {SYSTEM PANEL} - {PORT}
WHERE SYSTEM PANEL IS DEFINED AS:
D# - DATA PATCH PANEL (HORIZONTAL RACK)
PM# - PHYSIOLOGICAL MONITOR PATCH PANEL (FMS/BIOMED RACK)
S# - SECURITY PATCH PANEL (UPS/SECURITY RACK)
HC# - HEALTHCARE CAMERA PANEL (FMS/BIOMED RACK)
EX: H1-217-D1-01 IBS BUILDING (H) FLOOR 1, CLOSET ROOM 217, DATA PATCH PANEL, PORT #1
X,Y,Z
DEVICE TAG
DEVICE TYPE
CAT 6 / COAX / FIBER (F)
HEIGHT AFF TO CENTER OF BOX
File details come from the government source that posted it. Updated .